SPECIFICATION SHEET
MODEL HRV700
INDOOR POOL HEAT RECOVERY VENTILATOR
FEATURES
TYPICAL SPECIFICATIONS
BLOWER:
Fresh and stale air streams are isolated from each other to
prevent mixing of stale air with fresh air
High pressure, centrifugal blower accommodates many ducting
configurations
Balanced centrifugal blower wheels for quiet operation and
long motor life
Energy efficient two-speed PSC motors with sealed ball
bearings, polyurethane paint and stainless steel shafts
1075/600 rpm, 115 VAC, 60 Hz, 2.5 amps each
The Heat Recovery Ventilator shall be Broan-NuTone Model
HRV700.
HOUSING:
Rugged steel housing with baked powder coated finish
Installed suspended
Every part is removable in less than five minutes
Square inlets and outlets for easy duct connections
Flanges on outdoor air stream connections allow for taping
insulated ductwork
All inside surfaces covered with foil-faced thermal/acoustic
insulation
Easily removable, washable air filters
Built-in drain tube connection
All interior surfaces to be covered with foil-faced thermal/
acoustic insulation.
CONTROLS:
Off/Low/High switch on side of unit
Provisions for 24 volt low voltage control
Fully enclosed, modular controls mounted to outside of cabinet
for improved reliability and easy servicing
Rated air flow shall be 650 cfm at 0.4 in. wg.
Unit to include easily-removable energy recovery core - no tools
should be required to remove.
Fresh air and stale air streams to be isolated from each other
to prevent mixing of stale air with fresh air.
Built-in defrost mechanism to be provided to prevent freeze-ups.
Every part shall be removable in less than five minutes.
Housing shall be of rugged steel with baked powder coated finish.
Unit shall include easily removable, washable air filters. No tools
are to be required for filter cleaning/replacement.
The controls are to be mounted outside of the unit and include
an off/low/high switch and provisions for low voltage controls.
Unit to accommodate square duct. Taping flanges on outdoor
air stream connections shall be provided.
Blower shall be energy efficient, two-speed PSC motors with
sealed ball bearings, polyurethane paint and stainless steel shaft.
Unit to be ETL listed and cETL certified.
CORE:
Non-enthalpic core transfers energy without moisture vapor
transfer
Easily removable for cleaning and replacement - no tools
required
Material is U.L. flammability classified 94 HB.
Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin 53027 (1-800-637-1453)
REFERENCE
QTY.
REMARKS
Project
Location
Architect
Engineer
Contractor
Submitted by
Date
99042561C
PERFORMANCE RATINGS
MODEL HRV700
HEAT RECOVERY VENTILATOR
1.875"(48mm)
14.000"
(356mm)
2.000"
(51mm)
8.000"(203mm)
Option Installed: Defrost
Electrical Requirements: 115 Volts 2.5 Amps
Defrost Air Port
3.625"(92mm)
2.750"(70mm)
3.750"(95mm)
8.000"
(203mm)
40.500"
(1029mm)
2.000"
(51mm)
2.000"
(51mm)
12.250"
(311mm)
8.000"
(203mm)
Exhaust Air
To Outside
Fresh Air
From Outside
10.750"(273mm)
2.750"
(70mm)
Fresh Air
To Building
Exhaust Air
From Building
8.000"(203mm)
8.000"(203mm)
12.000"(305mm)
26.625"(676mm) to drain
10.145"(258mm)
Condensate Drain
31.125"(791mm) to drain
51.000"(1295mm)
A minimum of 21.00" (533mm) clearance from any obstru
is required for removal of heat recovery cores, fans,
door can be removed from cabinet with only 2.00" (51m
A minimum of 6.00" (152mm) clearance from any obstruction
is required for power hook-up, low voltage remote connection,
and control panel access.
21.000"(533mm)
Power Connection
Low Voltage
Remote Connection
Heat Recovery Core
Control Switch
Access Door