Tracking Controller - Price Critical Controls

advertisement
MANUAL – INSTALLATION
Tracking Controller
TC Series
v100 – Issue Date: 02/25/16
© 2016 Price Industries Limited. All rights reserved.
Firmware: 1.3.0
TRACKING CONTROLLER
TABLE OF CONTENTS
Product Overview
General.......................................................................... 1
Tracking Controller (TC) Features.................................... 1
Operation....................................................................... 2
Expansion Modules........................................................ 2
Input/Output Description ............................................... 3
Flow Response Chart .................................................... 4
Sample Wiring Diagram.................................................. 5
Thermostat Options ..................................................... 6
Thermostat Installation................................................... 7
Thermostat Functions.................................................... 8
Display Navigation
Initial Setup.................................................................... 9
Information Menu......................................................... 10
Service Menu............................................................... 11
Application Menu......................................................... 12
Balancing Menu........................................................... 12
VAV with Track Menu.................................................... 13
Setpoint Menu.............................................................. 14
Discharge Air Temperature Menu.................................. 15
Input Menu................................................................... 16
Output Menu................................................................ 19
BACnet Menu.............................................................. 24
Stat Setup Menu.......................................................... 25
Diagnostics Menu........................................................ 26
Networking and Setup
Setting the MAC Address............................................. 27
Setting the Device Instance.......................................... 28
Linker2 – USB Service Tool.......................................... 29
Troubleshooting............................................................ 30
Hardware Specifications............................................... 33
TRACKING CONTROLLER
PRODUCT OVERVIEW
General
Tracking Controller (TC) Features
The Tracking Controller (TC) is a direct
digital controller for venturi valves or
VAV terminals that offers cutting edge
zone control and airflow control. The TC
combines the accuracy of direct digital
control with the flexibility of an individual
room control system, providing maximum
control and efficiency. An advanced
and configurable proportional integral
controller allows for exceptional user
comfort and energy efficiency. Installation
of the controller and thermostat is simple
and error proof with RJ-45 (network
type) connections to the thermostat and
BACnet network.
•
24 VAC power terminal or RJ-12 power connection
•
4 VAC Binary Outputs (7) – A variety of binary outputs for heating, cooling
2
or fan operation which are rated for maximum 0.5 amps each. Max: 1.85 amps
total. Field switchable from HOT to COM.
•
nalog Outputs (4) – Fully configurable (2 to 10 VDC, 0 to 10 VDC, 10 to 2
A
VDC etc.) outputs for heating, cooling, and auxiliary, rated at maximum 10 mA
each.
•
.A.T Sensor Input (1) 10K type J thermistor - discharge temperature control
D
is required and a temperature probe must be connected.
•
Contact Closure Input (1) – night setback.
•
BACnet Expansion Module (optional) – providing a native BACnet MS/TP
interface.
•
VAV Expansion Module – provides air flow input from the exhaust valve.
•
Integrated Damper Actuator – default stroke time of 95 seconds.
•
T-stat port - for RJ-45 connection to thermostat from the TC controller.
•
ervice Port – RJ-12 port used to connect Price Linker for system balancing
S
and setup, or to connect an PIC
LCD
Thermostat
for system
balancing and setup.
– installation
and service manual
– V1.08
0624L
The LINKER is a USB 2.0 interface
to Price controls and is used in conjunction
with FREE setup and balancing software available from Price.
The TC typically comes factory mounted
to the Price VAV terminals, but may also
be ordered stand-alone for retrofit jobs.
TC FEATURES
The Price Intelligent Controller (PIC) is a direct digital controller for VAV terminals or fan coils that offers
cutting edge zone control. The PIC combines the accuracy of direct digital control with the flexibility of an
• LED Indication – for ease of troubleshooting.
individual room control system, providing maximum control and efficiency. An advanced and configurable
proportional integral controller allows for exceptional user comfort and energy efficiency. Installation of the
controller and thermostat is simple and error proofwith RJ-45 (network type) connections to the thermostat
and BACnet network.
The PIC typically comes factory mounted to Price VAV boxes, but may also be ordered stand-alone for
retrofit jobs.
T-Stat Port for
Thermostat
Connection
D.A.T. Sensor
Input
Contact Closure Input
4 Analog Outputs
Optional BACnet
Expansion Module
Service Port for
Price Linker
Switchable
24 VAC Hot/Com
Output Selection
Hot or COM
Pluggable 24 VAC Power
Terminal or
RJ-12 Power Connection
LED Indication for
Troubleshooting
Expansion Module
Binary Cooling Output
3 Binary Staged
Heating Outputs
priceindustries.com | TRACKING CONTROLLER - Manual
1
TRACKING CONTROLLER
PRODUCT OVERVIEW
Operation
The TC is an advanced and fully configurable VAV terminal controller that can be used
as a pressure independent zone control system.
TC - SUPPLY EXPANSION BOARD
WITH FLOW TRANSDUCER
The TC offers five thermostat options that provide a range of control from room
temperature sensing, all the way to motion sensing. With a variety of output
configurations, the TC can control analog heating and cooling valves, fan motors,
and other types of analog devices. As well as On/Off heating and cooling stages, on/
off fan operation, fan coils etc. With the use of the LCD Thermostat, balancing and
system setup can be performed. Further, with the use of the LCD Thermostat with
Motion Sensing, the TC can be used as a motion sensor and lighting controller with
different levels of sensitivity, as well as a system balancing tool.
Expansion Modules
The TC is also expandable for BACnet networking capabilities using the BACnet
expansion module, which allows for MS/TP connectivity to building management
systems. LED indicators show current status of communication and any electrical
fault conditions. For Airflow measurement, two options are available. The first option
uses a flow transducer combined with the SP300 sensor to measure and control to
the targeted airflow. This is typically used with VAV terminal units. The second option
uses an analog input that reads the signal from a Linear Module on a Venturi Valve.
This system uses position feedback from the Venturi Valve. The expansion modules
come equipped with a ribbon cable that is easy to plug in from the TC to the selected
module.
(TC-BAC) - BACNET MODULE
TC - SUPPLY EXPANSION BOARD
WITH LM(X)
2
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
PRODUCT OVERVIEW
Input/Output Description
24VAC Binary Outputs:
Stg1/Open
Binary (electric, or binary hot water)
Tristate (floating) open signal of hot water valve
Stg2/Closed
Binary (electric, or binary hot water)
Tristate (floating) open signal of hot water valve
Stg3
Cool/Aux
Binary (electric, or binary hot water)
24VAC PWM to SSR (10 second period)
Binary Output for one stage of cooling if required.
Can be used as an auxiliary binary output if required.
Analog Outputs:
AO1 - Spare
Spare analog output
AO2 - Heat
Analog Output for modulating heating valve (0 to 10 VDC, 2 to 10 VDC, 10 to 2 VDC etc.)
AO3 - Cool
Analog Output for modulating cooling valve (0 to 10 VDC, 2 to 10 VDC, 10 to 2 VDC etc.)
AO4 - Spare
Spare analog output – normally indicates damper position (0 to 10 VDC = 0-100%)
Inputs:
Contact Closure
D.A.T. Sensor
Configurable Binary Input can be used for night setback, damper force open/close etc.
Analog Input for temperature probe hookup for discharge temperature if required.
10k Type J Thermistor.
Switched HOT/COM Jumper: TC offers a jumper selectable HOT/COM switch that allows the binary outputs to be switched
HOT or switched COMMON.
COM Terminals: All COM terminals on the TC are internally connected, which allows for a common reference point throughout
the board.
Damper Actuator: Factory installed and wired, the TC offers LED indication of the damper direction, (either OPN or CLO). Default
drive time of the actuator is 90 seconds, but is configurable through software, or by using the LCD Thermostat.
T-Stat RJ-45 Port: The TC comes equipped with an RJ-45 port to provide ease of plugging in a thermostat cable from the TC to
any of the selected thermostats. The thermostat cable is supplied by Price.
Service Port: The TC comes equipped with an RJ-12 port to provide ease of plugging in an RJ-12 cable to the Price LINKER 2
for system balancing and setup, or to connect an LCD Thermostat for system balancing and setup. The LINKER 2 is a USB 2.0
interface to Price controls, and is used in conjunction with FREE setup and balancing software available from Price.
priceindustries.com | TRACKING CONTROLLER - Manual
3
TRACKING CONTROLLER
PRODUCT OVERVIEW
Flow Response Chart
Output
HCCO box
Cooling Min
Cooling Flows
Heating Min
Heating Flows
Neutral
Supply
Air Flow

PI = Cooling
Duct air = Cold
PI = Heating
Duct air = Cold
PI = Neutral
Duct air = Cold

PI = Cooling
Duct air = Hot

PI = Heating
Duct air = Hot
PI = Neutral
Duct air = Hot
PI = Cooling
Duct air = Neutral
PI = Heating
Duct air = Neutral
PI = Neutral
Duct air = Neutral






Above is a Flow Response chart for the TC, showing the demand, Duct Air condition, and the controller’s output.
E.g.: PI = Cooling, Duct Air = Cold, Output = Cooling Flows. This indicates that the Room Demand is in Cooling, the Duct Air is
Cold, and the controller would modulate between the Cool Min and Cool Max values.
NOTE: If no Temperature Probe is present, the TC assumes cold duct air.
PI = Proportional Integral = room load (either cooling/neutral/heating)
TECH TIP
Use the above table to determine what airflows are being targeted in certain modes.
Example: If TC is trying to heat the room (PI=heating) and cool air is being supplied (Duct air=Cold) it will chase its heating min flow.
4
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
PRODUCT OVERVIEW
COM
BO2
COM
COM
CW
T-STAT
AO4
ROOM THERMOSTAT
AO3
HOT
VALVE
POWER 24V
COM
COMMON
A02
AO2
AO1
CCW
EXPANSION MODULES
3
2
1
VALVE
SIGNAL (0-10V)
TO SUPPLY
REHEAT VALVE
DPR
*
24VAC POWER
HOT COM
DISCONNECT
CONTROLLER
FUNCTION
TERMINALS
IN COM
24/120/208/
240/277
TO 24 VAC
50VA TRANS.
CAT5E CABLE
SAT
SENSOR
24VAC BINARY OUTPUTS
STG1
/OPN
STG2
/CLO
STG3
CONTACT
CLOSURE
C
BO1
COM
ANALOG OUTS
L1
TRACKING CONTROLLER
H
N/L2
OUTPUTS
SWITCHED
POWER
SOURCE
SERVICE
Sample Wiring Diagram
BACNet
EXHAUST TRACKING VALVE
ACTUATOR
IOLM-S
SUPPLY TRACKING VALVE
NET
COM
NET IN NET OUT
AI7
SIG
LEGEND
COM
FROM BACnet
MSTP DEVICE
24VAC
CAT5E CABLE
BA+
CAT5E CABLE
TO BACnet
MSTP DEVICE
ACTUATOR
1
FACTORY ELECTRICAL WIRING
FIELD ELECTRICAL WIRING
2
3
EXHAUST TRACKING VALVE
CAT5E CABLE
priceindustries.com | TRACKING CONTROLLER - Manual
5
TRACKING CONTROLLER
PRODUCT OVERVIEW
Thermostat Options
All thermostats are connected with a CAT-5 cable (RJ-45) connection from the TC to the back of the selected
thermostat. Each thermostat has an RJ-12 Service Port on the bottom, providing a computer interface using the
USB LINKER2 service tool for setup and balancing, and without having to access the plenum.
DIAL THERMOSTAT (TC-TS-DIAL)
ROOM SENSOR THERMOSTAT TC-TS-SENS)
1. Setpoint Adjust – from hidden dial on the back
2. Service Port - Linker2 Connection
1.
2.
3.
4.
Dial Adjustment for Temperature
Occupancy Override Button
LED – 1 blink cooling mode, 2 – heating, 3 - neutral
Service Port - Linker2 Connection
1
1
2
2
3
4
LCD THERMOSTAT (TC-TS-LCD)
1. LCD screen for menu display
2. Menu Button
3. Increase and decrease push buttons for day temperature
setpoint adjustment
4. Service Port - Linker2 Connection
1
LCD THERMOSTAT W/MOTION SENSOR: (PIC-TS-MOTION)
1. LCD screen for menu display
2. Menu Button
3. Increase and decrease push buttons for day temperature
setpoint adjustment, as well as manual light on/off
buttons
4. Motion sensor allows for automatic detection of
occupancy
5. Service Port – Linker2 connection
2
3
1
4
2
3
4
5
6
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
PRODUCT OVERVIEW
Thermostat Installation
Thermostat Installation
General Description
SURFACE MOUNT DETAIL
The TC thermostats are all physically the same size and
mounting instructions
will
be
typical.
General Description
The PIC thermostats are all physically the same size and mounting instructions will be typical.
1.25”
Location
(32)
1.The TC Thermostats
must be mounted to a wall and
Location
The Price
Intelligent
Controller
wired to the TC via the1.supplied
plenum
rated 35ft
CAT- (PIC) Thermostats must be mounted to a wall and wired to the PIC
controller
via the supplied
5 cable. This cable plugs into
the thermostat
and the plenum rated 35ft CAT-5 cable. This cable plugs into the thermostat
and
the
PIC
controller
with the ease of RJ-45 connections. Note: the cable run can be extended
TC with the ease of RJ-45 connections.
to 70 ft using a Price cable coupler and additional 35ft cable.
NOTE: The cable run can be extended to 70 ft. using a
Price cable coupler and
35required
ft. cable. thermostat in a place that is convenient for the end user, but the following
2. additional
Mount the
should
taken
into
2.Mount the required thermostat
in be
a place
that
is consideration:
Dobut
notthe
mount
a thermostat
convenient for the end•user,
following
should be in direct sunlight i.e. across from a window where heat can alter
4.875”
Wall Fasteners
taken into consideration: thetemperature reading.
• Should not be installed on an outside wall.
(125)
by others
Do not mount a thermostat in direct sunlight
• Keep away from hot equipment like computers, monitors and heaters etc.
i.e. across from a window
where
heat
can
alter
the
• Ensure nothing will restrict vertical air circulation to the thermostat. (Do Not Cover)
temperature reading. •
***Ensure wall is NOT pressurized! Hot/cold air from a pressurized wall will direct blow
Should not be installed onto
on anthe
outside
wall.
thermostat’s
temperature sensor causing ‘bad’ readings. ***
Keep away fromInstallation
hot equipment like computers,
1. The back plate on each thermostat is removable and can be mounted to a standard electrical box
monitors and heaters etc.
or directly
to air
drywall
using anchors supplied by others.
Ensure nothing will restrict
vertical
circulation
the CAT-5 cable through the center hole in the plate. Connect the cable to the thermostat,
to the thermostat. (Do2.
NotRun
Cover)
and then secure the thermostat onto the wall plate inserting the top portion of the thermostat first,
***Ensure wall is NOT pressurized! Hot/cold air
and then snapping the bottom half in.
from a pressurized wall will direct blow onto
3. All thermostats will come equipped with35a FOOT
0.050”
Allen key
forCABLE
the set- INCLUDED
screw at the bottom.
PLENUM
RATED
the thermostat’s temperature sensor causing
incorrect readings.***
Surface Mount Detail
Installation
1.The back plate on each thermostat is 1.25”
removable and
(32)
can be mounted to a standard electrical box or directly
to drywall using anchors supplied by others.
2.Run the CAT-5 cable through the center hole in the
plate. Connect the cable to the thermostat, then secure
Wall Fasteners
the thermostat onto the wall plate inserting top portion
by others
of the thermostat first, then snapping the bottom half in.
3.All thermostats will come equipped with a 0.050 in.
Allen key for the set screw at the bottom.
TECH TIP
35 foot plenum rated cable included
with thermostat (PIC-CABLE)
Careful thermostat installation will reduce field issues! Do
not twist or kink the blue CAT5 thermostat cable.
TECH TIP: Careful thermostat installation will reduce field
issues! Do not twist or kink the blue CAT5 thermostat
Damaged cables are difficult to troubleshoot! Thermostat
cable. Damaged cables are difficult to troubleshoot!
cable product code: TC-CABLE.
Thermostat cable product code: PIC-CABLE
priceindustries.com | TRACKING CONTROLLER - Manual
www.priceelectronics.ca/PIC
7
TRACKING CONTROLLER
PRODUCT OVERVIEW
Thermostat Functions
Room Sensor Thermostat
•
Powered from the TC.
•
Measures room temperature.
•
et point can be adjusted from a hidden dial on the back of the T-Stat using a
S
small flat-head screw driver.
•
etpoint limits can be adjusted through free setup software using the Price
S
LINKER2, or through BACnet system.
•
Eliminates problem of unauthorized tampering to the thermostat.
Dial Thermostat
•
Powered from the TC.
•
Measures room temperature & features a dial adjustment & an occupancy
button.
•
Temperature Setpoint limits can be adjusted through free setup software using
the Price LINKER2, or through a BACnet system.
•
Simply use the adjustable dial for temperature adjustment.
•
ccupancy button can be used to override the system during unoccupied times
O
Default setting is 4 hrs.
LCD Thermostat
•
Powered from the TC and has a variety of features.
•
easures room temperature and features an LCD screen with push button day
M
setpoint adjustment.
•
emperature set point limits are set through free setup software using the Price
T
LINKER2, or through a BACnet system.
•
CD Thermostat can also be used as a balancing tool for the TC system by
L
simply connecting the RJ-45 cable to the back of the thermostat.
ROOM SENSOR THERMOSTAT
DIAL THERMOSTAT
LCD THERMOSTAT
LCD Thermostat with Motion Sensor
•
Powered from the TC and has a variety of features.
•
his model measures room temperature, features an LCD screen with day
T
Setpoint adjustment, and motion sensor with lighting control.
•
emperature set point limits are set through free setup software using the Price
T
LINKER2, or through a BACnet system.
•
he LCD Thermostat with Motion Sensor can be used as a balancing tool for the
T
PIC system by simply connecting the RJ-45 cable to the back of the thermostat.
•
his thermostat can also be used as a motion sensor for occupied and
T
unoccupied times in a space. It also has the capability to act as a lighting
controller for occupied/unoccupied schedules.
8
TRACKING CONTROLLER - Manual | priceindustries.com
LCD THERMOSTAT
W/ MOTION SENSOR
TRACKING CONTROLLER
DISPLAY NAVIGATION
Initial Setup (LCD Thermostats (T-STAT) Only)
When the Interface is first powered from the TC controller, it will display the following information: (Also press both UP/DOWN at
same time to show this screen anytime.)
PRICE ELECTRONICS
INTERFACE STANDARD
MODEL
INTERFACE
VERSION X.XX.X
LOADING
*INITIALIZING*
Start-up screen.
Displays the type of interface being used.
Displays firmware version of T-STAT.
Loading parameters from the TC.
PIC
VERSION X.XX
SEQUENCE
XXX
Displays sequence programmed into the TC NOTE: a sequence number of 0 means the TC has NOT been calibrated.
DUCT SIZE
XX INCHES
Displays inlet size.
MAC ADDRESS 1
DEVICE INST. 158,001
ROOM TEMP. 75.0°F
Displays current MAC Address (local MS/TP segment) - Must be unique to MS/TP segment.
Displays current Device Instance (System address) - Must be unique to building.
Displays the current temperature that the Thermostat is reading.
Controller
Down Button
Used for day setpoint adjustment.
INTERFACE
Up Button
Used for day setpoint adjustment.
Day Setpoint Adjustment
Increase and decrease push buttons for
Day setpoint adjustment.
priceindustries.com | TRACKING CONTROLLER - Manual
9
TRACKING CONTROLLER
DISPLAY NAVIGATION
Information Menu (LCD Thermostats Only)
The info menu shows information about the controller status regarding room load, damper position and BACnet address info.
No values can be changed from this menu and it is not locked or protected in any way.
APPLICATION
SUP/EX TRACK
OCCUPANCY
ON-CONTACT
Displays the current application the Tracking Controller is being utilized for. The menus shown below follow the Supply/
Exhaust tracking application. For other options, please see the Application menu on page 12.
Occupancy can be determined by airflow, contact closure, motion or by a user pressing a button.
HEATING MODE
LOAD 100%
Displays the current mode the controller is in.
Neutral mode -The Tracking Controller is satisfied.
Cooling 1 to 100%.
Heating 1 to 100%.
SUPPLYAIRTEMP
70.0°F
Supply probe not present: LCD will display ‘No Probe’.
Supply probe present: LCD will display the Supply Air Temperature.
SUPPLYDPR.POS
50%
This indicates the current position of the supply damper in percent (%).
Range is 0 to 100% (100% = fully open or maximum air).
EXHAUST POS.
50%
This indicates the current position of the exhaust damper in percent (%).
Range is 0 to 100% (100% = fully open or maximum air).
ECM OUTPUT
8.0 VDC
Current Voltage on output A01.
SUPPLY FLOW
500 CFM
Current supply airflow.
EXHAUST FLOW
700 CFM
Current exhaust airflow.
SUPLYFLOWTARGT
500 CFM
Shows the current supply airflow target cfm.
EXHAUST TARGET
700 CFM
Shows the current exhaust airflow target cfm.
LMX ALARMSTAT
NORMAL
Indicates if the Linear Module is within the required pressure range.
MAC ADDRESS
HARDWARE 1
(MAC address must be unique on the network segment). Shows the BACnet MAC address. Range 1 to 99.
MAC address can be set via dip switch. If no BACnet module is attached, LCD will display MAC address None.
DEVICE INST.
158,001
(Instance must be ‘globally’ unique on your site) Displays controllers BACnet Device Instance (if BACnet is attached).
If no BACnet module attached, LCD will display MAC address None.
DEVICE INST.
158,001
(Instance must be ‘globally’ unique on your site).
Displays controllers BACnet Device Instance (if BACnet is attached).
Device Instance can range from 0 to 4,194,303.
PRESS MENU
TO EXIT
10
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Service Menu (LCD Thermostats Only)
The service menu allows the balancer/installer to access the controller setup to change settings (e.g setting flows, heating outputs, etc.).
SERVICE MENU:
APPLICATION
Change the application the unit is operating as.
See page 12.
SERVICE MENU:
BALANCING
Allows you to force damper open/close/min/max.
See page 12.
SERVICE MENU:
VVT
Allows you to set flows or set limits.
See page 13.
SERVICE MENU:
SETPOINT
Setup of Setpoint limits (day minimum/maximum).
F/C selection.
See Page 14.
SERVICE MENU:
DISCHARGE AIR
TEMPERATURE
When DAT control has been enabled, the “Discharge Air Temperature” service menu will be activated.
SERVICE MENU:
INPUT
Shows supply air temperature reading.
Shows if VAV and BACnet modules are attached.
See page 16.
SERVICE MENU:
OUTPUT
Allows setup of fan, heat, cool outputs.
See page 19.
SERVICE MENU:
BACNET
Allows setup of BACnet addresses, MAC Address, Device Instance, Baud Rate.
Included on if BACnet module is attached.
See page 24.
SERVICE MENU:
STAT SETUP
Allows setup of LCD back lighting, sounds, motion sensor.
Adjustment of HVAC and room lighting timeouts.
See page 25.
SERVICE MENU:
DIAGNOSTIC
Allows you to reset set the factory defaults and to reset the controller. See page 26.
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
11
TRACKING CONTROLLER
DISPLAY NAVIGATION
Application Menu
SERVICE MENU:
APPLICATION
CONTROL APP.
CO2 TRACKING
Not applicable.
MIXING BOX DAT
Not applicable.
SUPPLY/EXHAUST
TRACKER
Volumetric offset application, typically for Venturi valves,
but also for single ducts.
This manual covers this Supply/Exhaust tracking
application.
EXHAUST BOX
Exhaust box typically with constant flow. Reference PIC
Manual for more information.
DUAL DUCT
Not applicable.
FAN COIL 2 PIPE
Not applicable.
FAN COIL 4 PIPE
Not applicable.
AIR TERMINAL
Supply box typically with constant flow. Reference PIC
Manual for more information.
PRESS MENU
TO EXIT
Balancing Menu
SERVICE MENU:
BALANCING
SET SUPPLY FLOW NO OVERRIDE
1 to 9,999 cfm - Set the output flow of the supply duct.
No Override - Normal operation default.
Go to full open - Fully opens the supply duct.
Go to full close - Fully closes the supply duct.
SET EXHAUST FLOW NO OVERRIDE
1 to 9,999 cfm - Set the output flow of the exhaust duct.
No Override - Normal operation default.
Go to full open - Fully opens the supply duct.
Go to full close - Fully closes the supply duct.
SUPPLY TWEAK %
Tweak the supply airflow by +/-100%.
NOTE: For single duct terminals, this menu will be the K-Factor for the crossflow sensor.
Adjust this value to tweak the airflow reading.
EXHAUST TWEAK %
Tweak the exhaust airflow by +/-100%.
NOTE: For single duct terminals, this menu will be the K-Factor for the crossflow sensor.
Adjust this value to tweak the airflow reading.
PRESS MENU
TO EXIT
12
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
VAV with Track Menu
Application specific options
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
SERVICE MENU:
VVT
FLOW UNITS
CFM
Choose between litres per second or cubic feet per minute.
COOL MIN FLOW
132 CFM
Minimum cooling flow.
COOL MAX FLOW
800 CFM
Maximum cooling flow.
HEAT MIN FLOW
132 CFM
Minimum heating flow.
HEAT MAX FLOW
800 CFM
Maximum heating flow.
NEUTRAL FLOW
132 CFM
Flow when controller is satisfied.
EXHAUST OFFSET
0 CFM
Applies an offset to the flow.
Example: If the Exhaust offset is 50 cfm and the flow is 500 cfm, exhaust will track to 550
cfm.
UNOCCUPIED VAV MODE
Damper position only.
• When unoccupied the unoccupied damper position is the targeted cfm.
• When unoccupied, if there is flow, the unoccupied airflow is targeted.
UNOCCUPIED AIRFLOW
Only visible if Unoccupied VAV Mode is set to cfm target.
When TC is unoccupied damper will ‘rest’ at this airflow.
Range: 0 to 9,999 cfm.
Default 132 cfm.
DAMPER RUNTIME
95 SEC
DAMPER DIRECTION
NORMAL
DAMPER CAL
NORMAL
FLOW RESPONSE
NORMAL
Change the total runtime of the damper.
Changes the direction that damper open and damper close are set to.
Normal - Damper reads after a set number of movements Default.
No Cal Mode - The damper remains in direct control of airflow but assumes the damper
position. Damper will not recalibrate after a set number of movements to ensure continuous
flow control.
Normal - Typical response, airflow target based on room condition (PI) and duct
temperature.
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
13
TRACKING CONTROLLER
DISPLAY NAVIGATION
Setpoint Menu
Setpoint limits and temperature units
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
SERVICE MENU:
SETPOINT
SET LO LIMIT
65.0°F
This is the lowest Setpoint allowed.
Range: 10.0 to 100.0°F Default: 65.0°F.
SET HI LIMIT
80.0°F
This is the highest Setpoint allowed.
Range: 10.0 to 100.0°F Default 80.0°F.
TEMP. UNITS
FAHRENHEIT
Fahrenheit or Celsius.
Default: °F.
NIGHT HEAT SETPOINT
62.0°F
TC will maintain the heating Setpoint when unoccupied.
Range: 10.0 to 100.0°F Default: 62.0°F.
NIGHT COOL SETPOINT
83.0°F
TC will maintain the heating Setpoint when unoccupied
Range: 10.0 to 100.0°F Default: 62.0°F.
PRO. BAND
2.0°F
DAY DIFF.
1.0°F
14
Default 2°F, 1°C.
Default 1°F, 0.5°C.
PI ANALOGHEAT
NORMAL PI
PI references the cooling or heating load of the space.
Normal PI - A PI of 0 percent is min flow, 100 percent is max flow.
Low Range PI - A PI of 0 percent is min flow, 50 to 100 percent is max flow.
High Range PI - A PI of 0 to 50 percent is min flow, 100 percent is max flow.
PI ANALOGCOOL
NORMAL PI
Normal PI - A PI of 0 percent is min voltage, 100 percent is max voltage.
Low Range PI - A PI of 0 percent is min voltage, 50 to 100 percent is max voltage.
High Range PI - A PI of 0 to 50 percent is min voltage, 100 percent is max voltage.
PI ECM HEAT
NORMAL PI
Normal PI - A PI of 0 percent is min voltage, 100 percent is max voltage.
Low Range PI - A PI of 0 percent is min voltage, 50 to 100 percent is max voltage.
High Range PI - A PI of 0 to 50 percent is min voltage, 100 percent is max voltage.
PI ECM COOL
NORMAL PI
Normal PI - A PI of 0 percent is min voltage, 100 percent is max voltage.
Low Range PI - A PI of 0 percent is min voltage, 50 to 100 percent is max voltage.
High Range PI - A PI of 0 to 50 percent is min voltage, 100 percent is max voltage.
PRESS MENU
TO EXIT
Normal PI - A PI of 0 percent is min voltage, 100 percent is max voltage.
Low Range PI - A PI of 0 percent is min voltage, 50 to 100 percent is max voltage.
High Range PI - A PI of 0 to 50 percent is min voltage, 100 percent is max voltage.
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Discharge Air Temperature Menu
SERVICE MENU:
DISCHGAIRTEMP
DAT CTRL MODE
DAT HEAT ONLY
DAT CTRL MODE
DAT COOL ONLY
Not applicable
DAT CTRL MODE
DAT HEAT ONLY
The Tracking Controller will default to Heat Only.
DAT CTRL MODE
DAT HEAT/COOL
Not applicable
PRESS MENU
TO EXIT
DISCHGAIRTEMP
21.0˚C
Discharge Air Temperature - Current temperature reading of the DAT. If display is at 300˚F,
thermistor is shorted. If no thermistor is detected -59˚F will be displayed.
DAT COOL SET.
13.0˚C
Discharge Air Temperature Cooling Setpoint - This is the DAT cooling target while in cooling
mode.
DAT HEAT SET.
32.0˚C
Discharge Air Temperature Heating Setpoint - This is the DAT heating target while in heating
mode.
DATWHILEPI/DB
DISABLED
Discharge Air Temperature in Deadband - When the room temperature is satisfied, the DAT
will target for this temperature.
DAT UNOCC SET
DISABLED
Discharge Air Temperature Unoccupied Setpoint - Temperature target while
room is unoccupied and room temperature is satisfied. Default: Disabled
DAT SVC. TIME
60 SEC.
Discharge Air Temperature Service Time - Control loop update period. Amount of time that
determines how often the control loop for the DAT is updated. Default: 60 sec. (10 to 3,600
sec.).
DAT STEP DIV.
10
Discharge Air Temperature Step Division - This controls the rate at which the output will
change. Rate range is 1 to 50. 1 -maximum change rate. 50 -minimum change rate.
Default: 10.
DAT STEP MIX
10%
Discharge Air Temperature Step Mix - The maximum amount the output will change at every
loop service. Step range is 1% to 50%. The higher the percentage, the larger the change.
Default: 10%
DATDIFRENTIAL
1.0˚C
Discharge Air Temperature Differential - Acceptable difference in temperature before system
makes changes. Range is 0.0˚F to 25.0˚F. Default: 3.0˚F
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
15
TRACKING CONTROLLER
DISPLAY NAVIGATION
Input Menu
Supply air temp and neutral mode
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
SERVICE MENU:
INPUT
SUPPLYAIRTEMP
NO PROBE
Shows current SAT reading if probe connected (TC-PRB).
Range: -59 to 399°F.
"No Probe" indicates there is no sensor connected.
NEUTRAL MODE
DYNAMIC
• W
hen supply air temp (DAT) is below room temp it is
considered cooling.
• When supply air temp (DAT) is above room temp it is
considered heating.
• This mode is recommended as the TC will always use
the supply air if it can help satisfy the room load.
NEUTRAL MODE
CONVENTIONAL
Uses the Hot and Cold Switch temperatures to determine
whether it is in heating mode or cooling mode.
NEUTRAL MODE
FORCE COOL
The TC will always assume cold supply air.
NEUTRAL MODE
FORCE HEAT
The TC will always assume warm supply air.
NEUTRAL MODE
DYNAMIC
HOT SWITCH
81.0˚F
Only active/visible when Neutral mode is Conventional.
TC will consider the supply air warm if at the hot switch temp or above.
Default: 0.0˚F - uses dynamic neutral mode.
COLD SWITCH
73.0˚F
Only active/visible when Neutral mode is conventional.
TC will consider the supply air cold if at the cold switch temp or below.
Default: 0.0˚F - uses dynamic neutral mode (neutral mode disabled).
VAV MODULE
OMRON SENSOR
2NDVAV MODULE SAME
AS MODULE 1
Displays the VAV sensor.
• Not attached.
• OMROM sensor.
• Kavlico Sensor.
• Linear Module.
Displays the second VAV sensor.
• Same as module 1.
• DP Sensor.
• OMRON Sensor.
• Linear module.
INPUT
LM SETUP
16
TRACKING CONTROLLER - Manual | priceindustries.com
SUPLM MIN VIN
2.0 VDC
Supply Linear Module Minimum Voltage - Factory set to
the minimum voltage of the flow signal from the supply
linearization module. This value should always be changed
in conjunction with the flow signal range on the supply
linearization module.
TRACKING CONTROLLER
DISPLAY NAVIGATION
Input Menu Continued...
Supply air temp and neutral mode
SUPLM MAX VIN
10.0 VDC
Supply Linear Module Maximum Voltage - Factory set to
the maximum voltage of the flow signal from the supply
linearization module. This value should always be changed
in conjunction with the flow signal range on the supply
linearization module.
SUPPLY LM MIN
90 CFM
Supply Linear Module Minimum Flow - Factory set to the
minimum flow rate of the supply linearization module. This
value should always be changed in conjunction with the
airflow range on the supply linearization module.
SUPPLY LM MAX
1500 CFM
Supply Linear Module Maximum Flow - Factory set to the
maximum flow rate of the supply linearization module. This
value should always be changed in conjunction with the
airflow range on the supply linearization module.
EXLM VIN MIN
2.0 VDC
Exhaust Linear Module Minimum Voltage - Factory set to
the minimum voltage of the flow signal from the exhaust
linearization module. This value should always be changed
in conjunction with the flow signal range on the exhaust
linearization module.
EXLM VIN MAX
10.0 VDC
Exhaust Linear Module Maximum Voltage - Factory
set to the maximum voltage of the flow signal from
the exhaust linearization module. This value should
always be changed in conjunction with the flow
signal range on the exhaust linearization module.
EXHAUST LM MIN
90 CFM
Exhaust Linear Module Minimum Flow - Factory set to the
minimum flow rate of the exhaust linearization module.
This value should always be changed in conjunction with
the airflow range on the exhaust linearization module.
EXHAUST LM MAX
1500 CFM
Exhaust Linear module Maximum Flow - Factory set to the
maximum flow rate of the exhaust linearization module.
This value should always be changed in conjunction with
the airflow range on the exhaust linearization module.
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
17
TRACKING CONTROLLER
DISPLAY NAVIGATION
Input Menu Continued...
Supply air temp and neutral mode
PRESSURE TYPE
VAV-AUTO
ROOM TEMPERATURE
OFFSET 0.0˚F
VAV-auto - VAV module is being used and sensing airflow.
VVT-manual - VAV module DISABLED in software (override).
VVT-auto - no VAV mode.
Apply an offset to the room temperature.
SAT OFFSET
0.0˚F
Apply an offset to the Supply Air Temperature.
CONTACT CLOSER
CONFIGURATION
DAMPER FULL OPEN
All Output Halt - disables all outputs.
Disable Binary Cool.
Disable Binary Heat.
Disable Binary Fan.
Disable A04.
Idle Analog Cool - default 0 VDC.
Idle Analog Heat - default 0 VDC
Idle Analog ECM - default 1.5 VDC.
Damper Full Close.
Damper Full Open.
Occupied when Closed - Forces Occupied.
Unoccupied on Closed - Forces Unoccupied.
Not used -disabled.
CO2 SENSOR
NOT DETECTED
Display whether or not a C02 sensor is detected.
CO2 TWEAK
0%
Only displayed if C02 sensor is detected.
Adjust the C02 reading by +/-100%.
C02 OFFSET
0 PPM
Only displayed if C02 sensor is detected.
Adjust the C02 reading by +/-500 ppm.
HUMIDITY SENSOR
NOT DETECTED
Displays whether or not a humidity sensor was detected.
HUMIDITY TWEAK
Only displayed if humidity sensor is detected.
Adjust humidity by +/-100% RH.
HUMIDITY OFFSET
Only displayed if humidity sensor is detected.
Adjust the humidity with an offset by +/-100% RH.
PRESS MENU
TO EXIT
18
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Output Menu
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
SERVICE MENU:
OUTPUT
OUTPUT
FAN
ECM COOL MIN
2.0 VDC
Not applicable.
ECM COOL MAX
8.0 VDC
Not applicable.
ECM HEAT MIN
2.0 VDC
Not applicable.
ECM HEAT MAX
10.0 VDC
Not applicable.
ECM DEADBAND
1.5 VDC
Not applicable.
ECMUNOCCUPIED
1.5 VDC
Not applicable.
BINARYFANTYPE
HEATING
PRESS MENU
TO EXIT
FAN TYPE
HEAT & COOL
Not applicable.
FAN TYPE
DAY & NIGHT HT/CL
Not applicable.
FAN TYPE
CONTINUOUS
Not applicable.
FAN TYPE
DAY & NIGHT HEAT
Not applicable.
FAN TYPE
HEATING
Not applicable.
FAN TYPE
NO FAN
Not applicable.
PRESS MENU
TO EXIT
Not applicable.
priceindustries.com | TRACKING CONTROLLER - Manual
19
TRACKING CONTROLLER
DISPLAY NAVIGATION
Output Menu Continued...
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
REHEAT TYPE
BINARY
Binary - Uses stage 1, 2, 3 - Default.
Hot Water - Uses stage 1&2 for open/close floating point
valve, stage 3 is binary.
Binary/PWN - Stage 1&2 are binary, stage 3 is 24 VAC
PWM 10 second cycle.
Hot Water/PWM - Uses stage 1&2 for open/close floating
point valve, Stage 3 is 24 VAC PWM 10 second cycle.
Hot Water, Hot Air Disabled -Same as above except hot air
disabled.
Binary, Hot Water Disabled - Same as above except hot air
disabled.
Binary PWM, Hot Air Disabled - Same as above except hot
air disabled.
Hot Water/PWM, Hot Air Disabled - Same as above except
hot air disabled.
HEAT STAGE 1
33%
Not shown if Hot Water Heat is used.
Stage 1 engages at 33% heating.
HEAT STAGE 2
66%
Not shown if Hot Water Heat is used.
Stage 2 engages at 66% heating.
HEAT STAGE 3
100%
Stage 3 engages at 100% heating.
DRIVE TIME
90 SECONDS
Hot water only, not shown if Binary Heat is used.
Hot water runtime in seconds.
OUTPUT
HEAT
REHEAT FAIL SAFE
OFF
Off - outputs send 24 VAC on call for heat.
On - outputs send 24 VAC when no call for heat (fail open
valve in cold climates).
ANALOG HEAT MIN
2.0 VDC
Outputs this voltage on heat analog pin when
there is a minimum call for heating.
ANALOG HEAT MAX
10.0 VDC
Outputs this voltage on heat analog pin when there is a
maximum call for heating.
ANALOG HEAT IDLE
0.0 VDC
Outputs this voltage on heat analog pin when there is no
call for heating.
AIRFLOW INTERLOCK
DISABLED
Disabled - Heat is engaged whenever there is a demand
for heat.
Enabled - Airflow must be greater than VAV heat min flow
before heat is energized.
PRESS MENU
TO EXIT
20
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Output Menu Continued...
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
OUTPUT
COOL
BINARY COOL
33%
Cooling engages at 33% cooling load.
ANALOG COOL MIN
0.0 VDC
Outputs this voltage on cool analog pin when there is a
minimum call for cooling.
ANALOG COOL
MAX 10.0 VDC
Outputs this voltage on cool analog pin when there is a
maximum call for cooling.
ANALOG COOL IDLE
0.0 VDC
Outputs this voltage on cool analog pin when there is no
call for cooling.
PRESS MENU
TO EXIT
OUTPUT
OUTPUT PINS
OUTPUT PINS
ANALOG OUTPUTS
A01 USAGE
ECM
Sends a 2 to 10 VDC signal
proportional to the airflow
demand of the room.
A02 USAGE
HEAT
Sends a 2 to 10 VDC
signal proportional to the
heating demand of the
room.
A03 USAGE
COOL
Send a 2 to 10 VDC signal
proportional to the cooling
demand of the room.
A04 USAGE
AUX
Sends a 2 to 10 VDC
signal.
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
21
TRACKING CONTROLLER
DISPLAY NAVIGATION
Output Menu Continued...
OUTPUT PINS
BINARY OUTPUTS
B01 USAGE
FAN
Will output a 24 VAC
signal when the controller
calls for the Fan.
B02 USAGE
HEAT 1
Heat 1 is used for Stage
1 of the reheat stages.
It will output a 24 VAC
signal when the controller
is in Stage 1 of the reheat
stages.
B03 USAGE
HEAT 2
Heat 2 is used for Stage
2 of the reheat stages.
It will output a 24 VAC
signal when the controller
is in Stage 2 of the reheat
stages.
B04 USAGE
HEAT 3
Heat 3 is used for Stage
3 of the reheat stages.
It will output a 24 VAC
signal when the controller
is in Stage 3 of the reheat
stages.
B05 USAGE
COOL
When the controller
goes into cooling mode,
a 24 VAC signal will
be outputted from the
selected binary output.
B08 USAGE
DISABLED
Not Applicable.
B09 USAGE
DISABLED
Not Applicable.
PRESS MENU
TO EXIT
22
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Output Menu Continued...
OUTPUT
ANALOGDATCTRL
USE DAT CTRL
YES
Enable Discharge Air Temperature Control. When DAT
control has been enabled, the "Discharge Air Temperature"
service menu will be activated.
PRESS MENU
TO EXIT
OUTPUT
ROOM LIGHTS
ROOM LIGHTS
DISABLED
Disabled - No outputs used -Default.
Fan - Will trigger room lights.
Heat Stage 3 - Will trigger room lights.
Binary Cool - Will trigger room lights.
B09 - Output will trigger room lights (expansion board).
NOTE: the room lights option will override the selected
output to control a 24 VAC relay which is intended to
control lighting. Use a spare output so there is no conflict
with your current sequence of operations.
PRESS MENU
TO EXIT
PRESS MENU
TO EXIT
priceindustries.com | TRACKING CONTROLLER - Manual
23
TRACKING CONTROLLER
DISPLAY NAVIGATION
BACnet Menu
BACnet Addressing Setup
Scroll through menu with 'Up' and 'Down' keys. Press Enter/Menu button to apply your changes.
*---Saving---* will display as your changes are applied.
SERVICE MENU:
BACNET
MAC SET IN
MAC ADDRESS
HARDWARE: 1
DEVICE INSTANCE:
101
BAUD RATE
76800
Hardware - uses DIP switches on BACnet module for MAC address -default -recommended.
Software - uses STAT to set MAC address -this OVERRIDES the hardware switches and
could be confusing if used improperly.
NOTE: The MAC address (range 1 to 99) is added to the device instance.
Example: MAC address = 1, Device instance = 100 - total address for this device would be
101.
Display current MAC address.
NOTE: DIP switches and software MAC address are only read on startup! See device
instance below.
This is the 'software' BACnet address and MUST be unique on your building site (network).
Range: 1 to 4,194,303.
NOTE: After changing the device instance the STAT will send a RESET command to the TC
to apply the ADDRESS changes. Addresses are only READ on startup, so after any changes
you must reset the controller either via STAT (which is automatic) or cycle 24 VAC power.
NOTE: Addresses are only read on startup to prevent a controller with faulty/damaged/
improperly set DIP switches from popping up all over a network, which would be extremely
difficult to troubleshoot.
This sets the BACnet MS/TP baud rate.
9600 baud (all BACnet devices must at least support this speed) - slowest.
19200 baud.
38400 baud.
76800 baud (default baud rate for PRICE products) - fastest.
PRESS MENU
TO EXIT
BACNET
For more information on BACnet networking - see page 27.
24
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
DISPLAY NAVIGATION
Stat Setup Menu
Stat Options
SERVICE MENU:
STAT SETUP
OCCUPANCY
ON-VVT MODE
MOTION ENABLE
OFF
Shows current occupancy source.
ON from VVT (always on), ON from Airflow, ON from contact, On from Motion Sensor.
Motion Enable (Motion sensor STAT only).
OFF- motion sensor disabled - default.
ON - motion sensor enabled (only enabled if you have a motion stat).
SENSITIVITY
5
Motion Sensitivity (Motion sensor STAT only).
Sets the sensitivity of the motion sensor.
1 - Least sensitive.
9 - Most sensitive.
5 - Default.
MOTION TEST
OFF
Motion test (motion sensor STAT only).
Motion stat will beep each time motion is sensed.
This is useful for adjusting the sensitivity value and testing.
TC will go into unoccupied after no motion is detected and this timer expires.
OCC TIMEOUT
2 MIN.
TC will go into unoccupied after no motion is detected and this timer expires.
LCD BACKLIGHT
Always On
Always Off - push button, lights up on button press..
BACKLIGHT COLOR
AQUA
Allows user settable backlight (Aqua, While, Green and Blue).
SOUND OPTION
ON
On - Stat will beep when user tries to exceed a limit - default.
Off - No sounds, except ping.
DISPLAY OPTIONS
TEMP AND SETPOINT
NAME AND SETPOINT
Displays the T-Stats custom name and the current
Setpoint.
NAME, TEMP./ SETPOINT
DISABLE
Displays the T-Stats custom name and local temperature,
prevents users from changing the local Setpoint.
NAME, TEMP./SETPOINT
ENABLE
Displays the T-Stats custom name and local temperature,
allows users to change the local Setpoint.
CONTROLLER NAME/
SETPOINT DISABLE
Displays the T-Stats custom name and prevents users from
changing the local Setpoint.
CONTROLLER NAME/
SETPOINT ENABLE
Displays the T-Stats custom name and allows users to
change the local Setpoint.
ROOM TEMP. ONLY
Displays only the current temperature, prevents
users from changing the local Setpoint.
priceindustries.com | TRACKING CONTROLLER - Manual
25
TRACKING CONTROLLER
DISPLAY NAVIGATION
Stat Setup Menu Continued
Stat Options
SETPOINT ONLY
TEMP. AND SETPOINT
Displays only the current Setpoint.
Displays only the current temperature, allows users to
change the local Setpoint.
PRESS MENU
TO EXIT
CONTROLLER NAME
Set a custom name for the stat.
PRESS MENU
TO EXIT
Diagnostics Menu
SERVICE MENU:
DIAGNOSTICS
DIAGNOSTICS
LOAD DEFAULTS
DIAGNOSTICS
RESET CONTROLLER
Reload the factory defaults to the controller.
Reset the controller.
PRESS MENU
TO EXIT
26
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
NETWORKING AND SETUP
Setting the MAC Address
MAC Address: MAC (media access control) must be UNIQUE on an MS/TP
network segment within a building. An installer setting up an MS/TP segment
with 30 devices must ensure each device has a UNIQUE MAC address (Range
1-99). The MAC address is set with dip switches on the BACnet Module. This
is the hardware setup for the MAC address. The MAC address can also be set
in software, through the LCD thermostat. This option of setting the address
through software is available when the controller is not accessible to the user
(finished drywall ceiling for example).
NETWORK SEGEMENT 1
MSTP Network 1
PC OR ROUTER
1
DEVICE INSTANCE
101
2
102
3
103
4
104
MAC ADDRESS OF DEVICES
MAXIMUM RECOMMENDED
30 DEVICES ON A SEGMENT
MAC RANGE 1-99
NETWORK SEGMENT 2
MSTP NETWORK 2
PC OR ROUTER
1
DEVICE INSTANCE
201
2
202
3
203
4
204
MAC ADDRESS OF DEVICES
MAXIMUM RECOMMENDED
30 DEVICES ON A SEGMENT
MAC RANGE 1-99
TECH TIP
Each device needs a unique MAC and device instance. All devices must be at the same baud rate. 24 VAC
hot and common polarities are critical and must not be reversed on ANY devices! Reverse polarity will stop
communication on that MS/TP segment.
priceindustries.com | TRACKING CONTROLLER - Manual
27
TRACKING CONTROLLER
NETWORKING AND SETUP
Setting the Device Instance
Device Instance: A device instance number identifies a device within an entire
building, therefore giving it a unique number or address, much like a telephone
ext. number. A building can have one telephone number, but all the extensions
have a unique number to identify them. A device instance number would work
the same way and must be unique throughout the building. The Device Instance
number is user set through the LCD thermostat or the USB LINKER tool.
Below is a table defining how a device instance number is obtained.
NOTE: Each device on a network segment must be set to run at the same
speed or baud rate.
Description
Default Value (Factory)
Notes
MAC Address
Set by DIP switch
Value: limited to 1 to 99
Tier1 (x100)
58
Value: limited to 0 to 99
Tier2 (x10,000)
1
Value: limited to 0 to 99
Tier3 (x1,000,000)
0
Value: limited to 0 to 4
EXAMPLE DEVICE INSTANCE SETUP WITH DEFAULT SETTINGS
MAC Address = 4 (4 x 1 = 4) – Set by DIP Switches on BACnet module, or through software.
+
TIER 1 = 58 (58 x 100 = 5,800) – Set through software
+
TIER 2 = 1 (1 x 10,000 = 10,000) – Set through software
+
TIER 3 = 0 (0 x 1,000,000 = 1,000,000) – Set through software
=
Final Device instance
=
0,015,804
Final Device instance
=
0
Tier3
Multiplier
28
01
58
Tier1
Tier2
Multiplier
Multiplier
TRACKING CONTROLLER - Manual | priceindustries.com
04
MAC
Address
TRACKING CONTROLLER
NETWORKING AND SETUP
VC/TC v3.10.0 BACnet Points List
Object
Name
Units
Range
AI1
Room Temperature
°F; °C
(-59)-300
AI2
Airflow or Supply Airflow – applicable for Supply/
Exhaust Tracking mode
CFM; L/s
AI3
Supply Air Temperature or Discharge Air
Temperature – applicable for Exhaust Box mode
AI4
Description
R/W
Current room temperature
R
0-9999
Current duct airflow or Current supply duct airflow – applicable
for Supply/Exhaust Tracking mode
R
°F; °C
Dynamic
Current supply air temperature or Current discharge air
temperature – applicable for Exhaust Box mode
R
CO2 Reading
PPM
Dynamic
Current CO2 at the T-Stat
R
AI5
Humidity Reading
%RH
Dynamic
Current relative humidity at the T-Stat
R
AI6
AI4 (Expan) or Exhaust Airflow – applicable for
Supply/Exhaust Tracking mode
Volts VDC or
CFM; L/s
Dynamic
Current voltage at AI6 of expansion module or Current exhaust
duct airflow – applicable for Supply/Exhaust Tracking mode
R
AI7
AI5 (Expan)
Volts VDC
Dynamic
Current voltage at AI7 of expansion module
R
AI8
AI6 (Expan)
Volts VDC
Dynamic
Current voltage at AI8 of expansion module
R
°F; °C
Dynamic
Current temperature from expansion module
R
Contact
Open;
Contact
Closed
Binary input that can be tied to several usages
R
State of valve pressure alarm
R
AI9
Thermistor (Expan)
Note 1: Hidden if T-Stat does not measure CO2
Note 1: Hidden if T-Stat does not measure humidity
Note 1: Hidden if VAV module set to Linear Module
BI1
Contact Closure
Contact
Open;
Contact
Closed
BI2
Valve Pressure
Normal/
Alarm
Normal/
Alarm
AO1
Analog Out 1 ([Usage])
Volts VDC
0-10
Analog output that can be tied to several usages
R/W
AO2
Analog Out 2 ([Usage])
Volts VDC
0-10
Analog output that can be tied to several usages
R/W
AO3
Analog Out 3 ([Usage])
Volts VDC
0-10
Analog output that can be tied to several usages
R/W
AO4
Analog Out 4 ([Usage])
Volts VDC
0-10
Analog output that can be tied to several usages
R/W
AO5
Damper Position
%
0-100
BO1
Binary Out 1 ([Usage])
On; Off
On; Off
Binary output that can be tied to several usages
R/W
BO2
Binary Out 2 ([Usage])
On; Off
On; Off
Binary output that can be tied to several usages
R/W
BO3
Binary Out 3 ([Usage])
On; Off
On; Off
Binary output that can be tied to several usages
R/W
BO4
Binary Out 4 ([Usage])
On; Off
On; Off
Binary output that can be tied to several usages
R/W
BO5
Binary Out 5 ([Usage])
On; Off
On; Off
Binary output that can be tied to several usages
R/W
BO6
Binary Out 8 ([Usage])
On; Off
On; Off
BO7
Binary Out 9 ([Usage])
On; Off
On; Off
MO1
Room Lights
Text
4 States
Note 1: See Input Menu in O&M manual for options
Note 1: Only visible if VAV module set to Linear Module
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Analog output that can be tied to several signals
Note 1: See Output Menu in O&M manual for options
Note 2: Hidden if Damper Cal. Mode is set to No Cal.
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Note 1: See Output Menu in O&M manual for options
Binary output that can be tied to several usages
Note 1: See Output Menu in O&M manual for options
Note 2: Hidden if in Sup/Ex Tracking Mode
Binary output that can be tied to several usages
Note 1: See Output Menu in O&M manual for options
Note 2: Hidden if in Sup/Ex Tracking Mode
State of control for room lights
1 – Off (Auto)
2 – On (Auto)
3 – Off (Manual)
4 – On (Manual)
R/W
R/W
R/W
R/W
Note 1: Hidden if room lights output is not set
priceindustries.com | TRACKING CONTROLLER - Manual
29
TRACKING CONTROLLER
NETWORKING AND SETUP
VC/TC v3.10.0 BACnet Points List – Continued
Object
Name
Units
Range
Description
CFM; L/s
0–9999
Current airflow target or Current supply airflow target–
applicable for Supply/Exhaust Tracking mode
R/W
AV1
Airflow Target or Supply Airflow Target –
applicable for Supply/Exhaust Tracking mode
AV2
Room Setpoint – High Limit
°F; °C
AV3–100
Highest user-adjustable temperature set point on the T-Stat
R/W
AV3
Room Setpoint – Low Limit
°F; °C
32–AV2
Lowest user-adjustable temperature set point on the T-Stat
R/W
R/W
R
AV4
Night Heat Setpoint
°F; °C
32–AV5
Setpoint at which the room will enter heating mode during
unoccupied periods
AV5
Night Cool Setpoint
°F; °C
AV4–100
Setpoint at which the room will enter cooling mode during
unoccupied periods
R/W
AV6
Room Setpoint
°F; °C
AV3–AV2
Current room setpoint
R/W
AV7
Unoccupied (Night) Damper Position/
Unoccupied Airflow Target
% or CFM;
L/s
0–100 or
0–9999
Position (%) or airflow (CFM; L/s) controller will target when in
cooling mode during unoccupied periods
R/W
AV8
Neutral Duct Temp Airflow Target
CFM; L/s
0-9999
See TC flow response chart in O&M manual
R/W
AV9
Cool Min Airflow Setpoint
CFM; L/s
0-AV10
See TC flow response chart in O&M manual
R/W
AV10
Cool Max Airflow Setpoint
CFM; L/s
AV9-9999
See TC flow response chart in O&M manual
R/W
AV11
Heat Min Airflow Setpoint
CFM; L/s
0-AV12
See TC flow response chart in O&M manual
R/W
AV12
Heat Max Airflow Setpoint
CFM; L/s
AV11-9999
See TC flow response chart in O&M manual
R/W
T-Stat tied to controller will sound number of times that is
written
R/W
AV13
Ping
#
0-255
Note 1: Useful for locating a T-Stat that is tied to the controller
Current Room Load
-100% to -1% = cooling load
0% = deadband/neutral mode
1% to 100% = heating mode
AV14
Controller Status
%
(-100)-100
R
AV15
Proportional Band
°F; °C
1-20
Temperature band through which the PI controller travels
through 1% to 100% load
R/W
AV16
Day Differential
°F; °C
1-20
This is the +/- value around the setpoint that determines the
controller is in deadband
R/W
Text
0-1
Controller commissioning status. Should be changed to
commissioned after controller has been set up
0 = Not Commissioned
1 = Commissioned
R/W
AV17
Commissioned
AV18
Exhaust Offset Target
CFM; L/s
0-9999
Airflow difference between the supply and exhaust valves
R
AV19
Exhaust Airflow Target
CFM; L/s
0-9999
Current exhaust airflow target
R
AV20
Current DAT Target
°F; °C
32-150
Current discharge air temperature target
R
30
TRACKING CONTROLLER - Manual | priceindustries.com
Note 1: Visible in Supply/Exhaust Tracking mode
Note 1: Visible in Supply/Exhaust Tracking mode
Note 1: Hidden if DAT control is not active
TRACKING CONTROLLER
NETWORKING AND SETUP
VC/TC v3.10.0 BACnet Points List – Continued
Object
Name
Units
Range
Description
R/W
R/W
MV1
Damper Override
Text
8 states
Damper override value
1 = Disabled (No Override)
2 = Go to Cool Min
3 = Go to Cool Max
4 = Go to Heat Min
5 = Go to Heat Max
6 = Go to Neutral
7 = Go to Full Open
8 = Go to Full Closed
MV2
Occupancy
Text
2 states
State of occupancy
1 = Unoccupied
2 = Occupied
R
R
MV3
Occupancy Source
Text
13 states
Occupancy Source
1 = Default Mode (Occupied)
2 = Airflow (Occupied)
3 = Contact Closure (Occupied)
4 = T-Stat Button (Occupied)
5 = Motion Sensor (Occupied)
6 = Network Override (Occupied)
7 = Local Override (Occupied)
8 = Airflow (Unoccupied)
9 = Contact Closure (Unoccupied)
10 = T-Stat Button (Unoccupied)
11 = Motion Sensor (Unoccupied)
12 = Network Override (Unoccupied)
13 = Local Override (Unoccupied)
MV4
Occupancy Override
Text
3 states
Occupancy override value
1 = No Override
2 = Force Unoccupied
3 = Force Occupied
R/W
6 states
Type of binary fan in use
1 = No Fan
2 = Day Heat/Night Heat
3 = Day Constant/Night Heat
4 = Constant
5 = Day Constant/Night Demand
6 = Day Demand/Night Demand (air terminal)
R/W
9 states
Type of binary reheat in use
1 = Binary
2 = Hot water/Binary
3 = Binary/PWM
4 = Hot water/PWM
5 = Binary (dis. with hot air)
6 = Hot water/Binary (dis. with hot air)
7 = Binary/PWM (dis. with hot air)
8 = Hot water/PWM (dis. with hot air)
9 = Disabled
R/W
8 states
Application
1 = Air Terminal – Applicable for VC
2 = Fan Coil (4 pipe) – Not applicable for TC/VC
3 = Fan Coil (2 pipe) – Not applicable for TC/VC
4 = Dual Duct – Not applicable for TC/VC
5 = Exhaust box – Applicable for VC
6 = Supply/Exhaust Tracking – Applicable for TC
7 = Mixing Box D.A.T. – Not applicable for TC/VC
8 = CO2 Tracking – Not applicable for TC/VC
R/W
MV5
MV6
MV7
Binary Fan Type
Binary Reheat Type
Application
Text
Text
Text
priceindustries.com | TRACKING CONTROLLER - Manual
31
TRACKING CONTROLLER
NETWORKING AND SETUP
Linker 2 - USB Service Tool
The Price USB LINKER2 is the
interface that can be used with any
of the Price thermostats for the TC.
The LINKER2 connects to a laptop
(not supplied) via a Type A USB A
to B cable supplied by Price, and
then connects to the service jack of
the thermostat via an RJ-12 Cable
supplied by Price. The laptop is
required as a setup tool to setup
up your parameters for your VAV
application. If a laptop is not available,
an LCD Thermostat can be purchased
as an upgrade and used as a setup/
balancing tool. The LCD Thermostat
provides full functionality for setting up
system parameters.
REQUIRED ITEMS
LAPTOP SETUP TOOL
LINKER 2 INTERFACE
USB A-B CABLE
DIAL THERMOSTAT
RJ-12 CABLE
FOR LATEST SOFTWARE SEE:
priceindustries.com
LCD TERMOSTAT
TECH TIP
When using a TC with a DIAL thermostat, the USB LINKER2 is one option for setting up the TC. Or you can
purchase a single LCD thermostat (TC-TS-LCD) and use that for setup. Remember all settings are stored in the
TC, not the STAT!
32
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
NETWORKING AND SETUP
Troubleshooting
The following information is provided in the event that the TC does not appear to function properly after installation.
Fault
Solution
TC appears to be not responding or have
no power. Green light on the controller is not
blinking. Thermostat green indication light not
on, or LCD screen is blank.
Check thermostat first for either green indication light, or LCD display.
If either of these does not appear, then check the TC for power (green
blinking light). If no power is present, check 24 VAC power with a
Multimeter. Cycle power to the controller. If this doesn’t restore power,
check the power that is feeding that controller for your problem.
Damper acts erratically
Check actuator mounting; ensure that the damper is fully closed when
the actuator is in the fully closed position. Pivot the grey release clutch on
actuator and move by hand. Ensure that the set screw on the damper shaft
is torqued down tight and no slipping is occurring.
Also, ensure the 3 wires in the actuator itself are wired correctly. Green to
COM, red to CW and yellow to CCW.
Airflow readings not as specified
RED (HI)
GREEN (LO)
On TC's ordered with the VAV module option, ensure that the tubing is
correct. Red tube from Price SP300 sensor to the positive terminal on the
air flow sensor, green tube from SP300 to the negative terminal on the air
flow sensor. Also, ensure that the tubes are fully over the barbed fitting on
the sensor, and that the tubes are not pinched in any way.
PRICE
SP3000
Flow Sensor
Check inlet size of duct and ensure that size is correctly set in the
controller. Note: the STAT does not store the duct size, it is stored in the
TC.
24 VAC Binary Outputs not functioning
Ensure that the TC has 24 VAC power.
Ensure that there is a call for heating or for cooling. If so, check to see that
the indication light is on for the output.
The next step would be to check the output with a relay. Ensure that the
relay has engaged (pulled in) for either heating or cooling application.
The next item to check for would be the Hot/COM jumper on the TC. Make
sure that if you're switching the Hot side, that the jumper is on the Hot,
likewise for switching a common, ensure the jumper is on the COM.
priceindustries.com | TRACKING CONTROLLER - Manual
33
TRACKING CONTROLLER
NETWORKING AND SETUP
Troubleshooting - Continued
The following information is provided in the event that the TC does not appear to function properly after installation.
Fault
Solution
Analog Outputs not functioning
Ensure that the TC has 24 VAC power.
Troubleshooting - continued
Check the analog output for voltage with a Multimeter. You should
see a voltage in the range of 0-10VDC. Direct Acting Output – 0 VDC
indicates that the field device is closed or at a minimum position. 10
Solution
VDC indicates
thepower.
field
is open or at a full open position.
Ensure that the PICthat
has 24 VAC
Checkdevice
the
analog output for voltage with a Multimeter. You should
a voltage inis
the typical
range of 0-10vdc.
Direct see
acting
with cooling applications.
Direct Acting Output – 0 Vdc indicates that the field
The following information is provided in the eventthat the Price Intelligent controller (PIC) does not appear
to function properly after installation.
Fault
Analog Outputs not functioning
device is closed or at a minimum position. 10 Vdc
indicates that the field device is open or at a full open
position.
Direct acting
is typical with –
cooling
Reverse
Acting
Output
0VDC indicates that the field device is full
applications.
Reverse Acting Output – 0 Vdc indicates that the field
open or
maximum position, and 10VDC indicates fully closed or
device is full open or maximum position, and 10 Vdc
indicates fully closed or minimum position. Reverse
minimum
acting is typical with heating applications.
acting isposition.
typical with heatingReverse
applications.
SAT Sensor Analog input not functioning
SAT Sensor Analog
input not functioning
Ensure that there is a sensor wired to the input on the TC. Check the
type of sensor, it should be a 10k Ohm type J thermistor.
BACnet Communication Errors
BACnet Communication Errors
Ensure that there is a sensor wired to the input on the
PIC controller. Check the type of sensor, it should be a
10k Ohm type thermistor.
tm
BACnet
MS/TP is based on a RS-485 network. It must be wired
in a daily chain configuration. A daisy chain means that
BACnet
MS/TP is based on a RS-485 network. It must be wired in a
there is only one main cable, and every network device
is connected directly along its path.
daily chain
configuration. A daisy chain means that there is only one
main cable, and every network device is connected directly along its
path.
DO NOT use Star, Bus, “T”, or any other type of
network configuration. Any of these other network
configurations will result in an unreliable network, and
make troubleshooting almost impossible.
Correct polarity is imperative on MSTP wiring. Always
ensure that the positive terminal on a device has the
same color wire connected to it throughout the network,
same for the negative terminal.
Eg. 2 wire conductor with black and white wires – black
to the positive terminal, and white to the negative
terminal. Keep this consistency throughout the network.
DO NOT use Star, Bus, “T”, or any other type of network configuration.
Any of these other network configurations will result in an unreliable
network, and make troubleshooting almost impossible.
www.priceelectronics.ca/PIC
Page 37 of 44
Correct polarity is imperative on MSTP wiring. Always ensure that the
positive terminal on a device has the same color wire connected to it
throughout the network, same for the negative terminal.
Eg. Two wire conductor with black and white wires – black to the
positive terminal, and white to the negative terminal. Keep this
consistency throughout the network.
34
TRACKING CONTROLLER - Manual | priceindustries.com
g - continued
mation is provided in the eventthat the Price Intelligent controller (PIC) does not appear
after installation.
TRACKING CONTROLLER
Solution
NETWORKING AND
cation Errors
TheSETUP
network should be terminated twice, once at the beginning,
and again at the end of each run. This is strongly
tm
Troubleshooting - recommended
Continued
The following information is provided in the event that the TC does not appear to function properly after installation.
Fault
BACnet
Communication
Errors
cation Errors
tm
BACnet
Communication
Errors
cation Errors
cation
BACnet
Communication
Errors
BACnet
Communication
Errors
Errors
TC
The network speed or baud rate must be the same throughout the
network.
Note:Solution
the default speed for Price BACnet MS/TP controls is
76800. BACnet MS/TP currently supports 4 standard speeds
network
be terminated
twice,76800.
once at the beginning, and again at the end of each run. This is
whichThe
are:
9600,should
19200,
38400 and
strongly recommended.
BinaryThe
address
mustorbe
unique
for be
each
device
on thethe
network.
network speed
baud
rate must
the same
throughout
network.
No two
devices
can
have
the
same
address.
This
includes
if you
NOTE: the default speed for Price BACnet MS/TP controls is 76800. BACnet
MS/TP currently supports 4
are incorporating
a
Price
product
into
an
existing
network.
standard speeds which are: 9600, 19200, 38400 and 76800.
Determine the existing addressing scheme for the existing
network. The address is set on the addressable dip switches on
the BACnet
module
is expanded
offonofthethe
PIC controller.
Binary address
mustwhich
be unique
for each device
network.
No two devices can have the same
address. This includes if you are incorporating a Price product into an existing network. Determine the
existing addressing
scheme
for the existing network. The address is set on the addressable dip switches
Grounding
and 24 VAC
polarity:
on
the
BACnet
module
which
is expanded
off of when
the TC. wiring the MS/TP
Proper grounding is absolutely
essential
BACnet Network. Proper grounding will prevent manypotential
problems
thatand
can24occur
in a network
of devices.
Common
Grounding
VAC polarity:
Proper grounding
is absolutely
essential when wiring the MS/TP
symptoms
of
a
poorly
grounded
network
can
include
inconsistent
BACnet Network. Proper grounding will prevent many potential problems
that can occur in a network
of devices.
Common
symptoms of a and
poorlydamage
grounded network
can include inconsistent BACnet MS/TP
BACnet
MS/TP
communications
from voltage
communications
and damage
from voltage
spikes. The most
method of grounding is to ground
spikes.
The most practical
method
of grounding
is topractical
ground
every
24
VAC
transformer
common/neutral
used
to
power
the
controls.
every 24 VAC transformer common/neutral used to power the
Connect the “common/neutral” wire of the SECONDARY side of the transformer to earth ground – such
controls.
as the
ground
screw on in the electrical
Connect
the
“common/neutral”
wirebox.
of the SECONDARYside of
the transformer to earth ground – such as the ground screw on in
the electrical
box.
Note: Flipping
24 VAC HOT and COMMON will cause the BACnet MS/TP network to stop
Ensure
HOT and
and COMMON
are not
ANY controllers. (Warning: Controllers
Note:communicating!!!
Flipping 24 VAC
HOT
COMMON
willreversed
causeonthe
will
still
power
up
and
run
even
if
HOT
and
COMMON
are
reversed.
HOT output signals to other
BACnet MS/TP network to stop communicating!!! EnsureHowever
devices such as heaters, relays, etc will not work as intended!)
and COMMON are not reversed on ANY controllers. (Warning:
Controllers will still power up and run even if HOT and COMMON
are reversed. However output signals to other devices such as
heaters, relays, etc will not work as intended!)
24 VAC Hot
High Voltage Primary
Side
24 VAC Common
priceindustries.com | TRACKING CONTROLLER - Manual
www.priceelectronics.ca/PIC
Page 38 of 44
35
TRACKING CONTROLLER
NETWORKING AND SETUP
Hardware Specifications
Power Requirements
24 VAC, 47-63 Hz 6 VA (not including output loading) NEC Class II.
Ambient Ratings
32º to 131º F (0º to 55º C) 10 to 90% RH (non-condensing)
Outputs
24 VAC Binary (x7). Max 0.5Amps each, MAX 1.85A total Switched HOT
or Switched COMMON
Stages of heat or heat open/close (x3)
Fan
Cooling
Damper CW
Damper CCW
Analog 0-10 VDC (x4). Max: 10mA each.
Fan (ECM)
Heat
Cool
Aux
Inputs
Changeover sensor (10k Type J thermistor)
Contact closure (night setback)
Airflow sensor (optional)
Thermostat inputs
Room setpoint dial
Temperature sensor (10K Type J thermistor)
Accuracy of +/- 0.5°F from 55°F to 85°F (+/ 0.25°C from 13°C to 25°C)
Communication ports
BACnet MS/TP Connection (optional)
Communication speeds: 9,600, 19,200, 38,400, 76,800 (default)
Maximum recommended devices per MS/TP segment: 30
LINKER2 port
For local setup using Price USB LINKER2 service tool
Actuator Specifications
40 in-lbs (nominal torque). 90 seconds running time 90º maximum angle of rotation. External slide knob
for manual override. Less than 35 db (A) noise level
Airflow Sensor
Specifications
Mems technology Optional 0-1 SLM flow sensor.
(0-1” W.C. equivalent) Not position sensitive.
Tubing Specifications
Flow Sensor tubing must be ¼ inch outside diameter
Size
11" x 5.74" x 2.75"
Weight
1.8lb. (816g)
36
TRACKING CONTROLLER - Manual | priceindustries.com
TRACKING CONTROLLER
NOTES
priceindustries.com | TRACKING CONTROLLER - User Guide
37
TRACKING CONTROLLER
NOTES
38
TRACKING CONTROLLER - User Guide | priceindustries.com
TRACKING CONTROLLER
NOTES
priceindustries.com | TRACKING CONTROLLER - User Guide
39
This document contains the most current product information as of this printing.
For the most up-to-date product information, please go to priceindustries.com.
© 2014 Price Industries Limited. All rights reserved.
Download