30, 60 and 100 Amp
Enclosure Type 3,4,4X,12
IP66
UL and cUL Listed
Typedriver Name: TS name csm no.: 100
Watertight
Corrosion-Resistant
Fused and Non-Fused
WSRD SMS901 SERIES
STAINLESS STEEL
ARKTITE® INTERLOCKED
RECEPTACLES
Cooper Crouse-Hinds Arktite
Stainless Steel Interlocks
prevent engagement and
disengagement of the plug
under load, providing safe
portable connections and
extended product life.
Available in 30-100 Amp in both
fused and nonfused versions,
the Stainless Steel Interlock is
rated Enclosure Type 4X
watertight and features an
optional viewing window.
Arktite stainless steel
interlocked receptacles:
ឣ supply power to portable or
fixed electrical equipment such
as welders, compressors,
conveyors, portable tools,
lighting systems and similar
equipment.
ឣ are used in damp or corrosive
locations.
ឣ are ideal for use in wet
locations & hosedown areas.
ADDITIONAL FEATURES AND BENEFITS
ɀ Heavy duty Arktite receptacle is compatible with existing Cooper Crouse-Hinds Arktite plugs
of same rating and configuration.
ɀ Self-wiping, naval brass contacts in receptacle assure reliable performance and long
dependable life
ɀ Stainless steel interior hardware.
ɀ Ground bar supplied as standard and connected to 4th wire in receptacle.
ɀ UL and cUL Listed
ORDERING INFORMATION (3 Pole, 4 Wire - 600 VAC)
Catalog
Amps Number
1020
STIBOINFO((CRH:66008com:3P:1020))
CH0 0 4 F - 5
US: 1-866-764-5454
Description
Cooper Crouse-Hinds
Weight Mating Arktite Plug
lbs.
Catalog Numbers
30
30
30
WSRDW3352SMS901
WSRD33542SMS901
WSRDW33542SMS901
Fused w/Window
Non-Fused
Non-Fused w/Window
24
22
22
APJ3485 & NPJ3485
APJ3485 & NPJ3485
APJ3485 & NPJ3485
60
60
60
WSRDW6352SMS901
WSRD63542SMS901
WSRDW63542SMS901
Fused w/Window
Non-Fused
Non-Fused w/Window
30
29
29
APJ6485 & NPJ6485
APJ6485 & NPJ6485
APJ6485 & NPJ6485
100
100
100
WSRDW10352SMS901
Fused w/Window
WSRD103542SMS901
Non-Fused
WSRDW103542SMS901 Non-Fused w/Window
36
35
35
APJ10487 & NPJ10487
APJ10487 & NPJ10487
APJ10487 & NPJ10487
CAN: 1-800-265-0502
Copyright© 2006 Cooper Crouse-Hinds
Zoom: 100
2:
5:
SYS19: BASE2
PDFINFO
50:
95:
98:
JOB: CRMAIN06-1018-1 Name: 3P-1018
100:
DATE: JAN 19 2006
Typedriver Name: TS name csm no.: 100
30,60,100A
NEMA 3,3R,4,4X,12
Raintight
Watertight
Corrosion-Resistant
WSR
WSRD
WSRDW
Sheet Metal
NEMA 3R,12
Sheet Metal
Viewing Window
NEMA 3R,12
ɀ The WSR and WSRD disconnect switches
are used as a service outlet for portable or
fixed electrical equipment – generators,
compressors, welders, etc.
ɀ They are designed for use in nonhazardous areas where dust, moisture and
corrosion may be a problem.
ɀ Designed for flush or surface mounting.
ɀ A fusible type switch, when used, also
provides short circuit protection.
Features:
WSR and WSRD:
ɀ Switches are NEMA type HD heavy duty
3-pole, with visible blades; a quick makeand-break mechanism with reinforced,
positive pressure type blade and jaw
construction. Fusible types have fuse clips
with steel reinforcing springs of positive
pressure type. Pressure connectors are used
for wire connectors.
ɀ For maximum safety, the spring door
receptacle at the bottom of the unit is
mechanically interlocked with the switch
operating mechanism. The switch cannot be
closed until the plug is fully inserted and the
plug cannot be withdrawn or inserted unless
the switch is open. With the switch open,
accidental plug withdrawal is prevented by
the interlock mechanism. Withdrawal can
only be accomplished by activation of the
interlock release lever located on the
receptacle.
ɀ Enclosures are compact and rectangular in
shape with a gasketed, hinged door.
ɀ Enclosure, handle and other exterior parts
are corrosion resistant.
STIBOINFO((CRH:66008com:3P:1018))
TCP: 15001
Aluminum
NEMA 3R,12
Application:
CH0 0 3 P - 2
COLOR: CMYK
WSR, WSRD, WSRDW Interlocked Arktite®
Receptacles with
Enclosed Disconnect Switches
3P
1018
Time: 6:08:42 PM Operator: RB
ɀ The switch enclosure covers are
interlocked with the body and operating
mechanism and cannot be opened when the
plug is engaged and the switch is closed
(‘‘ON’’). When the switch is open, the switch
cannot be put in a closed (‘‘ON’’) position
with the door open.
WSR:
ɀ Mounting lugs may be rotated 90° or
moved to the vertical centerline portion for
pole mounting.
ɀ Side hinged covers are retained in a closed
position by compression spring draw-pull
catches, which permit the opening or closing
of the cover without tools.
ɀ The switch operating handle may be
padlocked in the ‘‘ON’’ or ‘‘OFF’’ position,
thereby preventing unauthorized operation of
the switch and/or opening of the enclosure.
Up to three padlocks may be used. In
addition, a unique hinge arrangement has
been devised to allow the door of the unit to
be padlocked. This feature allows operation
while preventing unqualified or unauthorized
entry.
Standard Materials:
WSR and WSRD:
ɀ Receptacle housings and plug exteriors –
copper-free aluminum
ɀ Insulation (plug and receptacle) –
fiberglass-reinforced polyester
ɀ Pressure contacts – brass
ɀ Crimp/solder contacts – leaded red brass
WSR:
ɀ Enclosure – copper-free aluminum
ɀ Operating handle – copper-free aluminum
ɀ Other exterior parts – stainless steel
WSRD:
ɀ Enclosure – sheet steel
ɀ Operating handle – sheet steel
ɀ Other exterior parts – stainless steel
US: 1-866-764-5454
CAN: 1-800-265-0502
Standard Finishes:
ɀ Copper-free aluminum – WSR enclosure,
plug exteriors – natural
ɀ Leaded red brass – electro-tin-plate
ɀ Brass – natural
ɀ Sheet steel – baked grey enamel
ɀ Fiberglass-reinforced polyester – natural
(red)
Electrical Rating Ranges:
ɀ 3 and 4 pole; fusible or non-fusible; 240
vac, 250 vdc; 600 vac
ɀ 30, 60, 100 amperes
ɀ 71⁄2 to 75 HP
Certifications and
Compliances:
WSR:
ɀ NEMA 3R, 4, 12 (enclosure)
ɀ UL Standard 98
WSRD:
ɀ NEMA 3R, 12
ɀ UL Standard 98
Options:
ɀ Interiors rotated 221⁄2° to the right (viewed
from face) – add suffix S4 to Cat. No.
ɀ Auxiliary switch, 600 vac-dc heavy duty
push button station rating, can be supplied,
and its contacts will close after safety switch
contacts open and close before safety switch
opens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . S483
ɍɍ Pressure connectors are supplied as standard. To
specify crimp/solder type terminations, add the suffix ‘‘T’’ to
the catalog number. For example: APJ3375-T (Plug)
Copyright© 2006 Cooper Crouse-Hinds
Zoom: 100
2:
5:
SYS19: BASE2
PDFINFO
50:
95:
98:
100:
JOB: CRMAIN06-1022-3 Name: 3P-1022
3P
DATE: JAN 19 2006
Time: 6:08:49 PM Operator: JB COLOR: CMYK
Arktite® WSRD SM S901
Stainless Steel Interlocked
Receptacles
TCP: 15001
30, 60 and 100 Amp
Enclosure Type 3,4,4X,12
IP66
UL and cUL Listed
Typedriver Name: TS name csm no.: 100
Watertight
Corrosion-Resistant
Fused and Non-Fused
HORSEPOWER RATINGS
Cooper Crouse-Hinds
Catalog Number
WSRD33542SMS901
WSRDW33542SMS901
WSRDW3352SMS901
240 VAC
(1 PH)
5
5
1.5 (3)
240 VAC
(3 PH)
10
10
3 (7.5)
480 VAC
(1 PH)
7.5
7.5
3 (7.5)
480 VAC
(3 PH)
20
20
5 (15)
600 VAC
(1 PH)
10
10
3 (10)
600 VAC
(3 PH)
30
30
7.5 (20)
250
VDC
5
5
5
10
10
3 (10)
20
20
7.5 (15)
20
20
5 (20)
50
50
15 (30)
25
25
10 (25)
60
60
15 (50)
10
10
10
WSRD103542SMS901
100
Non-Fused
15
40
30
75
40
WSRDW103542SMS901 100
Non-Fused
15
40
30
75
40
WSRDW10352SMS901
100
Fused
7.5 (15)
15 (30)
10 (30)
25 (60)
15 (40)
NOTE:
Values for Non-Fused units are maximum horsepower.
Values for Fused units are standard horsepower with standard fuse and (maximum horsepower with time delay).
100
100
30 (75)
20
20
20
WSRD63542SMS901
WSRDW63542SMS901
WSRDW6352SMS901
Amps
Fusing
30
Non-Fused
30
Non-Fused
30
Fused
60
60
60
Non-Fused
Non-Fused
Fused
DIMENSIONS (Inches)
1022
STIBOINFO((CRH:66008com:3P:1022))
CH0 0 4 F - 5
US: 1-866-764-5454
Amps
A
B
C
D
E
30
60
5.47
7.99
16.49
18.49
23.49
25.49
9.00
11.52
8.61
8.61
100
8.47
24.18
31.18
12.00
8.61
CAN: 1-800-265-0502