F-35-1000 January 2016 Platform Ignition Module Application Guide TABLE OF CONTENTS CHAPTER 1 PRODUCT OVERVIEW AND DESCRIPTION 1-1 Introduction ......................................................................................... 1-1 1-2 Applications ......................................................................................... 1-1 1-3 System Integration ............................................................................... 1-2 1-4 Features .............................................................................................. 1-3 1-5 Agency Approvals ................................................................................. 1-3 1-6 Reference Documents............................................................................ 1-4 1-7 Specifications ....................................................................................... 1-4 CHAPTER 2 PIM FEATURES 2-1 Control Power....................................................................................... 2-1 2-2 Wiring Connections ............................................................................... 2-1 2-3 Ignition Outputs ................................................................................... 2-1 2-4 Gas Valve Options................................................................................. 2-1 2-5 Combustion Blower ............................................................................... 2-1 2-6 High-Current Blower Option.................................................................... 2-1 2-7 Auxiliary Relay Outputs.......................................................................... 2-1 2-8 UL353 High Limit Sensor........................................................................ 2-2 2-9 Temperature Sensors ............................................................................ 2-2 2-10 Demand Inputs..................................................................................... 2-2 2-11 Safety Inputs ....................................................................................... 2-2 2-12 RATE INPUTS ....................................................................................... 2-2 2-13 Temperature Control ............................................................................. 2-2 2-14 Potentiometer (Setpoint) ....................................................................... 2-2 2-15 Configuration (DIP Switch Settings)......................................................... 2-2 2-16 ID Card ............................................................................................... 2-3 CHAPTER 3 HYDRONICS FUNCTIONS 3-1 Outdoor Reset ...................................................................................... 3-1 3-2 Domestic Hot Water Control ................................................................... 3-1 3-3 Pump Control ....................................................................................... 3-1 3-4 Freeze Protection .................................................................................. 3-1 CHAPTER 4 COMMUNICATIONS AND DIAGNOSTICS 4-1 RS485 Communications ......................................................................... 4-1 4-2 Energy Management System (Customer provided)..................................... 4-1 4-3 Indicators ............................................................................................ 4-1 4-4 Self-Check/Control Failure...................................................................... 4-1 4-5 System Safety Checks ........................................................................... 4-1 4-6 Flame Current Measurements ................................................................. 4-2 4-7 Non-Volatile Lockout/Manual Reset.......................................................... 4-2 CHAPTER 5 APPLICATION EXAMPLES 5-1 Application Examples............................................................................. 5-1 5-1.1 High Efficiency Modulating Boiler............................................................. 5-1 5-1.2 HVAC Space Heater............................................................................... 5-2 5-1.3 Commercial Cooking.............................................................................. 5-3 F-35-1000 i January 2016 TABLE OF CONTENTS (CONT.) APPENDIX A A-1 A-2 A-3 A-4 APPLICATION WORKSHEET Factory Low-Voltage Connections (30 VAC Max)........................................ A-1 Factory Line-Voltage Connections............................................................ A-1 Low-Voltage Field Wiring Connections (30 VAC Max).................................. A-2 Hardware Configuration ......................................................................... A-2 APPENDIX B B-1 PIM PARAMETER DESCRIPTIONS PIM Parameters .................................................................................... B-1 APPENDIX C C-1 PART NUMBER BREAKDOWN PIM Part Number .................................................................................. C-1 APPENDIX D D-1 FENWAL DEVELOPMENT TOOL Fenwal Development Tool ...................................................................... D-1 January 2016 ii F-35-1000 Product Overview and Description CHAPTER 1 PRODUCT OVERVIEW AND DESCRIPTION 1-1 INTRODUCTION The Fenwal Controls® Platform Ignition Module (PIM™) integrates the functions of Automatic Ignition Control with temperature regulating and appliance control functions. The PIM is designed for a range of applications including both staged systems and modulating types. The PIM can be configured as a direct spark ignition (DSI), intermittent pilot (IP) or Hot Surface Ignition (HSI) to provide safe lighting and supervision of the burners in an appliance. The PIM is capable of RS485 communications which can be tailored to interact with User Interface/Displays, OEM controls, networks, PC analysis tools, or other devices. It also accepts analog signals from other controllers or Energy Management Systems (EMS). For hydronics applications, the PIM directly connects and communicates with the tekmar® Boiler Temperature Control (BTC_II). When connected to a BTC_II, the PIM offers expanded control functionality including Domestic Hot Water (DHW), outdoor reset, diagnostic messages, and other system capabilities. Figure 1-1. PIM and Associated Components 1-2 APPLICATIONS The PIM control system is suited to a wide variety of residential and commercial gas-fired heating systems including: F-35-1000 • High-efficiency Modulating Condensing Boilers • Fan-assisted single and multi-staged Systems • Intermittent Pilot based appliances • Water Heaters • Pool and Spa Heaters • Commercial Cooking • HVAC and Air-Handling Systems • Industrial Process Systems 1-1 January 2016 Product Overview and Description 1-3 SYSTEM INTEGRATION The PIM is able to intelligently integrate and replace multiple discrete components with a single control. In a typical application it will replace all of the blue shaded items in the figure below. This allows the OEM to increase burner and system performance while simplifying wiring and construction with a high-value solution. Temp Sensor Limit Sensor Flame Sense Temperature Control High Limit 2nd Stage Demand PWM Blower Control Blower Relay Burner Gas Valve Ignition Control TDR 2nd Stage Valve Combustion Blower Gas Flow Diagnostics with Fault Control Blower Contactor Circulation Blower TDR Temp Sensor AUX Function Control Vent Damper Figure 1-2. System Integration January 2016 1-2 F-35-1000 Product Overview and Description 1-4 FEATURES The PIM provides the following features: 1-5 • Integrated UL353 High Limit using Thermistor Sensor • Configuration parameters selected through a unique Identification Card • Communicates via RS485 • Measures up to seven temperature sensors using NTC curve J Thermistors, 10 KΩ (β3892) at 25°C (12 KΩ Thermistors optional). • Optional signals from DHW, System, and Outdoor Air sensors to a tekmar BTC_II for Outdoor Reset and DHW functions. • Supports external input (0-10 VDC or 4-20 mA) from an Energy Management System • Controls up to three relays for auxiliary functions. • Controls the gas ignition sequence in response to heating demand • Rate sensor input for processing flow rates • Modulation of firing rate using combustion blower speed control, providing a PWM output or a 4-20 mA signal. • Closed-loop control of blower speed (RPM) through tachometer signal monitoring • Optional support for two-stage blowers by re-assigning an auxiliary relay • Low-voltage detection and safe shutdown below 18.0VAC supply input • Hot Surface or Direct Spark Ignition (also allows for external HV transformer) • Intermittent Pilot Ignition (single stage only) • Fail-safe Control for one or two stages of gas valves • 24 VAC or Isolated Contact Gas Valve operation • Five safety switch inputs for monitoring and diagnostics • Optional automatic reset after ignition lockout (one hour or as defined) • Safe-Start and full-time Flame sensing • Local (through the HSI or DSI element) or Remote Flame sensing • Configurable as needed to meet CSD-1 applications • System and Control Diagnostics through use of on-board or remote LED • Communication of Diagnostic status through RS485 • Manual Reset for Ignition Lockout or Hi-Limit (on-board or remote) • Field Test capability • Dry contact relay output for Alarm and Alert conditions • Capability of dual PIM operation to support up to 4 gas valve stages using a master/member configuration AGENCY APPROVALS CSA Design certified to ANSI Z21.20, CAN/CSA C22.2 No. 199-M99 F-35-1000 1-3 January 2016 Product Overview and Description 1-6 REFERENCE DOCUMENTS The PIM complies with the documents listed below and any applicable materials referenced in the documents listed. Table 1-1. Reference Documentation Document Number Name ANSI Z21.20-2005 Thermostats and Automatic Gas Ignition Systems and Components CAN C22.2 #199 Combustion Safety Controls and Solid State Igniters for Gas and Oil Burning Equipment UL 372 Primary safety Controls for Gas and Oil Fire Appliances (Harmonized version) UL 1998 Software in Programmable Components, 2nd edition UL 353 Limit Controls ASME CSD-1-2009 Requirements CF-200, CF-300 and CW-400 1-7 SPECIFICATIONS Table 1-2. Specifications Specification Value Input Power Control: 18-30 VAC 50/60 Hz (Class 2 Transformer) Input Current Drain 400 mA @ 24 VAC with gas and blower relays energized (Control only) Gas Valve Relays 5.0A max (continuous) Combustion Blower 5.0 A max for standard (J2) connection 15.0 A max for heavy-duty (K5 relay) terminals Hot Surface Igniter 5.0 A max, 120/240 VAC Auxiliary Relays 5.0 A max (continuous) Alarm Relay 2.0 A, 30 VDC or 30 VAC max Operating Temperature -40°F to + 165°F (-40°C to +74°C) Storage Temperature -40°F to + 185°F (-40°C to +85°C) Sensor Temperature Range -22°F to + 260°F (-30°C to +126°C) Flame Sensitivity 0.7 μA minimum Flame Failure Response or Reignition Time 0.8 seconds minimum Types of Gas Natural, LP, or manufactured Spark Rate Remote sense (50/60 Hz) Local sense (25/30 Hz) Size (LxWxH) 8.50 x 6.50 x 2.50 inches (21.59 x 16.51 x 6.35 cm) Moisture Resistance Conformal coated to operate non-condensing to 95% R.H. Tries for Ignition One or three try versions available Trial for Ignition Period 1 to 30 seconds, up to 300 seconds (IP) Pre-purge Timings 1 to 255 seconds Inter-purge Timings 1 to 255 seconds January 2016 1-4 F-35-1000 PIM Features CHAPTER 2 PIM FEATURES 2-1 CONTROL POWER The PIM requires 24 VAC to operate its microprocessor circuits, the safety switch connections, and the field demand inputs. An onboard fuse protects the 24 VAC circuits and the 24 VAC relay outputs to the gas valves. 2-2 WIRING CONNECTIONS The PIM is designed for simplified wiring and acts as the central wiring point of a system. All OEM factory connections are through unique multi-pin connectors to prevent mis-wiring. Field connections for sensors, communications, EMS, and thermostats are provided by screwterminal blocks. These may be fixed or pluggable types. A RJ-45 style connector is used for the BTC_II or system-level controller. 2-3 IGNITION OUTPUTS The PIM is capable of DSI, IP, or HSI ignition depending on configuration. For spark ignition (DSI or IP) the electrode is connected to the ignition coil. For HSI the igniter element connects to P1 and is driven off the L1 supply voltage. If configured, an external spark ignition transformer can be used by connecting it to P1. It is powered by L1 and the spark output will be disabled. 2-4 GAS VALVE OPTIONS The PIM is able to control one or two stage valves. It can also control a modulating valve using PWM or 4-20mA output. If the optional isolated valve configuration is used, the valve power and return must be separately supplied and the valve outputs are not protected by the fuse. 2-5 COMBUSTION BLOWER The blower motor operates off the power supplied to L1, which can be 120VAC or 240VAC. If a modulating blower is used, PWM or 4-20 mA signals are provided by the PIM for speed control. The blower motor tachometer signal is required when configured for closed-loop fan speed control. 2-6 HIGH-CURRENT BLOWER OPTION With this option, the relay contacts of K5 must be used to connect the blower. The QC drycontact terminals on top of the relay are used for the blower output and supply voltage, which may be 120VAC or 240VAC. The maximum current rating is 15.0A. 2-7 AUXILIARY RELAY OUTPUTS Three additional relay outputs provide capability for integrating appliance functions into the PIM. They may be operated off 120VAC or 240VAC. Two relays are sourced from L1, while the third relay is powered by L1-S, providing isolated contacts if needed. F-35-1000 2-1 January 2016 PIM Features 2-8 UL353 HIGH LIMIT SENSOR The PIM requires two thermistor sensors for burner firing rate control and high-limit sensing using the integrated UL353 high-limit function. These two thermistors may be independent but co-located so they provide similar readings. 2-9 TEMPERATURE SENSORS The PIM provides standard support for up to seven 10K ohm @ 77°F NTC curve J Thermistor probes (β=3892). Special models may support other sensor types as required by the specific application. Four temperature sensors are directly processed by the PIM. For hydronics applications, the optional System, Outdoor, and DHW tank sensors are also connected to the PIM but passed through to the BTC_II which is required to provide those additional features. 2-10 DEMAND INPUTS The PIM supports two demand inputs which can initiate heating cycles. These may be used for two-stage thermostats or space heating and domestic hot water (DHW) calls in a hydronics application. The 24VAC source for the demand inputs is supplied by the PIM. 2-11 SAFETY INPUTS Four switch-closure safety inputs are provided sourced by the 24VAC control supply voltage. One is dedicated for airflow proving and the others can be used for gas pressures, waterflow, dampers, blocked drains, LWCO, interlocks, etc. One of the safety inputs is on the field connections and the others on the factory wiring. Two of the inputs can accept either normally open or normally closed switches for additional flexibility. 2-12 RATE INPUTS The PIM can accept two rate-based signals. Usually one of these is RPM from the blower tachometer. The other rate input can be waterflow, airflow, or as needed by the specific application. 2-13 TEMPERATURE CONTROL The PIM calculates the required firing rate or stage demand using a PID-based algorithm. This algorithm uses the sensor inputs and the target setpoint from the onboard potentiometer or as communicated through RS485. The PIM is also able to respond directly to firing rate commands from the BTC_II or other system control and the EMS analog input. 2-14 POTENTIOMETER (SETPOINT) The PIM’s integrated potentiometer allows assignment of a user setpoint. Examples are the operating setpoint, economizer setpoint, or as required by a particular application. 2-15 CONFIGURATION (DIP SWITCH SETTINGS) The PIM includes an 8-position DIP switch, located near the field wiring terminals. This DIP switch allows the setting of field configurable items during installation or modification. January 2016 2-2 F-35-1000 PIM Features 2-16 ID CARD The PIM determines its operating parameters by reading the identification code of an external plug-in ID card. Note: This ID card must be present for the PIM and appliance to operate. A total of up to 126 unique codes are supported. This card selects the proper settings in the PIM's memory for various appliance models. These parameters include ignition timings and operation, system configuration, and OEM configuration settings. Appendix B details the parameters that are configurable for each unique ID code. Fenwal supplies the PIM with its internal ID card settings blank. The first time a PIM is poweredup attached to an ID card, the PIM stores the ID card setting in non-volatile memory. Once set, the PIM only operates with the correct ID card installed that matches the PIM’s internal ID settings. The PIM verifies the ID card at power-up and on each heating cycle. F-35-1000 2-3 January 2016 PIM Features THIS PAGE INTENTIONALLY LEFT BLANK. January 2016 2-4 F-35-1000 Hydronics Functions CHAPTER 3 HYDRONICS FUNCTIONS 3-1 OUTDOOR RESET If an optional outdoor sensor is connected to the PIM, the BTC_II control will optimize the target setpoint for energy efficiency based on the outdoor reset curve settings. 3-2 DOMESTIC HOT WATER CONTROL When the DHW call for heat is active, the PIM communicates this to the BTC_II. The BTC_II calculates the optimal operation and sends the firing rate and pump output requests to the PIM so it can activate the DHW pump and Boiler pump if needed. If an optional DHW sensor is connected to J2-1 and J2-2 the PIM will pass this signal to the BTC_II. This allows the BTC_II to optimize the DHW demand to maintain the DHW setpoint. The DHW thermostat switch closure is not required when using the DHW sensor. If a BTC_II is not present the PIM shall activate the DHW pump whenever the DHW call is active. The Boiler pump may also be activated based on the DHW piping configuration setting. 3-3 PUMP CONTROL The PIM supports direct control of the boiler, system and DHW pumps including optimization when a BTC_II is connected. The boiler pump and the optional system pump will run whenever there is a demand for space heating. The DHW pump will run whenever there is a DHW demand. Depending on the system configuration and DHW piping, the boiler pump may be required to turn off during DHW pump operation. Pump Postpurge is controlled by the BTC_II or uses fixed timings in stand-alone mode. Pump Exercising will cycle the pumps for 10 seconds every 72 hours, even with no heat demand, to help extend the life of the pumps. 3-4 FREEZE PROTECTION Freeze protection automatically provides the pump enable commands and/or boiler firing rate to prevent freezing. F-35-1000 • If either the Outlet or Inlet temperature drops below 45°F, the Boiler and System pumps shall be enabled. The pumps shall be turned off when both the Inlet and Outlet temperatures rise above 50°F. • If either the Outlet or Inlet temperature drops below 38°F, the Burner shall start at the minimum firing rate. The Burner cycle will terminate when both the Inlet and Outlet temperatures rise above 42°F. 3-1 January 2016 Hydronics Functions THIS PAGE INTENTIONALLY LEFT BLANK. January 2016 3-2 F-35-1000 Communications and Diagnostics CHAPTER 4 COMMUNICATIONS AND DIAGNOSTICS 4-1 RS485 COMMUNICATIONS The PIM supports serial RS485 communications to a system-level control, network, PC monitoring tool, or second PIM. The messaging software can be customized by Fenwal as needed for the OEM's particular application. For hydronics applications the PIM supports the Ft-bus protocol to communicate directly with the tekmar BTC_II system control. 4-2 ENERGY MANAGEMENT SYSTEM (CUSTOMER PROVIDED) An external EMS system can provide direct control of the PIM through the analog 0-10 VDC input. This is enabled through the DIP switch. When active, the PIM internal commands for firing rate will be ignored. Once a valid call for heat is detected on the Analog EMS input, the PIM will operate to maintain a target temperature or accept a direct drive demand request as determined by the system configuration. The PIM normally expects the signal on the analog EMS input to be 0-10VDC. For flexibility, the PIM can also accept a 4-20mA EMS input provided a 500Ω, 1/2W resistor is placed across the EMS terminals. 4-3 INDICATORS The PIM has three LED indicators to display operational status and to help diagnose system error conditions. 4-4 • Power: Green LED indicating the PIM module is receiving 24 VAC power. • Alarm/Test: Amber LED which indicates the PIM is in Commission Test Mode or that a diagnostic alarm (fault) is present. • Diagnostic Code: Red LED that is normally off. During a control or system fault condition, this LED flashes the error codes. SELF-CHECK/CONTROL FAILURE The PIM confirms the integrity of the gas valve relay contacts to insure safety. It also monitors the processor memory and software execution for proper program flow. If the control detects an error in its software or hardware, all outputs are turned off and the LED displays a steady ON condition. If this condition persists after an attempt to restart then the control must be replaced. 4-5 SYSTEM SAFETY CHECKS The PIM monitors the safety switches, temperature sensors, supply voltage, and blower speed and will go to soft lockout until the error condition is corrected. Individual LED diagnostic codes or messages on the RS485 communications help identify the problem for efficient troubleshooting. F-35-1000 4-1 January 2016 Communications and Diagnostics 4-6 FLAME CURRENT MEASUREMENTS The PIM supports direct measurement of flame signal strength using the flame current test pins (FC+,FC-) on connector P2. Flame current may be measured by a micro-ammeter, or alternately by using a standard digital voltmeter. The signal on P2 is calibrated to 1 microamp/volt, so flame current in micro-amps can be directly read on the volts scale. If a user interface control is connected an approximation of flame current can be displayed, with an upper limit of 5 micro-amps. 4-7 NON-VOLATILE LOCKOUT/MANUAL RESET The PIM normally allows for volatile ignition lockout where a lockout condition is reset by a loss in 24VAC power or the call for heat demand. In certain applications or where required by standards (such a CSD-1), it can be configured through the parameter settings for non-volatile lockout after ignition failure. In this case the lockout may only be reset by the on-board manual reset button, or the remote reset input. If the UL353 High Limit feature is used, any high limit fault will go to non-volatile lockout requiring a manual reset. January 2016 4-2 F-35-1000 Application Examples CHAPTER 5 APPLICATION EXAMPLES 5-1 APPLICATION EXAMPLES Figure 5-1, Figure 5-2, and Figure 5-3 illustrate standard configurations for the PIM. 5-1.1 High Efficiency Modulating Boiler DHW TH Thermostat Flow Switch LWCO Alarm FT-Bus A FT-Bus B tN4 + EMS - 0-10 VDC Remote Reset Outdoor Sensor DHW Sensor System Sensor Complete control of a modulating-condensing boiler including direct spark ignition, firing rate, outlet water temperature, high limit shutdown, domestic hot water priority, system safety inputs, outdoor reset, and LWCO. Efficiency optimized through communications with an energy management system, boiler temperature control, and thermostat network. The boiler temperature control monitors all system information to calculate burner firing rate. Integrated control of boiler, system, and DHW pumps provides intelligent pump purging, residual heat capture, and freeze protection. Boiler Temperature Control 1 J4 J3 2nd PIM FT-Bus B FT-Bus A 1 V+ 1 V in GND 2 9 1 J2 10 J1 R91 J5 2 Operator Set Point PIM Identity Card SW2 J6 Limit 3 Field Setting DIP Switch High Limit Sensor SW1 1 2 J7 3 Reset 4 Outlet Sensor Air Flow Safety #2 4 1 5 2 6 3 J8 To J10 Pin 3 To J10 Pin 4 Flow Sensor Tachometer Safety #1 Inlet Sensor 3 1 4 2 Fan Power (18 VDC) PWR D23 Alarm D80 Diag J15 Remote LED F1 J9 Vent Sensor 4 to 20 MA 5 1 Fan GND 6 2 Flow SEN GND 7 3 Flow SEN PW (12 VDC) 8 4 T3 J10 Spark Electrode PWM-Out L1 2 1 4 1 5 2 6 3 3 1 4 2 5 1 6 2 7 3 8 4 J11 24 VAC 120 VAC RTN 2 STG / MV Dry Contact Hot MV / PV T2 J12 120 VAC Blower L1 – S DHW Pump System Pump J13 J14 FS 120 VAC P2 GND FCFC+ L2 D90 Boiler Pump Remote Flame Sense Rod Figure 5-1. High Efficiency Modulating Boiler F-35-1000 5-1 January 2016 Application Examples 5-1.2 HVAC Space Heater 1 J4 J3 RS485 Communications PC Based Development Tool 1 9 Ventilate Remote Reset Thermostat 1 J2 10 J1 R91 J5 2 Damper End Switch Interlock Alarm + EMS - 0-10 VDC Complete system operation including proven hot surface ignition, modulating blower, discharge air temperature control, high limit shutdown, economizer mode, selectable purge times, freeze protection, and ventilation. The PIM uses its internal PID algorithm to calculate optimum firing rate. Integrated control of circulation fan, power exhaust, and vent damper allows intelligent response to any input condition and combines several existing controls into a single intelligent solution. Econ Set Point PIM Identity Card V+ 1 V in GND 2 SW2 J6 Limit 3 Field Setting DIP Switch High Limit Sensor SW1 1 2 J7 3 Reset 4 Discharge Sensor Air Flow Change Filter Inlet Sensor (OAT) 4 1 5 2 6 3 3 1 4 2 Fan Power (18 VDC) 5 1 Fan GND 6 2 7 3 8 4 RPM J8 D90 PWR D23 Alarm D80 Diag J15 Remote LED F1 J9 J10 PWM-Out L1 L2 2 1 4 1 5 2 6 3 5 1 6 2 7 3 8 4 J11 24 VAC 120 VAC RTN Dry Contact Gas Valve T2 J12 High Current Blower Hot L1 Comb. Blower GND L1 – S Power Exhaust Circ. Blower J14 FS 120 VAC P2 GND S1 24 VAC RETURN S2 24 VAC FCFC+ L2 Vent Damper Hot Surface Ignitor Remote Flame Sense Rod Figure 5-2. HVAC Space Heater January 2016 5-2 F-35-1000 Application Examples 5-1.3 Commercial Cooking Cooking Computer 1 J4 J3 RS485 Communications Network 1 9 2nd Stage 1 J2 10 J1 R91 J5 2 Thermostat Interlock Alarm Intelligent operation of advanced fryer including intermittent pilot ignition, two speed PWM blower, and high limit shutdown. Fixed firing rate control using the two heating demand inputs. Smart ramping of blower speed to smoothly control burner after light-off and allow fat melt cycles. Optional communication to a cooking computer or user interface. Three available relay outputs for integrating auxiliary functions. Operator Set Point PIM Identity Card V+ 1 V in GND 2 SW2 J6 Limit 3 Field Setting DIP Switch High Limit Sensor SW1 1 2 J7 3 Reset 4 Temp Sensor Air Flow Safety #2 4 1 5 2 6 3 J8 Safety #1 3 1 4 2 Fan Power (18 VDC) 5 1 Fan GND 6 2 7 3 8 4 RPM J10 MV PV Blower Relay #1 Relay #2 Diag J15 Remote LED 2 1 4 1 5 2 6 3 3 1 4 2 5 1 6 2 7 3 8 4 J11 Local Sense T2 J12 J13 J14 FS 120 VAC P2 GND FCFC+ L1 – S Alarm D80 Spark Electrode L2 Dry Contact D23 T3 24 VAC 120 VAC PWR F1 J9 PWM-Out L1 D90 Relay #3 Figure 5-3. Commercial Cooking F-35-1000 5-3 January 2016 Application Examples THIS PAGE INTENTIONALLY LEFT BLANK. January 2016 5-4 F-35-1000 APPENDIX A APPLICATION WORKSHEET A-1 FACTORY LOW-VOLTAGE CONNECTIONS (30 VAC MAX) Connector J5 Input/Output RS485 Communications (PIM to PIM) J6 ID Card J7 J7 Hi-Limit Sensor Outlet Temp Sensor J8 J8 J8 Airflow switch Safety #1 switch Safety #2 switch J9 J9 Temp Sensor #1 Temp Sensor #2 J10 J10 J10 J10 4-20 mA Out (modulation %) PWM Out (modulation %) Rate Sensor Signal Tachometer Signal (RPM) J11 24VAC Power (R) A-2 F-35-1000 Assigned Function FACTORY LINE-VOLTAGE CONNECTIONS Connector J12 J12 Input/Output Gas Valve (MV/PV) 2nd stage Valve J13 J13 Blower Output L1 supply input J14 J14 J14 J14 J14 AUX Relay #1 AUX Relay #2 AUX Relay #3 (Isolated) L1s – Relay #3 Supply Power L1 Supply Power Assigned Function A-1 January 2016 A-3 LOW-VOLTAGE FIELD WIRING CONNECTIONS (30 VAC MAX) Connector J4 Input/Output FT-bus Connection to tekmar J3 RS-485 Communications J2 J2 J2 J2 J2 Temp Sensor #3 Temp Sensor #4 Temp Sensor #5 tN4 Communications 0-10Vdc Analog EMS Input J1 J1 J1 J1 J1 J1 Alarm Relay (Dry Contacts) Interlock (LWCO) Remote Reset Safety #3 Switch DHW or 2nd Stage Call Heat Call (TH) A-4 Assigned Function HARDWARE CONFIGURATION PIM Configuration Ignition Type (DSI, HSI, IP, or PHSI) Valve Type (1 stage, 2 stage, or Modulating) Isolated Valve Contacts (Yes or No) Blower Type (1 stage, 2 stage, or Modulating) High-Current Blower Relay (Yes or No) Flame Sense Method (Local, Remote, or Both) Field Terminals (Fixed or Pluggable) January 2016 Selected Option A-2 F-35-1000 APPENDIX B PIM PARAMETER DESCRIPTIONS B-1 PIM PARAMETERS The following tables list the parameters available for the PIM™. Name Description Allowed Range Ignition Settings Type Ignition Type DSI, HSI, Proven HSI, IP Ext_Spark External spark transformer Yes or No TFI Trial for Ignition (seconds) 1 to 300 (limit 25 if not IP) Trials Number of ignition tries 1 to 3 Heatup HSI Heat-up period (seconds) 0 to 255 HSI Current Ignitor Proving Current (amps) 0.5 to 4.0 Prepurge Ignition Prepurge (seconds) 0 to 255 Interpurge Ignition Interpurge (seconds) 0 to 255 Postpurge Blower Postpurge (seconds) 0 to 255 Sense Flame Sense Method Local or Remote Recycle/Re-ignition Flame Loss Retry Method (re-ignition N/A with HSI) Recycle or Re-ignition Lockout on Loss of Flame Locks-out on loss of flame or airflow in TFI and burn (CSD-1) Yes or No Reset Method Lockout Reset Method Volatile or Manual Automatic Reset Automatic Reset Delay after Lockout (seconds) 0 - Off 60 - 3600 (enabled) Gas Stages Number of Gas Valve Stages One Stage, Two stage, Three Stage, or Four Stage Blower Type Blower Configuration One Stage, Two-stage, Modulating, None Flame Period Ignition Flame Integration Period during Ignition and first 5 seconds after 10 to 30 (25mS periods) Flame Period Burn Flame Integration Period during Burner On Cycle 4 to 30 (25mS periods) System Settings Type Selects order of 's for Multi stage boilers Master or Member Hi-Limit Hi-Limit setpoint 100-240 (°F) Operator Safeguard Maximum allowed Operating setpoint below Hi-Limit Setting 0 to 30 (°F) Manual Differential Operator setpoint differential when Manual Differential DIP switch enabled 5 to 30 (°F) F-35-1000 B-1 January 2016 Name Tachometer Type Description Allowed Range Tach signal (pulses/revolution) 0,1,2 or 3 0 indicates Tach not present. 0 uses open loop control Temp Sensor #1 Temp Sensor #1 Present Yes or No Temp Sensor #2 Temp Sensor #2 Present Yes or No Rate Sensor Rate Sensor Present Yes or No Airflow Switch Airflow Switch Monitoring Normal, Ignore Open switch test, or Ignore All Safety #1 Input Safety Switch Input Monitoring Normally Open, Normally Closed, or Ignore Safety #2 Input Additional Safety Input Monitoring Normally Open, Normally Closed, or Ignore Safety #3 Input Additional Safety Switch Monitoring Normal, Ignore Open switch test, or Ignore All Pump Prepurge Pump Prepurge Period (seconds) 0 to 255 Pump Postpurge Pump Postpurge Period (seconds) 0 to 255 (stand-alone mode only) DHW Pump Piping Activate Boiler pump when DHW Pump is active (stand-alone only) Yes or No Boiler Configuration Settings Boiler Mass Boiler Construction (thermal mass) Low, Medium, High or Proportional Application Type Designates application settings for BTC_II to follow Boiler, Water Heater or Pool Heater Hi-Delta T Threshold Difference between outlet and inlet temperatures for Delta T limiting 20 to 200 (°F) Vent Temperature Limit Threshold setting for High Vent temperature shutdown 100 to 300 (°F) Turndown Minimum Modulation Rate (% of full fire) 5% -50% Closed Loop Modulating Blower Settings (tach required) Maximum Blower Speed Blower RPM at Maximum Modulation Rate (100% full-fire) 0 - 16000 Purge Blower Speed Blower RPM during Prepurge and Interpurge periods 0 - 16000 Light off Blower Speed Blower RPM during Ignition period 0 - 16000 Minimum Blower Speed Blower RPM at Minimum Modulation Rate (Turndown) 0 - 16000 Postpurge Blower Speed Blower RPM during Postpurge 0 - 16000 Open Loop Modulating Blower Settings Maximum PWM Rate Blower Modulation Rate (PWM output % at 100% full-fire) 0 - 100% Purge Blower Rate Modulation of Blower during Purge periods (% of full fire) 20% - 100% Light off Blower Rate Modulation of Blower during Ignition period (% of full fire) 10% - 100% Postpurge Blower Speed Modulation of Blower during Postpurge (% of full fire) 20% - 100% January 2016 B-2 F-35-1000 APPENDIX C PART NUMBER BREAKDOWN C-1 PIM PART NUMBER The following image explains the meaning of the various digits in the part number. Use this information to order the correct board. 35 – 9 X X X X X – X X X Description FLAME SENSE METHOD 0 = Local Sense 1 = Remote Sense 3 = Dual (Local and Remote) BLOWER RELAY 0 = Standard (5A) 1 = High-Current (15A) TERMINAL CONFIGURATION 0 = Standard 1 = Pluggable Field Terminal Blocks RESERVED 0 = Standard Model 0-9 = Special Feature Assignment RESERVED 0 = Standard Model 0-9 = Special Feature Assignment MODEL CONFIGURATION 0 = Standard Model 2 = CE (EN298) Standard Model 3 = CE (EN298) OEM Special Feature Model (Consult Factory for Number) 9 = OEM Special Feature Model (Consult Factory for Number) VALVE/FAN CONFIGURATION 0 = Modulating (1-stage) 1 = One Stage 2 = Two Stage 3 = Intermittent Pilot (PV/MV)* 4 = One Stage with Auxiliary 5 = Isolated Modulating (1-stage) 6 = Isolated One Stage 7 = Isolated Two Stage * Not included under scope of current CSA certification IGNITION TYPE 1 = Direct Spark 2 = Direct Spark with External Relay 6 = Hot Surface Ignition 7 = Proven Hot Surface Ignition Figure C-1. Part Number Breakdown F-35-1000 C-1 January 2016 THIS PAGE INTENTIONALLY LEFT BLANK. January 2016 C-2 F-35-1000 APPENDIX D FENWAL DEVELOPMENT TOOL D-1 FENWAL DEVELOPMENT TOOL To assist in developing and testing PIM applications Fenwal provides free development tool support using a customized software package and PC-to-PIM converter box. This allows the parameters to be modified as needed and provides visual and graphic feedback on all aspects of PIM operation and system performance. Once parameters are finalized they can be programmed into the production control and accessed by the corresponding ID card. For production versions, the parameters cannot be modified but the Development Tool can still be used to monitor and record system operation. Figure D-1. Fenwal Development Tool F-35-1000 D-1 January 2016 THIS PAGE INTENTIONALLY LEFT BLANK. January 2016 D-2 F-35-1000 Fenwal Controls is a registered trademark of Kidde-Fenwal Inc. PIM is a trademark of Kidde-Fenwal Inc. All trademarks are property of their respective owners. Kidde-Fenwal Inc. 400 Main Street Ashland, MA 01721 USA Customer Service: (508) 881-2000 Website: www.fenwal.com These instructions do not purport to cover all the details or variations in the equipment described, nor do they provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to Kidde-Fenwal, Inc., Ashland, Massachusetts. F-35-1000 Rev. AA ©2016 Kidde-Fenwal All Rights Reserved.