P O W E R I N G DPGF1U SERIES T E C H N O L O G Y FRONT ACCESS/CONNECT GMT DISTRIBUTION PANELS DESCRIPTION UNIPOWER’s DPGF1U Series of all Front Connected GMT fuse distribution panels provide distribution and overload protection for 4/6 or 8/12 circuits. The one mounting position (1.75 inches) high GMT fuse panels provide 4/6 single-bus fuses or 8/12 dual-bus (A&B) fuses (4 or 6 per bus). They distribute up to a total of 160 amperes of load current from two separate 80-ampere sources with true A and B distribution and alarm capabilities. LVD2006/95/EC ROHS2011/65/EU A and B sections of the dual-bus panel are isolated and can be separately configured for 12, 24/48 volts and are polarity neutral. Fuse sizes are ½ to 20 amperes. Fuse trip and power off alarm is indicated by an LED for each bus and one Form C relay contact per bus. The panels come with brackets that permit mounting in either a 19- or 23-inch relay rack. They can be mounted from the front of the rack with offsets every quarter-inch from front to back to align with existing rack-mounted equipment. FEATURES All Connections Made at the Front One Mounting Position High: 1.75” 19- or 23-Inch Rack Mounting GMT Fuses, ½A to 20A Single Bus with 4 or 6 Fuses Dual Bus (A/B) with 4 or 6 Fuses per Bus Bus Capacity: 80A per Bus Operating Voltage: 12, 24/48VDC POLARITY NEUTRAL A & B are Isolated Loads A & B Can Be Separately Configured Status LED One Form C Relay Contact per Bus TWO-YEAR WARRANTY SAFETY COMPLIANCE UL60950-1 2nd Edition CSA22.2, No. 60950-1 2nd Edition EN60950-1 2nd Edition STANDARD MODELS VOLTS EACH FEED MODEL NUMBER DPGF1U-A1-4 24/48 DPGF1U-A6-4 12 DPGF1U-A1-6 24/48 DPGF1U-A6-6 12 DPGF1U-A1-4-B1-4 24/48 DPGF1U-A6-4-B6-4 12 DPGF1U-A1-6-B1-6 24/48 DPGF1U-A6-6-B6-6 NOTE: 12 INPUT FEEDS FUSES POSITIONS AMPS EACH BUS TOTAL AMPS 1 4 x ½ to 20A 64 64 1 4 x ½ to 15A 2 x ½ to 20A 80 80 2 4 x ½ to 20A Each Feed 64 128 2 4 x ½ to 15A 2 x ½ to 20A Each Feed 80 160 The above are standard configurations. For voltage combinations not shown see the configuration guide on page 2 of this datasheet. GMT FUSE ORDERING GUIDE AMPS COLOR ½ Red 401-1500-0010 Brown 401-1500-0020 ¾ PART NUMBER 1 Gray 401-1500-0030 1⅓ White 401-1500-0040 2 Orange 401-1500-0050 3 Blue 401-1500-0060 5 Green 401-1500-0070 10 Red/White 401-1500-0080 12 Green/Yellow 401-1500-0090 15 Red/Blue 401-1500-0110 20 Green/White 401-1523-0000 Dummy 401-1500-0100 NOTE: Fuses need to be ordered individually and are shipped with each panel as separate items for field installation. www.unipowerco.com NORTH AMERICA CALL: +1-954-905-1071 • LATIN AMERICA CALL: +1-954-905-1078 • EUROPE CALL: +44 1903 768200 P O W E R I N G DPGF1U SERIES GMT DISTRIBUTION UNITS - 2 T E C H N O L O G Y SPECIFICATIONS Typical at 25°C Unless Otherwise Noted. INPUT / OUTPUT Panel Capacity......................................................................................................80A Per Bus, 160A Total Configuration...............................................................................................Single Bus with 4 or 6 Fuses .................Dual Bus with 4 or 6 Fuses Each Fuse Type.................................................................................................................................................................GMT Fuse Capacity 1............................................4 x 15A max. with 2 x 20A max. OR 4 x 20A max. Voltage 2 24/48V Version..................................................................................................................................21-60VDC 12V Version....................................................................................................................................... 10.5-15VDC Polarity............................................................................................................................................Polarity Neutral ALARMS Alarm Indicator.................................................................................................... Dual-Color LED Per Bus LED Status Indication......................................................................................................... Green = Normal .Red = Fuse Trip Alarm .Off = No Powe Alarm Connections................................................................One Form C Relay Contact Per Bus SAFETY COMPLIANCE.............................UL60950-1 2nd. Ed., CSA22.2 No.950-1 2nd Ed., .EN60950-1 2nd. Ed. ENVIRONMENTAL Operating Temp. Range........................................................................................................-10°C to +70°C Storage Temp. Range............................................................................................................-40°C to + 85°C Humidity......................................................................................................0% to 95%, Non-Condensing PHYSICAL SPECIFICATIONS Case Material........................................................................................................................................................Steel Finish....................................................................................................................................... Powder Coat Black Dimensions, Inches (mm)..........................................................................1.75 H x 19.00 W x 9.00 D .(44.5 x 483 x 229) Weight..........................................................................................................................................8.38 lbs. (3.80kg.) Rack Mounting Width..........................................................................................................19 or 23 Inches CONNECTIONS Input Connections.............................................................................Crimp Type Lug or ¼ - 20 Stud Output Connections.....................................................................Barrier Terminal Strips, No. 6-32 Chassis Ground Connection................................................................................................No. 8-32 Stud Alarm Relay Connections..................................................Spring Clamp Terminals,16-26AWG NOTES: 1. See table for fuse sizes. 2. See Ordering Guide to specify voltage. FRONT VIEW 17.12 (434.9) A Input ¼-20 Studs Alarm LED A Alarm Contacts A SIDE B A T 0.34” 1 1 2 3 4 5 6 5 0.625” 1.48” B SIDE B A T 6 FA 1 1 NO-C-NC R T N 0.5” A Outputs #6-32 Terminal Strip B Input ¼-20 Studs Alarm LED B NO-C-NC 2 3 4 5 6 5 6 1.74 (44.2) FA R T N B Outputs #6-32 Terminal Strip A Side Fuses Ground #8-32 Stud B Side Fuses Case depth: 8.94 (227.1) 2.28 (57.8) CONNECTION DETAILS 0.625” Crimp Lugs for input bus bars should be ordered separately. For a kit of 4 two-hole lugs for #6AWG wire order part number 775-1434-0000. 0.375” Clear Perspex Safety Cover (supplied as standard) 0.65” 0.34” 0.5” 0.32” 1.48” Connectors are Phoenix Contact spring clamp type. Wires (16-26AWG) do not require any termination. ALL DIMENSIONS IN INCHES (mm). ORDERING GUIDE CODE VOLTAGE 1 24/48V 6 12V Model: DPGF1U-A --B - POLARITY NEUTRAL - May be connected for Positive or Negative Ground operation. CODE FUSE CONFIGURATION 4 4 X ½ to 20A 6 4 x ½ to 15A 2 x ½ to 20A 2. The sum of all fuse currents on either side must not exceed 80 Amperes. © 2016 UNIPOWER LLC This document is believed to be correct at time of publication and Unipower LLC accepts no responsibility for consequences from printing errors or inaccuracies. All specifications subject to change without notice. UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • sales@unipowerco.com North America: +1 954-905-1071 • Latin America: +1 954-905-1078 • Europe: +44 1903 768200 dpgf1u-ds-revF1-0816.indd Notes: 1. If section B is not used a blank panel is installed at the factory and the “-B” is not required in the model number (see Standard Model tabel on page 1).