micom p132 - Schneider Electric Belgique

advertisement
MICOM P132
Feeder Management
and Bay Control
Version P132 -306 -415/416/417/418/419 -612 ff
Technical Data Sheet
This document does not replace the Technical Manual.
station. For the selection of the bay type the
MiCOM P132 is provided with over 80 predefined
bay types and allows download of customized bay
type.
External auxiliary devices are largely obviated
through the integration of binary inputs and power
outputs that are independent of auxiliary voltages,
by the direct connection option for current and
voltage transformers and by the comprehensive
interlocking capability. This simplifies handling of
the protection and control technology for a
switchbay from planning to commissioning.
The MiCOM P132 provides an extensive number
of functions which can select individually for
inclusion in the unit's configuration or cancel them
as desired. By means of a straight-forward
configuration procedure, the user can adapt the
device flexibly to the scope of protection required
in each particular application. Due to the powerful,
freely configurable logic of the device, special
applications can be accommodated.
Application and Scope
The unit's protection functions provide selective
short-circuit protection, ground fault protection
and overload protection in medium- and
highvoltage systems. The systems can be
operated as solidly-grounded, low-impedancegrounded, resonant-grounded or isolated-neutral
systems. The multitude of protection functions
incorporated into the unit enable the user to cover
a wide range of applications in the protection of
cable and line sections, transformers and motors.
For easy adaptation to varying system operation
conditions four independent parameter subsets
are provided.
Alternatively to the variants with CT inputs or CT
and VT inputs the MiCOM P132 is optionally
deliverable with VT inputs only to be applied as
over-/under frequency/voltage protection unit only.
The optional control functions are designed for the
control of up to three electrically operated
switchgear units equipped with electrical checkback signaling located in the bay of a mediumvoltage substation or a non-complex high-voltage
P132
with VTs
Functional overview
50 / 51 P,Q,N
DTOC
Definite-time o/c protection, three stages, phase-selective
51 P,Q,N
IDMT_1
Inverse-time o/c protection, single-stage, phase-selective
P132
P132
with CTs
with VTs
and CTs
9
9
9
9
9
9
51 P,Q,N
IDMT_2
Inverse-time o/c protection, single-stage, phase-selective
67 P,N
SCDD
Short-circuit direction determination
50
SOTF
Switch onto fault protection
9
9
9
9
85
PSIG
Protective signaling
9
79
ARC
Auto-reclosure control (3-pole)
9
25
ASC
Automatic synchronism check
67W/YN
GFDSS
Ground fault direction determination
(wattmetric/neutral admittance)
TGFD
Transient ground fault direction determination
9
(9)
9
( 9 ) 1)
37/48/49/
49LR/50S/66
MP
Motor protection
9
9
49
THERM
Thermal overload protection
9
9
46
I2>
Unbalance protection
9
9
27/59/47
V<>
Over/Undervoltage protection
9
9
81
f<>
Over/Underfrequency protection
9
9
32
P<>
Directional power protection
50BF
CBF
Circuit breaker failure protection
CBM
Circuit breaker failure monitoring
MCMOM
Measuring circuit monitoring
LIMIT
Limit value monitoring
LOGIC
Programmable logic
9
9
9
9
9
9
9
9
9
9
9
9
9
PSS
Parameter subset selection
9
9
9
DEV
Control and monitoring of up to 3 switchgear units
( 9 ) 1)
( 9 ) 1)
( 9 ) 1)
CMD_1
Single-pole commands
( 9 ) 1)
( 9 ) 1)
( 9 ) 1)
SIG_1
Single-pole signals
( 9 ) 1)
( 9 ) 1)
( 9 ) 1)
ILOCK
Interlocking logic
(9)
(9)
( 9 ) 1)
COMMx
2 comm. interfaces, IRIG-B, protection comm. interface InterMiCOM1)
(9)
(9)
(9)
IRIGB
Time synchronisation IRIG-B
(9)
(9)
(9)
IEC
IEC-61850-interface
(9)
(9)
(9)
MEASI / MEASO
2x 20 mA outputs, 20 mA input, 1 RTD input
( 9 ) 1)
( 9 ) 1)
( 9 ) 1)
MEASI
9 RTD inputs
( 9 ) 1)
( 9 ) 1)
F_KEY
Function keys
6 1)
6 1)
1)
6 1)
1)
9 = standard; ( 9 ) = order option
1)
Figure 1:
not available for P132 in 24T case
Functional overview
P132_TechnicalDataSheet_EN_12_b
2
P132-306-415/416/417/418/419-612 ff
In addition to the functions listed in figure 1, as
well as comprehensive selfmonitoring, the
following global functions are available in the
MiCOM P132:
> Fault data acquisition
> Fault recording
(time-tagged signal logging together with fault
value recording of the three phase currents 1),
the residual current 1), the three phase-toground voltages 3) and the neutral
displacement voltage 3)).
> Parameter subset selection
(4 independent parameter subsets)
> Measured operating data to support the user
during commissioning, testing and operation
> Operating data recording
(time-tagged signal logging)
> Overload data acquisition
> Overload recording
The MiCOM P132 is of modular design. The
pluggable modules are housed in a robust
aluminum case and electrically connected via an
analog and a digital bus printed circuit board.
The nominal currents or the nominal voltages,
respectively, of the measuring inputs can be set
with the help of function parameters.
The nominal voltage range of the standard optical
coupler inputs is 24 to 250 V DC without internal
switching. Optional there are also other ranges
with higher pick-up thresholds possible.
The auxiliary voltage input for the power supply is
a wide-range design as well. The nominal voltage
ranges are 48 to 250 V DC and 100 to 230 V AC.
An additional version is available for the lower
nominal voltage range of 24 V DC.
All output relays are suitable for both signals and
commands.
1)
1)
(time-tagged signal logging)
> Ground fault data acquisition
> Ground fault recording
2)
2)
(time-tagged signal logging)
> Measured fault data
1) available if MiCOM P132 is provided at least with CTs
2) available if MiCOM P132 is provided with CTs and VTs
3) available if MiCOM P132 is provided at least with VTs
Figure 2:
Function diagram
P132-306-415/416/417/418/419-612 ff
3
P132_TechnicalDataSheet_EN_12_b
The optional resistance temperature detector
(RTD) inputs are lead compensated and
balanced. The optional 0 to 20 mA input provides
open-circuit and overload monitoring, zero
suppression defined by a setting, plus the option
of linearizing the input variable via 20 adjustable
interpolation points.
Two freely selected measured signals (cyclically
updated measured operating data and stored
measured fault data) can be output as a loadindependent direct current via the two optional 0
to 20 mA outputs. The characteristics are defined
via 3 adjustable interpolation points allowing a
minimum output current (4 mA, for example) for
receiver-side open-circuit monitoring, knee-point
definition for fine scaling and a limitation to lower
nominal currents (10 mA, for example). Where
sufficient output relays are available, a freely
selected measured variable can be output in
BCD-coded form via contacts.
Control and display
> Local control panel with LC-display
> 6 function keys
(available in the 40T and 84T case)
> 23 LED indicators, 18 of which allow freely
configurable function assignment for red,
green or yellow visualization.
(in the 24T case there are 10 unicoloured LED
indicators available for this functions).
> PC interface
> Communication interfaces (optional)
> IRIG-B signal input (optional)
> Protection communication interface
InterMiCOM (optional)
Function keys
(available in 40T and 84T case)
The MiCOM P132 has six freely configurable
function keys. A single function can be assigned
to each function key. So circuit breakers and
functions can be switched on or off and recorded
information can be reseted directly via function
key.
Instead of a single function, a menu jump lists with
up to 16 elements can be assigned. Setting
parameters, event counters and/or event records
can be selected into a menu list. Repeated
pressing of the relevant function key will then
sequentially trigger the element of the selected
menu jump list.
For each function key, the user can define an
operating mode suitable to the assigned
functionality. To guard against inadvertent or
unauthorized use each function key is protected
with a password.
Figure 3:
MiCOM P132 in 24T, 40T and 84T cases
P132_TechnicalDataSheet_EN_12_b
4
P132-306-415/416/417/418/419-612 ff
Detachable HMI
(available in 40T and 84T case)
Information interfaces
(optional)
For remote mounting in switch gears the MiCOM
P132 can be equipped with a detachable HMI.
This design has the advantage of a comfortable
device handling even in switch gears with
protection arrangements difficult to access.
Information exchange is done via the local control
panel, the PC interface and 2 optional
communication interfaces.
The first communication interface has settable
protocols conforming to IEC 60870-5-103,
IEC 60870-5-101, DNP 3.0, Modbus and Courier
(COMM1) or provides alternatively protocol
conforming to IEC 61850 (IEC). It’s intended for
integration in substation control systems.
The 2nd communication interface (COMM2)
conforms to IEC 60870-5-103 and is intended for
remote setting access only.
Clock synchronization can be achieved using one
of the protocols or using the IRIG-B signal input.
Additionally, the optional InterMiCOM interface
(COMM 3) allows a direct transfer of any digital
status information between two devices.
Figure 4:
Detachable HMI in a medium voltage
switchgear
The design of the protection device MiCOM P132
allows a connection or disconnection to the
detachable HMI at any time. The HMI hardware
module will be completely and automatically
recognized.
The visualisation of the device status is done via
the display of the HMI and via 4 LED`s at the
basic device.
Even if the detachable HMI is lacking all device
functions are completely warranted. With a
connected HMI the PC-interface of the device
cannot be enabled.
To connect the basic device and the detachable
HMI standardised cable (Ethernet cable, max.
length 10 m) can be used. One connection cable
of three meter length is included in the
MiCOM P132 scope of delivery.
Figure 5:
Basic device with detachable HMI
P132-306-415/416/417/418/419-612 ff
5
P132_TechnicalDataSheet_EN_12_b
Main Functions
Inverse-Time Overcurrent Protection
Main functions are autonomous function groups
and can be individually configured or disabled to
suit a particular application. Function groups that
are not required and have been disabled by the
user are masked completely (except for the
configuration parameter) and functional support is
withdrawn from such groups.
This concept permits an extensive scope of
functions and universal application of the device
in a single design version, while at the same time
providing for a clear and straight-forward setting
procedure and adaptation to the protection and
control task under consideration.
For the inverse-time overcurrent protection the
three phase currents, residual current and
negative-sequence current determined from the
filtered fundamental wave of the three phase
currents are evaluated in separate, single stage
measuring systems. For the residual current stage
the use of the residual current measured directly
or calculated from the three phase currents is
offered for selection.
The effect on the general starting signal of the
stages measuring in the residual path and in the
negative-sequence system, respectively, can be
suppressed if desired.
For the individual measuring systems, the user
can select from a multitude of tripping
characteristics (see figure 6).
Definite-Time Overcurrent Protection
Definite-time overcurrent protection is provided
for the three phase currents and the negativesequence current with three timer stages and for
the residual current with four timer stages. For the
first three residual current stages the use of the
residual current measured directly or calculated
from the three phase currents is offered for
selection. For the fourth residual current stage with extended setting range - the calculated
residual current is always used. The residual and
negative-sequence currents stages affect the
general starting signal. This effect can be
suppressed if desired.
Starting of the phase current stage I> and the
negative-sequence current stage Ineg> can be
stabilized under inrush conditions if desired. The
ratio of the second harmonic component of the
phase currents to the fundamental wave serves
as the criterion. This stabilization is either phaseselective or effective across all three phases
depending on the chosen setting. The negativesequence current stage Ineg> is subject to all
phase current stabilizations. The phase current
stages I>> and I>>> and the negative-sequence
current stages Ineg>> and Ineg>>> are never
affected by this stabilization procedure.
Intermittent startings of the residual current stage
IN> can be accumulated over time by means of a
settable hold time. If the accumulated starting
times reach the trip limit value (which is also
adjustable by setting) then a trip with selective
signaling ensues.
Additionally, the operate values of all overcurrent
stages can be set as dynamic parameters. For a
settable hold time, switching to the dynamic
operate values can be done via an external
signal. Once the hold time has elapsed, the static
operate values are reinstated.
P132_TechnicalDataSheet_EN_12_b
No.
Tripping time chraracteristic
(k= 0.05 … 10.00)
Constants and formulae (t in s)
A
B
C
0
Definite Time
1
Normally inverse
0.14000
0.02000
2
Very inverse
13.50000
1.00000
3
Extremely inverse
80.00000
2.00000
4
Long time inverse
120.00000
1.00000
per ANSI / IEEE C37.112
Trip
5
Moderately inverse
6
Very inverse
7
Extremly inverse
t
=
R
k
per IEC 255-3
per ANSI
A
⎛ I ⎞
⎜⎜
⎟⎟
⎝ IB ⎠
B
−1
Release
0.05150
0.02000
0.11400
4.85000
19.61000
2.00000
0.49100
21.60000
28.20000
2.00000
0.12170
Trip
29.10000
Release
8
Normally inverse
8.93410
2.09380
0.17966
9
Short time inverse
0.26630
1.29690
0.03393
0.50000
10
Long time inverse
5.61430
1.00000
2.18592
15.75000
⎛
⎜
⎜
t = k ⋅⎜
⎜⎛ I
⎜ ⎜⎜
⎝ ⎝ I ref
not per standard
11
RI-type inverse
12
RXIDG-type inverse
Figure 6:
t = k ⋅
A
⎞
⎟⎟
⎠
B
⎞
⎟
⎟
−C ⎟ tr = k ⋅
⎟
⎛ I
−1
⎟
⎜⎜ I
⎝ ref
⎠
9.00000
R
⎞
⎟⎟
⎠
B
−1
1
0 . 339 −
not per standard
6
t = k ⋅
0 . 236
⎛ I ⎞
⎜⎜ I
⎟⎟
⎝ ref ⎠
⎛
I
t = k ⋅ ⎜⎜ 5 . 8 − 1 . 35 ⋅ ln
I ref
⎝
⎞
⎟⎟
⎠
Tripping time characteristics of Inverse-Time
Overcurrent Protection
P132-306-415/416/417/418/419-612 ff
Starting of the phase current stage and the
negative-sequence current stage can be
stabilized under inrush conditions if desired. The
ratio of the second harmonic component of the
phase currents to the fundamental wave serves
as the criterion. This stabilization is either phaseselective or effective across all three phases
depending on the chosen setting. The negativesequence current stage is subject to all phase
current stabilizations.
Intermittent startings of the phase, negativesequence or residual current stage can be
accumulated on the basis of the set tripping
characteristic by means of a settable hold time.
Tripping is also performed in accordance with the
relevant tripping characteristic.
Additionally, the operate values of all overcurrent
stages can be set as dynamic parameters. For a
settable hold time, switching to the dynamic
operate values can be done via an external
signal. Once the hold time has elapsed, the static
operate values are reinstated.
Meas. Starting
P
G
Variables selected for measurement
I meas Vmeas
system
Characteristic
angle αP or αN
A
IA
V BC = V BN - V CN
+45°
B
IB
V CA = V CN - V AN
+45°
C
IC
V AB = V AN - V BN
+45°
A-B
IA
V BC = V BN - V CN
+60°
B-C
IC
V AB = V AN - V BN
+30°
C-A
IC
V AB = V AN - V BN
+60°
A-B-C
IC
V AB = V AN - V BN
+45°
GF
IN
V NG =
-90°...+90°
1/3 · (VAN+VBN+VCN) (adjustable)
I meas
Forward decision
V meas
(reference var.)
Backward decision
Short-Circuit Direction Determination
Due to the short-circuit direction determination
function, the MiCOM P132 can be used as a
directional time-overcurrent protection device. For
the individual overcurrent timer stages the user
may select whether the stage shall be forwarddirectional, backward-directional or nondirectional. Direction determination is performed
in separate measuring systems for the phase
current and residual current timer stages,
respectively.
In the direction-measuring system for the phase
current timer stages, the phase-to-phase voltage
opposite to the selected phase current is used for
direction determination as a function of the type of
fault, and an optimum characteristic angle is
employed (see figure 7).
P132-306-415/416/417/418/419-612 ff
Figure 7:
Directional charakteristics in Short-Circuit
Direction Determination
A voltage memory is integrated to provide the
required voltage data for direction determination
in the event of 3-pole faults with a large 3-phase
voltage drop.
In the direction measuring system for the residual
current timer stages, direction is determined using
the internally computed neutral displacement
voltage; the characteristic angle is adjustable
taking account of the various neutral-point
treatments in the system. The direction measuring
system for the residual current timer stages is not
enabled until a set value for neutral displacement
voltage is exceeded. The user may select whether
the triggering pre-orientation for a non-enabled
direction measuring system for residual current
timer stages shall be blocked in the event of
phase current starting.
7
P132_TechnicalDataSheet_EN_12_b
Protective Signaling
Auto-Reclosing Control
Protective signaling can be used in conjunction
with short-circuit direction determination. For this
purpose the protection devices must be suitably
connected by pilot wires or the optional protection
interface InterMiCOM on both ends of the line
section to be protected. The user may select
whether teleprotection will be controlled by the
direction measuring system of the phase current
timer stages only, by the direction measuring
system of the residual current timer stages only,
or by the direction measuring systems of the
phase current and residual current timer stages.
For protection devices on the infeed side of radial
networks, teleprotection can also be controlled
without the short-circuit direction determination
function.
The auto-reclosing control operates in threephase mode. ARC cycles with one high-speed
reclosing (HSR) and multiple (up to nine)
subsequent time-delay reclosing (TDR) may be
configured by the user. Reclosing cycles without
prior HSR are possible. For special applications,
tripping prior to an HSR or TDR can be delayed.
HSR and TDR reclosings are counted and
signaled separately. A test HSR can be triggered
via any of the unit's interfaces.
Automatic Synchronism Check
(optional)
This function can be used in conjunction with
automatic or manual (re)closure or close
command of the optional control functions. In nonradial networks this ensures that reclosure or
close command will proceed only if the
synchronism conditions are met.
For the control functions a second mode with a
decoupled operation of the automatic
synchronism check and close command is
available.
Protection Interface InterMiCOM
(optional)
InterMiCOM allows high performance permissive
and blocking type unit protection to be configured,
plus transfer of any digital status information
between line ends. Intertripping is supported too,
with channel health monitoring and cyclic
redundancy checks (CRC) on the received data
for maximum message security.
InterMiCOM provides eight end-end signal bits,
assignable to any function within a MiCOM relay’s
programmable logic.
Default failsafe states can be set in case of
channel outage.
Over-/Underfrequency Protection
Over-/underfrequency protection has four stages.
Each of these can be operated in one of the
following modes:
> Over-/underfrequency monitoring
> Over-/underfrequency monitoring combined
with differential frequency gradient monitoring
(df/dt) for system decoupling applications
Switch on to Fault Protection
> Over-/underfrequency monitoring combined
Closing of a circuit breaker might inadvertently
lead to a short-circuit fault due to a feeder
grounding connection not yet removed, for
example.
The function ‘switch on to fault protection’
provides for an undelayed protective tripping
during a settable time after a manual close
command has been issued.
Depending on the operating mode, either a trip
command with initialization of the general starting
or a phase overcurrent stage results.
P132_TechnicalDataSheet_EN_12_b
with medium frequency gradient monitoring
(Δf/Δt) for load shedding applications
8
P132-306-415/416/417/418/419-612 ff
Over-/Undervoltage Protection
Circuit Breaker Monitoring
The over-/undervoltage-time protection function
evaluates the fundamental wave of the phase
voltages and of the neutral displacement voltage
as well as the positive-sequence voltage and
negative-sequence voltage obtained from the
fundamental wave of the three phase-to-ground
voltages. Two definite-time-delay overvoltage
stages each are provided for evaluation of the
neutral displacement voltage and negativesequence voltage. Two additional definite-timedelay undervoltage stages each are provided for
evaluation of the phase voltages and the positivesequence voltage. As an option, a minimum
current level can be specified to enable the
undervoltage stages.
Evaluation of the phase voltages can be
performed using either the phase-to-phase
voltages or the phase-to-ground voltages as
desired. For evaluating the neutral displacement
voltage, the user may choose between the neutral
displacement voltage formed internally from the
three phase-to-ground voltages and the neutral
displacement voltage formed externally (from the
open delta winding of the voltage transformer, for
example) via the fourth voltage measuring input.
This function provides the user with several
criteria for the assessment of circuit breaker wear:
> Calculated number of remaining operations
based on the CB wear curve (see figure 8)
> Mechanical operations count
> Accumulation of the Interrupted currents sum
(linear and squared)
> Accumulated current-time integrals of trips
Number of permissible CB operations
For each of these criteria, a signaling threshold
can be set by the user.
Directional Power Protection
The directional power protection monitors
exceeding the active and reactive power limit, a
power drop and the reversal of direction at
unsymmetrically operated lines. Evaluation of the
power is performed using the fundamental wave
of the phase currents and of the phase-to-ground
voltages.
Figure 8:
This function can be blocked for testing purposes.
The measuring values of the last circuit breaker
operations are resettable.
Also the measurands and the counters of the
circuit breaker monitoring can be resetted if the
concerned circuit breaker was changed.
Circuit Breaker Failure Protection
With either the internal or an external trip
command, two timer stages are started for the
monitoring of the circuit breaker action. If the first
timer elapses while the fundamental of the current
stays above a settable threshold, a 'circuit breaker
failure' condition is determined and a re-trip
command (e.g. to the 2nd breaker trip coil) can be
issued.
Upon elapsing of the 2nd timer stage, a back-trip
command can be issued to trip the upstream
breaker.
The input of a 'circuit breaker failure' signal via an
appropriately configured binary input while the
general starting persists, effects an undelayed trip
command.
P132-306-415/416/417/418/419-612 ff
Circuit breaker wear curve
9
P132_TechnicalDataSheet_EN_12_b
Thermal Overload Protection
Using this function, thermal overload protection
for lines, transformers and stator windings of h.v.
motors can be realized. The highest of the three
phase currents serves to track a first-order
thermal replica according to IEC 255-8.
The tripping time is determined by the set thermal
time constant τ of the protected object and the set
tripping level Δϑtrip and depends on the
accumulated thermal load Δϑ0:
Motor Protection
For the protection of directly switched h.v.
induction motors with thermally critical rotor, the
following specially matched protection functions
are provided:
> Recognition of operating mode
> Rotor overload protection using a thermal
motor replica
> Choice of reciprocally quadratic or logarithmic
tripping characteristic
> Inclusion of heat dispersion processes in the
rotor after several startups
> Separate cooling periods for rotating and
stopped motors
> Startup repetition monitoring with reclosure
The temperature of the cooling medium can be
taken into account in the thermical replica using
the optional resistance temperature inputs or the
0 to 20 mA input. Additionally a second input
could be defined as a back-up in case of failure of
the main 0 to 20 mA input.
The user has a choice of using a thermal replica
on the basis of either relative or absolute
temperature.
A warning signal can be issued in accordance
with the set warning level Δϑwarning. As an
alternative method of generating a warning, the
cyclically updated measured operating value of
the predicted time remaining before tripping is
monitored to check whether it is falling below a
set threshold.
blocking (see figure 9)
> Control logic for heavy starting and protection
of locked rotor
> Loss of load protection
Using the optional resistance temperature
detector inputs direct monitoring of the
temperature of the stator windings and the
bearings can be realized (see figure 10).
Overload memory
100
m in %
80
60
Unbalance Protection
40
The negative-sequence current is determined
from the filtered fundamental wave of the three
phase currents. The evaluation of the negativesequence current is performed in two timeovercurrent stages with definite-time delay.
20
0
Reclosure blocking
three successive startups
Figure 9:
t
11888e.DS4
3
2
1
t
Permissible number of startups
Overload memory and start-up counter
P132_TechnicalDataSheet_EN_12_b
10
P132-306-415/416/417/418/419-612 ff
Ground-Fault Direction Determination
Measuring-Circuit Monitoring
For the determination of the ground-fault direction
in isolated or Peterson-coil compensated power
systems several proven methods are provided:
> Steady-state power or admittance evaluation
methods - complemented by signaling
schemes and tripping logic
Measuring-circuit monitoring includes the
monitoring of the phase currents and phase-tophase voltages.
Phase current monitoring is based on the principle
of maximum allowable magnitude unbalance,
whereby the arithmetic difference between the
maximum and minimum phase currents - as
referred to the maximum phase current - is
compared to the set operate value. Even with an
economy-type CT connection (CTs in only two
phases) it is possible to monitor the phase
currents given appropriate settings.
Phase-to-phase voltage monitoring is based on a
plausibility check involving the phase currents. If a
low current threshold setting is exceeded by at
least one phase current, the three phase-to-phase
voltages are monitored for a set minimum level. In
addition to magnitude monitoring, phase
sequence monitoring of the phase-to-phase
voltages may be activated.
> Transient signal method (optional)
Ground Fault Direction Determination Using
Steady-State Values
The ground fault direction is determined by
evaluating the neutral displacement voltage and
the residual current (from a core balance or
window-type current transformer). The directional
characteristic (cos ϕ or sin ϕ circuit) can be set to
suit the neutral-point treatment (resonantgrounded or isolated-neutral). In the cos ϕ mode
(for a resonant-grounded network), the adjustable
sector angle also has an effect so that faulty
direction decisions (resulting, for instance, from
the phase angle error of the CT and VT) can be
suppressed effectively. Operate sensitivity and
sector angle can be set separately for the forward
and backward direction, respectively.
Either steady-state power or steady-state
admittance can be selected for evaluation.
Alternatively, an evaluation based on current only
can be performed. In this case, only the
magnitude of the filtered neutral current is used as
ground fault criterion.
Both procedures operate with either the filtered
fundamental wave or the fifth harmonic
component in accordance with the chosen setting.
Transient Ground Fault Direction
Determination
(optional)
The ground fault direction is determined by
evaluating the neutral displacement voltage
calculated from the three phase-to-ground
voltages and the neutral current on the basis of
the transient ground fault measuring procedure.
The direction decision is latched. The user may
select either manual or automatic resetting after a
set time delay.
P132-306-415/416/417/418/419-612 ff
11
P132_TechnicalDataSheet_EN_12_b
Also the neutral displacement and the reference
voltage, the temperatures of the resistance
temperature detectors and the value of the
linearised 0 to 20 mA input are monitored. The
evaluations uses an operate value and time delay
set by the user. Thereby, all values can be
monitored for exceeding an upper limit or falling
below a lower limit.
Limit value monitoring is not a fast protection
function and is intended to be used for monitoring
and signaling purposes e.g. limit temperature
monitoring.
The phase currents, the phase-to-ground voltages
and the phase-to-phase voltages are monitored.
For 3-phase sets, the highest and the lowest
value is determined.
RTD
Prime sensor
RTD Phase
A
B
C
RTD
RTD
RTD
RTD
RTD
stator
RTD
RTD
RTD
RTD
RTD
Backup sensor
RTD
anbient temperature /
coolant temperature
RTD
Limit Monitoring
rotor
bearing
bearing
Figure 10: Temperature detection of a motor for Limit Monitoring and Thermal Overload Protection
P132_TechnicalDataSheet_EN_12_b
12
P132-306-415/416/417/418/419-612 ff
Measured Data Input
(optional)
Programmable Logic
User-configurable logic enables the user to set up
logic operations on binary signals within a
framework of Boolean equations. By means of a
straightforward configuration procedure, any of
the signals of the protection device can be linked
by logic 'OR' or 'AND' operations with the
possibility of additional negation operations.
The output signal of an equation can be fed into a
further, higher-order equation as an input signal
thus leading to a set of interlinked Boolean
equations.
The output signal of each equation is fed to a
separate timer stage with two timer elements
each and a choice of operating modes. Thus the
output signal of each equation can be assigned a
freely configurable time characteristic.
The two output signals of each equation can be
configured to each available input signal. The
user-configurable logic function is then able to
influence the individual functions without external
wiring (block, reset, trigger, for example).
Via non-storable continuous signals, monostable
trigger signals and bistable stored
setting/resetting signals, the Boolean equations
can be controlled externally via any of the device's
interfaces.
The optional analog I/O module provides a
0 to 20 mA input for the acquisition of externally
measured variables such as transducer outputs.
The external input characteristics can be
linearized via adjustable interpolation points. This
feature also provides for an adaptation of the
range to, for example, 4 to 20 mA or 0 to 10 mA.
The optional RTD module offers the possibility of
connecting up to 9 resistance temperature
detectors for direct temperature acquisition.
Depending on the set operating mode, all the
RTD's operate in parallel or the RTD's can be
subdivided into regular inputs and reserve inputs
which take over when the corresponding regular
inputs fail.
The measured variables acquired by the analog
measured data input function are monitored for
exceeding or falling below set limits. Furthermore,
they are used by thermal overload protection
function for the acquisition of the coolant
temperature.
Measured Data Output
The protection device provides the options of
operating data output and fault data output. The
user can select an output in BCD-coded form
through relay contacts or an output in analog form
as load-independent current (0 to 20 mA). For the
current output, a special analog I/O module is
required. For an output in BCD-coded form, an
appropriate number of free output relays need to
be available.
P132-306-415/416/417/418/419-612 ff
13
P132_TechnicalDataSheet_EN_12_b
For integration of the MiCOM P132 into an
integrated control systems, the equations for the
bay interlock with station interlock form the basis
of interlock checking.
Without integration into the substation control
system or with integration using IEC 61850, the
bay interlock without station interlock is used in
interlock checking; external ring feeders or signals
received via IEC 61850 may be included in the
interlocking logic.
If the bay or station topology (as applicable) is
permissible then the switching command is
issued. If a non-permissible state would result
from the switching operation then the switching
command is rejected and a signal to this effect is
issued.
If the bay type does not require all binary outputs
then the remaining outputs are available for free
configuration.
In addition to the switching command output, a
triggering of binary outputs by continuous
commands is possible.
Control Functions
(optional)
The optional control functions of the MiCOM P132
are designed for the control of up to three
electrically operated switchgear units equipped
with electrical check-back signaling. For this task,
the MiCOM P132 is fitted with the optional binary
I/O module X (6I/6O) for the control of switchgear
units. This module provides binary inputs for the
acquisition of switching positions and output
relays for switching commands.
For the control of switchgear units either the
binary inputs or the optional communication
interface or the function keys of the local control
panel can be used.
Up to 12 single-pole operating signals can be
acquired and processed in accordance with their
significance for the substation (circuit breaker
readiness, for example). For the setting of the
debounce and chattering times, three
independent setting groups are available. These
can be assigned to the switching position
signaling inputs and single-pole operating signals.
The MICOM P132 issues switching command
outputs with the integration of switching readiness
and permissibility tests; subsequently the MiCOM
P132 monitors the intermediate position times of
the switchgear units. If a switchgear malfunction is
detected, this fact will be indicated (e.g. by an
appropriately configured LED indicator).
Before a switching command output is executed,
the interlocking logic of the MiCOM P132 will
check whether the new switchgear unit state
corresponds to a permissible bay or substation
topology. The interlocking logic is set out for each
bay in the default setting as bay interlock with and
without station interlock. By means of a straightforward parameter setting procedure, the
interlocking equations can be adapted to the
prevailing bay and substation topology. The
presentation and functioning of the interlocking
system correspond to those of the programmable
logic.
P132_TechnicalDataSheet_EN_12_b
Figure 11: Control panel of the MiCOM P132
14
P132-306-415/416/417/418/419-612 ff
Global Functions
Overload Data Acquisition
Functions operating globally allow the adaptation
of the unit's interfaces to the protected power
system, offer support during commissioning and
testing and provide continuously updated
information on the operation, as well as valuable
analysis results following events in the protected
system.
Overload situations in the network represent a
deviation from normal system operation and can
be permitted for a brief period only. The overload
protection functions enabled in the device
recognize overload situations in the system and
provide for acquisition of overload data such as
the magnitude of the overload current, the relative
heating during the overload situation and its
duration.
Clock Synchronization
The device incorporates an internal clock with a
resolution of 1ms. All events are time-tagged
based on this clock, entered in the recording
memory appropriate to their significance and
signaled via the communication interface.
Alternatively two external synchronisation signals
can be used according to the selected
communication protocol: using one of the
protocols Modbus, DNP3, IEC 60870-5-103,
IEC 60870-5-101 or IEC 61850 the device will be
synchronized by a time telegram from a higherlevel substation control system. With IEC 61850
communication time synchronisations can be
done using SNTP services.
In any other case it will be synchronized using the
IRIG-B signal input. The internal clock will then be
adjusted accordingly and operate with an
accuracy of ±10 ms if synchronized via protocol
and ±1ms if synchronized via IRIG-B signal.
Overload Recording
While an overload condition persists in the
network, the relevant signals, each fully tagged
with date and time at signal start and signal end,
are entered into a non-volatile memory in
chronological sequence. The measured overload
data, fully tagged with the date and time of
acquisition, are also entered.
Up to eight overload situations can be recorded.
If more than eight overload situations occur
without interim memory clearance then the oldest
overload recording is overwritten.
Ground Fault Data Acquisition
The function parameters for setting the protection
functions are, to a large extent, stored in four
independent parameter subsets. Switching
between these subsets is readily achieved via any
of the device's interfaces.
While a ground fault in a network with isolated
neutral or resonant grounding represents a
system fault, it is usually nevertheless possible, in
the first instance, to continue system operation
without restrictions. The ground fault
determination functions enabled in the protection
device recognize ground faults in the system and
provide for the acquisition of the associated
ground fault data such as the magnitude of the
neutral displacement voltage and the ground fault
duration.
Operating Data Recording
Ground Fault Recording
For the continuous recording of processes in
system operation or of events, a non-volatile ring
memory for up to 128 entries is provided. The
relevant signals, each fully tagged with date and
time at signal start and signal end, are entered in
chronological sequence. Included are control
actions such as the enabling or disabling of
functions as well as local control triggering for
testing and resetting. The onset and end of events
in the network, as far as these represent a
deviation from normal operation (overload or
short-circuit, for example) are recorded.
While a ground fault condition persists in the
power system, the relevant signals, each fully
tagged with date and time at signal start and
signal end, are entered into a non-volatile memory
in chronological sequence. The measured ground
fault data, fully tagged with the date and time of
acquisition, are also entered.
Up to eight ground faults can be recorded. If more
than eight ground faults occur without interim
memory clearance then the oldest ground fault
recording is overwritten.
Parameter Subset Selection
P132-306-415/416/417/418/419-612 ff
15
P132_TechnicalDataSheet_EN_12_b
Fault Data Acquisition
Reset Functionalities
A short-circuit within the network is described as a
fault. The short-circuit protection functions
enabled in the devices recognize short-circuits
within the system and trigger acquisition of the
associated measured fault data such as the
magnitude of the short-circuit current and the fault
duration. As acquisition time, either the end of the
fault or the start of the trip command can be
specified by the user. Triggering via an external
signal is also possible. The acquisition of the
measured fault data is performed in the
measuring loop selected by the protective device
and provides impedances and reactances as well
as current, voltage and angle values.
The fault distance is determined from the
measured short-circuit reactance and is read out
with reference to the set 100% value of the
protected line section. The fault location is output
either with each general starting or only with a
general starting accompanied by a trip (according
to the user's choice).
Counter and record information, latchings, logical
equations or stored measuring values can be
reset by single or accumulative functions.
The reset functionalities can be activated via the
communication interfaces, the function keys or
any binary input of the MiCOM P132.
Furthermore the user has the possibility to adapt
the functional range of the reset key to the
required application.
Self-Monitoring
Comprehensive self-monitoring procedures within
the devices ensure that internal hardware or
software errors are detected and do not cause
malfunctions of the protective devices.
As the auxiliary voltage is turned on, a functional
test is carried out. Cyclic self-monitoring tests are
run during operation. If test results deviate from
the default value then the corresponding signal is
entered into the non-volatile monitoring signal
memory. The result of the fault diagnosis
determines whether a blocking of the protection
device will occur or whether a warning only is
issued.
Fault Recording
While a fault condition persists in the power
system, the relevant signals, each fully tagged
with date and time at signal start and signal end,
are entered into a non-volatile memory in
chronological sequence. The measured fault data,
fully tagged with the date and time of acquisition,
are also entered.
Furthermore, the sampled values of all analog
input variables such as phase currents and
neutral current, phase-to-ground voltages and
neutral displacement voltage are recorded during
a fault.
Up to eight faults can be recorded. If more than
eight faults occur without interim memory
clearance then the oldest fault recording is
overwritten.
Control
All data required for operation of the
MiCOM P132 are entered from the integrated
local control panel, and the data important for
system management are read out there as well.
The following tasks can be handled via the local
control panel:
Blocking Functionalities
Protection functions and their timer stages can be
temporarily blocked in case of commissioning and
cyclic testing. For this purpose single or
accumulative blocking functions can be used.
The blocking functionalities can be activated and
deactivated via the communication interfaces, the
function keys or any binary input.
P132_TechnicalDataSheet_EN_12_b
16
>
Readout and modification of settings
>
Readout of cyclically updated measured
operating data and state signals
>
Readout of operating data logs and of
monitoring signal logs
>
Readout of event logs (after overload
situations or short-circuits in the power
system)
>
Resetting of the unit and triggering of further
control functions designed to support testing
and commissioning tasks
P132-306-415/416/417/418/419-612 ff
The local control panel shown in figure 12
comprises the local control elements and
functions described below.
6
5
1
P132
Operation
(1) The integrated local control panel has an
graphical back-lit LCD Display with 4 x 20
alphanumeric characters.
23(resp. 10 in the 24T case) LED indicators are
provided for signal display
Mi COM P13 2
Pa r a me t er s
2
3
3
(2) 5 LED indicators are permanently assigned to
signals.
(3) The remaining 18 LED indicators are
available for free assignment by the user and
can be configured for the colours red, green or
yellow. Furthermore different operation and
flashing modes are available.
In the 24T case 5 unicoloured LED indicators
are available for this functions.
7
4
Figure 12: Local control panel
Function Keys
(available in 40T and 84T case)
A separate adhesive label is provided for userdefined labeling of these LED indicators according
to the chosen configuration.
(5) 6 Function Keys (F1…F6) are available for
free assignment to any logical binary input or
control function. This facilitates control, e.g. of
manual trip and close commands.
Menu Tree
(4) By pressing the cursor keys
Type Label and PC- Interface
(6) An upper cover identifying the product name.
The cover may be raised to provide access to
the product model number and ratings.
,
,
and
guided by the LCD
display, the user moves within a plain text
menu. All setting parameters and measured
variables as well as all local control functions
are arranged in this menu which is
standardized for all devices of the system.
G
(7) A lower cover concealing the RS232 serial
interface to connect a personal computer.
(8) To guard the lower cover against unauthorized
opening it is provided a facility for fitting a
security lead seal.
G
Changes to the settings can be prepared and
confirmed by means of the Enter Key
which also serves to trigger local control
functions. In the event of erroneous entries,
exit from the enter mode with rejection of the
entries is possible at any time by means of the
Clear Key C When the edit mode is not
activated, pressing the Clear Key has the
effect of resetting the indications. Pressing the
Read Key
provides direct access to a
preselected point in the menu.
Display Panels
The configuration of the local control panel
allows the installation of measured value
`Panels`on the LCD display. The Panels are
automatically displayed for certain operation
conditions of the system. Priority increases
from normal operation to operation under
overload conditions and finally operation
following a short-circuit in the system. The
protection device thus provides the measured
value data relevant for the prevailing
conditions.
Devices with the optional control functions
have additionally a control panel display to
show the active switchgear status and for local
control via function keys.
Password Protection
Access barriers protect the enter mode or the
function keys in order to guard against
inadvertent or unauthorized changing of
parameter settings or triggering of control
functions.
P132-306-415/416/417/418/419-612 ff
8
17
P132_TechnicalDataSheet_EN_12_b
Mechanical Design
Transformer Module T
The devices are supplied in four case designs.
> Surface-mounted case with detachable HMI
The transformer module converts the measured
current and voltage variables to the internal
processing levels and provides for electrical
isolation.
> Flush-mounted case
Power Supply Module V
> Surface-mounted case
> Flush-mounted case with detachable HMI
The power supply module ensures the electrical
isolation of the device as well as providing the
power supply. Depending on the chosen design
version, optical coupler inputs and output relays
are provided in addition.
With all case designs, connection is via threaded
terminal ends with the option of either pin-terminal
or ring-terminal connection.
Two 40T respective three 24T flush-mounted
cases can be combined to form a complete 19"
mounting rack.
Figure 13 shows the modular hardware structure
of the devices. The plug-in modules can be
combined to suit individual requirements. The
device itself can identify the fitted modules. During
each startup, the number and type of fitted
modules are identified and checked for
compliance with the permissible configurations.
As function of the components actually fitted, the
corresponding configuration parameters are then
enabled for application.
Processor Module P
The processor module performs the analog/digital
conversion of the measured variables as well as
all digital processing tasks.
Local Control Module L
The local control module encompasses all control
and display elements as well as a PC interface.
The local control module is located behind the
front panel and connected to the processor
module via a ribbon cable.
The detachable HMI gets connected to the
processor module via interfacing module (cover
plate) and connection cable.
Bus Modules B
Bus modules are printed circuit boards (PCBs).
They provide the electrical connection between
the other modules. Two types of bus modules are
used, namely the analog- and the digital-bus PCB.
P132_TechnicalDataSheet_EN_12_b
18
P132-306-415/416/417/418/419-612 ff
Communication Module A
(optional)
Binary I/O Modules X
(optional)
The optional communication module provides one
or two serial information interfaces for the
integration of the protection device into a
substation control system and for remote access
respectively a protection communication interface
for the transfer of digital information between two
protective devices. The communication module
with serial communication interface(s) is plugged
into the processor module.
The binary I/O modules are equipped with optical
couplers for binary signal input as well as output
relays for the output of signals and commands or
combinations of these.
Transient Ground Fault Evaluation Module N
(optional)
The optional transient ground fault module
evaluates the measured variables according to
the transient ground fault evaluation scheme.
Protection Interface A (InterMiCOM)
(optional)
Analog Modules Y
(optional)
The optional protection interface provides point to
point digital communication between two MiCOM
protection devices.
Der optional RTD module is fitted with 9
resistance temperature detector inputs. The
optional analog module is fitted with a resistance
temperature detector input, a 20 mA input and two
20 mA outputs. One output relay each is assigned
to the two 20 mA outputs. Additionally four optical
coupler inputs are available.
PC Interface
L
TRIP
F1
A LARM
OUT OF SE RVI CE
HEALTHY
F2
E DIT MODE
G
G
G
F3
Protection Interface
InterMiCOM
A
A
F4
G
G
C
A
MiCOM
G
C
N
Communication
Interfaces
G
F5
F6
P
P
B
T
Currents / Voltages
X
Y
V
Binary signals / Measured data / Commands
Power supply
Figure 13: System structure
P132-306-415/416/417/418/419-612 ff
19
P132_TechnicalDataSheet_EN_12_b
Technical Data
Terminals
General Data
PC Interface (X6)
DIN 41652 connector ,
type D-Sub, 9-pin
Design
Communication Interfaces COMM1, COMM2, COMM3
Optical fibers (X7, X8 and X31, X32):
F-SMA-interface per IEC 60874-2 per plastic fiber
or
®
BFOC-(ST )-interface 2.5 per IEC 60874-10-1 per glass fiber
or
Leads (X9, X10, X33):
Threaded terminal ends M2 for wire cross
2
sections up to 1.5 mm
or (only for COMM3 (InterMiCOM))
RS232 (X34):
DIN 41652 connector,
Type D-Sub, 9 pin.
Surface-mounted case suitable for wall installation or flushmounted case for 19" cabinets and for control panels
Installation position
Vertical ±30°
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for the rear connection area of the flush-mounted
case
Weight
Case 24T: max. 5 kg
Case 40T: max. 7 kg
Case 84T: max. 11 kg
Communication Interface IEC 61850
Optical fibers (X7, X8):
®
BFOC-(ST )-interface 2.5 per IEC 60874-10-1 per glass fiber
or
optical fibers (X13):
SC-interface per IEC60874-14-4 per glass fiber
and
Leads (X12):
RJ45 connector per ISO/IEC 8877
Dimensions
See “Dimensions”
Terminal Connection Diagrams
See “Connections”
IRIG-B Interface (X11)
BNC plug
Current-Measuring Inputs
Threaded terminals for pin-terminal connection:
Threaded terminal ends M5,
self-centering with wire protection for
conductor cross sections of ≤ 4 mm2
or
Threaded terminals M4 for ring-terminal connection
Other Inputs and Outputs
Threaded terminals for pin-terminal connection:
Threaded terminal ends M3,
self-centering with wire protection for
conductor cross sections of 0.2 to 2.5 mm2
or
Threaded terminals M4 for ring-terminal connection
Creepage Distance and Clearance
Per EN 61010-1 and IEC 664-1,
pollution degree 3,
working voltage 250 V,
overvoltage category III,
impulse test voltage 5 kV
P132_TechnicalDataSheet_EN_12_b
20
P132-306-415/416/417/418/419-612 ff
Tests
Insulation
Voltage Test
Per IEC 255-5 or DIN EN 61010, 2 kV~, 60 s
For the voltage test of the power supply inputs,
direct voltage (2.8 kVDC) must be used.
The PC Interface must not be subjected to the voltage test.
Type Test
Tests according to EN 60255-6, IEC 255-6 or EN 50121-5
EMC
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A
Impulse Voltage Withstand Test
Per IEC 255-5,
Front time: 1.2 µs, Time to half-value: 50 µs,
Peak value: 5 kV, Source impedance: 500 Ω
1 MHz Burst Disturbance Test
Per IEC 255 Part 22-1 or IEC 60255-22-1, Class III,
Common-mode test voltage: 2.5 kV,
Differential test voltage: 1.0 kV,
Test duration: > 2 s, Source impedance: 200 Ω
Mechanical Robustness
Vibration Test
Per DIN EN 60255-21-1 or IEC 255-21-1,
test severity class 1:
frequency range in operation:
10...60 Hz, 0.035 mm,
60...150 Hz, 0.5 g,
frequency range during transport:
10...150 Hz, 1 g
Immunity to Electrostatic Discharge
Per EN 60255-22-2 or IEC 60255-22-2, Level 3,
Contact discharge, single discharges : > 10,
Holding time: > 5 s, Test voltage: 6 kV,
Test generator: 50...100 MΩ, 150 pF / 330 Ω
Immunity to Radiated Electromagnetic Energy
Per EN 61000-4-3 and ENV 50204, Level 3,
Antenna distance to tested device: > 1 m on all sides,
Test field strength, frequ. band 80...1000 MHz: 10 V / m,
Test using AM: 1 kHz / 80 %,
Single test at 900 MHz: AM 200 Hz / 100 %
Shock Response and Withstand Test, Bump Test
Per DIN EN 60255-21-2 or. IEC 255-21-2,
acceleration and pulse duration:
Shock Response test to verify full operability
(during operation): test severity class 1, 5 g for 11 ms,
Shock Response test to verify endurance
(during transport): test severity class 1, 15 g for 11 ms
Electrical Fast Transient or Burst Requirements
Per IEC 60255-22-4, Class B:
Power supply: Amplitude: 2 kV, Burst frequency: 5 kHz
Inputs / Outputs: Amplitude: 2 kV, Burst frequency: 5 kHz
Communication: Amplitude: 1 kV, Burst frequency: 5 kHz
Per DIN EN 61000-4-4, severity level 4:
Power supply:
Amplitude: 4 kV, Burst frequency: 2,5 kHz and 5 kHz
Inputs / Outputs: Amplitude: 2 kV, Burst frequency: 5 kHz
Communication: Amplitude: 2 kV, Burst frequency: 5 kHz
Rise time of one pulse: 5 ns,
Impulse duration (50% value): 50 ns,
Burst duration: 15 ms,
Burst cycle: 300 ms,
Source impedance: 50 Ω
Seismic Test
Per DIN EN 60255-21-3 or IEC 255-21-3,
test procedure A, Class 1:
frequency range:
5...8 Hz, 3.5 mm / 1.5 mm,
8...35 Hz, 10 / 5 m/s2
3 × 1 cycle
1)
Vibration Test
Per DIN EN 60255-21-1 or IEC 255-21-1,
test severity class 2:
frequency range in operation:
10...60 Hz, 0.075 mm,
60...150 Hz, 1.0 g,
frequency range during transport:
10...150 Hz, 2 g
Conducted Disturbance Induced by Radiofrequency Fields
Per IEC 60255-22-7, Class A:
Phase-to-Phase:
Voltage 150 V r.m.s,.
Coupling resistor 100 Ω,
Coupling capacitor 0.1 μF, for 10 s.
Phase-to-Ground:
Voltage 300 V r.m.s.,
Coupling resistor 220 Ω,
Coupling capacitor 0.47 μF, for 10 s.
1)
Shock Response and Withstand Test, Bump Test
Per DIN EN 60255-21-2 or IEC 255-21-2,
acceleration and pulse duration:
Shock Response test to verify full operability
(during operation): test severity class 2, 10 g für 11 ms,
Shock Response test to verify endurance
(during transport): test severity class 1, 15 g für 11 ms
Shock bump test to verify permanent shock
(during transport): test severity class 1, 10 g für 16 ms
Surge Immunity
Per EN 61000-4-5 or IEC 61000-4-5, Level 4,
Testing of power supply circuits,
unsymmetrically / symmetrically operated lines,
Open-circt. voltg. front time/time to half-value: 1.2 / 50 µs,
Short-circuit current front time/time to half-value: 8 / 20 µs,
Amplitude: 4 / 2 kV, Pulse frequency: > 5 / min,
Source impedance: 12 / 42 Ω
1)
Seismic Test
Per DIN EN 60255-21-3 or IEC 255-21-3,
test procedure A, Class 2
frequency range:
5...8 Hz, 7.5 mm / 3.5 mm,
8...35 Hz, 20 / 10 m/s2
3 × 1 cycle
Immunity to Conducted Disturbances Induced by Radio
Frequency Fields
Per EN 61000-4-6 or IEC 61000-4-6, Level 3,
Disturbing test voltage: 10 V
Power Frequency Magnetic Field Immunity
Per EN 61000-4-8 or IEC 61000-4-8, Level 4,
Frequency: 50 Hz,
Test field strength: 30 A / m, 100 A / m
Alternating Component (Ripple) in DC Auxiliary Energizing
Quantity
Per IEC 255-11, 12 %
P132-306-415/416/417/418/419-612 ff
1) Enhanced mechanical robustness for the following case variants:
Flush mounted case, version 2 (with angle brackets and frame)
Surface mounted case
21
P132_TechnicalDataSheet_EN_12_b
Routine Test
Binary Signal Inputs
Test per EN 60255-6 or IEC 255-6
Max. permissible voltage: 300 VDC
Voltage Test
Per IEC 255-5:
2.2 kVAC, 1 s
For the voltage test of the power supply inputs,
direct voltage (2.8 kVDC) must be used.
The PC Interface must not be subjected to the voltage
test.
Switching threshold (as per order option)
order option:
Standard variant: 18V (VA,nom: 24 ... 250 VDC):
Switching threshold range 14 V ... 19 VDC
Special variant with switching thresholds from
58 ... 72 % of the nominal supply voltage (VA,nom)
(definitively "low" at VA < 58 % of the nominal supply
voltage, definitively "high" at VA > 72 % of the nominal
supply voltage):
"Special variant 73 V": nom. supply voltage 110 VDC
"Special variant 90 V": nom. supply voltage 127 VDC
"Special variant 146 V": nom. supply voltage 220 VDC
"Special variant 155 V": nom. supply voltage 250 VDC
Additional Thermal Test
100 % controlled thermal endurance test, inputs loaded.
Environmental Conditions
Ambient Temperature Range
Power Consumption (as per order option):
Standard variant:
VA = 19...110VDC : 0.5 W +/-30%
VA > 110VDC : VA ∗ 5 mA +/- 30 %
Special variants:
VA > switching threshold: VA ∗ 5mA +/-30 %
Recommended temperature range:
–5 °C...+55 °C, or +23 °F...+131 °F
Limit temperature range:
–25 °C...+70 °C, or -13 °F...+158 °F
Ambient Humidity Range
≤ 75 % relative humidity (annual mean),
up to 56 days at ≤ 95 % relative humidity and 40 °C,
condensation not permissible
Note:
The standard variant of binary signal inputs (opto-couplers) is
recommended in most applications, as these inputs operate
with any voltage from 19V. Special versions with higher pickup/drop-off thresholds are provided for applications where a
higher switching threshold is expressly required.
Solar Radiation
Avoid exposure of the front panel to direct solar radiation.
Analog Inputs and Outputs
Ratings
Direct Current Input
Input current: 0...26 mA
Value range 0.00...1.20 IDC,nom (IDC,nom = 20 mA)
Maximum permissible continuous current: 50 mA
Maximum permissible input voltage: 17 V
Input load: 100 Ω
Open-circiut monitoring: 0...10 mA (adjustable)
Overload monitoring: > 24.8 mA
Zero suppression:
0.000...0.200 IDC,nom (adjustable)
Measurement Inputs
Nominal frequency fnom: 50 Hz and 60 Hz (settable)
Operating range: 0.95...1.05 fnom
Frequency protection: 40…70 Hz
Current
Nominal current Inom: 1 A and 5 A (settable)
Nominal consumption per phase: < 0.1 VA at Inom
Load rating:
continuous: 4 Inom
for 10 s: 30 Inom
for 1 s: 100 Inom
Nominal surge current: 250 Inom
Resistance Temperature Detector
For analog module only PT100 permitted,
For RTD module PT100, Ni100, Ni120 permitted
Value range: -40...+215 °C
3-wire configuration: max. 20 Ω per conductor
open and short-circuit input permitted
Open circuit monitoring:
Θ > +215 °C (or Θ > +419 °F) and
Θ < -40 °C (or Θ < -40 °F)
Voltage
Nominal voltage Vnom: 50...130 VAC (settable)
Nominal consumption per phase: < 0.3 VA at Vnom=130 VAC
Load rating: continuous 150 VAC
Direct Current Output
Output current: 0 … 20 mA
Maximum permissible load: 500 Ω
Maximum output voltage: 15 V
P132_TechnicalDataSheet_EN_12_b
22
P132-306-415/416/417/418/419-612 ff
Output Relays
PC-Interface
Binary module X (4H)
with High-break contacts
applicable to DC circuits only
Rated voltage: 250 VDC
Continuous current: 10 A
Short-duration current:
250 A for 0.03 s
30 A for 3 s
Making capacity: 30 A
Breaking capacity:
7500 W resistive or 30 A at 250 VDC
maximum values: 30 A and 300 VDC
2500 W inductive (L/R = 40 ms) or 10 A at 250 VDC
maximum values: 10 A and 300 VDC
Transmission rate: 300...115200 Baud (settable)
Communication Interfaces
COMM1, COMM2, COMM3
Communication Interface COMM1:
Protocol switchable between IEC 60870-5-103,
IEC 870-5-101, Modbus, DNP 3.0, Courier
Transmission speed: 300...64000 bit/s (settable)
Communication Interface COMM2:
Protocol per IEC 60870-5-103
Transmission speed: 300...57600 bit/s (settable)
Protection Interface COMM3:
InterMiCOM, asynchronous, full duplex
Transmission speed: 600...19200 bit/s (settable)
Binary module X (6I/6O)
for control of switchgear units
Rated voltage: 250 VDC, 250 VAC
Continuous current: 8 A
Short-duration current: 30 A for 0.5 s
Making capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity:
0.2 A at 220 VDC and L/R = 40 ms,
4 A at 230 VAC and cos ϕ = 0.4
Wire Leads
Per RS 485 or RS 422, 2 kV-isolation
Distance to be bridged:
peer to peer link: max. 1200 m
multi-endpoint link: max. 100 m
Plastic Fiber Connection
Optical wavelength : typ. 660 nm
Optical output: min. – 7.5 dBm
Optical sensivity: min. – 20 dBm
Optical input: max. – 5 dBm
Distance to be bridged: max. 45 m 1)
Other modules
Rated voltage: 250 VDC, 250 VAC
Continuous current: 5 A
Short-duration current: 30 A for 0.5 s
Making capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity:
0.2 A at 220 VDC and L/R = 40 ms,
4 A at 230 VAC and cos ϕ = 0.4
Class Fiber Connection G 50/125
Optical wavelength : typ. 820 nm
Optical output: min. – 19.8 dBm
Optical sensivity: min. – 24 dBm
Optical input: max. – 10 dBm
Distance to be bridged: max. 400 m 1)
IRIG-B Interface
Min./max. input voltage level (peak-peak):
100 mVpp / 20 Vpp
Input impedance: 33 kΩ at 1 kHz
Galvanic isolation: 2 kV
Class Fiber Connection G 62,5/125
Optical wavelength : typ. 820 nm
Optical output: min. – 16 dBm
Optical sensivity: min. – 24 dBm
Optical input: max. – 10 dBm
Distance to be bridged: max. 1400 m 1)
Power Supply
Nominal Auxiliary Voltage
VA,nom: 48…250 VDC and 100...230 VAC or
VA,nom: 24 VDC (depends on ordering)
Operating Range
for direct voltage: 0.8…1.1 VA,nom
with a residual of up to 12 % of VA,nom
for alternating current: 0.9…1.1 VA,nom
Nominal Consumption
at VA = 220 VDC and maximum number of modules fitted
in case24T:
Inital position approx.:
11 W
Active position approx.:
20 W
in case 40T:
Inital position approx.:
11 W
Active position approx.:
25 W
in case 84T:
Inital position approx.:
11 W
Active position approx.:
44 W
Start-Up Peak Current
< 3 A, duration 0.25 ms
Stored-Energy Time
≥ 50 ms for interruption of VA ≥ 220 VDC
1) Distance to be bridged for optical outputs and inputs that are
equal on both ends, taking into account a system reserve of 3 dB
and typical fiber attenuation.
P132-306-415/416/417/418/419-612 ff
23
P132_TechnicalDataSheet_EN_12_b
Communication Interface IEC
Deviations of the Operate Values
Wire Leads
Ethernet based communication per IEC 61850
Transmission rate: 10 resp. 100 Mbit/s
RJ45, 1.5kV-isolation,
Distance to be bridged: max. 100 m
Deviation relative to the set value of
sinusoidal signals with
nominal frequency fnom,
total harmonic distortion ≤ 2 %,
ambient temperature 20°C and
nominal auxiliary voltage VA,nom.
Optical Fiber (100 Mbit/s)
Ethernet based communication per IEC 61850
SC- or ST-interface
Optical wavelength: typ. 1300 nm
For glass fiber G50/125
Optical output: min. –23.5 dBm
Optical sensitivity: min. -31 dBm
Optical input: max. -14 dBm
For glass fiber G62.5/125
Optical output: min. -20 dBm
Optical sensitivity: min. -31 dBm
Optical input: max. -14 dBm
Measuring-circuit monitoring
Operate values Ineg , Vneg: ± 3 %
Overcurrent-Time Protection
Operate values I>, IN>: ± 5 %
Short-circuit direction determination
Operate values: ± 10 °
Motor and Thermal Overload Protection
Reaction time: ± 7.5 % at I/Iref =6
IRIG-B Interface
Over-/Underfrequency Protection
Operate values f<>: +/- 30 mHz (fnom = 50 Hz)
+/- 40 mHz (fnom = 60 Hz)
Operate values df/dt:
+/- 0.1 Hz/s (fnom = 50 or 60 Hz)
Format B122,
Amplitude modulated, 1 kHz carrier signal,
BCD time-of-year code
Typical Characteristic Data
Over-/Undervoltage Protection
Operate values V<>, Vpos<>: ± 1 % (setting 0.6…1.4 Vnom)
Operate values VNG>, Vneg>: ± 1 % (setting > 0.3 Vnom)
Main Function
Minimum output pulse for a trip command:
0.1 … 10 s (settable)
Output pulse for a close command:
0.1 to 10 s (settable)
Unbalance Protection
Operate values: ± 5 %
Definite-Time and Inverse-Time Overcurrent Protection
Shortest tripping time:
time delayed stage:
directional operation: approx. 0.7 cycles
nondirectional operation: approx. 1.2 cycles
Earth current stage: < 10ms (at tIN> = 0 ms)
Starting reset time (from twice the set threshold to zero)
approx. 1.5 cycles
Starting and measurement resetting ratio: 0.95
Directional Power Protection
Operate values P<>, Q<>: ± 5 %
GF Direction Determination
Operate values: VNG>, IN,act , IN,reac, IN> ± 3 %
Sector Angle: 1 °
Deviations of the Timer Stages
Deviation relative to the set value of
sinusoidal signals with
nominal frequency fnom,
total harmonic distortion ≤ 2 %,
ambient temperature 20°C and
nominal auxiliary voltage VA,nom.
Short-Circuit Direction Determination
Nominal acceptance angle for forward decision: ±90 °
Resetting ratio forward/backward recognition: ≤ 7 °
Base point release for phase currents: 0.1 Inom
Base point release for phase-to-phase voltages:
0.002 Vnom at Vnom = 100 V
Base point release for residual current: 0.01 Inom
Base point release for neutral displacement voltage:
0.015 to 0.6 Vnom /√3 (adjustable)
Definite-Time Stages
± 1% + 20...40 ms
Neutral current: ≤ 3 ms (at tIN> = 0 ms)
Inverse-Time Stages
± 5 % + 10...25 ms (measured variable greater than 2 Iref)
or
for IEC characteristic‚ extremely inverse‘ and for
thermal overload protection:
± 7,5 % + 10...20 ms
Over-/Undervoltage Protection
Operate time inclusive of output relay (measured variable from
nominal value to 1.2-fold operate value or measured variable
from nominal value to 0.8-fold operate value):
≤ 40 ms, approx. 30 ms
Reset time (measured variable from 1.2-fold operate value to
nominal value or measured variable from 0.8-fold operate
value to nominal value):
≤ 45 ms, approx. 30 ms
Starting resetting ratio: settable hysteresis 1...10%
Deviations in Measured Data Aquisiton
Deviation relative to the nominal value of
sinusoidal signals with
nominal frequency fnom,
total harmonic distortion ≤ 2 %,
ambient temperature 20°C and
nominal auxiliary voltage VA,nom.
Directional Power Protection
Operate time inclusive of output relay (measured variable from
nominal value to 1.2-fold operate value or measured variable
from nominal value to 0.8-fold operate value):
≤ 60 ms, approx. 50 ms
Reset time (measured variable from 1.2-fold operate value to
nominal value or measured variable from 0.8-fold operate
value to nominal value):
≤ 40 ms, approx. 30 ms
Resetting ratio for
P>, Q>: settable hysteresis 0.05...0.95
P<, Q<: settable hysteresis 1.05...20
P132_TechnicalDataSheet_EN_12_b
24
P132-306-415/416/417/418/419-612 ff
Adress List
Operating Data
Currents / measuring inputs: ±1%
Voltages / measuring inputs: ± 0,5 %
Currents / internally calculated: ± 2 %
Voltages / internally calculated: ± 2 %
Active and reactive power / energy:
approx. ± 2 % of meas. value for cos ϕ = ± 0.7
approx. ± 5 % of meas. value for cos ϕ = ± 0.3
Load angle: ± 1 °
Frequency: ± 10 mHz
Function Parameters
Global Functions
PC Link (PC):
Command blocking: No / Yes
Sig./meas.val.block.: No / Yes
Communication Link 1 (COMM1):
Command block. USER: No / Yes
Sig./meas.block.USER: No / Yes
Fault Data
Currents and voltages: ± 3 %
Short circuit impedance: ± 5 %
Fault location: ± 5 %
Communication Link 2 (COMM2):
Command block. USER: No / Yes
Sig./meas.block.USER: No / Yes
Internal Clock
With free running internal clock: < 1 min. / month
With external synchronization
via protocol, synch. interval ≤ 1 min: < 10 ms
via IRIG-B signal input: ± 1 ms
Binary Output (OUTP):
Outp.rel.block USER: No / Yes
Main function (MAIN):
Device on-line: No (= off) / Yes (= on)
Test mode USER: No / Yes
Nominal frequ. fnom: 50 Hz / 60 Hz
Phase sequence: A – B – C / A – C – B
Time tag:
1stEgde.,OpMem sorted
1stEgde.,OpMem unsort
after debounce time
Inom C.T. prim.: 1..10000 A
IN,nom C.T. prim.: 1..10000 A
Vnom V.T. prim.: 0.1....1000.0 kV
VNG,nom V.T. prim.: 0.1....1000.0 kV
Vref,nom V.T. prim.: 0.1...1000.0 kV
Inom prim. NCIT: 50…4000 A
IN,nom prim. NCIT: 10…800 A
Vnom prim. NCIT: 0.1...1000.0 kV
Ph. err. VAG,1 NCIT: -5.0…5.0°
Ph. err. VBG,1 NCIT: -5.0…5.0°
Ph. err. VCG,1 NCIT: -5.0…5.0°
Ph. err. VAG,2 NCIT: -5.0…5.0°
Ph. e. VBG/Vref,2 NCIT: -5.0…5.0°
Ph. err. VCG,2 NCIT: -5.0…5.0°
Channel select NCIT:
No channel
Channel 1 on
Channel 2 on
Inom device: 1 A / 5 A
IN,nom device: 1 A / 5 A
Vnom V.T. sec.: 50...130 V
VNG,nom V.T. sec.: 50...130 V
Vref,nom V.T. sec.: 30...130 V
Conn. meas. circ. IP: Standard / Opposite
Conn. meas. circ. IN: Standard / Opposite
Meas. direction P,Q: Standard / Opposite
Meas. value rel. IP: 0.000...0.200 Inom
Meas. value rel. IN: 0.000...0.200 IN,nom
Meas. value rel. V: 0.000...0.200 Vnom
Meas. val. rel. VNG: 0.000...0.200 VNG,nom
Meas. val. rel. Vref: 0.000...0.200 Vref,nom
Op. mode energy cnt.: Procedure 1 / Procedure 2
Settl. t. IP,max,del: 0.1...60.0 min
Fct.assign. reset 1: see selection table
Fct.assign. reset 2: see selection table
Fct.assign. block. 1: see selection table
Fct.assign. block. 2: see selection table
Trip cmd.block. USER: No / Yes
Fct.assig.trip cmd.1: see selection table
Fct.assig.trip cmd.2: see selection table
Min.dur. trip cmd. 1: 0.10...10.00 s
Resolution in Fault Data Aquisition
Time Resolution Fault Data Aquisition:
1 ms
Currents
Dynamic range: 100 Inom resp 25 Inom
Amplitude resolution
at Inom = 1 A: 6.1 mAr.m.s resp 1.5 mAr.m.s
at Inom = 5 A: 30.5 mAr.m.s resp 7.6 mAr.m.s
Residual Current
Dynamic range: 16 Inom resp. 2 Inom
Amplitude resolution
at Inom = 1 A: 0.98 mA r.m.s. resp. 0.12 mA r.m.s.
at Inom = 5 A: 4.9 mA r.m.s. resp. 0.61 mA r.m.s.
Voltage
Dynamic range: 150 V
Amplitude resolution: 9.2 mVr.m.s
P132-306-415/416/417/418/419-612 ff
25
P132_TechnicalDataSheet_EN_12_b
Min.dur. trip cmd. 2: 0.10...10.00 s
Latching trip cmd. 1: No / Yes
Latching trip cmd. 2: No / Yes
Close cmd.pulse time 0.10...10.00 s
Sig. asg. CB open: see selection table
Inp.asg. ctrl.enabl.: see selection table
valid for y = ‚1‘ to ‚3‘
Debounce time gr. y: 0.00...2.54 s
Chatt.mon. time gr. y: 0.0...25.4 s
Change of state gr. y: 0...254
Cmd. dur.long cmd.: 1...254 s
Cmd. dur. short cmd.: 1...254 s
Inp.asg.interl.deact: see selection table
Inp.asg. L/R key sw.: see selection table
Auto-assignment I/O: No / Yes
Electrial control: Remote / Local
Delay Man.Op.Superv.: 0...255 s
W. ext. cmd. termin.: No / Yes
Inp.assign. tripping: see selection table
Prot.trip>CB tripped:
Without function
Gen. trip command 1
Gen. trip command 2
Gen. trip command 1/2
Inp. asg. CB trip: see selection table
Sig. asg. CB closed: see selection table
Inp.asg.CB tr.en.ext: see selection table
Inp.asg. CB trip ext: see selection table
Inp.asg. mult.sig. 1: see selection table
Inp.asg. mult.sig. 2: see selection table
Fct. assign. fault: see selection table
General Functions
Main function (MAIN):
Syst.IN enabled USER: No / Yes
Definite-time overcurrent protection (DTOC):
General enable USER: No / Yes
Inverse-time overcurrent protection (IDMT1 resp. IDMT2):
General enable USER: No / Yes
Shortcircuit direction determination (SCDD):
General enable USER: No / Yes
Switch on to fault protection (SOTF):
General enable USER: No / Yes
Operating mode:
Trip by I>
Trip by I>>
Trip b< I>>>
Trip by gen. start.
Manual close timer: 0.00...10.00 s
Protective signaling (PSIG):
General enable USER: No / Yes
Autoreclosing control (ARC):
General enable USER: No / Yes
Sig.asg.trip t.GFDSS:
Starting LS
Starting Y(N)>
Starting LS / Y(N)>
Fct.assign. tLOGIC: see selection table
Parameter Subset Selection (PSS):
Control via USER: No / Yes
Param.subs.sel. USER:
Parameter subset 1
Parameter subset 2
Parameter subset 3
Parameter subset 4
Keep time: 0.000...65.000 s / Blocked
Automatic synchronism check (ASC):
General enabled USER: No / Yes
Transm.cycle,meas.v.: 0...10 s
Ground fault direction determination using
steady-state values (GFDSS):
General enable USER: No / Yes
Operating mode:
Steady-state power
Steady-state current
Steady-state admitt.
Self-Monitoring (SFMON):
Fct. assign. warning: see selection table
Mon.sig. retention: 0...240 h / Blocked
Fault data acquisition (FT_DA):
Line length: 0.01...500.00 km
Line reactance:
0.10...200.00 Ω for Inom = 1.0 A
0.02...40.00 Ω for Inom = 5.0 A
Angle kG: -180...180 °
Abs. value kG: 0.00...8.00
Start data acquisit.: End of fault / Trigg., trip, GS end
Output fault locat.:
On general starting
On gen.start.w.trip
Transient ground fault direction determination (TGFD):
General enable USER: No / Yes
Motor protection (MP):
General enable USER: No / Yes
Hours_Run >: 1…65000 h
Thermal overload protection (THERM):
General enable USER: No / Yes
Operating mode:
Relative replica
Absolute replica
Fault Recording (FT_RC):
Fct. assign. trigger: see selection table
I>: 0.01...40.00 Inom / Blocked
Pre-fault time: 1...50 Periods
Post-fault time: 1...50 Periods
Max. recording time: 5...750 Periods
Unbalance protection (I2>):
General enable USER: No / Yes
Over-/undervoltage protection (V<>):
General enable USER: No / Yes
Over-/ underfrequency protection (f<>):
General enable USER: No / Yes
Selection meas. volt:
Voltage A-G
Voltage B-G
Voltage C-G
Voltage A-B
Voltage B-C
Voltage C-A
Evaluation time: 3...5 Periods
Undervolt. block. V<: 0.20...1.00 Vnom(/√3)
Directional power protection (P<>):
General enable USER: No / Yes
P132_TechnicalDataSheet_EN_12_b
26
P132-306-415/416/417/418/419-612 ff
Circuit Breaker Failure Protection (CBF)
General enable USER: No / Yes
Start with man. trip: No / Yes
Fct.assignm. CBAux.: see selection table
I>: 0.05…20.00 Inom
t1 3p: 0,00…100,00 s / Blocked
t2: 0.00…100.00 s / Blocked
Min.dur. trip cmd. t1: 0.10…10.00 s
Min.dur. trip cmd. t2: 0.10…10.00 s
Latching trip cmd. t1: No / Yes
Latching trip cmd. t2: No / Yes
Delay/starting trig.: 0.00…100.00 s / Blocked
Delay/fault beh. CB: 0.00…100.00 s / Blocked
Delay/CB sync.superv.: 0.00…100.00 s / Blocked
tVPP<<: 1...1000 s / Blocked
VNG>: 0.010... 1.000 Vnom / Blocked
VNG>>: 0.010... 1.000 Vnom / Blocked
tVNG>: 1...1000 s / Blocked
tVNG>>: 1...1000 s / Blocked
Vref>: 0.10...2.50 Vnom / Blocked
Vref>>: 0.10...2.50 Vnom / Blocked
tVref>: 1...1000 s / Blocked
tVref>>: 1...1000 s / Blocked
Vref<: 0.10...2.50 Vnom / Blocked
Vref<<: 0.10...2.50 Vnom / Blocked
tVref<: 1...1000 s / Blocked
tVref<<: 1...1000 s / Blocked
IDC,lin>: 0.100...1.100 IDC,nom / Blocked
IDC,lin>>: 0.100...1.100 IDC,nom / Blocked
tIDC,lin>: 0.00...20.00 s / Blocked
tIDC,lin>>: 0.00...20.00 s / Blocked
IDC,lin<: 0.100...1.100 IDC,nom / Blocked
IDC,lin<<: 0.100...1.100 IDC,nom / Blocked
tIDC,lin<: 0.00...20.00 s / Blocked
tIDC,lin<<: 0.00...20.00 s / Blocked
T>: -20...200°C
T>>: -20...200°C
tT>: 0...1000 s / Blocked
tT>>: 0...1000 s / Blocked
T<: -20...200°C
T<<: -20...200°C
tT<: 0...1000 s / Blocked
tT<<: 0...1000 s / Blocked
Valid for y = ‚1‘ to ‚9‘
Ty>: -20...200°C
Ty>>: -20...200°C
tTy>: 0...1000 s / Blocked
tTy>>: 0...1000 s / Blocked
Ty<: -20...200°C
Ty<<: -20...200°C
tTy<: 0...1000 s / Blocked
tTy<<: 0...1000 s / Blocked
Circuit Breaker Monitoring (CBM)
General enable USER: No / Yes
Blocking USER: No / Yes
Sig. asg. trip cmd: see selection table
Operating mode: see selection table
Inom, CB: 1…65000 A
Perm. CB op. Inom,CB: 1…65000
Med. curr. Itrip,CB: 1…65000 A / Blocked
Perm. CB op. Imed,CB: 1…65000 / Blocked
Max. curr. Itrip,CB: 1…65000 A
Perm. CB op. Imax,CB: 1…65000
No. CB operations>: 1…65000
Remain No. CB op. <: 1…65000
ΣItrip>: 1...65000 Inom,CB
ΣItrip**2>: 1...65000 Inom,CB**
ΣI*t>: 1.0...4000.0 kAs
Corr. acquis. time: -0.200...0.200 s
Measuring circuit monitoring (MCMON):
General enable USER: No / Yes
Op. mode Idiff>:
Without
IA,IC
IA, IB, IC
Idiff>: 0.25...0.50 IP,max
Op. mode Vmin< monit:
Vmin<
Vmin< with I enable
Vmin< w. CB cont. enab.
Vmin<: 0.40…0.90 Vnom / Blocked
Operate delay: 0.50...10.00 s / Blocked
Phase sequ. monitor.: No / Yes
FF,Vref enabled USER: No / Yes
Oper. delay FF, Vref: 00.00...10.00 s
Programmable Logic (LOGIC):
General enable USER: No / Yes
Valid for y = ‚1‘ to ‚8‘: Set y USER: No / Yes
Valid for y = ‚1‘ to ‚32‘:
Fct.assignm. outp. y: see selection table
Op. mode t output y:
Without timer stage
Oper./release.delay
Oper.del./puls.dur
Op./rel.delay,retrig
Op.del./puls.dur.,rt
Minimum time
Time t1 output y: 0.00...600.00 s
Time t2 output y: 0.00...600.00 s
Sig.assig. outp. y: see selection table
Sig.assig. outp. y(t): see selection table
Limit Value Monitoring (LIMIT):
General enable USER: No / Yes
I>: 0.10... 2.40 Inom / Blocked
I>>: 0.10... 2.40 Inom / Blocked
tI>: 1...1000 s / Blocked
tI>>: 1...1000 s / Blocked
I<: 0.10... 2.40 Inom / Blocked
I<<: 0.10... 2.40 Inom / Blocked
tI<: 1...1000 s / Blocked
tI<<: 1...1000 s / Blocked
VPG>: 0.10... 2.50 Vnom/√3 / Blocked
VPG>>: 0.10... 2.50 Vnom/√3 / Blocked
tVPG>: 1...1000 s / Blocked
tVPG>>: 1...1000 s / Blocked
VPG<: 0.10... 2.50 Vnom/√3 / Blocked
VPG<<: 0.10... 2.50 Vnom/√3 / Blocked
tVPG<: 1...1000 s / Blocked
tVPG<<: 1...1000 s / Blocked
VPP>: 0.10... 1.50 Vnom / Blocked
VPP>>: 0.10... 1.50 Vnom / Blocked
tVPP>: 1...1000 s / Blocked
tVPP>>: 1...1000 s / Blocked
VPP<: 0.10... 1.50 Vnom / Blocked
VPP<<: 0.10... 1.50 Vnom / Blocked
tVPP<: 1...1000 s / Blocked
P132-306-415/416/417/418/419-612 ff
Commands (CMD_1):
Valid for y = ‚C001‘ to ‚C012‘
Design. command y: see selection table
Oper. mode cmd. y:
Long command
Short command
Persistent command
Signaling (SIG_1):
Valid for y = ‚S001‘ to ‚S012‘
Designat. signal y: see selection table
Oper. mode sig. y:
Without function
Start/end signal
Transient signal
Gr.asg. debounc. y:
Group 1 ... Group 3
Min. sig. dur. y: 0...254 s
27
P132_TechnicalDataSheet_EN_12_b
Parameter Subset
Inverse-time overcurrent protection (IDMT1 resp. IDMT2):
Enable PSx: No / Yes
Iref,P PSx: 0.10...4.00 Inom / Blocked
Iref,P dynamic PSx: 0.10...4.00 Inom / Blocked
Characteristic P PSx:
Definite Time
IEC Standard Inverse
IEC Very Inverse
IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IEEE Very Inverse
IEEE Extremely Inv.
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
Factor kt,P PSx: 0.05...10.00
Min. trip t. P PSx: 0.00...10.00 s
Hold time P PSx: 0.00...600.00 s
Release P PSx: Without delay / Delayed as per char.
Evaluation IN PSx: calculated / Measured
Valid for y = ‚neg‘ or ‚N‘:
Iref,y PSx: 0.01...4.00 Inom / Blocked
Iref,y dynamic PSx: 0.01...4.00 Inom / Blocked
Characteristic y PSx:
Definite Time
IEC Standard Inverse
IEC Very Inverse
IEC Extr. Inverse
IEC Long Time Inv.
IEEE Moderately Inv.
IEEE Very Inverse
IEEE Extremely Inv.
ANSI Normally Inv.
ANSI Short Time Inv.
ANSI Long Time Inv.
RI-Type Inverse
RXIDG-Type Inverse
Factor kt,y PSx: 0.05...10.00
Min. trip t. y PSx: 0.00...10.00 s
Hold time y PSx: 0.00...600.00 s
Release y PSx:
Without delay / Delayed as per char.
(valid for parameter subsets x = = ‚1‘ to ‚4‘:
Measured Data Input (MEASI):
BackupTempSensor PSx:
None
Group 1 – 2
Group 1 - 2/3
Main function (MAIN):
Neutrl-pt threat. PSx:
Low-imped. Grounding
Isolated/res.ground.
Hld time dyn.par. PSx: 0.00...100.00 s / Blocked
Bl.tim.st. IN,neg PSx:
Without
For single-ph. start
For multi-ph. start
Gen. start. mode PSx: W/o start. IN, Ineg/With start. IN, Ineg
Op. rush restr. PSx:
Without
Not phase-selective
Phase-selective
Rush I(2*fn)/I(fn) PSx: 10...35 % / Blocked
I> lift rush restr. PSx: 5.0...20.0 Inom / Blocked
Suppr.start. sig. PSx: 0.00...100.00 s
tGS PSx: 0.00...100.00 s / Blocked
Definite-time overcurrent protection (DTOC):
Enable PSx: No / Yes
I> PSx: 0.10...40.00 Inom / Blocked
I> dynamic PSx: 0.10...40.00 Inom / Blocked
I>> PSx: 0.10...40.00 Inom / Blocked
I>> dynamic PSx: 0.10...40.00 Inom / Blocked
I>>> PSx: 0.10...40.00 Inom / Blocked
I>>> dynamic PSx: 0.10...40.00 Inom / Blocked
tI> Psx: 0.00...100.00 s / Blocked
tI>> PSx: 0.00...100.00 s / Blocked
tI>>> PSx: 0.00...100.00 s / Blocked
Ineg> PSx: 0.10...25.00 Inom / Blocked
Ineg> dynamic PSx: 0.10...25.00 Inom / Blockedt
Ineg>> PSx: 0.10...25.00 Inom / Blocked
Ineg>> dynamic PSx: 0.10...25.00 Inom / Blocked
Ineg>>> PSx: 0.10...25.00 Inom / Blocked
Ineg>>> dynamic PSx: 0.10...25.00 Inom / Blocked
tIneg> PSx: 0.00...100.00 s / Blocked
tIneg>> PSx: 0.00...100.00 s / Blocked
tIneg>>> PSx: 0.00...100.00 s / Blocked
Eval. IN>,>>,>>> PSx: Calculated / Measured
IN> PSx: 0.002...8.000 Inom / Blocked
IN> dynamic PSx: 0.020...8.000 Inom / Blocked
IN>> PSx: 0.002...8.000 Inom / Blocked
IN>> dynamic PSx: 0.020...8.000 Inom / Blocked
IN>>> PSx: 0.002...8.000 Inom / Blocked
IN>>> dynamic PSx: 0.020...8.000 Inom / Blocked
IN>>>> PSx: 0.10...40.00 Inom / Blocked
IN>>>> dynamic PSx: 0.10...40.00 Inom / Blocked
tIN> PSx: 0.00...100.00 s / Blocked
tIN>> PSx: 0.00...100.00 s / Blocked
tIN>>> PSx: 0.00...100.00 s / Blocked
tIN>>>> PSx: 0.00...100.00 s / Blocked
Puls.prol.IN>,int PSx: 0.00...10.00 s
tIN>,interm. PSx: 0.00...100.00 s / Blocked
Hold-time tIN>,intm. PSx: 0.0...600.0 s
P132_TechnicalDataSheet_EN_12_b
Short-circuit direction determination (SCDD):
Enable PSx: No / Yes
Trip bias PSx: No / Yes
valid values for:
Direction tI> PSx:
Direction tI>> PSx:
Direction tIref,P> PSx:
Direction tIN> PSx:
Direction tIN>> PSx:
Direction tIref,N> PSx:
Forward directional
Backward directional
Non-directional
Charact. angle G PSx: -90... -45...90 °
VNG> PSx: 0.015... 0.100...0.600 Vnom/√3
Block. bias G PSx: No / Yes
Oper.val. Vmemory PSx: 0.01...1.00 Vnom
Protective signaling (PSIG):
Enable PSx: No / Yes
Tripping time PSx: 0.00...10.00 s
Release t. send PSx: 0.00...10.00 s
DC loop op. mode PSx:
Transm.rel.break con / Transm.rel.make con.
Direc. Dependence PSx:
Without
Phase curr. System
Residual curr.system
Phase/resid.c.system
28
P132-306-415/416/417/418/419-612 ff
Autoreclosing control (ARC):
Enable PSx: No / Yes
CB clos.pos.sig. PSx: Without / With
Operating mode PSx:
HSR/TDR permitted
TDR only permitted
Test HSR only permit
Operative time PSx: 0.00...10.00 s
HSR trip.time GS PSx: 0.00...10.00 s / Blocked
HSR trip.time I> PSx: 0.00...10.00 s / Blocked
HSR trip.time I>> PSx: 0.00...10.00 s / Blocked
HSRtrip.time I>>> PSx: 0.00...10.00 s / Blocked
HSR trip.time IN> PSx: 0.00...10.00 s / Blocked
HSRtrip.time IN>> PSx: 0.00...10.00 s / Blocked
HSRtrip.t. IN>>> PSx: 0.00...10.00 s / Blocked
HSRtrip.t. Iref,P PSx: 0.00...10.00 s / Blocked
HSRtrip.t.Iref,N PSx: 0.00...10.00 s / Blocked
HSRtr.t. Iref,neg PSx: 0.00...10.00 s / Blocked
HSR trip t.GFDSS PSx: 0.00...10.00 s / Blocked
HSRtrip.t. LOGIC PSx: 0.00...10.00 s / Blocked
HSR block.f. I>>> PSx: No / Yes
HSR dead time PSx: 0.15...600.00 s
No. permit. TDR PSx: 0...9
TDR trip.time GS PSx: 0.00...10.00 s / Blocked
TDR trip.time I> PSx: 0.00...10.00 s / Blocked
TDR trip.time I>> PSx: 0.00...10.00 s / Blocked
TDRtrip.time I>>> PSx: 0.00...10.00 s / Blocked
TDR trip.time IN> PSx: 0.00...10.00 s / Blocked
TDRtrip.time IN>> PSx: 0.00...10.00 s / Blocked
TDRtrip.t. IN>>> PSx: 0.00...10.00 s / Blocked
TDRtrip.t. Iref,P PSx: 0.00...10.00 s / Blocked
TDRtrip.t.Iref,N PSx: 0.00...10.00 s / Blocked
TDRtr..t. Iref,neg PSx: 0.00...10.00 s / Blocked
TDR trip t.GFDSS PSx: 0.00...10.00 s / Blocked
TDRtrip.t. LOGIC PSx: 0.00...10.00 s / Blocked
TDR dead time PSx: 0.15...600.00 s
TDR block.f. I>>> PSx: No / Yes
Reclaim time PSx: 1...600 s
Blocking time PSx: 0...600 s
Ground fault direction determination using
steady-state values (GFDSS):
Enable PSx: No / Yes
Op.m.GF pow./adm PSx:
cos phi circuit / sin phi circuit
Evaluation VNG PSx: Calculated / Measured
Meas. direction PSx: Standard / Opposite
VNG> PSx: 0.02...1.00 Vnom(/√3)
tVNG> PSx: 0.02...10.00 s
f/fnom (P meas.) PSx: 1 / 5
f/fnom (I meas.) PSx: 1 / 5
IN,act>/reac> LS PSx: 0.003...1.000 IN,nom
Sector angle LS PSx: 80...89 °
Operate delay LS PSx: 0.00...100.00 s / Blocked
Release delay LS PSx: 0.00...10.00 s
IN,act>/reac> BS PSx: 0.003...1.000 IN,nom
Sector angle BS PSx: 80...89 °
Operate delay BS PSx: 0.00...100.00 s / Blocked
Release delay BS PSx: 0.00...10.00 s
IN> PSx: 0.003...1.000 IN,nom
Operate delay IN PSx: 0.00...100.00 s / Blocked
Release delay IN PSx: 0.00...10.00 s
G(N)> / B(N)> LS PSx: 0.01...1.00 YN,nom
G(N)> / B(N)> BS PSx: 0.01...1.00 YN,nom
Y(N)> PSx: 0.01...2.00 YN,nom
Correction angle PSx: -30...+30°
Oper. delay Y(N)> PSx: 0.00...100.00 s / Blocked
Rel. delay Y(N)> PSx: 0.00...10.00 s
Transient ground fault direction
determination (TGFD):
Enable PSx: No / Yes
Evaluation VNG PSx: Sum (VA-B-C-G) / Measured
Measurem. direc PSx: Standard / Opposite
VNG> PSx: 0.15...0.50 Vnom(/√3)
Operate delay PSx: 0.05...1.60 s
IN,p> PSx: 0.03...0.50 Inom
Buffer time PSx: 0...1200 s / Blocked
Motor protection (MP):
Enable PSx: No / Yes
Iref PSx: 0.10...4.00 Inom
Factor kP PSx: 1.05...1.50
IStUp> PSx: 1.8...3.0 Iref
tIStUp> PSx: 0.1...1.9 s
Character. type P PSx: Reciprocal squared / logarithmic
t6Iref PSx: 1.0...100.0 s
Tau after st-up PSx: 1...60 s
Tau mach. running PSx: 1...1000 min
Tau mach. stopped PSx: 1...1000 min
Permiss.No.st-ups PSx:
2/1 (cold/warm) / 3/2 (cold/warm)
RC permitted, Θ< PSx: 22...60 % / Blocked
Operating mode PSx: Without THERM / With THERM
St-up time t,StUp PSx: 2.0...100.0 s
Blocking time tE PSx: 2.0...100.0 s
I< PSx: 0.2...0.9 Iref / Blocked
tI< PSx: 0.1...20.0 s
Automatic synchonism check (ASC):
Enable PSx: No / Yes
CB assignment PSx: see selection table
System integrat. PSx:
Autom.synchron.check
Autom.synchron.control
Active for HSR PSx: No / Yes
Active for TDR PSx: No / Yes
Clos.rej.w.block PSx: No / Yes
Operative time PSx: 0.0...6000.0 s
Operating mode PSx:
Voltage-checked
Sync.-checked
Volt./sync.-checked
Op.mode volt.chk. PSx:
Vref but not V
V but not Vref
Not V and not Vref
Not V or not Vref
V> volt.check PSx: 0.10...0.80 Vnom(/√3)
V< volt. check PSx: 0.10...0.80 Vnom(/√3)
tmin volt. check PSx: 0.00...10.00 s
Measurement loop PSx:
Loop A-G/ B-G/ C-G/ A-B/ B-C/ C-A
V> sync. check PSx: 0.40...1.20 Vnom(/√3)
Delta Vmax PSx: 0.02...0.40 Vnom
Delta f max PSx: 0.03...1.00 Hz
Delta phi max PSx: 5...100 °
Phi offset PSx: -180...180 °
tmin sync. check PSx: 0.00...10.00 s
P132-306-415/416/417/418/419-612 ff
Thermal overload protection (THERM):
Enable PSx: No / Yes
Sel. backup th. PSx: see selection table
Iref PSx: 0.10...4.00 Inom
Start.fact OL_RC PSx: 1.05...1.50
Tim.const.1,>Ibl PSx: 1.0...1000.0 min
Tim.const.2,<Ibl PSx: 1.0...1000.0 min
Max.perm.obj.tmp. PSx: 0...300 °C
Max. perm.cool.temp. PSx: 0...70 °C
Select.meas.input PSx: see selection table
Default CTA PSx: -40...70 °C
Bl. f. CTA fault PSx: No / Yes
Rel. O/T warning PSx: 50...200 %
Rel. O/T trip PSx: 50...200 %
Hysteres.is trip PSx: 2...30 %
Warning pre-trip PSx: 0.0...1000.0 min / Blocked
29
P132_TechnicalDataSheet_EN_12_b
Unbalance protection (I2>):
Enable PSx: No / Yes
Ineg> PSx: 0.10...0.80 Inom / Blocked
Ineg>> PSx: 0.10...0.80 Inom / Blocked
tIneg> PSx: 0.00...100.00 s / Blocked
tIneg>> PSx: 0.00...100.00 s / Blocked
Directional power protection (P<>):
Enabled PSx: No / Yes
Valid for y = ‚>‘ and ‚>>‘:
Py PSx: 0.010...1.500 Snom / Blocked
Qy PSx: 0.010...1.500 Snom / Blocked
Diseng. ratio Py PSx: 0.05...0.95
Diseng. ratio Qy> PSx: 0.05...0.95
Valid for y = ‚<‘ and ‚<<‘:
Py PSx: 0.010...0.500 Snom / Blocked
Qy PSx: 0.010...0.500 Snom / Blocked
Diseng. ratio Py PSx: 1.05...20.00
Diseng. ratio Qy PSx: 1.05...20.00
Valid for y = ‚>‘ and ‚>>‘ and ‚<‘ and ‚<<‘:
Operate delay Py PSx: 0.00...100.00 s / Blocked
Release delay Py P Sx: 0.00...100.00 s
Direction Py PSx:
Forward directional
Backward directional
Non-directional
Operate delay Qy PSx: 0.00...100.00 s / Blocked
Release delay Qy PSx: 0.00...10.00 s
Direction Qy PSx:
Forward directional
Backward directional
Non-directional
tTransient pulse PSx: 0.00...100.00 s
Over-/undervoltage protection (V<>):
Enable PSx: No / Yes
Operating mode PSx: Delta / Star
I enable V< PSx: 0.04...1.00 Inom
Op.mode V< mon. PSx: Without / With
Evaluation VNG PSx: Calculated / Measured
V> PSx: 0.20...1.50 Vnom(/√3) / Blocked
V>> PSx: 0.20...1.50 Vnom(/√3) / Blocked
tV> PSx: 0.00...100.00 s / Blocked
tV> 3-pole PSx: 0.00...100.00 s / Blocked
tV>> PSx: 0.00...100.00 s / Blocked
V< PSx: 0.20...1.50 Vnom(/√3) / Blocked
V<< PSx: 0.20...1.50 Vnom(/√3) / Blocked
tV< PSx: 0.00...100.00 s / Blocked
tV< 3-pole PSx: 0.00...100.00 s / Blocked
tV<< PSx: 0.00...100.00 s / Blocked
Vpos> PSx: 0.20...1.50 Vnom/√3 / Blocked
Vpos>> PSx: 0.20...1.50 Vnom/√3 / Blocked
tVpos> PSx: 0.00...100.00 s / Blocked
tVpos>> PSx: 0.00...100.00 s / Blocked
Vpos< PSx: 0.20...1.50 Vnom/√3 / Blocked
Vpos<< PSx: 0.20...1.50 Vnom/√3 / Blocked
tVpos< PSx: 0.00...100.00 s / Blocked
tVpos<< PSx: 0.00...100.00 s / Blocked
Vneg> PSx: 0.20...1.50 Vnom/√3 / Blocked
Vneg>> PSx: 0.20...1.50 Vnom/√3 / Blocked
tVneg> PSx: 0.00...100.00 s / Blocked
tVneg>> PSx: 0.00...100.00 s / Blocked
VNG> PSx: 0.02...1.00 Vnom(/√3) / Blocked
VNG>> PSx: 0.02...1.00 Vnom(/√3) / Blocked
tVNG> PSx: 0.00...100.00 s / Blocked
tVNG>> PSx: 0.00...100.00 s / Blocked
tTransient PSx: 0.00...100.00 s / Blocked
Hyst. V<> meas. PSx: 1...10 %
Hyst. V<> deduc. PSx: 1...10 %
Control
Main function (MAIN):
BI active USER: No / Yes
SI active USER: No / Yes
Inp.asg. fct.block.1: see selection table
Inp.asg. fct.block.2: see selection table
Op. delay fct. block: 0...60 s
CB1 max. oper. cap.: 1...99
CB1 ready fct.assign: see selection table
External device (DEV01 to DEV03):
Designat. ext. dev.: see selection table
Op.time switch. dev.: 0...254 s
Latching time: 0.00...5.00 s
Gr. assign.debounce: Group 1 ... Group 3
Interm. pos. suppr.: No / Yes
Stat.ind.interm.pos.: No / Yes
Oper.mode cmd:
Long command / Short command / Time control
Inp.asg. sw.tr. plug: see selection table
With gen.trip cmd.1: No / Yes
With gen.trip cmd.2: No / Yes
With close cmd./prot: No / Yes
Inp.asg.el.ctrl.open: see selection table
Inp.asg.el.ctr.close: see selection table
Inp. asg. end Open: see selection table
Inp. asg. end Close: see selection table
Open w/o stat.interl: No / Yes
Close w/o stat. int.: No / Yes
Fct.assig.BIwSI open: see selection table
Fct.assig.BIwSI clos: see selection table
Fct.asg.BI w/o SI op: see selection table
Fct.asg.BI w/o SI cl: see selection table
Over-/ underfrequency protection (f<>):
Enable PSx: No / Yes
Valid for y = ‚1‘ to ‚4‘
Oper. mode fy PSx:
f
f with df/dt
f w. Delta f/Delta t
fy PSx: 40.00...70.00 Hz / Blocked
tfy PSx: 0.00...10.00 s / Blocked
dfy/dt PSx: 0.1...10.0 Hz/s / Blocked
Delta fy PSx: 0.01...5.00 Hz / Blocked
Delta ty PSx: 0.04...3.00 s
Interlocking logic (ILOCK):
Valid for y = ‚1‘ to ‚32‘
Fct.assignm. outp. y: see selection table
P132_TechnicalDataSheet_EN_12_b
30
P132-306-415/416/417/418/419-612 ff
Voltage A-G p.u.: 0.000...25.000 Vnom
Voltage B-G p.u.: 0.000...25.000 Vnom
Voltage C-G p.u.: 0.000...25.000 Vnom
Volt. Σ(VPG)/√3 p.u.: 0.000...12.000 Vnom
Voltage VNG p.u.: 0.000...25.000 VNG,nom
Voltage Vref p.u.: 0.000...3.000 Vnom
Voltage VPP,max p.u.: 0.000...25.000 Vnom
Voltage VPP,min p.u.: 0.000...25.000 Vnom
Voltage A-B p.u.: 0.000...25.000 Vnom
Voltage B-C p.u.: 0.000...25.000 Vnom
Voltage C-A p.u.: 0.000...25.000 Vnom
Voltage Vpos p.u.: 0.000...25.000 Vnom
Voltage Vneg p.u.: 0.000...25.000 Vnom
Appar. power S p.u.: -10.700...10.700 Snom
Active power P p.u.: -7.500...7.500 Snom
Reac. power Q p.u.: -7.500...7.500 Snom
Active power factor: -1.000...1.000
Load angle phi A: -180...180 °
Load angle phi B: -180...180 °
Load angle phi C: -180...180 °
Angle phi N: -180...180 °
Load angle phi A p.u.: -1.80...1.80 phi.ref
Load angle phi B p.u.: -1.80...1.80 phi.ref
Load angle phi C p.u.: -1.80...1.80 phi.ref
Angle phi N p.u.: -1.80...1.80 phi.ref
Angle ΣVPG vs. IN: -180...180 °
Angle ΣVPG/IN p.u.: -1.80...1.80 phi.ref
Phase rel.,IN vs ΣIP:
Equal phase / Reverse phase
Current ΣI unfilt. 0.000...25.000 Inom
Measured Operating Data
Logical Communication interface InterMiCOM (COMM3):
No. tel.errors p.u.: 0.0...100.0 %
No.t.err. max,stored: 0.0...100.0 %
Loopback result:
Not measured
Passed
Failed
Loopback receive: 0...255
Measured Data Input (MEASI):
Valid for y = ‚1‘ to ‚9 ‘
Temperature Ty: -40.0...215.0 °C
Temp. Ty max.: -40.0...215.0 °C
Temperature p.u. Ty: -0.40...2.15 100°C
Current IDC: 0.00...24.00 mA
Current IDC p.u.: 0.00...1.20 IDC,nom
Curr. IDC,lin. p.u.: 0.00...1.20 IDC,nom
Scaled value IDC,lin: -32000...32000
Temperature T: -40.0...215.0 °C
Temperature Tmax : -40.0...215.0 °C
Temperature p.u. T: -0.40...2.15 100 °C
Measured Data Output (MEASO):
Current A-1: 0.00...20.00 mA
Current A-2: 0.00...20.00 mA
Main Function (MAIN):
Date: 01.01.1997...31.12.2096 dd.mm.yy
Time: 00:00:00...23:59:59 hh:mm:ss
Time switching: Standard time / Daylight saving time
Frequency f: 40.00...70.00 Hz
Curr. IP,min prim.: 0...25000 A
IP,max prim.,delay: 0...25000 A
IP,max prim.,stored: 0...25000 A
Curr. IP,min prim.: 0...25000 A
Current A prim.: 0...25000 A
Current B prim.: 0...25000 A
Current C prim.: 0...25000 A
Current Σ (IP) prim.: 0...25000 A
Current IN prim.: 0...25000 A
Volt. VPG,max prim.: 0.0...2500.0 kV
Volt. VPG,min prim.: 0.0...2500.0 kV
Voltage A-G prim.: 0.0...2500.0 kV
Voltage B-G prim.: 0.0...2500.0 kV
Voltage C-G prim.: 0.0...2500.0 kV
Volt. Σ(VPG)/3 prim.: 0.0...2500.0 kV
Voltage VNG prim.: 0.0...2500.0 kV
Voltage Vref prim.: 0.0...3000.0 kV
Volt. VPP,max prim.: 0.0...2500.0 kV
Volt. VPP,min prim.: 0.0...2500.0 kV
Voltage A-B prim.: 0.0...2500.0 kV
Voltage B-C prim.: 0.0...2500.0 kV
Voltage C-A prim.: 0.0... 2500.0 kV
Volt. VPG, min prim: 0.0…2500.0 kV
Appar.power S prim.: -1399.9...1400.0 MVA
Active power P prim.: -999.9...1000.0 MW
Reac. power Q prim.: -999.9...1000.0 Mvar
Act.energy outp.prim: 0.00...655.35 MWh
Act.energy inp. prim: 0.00...655.35 MWh
React.en. outp. prim: 0.00...655.35 Mvar h
React. en. inp. prim: 0.000...655.35 Mvar h
Frequency f p.u.: 0.200...4.000 fnom
Current IP,max p.u.: 0.000...25.000 Inom
IP,max p.u.,delay: 0.000...25.000 Inom
IP,max p.u.,stored: 0.000...25.000 Inom
Current IP,min p.u.: 0.000...25.000 Inom
Current A p.u.: 0.000...25.000 Inom
Current B p.u.: 0.000...25.000 Inom
Current C p.u.: 0.000...25.000 Inom
Current Σ (IP) p.u.: 0.000...25.000 Inom
Current IN p.u.: 0.000...16.000 IN,nom
Current Ipos p.u.: 0.000...25.000 Inom
Current Ineg p.u.: 0.000...25.000 Inom
Voltage VPG,max p.u.: 0.000...25.000 Vnom
Voltage VPG,min p.u.: 0.000...25.000 Vnom
P132-306-415/416/417/418/419-612 ff
Ground fault direction determination using
steady-state values (GFDSS):
Current IN,act p.u.: 0.000...30.000 IN,nom
Curr. IN,reac p.u.: 0.000...30.000 IN,nom
Curr. IN filt. p.u.: 0.000...30.000 IN,nom
Admitt. Y(N) p.u.: 0.000... 5.000 YN,nom
Conduct. G(N) p.u.: -5.000... 5.000 YN,nom
Suscept. B(N) p.u.: -5.000... 5.000 YN,nom
Motor Protection (MP):
Therm.repl.buffer MP: 0...100 %
St-ups still permitt: 0...3
Therm. repl. MP p.u.:0.00...1.00 100%
St-ups st. perm.p.u.: 0.00...0.30 factor 10
Thermal overload protection (THERM):
Status THERM replica: -25000...25000 %
Object temperature: -40...300 °C
Coolant temperature: -40...200 °C
Pre-trip time left: 0.0...1000.0 min
Therm. replica p.u.: -2.50...2.50 100 %
Object temp. p.u.: -0.40...3.00 100 °C
Coolant temp.p.u.: -0.40...0.20 100 °C
Temp. offset replica: -25000...25000 %
31
P132_TechnicalDataSheet_EN_12_b
Dimensions
Surface-mounted case 24T
ALARM
OUT OF SERVICE
HEALTHY
184.5
TRIP
177.5
147.5
Mi COM P1 3 2
Pa r a me t e r s
EDIT MODE
139.6
257.1
168.8
186.4
Surface-mounted case 40 T
TRIP
ALARM
Mi COM P 1 3 2
P a r a me t e r s
OUT OF SERVICE
HEALTHY
184.5
177.5
147.5
EDIT MODE
213.4
257.1
242.6
260.2
Figure 14: Dimensional drawings for surface-mounted case, part 1
P132_TechnicalDataSheet_EN_12_b
32
P132-306-415/416/417/418/419-612 ff
Surface-mounted case 84T
TRIP
ALARM
Mi COM P1 3 2
Pa r a me t e r s
OUT OF SERVICE
HEALTHY
184.5
177.5
147.5
EDIT MODE
257.1
434.8
464.0
481.6
Figure 15: Dimensional drawings for surface-mounted case, part 2
Flush-mounted case 24T with panel cutout, version 1 (without angle brackets)
177.5
Mi COM P1 3 2
P a r a me t e r s
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
139.6
227.9
253.6
129.2
168.0
159.0
77.5
5.0
5.0
103.8
Figure 16: Dimensional drawings for flush-mounted case version 1 (without angle brackets), part 1
P132-306-415/416/417/418/419-612 ff
33
P132_TechnicalDataSheet_EN_12_b
Flush-mounted case 40T with panel cutout, version 1 (without angle brackets)
TRIP
ALARM
Mi COM P1 3 2
P a r a me t e r s
OUT OF SERVICE
HEALTHY
177.5
EDIT MODE
227.9
213.4
253.6
203.0
168.0
159.0
155.4
5.0
5.0
181.3
Flush-mounted case 84T with panel cutout, version 1 (without angle brackets)
TRIP
ALARM
Mi COM P1 3 2
Pa r a me t e r s
OUT OF SERVICE
HEALTHY
177.5
EDIT MODE
227.9
434.8
253.6
284.9
259.0
168.0
159.0
25.9
5.0
5.0
410.0
Figure 17: Dimensional drawings for flush-mounted case version 1 (without angle brackets), part 2
P132_TechnicalDataSheet_EN_12_b
34
P132-306-415/416/417/418/419-612 ff
Flush-mounted case 24T with panel cutout, Version 2 (with angle brackets and frame)
101.6
177.5
Mi COM P1 3 2
P a r a me t e r s
TRIP
ALARM
OUT OF SERVICE
HEALTHY
EDIT MODE
139.6
227.9
253.6
168.8
186.4
101.6
186.5
6.4
150.7
168.8
Flush-mounted case 40T with panel cutout, Version 2 (with angle brackets and frame)
TRIP
ALARM
Mi COM P 1 3 2
P a r a me t e r s
OUT OF SERVICE
HEALTHY
101.6
177.5
EDIT MODE
213.4
227.9
253.6
242.6
260.2
101.6
186.5
6.4
224.5
242.6
Figure 18: Dimensional drawings for flush-mounted case version 2 (with angle brackets and frame), part 1
P132-306-415/416/417/418/419-612 ff
35
P132_TechnicalDataSheet_EN_12_b
Flush-mounted case 84T with panel cutout, Version 2 (with angle brackets and frame)
TRIP
ALARM
Mi CO M P 1 3 2
P a r a me t e r s
OUT OF SERVICE
HEALTHY
101.6
177.5
EDIT MODE
434.8
227.9
253.6
464.0
481.6
101.6
186.5
6.4
445.9
464.0
Figure 19: Dimensional drawings for flush-mounted case version 2 (with angle brackets and frame), part 2
P132_TechnicalDataSheet_EN_12_b
36
P132-306-415/416/417/418/419-612 ff
Front view 40T case for connection of a detachable HMI
WARNING:
Connection for remote
control panel only.
Not for network
connection!
Front view 84T case for connection of a detachable HMI
WARNING:
Connection for remote
control panel only.
Not for network
connection!
Aus-Kommando
Warnung
Block./Störung
Mi COM P1 32
Pa r a me t e r s
Betrieb
177,5
Änderungsmod.
213,4
107,3
Detachable HMI with panel cutout
20,7
46,3
197,5
168,0
148,0
192,5
3,0
181,3
Figure 20: Dimensional drawings for detachable HMI
P132-306-415/416/417/418/419-612 ff
37
P132_TechnicalDataSheet_EN_12_b
Location of the modules
MiCOM P132 in cases 24T and 40T
- Pin-terminal connection (24T: diagram P132 -415, 40T: diagram P132 -417)
- Transformer board ring-, other boards pin terminal connection
(24T: diagram P132 -416, 40T: diagram P132 -418)
01 02 03 04 05 06 07 08 09 10
P A N
CH1
CH2
alt.
A
alt.
Y
T
X X X V X
-/4I
6I 6I 24I 4I
8O 6O
-/4V/5V 6O 6O
alt. alt. alt.
alt.
alt.
X X Y
X
A
6I 6I 4I
8O 8O
4H
9T
ETH
CH2 CH3
01 02 03 04 05 06 07 08 09 10
MiCOM P132 in case 84T
- Ring-terminal connection (diagram P132 -419)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A N
T
X
X
X
-/4I
-/4V/5V
6I
6O
6I
6O
24I
alt. 9T
alt.
alt.
alt.
alt.
alt.
X
X
Y
X
A
6I
8O
6I
8O
4I
CH1
CH2
A
alt.
Y
ETH
CH2 CH3
X
V
6O
4I
8O
4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Figure 21: Location diagrams
Transformer
module
Ring
Pin
X04
X041
1
1
13
2
14
3
15
4
16
5
17
6
Type T
-/4J -/4/5V
Voltage measuring
inputs
Option:
U
T5
V
T6
W
T7
N
N(e)
T90
E(n)
18
7
11
8
Option:
1U
2U
2
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Current measuring
inputs
Option:
T1
IA
IB
T2
IC
T3
IN
Ring
Pin
X_1
X_1
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
T15
12
X04
Power supply
module
Type V
4I / 8O
Output relays
K_01
K_02
K_03
X_2
10
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
K_04
K_05
K_06
K_07
K_08
Signal inputs
Vin
T4
U_01
X_3
19
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
Vin
Vin
Vin
U_02
U_03
U_04
Power supply
+ Vaux
-
U100
PE
‘_‘is used as a wildcard for the location
Figure 22
Terminal connection diagrams of the modules, part 1
P132_TechnicalDataSheet_EN_12_b
38
P132-306-415/416/417/418/419-612 ff
Type X
6I / 8O
5
5
6
6
7
7
7
8
8
8
9
9
9
5
5
6
6
7
8
9
K_01
K_02
K_01
K_02
K_03
K_03
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
K_04
K_05
K_06
10
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
X_3
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
K_08
9
U_01
Vin
U_02
Vin
19
1
20
2
U_04
Vin
21
3
22
4
23
5
24
6
25
7
26
8
27
9
Vin
U_06
Type A
CH1 / CH2
4
5
5
6
6
7
7
8
8
9
9
X_2
10
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
U_09
U_10
U_11
U_12
U_13
U_14
U_15
U_16
U_01
Vin
Vin
Vin
Vin
Communication
module
U_02
U_03
U_04
U_05
19
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
Vin
U_17
U_18
U_19
U_20
U_21
U_22
U_23
U_24
U_06
Type A
ETH / CH2
Communication
Type A
module (InterMiCOM)
CH3
Per order
Per order
Channel 1
optical fiber link
IEC 61850
optical fiber link ST
COMM3
optical fiber link
X7
X//Y U17
X31
RX
X/Y
U17
X8
X//Y U18
U18
X13
D2[R]
3
X/Y
or
optical fiber link SC
X//Y
D1[T]
X//Y U22
1
X//Y U23
or wire link
X33
U26
D1[T]
RS 485
and wire link
1
2
4
5
X//Y U25
X10
1
2
U21
4
COMM2
wire link
U20
D1[T]
#
M5[DCD]
D2[R]
D1[T]
2
3
D2[R]
#
X34
1
RJ45
IRIG-B
time synchronization
1
X//Y
1
RS 485
X11
or wire link
X12
X//Y
3
5
5
E
E2[G]
7
X//Y
+UB
D2[R]
3
4
2
3
3
X_1
Meas. inputs
1
K_01
2
valid
4
4
4
5
5
6
6
7
7
8
8
9
9
0..20 mA
5
7
U_08
U82
#
6
#
U81
#
3
8
U83
#
9
K_02
valid
10
1
11
2
12
3
1
0..20 mA
2
4
U_09
5
7
13
4
14
5
15
6
16
7
17
8
18
9
Vin
U_01
Vin
U_02
Vin
U_03
Vin
U_04
8
X_3
1
2
4
5
6
1
7
20
2
21
3
22
4
23
5
24
6
Binary
module
#
U_06
6O
Pin
X_1
X_1
1
1
2
2
3
3
4
4
5
U89
#
9
Type X
Ring
U88
#
8
U_05
#
U87
#
3
19
PT100
U86
#
9
X_3
0..20 mA
U85
#
6
Signal and
measuring inputs
U84
#
3
#
Binary
module
Type X
4H
Ring
Pin
X_1
X_1
1
1
2
2
3
3
4
4
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
9
9
9
9
Output relays
K_01
K_02
X_2
U24
4
RS 485
X10
2
D2[R]
2
3
X/Y
TX
5
Channel 2
wire link only
1
High-break
contacts
K_01
+
X//Y
1
RX
U19
1
X32
TX
or wire link
Pin
Measuring outputs
X_2
Vin
Per order
1
5
Vin
U_05
X8
4
4
U_01
U_02
U_03
U_04
U_05
U_06
U_07
U_08
X_3
U_03
Vin
1
2
3
X_3
Vin
X7
1
Vin
Signal inputs
Communication
module
X9
2
3
1
9T
X_2
K_04
K_05
K_06
K_07
Signal inputs
19
1
2
X_2
X_2
10
1
Vin
X_1
U
4
4
X_1
Pin
X_1
U
3
4
3
4
X_1
Ring
Type Y
U
2
3
2
3
Signal inputs
RTD
module
U
2
2
Pin
4I
U
1
1
Ring
Output relays
Type Y
U
1
1
Output relays
Analog
module
U
X_1
X_1
24I
U
Pin
X_1
Pin
X_1
Type X
U
Ring
Ring
Binary
module
U
Binary
module
U
6I / 6O
U
Type X
U
Binary
module
RS 232
U20
D1[T]
X_2
1)
10
1
10
1
11
2
11
2
12
3
12
3
13
4
13
4
14
5
14
5
15
6
15
6
16
7
16
7
17
8
17
8
18
9
18
9
1)
K_03
X_3
U27
19
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
K_02
+
X_3
1)
K_04
1)
K_05
K_06
19
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
K_03
+
K_04
+
RS 485
‘_‘ is used as a wildcard fort he location
Binary module X (6O) optional with 4 static outputs, in parallel with closer contact K_02.2, K_03.1, K_04, K_05
1)
Figure 23: Terminal connection diagrams of the modules, part 2
P132-306-415/416/417/418/419-612 ff
39
P132_TechnicalDataSheet_EN_12_b
Connection Examples
Figure 24: Connection example currents and voltages
Power supply
Disconnector
Q1
Circuit
breaker
Q0
OPEN
CLOSE
X061:
X061:
X061:
X061:
5
6
3
4
Earthing
switch
Q8
1
2
Vin
X063: 1
Vin
X063: 2
X063: 3
X063: 4
Vin
X063: 5
X063: 6
X063: 7
Vin
Vin
Vin
X063: 8
X063: 9
P132 (Detail)
Figure 25: Connection example optional control
P132_TechnicalDataSheet_EN_12_b
40
P132-306-415/416/417/418/419-612 ff
Ordering Information
MiCOM P132
Feeder Management and Bay Control P132
P132-
Basic device:
Basic device 24TE, pin-terminal connection,
Basic device 24TE, CT/VT ring-, I/O pin-terminal connection,
Basic device 40TE, pin-terminal connection,
Basic device 40TE, CT/VT ring-, I/O pin-terminal connection,
Basic device 84TE, ring-terminal connection,
basic complement with 4 binary inputs and 8 output relays;
6 function keys (40TE and 84TE only)
Mounting option and display:
Surface-mounted, local control panel with text display
Flush-mounted, local control panel with text display
16)
Surface-mounted, with detachable HMI
16)
Flush-mounted, with detachable HMI
Current transformer:
11)
Without
9
0
-306
1
2
3
5
8
-4xx
-612
-7xx
-46x
-9x x -9x x
-8xx
-415
-416
-417
-418
-419
3
4
7
9
0
Inom = 1 A / 5 A (T1...T4)
9
2)
Voltage transformer:
11)
Without
Vnom = 50 ... 130 V (4-pole)
12)
Vnom = 50 ... 130 V (5-pole) f. Automatic Synchronism Check
0
4
5
16)
Additional binary I/O options:
Without
With 1 binary module (add. 6 binary inputs and 8 output relays)
0
1
With 2 binary modules (add. 12 binary inputs and 16 output relays)
2
With 1 binary module (add. 6 binary inputs and 6 output relays)
for the control of up to 3 switchgear units
With 1 binary module (add. 6 binary inputs and 6 output relays)
and 1 binary module (add. 6 binary inputs and 6 output relays)
for the control of up to 3 switchgear units
With 1 binary module (add. 6 binary inputs and 8 output relays)
and 1 binary module (add. 6 binary inputs and 6 output relays)
for the control of up to 3 switchgear units
5
6
8
Power supply and additional outputs:
VA,nom = 24 VDC
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC
VA,nom = 24 VDC and 6 output relays, 4 with thyristor
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC
and 6 output relays, 4 with thyristor
VA,nom = 24 VDC and 6 output relays
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 6 output relays
VA,nom = 24 VDC and 4 high break contacts
VA,nom = 48 ... 250 VDC / 100 ... 230 VAC and 4 high break contacts
3
4
6
7
8
9
C
D
16)
Further add. options:
Without
3) 10)
With TGF (transient ground fault direction determination) module
With analogue module
3) 10)
With TGF and analogue module
With binary module (add. 24 binary inputs)
3) 10)
With TGF and binary module (add. 24 binary inputs)
3) 12)
With RTD module
3) 12)
With RTD and analogue module
3) 12)
With RTD module and binary module (add. 24 binary inputs)
Switching threshold on binary inputs:
>18 V (standard variant)
8)
>90 V (60...70% of VA,nom = 125...150 V)
8)
>155 V (60...70% of VA,nom = 220...250 V)
8)
>73 V (67% of VA,nom = 110 V)
8)
>146 V (67% of VA,nom = 220 V)
0
1
2
3
4
5
7
8
9
Without order extension no.
-461
-462
-463
-464
With communication / information interface:
Only IRIG-B input for clock synchronization
Protocol can be switched between:
IEC 60870-5-101/-103, Modbus, DNP3, Courier
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)
For connection to wire, RS485, isolated
For connection to plastic fibre, FSMA connector
For connection to glass fibre, ST connector
Protocol IEC61850:
For connection to 100 Mbit/s Ethernet, glass fibre SC and wire RJ45
and 2nd interface (RS485, IEC 60870-5-103)
For connection to 100 Mbit/s Ethernet, glass fibre ST and wire RJ45
and 2nd interface (RS485, IEC 60870-5-103)
-90 0
-92
1
2
4
-94
6
7
16)
With guidance / protection interface:
Protocol InterMiCOM
For connection to wire, RS485, isolated
For connection to plastic fibre, FSMA connector
For connection to glass fibre, ST connector
For connection to wire, RS232, isolated
Language:
4)
English (German)
4)
Px40 English (English)
4)
German (English)
4)
French (English)
4)
Spanish (English)
4)
Polish (English)
4) 7)
Russian (English)
-95
1
2
4
5
Without order extension no.
on request
on request
on request
on request
on request
-800
-801
-802
-803
-804
-805
2) Switching via parameter, default setting is underlined!
3) This option is excluded if the InterMiCOM (-95x) is ordered
4) Second included language in brackets
7) Hardware option, supports cyrillic letters instead of special West. Europe characters
8) Standard variant recommended, if higher pickup threshold not explicitly required by the application
10) Transient ground fault option for variants with current and voltage transformers only
11) Option without current transformers and without voltage transformers not possible
12) Option without current transformer not possible
16) Options for basic device 24 TE not possible
P132-306-415/416/417/418/419-612 ff
41
P132_TechnicalDataSheet_EN_12_b
T&D Worldwide Contact Centre
Available 24h a day: +44 (0) 1785 25 00 70
contact.centre@areva-td.com
www.areva-td.com
Download