POWER INSTRUMENTS SPECTRATM BC11 FLAME SENSOR INSTALLATION AND OPERATIONS MANUAL 1085-150 Rev. A Disclosure Notice THE INFORMATION (INCLUDING TECHNICAL DATA) CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF AMETEK POWER INSTRUMENTS. IT IS DISCLOSED IN CONFIDENCE. THEREFORE, NONE OF THE INFORMATION MAY BE DISCLOSED TO OTHER THAN THE RECIPIENT, OR USED FOR PURPOSES OTHER THAN TO RENDER SERVICES TO AMETEK, WITHOUT THE EXPRESS PRIOR WRITTEN AUTHORIZATION OF AMETEK. Spectra and the Spectra logo are trademarks of Ametek Power Instruments. Ametek, and the Ametek logo are trademarks of Ametek Inc. Copyright © 2005. By Ametek Inc. All Rights Reserved Warranty AMETEK warrants equipment of its own manufacture to be free from defects in material and workmanship, under normal conditions of use and service. AMETEK will replace any component found to be defective, upon its return, transportation charges prepaid, within one year of its original purchase. AMETEK will extend the same warranty protection on accessories that is extended to AMETEK by the original manufacturer. AMETEK assumes no responsibility, expressed or implied, beyond its obligation to replace any component involved. Such warranty is in lieu of all other warranties expressed or implied. ii 10845-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Contents 1. Introduction and Installation .....................................................................1-1 General ................................................................................................................................ 1-1 Sensor Construction........................................................................................................ 1-1 Optical Sensitivity........................................................................................................... 1-2 General Notes on Flame Sensor Installation.................................................................... 1-4 Installation ........................................................................................................................... 1-8 2. Operation ..................................................................................................2-1 Inspection ............................................................................................................................ 2-1 Testing and Fault Isolation .................................................................................................... 2-2 Current Measurement ..................................................................................................... 2-3 Voltage Measurement ..................................................................................................... 2-4 3. Cleaning and Storage .................................................................................3-1 Cleaning and Preparation for Storage or Shipment................................................................ 3-1 Sensor Cleaning.............................................................................................................. 3-1 Preparation for Shipment or Storage................................................................................ 3-2 Appendix A. Specifications and Accessories ................................................. A-1 Specifications .......................................................................................................................A-1 Compliance Tests .................................................................................................................A-2 Optional Accessories............................................................................................................A-3 Appendix B. Schematics ................................................................................B-1 1085-150 Rev. A 1/05 iii iv 1085-150 Rev. A 1/05 Preface Purpose and Scope This manual describes the AMETEK SpectraTM BC11 Flame Sensor operation, maintenance and installation procedure. The manual contains information to support the use of the sensor for flame monitoring of a burner in the boiler of an industrial power utility or other application. If more data is necessary or special problems occur that are not covered in this manual, refer inquiries to: AMETEK Power Instruments 255 North Union Street Rochester, NY 14605 Phone: 585-263-7700 Fax: (585) 454-7805 Website: http://www.ametekpower.com Reference Documents ANSI/ISA-1995 (S50.1) Compatibility of Analog Signals for Electronic Industrial Process Instruments ANSI/ISA-1995 (S71.01) Environmental Conditions for Process Measurement and Control Systems: Temperature and Humidity ANSI/ISA-1995 (S71.03) Environmental Conditions for Process Measurement and Control Systems: Mechanical Influences ANSI/ASME CSD-1-195 Controls and Safety Devices for Automatically Fired Boilers by ASME FACTORY MUTUAL Approval Standards for Combustion Safeguards NFPA 70 1085-150 Rev. A 1/05 National Electrical Code by NFPA v Notes, Cautions, and Warnings Note, Caution, and Warning icons denote information of special interest. The icons appear in the column to the left of the text and are reproduced below, along with explanations of their meanings. NOTE The NOTE icon signifies a cautionary statement, an operating tip or maintenance suggestion. CAUTION The CAUTION icon signifies information that, if ignored, could lead to instrument damage. WARNING The WARNING icon signifies information that denotes a potentially hazardous situation, which, if not avoided, may result in death or serious injury. Document Conventions Bold type indicates an item (button, etc.) on which an action is performed. Italics is used for emphasis. vi 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual 1. Introduction and Installation General The Spectra™ BC11 Flame Sensor is a two-wire loop-powered optical flame sensor that receives either IR or UV energy from the combustion process and transmits a 4-20 mA analog signal proportional to flame intensity. The Spectra™ BC11 operates continuously up to 125 °C (257 °F). The Spectra™ BC11 is mounted directly to the burner or on a short standoff pipe via an internal 1" NPT thread. Sensor Construction Sensor models and differences among them are given in Table 1.1. The housing of the sensor has a viewing port at one end with installation threads. The sensor is attached to the application using the 1" NPT female thread. The other end of the housing has a MAIN electrical connector that mates with the interconnection cable. The housing, environmentally sealed for operation in a relative humidity from 0 to 95% non-condensing, contains the optics and electronics that convert the radiation collected at the viewing port to a variety of output formats. Table 1.1 Flame Sensor Model Differences Model Radiation Sensitivity Threads Electrical Code Class Ambient Temperature BC11-UV UV 200 nm 380 nm 1" NPT Class 1 Div 2 -40 to 125° C BC11-IR IR 700 nm 1100 nm 1" NPT Class 1 Div 2 -40 to 125° C 1085-150 Rev. A 1/05 1-1 Optical Sensitivity The intensity of optical energy, emitted by heated bodies, varies with temperature and wavelength. Figure 1.1 shows the relation of emission intensity to wavelength for an ideal black body at several temperatures in the visible (400 to 700 nm) and ultraviolet range (200 to 400 nm). Emission of optical energy by flames is similar to that of a black body, except that, additional optical energy is generated by the chemical reaction that results from combustion of the fuel that produces the flame. Figure 1.1 Black Body Emissions Coal and Oil Burners In burners of coal and oil droplets, heat emission from flames is much greater than chemical emission at all wavelengths, so their flames act like a black body. Emission intensity is greatest in the IR range (700 to 1100 nm). Therefore, sensors for monitoring flames from the burning of coal and oil have optical detectors with greatest sensitivity to IR radiation. Natural Gas Burners In burners of natural gas, optical energy from chemical emission is more significant, especially in the UV/Visible region. Figure 1.2 on page 1-3 shows the relative intensity of optical energy at a range of wavelengths. Narrow peaks, or lines of optical energy, resulting from chemical action are superimposed on the more uniform response characteristic of heat emission. The lines give the natural gas flame a unique signature. The line at 310 nm is important in discriminating between flame emission and heat emission at longer wavelengths from hot metal parts. Because of the unique characteristics of optical energy emitted by gas flames, the BC11-UV sensors have detectors with greatest sensitivity to UV radiation. 1-2 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Figure 1.2 Gas Flame Emissions Spectral Response of Detectors Figure 1.3 shows the response of three types of optical detectors. Figure 1.3 Differences in Detector Responses Silicon sensitivity includes much of the visible and IR range with greatest sensitivity in the IR range. This type of detector is satisfactory for monitoring coal and oil flames. It is used in the BC11-IR sensor. The detector used in an older tube detector has a narrow range of sensitivity in the UV region, but is insensitive to the 310 nm line of energy, characteristic of the natural gas flame. The AMETEK UV detector has maximum sensitivity near 310 nm and has a narrow bandpass that excludes higher wavelength energy, such as that in the IR region generated by hot metal parts. It is used in the BC11-UV sensor. 1085-150 Rev. A 1/05 1-3 General Notes on Flame Sensor Installation Flame sensor installation consists of: • ”1. Flame Sensor Selection” : • UV or IR (Based on Fuel) • Environment • ”2. Flame Sensor Sighting” : • Which flame will the sensor be used to monitor • Main burner Flame • Igniter • Main Fireball 1. Flame Sensor Selection Environment IR and UV Selection Based On Fuels BC 11 series flame sensors are used when temperatures are 125 °C maximum. As a general guide for sensor selection: • IR is used for heavy fuel oils and coal. • UV is used for light fuel oils and natural gas. Most systems use 2 fuels 2. Flame Sensor Sighting NOTE WARNING 1-4 An acceptable scanner location must ensure the following: • Reliable pilot flame detection. • Reliable main flame detection. • Rejection of a pilot flame too short or in the wrong position to ignite the main flame reliably, prohibiting main fuel admission. Reliable signals must be obtained at all air flows and furnace loads (ranges of fuel firing). Incorrect sensor installation can cause the sensor to generate a false flame signal. This can cause unburned fuel to collect in the combustion chamber, resulting in explosions, injuries and property damage. Be certain that the flame sensor detects only the pilot and main flames, not glowing refractory or burner parts. 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Use the following guidelines: • The best results are obtained when the scanner is aimed so that the scanner’s line of sight intersects the burner center at a slight angle (e.g. 5 °) and sees a maximum of the primary combustion zone (Figure 1.4). If only one scanner is used per burner, the line of sight should also intersect the igniting flame. • For installations where separate scanners are used to monitor main and ignitor flames, the main flame scanner should be sighted so it does not detect the ignitor flame. The scanner should have an unrestricted view of flame, as far as possible. Figure 1.4 Single Burner Scanner Sighting • Consider burner secondary air rotation: clockwise (CW) or counterclockwise (CCW) air rotation. If combustion air enters the furnace with a rotational movement of sufficient velocity to deflect the ignitor flame in the direction of rotation, position the scanner 10 to 30 ° downstream of the ignitor (Figure 1.5) and close to the periphery of the burner throat. Figure 1.5 Scanner Location vs. Secondary Air Rotation 1085-150 Rev. A 1/05 1-5 Sighting Inspection Always check sighting prior to the installation of a flame sensor (Figure 1.6). Figure 1.6 Proper Sighting WARNING Wear protective filtered lenses when viewing the flame. Infrared and ultraviolet energy from the flame can damage eyes. Figure 1.7 shows an example ignitor and main flame setup. • Setup A: Depicts a MAIN FLAME only sighting • Setup B: Depicts a minimal IGNITOR and MAIN FLAME sighting. • Setup C: Depicts a normal (RECOMMENDED) IGNITOR and MAIN FLAME sighting. Figure 1.7 Example Ignitor and Main Flame Setup 1-6 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Additional Considerations CAUTION Some considerations on BC11 placement include: Use only isolated DC power supplies for the BC11. Do not use a Variac power supply. Burner Flame Considerations A burner has main and igniter or pilot flames. If one sensor is used to monitor both flames, the line of sight should intersect both. If separate sensors are used, the lines of sight should not intersect. Obstruction Considerations If possible, obstructions, such as, air register blades, vanes, or other hardware, should be modified so that they do not interfere with the line of sight. Unwanted matter, resulting from combustion in the burner, can also obscure the viewing port of the sensor. Purge air is used to direct such matter away from the sensor. Air Rotation Considerations If combustion air enters the furnace or burner with a rotational movement of sufficient velocity to deflect the igniter flame in the direction of rotation, aim the sensor 10° to 30° downstream of the igniter and close to the periphery of the burner throat. Load Considerations Flame characteristics vary with burner load and firing rates. The optimum alignment of a sensor with respect to a monitored flame is that which gives the highest average output under all considerations. 1085-150 Rev. A 1/05 1-7 Installation Installation of a the Spectra™ BC11 flame sensor includes installation of the sensor to the burner, making connections to the sensor, and sighting the sensor for best response. Table 1.2 lists the tools required for either installation type. Table 1.2 Installation Material and Equipment Item Description Wrench Adjustable to 15/8" Anti-seize compound High temperature grade Screw driver Standard tip To install: 1. Attach the sensor to the installation pipe or mounting flange using the internal 1" NPT thread connection at the sensor window, and tighten using an adjustable wrench (Figure 1.8). CAUTION The use of high temperature anti-seize compound is recommended. When using any anti-seize or thread sealant take care not to get any on the sensor window, as it degrades sensor operation. 2. Attach the mating cable by aligning the keyways of the connectors and tightening the coupling ring clockwise until the cable is fully mated. The cable is fully mated when the red indicator band on the receptacle connector is not visible. Figure 1.8 BC11 Installation Diagram 1-8 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual 3. Wire per National Electrical Code standards (Figure 1.9). Figure 1.9 BC11 Installation Wiring See Table A.3 on page A-3 for wire identification. 1085-150 Rev. A 1/05 1-9 1-10 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual 2. Operation Inspection You must have a 3X magnifying glass to perform an inspection. Inspect the sensor for conditions given in Table 2.1. If conditions are found during inspection that cannot be repaired locally, return the unit to: AMETEK Power Instruments 255 North Union Street Rochester, NY 14605 Phone: 585-263-7700 Fax: 585-238-4945 Website: http://www.ametekpower.com NOTE CAUTION Before returning any item you must call for a Return Material Authorization (RMA). Ametek takes no responsibility for field repairs. Table 2.1 Inspection Criteria Condition Corrective Action Sensor window: Surface scratches on the sensor window Return to AMETEK. Sensor window: Unwanted material/contamination on window Refer to ”Cleaning and Storage” on page 3-1. Sensor window: Damaged threads Repair damaged threads with thread chaser or return to AMETEK for repair. Connector: Unwanted material/contamination Remove unwanted material; refer to ”Cleaning and Storage” on page 3-1. Connector: Bent pins Carefully straighten the pins so that they fit into the mating receptacle. Connector: Broken pins Return to Ametek if pins A,B or C are broken. 1085-150 Rev. A 1/05 2-1 Testing and Fault Isolation The sensor and interconnection cable can be tested as a system. If the result is not satisfactory, isolate the fault by testing the sensor and by performing a continuity test of the system interconnections. To aid in fault isolation, refer to ”Current Measurement” on page 2-3 or ”Voltage Measurement” on page 2-4. Table 2.2 lists the equipment needed for Testing and Fault isolation. Table 2.2 Test Equipment 2-2 Item Description AC/DC Light Source Quartz halogen lamp (100 W minimum) or equivalent DC Power Supply 0-30 VDC adjustable Multimeter 0-5 VDC, 0.1% accuracy, 20 mA,1% accuracy Resistor 250 Ω, 1%, 1/4 W minimum 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Current Measurement To perform this test: CAUTION Ametek takes no responsibility for field repairs. 1. Connect the sensor as shown in Figure 2.1. 2. Block the sensor window to prevent any light from entering. 3. Vary the output of the DC power supply from 20 VDC minimum to 30 VDC maximum. Ensure that the multimeter steadily reads 4.00±0.50 mA. 4. Shine direct light from the AC/DC light source into the sensor window until the multimeter reads greater than 6.00 mA. 5. Vary the output of the DC power supply from 20 VDC minimum to 30 VDC maximum. Ensure that the multimeter steadily reads greater than 6.00 mA. Figure 2.1 Current Measurement 1085-150 Rev. A 1/05 2-3 Voltage Measurement To perform this test: CAUTION Ametek takes no responsibility for field repairs. 1. Connect the sensor as shown in Figure 2.2. 2. Block the sensor window to prevent any light from entering. 3. Vary the output of the DC power supply from 20 VDC minimum to 30 VDC maximum. Ensure that the multimeter steadily reads 1.00±0.13 VDC. 4. Shine direct light from the AC/DC light source into the sensor window until the multimeter reads greater than 1.5 VDC. 5. Vary the output of the DC power supply from 20 VDC minimum to 30 VDC maximum. Ensure that the multimeter steadily reads greater than 1.5 VDC. Figure 2.2 Voltage Measurement 2-4 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual 3. Cleaning and Storage Cleaning and Preparation for Storage or Shipment The sensor should always be cleaned: • Before a test • Before shipping or storing Refer to Table 3.1 on page 3-2 for material and equipment used in cleaning and preparing for shipment. Sensor Cleaning WARNING Contact with liquid or particles propelled by compressed air can permanently damage eyes. Inhalation of air-blown particles or solvent vapor can damage lungs. Cleaning fluids may be toxic and/or flammable. For safety, use only with adequate ventilation; wear protective clothing; avoid contact with skin and eyes; avoid breathing fumes. Do not expose to flame or sparks. CAUTION Do not direct compressed air flow at the lens; damage may result. Do not let solvent come in contact with the window. To clean the sensor: 1. Remove unwanted material from the external surface and threads using filtered compressed air. 2. If residue remains, remove it from the external surface and threads with a brush and a lint-free cloth moistened with cleaning solvent. 3. Dry the external surfaces and threads with filtered compressed air. 4. Clean the sensor window using a lint-free cloth or cotton swab and glass cleaner. 5. Install protective covers on the sensor window and the connector. 1085-150 Rev. A 1/05 3-1 Preparation for Shipment or Storage Table 3.1 lists items required to prepare for storage or shipment. To perform this procedure: 1. Seal the unit in a clean plastic bag with a label indicating its part number and serial number. 2. Pack the unit in a shipping box, protecting it with packing material. 3. Attach a label to the shipping box that indicates the part number and serial number of the unit. NOTE Before returning any item you must call for a Return Material Authorization (RMA). NOTE Store the unit in a location with low humidity. Table 3.1 Material and Equipment 3-2 Item Description Plastic bag 12" by 8" Cardboard box 12" by 6" by 6" Brush Non-metallic Cloth Soft, lint free Compressed air 25-35 psig, filtered Glass cleaner #1 denatured alcohol Safety goggles GG-G-531 or equivalent Safety gloves ZZ-G-381 or equivalent Dry cleaning solvent P-D-680 Type II or equivalent 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Appendix A. Specifications and Accessories Specifications The Spectra™ BC11 physical and operational specifications are listed in Table A.1. See Table A.2 on page A-2 for a listing of Spectra™ BC11 compliance tests and Table A.3 on page A-3 for a listing of optional accessories. Table A.1 Specifications Specification Range Physical Wire connections • • • • • • • • Pin A: +24 VDC nominal Pin B: 4–20 mA current return Pin C: Case ground Pin D: No connection Pin E: No connection Pin F: No connection Pin G: No connection Pin H: No connection Mounting flange connection 1" NPT internal thread Body Anodized aluminum NEMA-4x Weight 0.6 kg (~1.4 lbs) Operational Operating temperatures −40 to 125 °C (–40 °F to +257 °F) Humidity 95% relative per MIL-STD-202F Input • IR or UV energy from flame • 4° field of view Power requirement 1085-150 Rev. A 1/05 +24 VDC nominal power input (20–30 VDC range) A-1 Table A.1 Specifications (Continued) Specification Range Output Output current 25 mA maximum Signal output Industry standard 4 to 20 mA current loop, no light input (total darkness) = 4.0 mA, ± 0.5 mA over entire temperature range Compliance Tests Table A.2 lists the compliance tests for the Spectra™ BC11. Table A.2 Compliance Tests A-2 Standard Tests Conducted CE EN55011: Radiated emissions EN61000-4-2: ESD EN61000-4-3: Radiated immunity EN61000–4–4: EFT EN61000-4-6: Conducted immunity Factory Mutual (FM) To standards: FM7610 FM3611 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Optional Accessories Table A.3 lists the accessories available to perform unit installation. NOTE Consult factory for other cable options. Table A.3 Optional Accessories Part Number Description ET-1215 Relay Module • • • • SC-7403-N Relay Module • Single Input • Single Output (SPDT) • Software Adjustable Trip only (PC-7400-3 Required) • Power 24 VDC, 48VDC, 110 VDC, 120 VAC 50/60 Hz SC-7404-N Relay Module • Single Input • Dual Output (SPDT) • Software Adjustable Trip only (PC-7400-3 Required) • Power 24 VDC, 48VDC, 110 VDC, 120 VAC 50/60 Hz SC-7405-N Relay Module • Single Input • Single Output (SPDT)·Single 4-20mA Retransmit Output • Software Adjustable Trip only (PC-7400-3 Required) • Power 24 VDC, 48VDC, 110 VDC, 120 VAC 50/60 Hz PC-7400-3 Configuration Kit • Configuration software and cable • Used on 7403-N, 7404-N, 7405-N 8998A31P002 Power Supply • 24 VDC, 0.6A Output • Din mount • Power Input 115 VAC 1085-150 Rev. A 1/05 Single or double 4–20 mA inputs - specify Two SPDT inputs Trip mode to be specified Power 115 VAC A-3 Table A.3 Optional Accessories (Continued) A-4 Part Number Description 8998A31P003 Power Supply • 24 VDC, 2.0A Output • Din mount • Power Input 115 VAC 8998A31P004 Power Supply • 24 VDC, 5.0A Output • Din mount • Power Input 115 VAC 8TL41AAA1 Cable • 10’ long 1085-150 Rev. A 1/05 SpectraTM BC11 Installation and Operations Manual Appendix B. Schematics Figure B.1 SpectraTM BC11 Flame Sensor 1085-150 Rev. A 1/05 B-1 Figure B.2 Cable Shield Drawing and Wiring B-2 1085-150 Rev. A 1/05