Definitions: Ground-fault protection: Ground-fault protection is used in solidly grounded neutral distribution systems where ground faults may be limited by high impedances (arc presence, incorrect connection between frames and ground). High impedance current levels are not detected by either the overload protection devices or the short-circuit protection devices (pickup level too high). The purpose of ground-fault protection is to protect the electrical system from serious damage and risk of fire. Zone-selective interlocking (ZSI, also called zone restraint): Zone-selective interlocking is used to reduce the stress on electrical distribution equipment during fault conditions while maintaining coordination. ZSI limits fault stress on the power distribution system by reducing the time it takes to clear the fault, while maintaining system coordination between overcurrent protective devices. ZSI allows electronic trip devices to communicate with each other so that a short-circuit or ground fault will be isolated and cleared by the nearest upstream circuit breaker with no intentional time delay. Devices in all other areas of this system (including upstream) remain closed to maintain service to unaffected loads. Without ZSI, a coordinated system results in the circuit breaker closest to the fault clearing the fault, but with an intentional delay. With ZSI, the device closest to the fault will ignore its preset short-time and/or ground-fault delays and clears the fault with no intentional delay. Eliminating intentional delay, without sacrificing coordination, results in faster tripping times. This limits fault stress by reducing the amount of let-through energy the system is subjected to during an overcurrent. The reduction in let-through energy can be as much as 80%. Long Time Ampere Rating and Delay: This adjustable function simulates the effect of a bimetal in a thermal-magnetic circuit breaker. It reacts to overload conditions and determines how much current the circuit breaker will carry continuously. The nominal pickup point where a circuit breaker trip unit detects an overload is a predetermined amount (typically 1.1) times the selected ampere rating of the circuit breaker. After the circuit breaker has picked up, it will not trip until the delay determined by the long time delay adjustment has been achieved. Short-Time Pickup and Delay: The short-time function allows the circuit breaker to delay before tripping on high level overcurrents, resulting in maximum coordination. A high level selective override is placed into all (???) circuit breakers to instantaneously trip them in the event of an extremely high level short-circuit. On circuit breakers without the instantaneous pickup adjustment, this particular function is referred to as short-time withstand rating. I2 t IN: results in an inverse time delay characteristic that coordinates best with thermalmagnetic and electronic trip circuit breakers. I2 t OUT: results in a constant delay characteristic that coordinates best with thermalmagnetic and electronic trip circuit breakers. Instantaneous Pickup: The instantaneous pickup function simulates the magnetic characteristic of a thermal-magnetic circuit breaker. This function trips the circuit breaker with no intentional time delay. In circuit breakers with both short-time and instantaneous pickup, the instantaneous pickup will override the short-time pickup if the instantaneous pickup is set at the same or lower setting than the short-time pickup. Ground Fault Pickup and Delay: The ground fault function is divided into pickup and delay components. The pickup portion determines at what point the circuit breaker will begin detecting a ground fault. The delay adjustment determines how long the circuit breaker will delay tripping after a ground fault has been detected. Interrupting Rating: The highest current at rated voltage that a circuit breaker is intended to interrupt under standard test conditions. The interruption rating of a circuit breaker must be equal to or greater than the available short-circuit current at the point at which the circuit breaker is applied on the system Shorter definitions: Continuous Current Rating: The designated amperes (rms ac or dc) that a device or assembly will carry continuously in free air without tripping or exceeding temperature limits. Current Transformer (current sensor)(CT): An instrument transformer that converts actual system current to a lower value of current for metering or control. Ground-Fault: An unintentional current path, through ground, back to the source. Ground-Fault Delay: The length of time the circuit breaker trip unit will delay before initiating a trip signal to the circuit breaker after a ground fault has been detected. Ground-Fault Pickup: The level of ground-fault current at which the trip system begins timing. Instantaneous Pickup: The current level at which the circuit breaker will trip with no intentional time delay. Inverse Time: A qualifying term indicating that there is a purposely introduced delayed tripping in which the delay decreases as the magnitude of the current increases. I2 t IN: An inverse time delay characteristic. I2 t OUT: A constant time delay characteristic. Long-time Delay: The length of time the circuit breaker will carry a sustained overcurrent (greater than the long-time pickup value) before initiating a trip signal. Long-time Pickup: The current at which the long-time delay function is initiated. Overcurrent: Any current in excess of the rated continuous current of equipment or the ampacity of a conductor. Overload: A sustained low-level overcurrent. Rating Plug: A component that plugs into the electronic trip unit, establishing the maximum continuous current rating of the circuit breaker. Sensor Ampere Rating: The size of the current transformer for rated output. Short-Time Delay: The length of time the circuit breaker will carry a short-circuit current (greater than the short-time pickup value) before initiating a trip signal. Short-Time Pickup: The current at which the short-time delay function is initiated. Zone-Selective Interlocking (ZSI): A communication capability between electronic trip systems and ground-fault relays that permits a short circuit or ground fault to be isolated and cleared by the nearest upstream device with no intentional time delay. OR Zone Selective Interlocking establishes a higher level of circuit protection by enabling electronic trip circuit breakers and ground fault relays to communicate with each other. The communication between relays allows the system to locate the short circuit or ground fault and isolate it. It is then cleared by the nearest upstream device with no intentional time delay.