application note

advertisement
APPLICATION NOTE
Contents
Introduction....................................... 1
What are the Possibilities?.................. 1
Circuit Power Options......................... 1
Conventional Large Fire/
Small Burglary ................................ 2
Installation Notes:...................... 2
Conventional Large Burglary/
Small Fire ...................................... 3
Installation Notes:...................... 3
Distributed Power Notification Circuit .. 4
Installation Notes:...................... 4
Separate Horn and Strobe Circuits ...... 6
Installation Notes:...................... 6
Model 867 Style W LX-Bus™
Notification Module.......................... 7
Model 866 Style W Notification
Module........................................... 7
Model 865 Style Y or Z Notification
Module........................................... 8
Product Compliance Certifications........ 8
Introduction
To meet today’s demanding installation requirements, an alarm
installer needs a control panel that provides a wide variety of fire
notification and local burglary alarm circuit configurations. The DMP
XR500 Series, XR2500F, XR100 Series, and XR200 Command Processor™
Panels meet and exceed those needs with a unique blend of industryleading UL listed hardware and software operations. This application
note provides technical information needed to apply one of many flexible
solutions to your installation, whether the application is a stand-alone
fire system, a burglary system, or a cost-effective combination system.
What are the Possibilities?
Typical fire and burglary alarm control panels offer single or multiple
notification outputs directly powered by the panel. This type of design
requires all notification circuits be wired from the most remote points of
the system directly to the panel. Increasing the wire gauge and limiting
the number of notification appliances are typical strategies required to
maintain voltage levels at the end of a circuit.
The UL listed XR500 Series, XR2500F, XR100 Series, and XR200 Panels
provide a single output, or zoned outputs that allow power supplies to
be distributed throughout the facility. Supervised power supplies can be
located anywhere along the panel LX-Bus™ placing the notification circuit
power near the notification appliances where it is needed.
Circuit Power Options
The system can be configured to provide a traditional 12 VDC burglary
output, a 24 VDC fire output, or a combination of both outputs. A
12 VDC, 1.5 Amp output is standard on the XR500 Series, XR2500F, XR100
Series, and XR200 panels and can be used for burglary or fire appliances.
Easily add 12 or 24 VDC power supplies to the system by employing
any of the available notification modules. Expand a panel to support
independently supervised, fully programmable circuits for customized
applications:
• XR500 Series or XR2500F panels support up to 574 circuits
• XR100 Series panels support up to 142 cirucits
• XR200 panel supports up to 242 circuits
This application note illustrates several different system configurations.
NOTIFICATION CIRCUIT OPTIONS
FOR COMBINATION SYSTEMS
APPLICATION NOTE
Conventional Large Fire/Small Burglary
Command Processor Panel
This application provides a 12 VDC, 1.5 Amp burglary output, and a 12 VDC,
5 Amp fire output. This would be useful in a facility where the major
objective is fire notification, but a local burglary alarm is also desired. The
XR500 Series, XR2500F, XR100 Series, and XR200 Panel 12 VDC, 1.5 Amp
output is used to power all burglary alarm appliances and the auxiliary
outputs are used to activate the DMP 866 Fire Notification Module. The 866
module switches the power supply to power the fire notification appliances.
Because DMP supports 12 or 24 VDC configurations the fire notification
appliances can be 12 or 24 VDC to meet local requirements.
Bell
Output
Output
1
DMP
Notification
Module
Notification
Device
Polarized
Burglary
Alarm
12 VDC
or
24 VDC
Power
Supply
Installation Notes:
1.The Model 865 Style Y/Z Notification Circuit Module may be substituted for the Model 866 to provide Class A
notification.
2.Bell Action programming must activate for burglary zones.
3.Zones 1 and 2 must be programmed as supervisory type zones with appropriate names.
4.Fire Bell Output programming must activate output 1.
5.For UL burglary systems where the bell is tested daily at closing, circuit supervision is not required.
6.See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series
Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions.
7.See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or
XR200 Programming Guide (LT-0196) for complete programming instructions.
XR500 Series/XR2500F
XR100 Series
Command Processor™
Panel
J
a per
J
one e in
J6
Interface
Card
Expansion
Connector
J
P
J
odel XR200
tp t
eader J
ra
J
tp t
J
J
C
J
C
E
E
J
6
ra
C I
ones
one
r
ar
ones
see notes
and
tp t
J 6
eset
tp t
E
ran e
6
6
E
ire
e
ee note
t
C
C
ire
t
J
atter
tart
6
a e
tead
e
C
o ari ed
r
ar
otification pp iance
pe
tp t
ps
E
o er
6
E
a e
ire otification
pe
per isor
ee note
pp
per isor
ee note
t
e
ode
66
ee note
otification Circ it e od
E
x
r
ro e
contacts
E
C or
C
o er
pp
o er
C
E
pp
Co
on
C po r e
inp t
ar
inp
t
C o tp t
eries
s
p
ro e
contacts
ire
otification
orns
12 VDC @ 1.5 Amp Bell Output from the Panel
12 VDC @ 5 Amps Fire Output from a DMP 505 Series 12 VDC Power Supply
Notification Circuit Application Note
2
Digital Monitoring Products
APPLICATION NOTE
Conventional Large Burglary/Small Fire
Command Processor Panel
This application is appropriate for a large burglary system which
requires only a small amount of fire notification, such as central
station water flow. The complete system is a 12 VDC design with
the fire notification appliances powered by the XR500 Series,
XR2500F, XR100 Series, or XR200 Command Processor™ Panel. The
addition of the DMP 866 Fire Notification Module provides the
panel with the circuit supervision required for fire notification.
A separate, auxiliary power supply can also be added to sound
burglary alarm appliances. This power supply is switched by a
second 866 module that is controlled by the panel Burglary Bell
Output programming option.
Bell
Output
Output
1
866
NAC
Module
866
NAC
Module
Polarized
Burglary
Alarm
Fire
Notification
Device
12 VDC
Power
Supply
Installation Notes:
1.The Model 865 Style Y/Z Notification Circuit Module may be substituted for the Model 866 to provide Class A
notification.
2.Bell Action programming for fire zones may be steady, pulse, or temporal to meet local requirements.
3.Zones 1, 2, and 3 must be programmed as a supervisory type with appropriate names.
4.Burglary Bell Output programming must activate output one. The Model 866 is needed to switch more than
1 Amp.
5.For UL burglary systems where the bell is tested daily at closing, circuit supervision is not required.
6.See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series
Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions.
7.See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or
XR200 Programming Guide (LT-0196) for complete programming instructions.
XR500 Series/XR2500F
XR100 Series
Command Processor™
Panel
J
a per
J
one e in
J6
Interface
Card
Expansion
Connector
J
P
J
odel XR200
tp t
eader J
tp t
ra
J
J
J
C
t
J
atter
tart
ra
J
C
C
E
E
tp t
E
C I
ones
se or e pora
r
ar
one
one
ee notes
and
a e
E
6
E
ire otification
pe
per isor
ee note
x
r
Co
on
ar inp t
C po r e
ro
contacts
t
e
J 6
eset
6
ptiona
E
a e
r
ar
pe
per isor
ee notes
and
tar
Circ i
E
E
E
Co
C or
C
o er
pp
ire
otification
orns
ar
inp t
ro e
contacts
E
e
on
C po r e
inp t
ro e
contacts
ptiona
E
a e
o er
pp
eries
pe
per isor o er
pp
ee note
C
ps
e
ode
66
ee note
otification Circ it od
e ran
6
6
E
ire
J
6
t
C
t
e
ode
66
ee note
otification Circ it od
o ari ed
r
ar
otification pp iance
e
12 VDC @ 1.5 Amp Bell Output from the Panel for NAC
12 VDC @ 5 Amps Burglary Output from a DMP 505 Series 12 VDC Power Supply
Digital Monitoring Products
Notification Circuit Application Note
3
APPLICATION NOTE
Distributed Power Notification Circuit
When a large number of fire notification and burglary alarm
appliances are required, the DMP LX-Bus™ provides extremely
flexible and expandable system design capabilities. Either 12 or
24 VDC power supplies can be installed at any point on the
panel LX‑Bus to provide burglary or fire, 12 or 24 VDC, zoned or
simultaneous operation.
Each of the five XR500 Series/XR2500F panel LX‑Bus expansion ports
can supervise 100 devices including power supplies for a total of
500. Up to 100 devices including power supplies can be supervised
on the XR100 Series LX-Bus for a total of 100. Each of the two
XR200 LX-Bus expansion ports can supervise up to 100 devices
including power supplies for a total of 200.
Command Processor Panel
481
Expansion
Card
LX-Bus
867
NAC
Module
867
NAC
Module
Polarized
Burglary or
Fire Alarm
Bell
Fire
Notification
Horns
12 VDC
Power
Supply
24 VDC
Power
Supply
The 505-12LX Power Supply includes a power supply and two 867 Notification Circuit Modules, and can be addressed
for independent supervision to indicate auxiliary power supply or notification circuit troubles. All power supplies can
operate from a common output, from separate burglary or fire outputs, or individual assignment by a panel zone.
Installation Notes:
1.The Model 867 LX-Bus Notification Module provides a secondary set of address switches so that supervisory
trouble on the notification circuit or 12 or 24 VDC power supply can be indicated by the panel via the LX-Bus.
2.By selecting different bell addresses on the burglary 867 module and fire 867 module, the panel’s Burglary Bell
Output and Fire Bell Output programming controls the modules independently. See the 867 Installation Guide
(LT-0178).
3.Multiple 867 modules may be set to the same bell address so that all sound at the same time, or independent
addresses so that notification may be zoned for burglary or fire. See the 867 Installation Guide (LT-0178).
4.To add a second LX-Bus to an XR500 Series/XR2500F panel, install a 481 Zone Expansion Card, 462N Network
Interface Card, or 462P Printer Interface Card into the J6 Interface Card Expansion Connector.
To add multiple LX-Buses to an XR500 Series/XR2500F panel, use a Model 461 Interface Adaptor Card and
additional Interface Cards, such as a 481 Zone Expansion Card, 462N Network Interface Card, or 462P Printer
Interface Card.
To add a second LX-Bus to an XR200 use a Model 460 Interface Adaptor Card and a second Interface Card, such
as a 481 Zone Expansion Card, 462N Network Interface Card, or 462P Printer Interface Card.
Note: The XR100 Series panel only supports one on-board LX-Bus.
5.See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series
Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions.
6.See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or
XR200 Programming Guide (LT-0196) for complete programming instructions.
Notification Circuit Application Note
4
Digital Monitoring Products
APPLICATION NOTE
4
Tamper
3
Phone Line
1
DMP Model
481 L -Bus
E pansion Card
(See note 4)
XR500 Series/XR2500F
XR100 Series
Command Processor™
Panel
se on
P XR200
1
2
3
2
L
22 L B
- us
K6
P
AC AC +B
1
2
3
B BELL
4
5
ND
6
ED EL
7
8
8
O
N BLK SMK
10
11
ND
12 13
2
Out 1 Out 2
0
1
Battery
Start
1
1
K7
ND
14
2
3 ND
15 16
17 18
6
1
eset
4
5
1
ND
6
20
21 22
7
ND
23
8
+
24
25
10+ 10
26
27
10K
EOL
+
-
+
12 VDC or
24 VDC
Power Supply
DMP 505 Series
Power Supply
12 VDC @ 5 Amps
Trouble
contacts
10K
EOL
+
-
NAC power
input
Polarized Burglary
Notification Appliances
(See notes 2 and 3)
DMP Model 867 (See note 1)
Style W Notification Circuit Module
To other 867 modules
for burglary or fire notification
28
+
-
NAC power
input
+
-
+
12 VDC or
24 VDC
Power Supply
DMP 505 Series
Power Supply
12 VDC @ 5 Amps
Trouble
contacts
-
DMP Model 867 (See note 1)
Style W Notification Circuit Module
Fire Notification
Appliances
(See notes 2 and 3)
To other 867 modules
for burglary or fire notification
Multiple distributed 12 VDC @ 5 Amps Fire and Burglary Outputs from a DMP 505 Series 12 VDC Power Supply
Digital Monitoring Products
Notification Circuit Application Note
5
APPLICATION NOTE
Separate Horn and Strobe Circuits
Command Processor Panel
Some applications require that during a system reset, fire horns be silenced
first, followed later by strobes. This type of operation allows the strobes to
remain active after the initial fire notification horn silencing. The strobes
deactivate only after the cause of the alarm is investigated and the system
is reset.
Bell
Output
Polarized
Burglary Alarm
The XR500 Series, XR2500F, XR100 Series, and XR200 panels provide this
operation by the addition of an 866 Notification Module which supplies
power to the strobe circuit. This second module is activated by the panel
Fire Alarm Output, which does not deactivate until a Sensor Reset Command
is performed at any Fire Command™ or other DMP keypad.
Output
1
Output
2
866
NAC
Module
866
NAC
Module
Fire
Notification
Horns
Fire
Notification
Strobes
Power
Supply
Power
Supply
This diagram illustrates how to accomplish separate horn/strobe
deactivation. In addition, an optional combination local burglary alarm is
included.
Installation Notes:
1.The Model 865 Style Y/Z Notification Circuit Module can be substituted for the Model 866 to provide Class A
notification.
2.Bell Action programming must activate steady for burglary zones.
3.Zones 1 and 2 must be programmed as supervisory type zones with appropriate names.
4.Fire Bell Output programming must activate output one. If no burglary alarm is needed, the panel Bell Output
can activate the fire horn.
5.For UL burglary systems where the bell is tested daily at closing, supervision of the circuit is not required.
6.Fire Alarm Output programming must activate output two.
7.See the XR500 Series Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series
Installation Guide (LT-0899) or XR200 Installation Guide (LT-0197) for complete installation instructions.
8.See the XR500 Series/XR2500F Programming Guide (LT-0679), XR100 Seriels Programming Guider (LT-0896), or
XR200 Programming Guide (LT-0196) for complete programming instructions.
XR500 Series/XR2500F
XR100 Series
Command Processor™
Panel
J
a per
J
one e in
J6
Interface
Card
Expansion
Connector
t
e
ode
66
ee note
otification Circ it od
J
P
J
x
odel XR200
tp t
J
Co
eader J
tp t
J
ran e
t
J
6
ra
J
ran e
ee
C
C
E
E
E
ire
6
C I
ones
none
ar
ones
stead
ee notes
E
a e
e
C
r
ire
otification
orns
on
C po r e
inp t
E
E
ar
inp t
C o tp t
ote
ro e
contacts
I E
ote 6
6
6
r
I E
J 6
eset
t
C
ite
ee
J
J
atter
tart
ran e
ran e
tp t
C
e
pe
tp t
ps
E
a e
ire otification
pe
per isor
ee note
E
o er
pp
s per isor
ee note
6
E
E
Co
ro e
Contacts
o ari ed
r
ar
otification pp iance
C
on
ar
pp
inp
t
C po r e
inp t
C or
C
o er
pp
o er
ire
otification
tro se
x r
E
C o tp t
eries
ro e
contacts
ps
t
e
are
ode
66
ee note
otification Circ it od
nc
od
e re
ired if sstro e
ocated in sa e roo
e
12 VDC @ 1.5 Amp Burglary Output from the Panel
12 VDC @ 5 Amps Fire Output from a DMP 505 Series 12 VDC Power Supply
Notification Circuit Application Note
6
Digital Monitoring Products
APPLICATION NOTE
Model 867 Style W LX-Bus™ Notification Module
The Model 867 provides one supervised Style W notification circuit for system expansion and connects at any point
on the panel LX-Bus. Two sets of rotary switches provide a unique addressing scheme which enables the module to
respond to one address for supervision, yet operate the notification circuit on a second address. Having separate
supervisory and notification addresses allows multiple modules to be activated in groups, while monitored by the
XR500 Series, XR2500F, XR100 Series, or XR200 panel individual supervisory zone programming.
A ring style jumper allows any one of four notification cadences to be selected: Steady, Pulse, Temporal, or
California School Code. The 867 is also capable of switching 12 or 24 VDC up to 5 Amps from an auxiliary power
supply. Mount the 867 Module in the power supply enclosure for supervised operation.
10K EOL
Normal/Silence Switch
NAC Power Supply:
Up to 5 Amps @
12 VDC or 24 VDC
Ground Fault LED
Bell Trouble LED
1
2
867 Module
Trouble
Contacts
12 or 24 VDC
3
4
5
6
7
TENS
867 Style W LX-Bus
Notification Module
Steady
Pulse
Termporal
California Schools
8
ONES
Bell Relay
Address
TENS
ONES
Supervisory
Address
To optional auxiliary
trouble indicator
To additional
LX-Bus Modules
From
Panel
LX-Bus™ Wiring
Model 866 Style W Notification Module
The 866 module is suitable for use with 2-wire circuits and can switch up to 5 Amps at 12 or 24 VDC. Trouble
contacts are included to indicate notification circuit trouble. The 866 module can be used in parallel or zoned
applications.
DMP Model 866
Normal
NAC Power Supply:
Up to 5 Amps @
12 VDC or 24 VDC
10K EOL
Bell Silence
AUX PWR 1
GND 2
12 or 24 VDC
Alarm In 3
Bell PWR In 4
Bell Out + 5
866 Style W
Notification Module
Bell Out – 6
Bell Trouble 7
Bell Trouble 8
Digital Monitoring Products
Notification Circuit Application Note
7
Model 865 Style Y or Z Notification Module
The 865 Module is suitable for use with 2-wire or 4-wire circuits and provides a trouble LED, ground fault LED, and a
set of trouble contacts to indicate off normal conditions. The module can be used in parallel, activated by a single
output, or activated independently by using zoned outputs from the panel. The 865 can switch up to 5 Amps at 12 or
24 VDC.
Normal/Silence Switch
NAC Power Supply:
Up to 5 Amps @
12 VDC or 24 VDC
865 Module
AUX PWR 1
GND 2
Alarm In 3
Bell PWR In + 4
Bell PWR In – 5
Bell Out A + 6
Bell Out A – 7
Bell Trouble Out + 8
Bell Trouble Out – 9
N/C Trbl Contacts 10
N/C Trbl Contacts 11
865 Style Y or Z
Notification Module
Style Z
+
+
+
-
-
-
10K EOL
Style Y Only
Style Y
For Style Y circuit, remove wires
from terminals 8 and 9 and
install the 10K EOL as shown.
Product Compliance Certifications
The products discussed in this Application Note are certified by the agencies listed in the table below. For complete
compliance information see the specific listing cards from each agency and the following guides: XR500 Series
Installation Guide (LT-0681), XR2500F Installation Guide (LT-0759), XR100 Series Installation Guide (LT-0899), XR200
Installation Guide (LT-0197), XR500 Series/XR2500F Programming Guide (LT‑0679), XR100 Series Programming Guide
(LT-0896), or XR200 Programming Guide (LT‑0196). This information is also available at www.dmp.com.
Model
Description
UL
CSFM
MEA
574-Zone Command Processor™ Panel
S3598
7165-1157:123
168-93-E VOL. VI
574-Zone Fire Command Processor™ Panel
S3598
7165-1157:124
168-93-E VOL. VI
XR100 Series
142-Zone Command Processor™ Panel
S3598
7165-1157:123
Future
XR200
242-Zone Command Processor™ Panel
S3598
7165-1157:105
168-93-E VOL. III
865
Style Y or Z Notification Circuit Module
S3598
7165-1157:105
168-93-E VOL. III
866
Style W Notification Circuit Module
S3598
7165-1157:105
168-93-E VOL. III
867
Style W LX-Bus™ Notification Circuit Module
S3598
7165-1157:105
168-93-E VOL. III
461
XR500 Series/XR2500F Interface Adaptor Card
S3598
7165-1157:123
168-93-E VOL. VI
460
XR500 Series
XR2500F
XR200 Interface Adaptor Card
S3598
7165-1157:105
168-93-E VOL. III
462N
Network Interface Card
S3598
7165-1157:105
168-93-E VOL. III
462P
Printer Interface Card
S3598
7165-1157:105
168-93-E VOL. III
481
LX-Bus™ Expansion Card
S3598
7165-1157:105
168-93-E VOL. III
505-12
12 VDC Power Supply
S7400
7315-1157:114
168-93-E VOL. VI
Power Supplies
505-12L
12 VDC Power Supply
S7400
7315-1157:114
168-93-E VOL. VI
505-12LX
12 VDC Power Supply w/2 built-in NACs
S7400
7315-1157:114
168-93-E VOL. VI
505-12A
12 VDC Power Supply
S7400
7315-1157:114
168-93-E VOL. VI
800 - 641 - 4282
INTRUSION
•
FIRE
•
ACCESS
•
NETWORKS
www.dmp.com
2500 North Partnership Boulevard
Designed, Engineered and
Assembled in U.S.A.
S p r i n g fi e l d , M i s s o u r i 6 5 8 0 3 - 8 8 7 7
LT-2012 (12\06) © 2013 Digital Monitoring Products, Inc.
Command Processor™ Panel Equipment
Download