D ATA S H E E T HDDC High Power Density D C P o w e r D i st r i b u t i o n C e n te r Features 200A per bus redundant A/B/C version 300A per bus high ampacity (22 circuit versions) Overview High density DC distribution for rack mount servers and broadband applications such as VOD, CMTS, VOIP. Allows high density distribution of DC capacity for point of use in high circuit count server racks or for use in CSI PowerBay BDFB cabinets ūūSingle input 19”/ 23” rack mount (3RU high): high breaker circuit count to support multiple servers and their redundant power supply requirements and combined high current loads ūūA/B isolated input High power density and ampacity: Configurable power routing options ūūA/B input, C-source redundant diode routed A/B redundant input version 300A maximum load per bus 11A and 11B circuit breaker positions ūū 300 amperes per input: (single input, A/B input) high ampacity versions ūū 200 amperes combined load: (A/B/C -source) low ampacity redundant version ūū Accepts up to 22 plug-in bullet terminal circuit breakers for convenience and flexibility High output ampacity terminal configuration per-breaker-channel Small RU requirement leaves room for maximum network equipment space in equipment racks A/B redundant input, C bus output version Two-hole lug high current bus bars for input and return terminations (supports large AWG input cable feeders) 200A maximum load 22 circuit breaker positions High output ampacity terminal configuration per-breaker-channel (up to 100A per channel maximum) Single input version ūū22 outputs with 300A maximum bus load ūūHigh output ampacity terminal configuration per-breaker-channel (up to 100A per channel) ūūUsed in CSI PowerBay BDFB cabinets Alphanumeric LCD display for voltage, load current per bus, and breaker status Bright, color-coded LED indicators for power input power status, breaker trip, and alarms Form C alarm contacts for major and minor alarms Single- or two-hole lug termination bus bar array for circuit breaker protected outputs and returns (low ampacity) A/B/C versions available with either setscrew barrier strip output terminals for low ampacity per channel or high ampacity version with two-hole lug landing Accepts bullet terminal circuit breakers available from CSI in numerous amperage ratings (interchangeable breakers reduces spare parts inventory and cost) Flip down front cover panel protects breakers from nuisance tripping (convenient front access for breaker installation) Plug-in breakers can be installed incrementally as needed to reduce install cost Breakers can be changed in seconds to support equipment load and configuration changes over time Input/output clear plastic termination guard High Density HDDC DC Power Distribution Center Page 1 D ATA S H E E T Common Specifications for All Models: Dimensions: 17” wide x 5.25” high (3RU) x 12.5” deep (including bus bar protrusion) Two mounting positions: front flush or mid-mount Weight: 27 lbs Plug-in bullet terminal circuit breakers (select amperage rating and quantity at time of order) Rack mount: via 19/23” reversible rack mount ears Rear clear cover panel for bus bar termination area General Specifications MOdel # Description PN 016-400-10 Single Input, High Ampacity Output Single input breaker panel 300 ampere rated 22 bullet breaker sockets 2 quantity Form C alarm contacts LED/LCD front panel indicators (also used in CSI PowerBay BDFB cabinets) -48VDC PN 016-402-10 A/B Input, C Bus Output -200A Isolated A/B inputs feed diode power routed output bus and 22 breakers for redundant operation of load circuits from either A/B inputs A/B input, C bus output 200A 30A per channel 200A combined output load rating 2 quantity Form C alarm contacts LED/LCD front panel indicators –48VDC PN 016-406-10 A/B Isolated Input/Output A/B isolated inputs/split bus output 11A/11B breaker sockets High ampacity 300A per bus 22 bullet breaker sockets 2 quantity Form C alarm contacts LED/LCD front panel indicators –48VDC PN 016-407-10 A/B Input, C-Output Diode Routed Bus 300 ampere rated High ampacity Redundant 22 bullet breaker sockets 2 quantity Form C alarm contacts 300A combined output (100A per channel) LED/LCD front panel indicators -48VDC Circuit Breakers Part# Description Part# Description 470-235-10 10 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-400-10 60 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-402-10 20 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-406-10 80 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-403-10 30 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-404-10 100 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-407-10 40 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) 470-269-10 200 AMP AM breaker, plug-in type, midtrip (5/16” bullet terminals) Figure 1. Front view of the HDDC. Figure 2. Rear view of the HDDC. About Comm/net Systems Comm/net Systems, Inc. (CSI) is the leader in high power density communications power systems. Comm/net offers comprehensive power and communications site systems integration and deployment services via a national footprint of regional branch offices. Additional information can be found at www.commnetsystems.com. Figure 3. Rear view with clear protective cover. Corporate Headquarters Comm/net Systems, Inc. 4237 – 24th Avenue West Seattle, WA 98199 24/7 Sales & Service To purchase Comm/net Systems solutions, contact your Comm/net Systems representative at: (800) 274-0544 or e-mail: sales@commnetsystems.com Tel: 206.282.8670 Fax: 206.282.8684 Order Information Shipping box is packaged for UPS or FedEx shipment and includes an instruction manual and accessories. www.commnetsystems.com © 2010 Comm/net Systems, Inc. All rights reserved. Comm/net Systems, and the Comm/net Systems logo are registered trademarks of Comm/net Systems, Inc. in the United States and other countries. All other trademarks, service marks, registered marks, or registered service marks are the property of their respective owners. Comm/net Systems assumes no responsibility for any inaccuracies in this document. Comm/net Systems reserves the right to change, modify, transfer, or otherwise revise this publication without notice. document number 048-008-00, Revision 2, Published July 2010