Genesis Enclosure Model Design and Planning Guide

advertisement
Genesis Enclosure Model
www.garaventa.ca
Genesis Enclosure and Shaftway Model
Table of Contents
Introduction .............................................................................................................................. 2
What is a Vertical Platform Lift? ............................................................................................. 3
Why a Vertical Platform Lift? .................................................................................................. 3
Design Assistance ................................................................................................................... 3
Custom Finishes ...................................................................................................................... 3
How it Works ............................................................................................................................. 4
Enclosure Model vs. Shaftway Model .................................................................................... 5
Platforms .................................................................................................................................. 6
Platform Controls ..................................................................................................................... 6
Call Stations ............................................................................................................................. 7
Lifting Heights and Mast Sizes ............................................................................................. 10
Leadscrew Drive System ...................................................................................................... 11
Hydraulic Drive System ........................................................................................................ 11
Special Features and Options .............................................................................................. 12
Enclosure Base and Pit Dimensions ................................................................................... 18
Enclosure Platform Clearances ........................................................................................... 19
Shaftway/Pit and Platform Clear Dimensions ..................................................................... 20
Garaventa Style Door and Gate Frames .............................................................................. 24
Fire Rated Door and Frames ................................................................................................ 25
Garaventa Style Door Clearances ........................................................................................ 26
Fire Rated Door Clearances ................................................................................................. 30
Attachment Methods ............................................................................................................. 34
Lead Screw Drive System: Technical Reference of Standard Features ........................... 36
Hydraulic Drive System: Technical Reference of Standard Features .............................. 37
Enclosure Model Loading Diagram ..................................................................................... 38
Shaftway Model Loading Diagram ....................................................................................... 39
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-1-
© Garaventa
Printed in Canada
Table of Contents
Table of Contents
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Introduction
Garaventa has been dedicated to developing safe and reliable accessibility solutions since 1978 and is
now an industry leader worldwide. Years of hard work and an uncompromising commitment to quality
have enabled us to perfect the internationally renowned Garaventa GSL Artira. This same commitment
to quality has been applied to the Xpress II inclined platform lift and the Genesis vertical platform lift.
The Xpress II is an inclined platform lift designed just for straight stairways. The sleek and attractive
Xpress II can be installed indoors or outdoors and is a cost-effective access solution.
The Genesis vertical platform lift incorporates state of the art features with elegant styling and quiet
operation. The Genesis has a variety of models and configurations with many standard and optional
features to choose from. With the development of the Genesis vertical platform lift, Garaventa has
taken a significant step towards being able to solve most accessibility challenges for building owners.
Our expertise in providing accessibility solutions has enabled our design team to take on the most
challenging access situation, and develop innovative solutions for schools, places of worship, offices,
hotels, airports, subways and a wide range of public and private buildings around the world.
We have built our business on service. Please contact us and let us help solve your access challenges.
©2003 Garaventa. As we are continuously improving our products,
specifications outlined in this guide are subject to change without notice.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-2-
© Garaventa
Printed in Canada
Introduction
Garaventa - the world’s #1 choice in accessibility solutions.
Genesis Enclosure Model
www.garaventa.ca
Product Description
What is a Vertical Platform Lift?
A vertical platform lift transports a passenger, in a wheelchair or someone who has difficulty using
stairs, from one landing to another. Vertical platform lifts provide a code compliant access solution for
lifting heights of up to 12 ft. (in some jurisdictions lifts can travel up to 14 ft.). A vertical platform lift can
be operated independently or by an attendant. The Garaventa Genesis Vertical Platform Lift is versatile,
attractive and suitable for indoor or outdoor applications.
Why a Vertical Platform Lift?
Cost-effective
Vertical lifts are more cost-effective than an elevator and do not require a machine room to house the
electrical and mechanical components.
Blends with Environment
A vertical lift can be an attractive alternative and take less space than a lengthy or winding ramp.
Adjacent to stairs or in an area complementary to your building, these lifts can be blended or finished to
compliment the aesthetics of the site.
Meets ADA Requirements
Garaventa vertical platform lifts are approved in the ADA Accessibility Guidelines as a means to provide
public building access.
Design Assistance
With over 25 years of experience, Garaventa has the expertise to overcome almost any design
challenge you face. Please call our Design Hot Line with your accessibility challenge.
1-800-663-6556
or
1+604-594-0422
Custom Finishes
The standard finish is electrostatically applied baked powder finish in Satin Grey for the steel panels
and champagne anodized aluminum extrusions for the framework. As an option, these components can
be painted from the large selection of RAL colors (global paint color system). Alternatively, the Genesis
enclosure can be supplied with 5mm (3/16") bronze tinted or clear plexiglass panels or 6mm (1/4”)
tempered glass panels.
As an option Garaventa also offers Graphic Imaging and Exotic Finishes. Exotic finishes include brass
and stainless effects created with special paint. Textured and speckled paint can be applied to the
panels and extrusions. The panels can also be supplied with wood finishes, Formica, architectural
metals or any material not exceeding 1/2” in thickness.
Outdoor Applications
When located outdoors, the Genesis is modified to ensure durability and reliable performance. Included
in the outdoor package are: hot dippped galvanized base, plated platform, plated mezzanine brackets,
sealed electrical box, rubber boots on switches and stainless steel fasteners. For outdoor installations
in extreme climates, consult Garaventa for feasibility and specifications. In certain indoor applications,
such as near a swimming pool, the outdoor package may be required.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-3-
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
How it Works
How it Works
The Genesis vertical platform lift is offered in a variety of configurations and styles for different
accessibility challenges. All versions of the Genesis Vertical Lift operate in the same manner and
consists of a complete drive system, a platform with side walls, doors with an interlock system and
call stations.
The mast houses the electrical and mechanical components that raises and lowers the catalivered
platform. The doors or gates can not be opened unless the platform is at the appropriate landing. The
platform is called to the landing by using the call stations located at each landing. When a pssenger
is on the lift, the platform controls override the call stations. Once at a landing, the door interlock is
released and the door can be opened to exit.
The Genesis can be used to provide access indoors or outdoors and can be installed directly on the
floor or in a 76mm (3") deep pit.
Upper Gate
Mast
Lower Door
Platform Controls
Grab Rail
Platform
Ramp
(required for floor
mount units only)
Mounting Base
Enclosure Model with Standard Straight-Through Configuration Shown
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-4-
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
System Overview
Enclosure Model vs. Shaftway Model
The Genesis is available in two styles, the Enclosure Model and the Shaftway Model. The Enclosure
Model consists of a mast, platform, doors and the walls that enclose the lift. The Shaftway Model
consists of a mast, platform and doors. The walls enclosing the shaftway unit are built by others in
accordance to Garaventa’s specifications.
Enclosure Model
The enclosure frame is constructed of champagne color anodized aluminum extrusions. The
attractive contoured corner posts feature vertical etched lines that enhance the appearance of the lift.
Due to the unique design of the corner posts, nuts, bolts and screws are hidden, giving the lift an
overall streamlined look. Horizontal cross members are fitted into the corner posts, securing the
enclosure panels. The panels come in a choice of 16 gauge painted galvanized mild steel, 5mm
(3/16”) bronze tinted or clear Plexiglas or 6mm (1/4”) tempered glass.
Shaftway Model
The Genesis Shaftway unit is designed to fit the essential lift components within your shaftway walls.
The Genesis Shaftway Model can have either aluminum frame doors/gates, fire rated steel doors, or
the doors can be supplied by others. All styles of doors/gates have interlocks integrated with our
control system.
Steel, Plexiglas
or Tempered
Glass Panels
Shaftway Wall
Supplied By
Others
Anodized Aluminum
Extrusion Corner Posts
Note: For visual
effects, both doors are
shown open; however
due to safety reasons
only one door can be
open at a time.
Anodized
Aluminum
Extrusion Cross
Members
Doors
Frame Mounted
Call Station
Enclosure Model
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Shaftway Model
-5-
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Platforms
Platforms
The platform is rated for a load of 340 kg. (750 lbs.) and has 1070 mm (42 1/8") high side walls. The
side wall in front of the mast includes a grab rail, platform controls and courtesy lights. The platform
lighting remains on during travel and for a period of 8 seconds after the lift reaches the designated
landing. This lighting is wired to a battery which provides emergency lighting power in the event of a
mains power failure. Additional general ambient lighting will most likely be required to satisfy local code.
Clear inside dimensions vary depending on the entry/exit configuration and size of platform. For sizes
and clear dimensions of an Enclosure Model please see page 19 and for the Shaftway Model pages
20-23.
Enclosure Platforms
Shaftway Platforms
The Genesis Enclosure Model has 3 platform
sizes to meet your requirements:
The Genesis Shaftway Model has 5 platform sizes
to meet your requirements:
• Compact (36” x 49”)
• Mid-Size (38” x 60”)
• Custom
• 36” x 54”
• 36” x 60”
• 42” x 60”
• Standard (38” x 54”)
• Large (43” x 60”)
Platform sizes listed are based on a Straight through configuration.
Side Walls
Grab Rail
Platform
Controls
Platform
Platform Controls
The platform controls consist of two directional
push buttons, a key switch, a safety indicator
light, an emergency stop/alarm button and
courtesy lights. The direction buttons are all
constant pressure operation, as required by
code. The platform is wired to support an ADA
compliant phone (see page 13).
Emergency Stop / Alarm
Key Switch
Safety Indicator Light
Directional Controls
Platform Light
Note: See page 17 for Three-Stop unit
platform control information.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-6-
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Call Stations
Call Stations
The platform is called to the landing by pressing the appropriate directional button. The platform will
automatically stop when it has reached that landing.
Enclosure Frame Mounted Call Stations
Call stations for the Genesis Enclosure can be mounted
in the aluminum extrusion frame of the lift beside both the
lower and upper door/gate. The call stations consist of up
and down continuous pressure buttons, a key switch and
an “in use” lamp. The lower call station also includes a
service key switch. Call stations are available, as an
option, for wall mounting, either flush mounted or surface
mounted.
Directly below the frame mount call station is the “Door
Interlock Emergency Access” which is accessed by
inserting a special tool into the hole and turning it 45°.
This will allow you to open the door for maintenance or
an emergency (power failure covered by standard
system).
Note: See page 17 for Three-Stop unit intermediate call
station information.
Up Button
Call/Send Button
Key Switch
“In Use” Lamp
Service Key Switch
(Lower Call Station Only)
Door Interlock
Emergency Access
Enclosure Frame Mounted Call Station
for Garaventa Style Door
Shaftway Frame Mounted Call Stations:
Garaventa Style Doors
Call stations for the Genesis Shaftway can be mounted in
the aluminum extrusion frame beside the upper and
lower door/gate. The call stations consist of up and down
continuous pressure buttons, a key switch, and an “in
use” lamp. The lower call station also includes a service
key switch. Call stations are also available, as an option,
for wall mounting, either flush mounted or surface
mounted.
Directly below the frame mounted call station is the “Door
Interlock Emergency Access” which is accessed by
inserting a special tool into the hole and turning it 45°.
This will allow you to open the door for maintenance or
an emergency (power failure covered by standard
system).
Note: See page 17 for Three-Stop unit intermediate call
station information.
Note: Frame mounted call stations must not be used at
landings with a ramp, or where a power door operator
is installed.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-7-
Call / Send
Buttons
Key Switch
“In Use”
Lamp
Service Key
(Lower Call Station
only)
Door Interlock
Emergency
Access
Shaftway Frame Mounted Call Station
for Garaventa Style Door
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Call Stations
Frame Mounted Call Station Dimensions
)
/2”
1
(1
38
235 (9 1/4”)
210 (8 1/4”)
)
/2”
1
(1
38
Lower Landing Call Station Plate
Dimensions
Upper & Intermediate (optional) Landing Call
Station Plate Dimensions
Wall Mounted Call Station Dimensions
Call stations for the Genesis can also be mounted on the wall. They can be surface mounted or
recessed into the wall with a flush mount call station (includes collar for finishing wall). The call stations
consist of up and down continuous pressure buttons, a key switch, and an “in use” lamp.
286 (11 1/4”)
250 (9 7/8”)
245 (9 5/8”)
125
44
(1
3/4
”)
/8”)
7
4
(
/8”)
1
5
(
130
Surface Wall Mounted
Call Station Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
/2”)
1
6
(
167
Flush Wall Mounted
Call Station Collar Dimensions
-8-
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Call Stations
Optional Call Station Features
Attendant Call Button
In situations where the lift must be attendant operated, the call station can be modified and re-wired by
your Garaventa representative to include an attendant call button. This optional call station
configuration has only one directional control, which will always call the platform to your landing.
Keyless Call Stations
Keyless call stations are available as an option. A keyless lift does not have a keyswitch on the call
stations or the platform. The directional buttons on the platform will override the directional buttons of
the call stations.
Shaftway Frame Mounted
Call Stations: Fire Rated
Doors
Call / Send
Buttons
“In Use Lamp”
When a fire rated door is used the call stations are
usually mounted in the steel frame of the door, similar to
the Garaventa style door call stations.
Note: See page 17 for Three-Stop unit intermediate call
station information.
Key Switch
Door Interlock
Emergency
Access
Shaftway Frame
Mounted Call Station for Fire Door
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
-9-
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Drive System
Lifting Heights and Mast Sizes
The mast size required for a particular site is determined by the vertical travel required between the
upper and lower landings. When the site is measured, the lift height “H” is always defined as the
distance from the surface at the lower landing (pit or floor) where the lift will sit to the upper
landing floor as shown in the diagram below. If the lift is to be mounted directly on the surface of the
lower landing and an entry ramp is used, then “H” equals the elevation change between the upper and
lower landings. If the lift is pit mounted, then the measurement “H” is 76mm (3”) greater than the
elevation change between landings. This measurement is crucial for your custom designed lift. Be
certain the height you provide is accurate. We recommend using the “as built” dimension.
The width of the mast is 980mm (38 5/8”) and is standard for all mast heights.
Based on the measured value of “H” the drive mast is selected as follows;
Max. “H” Value
Enclosure Model
Shaftway Model
Mast Height
1118mm (44”)
GVL - EN - 41
GVL - SW - 41
1558mm (61 3/8”)
1524mm (60”)
GVL - EN - 57
GVL - SW - 57
1965mm (77 3/8”)
1905mm (75”)
GVL - EN - 72
GVL - SW - 72
2346mm (92 3/8”)
2515mm (99”)
GVL - EN - 96
GVL - SW - 96
3035mm (119 1/2”)
3124mm (123”)
GVL - EN - 120
GVL - SW - 120
3645mm (143 1/2”)
3734mm (147”)
GVL - EN - 144
GVL - SW - 144
4255mm (167 1/2”)
4343mm (171”)*
GVL - EN - 168*
GVL - SW - 168*
4920mm (193 3/4”)*
* Hydraulic drive only.
Upper Landing
H
H
Lower Landing
Pit Mount
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Floor Mount
- 10 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Drive System
Leadscrew Drive System
Hydraulic Drive System
Driven by a single-phase 3/4 H.P motor attached
to a 1” ACME screw, the Genesis shaftway
platform travels between landings at 2.7 meters
(9 ft.) per minute.
Driven by a 3 HP (2.2 KW), 24VDC hydraulic
motor, the Genesis enclosure platform travels
between landings at 5.2 meters (17 ft.) per
minute.
Mains Power Requirement:
Mains Power Requirement:
North America
North America
208 - 240 VAC 60 Hz single phase on a
dedicated 20 amp circuit.
120 VAC 60 Hz single phase on a dedicated 20
amp circuit.
International
220 - 240 VAC 50 Hz single phase on a
dedicated 20 amp circuit.
Mast Top Cover
Manual Lowering Tool
Mast Top Cover
Upper Landing Switch
and Final Limit Switch
Upper Landing Switch
and Final Limit Switch
Travel Carriage
Electric Control Box
1” ACME Screw
Hydraulic Cylinder
Travel Carriage
Mast Side Rails
Mast Side Rails
3.0 HP Motor
(2.2 KW)
Electric Control Box
Emergency Manual
Lowering Valve
3/4 HP Motor
Hydraulic Fluid
Resevoir
Battery Backup
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 11 -
© Garaventa
Printed in Canada
Special Features and Options
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Special Features and Options
Electrical Disconnect
A code compliant electrical disconnect is installed on the lift for
both safety reasons and customer convenience. This
disconnect shuts off the mains power and the 24V battery
back-up system to the lift. For the Enclosure Model, the
disconnect is located on the side of the mast closest to the
lower landing door. For the Shaftway Model, the disconnect is
located on the outside of the shaftway walls in a location
determined by local code requirements.
Manual Emergency Lowering Handwheel
(Lead Screw Model Only)
The manual emergency lowering handwheel has a black
plastic handle and slotted shaft that engages the main drive
screw. It should be stored in a safe place and is used to
manually move the platform to the desired landing in case of a
power outage.
The Genesis can be supplied with an optional battery-powered
emergency lowering system which is automatically activated in
the event of a power failure.
A secondary 24 VDC motor is connected to the main drive
system of the lift and allows the passenger inside the lift to
travel downwards only. The battery powered emergency
lowering system moves the platform at a speed of
approximately 0.3m/min. (1 ft/min.). The battery powered
emergency lowering system is controlled by the same push
buttons. The only difference in operation is that travel is only
permitted in the down direction.
Emergency Lowering
ADA Compliant Telephone
Some jurisdictions require that vertical platform lifts be
equipped with an ADA compliant hands-free telephone. This
speical phone is activated by the push of a button and
automatically dials pre-programmed numbers to summon
emergency assistance. It also provides audible and visible
feedback to the passenger that assistance is on the way. The
ADA telephone is integrated with the platform controls and is
flush mounted.
Note: This option will require the building owner to provide and
maintain an active telephone line to the Genesis mast
location.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 12 -
© Garaventa
Printed in Canada
Control Systems
Battery Powered Emergency Lowering
(Lead Screw Model Only - Optional)
Manual Emergency Lowering
Handwheel
Genesis Enclosure Model
www.garaventa.ca
Optional Features
Manual Emergency Lowering
(Hydraulic Model Only - Standard)
The manual emergency lowering device consists of a pull knob
mounted in a box on the side of the mast. When this device is
used, the platform is lowered to the desired landing.
For the Enclosure Model the manual emergency lowering
device is located on the side of the mast closest to the lower
landing door. For the Shaftway Model the manual emergency
lowering device is located on the outside of the shaftway in a
location determined by local code requirements.
Upon request, thumbscrews are available as replacement
items for the screws that secure the lid to the emergency
platform lowering box.
Manual Emergency Lowering Mounted
on Mast Rail
Garaventa PDO - Power Door Operator
The Garaventa Power Door Operator (PDO) automatically
opens the door/gate when the platform arrives at a landing.
When the lift is at the landing, the passenger can press the call
station button or gently pull on the door/gate to activate the
door opener. ADA compliant and obstruction sensitive, the
door/gate mounted operator uses low voltage (24VDC) and
has all wiring concealed within the lift. Certain applications
may limit the use of this operator. Consult your authorized
Garaventa representative for which power door operator is
appropriate for your application.
Garaventa Power Door Operator
DMT Power Door Operator
This ADA compliant option provides assistance for opening
and closing the door/gate and is used for fire rated doors and
other special applications. This wall mounted operator requires
110 VAC and is wired outside the lift. Consult your authorized
Garaventa representative for which power door operator is
appropraite for your application.
Auxiliary Power System
(Hydraulic Model Only - Standard)
The Auxiliary Power System automatically activated in the
event of a power failure. Two 12 VDC batteries allow the user
inside the lift to travel up or down using the platform at a speed
of approximately 5.2m/min (17ft/min). The number of trips
varies with the state of the battery charge.
DMT Power Door Operator
Pit Switch
For areas where local codes require a service pit switch, one
can be mounted within arm’s reach of the lower landing door.
The pit switch locks out the lift while a serviceman is working
under the platform.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 13 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Optional Features
Plexiglas Dome
(Enclosure Model Only)
Plexiglas Dome
For outdoor applications, a bronze tint
Plexiglas dome can be mounted onto your
enclosure. This dome comes standard with
a drip rail for rain and condensation.
Fan and
Ventilation
System
Fan and Ventilation System
(Enclosure Model with Dome Only)
The fan and ventilation system consists of
two exhaust fans, thermostatic control and
a 12 VDC battery backup. The dual fans
circulate and completely replace the air in
the enclosure every minute when the
inside enclosure temperature exceeds
85°F, in accordance with ASME A17.1 and
A18.1 code requirements.
Mast
Note: Some local codes require a fan and
ventilation system for an enclosure lift
fitted with Plexiglas panels and a dome.
Dome, Fan and Ventilation System
(also shown is the Remote Manual Emergency Lowering knob and
access box, available with the Hydraulic Drive)
Enclosure Walls
826mm (32 1/2”)
Lower Landing Entry
Ramp (1:10 slope)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Entry/Exit Ramp
Base
76mm (3”)
A ramp is an alternative when a 76mm (3”)
deep pit cannot be provided. Six ramps
are available for the Genesis, depending
on the available space at landings. The
ramps are available in slopes of 1:10 and
1:12. Both slopes are available in widths of
1069mm (42”), 1225mm (48 1/4") or
1375mm (54 1/8"), depending on the door
width.
974mm (38 3/8”)
Lower Landing Entry
Ramp (1:12 slope)
- 14 -
76mm (3”)
Lower Landing Ramp
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Optional Features
Infill Panel Kits
(Enclosure Model Only)
Custom infill panel kits are available to seal
off the dead space between the enclosure
and the wall, next to the mast. The panel kit
will enhance the overall appearance of the
Genesis. The panel kit includes a frame and
panels to fill the area.
Infill Panel
Infill Panel
Infill Panel Kit
Custom mast side wall panel kits are
available to fill the open area on either side of
the mast. The panel kit will enhance the
overall appearance of the Genesis and seal
off this dead space. The panel kit includes
the painted steel panels to fill the area
between the mast and the inside of the
shaftway wall.
Optional Features
Mast Side Wall Panel Kits
(Shaftway Model Only)
Mast Side
Wall
Panels
Mast
Mounting
Base
Mast Side Wall Panel Kit
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 15 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Optional Features
Bridges
Barrier
A custom bridge can be supplied for
situations where a stairway must be crossed
in order to use the lift. Please contact your
Garaventa representative for pricing of these
custom fabricated bridges and barrier options.
Bridge
Existing Stairs
Bridges
Mezzanine Tie-Back Brace
A mezzanine tie-back brace is required to
stabilize the Genesis for installations where there
is no wall behind the mast to provide support. The
mezzanine brace attaches the mast to a
structural member at the upper landing level.
Custom mezzanine brackets are available for
various wall configurations.
Y-Shaped
Tie Back
Brace
U-Shaped Tie
Back Brace
U-Shaped Tie Back Brace
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Y-Shaped Tie Back Brace
- 16 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Optional Features
Three-Stop Lift
The Genesis can be configured for three landings. The
lower and middle landings must have a full-height
2032mm (6’ 8”) door and the upper landing may have
either a full-height door or a gate.
Platform
Call Button
Key Switch
“In Use” Lamp
Frame Mounted Middle Call Station
Call Stations on Three-Stop Lifts
The middle landing call station consists of a call button
and a key switch. This enables the lift to be called to
the middle landing regardless of the platform’s location.
A plug is used to replace the upper button of the call
station. The upper and lower call stations are the same
as two-stop lifts.
Surface and Flush Wall Mounted Middle
Call Stations
Platform Controls on Three-Stop Lifts
A third button is added to the platform controls on
Three-Stop lifts. Similar to an elevator, the lift continues
past the middle landing when traveling from either the
lower to upper or upper to lower landings. All other
standard features are available with the controls as
referenced on page 6 (Platform Controls section).
Three-Stop Lift Platform Controls
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 17 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Enclosure Base and Pit Dimensions
Enclosure Base and Pit Dimensions
(For Leadscrew or Hydraulic Drive System)
Platform Size
Base Width
Base Length
Pit Width
Pit Length
36” x 54”
1420mm (55 7/8”)
1508mm (59 3/8”)
1445mm (56 7/8”)
1533mm (60 3/8”)
36” x 60”
1420mm (55 7/8”)
1660mm (65 3/8”)
1445mm (56 7/8”)
1685mm (66 3/8”)
42” x 60”
1572mm (61 7/8”)
1660mm (65 3/8”)
1597mm (62 7/8”)
1685mm (66 3/8”)
Base Length
Pit Length
Add 38mm (1 1/2”) to pit width if the mast spreader bar is used.
Base Width
Pit Width
13mm (0.5”)
Mast
Typical
Clearance
Pit Depth 76 mm (3”)
Enclosure Base and Pit Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 18 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Enclosure Platform Clearance Dimensions
Enclosure Platform Clearances
Platform
Clear Width
Platform
Clear Length
Configuration
Platform
Size
Straight Through
36 x 54
915 mm
(36")
1370 mm
(53 7/8")
1.25 sq. m.
(13.5 sq. ft.)
(180º) Entry/Exit
36 x 60
915 mm
(36")
1522 mm
(59 7/8")
1.39 sq. m.
(15.0 sq. ft.)
42 x 60
1068 mm
(42")
1522 mm
(59 7/8")
1.63 sq. m.
(17.5 sq. ft.)
36 x 54
1002 mm (39 1/2")
1278 mm
(50 3/8")
1.28 sq. m.
(13.8 sq. ft.)
36 x 60
1002 mm (39 1/2")
1431 mm
(56 3/8")
1.43 sq. m.
(15.4 sq. ft.)
42 x 60
1155 mm (45 1/2")
1431 mm
(56 3/8")
1.65 sq. m.
(17.8 sq. ft.)
90º Entry/Exit
Net Usable Area
360º On/Off Same Side
36 x 54
915 mm
(36")
1278 mm
(50 3/8")
1.17 sq. m.
(12.6 sq. ft.)
(entry/exit
36 x 60
915 mm
(36")
1431 mm
(56 3/8")
1.31 sq. m.
(14.1 sq. ft.)
adjacent to mast)
42 x 60
1068 mm
(42")
1431 mm
(56 3/8")
1.53 sq. m.
(16.4 sq. ft.)
360º On/Off Same Side
36 x 54
1002 mm (39 1/2")
1187 mm
(46 3/4")
1.19 sq. m.
(12.8 sq. ft.)
(entry/exit
36 x 60
1002 mm (39 1/2")
1339 mm
(52 3/4")
1.34 sq. m.
(14.5 sq. ft.)
opposite to mast)
42 x 60
1155 mm (45 1/2")
1339 mm
(52 3/4")
1.55 sq. m.
(16.6 sq. ft.)
Entry/Exit Configurations
The Genesis is available in various entry/exit
configurations. The lift can be supplied as a
straight through (180°), a 90° (left or right exit) or
an on/off same side (360°) lift configuration. The
standard configuration is straight through (180°)
with a 36” x 54” platform.
Clear Length
Entry/
Exit
Clear Width
Entry/
Exit
Straight Through (180°) Configuration
Clear Length
Clear Width
Clear Width
Clear Length
Entry/
Exit
Entry/
Exit
Entry/Exit
90° Configuration
On/Off Same Side (360°) Configuration
(available with left or right enter/exit)
(must have a lift height of 2253mm (88 3/4”) or greater)
(available with enter/exit on either side)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 19 -
© Garaventa
Printed in Canada
Shaftway/Pit and Platform Clear Dimensions
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Shaftway Dimensions
Shaftway/Pit and Platform Clear Dimensions,
Straight Through (180°) Entry/Exit
Platform
Size
Shaftway/Pit
Width
Shaftway/Pit
Length
Compact 1368mm (53 7/8”) 1295mm (51”)
Clear Width
914mm (36”)
Clear Length
Net Usable Area
1257mm (49 1/2”) 1.15sq.m. (12.4 sq. ft.)
Standard 1415mm (55 3/4”) 1409mm (55 3/8”) 962mm (37 7/8”) 1370mm (53 7/8”) 1.32sq.m. (14.2 sq. ft.)
Mid-Size 1415mm (55 3/4”) 1561mm (61 3/8”) 962mm (37 7/8”) 1522mm (59 7/8”) 1.47sq.m. (15.8 sq. ft.)
Large
1568mm (61 3/4”) 1561mm (61 3/8”) 1089mm (42 7/8”) 1522mm (59 7/8”) 1.66sq.m. (17.8 sq. ft.)
Add 38mm (1 1/2”) to pit width if a mast spreader is used.
Shaftway / Pit Width
Clear Width
76mm (3”)
Pit Depth
Entry / Exit
19mm
(3/4”)
63mm
(2 1/2”)
Clear Length
Mast
Shaftway / Pit Length
Entry / Exit
19mm
(3/4”)
351mm
(13 3/4”)
Straight Through (180°) Entry/Exit Shaftway/Pit and Platform Clear Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 20 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Dimensions
Shaftway/Pit and Platform Clear Dimensions,
90° Entry/Exit
Platform
Size
Shaftway/Pit
Width
Shaftway/Pit
Length
Clear Width
Compact 1325mm (52 1/8”) 1338mm (52 3/4”) 955mm (37 5/8”)
Clear Length
Net Usable Area
1216mm (47 7/8”) 1.16sq.m. (12.5 sq. ft.)
Standard 1372mm (54”)
1451mm (57 1/8”) 1002mm (39 1/2”) 1329mm (52 3/8”) 1.33sq.m. (14.3 sq. ft.)
Mid-Size 1372mm (54”)
Large
1525mm (60”)
1603mm (63 1/8”) 1002mm (39 1/2”) 1482mm (58 3/8”) 1.49sq.m. (16.0 sq. ft.)
1603mm (63 1/8”) 1129mm (44 1/2”) 1482mm (58 3/8”) 1.67sq.m. (18.0 sq. ft.)
Add 38mm (1 1/2”) to pit width if a mast spreader is used.
Shaftway / Pit Width
19mm
(3/4”)
Clear Length
76mm (3”)
Pit Depth
Entry / Exit
19mm
(3/4”)
Entry / Exit
Mast
Shaftway / Pit Length
Clear Width
63mm
(2 1/2”)
351mm
(13 3/4”)
90° Entry/Exit Shaftway/Pit and Platform Clear Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 21 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Shaftway Dimensions
Shaftway/Pit and Platform Clear Dimensions,
On/Off Same Side (360°) Entry/Exit Adjacent to Mast
Platform
Size
Shaftway/Pit
Width
Shaftway/Pit
Length
Clear Width
Clear Length
Net Usable Area
Compact 1368mm (53 7/8”) 1338mm (52 3/4") 914mm (36”)
Standard 1415mm (55 3/4”) 1451mm (57 1/8”) 962mm (37 7/8”)
1216mm (47 7/8”) 1.11sq.m. (12.0 sq.
1329mm (52 3/8”) 1.28sq.m. (13.7 sq.
Mid-Size 1415mm (55 3/4”) 1603mm (63 1/8”) 962mm (37 7/8”) 1482mm (58 3/8”) 1.42sq.m. (15.3 sq.
1568mm (61 3/4”) 1603mm (63 1/8”) 1114mm (43 7/8”) 1482mm (58 3/8”) 1.65sq.m. (17.8 sq.
Large
ft.)
ft.)
ft.)
ft.)
Add 38mm (1 1/2”) to pit width if a mast spreader is used.
Shaftway / Pit Width
Shaftway / Pit Length
76mm (3”)
Pit Depth
Entry / Exit
Clear Length
63mm
(2 1/2”)
19mm
(3/4”)
Mast
Clear Width
63mm
(2 1/2”)
351mm
(13 3/4”)
On/Off Same Side (360°) Entry/Exit Adjacent to Mast Shaftway/Pit and Platform Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 22 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Dimensions
Shaftway/Pit and Platform Clear Dimensions,
On/Off Same Side (360°) Entry/Exit Opposite Mast
Platform
Shaftway/Pit
Shaftway/Pit
Clear Width
Size
Width
Length
Compact 1325mm (52 1/8”) 1381mm (54 3/8”) 955mm (37 5/8”)
1494mm (58 7/8”) 1002mm (39 1/2”)
Standard 1372mm (54”)
1646mm (64 7/8”) 1002mm (39 1/2”)
Mid-Size 1372mm (54”)
1525mm
(60”)
1646mm (64 7/8”) 1155mm (45 1/2”)
Large
Add 38mm (1 1/2”) to pit width if a mast spreader is used.
Clear Length
Net Usable Area
1176mm (46 1/4”) 1.12sq.m. (12.1 sq.
1288mm (50 3/4”) 1.29sq.m. (13.9 sq.
1441mm (56 3/4”) 1.44sq.m. (15.5 sq.
1441mm (56 3/4”) 1.66sq.m. (17.9 sq.
ft.)
ft.)
ft.)
ft.)
Shaftway / Pit Width
Shaftway / Pit Length
76mm (3”)
Pit Depth
Clear Length
19mm
(3/4”)
Entry / Exit
63mm
(2 1/2”)
Mast
Clear Width
63mm
(2 1/2”)
351mm
(13 3/4”)
On / Off Same Side (360°) Entry/Exit Opposite Mast Shaftway/Pit and Platform Dimensions
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 23 -
© Garaventa
Printed in Canada
Doors and Interlocks
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Garaventa Style Door and
Gate Frames
The Enclosure and Shaftway models utilize the Garaventa
style door and gate. These doors and gates are prehung
in an anodized aluminum champagne colored extrusion
frame. The door and gate are constructed of matching
aluminum extrusions with a powder coated 16 gauge
galvanized steel kickplate and an upper panel (powder
coated 16 gauge galvanized steel, bronze tinted or clear
plexiglass or tempered glass). Custom finishes are also
available as an option, please refer to page 3. This nonfire rated door and gate are an attractive alternative to the
industrial looking fire rated door.
The door height is 2032mm (6’8") and the gate height is
1070mm (42 1/8") and are both available in 3 widths:
• 905mm (35 5/8”)
• 1046mm (41 1/8”)
• 1198mm (47 1/8”)
See the Layouts and Clearances section on pages 26-29
for further door/gate and door/gate swing dimensions.
Custom width doors and gates are also available.
Interlock
The Genesis interlock is a solenoid powered deadbolt with
a monitoring circuit. The monitoring circuit verifies that the
door is closed and that the deadbolt is engaged. Standard
battery backup ensures locks still operate in the event of a
power failure. If the deadbolt monitoring circuit is not
complete, the lift can not be moved. The Garaventa
interlock is CSA tested and approved.
Door Interlock
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 24 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Doors and Interlocks
Fire Rated Door
and Frames
The fire rated door and frame is completely prehung
and is constructed of 16 gauge steel. The rigid foam
filled door has a vision panel and a delayed action
door closer. The door has a 1 1/2 hour ‘B’ label fire
rating with an integrated interlock system. This door
frame comes standard with a 2-button keyed call
station.
The fire rated door and frame is available in both
906mm (35 5/8”) and 1059mm (41 5/8”) clear door
widths. See the Door Layouts and Clearances section
on pages 30-33 for further door and door swing
dimensions.
This door is primarily used with Shaftway Model
applications although can be used with the Enclosure
Model when the enclosure is positioned adjacent to a
fire-rated wall (consult Garaventa for further details).
Interlock
The fire rated door comes standard with a solenoid
powered deadbolt with a monitoring circuit. The
monitoring circuit verifies that the door is closed and
that the deadbolt is engaged. Standard battery
backup ensures locks still operate in the event of a
power failure. If the deadbolt monitoring circuit is not
complete, the lift can not be moved.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 25 -
© Garaventa
Printed in Canada
Garaventa Style Door Clearances
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Garaventa Style Doors,
Straight Through (180°) Entry/Exit
Door
Door Width
R/O* Width
R/O* Height
Door Swing
Door Projection
36”
905mm (35 5/8”)
1070mm (42 1/8”)
2120mm (83 1/2”)
926mm (36 1/2”)
982mm (38 5/8”)
42”
1046mm (41 1/8”)
1211mm (47 5/8”)
2120mm (83 1/2”)
1067mm (42”)
1123mm (44 1/4”)
48”
1198mm (47 1/8”)
1363mm (53 5/8”)
2120mm (83 1/2”)
1219mm (48”)
1275mm (50 1/8”)
R/O* is Rough Opening
Platform C
L Dimension
Compact
808mm (31 7/8”)
Standard
832mm (32 3/4”)
Mid-Size
832mm (32 3/4”)
Large
921mm (36 1/4”)
Door Rough Opening
Door
Swin
g
Door Projection
Platform Size
79mm (3 1/8”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Platform
CL Dim.
Door
Swin
g
Door Rough Opening
- 26 -
Door Projection
47mm (1 7/8”)
Jamb Depth
(typ.)
Mast
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Door Dimensions
Garaventa Style Doors,
90° Entry/Exit
Door
Door Width
R/O* Width
R/O* Height
Door Swing
Door Projection
36”
905mm (35 5/8”)
1070mm (42 1/8”)
2120mm (83 1/2”)
926mm (36 1/2”)
982mm (38 5/8”)
42”
1046mm (41 1/8”)
1211mm (47 5/8”)
2120mm (83 1/2”)
1067mm (42”)
1123mm (44 1/4”)
48”
1198mm (47 1/8”)
1363mm (53 5/8”)
2120mm (83 1/2”)
1219mm (48”)
1275mm (50 1/8”)
R/O* is Rough Opening
Platform Size Platform CL Dimension
Compact
829mm (32 5/8”)
Standard
852mm (33 1/2”)
Mid-Size
852mm (33 1/2”)
Large
941mm (37”)
Door Projection
79mm (3 1/8”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Door
Swin
g
Door Rough Opening
- 27 -
Door Rough Opening
Door
Swin
g
Platform
CL Dim.
Door Projection
47mm (1 7/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Shaftway Door Dimensions
Garaventa Style Doors,
On/Off Same Side (Entry/Exit Adjacent to Mast)
Door
Door Width
R/O* Width
R/O* Height
Door Swing
Door Projection
36”
905mm (35 5/8”)
1070mm (42 1/8”)
2120mm (83 1/2”)
926mm (36 1/2”)
982mm (38 5/8”)
42”
1046mm (41 1/8”)
1211mm (47 5/8”)
2120mm (83 1/2”)
1067mm (42”)
1123mm (44 1/4”)
48”
1198mm (47 1/8”)
1363mm (53 5/8”)
2120mm (83 1/2”)
1219mm (48”)
1275mm (50 1/8”)
R/O* is Rough Opening
Platform Size Platform C
L Dimension
Compact
808mm (31 7/8”)
Standard
832mm (32 3/4”)
Mid-Size
832mm (32 3/4”)
Large
908mm (35 3/4”)
79mm (3 1/8”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Platform
CL Dim.
Doo
r Sw
ing
Door Rough Opening
- 28 -
DoorProjection
47mm (1 7/8”) Jamb
Depth (typ.)
Mast
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Door Dimensions
Garaventa Style Doors,
On/Off Same Side (Entry/Exit Opposite to Mast)
Door
Door Width
R/O* Width
R/O* Height
Door Swing
Door Projection
36”
905mm (35 5/8”)
1070mm (42 1/8”)
2120mm (83 1/2”)
926mm (36 1/2”)
982mm (38 5/8”)
42”
1046mm (41 1/8”)
1211mm (47 5/8”)
2120mm (83 1/2”)
1067mm (42”)
1123mm (44 1/4”)
48”
1198mm (47 1/8”)
1363mm (53 5/8”)
2120mm (83 1/2”)
1219mm (48”)
1275mm (50 1/8”)
R/O* is Rough Opening
79mm (3 1/8”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Doo
r Sw
ing
Door Rough Opening
- 29 -
Door Projection
47mm (1 7/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Fire Rated Door Clearances
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Fire Rated Doors,
Straight Through Entry/Exit
Door
Door Width
R/O* Width
R/O* Height
Door Swing
1131mm (44 1/2”)
2102mm (82 3/4”)
976mm (38 3/8”)
1019mm (40 1/8”)
42” 1060mm (41 3/4”) 1283mm (50 1/2”)
2102mm (82 3/4”)
1128mm (44 3/8”)
1171mm (46 1/8”)
36” 908mm (35 3/4”)
Door Projection
R/O* Rough Opening
Compact
808mm (31 7/8”)
Standard
832mm (32 3/4”)
Mid-Size
832mm (32 3/4”)
Large
921mm (36 1/4”)
Door Rough Opening
Doo
r Sw
ing
Door Projection
Platform Size Platform C
L Dimension
109mm (4 1/4”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Platform
CL Dim.
Doo
r Sw
ing
Door Rough Opening
- 30 -
Door Projection
156mm (6 1/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Door Dimensions
Fire Rated Doors,
90° Entry/Exit
Door
Door Width
R/O* Width
R/O* Height
Door Swing
1131mm (44 1/2”)
2102mm (82 3/4”)
976mm (38 3/8”)
1019mm (40 1/8”)
42” 1060mm (41 3/4”) 1283mm (50 1/2”)
2102mm (82 3/4”)
1128mm (44 3/8”)
1171mm (46 1/8”)
36” 908mm (35 3/4”)
Door Projection
R/O* Rough Opening
Platform Size Platform C
L Dimension
Compact
829mm (32 5/8”)
Standard
852mm (33 1/2”)
Mid-Size
852mm (33 1/2”)
Large
941mm (37”)
Door Projection
109mm (4 1/4”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Doo
r Sw
ing
Door Rough Opening
- 31 -
Door Rough Opening
Doo
r Sw
ing
Platform
CL Dim.
Door Projection
156mm (6 1/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Shaftway Door Dimensions
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Fire Rated Doors,
On/Off Same Side (Entry/Exit Adjacent to Mast)
Door
Door Width
R/O* Width
R/O* Height
Door Swing
1131mm (44 1/2”)
2102mm (82 3/4”)
976mm (38 3/8”)
1019mm (40 1/8”)
42” 1060mm (41 3/4”) 1283mm (50 1/2”)
2102mm (82 3/4”)
1128mm (44 3/8”)
1171mm (46 1/8”)
36” 908mm (35 3/4”)
Door Projection
R/O* Rough Opening
Platform Size Platform CL Dimension
Compact
808mm (31 7/8”)
Standard
832mm (32 3/4”)
Mid-Size
832mm (32 3/4”)
Large
908mm (35 3/4”)
109mm (4 1/4”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Platform
CL Dim.
Doo
r Sw
ing
Door Rough Opening
- 32 -
Door Projection
156mm (6 1/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Door Dimensions
Fire Rated Doors,
On/Off Same Side (Entry/Exit Opposite to Mast)
Door
Door Width
R/O* Width
R/O* Height
Door Swing
1131mm (44 1/2”)
2102mm (82 3/4”)
976mm (38 3/8”)
1019mm (40 1/8”)
42” 1060mm (41 3/4”) 1283mm (50 1/2”)
2102mm (82 3/4”)
1128mm (44 3/8”)
1171mm (46 1/8”)
36” 908mm (35 3/4”)
Door Projection
R/O* Rough Opening
Doo
r Sw
ing
109mm (4 1/4”)
Side of Rough
Opening to
Hinge (typ.)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
Door Rough Opening
- 33 -
Door Projection
156mm (6 1/8”)
Jamb Depth (typ.)
Mast
© Garaventa
Printed in Canada
Attachment Methods
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Enclosure Model
Base and Mast Attachment Methods
The base of the enclosure frame is fastened to the floor with lag screws. The floor or pit should be
concrete and must be 3500 psi. reinforced, with a minimum 102 mm (4") thickness. If the floor is not
concrete then it must be able to withstand the loads shown on page 38.
After the base has been attached to the floor, the mast is bolted to the base. The mast of the lift is then
attached to a wall using the mast tie back bracket and optional tie back rail kit (if required).
It is mandatory for mast heights of 57”, 72”, 96”, 120”, 144” and 168” to be tied back to the wall. It is
strongly recommended that all mast heights be tied back to the wall. Where no attachment wall exists,
a mezzanine tie back brace is required (see page 16 for more details).
Tie Back Bracket
Tie Back Rail Kit (optional)
Mast may be fastened
directly to the wall
Mast to Base
Connection
Enclosure Base
Attachment Method
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 34 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Attachment Methods
Shaftway Model Base and Mast Attachment Methods
The base of the Genesis Shaftway Model is fastened to the floor with lag screws. The floor or pit should
be concrete and must be 3500 psi. reinforced, with a minimum 102 mm (4") thickness. If the floor is not
concrete then it must be able to withstand the loads shown on page 39.
After the base has been attached to the floor, the mast is bolted to the base. The mast of the lift must
be attached to a wall using a mast tie back bracket and if required the optional tie back rail kit.
Tie Back Rail Kit
(Optional) Mast may be
fastened directly to the
wall
Tie Back Bracket
Tie Back Bracket
Mast to Base
Connection
Mounting Base
Attachment Method
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 35 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Technical Reference
Lead Screw Drive System:
Technical Reference of Standard Features
Platform Sizes:
Standard Enclosure Platform: 914mm (36”) x 1370mm (54”)
Optional Enclosure Platform: 914mm (36”) x 1522mm (60”)
1068mm (42”) x 1522mm (60”)
Standard Shaftway Platform: 962mm (38”) x 1370mm (54”)
Optional Shaftway Platform:
914mm (36”) x 1257mm (49”)
962mm (38”) x 1522mm (60”)
1089mm (43”) x 1522mm (60”)
Rated Load:
340 kg (750 lbs), with a safety factor of 5
Sample Data Label for Lead Screw Drive Unit
Speed:
2.7 meters (9 ft) per minute at full load
Operating Controls:
Keyed Controls: Keyswitch on call stations and platform controls
Directional Controls: Continuous pressure switches
Control Voltage: 24 VDC
Drive System:
Motor: Lifting heights of 1829mm (72”) and under utilize a 3/4hp single phase AC Motor,
208-240V, 50/60Hz, 8 Amps Lifting heights of 2438mm (96”) and over utilize a 1hp single
phase AC Motor, 208-240V, 50/60Hz, 9 Amps
Drive Type:
ACME screw (1” diameter)
Power Supply:
208 to 240 VAC single phase 60 Hz
Safety Features:
Safety Nut: Safety nut automatically engages if drive nut fails. Platform falls less than
13mm (1/2”) when safety nut engages. Engaging safety nut trips the safety circuit.
Door Interlocks:
Solenoid powered deadbolt with monitoring circuit. Deadbolt fails in the locked position in
the event of power failure. Battery backup provided.
Emergency Stop:
Stops platform travel and sounds audible alarm.
Emergency Operation: Equipped with a manual lowering wrench. Optional battery powered lowering system
available.
Finish:
Enclosure Frame and Drive Mast: Anodized aluminum
Platform Sidewalls and Drive Mast Cover: Electrostatically applied baked powder finish on 16 gauge galvanized
steel panels – RAL color #7030 (Stone Grey). Enclosure Sidewalls and Doors: Standard electrostatically applied
baked powder finish on 16 gauge galvanized steel panels – RAL color #7030 (Stone Grey) or optional 3/16” thick
Plexiglas (Grey tint). Optional Finishes: Extrusions and panels can be painted any color in the RAL chart. Graphic
Imaging or Exotic Paint Finishes can be applied to the enclosure panels.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 36 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Technical Reference
Hydraulic Drive System:
Technical Reference of
Standard Features
Platform Sizes:
Standard Enclosure Platform: 914mm (36”) x 1370mm (54”)
Optional Enclosure Platform: 914mm (36”) x 1522mm (60”)
1068mm (42”) x 1522mm (60”)
Standard Shaftway Platform: 962mm (38”) x 1370mm (54”)
Optional Shaftway Platform:
914mm (36”) x 1257mm (49.5”)
962mm (38”) x 1522mm (60”)
1089mm (43”) x 1522mm (60”)
Sample Data Label for Hydraulic Drive Unit
Rated Load:
340 kg (750 lbs), with a safety factor of 5
Speed:
5.2 meters (17 ft) per minute at full load
Operating Controls:
Keyed Controls: Keyswitch on call station and platform controls
Directional Controls: Continuous pressure switches
Control Voltage: 24 VDC
Drive System:
Motor: 2.2 KW (3 HP) Motor: 120 VAC single phase, 60 Hz. @ 15 Amps (Some international locations 220-240
VAC, 50/60 Hz., 8 Amps).
Drive Type: Chained Hydraulic (Dual 5/8” ANSI 50 chains)
Power Supply: 120VAC single phase, 50/60 Hz @ 12 Amp – standard for North America. 208 to 240 VAC single
phase 50/60 Hz @ 6 Amps – optional where required.
Safety Features:
Safety: Monitored slack chain device. Automatically engages if the drive chain fails. The platform falls less than
13mm (1/2”) when the slack chain safety device engages.
Door Interlocks: Solenoid powered deadbolt with monitoring circuit. Deadbolt fails in the locked position in the
event of power failure. Battery backup provided.
Emergency Stop: Stops platform travel and sounds audible alarm.
Emergency Operation: Equipped with auxiliary power system that operates lift in up and down direction. Also
equipped with manual lowering valve.
Finish:
Enclosure Frame and Drive Mast: Anodized aluminum
Platform Sidewalls and Drive Mast Cover: Electrostatically applied baked powder finish on 16 gauge galvanized
steel panels – RAL color #7030 (Stone Grey).
Enclosure Sidewalls and Doors: Standard electrostatically applied baked powder finish on 16 gauge galvanized
steel panels – RAL color #7030 (Stone Grey) or optional 3/16” thick Plexiglas (Grey tint).
Optional Finished: Extrusions and panels can be painted any color in the RAL chart. Graphic Imaging or Exotic
Paint Finishes can be applied to the enclosure panels.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 37 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Enclosure Model Loading Diagram
Enclosure Model Loading Diagram Wall and Floor Reactions
F2
(Mast Weight)
L1
F5
Tieback Height
F6
(Enclosure Weight)
F1 (1000 lbs.)
76.2mm (3.0”)
Size
L1
L2
36” x 54”
683mm (26.9”)
1171mm (46.11”)
36” x 60”
683mm (26.9”)
1171mm (46.11”)
42” x 60”
759mm (29.9”)
1324mm (52.11”)
F4
F3
L2
152.3mm (5.99”)
Mast Enclosure
Model Weight
Mast Height
139.88mm
(5.51”)
Tieback Height
F2
lbs
F3
lbs
F4
lbs
F5
lbs
F6
lbs
41”
400
1558mm (61.3”)
1456mm(57.3”)
175
1251
486
782
400
57”
450
1965mm (77.4”)
1863mm(73.3”)
215
1308
536
612
450
72”
500
2346mm (92.4”)
2244mm(88.3”)
260
1370
585
509
500
96”
625
3035mm (119.5”)
2933mm(115.5”)
375
1527
710
386
625
120”
700
3645mm (143.5”)
3543mm(139.5”)
450
1627
758
321
700
144”
800
4255mm (167.5”)
4153mm(163.5”)
525
1736
884
275
800
168”
900
4920mm (193.7”)
4818mm (189.7”)
600
1846
981
237
900
Reactions are based on a 144” mast and a 42” x 60” platform.
These are reaction forces generated by the lift. Adhere to building code, regulations and safety factors
for supporting structures. Consult a Structural Engineer or Architect in your jurisdiction. Wind loading
effects are not considered in these calculations.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 38 -
© Garaventa
Printed in Canada
Genesis Enclosure Model
www.garaventa.ca
Shaftway Model Loading Diagram
Shaftway Model Loading Diagram Wall and Floor Reactions
F2
(Mast Weight)
L1
Tieback Height
F5
F1 (1000 lbs.)
Size
76.2mm (3.0”)
L1
L2
Compact
683mm (26.9”)
1060mm (41.7”)
Standard
683mm (26.9”)
1060mm (41.7”)
Mid-Size
683mm (26.9”)
1060mm (41.7”)
Large
759mm (29.9”)
1060mm (41.7”)
F4
F3
L2
152.3mm (5.99”)
Mast
Model
Mast Height
Tieback Height
F2
lbs
F3
lbs
F4
lbs
F5
lbs
41”
1558mm (61.3”)
1456mm(57.3”)
175
1251
486
782
57”
1965mm (77.4”)
1863mm(73.3”)
215
1308
536
612
72”
2346mm (92.4”)
2244mm(88.3”)
260
1370
585
509
96”
3035mm (119.5”)
2933mm(115.5”)
375
1527
710
386
120”
3645mm (143.5”)
3543mm(139.5”)
450
1627
758
321
144”
4255mm (167.5”)
4153mm(163.5”)
525
1736
884
275
168”
4920mm (193.7”)
4818mm (189.7”)
600
1846
981
237
Reactions are based on a 144” mast and a 42” x 60” platform.
These are reaction forces generated by the lift. Adhere to building code, regulations and safety factors
for supporting structures. Consult a Structural Engineer or Architect in your jurisdiction. Wind loading
effects are not considered in these calculations.
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 39 -
© Garaventa
Printed in Canada
Design Hot Line: 1-800-663-6556 or 1+604-594-0422
Garaventa Vertical Lift
Vertical Wheelchair Platform Lift
Specification Template
Model: Genesis Enclosure and
Shaftway
Need Assistance Writing the Specification?
GSL Artira specifications will vary from one building site to another based on the stairway
configuration, building materials, user requirements and local codes. Your Local Authorized
Garaventa Dealer has the expertise to assist and develop an appropriate design
specification for your accessibility project.
Authorized Garaventa Dealers can be found Worldwide, call or email
Garaventa for the Dealership nearest you.
In addition, professional designers at Garaventa Accessibility are available to answer your
technical questions and to assist you with the design and specs.
Garaventa Accessibility
Phone: (604) 594-0422 Fax: (604) 594-9915
Toll Free: 1-800-663-6556
web Site: www.garaventa.ca
Email: productinfo@garaventa.ca
Other Garaventa Accessibility products include:
Stair-Lift GSL Artira - Inclined Platform Lift for straight and turning stairways
Stair-Lift Xpress II - Inclined Platform Lift for straight stairways
Genesis OPAL - Vertical Platform Lift for lifting heights up to 1448mm (57”)
Genesis Design and Planning Guide
Revised July, 2003
15808-B-DP
- 40 -
© Garaventa
Printed in Canada