EasyPact CVS - Schneider Electric

advertisement
Low Voltage
EasyPact CVS
Moulded-case circuit breakers
from 100 to 800 A
Catalogue
2011
Do you strain to find a high
quality circuit breaker that
is simple, flexible, and safe?
Have tight project budgets
restricted you from choosing
the best technology products?
Do you need the reach,
support and accessibility
of a global leader, with the
value of a local supplier?
Buildings
2
Industry
Energy &
Infrastructure
Residential
Compact CVS has helped our customers with a value system
focused on
Safety , Simplicity & Reliability.
Schneider Electric has always believed in customer satisfaction
and ensures that we renovate our offers to meet the changing
needs of our customers.
Now Schneider Electric is happy to announce that
Compact CVS is now EasyPact CVS
More Safe , Simple & Reliable
A global environment friendly range from Schneider Electric.
3
EasyPact CVS
brings more functionalities, options and
features which make it more
4
Environmentally responsible
n EasyPact CVS is part of the Schneider Electric energy efficiency approach. Designed
for easy disassembly and recycling at end of life, EasyPact CVS complies with
environmental directives RoHS* and WEEE**, and with ISO 14001 standards, thanks to
non - polluting factories.
@
@
@
@
Schneider Electric fully takes into account environmental requirements, starting right
from the design phase of every product through to the end of its service life:
the materials used for EasyPact CVS are not potentially dangerous to the
environment
the production facilities are non-polluting in compliance with the ISO 14001 standard
the energy dissipated per pole is low, making energy losses insignificant
the materials are marked to facilitate sorting for recycling at the end of product
service life.
EasyPact CVS moulded case circuit
breakers and accessories can be
recycled and reused optimally.
* RoHS = Restriction of Hazardous Substances
** WEEE = Waste Electrical and Electronic Equipment
5
Gain peace of mind
and optimized cost
for every installation
6
EasyPact CVS
from 100 to 800A
Frame 1
CVS 100 CVS 160 CVS 250
Frame 2
CVS 400 CVS 630
Frame 3
CVS 800*
N 50KA
F 36KA
B 25KA
*35kA for EasyPact CVS 800A
Breaking performance at 415 V A.C
EasyPact CVS 100 - 800A Adjustable version
n Various breaking capacities level are available as per the need of electrical
distribution network 25/36/50kA.
n Available in 3P and 4P Variants.
n Entire range is Ics=100% Icu.
Safe
Reliable
Simple
7
EasyPact CVS is...Safe
Isolation
Class II front Face
n
EasyPact CVS circuit breakers are
suitable for Isolation* as defined in IEC
standards 60947-2 .The aim of isolation
is to separate a circuit or apparatus
from the remainder of a system which is
energized in order the personnel may
carry out work on the isolated part with
complete safety.
n MCCB locking with external pad locks*
enables user to isolate and undertake
maintenance with utmost safety.
n
All EasyPact CVS* MCCBs are class II Front face devices, they
may be installed through the door of class II switchboards
without downgrading the switchboard insulation. Installation
requires no special operation, even when the Circuit Breaker is
equipped with a rotary handle.
Class II front face
Class II panel with circuit breaker
having a class II front face
Isolation
Locking in OFF position
n Key locks enables to lock* the breaker in
OFF position ensuring safety and better
control on installation.
n It also helps in interlocking multiple
circuit breakers in an installation.
* 100 to 630 A
8
Class II enclosure
EasyPact CVS is...Reliable
IEC 60947-2
Conforms to IEC 60947-2 for
circuit breaker
Fault current limitation
technology
nTested at renown international
laboratories like KEMA
nComplete range with Ics = 100% Icu
n EasyPact CVS Double break*
mechanism ensures high fault current
limitation
@ Reduces thermal stresses on the
electrical
distribution network
@ Increases the life of cables and
installation
High electrical & Mechanical
endurance
n 30000 mechanical operations for 100A
n 12000 electrical operations for 100A
Reliable accessories
n Continuous rated shunt coils
n Multifunctional Aux./Alarm contact
n Unique electrical fault trip indication (SDE)
Current limitation technology
EasyPact CVS offer protection
for human as well as Electrical
installation
nEarth leakage protection through Vigi
Module to protect human against leakage
current
nEarth Fault protection (UMGFP) to protect
Electrical distribution network against fire
* 100 to 630 A
EasyPact Double break Roto mechanism
9
EasyPact CVS is...Simple
Only three frame sizes
Frame - I
Frame – II
Frame – III
100 - 250 A
400 - 630A
800A
Spreaders
Terminal Shields
Line load reversibility for
entire EasyPact CVS range
System upgradeability
n Compact NSX/EasyPact CVS upto 630A
have the same foot print & mounting
dimensions, helps easy retrofitting and
system upgradeability.
Electrical auxiliaries
* Auxiliaries and accessories are common for MCCBs upto 630A.
Compact NSX
CVS Stands for
Compact Value System
Insulation Monitoring
EasyPact CVS
Rotary Operating handles
EasyPact CVS/Compact CVS and
Compact NS/NSX MCCBs share the
same value system.
Schneider Electric has a rich
experience in MCCBs with more
than 25 million circuit breakers
installed base world wide (more
than 100 countries).
10
Control accessories
Earth fault protection (UMGFP)
EasyPact CVS stands for customer value
EasyPact CVS 100 to 630 A
Panel builders
nOnly two frame sizes up to 630A
nCommon accessories for complete range (ON/OFF/Trip
Auxiliaries/Shunt/UV etc)
nLine load reversibility for entire range
nSuitable for class II switchboards
End Users
nIsolation as a standard feature enhances safety
n Excellent current limiting capability reduces stresses on
cables, busbars and loads
n Continuous rated accessories increase system reliability
n Moduler earth leakage and earth fault protection ensure
human/installation protection
OEMs
n High endurance’s and maintenance free operation assure
continuous performance of machines
n Unique common accessories help standardisation of
components
Contractors
n Sufficient pole pitch helps to terminate Copper and Aluminum
busbars or cables
n Easy availability of the product due to less number of frame
size
n Designed to perform in demanding applications
11
The easy choice for
quality and value
EasyPact CVS
LV circuit breakers from 100 to 800A
EasyPact CVS
12
EasyPact CVS
General contents
Functions
and characteristics
A-1
Installation
recommendations
B-1
Dimensions
and connection
C-1
Additional characteristics
D-1
Catalogue numbers
E-1
13
Functions and characteristics
EasyPact CVS
Functions and characteristics
Introduction
General characteristics
Protection of distribution systems
TM-D thermal-magnetic trip units
ETS 2.3 Microprocessor trip unit and accessories
Earth-leakage protection
Add-on protection againes insulation faults using a Vigi module
Ground fault protection
EasyPact CVS
Motor protection
MA instantaneous trip units
Introduction
Characteristics and performance
Functions & Characteristics
Protection of distribution systems for EasyPact CVS 800
Accessories and auxiliaries
A-2
A-3
A-4
A-5
A-6
A-7
A-8
A-10
Overview
Device installation
Connection of devices
Selection of auxiliaries
Indication contacts
Remote tripping
Rotary handles
Locks and sealing accessories
A-11
A-12
A-13
A-14
A-15
A-16
A-17
A-18
Installation recommendations
Dimensions and connection
Additional characteristics
Catalogue numbers
B-1
C-1
D-1
E-1
A-1
Introduction
Functions
and characteristics
General characteristics
100 to 630A
DB400000
1
2
7
8
3
4
5
6
cat.A
9
Standardised characteristics indicated on the rating plate:
1 Type of device: frame size and breaking capacity class
2 Ui: rated insulation voltage.
3 Uimp: rated impulse withstand voltage.
4 Ics: service breaking capacity.
5 Icu: ultimate breaking capacity for various values of the
rated operational voltage Ue
6 Ue: operational voltage.
7 Colour label indicating the breaking capacity class.
8 Suitable for Isolation symbol.
9 Reference standard.
Note: when the circuit breaker is equipped with an extended
rotary handle, the door must be opened to access the rating
plate.
Frame 1
CVS 100 CVS 160 CVS 250
Frame 2
CVS 400 CVS 630
Frame 3
CVS 800*
N 50KA
F 36KA
B 25KA
Breaking performance at 415 V A.C
Compliance with standards
EasyPact CVS circuit breakers and auxiliaries comply with the following international
recommendations:
b IEC 60947-1: general rules
b IEC 60947-2: circuit breakers
b IEC 60947-3: switch-disconnectors
Pollution degree
EasyPact CVS circuit breakers are certified for operation in pollution-degree III
environments as defined by IEC standards 60947-1 and 60664-1 (industrial
environments).
Climatic withstand
EasyPact CVS circuit breakers have successfully passed the tests defined by the
following standards for extreme atmospheric conditions:
b IEC 60068-2-1: dry cold (-55°C)
b IEC 60068-2-2: dry heat (+85°C)
b IEC 60068-2-30: damp heat (95 % relative humidity at 55°C)
b IEC 60068-2-52 severity level 2: salt mist.
Environment
EasyPact CVS respects the European environment directive EC/2002/95 concerning
the restriction of hazardous substances (RoHS).
All EasyPact CVS production sites have set up an ISO 14001 certified environmental
management system.
Ambient temperature
EasyPact CVS circuit breakers can be used between -25°C and +70°C. For
temperatures higher than 40°C (65°C for circuit breakers used to protect motor
feeders), devices must be derated (see page B-2).
b Circuit breakers should be put into service under normal ambient, operatingtemperature conditions. Exceptionally, the circuit breaker can be put into service
when the ambient temperature is between -35°C and -25°C.
b The permissible storage-temperature range for EasyPact CVS circuit breakers in
the original packing is -50°C and +85°C.
*35kA for EasyPact CVS 800A
Suitable for isolation with positive contact indication
All EasyPact CVS circuit breakers are suitable for isolation as defined in IEC standard
60947-2:
b The isolation position corresponds to the O (OFF) position.
b The operating handle cannot indicate the OFF position unless the contacts are
effectively open.
b Padlocks cannot be installed unless the contacts are open.
Installation of a rotary handle does not alter the reliability of the position-indication
system.
The isolation function is certified by tests guaranteeing:
b The mechanical reliability of the position-indication system
b The absence of leakage currents
b Over voltage withstand capacity between upstream and downstream connections.
The tripped position does not ensure isolation with positive contact indication.
Only the OFF position guarantees isolation.
IEC 60947-2
Installation in class II switchboards
All EasyPact CVS circuit breakers are class II front face devices. They can be installed
through the door of class II switchboards (as per IEC standards 61140 and 60664-1)
without downgrading switchboard insulation. Installation requires no special
operations, even when the circuit breaker is equipped with a rotary handle.
Degree of protection
The following indications are in accordance with standards IEC 60529 (IP degree of
protection) and IEC 62262 (IK protection against external mechanical impacts).
Bare circuit breaker:
b with toggle: IP40, IK07 front face
b with extended rotary handle: IP 55, IK08
Circuit breaker installed in a switchboard:
b with toggle: IP40, IK07 front face
b with extended rotary handle: IP 55, IK08
A-2
Protection of distribution systems
TM-D thermal-magnetic trip units
TM-D thermal-magnetic trip units
DB400003
TM-D thermal-magnetic trip units can be used on
EasyPact CVS100-630 circuit breakers with
performance levels B/F/N.
Protection ...........................................................................................
TM-D trip units are used mainly in electrical distribution applications for
protection of cables supplied by transformers.
Thermal protection (Ir)
Thermal protection operates according to:
b Ir that can be adjusted in amps from 0.7 to 1 times the rating of the trip unit (16 A
to 250 A), corresponding to settings from 11 to 250 A for the range of trip units
b a non-adjustable time delay.
Magnetic protection (Im)
Short-circuit protection with a fixed or adjustable pick-up Im that initiates
instantaneous tripping if exceeded.
b TM-D: fixed pick-up, Im, for 16 to 250 A ratings and adjustable from 5 to 10 x In for
400 A ratings, 4 to 8 x In for 600 A rating.
Protection versions
b
v
b
v
v
Thermal-magnetic trip units
3-pole:
3P 3D: 3-pole frame (3P) with detection on all 3 poles (3D)
4-pole:
4P 3D: 4-pole frame (4P) with detection on 3 poles (3D).
4P 4D: 4-pole frame (4P) with detection on all 4 poles (same threshold for phases
and neutral).
TM16D to 250D
TM320D to 630D
Ratings (A)
In at 40 °C (1)
16
25
32
40
50
63
80 100
125
160
200
250
Circuit breaker
CVS100
b
b
b
b
b
b
b
b
-
-
-
-
CVS160
-
-
-
-
-
-
CVS250
-
-
-
-
-
-
-
b
b
b
-
-
-
-
-
b
b
b
320 400 500 630*
CVS400
b
b
-
-
CVS630
-
-
b
b
Magnetic protection
Pick-up (A)
Im
fixed
accuracy ± ±20 %
CVS100
190
adjustable
300 400 500 500 500 640 800
CVS160/250
800
1250 1250 2000 2500
CVS400
5 to 10 x In
CVS630
4 to 8 x In
Thermal protection
Pick-up (A)
Ir = In x ...
adjustable in amps from 0.7 to 1 x In
Unprotected neutral
4P 3D
no detection
Fully protected neutral
4P 4D
1 x Ir
tripping between
1.05 and 1.20 Ir
Neutral protection
(1) For temperatures greater than 40°C, the thermal protection characteristics are modified. See the temperature derating table on page B-2.
* 630 A @ 30°C
Note: All the trip units have a transparent lead-sealable cover that protects access to the adjustment dials.
A-3
Functions
and characteristics
Protection of distribution systems
ETS 2.3 electronic trip unit and accessories
100 to 630A
DB400166
ETS 2.3 electronic trip unit
Protection ...........................................................................................
The protection functions can be set using the adjustment dials.
Overload protection
Long-time protection with an adjustable threshold and fixed tripping delay:
b Ir base setting (6-position dial from 0.5 to 1)
Short-circuit protection
Short-time and instantaneous protection:
b short-time protection with an adjustable pick-up and fixed tripping delay
b instantaneous protection with fixed pick-up.
Protection of the fourth pole
On 4-pole circuit breakers, neutral protection is set using a three-position switch to
4P 3D (neutral unprotected), 4P 3D + N/2 (neutral protection at 0.5 In) or 4P 4D
(neutral protection at In).
Trip units
Ratings (A) of circuit breaker
Circuit breaker
ETS 2.3
In 20 to 70 °C
CVS400 F/N
CVS630 F/N
400
b
-
Ir = In x …
0.5...1
adj., 6 settings
fixed
90...180
5...7.5
3.2...5.0
Overload protection (Long time)
Current setting
Time delay (s)
(min.…max.)
at 1.5 x Ir
at 6 x Ir
at 7.2 Ir
Short-circuit protection (Short time)
Pick-up (A)
accuracy ± 15 %
Time delay (ms)
Isd = Ir x …
max. resettable time
max. break time
2... 10
adj, 8 settings
fixed
y 40
y 60
Ii = In x …
11
Short-circuit protection (instantaneous)
Pick-up (A)
Protection of the fourth pole
Neutral unprotected
Neutral protection at 0.5 In
Neutral protection at In
Thermal memory
630
b
4P 3D
4P3D + N/2
4P 4D
no protection
0.5 x Ir
1 x Ir
CVS400 F/N
CVS630 F/N
Yes
Yes
Test equipment for ETS electronic trip unit
Mini test kit
The mini test kit is a portable unit requiring no external power supply, used to check
operation of the electronic trip unit and circuit breaker tripping.
It connects to the test connector on the front of the circuit breaker.
Required power source: five 9 V alkaline batteries (not supplied).
Portable test kit
The portable test kit is used to check all aspects of the protection functions:
b long time protection
b short time protection
b instantaneous protection
b earth-fault protection.
Required power source: 110 or 220 V AC, 50/60 Hz.
Spare test plug and wiring kit
A spare test plug and wiring kit are available for this offer.
A-4
Earth-leakage protection
Add-on protection againes insulation faults using
a Vigi module
PB106449
A Vigi module can be added to any three or four-pole
CVS100 to 630 circuit breaker to form a Vigi CVS.
Circuit breaker with add-on Vigi module (Vigi CVS)
b For general characteristics of circuit breakers, see pages A-2 and A-3.
b Add-on Vigi modules: Earth-leakage protection is achieved by installing a Vigi
module (characteristics and selection criteria on next page) directly on the circuit
breaker terminals. It directly actuates the trip unit (magnetic, thermal-magnetic or
ETS).
Vigi CVS100 to 630 circuit breakers with earth-leakage protection
Addition of the Vigi module does not alter circuit-breaker characteristics:
b compliance with standards
b degree of protection, class II front-face insulation
b positive contact indication
b electrical characteristics
b trip-unit characteristics
b installation and connection modes
b indication, measurement and control auxiliaries
b installation and connection accessories.
PB103580-36
Vigi CVS100 to 630
Dimensions and weights
Vigi CVS100/160/250
Vigi CVS400/630
Dimensions
105 x 236 x 86
135 x 355 x 110
3-pole
W x H x D (mm)
4-pole
140 x 236 x 86
180 x 355 x 110
Weight (kg)
3-pole
2.5
8.8
4-pole
3.2
10.8
Vigi earth-leakage protection modules
Compliance with standards
b
b
b
b
IEC 60947-2, annex B.
Decree dated 14 November 1988 (for France).
IEC 60755, class A, immunity to DC components up to 6 mA
operation down to -25 °C as per VDE 664.
Vigi module selection
2
3
4
5
6
DB112147
1
Type
Vigi ME
Vigi MH
Number of poles
3, 4 (1)
3, 4 (1)
Vigi MB
3, 4 (1)
CVS100
b
b
-
CVS160
b
b
-
CVS250
-
b
-
CVS400
-
-
b
CVS630
-
-
b
adjustable
0.3 0.03 - 0.3 - 1 - 3 - 10
adjustable
0.3 - 1 - 3 - 10 - 30
adjustable
Protection characteristics
1
2
3
4
Sensitivity setting
Time-delay setting (for selective earth-leakage protection).
Lead-seal fixture for controlled access to settings.
Test button simulating an earth-fault for regular checks on
the tripping function
5 Reset button (reset required after earth-fault tripping).
6 Rating plate
Sensitivity
In (A)
fixed
Time delay
fixed
adjustable
Intentional delay (ms)
< 40
0 - 60 (2) - 150 (2) - 310 (2)
0 - 60 - 150 - 310
Max. break time (ms)
< 40
< 40 < 140 < 300 < 800
< 40 < 140 < 300 < 800
Rated voltage V AC
50/60 Hz
200...440
200... 440 - 440...550
200...440 - 440...550
(1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection.
(2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Operating safety
The Vigi module is a user safety device. It must be tested at regular intervals (every 6
months) via the test button.
A-5
Ground Fault Protection
Functions
and characteristics
EasyPact CVS
100 to 800A
EasyPact CVS Ground Fault Protection is meant for human safety and to prevent fires
due to low level f aults resulting from a deterioration of electrical insulation or high
resistive faults.
Ground Fault Protection should be installed in the following
installations
b
b
b
b
Building housing inflammable or explosive material
Line voltage to ground exceeds 150V AC
Electrical equipments like welding sets
Electrical equipments used in close Proximity of water/other liquids and metallic
object
b Cable protection when distance between source and load is high
Protect electrical distribution network against fire
Selection for Ground Fault Protection is based on following:
b
b
b
b
Current sensitivity required
Rated voltage, Rated current and frequency
Operation time
Detection device and protection device co-ordination
Unique Modular Ground Fault (UMGFP) system is suitable for
EasyPact CVS / Compact NSX MCCBs
n
n
n
n
n
n
Adjustable earth fault sensitivity selection 10 to 60%
Adjustable time delay lnst / 0.5 - 3 Sec.
System healthiness check through LED indication
Individual fault indication for OL, SC, EF when used with Compact NSX (Optional)
Individual fault indication for OL/SC, EF when used with EasyPact CVS (Optional)
Test facility to check healthiness of earth fault protection system without tripping
MCCB
n Suitable for 3P3W & 3P4W electrical distribution network
Ground Fault Protection relay setting details
Relay
GFP11
GFP12
GFP13
GFP14
Overload setting
Ir selection in RM
32, 40, 50, 63, 80, 100
125, 160, 200, 250
400, 630
800
Sensitivity selection Time delay selection
10 - 60% of In
10 - 60% of In
10 - 60% of In
10 - 60% of In
0.5 to 3 Sec. /Instantaneous
0.5 to 3 Sec. /Instantaneous
0.5 to 3 Sec. /Instantaneous
0.5 to 3 Sec. /Instantaneous
Short circuit setting
Overload and
short circuit
protection
E/F Sensitivity Selector
Switch
Current Selector Switch
Ground Fault
Protection
Test Push
Button
A-6
Unique
system
Healthy
indication
Earth Fault
Indication
Reset
Push
Button
CT
details
Sealing
Stud
Time Delay Selector
switch (2 step setting)
Motor protection
MA instantaneous trip units
MA magnetic
trip up
units
for EasyPact
CVS100-630A
Motor
protection
to 250
kW
DB400006
E26988
Motor protection rating (kW)
CVS 100/160/250
CVS 400/630
Breaking
capacity (kA rms)
380/415V
1.1...110
18.5...250
B
F
N
25
36
-
25
36
-
36
50
Circuit breakers with an MA trip unit are combined with a thermal relay and a contactor
or a starter.
Protection
……………………………………………………………………
Magnetic protection (Im)
Short-circuit protection with an adjustable pick-up Im that initiates instantaneous
tripping if exceeded.
b Im = In x ... is set on an adjustment dial in multiples of the rating:
v 6 to 14 x In (2.5 to 100 A ratings)
v 9 to 14 x In (150 to 220 A ratings)
v 6 to 13 x In (320 to 500 A ratings)
Protection version
CVS100 to 630 circuit breakers, equipped with
an MA magnetic trip unit with adjustable thresholds,
offer:
- short-circuit protection
- suitability for isolation.
CVS100 to 630 circuit breakers with trip unit are
supplied ready-assembled.
b 3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D).
Motor protection up to 250 kW
Motor protection rating (kW)
CVS 100/160/250
CVS 400/630
380/415V N
1.1...110
18.5...250
-
N
-
50
MA trip units
Ratings (A)
In at 65 °C
CVS100
Circuit breaker
2.5
6.3
12.5
25
50
100
150
220
320
500
b
b
b
b
b
b
-
-
-
-
CVS160
-
-
-
-
-
b
b
-
-
-
CVS250
-
-
-
-
-
-
b
b
-
-
CVS400
-
-
-
-
-
-
-
-
b
-
CVS630
-
-
-
-
-
-
-
-
-
b
Short-circuit protection (magnetic)
Pick-up (A)
CVS100
CVS160/250
CVS400/630
Im = In x ...
setting
6...14 x ln
-
setting
9...14 x ln
-
setting
6...13 x ln
A-7
Functions
and characteristics
Introduction
Characteristics and performance
100 to 630A
PB106447
Common characteristics
Rated voltages
Insulation voltage (V)
Impulse withstand voltage (kV)
Operational voltage (V)
Suitability for isolation
Utilisation category
Pollution degree
Ui
Uimp
Ue
690
8
415
yes
A
3
AC 50/60 Hz
IEC/EN 60947-2
IEC 60664-1
Circuit breakers
Performance
Electrical characteristics as per IEC 60947-2
Rated current (A)
In
40 °C
lcu
AC 50/60 Hz 220/240 V
380/415 V
lcs
AC 50/60 Hz 220/240 V
380/415 V
Mechanical
Electrical
415V
Number of poles
Breaking capacity levels
EasyPact CVS100/160/250
Breaking capacity (kA rms)
PB106448
Service breaking capacity (kA rms)
Durability (C-O cycles)
In/2
In
Protection
Short-circuit protection
Overload/short-circuit protection
Earth fault protection
Earth-leakage protection
Magnetic only
Thermal magnetic electronic
Micro processor
with neutral protection (Off-0.5-1)
By UMGFP
By Vigi module
Installation/connections
Dimensions and weights
EasyPact CVS400/630
Dimensions (mm)
WxHxD
Fixed, front connections
Weight (kg)
Fixed, front connections
Connections
Connection terminals
Pitch
Without/With spreaders
Large Cu or Al cables
Cross-section
mm2
* 630 A @ 30°C
A-8
3P
4P
3P
4P
CVS100
CVS160
CVS250
CVS400
CVS630
100
160
250
400
630
3, 4
B
F
3, 4
B
F
3, 4
B
F
3, 4
F
N
3, 4
F
N
40
25
40
25
40
25
40
36
40
36
70
36
70
36
70
36
70
50
70
50
40 70
25 36
30000
30000
12000
40 70
25 36
25000
25000
12000
40 70
25 36
20000
20000
10000
40 70
36 50
15000
12000
6000
40 70
36 50
15000
8000
4000
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b*
b
b
b
b
105 x 161 x 86
140 x 161 x 86
2.05
2.4
105 x 161 x 86
140 x 161 x 86
2.2
2.6
105 x 161 x 86
140 x 161 x 86
2.4
2.8
140 x 255 x 110
185 x 255 x 110
6.05
7.90
140 x 255 x 110
185 x 255 x 110
6.2
8.13
35/45 mm
35/45 mm
35/45 mm
300
300
300
45/52.5 mm
45/70 mm
4 x 240
45/52.5 mm
45/70 mm
4 x 240
A-9
Functions & Characteristics
Functions
and characteristics
Protection of distribution systems
for EasyPact CVS 800
800A
EasyPact CVS 800A MCCBs are available in 3P/4P version with 35/50kA
breaking performances with Ics = 100% Icu. EasyPact CVS comes with host of
features including adjustable overload, short circuit setting, line load reversibility.
b Ics=100% Icu.
b Adjustable over load setting (0.8 to 1 x In)
b Adjustable short circuit setting for individual phase (3.5 to 10 In)
b Line load reversibility
CVS 800
Overload protection (thermal)
Tripping threshold (A) In
Adjustable 0.8...1 x In
Short-circuit protection (magnetic)
Tripping threshold (A) Im
EasyPact CVS 800
Adjustable
3.5...10 In
Accessories and Auxiliaries
b
b
b
b
b
b
Auxiliary contact with 1C/O & 2 C/O options.
Alarm contact with 1C/O & 2 C/O options.
Shunt trip coil.
Under voltage coil.
Direct and Extended Rotary Handle.
Unique modular ground fault protection for 3 phase 3 wire and 3 phase 4 wire
systems.
Function and characteristics
Protection of distribution system EasyPact CVS 800 A
EasyPact CVS Circuit breakers
Number of Poles
Control/manual/toggle
CVS 800
3/4
b
b
Direct or extended rotary handle
Electrical characteristics as per IEC 60947- 2
Rated current(A)
Rated insulation voltage(V)
Impulse withstand voltage(kV)
Rated operational voltage(V)
In
Ui
Uimp
Ue
40°C
AC 50/60 Hz
Icu
Ics
AC 415V 50/60HZ
%Icu
mechanical
electrical
In
Type of circuit Breaker
Ultimate Breaking Capacity(kA)
Service Breaking Capacity (KA)
Utilisation category
Durability (C-O cycles)
F
Protection
N
50
35
100%
A
8000
2500
Thermal Magnetic
Overload release setting (A)
Adjustable Ir(In x ...)
Short Circuit Protection
Short Circuit Release setting
Earth Fault Protection*
800
690
8
415
Isd (Ir x...)
By UMGFP
GFP Release setting = 10-60% of In
b
Centralised 0.8…..1
b
3.5 to 10
(independent adjustment of each phase)
b
b
b
Time Delay Setting (0.5 - 3 Sec./Inst.)
Additional indication & control auxiliaries
Indication Contacts
Alarm Contacts
1 C/O
2 C/O
1 C/O
2 C/O
1 C/O each
Auxiliary Contacts
Alarm - Auxiliary Contacts
MX shunt and MN under voltage Release
b
b
b
b
b
b
b
Installation and Connection
Bus Bar Max.
Cable Crimped lugs AL/CU (mm)2
width (mm)
40
300*2
Installation Accessories
b
b
Spreaders
Phase Barriers
Dimensions & Weight
Overall dimensions
WXHXD
Weight(kg)
A-10
(mm)
(mm)
3 /4Pole
3Pole
4Pole
210 x 274 x 103
280 x 274 x 103
10.3/13.7
Accessories and auxiliaries
Overview
CVS 100 to 630
Insulation accessories
DB400001
Connection
Cable connectors
Interphase barriers
Sealable terminal
shields
Rear connectors
Terminal
extensions
Cable connectors
Electrical auxiliaries
Indication contact
Voltage release
Insulation Monitoring
cat.A
Control accessories
Earth leakage protection
(VigiCVS)
Direct rotary handle
Extended rotary handle
Earth fault protection (UMGFP)
A-11
Accessories and auxiliaries
Functions
and characteristics
Device installation
100 to 630A
Fixed circuit breakers
DB400010
DB400012
Mounting on a backplate.
Mounting on a Prisma mounting plate.
DB400011
Fixed circuit breakers are designed for standard connection using bars or cables with
lugs. Bare-cable connectors are available for connection to bare copper or aluminium
cables.
DB400009
CVS circuit breakers may be installed horizontally,
vertically or flat on their back, without derating
performance levels.
Mounting on rails.
Mounting on DIN rail (with
adaptor).
Front connection
DB112169
DB400013
Fixed circuit breakers are designed for standard front
connection using bars or cables with lugs.
Cable connectors are available for bare cables. Rear
connection is also possible.
Bars or cables with lugs
Standard terminals
EasyPact CVS100 to 630 come with terminals comprising snap-in nuts with screws:
b EasyPact CVS100: M6 nuts and screws.
b EasyPact CVS160/250: M8 nuts and screws
b EasyPact CVS400/630: M10 nuts and screws.
These terminals may be used for:
b direct connection of insulated bars or cables with lugs
b terminal extensions.
Interphase barriers or terminal shields are recommended. They are mandatory for
certain connection accessories (in which case the interphase barriers are provided).
Bars
When the switchboard configuration has not been tested, insulated bars are
mandatory.
Insulated bar.
DB112170
Maximum size of bars
Small lug for copper cables.
EasyPact CVS circuit breaker
Without spreaders
pitch (mm)
maximum bar size (mm)
With spreaders
pitch (mm)
maximum bar size (mm)
100/160/250
35
20 x 2
45
32 x 2
400/630
45
32 x 6
52.5
40 x 6
Crimp lugs
DB112171
There are two modules of lugs, for aluminium and copper cables.
Interphase barriers or long terminal shields must be used with narrow lugs. The lugs
are supplied with interphase barriers.
Straight terminal
extensions.
Right-angle
terminal extensions
EasyPact CVS circuit breaker
Copper cables
size (mm2)
crimping
Aluminium cables
size (mm2)
crimping
100/160/250
400/630
150, 185
240, 300
hexagonal barrels or punching
150, 185
240, 300
hexagonal barrels
Terminal extensions
DB112177
DB112173
DB112172
Small lug for Al cables.
Spreaders.
Extensions with anti-rotation ribs can be attached to the standard terminals to
provide numerous connection possibilities in little space:
b straight terminal extensions
b right-angle terminal extensions
Spreaders
Spreaders may be used to increase the pitch:
b CVS100 to 250: the 35 mm pitch can be increased to 45 mm
b CVS400/630: the 45 mm pitch can be increased to 52 or 70 mm.
Bars, cable lugs or cable connectors can be attached to the ends.
Pitch (mm) depending on the type of spreader
EasyPact CVS circuit breaker
Without spreaders
With spreaders
A-12
CVS100 to 250
35
45
CVS100 to 630
45
52.5 or 70
Accessories and auxiliaries
Bare cables
DB112314
DB400014
Connection of devices
Bare-cable connectors may be used for both copper and aluminium cables.
1-cable connectors for EasyPact CVS100 to 250
The connectors snap directly on to the device terminals or are secured by clips to
right-angle and straight terminal extensions as well as spreaders.
1-cable connectors for EasyPact CVS400 to 630
The connectors are screwed directly to the device terminals.
Bare cable.
2-cable connectors for EasyPact CVS100 to 250 and 400/630
The connectors are screwed to device terminals or right-angle terminal extensions.
Four positions.
EasyPact CVS circuit breaker
100/160
Steel connectors
1.5 to 95 mm2
b
Aluminium connectors 25 to 95 mm2
DB111326
2-cable
connector for
CVS400/630. CVS100 to 250
DB111330
DB400015
1-cable
connector for
CVS100 to 250
DB112317
DB112315
DB112316
Maximum size of cables depending on the type of connector
250
400
630
2 cables 35 to 240 mm2
b
b
35 to 300 mm2
b
b
b
b
120 to 185 mm2
b
b
2 cables 50 to 120 mm2
b
b
CVS400/630.
Two lengths.
Rear connection
Device mounting on a backplate with suitable holes enables rear connection.
Bars or cables with lugs
Rear connections for bars or cables with lugs are available in two lengths. Bars may be
positioned flat, on edge or at 45° angles depending on how the rear connections are
positioned.
The rear connections are simply fitted to the device connection terminals. All
combinations of rear connection lengths and positions are possible on a given device.
Escutcheon for toggle without and with access to the trip unit.
IP40 escutcheons for fixed devices
There are three types of escutcheon with a gasket which are screwed to the door
cut-out:
b three escutcheons for all control types (toggle, handle or motor mechanism)
b a wide model for Vigi modules that can be combined with the above.
DB400032
DB400031
DB400030
Escutcheons are an optional feature mounted on the
switchboard door. They increase the degree of
protection to IP40, IK07. Protection collars maintain the
degree of protection, whatever the position of the
device (connected, disconnected).
Escutcheon for Vigi module.
A-13
Accessories and auxiliaries
Functions
and characteristics
Selection of auxiliaries
100 to 630A
DB115583
EasyPact CVS100/160/250
Standard
Rotary handle
OF1
SD
OF2
SDE
MN /
MX
SDV
All EasyPact CVS100/160/250 circuit breakers have slots for the electrical auxiliaries
listed below.
5 indication contacts (see page A-15)
b 2 ON/OFF (OF1 and OF2)
b 1 trip indication (SD)
b 1 fault-trip indication (SDE)
b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
1 remote-tripping release (see page A-16)
b either 1 MN undervoltage release
b or 1 MX shunt release.
All these auxiliaries can be installed with a rotary handle.
The illustration shown (TMD, MA standard) indicates auxiliary possibilities depending
on the type of trip unit.
DB115590
EasyPact CVS400/630
Standard
Rotary handle
OF1
OF2
OF3
Reserved
MN /
MX
SD
SDE
OF4
SDV
A-14
All EasyPact CVS400/630 circuit breakers have slots for the electrical auxiliaries
listed below.
6 indication contacts (see page A-15)
b 4 ON/OFF (OF4)
b 1 trip indication (SD)
b 1 fault-trip indication (SDE)
b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module.
1 remote-tripping release (see page A-16)
b either 1 MN undervoltage release
b or 1 MX shunt release.
All these auxiliaries can be installed with a rotary handle.
The illustration shown (TMD, MA and ETS 2.3 standard) indicates auxiliary possibilities
depending on the type of trip unit.
Accessories and auxiliaries
Indication contacts
One contact model provides circuit-breaker status
indications (OF - SD - SDE - SDV).
These common-point changeover contacts provide remote circuit-breaker status
information.
They can be used for indications, electrical locking, relaying, etc.
They comply with the IEC 60947-5 international recommendation.
DB125549
Functions
Indication contacts.
Breaker-status indications, during normal operation or after a fault
A single type of contact provides all the different indication functions:
b OF (ON/OFF) indicates the position of the circuit breaker contacts
b SD (trip indication) indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth fault (Vigi)
v operation of a voltage release
v operation of the “push to trip” button
v disconnection when the device is ON.
The SD contact returns to de-energised state when the circuit breaker is reset.
b SDE (fault-trip indication) indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v an earth fault (Vigi)
b SDV indicates that the circuit breaker has tripped due to an earth fault. It returns
de-energised state when the Vigi module is reset.
Installation
b OF, SD, SDE and SDV functions: a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts clip
into slots behind the front cover of the circuit breaker (or the Vigi module for the SDV
function).
The SDE function on a CVS100 - 630 A equipped with a magnetic, thermal-magnetic
or ETS2.3 trip unit requires the SDE adaptor.
Electrical characteristics of auxiliary contacts
Contacts
Standard
Types of contacts
All
Low level
OF, SD, SDE, SDV
Rated thermal current (A)
6
5
1 mA at 4 V DC
Minimum load
100 mA at 24 V DC
Utilisation cat. (IEC 60947-5-1)
AC12 AC15 DC12 DC14
AC12 AC15 DC12 DC14
Operational 24 V
current (A) 48 V
AC/DC
6
6
6
1
5
3
5
1
AC/DC
6
6
2.5
0.2
5
3
2.5
0.2
AC/DC
6
5
0.6
0.05
5
2.5
0.6
0.05
220/240 V AC
6
4
-
-
5
2
-
-
250 V
DC
-
-
0.3
0.03
5
-
0.3
0.03
380/440 V AC
6
2
-
-
5
1.5
-
-
110 V
A-15
Accessories and auxiliaries
Functions
and characteristics
Remote tripping
100 to 630A
DB125550
MN undervoltage release
b This release trips the circuit breaker when the control voltage drops below a
tripping threshold
b The tripping threshold is between 0.35 and 0.7 times the rated voltage
b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Characteristics
DB115605
MX or MN voltage release.
Failsafe opening
0
Possible opening
0.35
0.7
1.1 Un
DB115606
Opening conditions of the MN release.
Failsafe closing
0
0.85
1.1 Un
PB103752-32
DB115607
Closing conditions of the MN release.
Delayed
trip order
10
12
3
6
Time-delay
unit
Instantaneous
trip order
V AC
Operating threshold
V DC
Opening
Closing
Operating range
Consumption (VA or W)
Response time (ms)
50/60 Hz: 24 - 48 - 100/130 - 200/240
50 Hz: 380/415
60 Hz: 208/277
12 - 24 - 30 - 48 - 60 - 125 -250
0.35 to 0.7 Un
0.85 Un
0.85 to 1.1 Un
Pick-up: 10 - Hold: 5
50
Time-delay unit for an MN release
A time delay unit for the MN release eliminates the risk of nuisance tripping due to a
transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of
capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping.
The correspondence between MN releases and time-delay units is shown below.
Power supply
Unit with fixed delay 200 ms
48 V AC
220 / 240 V AC
Unit with adjustable delay y 200 ms
48 - 60 V AC/DC
100 - 130 V AC/DC
220 - 250 V AC/DC
Corresponding MN release
48 V DC
250 V DC
48 V DC
125 V DC
250 V DC
MX shunt release
The MX release opens the circuit breaker via an impulse-type (u 20 ms) or maintained
order.
Opening conditions
D2
When the MX release is supplied, it automatically opens the circuit breaker. Opening is
ensured for a voltage U u 0.7 x Un.
MN
Characteristics
D1
MN release with a time-delay
unit.
Power supply
Power supply
Wiring diagram for
emergency-off function with
MN + time-delay unit.
V AC
V DC
Operating range
Consumption (VA or W)
Response time (ms)
50/60 Hz: 24 - 48 - 100/130 - 200/240
50 Hz: 380/415
60 Hz: 208/277
12 - 24 - 30 - 48 - 60 - 125 -250
0.7 to 1.1 Un
Pick-up: 10
50
DB115608
Circuit breaker control by MN or MX
Possible opening
0
Failsafe opening
0.7
1.1
Un
Opening conditions of the MX release.
Note: circuit breaker opening using an MN or MX release must be
reserved for safety functions. This type of tripping increases
wear on the opening mechanism. Repeated use reduces the
mechanical endurance of the circuit breaker by 50 %.
A-16
When the circuit breaker has been tripped by an MN or MX release, it must be reset
before it can be reclosed.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary, is
not possible.
Connection using wires up to 1.5mm2 to integrated terminal blocks.
Accessories and auxiliaries
Rotary handles
PB106453
There are two types of rotary handle:
b direct rotary handle
b extended rotary handle.
Direct rotary handle
Standard handle
Degree of protection IP40, IK07.
The direct rotary handle maintains:
b
b
b
b
visibility of and access to trip-unit settings
suitability for isolation
indication of the three positions O (OFF), I (ON) and tripped
access to the "push to trip" button.
Device locking
The rotary handle facilitates circuit-breaker locking.
b Padlocking:
v standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to
8 mm, not supplied
EasyPact CVS with a rotary handle.
Extended rotary handle
PB106454
Degree of protection IP56, IK08.
The extended rotary handle makes it possible to operate circuit breakers installed at
the back of switchboards, from the switchboard front.
It maintains:
b visibility of and access to trip-unit settings
b suitability for isolation
b indication of the three positions O (OFF), I (ON) and tripped.
Device and door padlocking
PB106455
EasyPact CVS with an extended rotary handle installed at the
back of a switchboard, with the keylock option and key.
Padlocking locks the circuit-breaker handle and disables door opening:
b standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to
8 mm, not supplied
Parts of the extended rotary handles
b A unit that replaces the front cover of the circuit breaker (secured by screws).
b An assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally.
b An extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is:
v 185…600 mm for EasyPact CVS100 to 250
v 209…600 mm for EasyPact CVS 400/630.
Manual source-changeover systems
PB106456
An additional accessory interlocks two devices with rotary handles to create a sourcechangeover system. Closing of one device is possible only if the second is open.
This function is compatible with direct or extended rotary handles.
Up to three padlocks can be used to lock in the OFF or ON position.
A-17
Functions
and characteristics
Accessories and auxiliaries
Locks and sealing accessories
100 to 630A
DB400025
DB400026
Locks
Toggle locking using
padlocks and an accessory:
Removable device
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional
accessory.
Fixed device attached to the
case.
Control device
Function
Means Required accessories
Toggle
Lock in OFF position
Padlock
Lock in OFF or ON Padlock
position
Direct
handle
rotaryStandard Lock in
b OFF position
b OFF or ON position (1)
DB400027
Extended rotary handle
-
Keylock
Locking device + keylock
Padlock
Lock in
b OFF position
(1)
b OFF or ON position
with
door
opening
prevented (2)
-
Lock in OFF position
Padlock
UL508 control accessory
b OFF or ON position (1)
Keylock
Locking device + keylock
(1) Following a simple modification of the mechanism.
(2) Unless door locking has been voluntarily disabled.
DB400029
Sealing accessories
A-18
Rotary handle
DB400018
Access to Vigi-module
settings
DB400019
DB115033
Sealing accessories.
DB400017
DB400028
Rotary-handle locking using a keylock.
Toggle control
Fixed device
Padlock
inside the switchboard
Rotary-handle locking using a padlock or a keylock.
Removable device
Types of seals
Protection cover for settings
Protected operations
b modification of settings.
Installation
recommendations
EasyPact CVS
Installation recommendations
Contents
Functions and characteristics
A-1
Operating conditions and temperature derating
B-2
Installation in switchboards
Safety clearances and minimum distances
Installation example
B-3
B-4
Dimensions and connection
Additional characteristics
Catalogue numbers
C-1
D-1
E-1
B-1
Operating conditions and temprature
derating
Installation
recommendations
100 to 630A
When thermal-magnetic trip units are used at ambient
temperatures other than 40 °C, the Ir pick-up is
modified.
DB400035
(m)
2000
Altitude derating
Altitude does not significantly affect the characteristics of EasyPact CVS circuit
breakers up to 2000 m. Above this altitude, it is necessary to take into account the
decrease in the dielectric strength and cooling capacity of air.
Vibrations
CVS devices resist electromagnetic or mechanical vibrations.
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
b 2 to 13.2 Hz: amplitude ±1 mm
b 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Degree of protection
CVS circuit breakers have been tested for degree of protection (IP) and mechanical
impact protection (IK). See page A-2.
DB115053
Electronic trip units are not affected by variations in
temperature. If the trip units are used in hightemperature environments, the ETS setting must
nevertheless take into account the temperature limits
of the circuit breaker.
(A)
110
Settings of CVS100 to 630 equipped with TM-D trip units as a
function of the temperature
100
The table indicates the real Ir (A) value for a given rating and temperature.
90
Rat. Temperature (°C)
(A) 10
15
20
25
80
35
40
45
50
18.4
18
18
18
17
16.6
16
15.6
25
28.8
28
27.5
27
26.3
25.6
25
24.5 24
32
36.8
36
35.2
34.4
33.6
32.8
32
31.3 30.5
40
46
45
44
43
42
41
40
39
50
57.5
56
55
54
53
51
50
63
73
72
70
68
67
65
80
92
90
88
86
84
82
100 114
112
110
107
105
500
125 144
141
138
134
200
10
DB400102
30
16
20
30
40
50
60
70 (°C)
Temperature derating curve for CVS100.
DB400102
The overload protection is calibrated at 40 °C in the lab. This means that when the
ambient temperature is less than or greater than 40 °C, the Ir protection pick-up is
slightly modified.
To obtain the tripping time for a given temperature:
b see the tripping curves for 40 °C (see pages D-2 and D-3)
b determine tripping times corresponding to the Ir value (thermal setting on the
device), corrected for the ambient temperature as indicated in the tables below.
10 000
5 000
2 000
1 000
55
15.2 14.8
60
65
70
14.5 14
13.8
23.5
23
21
30
29.5 29
28.5
38
37
36
35
33.5
49
47
46
44
43
41
63
61
59
57
55
53
50
80
78
75.5 73
70.7
68
65
102.5 100
97
95
92.0
89
86
83
131
128
125
122
119
116
113
109 106
22
160 184
180
176
172
168
164
160
156
152
148
144
140 136
50
200 230
225
220
215
210
205
200
195
190
185
180
175 170
20
250 288
281
277
269
263
256
250
244
238
231
225
219 213
100
10
5
t(s)
2
TM80D/100D : Im = 8 x In
1
.5
.2
.1
.05
.02
.01
320 364.9 357.8 350.5 343.2 335.6 327.9 320
311.9 303.6 295
400 456.6 447.7 438.6 429.2 419.7 410
390
400
379.3 368.5 357.3 345.8 333.9
500 558.6 549.2 539.7 530.1 520.3 510.2 500
489.6 478.9 468
600 672
587.2 574
660.5 648.9 637
630
612.6 600
286.2 277.1 267.7
456.8 445.4 433.6
560.6 546.8 532.7 518.2
t < 10 ms
.005
.002
.001
.5 .7 1
CVS400 and 630 (equipped with ETS2.3 electronic trip unit)
2
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
values.
Thermal-protection curve with minimum and maximum
Note: For 800A please contact sales office
B-2
The table below indicates the maximum long-time (LT) protection setting Ir (A)
depending on the ambient temperature.
Type of
Rating (A) Temperature (°C)
device
40
45
50
55
60
65
70
CVS400
Fixed
CVS630
Fixed
400
400
400
400
390
380
370
360
630
630
615
600
585
570
550
535
Installation in switchboards
Safety clearances and minimum distances
General rules
When installing a circuit breaker, minimum distances (safety clearances) must
be maintained between the device and panels, bars and other protection devices
installed nearby. These distances, which depend on the ultimate breaking capacity,
are defined by tests carried out in accordance with standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
b use insulated bars for circuit-breaker connections
b segregate the busbars using insulating screens.
For CVS100 to 630 devices, terminal shields and interphase barriers are
recommended and may be mandatory depending on the operating voltage of the
device and type of installation (fixed, withdrawable, etc.).
Power connections
The table below indicates the rules to be respected for CVS100 to 630 devices to
ensure insulation of live parts for fixed devices.
CVS100 to 630: rules to be respected to ensure insulation of live parts
Fixed, rear
connection
DB400040
Fixed, front connection
DB400039
Type of connection
operating voltage
Long terminal
shields (1)
Short terminal
shields
DB115061
With:
y 440 V
Interphase
barriers
DB115060
No insulating
accessory
DB115059
Possible, recommended or mandatory accessories:
type of conductor
Insulated bars
Extension terminals
Cables + crimp lugs
Bare cables +
connectors
Possible
Possible
Possible
Recommended
No
Mandatory
(supplied)
Possible
(instead of ph. Recommended
barriers)
Possible for
CVS100 to
250
Possible for
CVS100 to
250
Possible for
CVS100 to
250
No
Mandatory
(supplied)
Possible
(instead of ph.
barriers)
Recommended
(1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical
impact).
B-3
Installation in switchboards
Installation
recommendations
Installation example
100 to 630A
Safety clearance
Minimum distance between circuit
breaker and front or rear panels
F
Front
panel
DB400047
DB400046
Minimum distance between two
adjacent circuit breakers
A1
B=0
F
Note: if F < 8 mm: an insulating screen or long
terminal shield is mandatory.
Bare or painted sheet metal
D1
D2
DB400050
DB400049
DB400048
Minimum distance between circuit breaker and top, bottom or side panels
D1
D1
D1
C1
Devices without accessories.
Devices with interphase barriers or long terminal shields.
Minimum safety clearances for CVS100 to 630
Operating voltage
U y 440 V
for devices equipped with:
b no accessories
b interphase barriers
b long terminal shields
A1
C1
D1
D2
C1
D1
D2
0
0
0
0
0
0
30
0
0
30
0
0
5
5
0
40
0
0
40
0
0
Spacing > 60 mm
Spacing y 60 mm
DB400051
Clearance (mm)
Between Between device and sheet metal
devices Painted sheet metal
Bare sheet metal
Bars
F1
Clearances with respect to live bare busbars
F1
Minimum clearances for CVS100 to 630
Operating voltage
F2
Live busbars.
B-4
Clearances with respect to live bare busbars
spacing > 60 mm
spacing y 60 mm
F1
F2
F1
F2
U < 440 V
350
350
80
80
These clearances can be reduced for special installations as long as the configuration is checked by
tests.
F2
Bars
Dimensions and connection
EasyPact CVS
Dimensions and connection
Contents
Functions and characteristics
Installation recommendations
Dimensions and mounting
EasyPact CVS100 to 630
Vigi CVS100 to 630
Front-panel accessories
EasyPact CVS100 to 630
Front-panel cutouts
EasyPact CVS100 to 630
Power connections
EasyPact and Vigi CVS100 to 630
Connection of insulated bars or cables with lugs to EasyPact and Vigi
CVS100 to 630
Connection of bare cables to EasyPact and Vigi CVS100 to 630
Dimension & installation recommendation
EasyPact CVS 800
Electrical wiring diagram
EasyPact CVS 3 Phase 3 Wire and 3 Phase 4 Wire operated GFP
Additional characteristics
Catalogue numbers
A-1
B-1
C-2
C-3
C-4
C-5
C-6
C-9
C-10
C-11
C-12
D-1
E-1
C-1
Dimensions and mounting
Dimensions and
connection
EasyPact CVS100 to 630
3P
4P
DB400058
DB400057
DB400056
DB400055
Dimensions
A4
A3
A2
A
A1
X
X
A
X
A2
A3
A4
C1
C2
B
B1
C3
B
B2
Y
Y
Long terminal shields (also available for CVS400/630 spreaders with 52.5 mm pitch:
B1 = 157.5 mm, B2 = 210 mm).
Z
Mounting
CVS100 to 250
CVS400/630
CVS100 to 630
On backplate
3P
3P
4P
DB400059
DB111411
Interphase barriers.
Short terminal shields.
F2
F1
F1
F1
F2
F1
F1 F1
F2
X
X
E1
F1
F3
E4
E2
DB112067
F1
DB112066
F1
X
E3
2 Ø6
ØT(1)
Y
4 Ø6
Y
4 Ø6
Y
(1) The ØT holes are required for rear connection only.
3P
DB400063
4P
DB112069
F1
F2
F1
DB112070
3P
DB111412
On rails
F2
F3
F2
U
X
E2
X
X
E1
Y
2 Ø6
Y
DB400169
DB400168
On DIN rail with adaptor plate (CVS100 to 250)
G4
G5
G3
X
G2
G1
Z
C-2
4 Ø6
Y
4 Ø6
Dimensions and mounting
Vigi CVS100 to 630
3/4P
CVS100 to 250
DB400070
DB400068
DB400069
3/4P
DB400067
Dimensions
CVS400/630
A4
A3
A2
A
X
A6
A5
X
X
A8
A7
A9
C1
C2
C3
B
B1
B2
Z
B
B1
B2
Y
Y
Mounting
CVS100 to 250
CVS400/630
CVS100 to 630
On backplate
3P
3P
4P
E1
F1
F2
F3
X
X
E6
F1 F1
DB112079
DB112078
DB400071
DB111420
F1 F1
F2
F1
F1 F1
F2
F1
X
E8
E5
E7
ØT(1)
Y
6 Ø6
Y
3 Ø6
6 Ø6
Y
(1) The ØT holes are required for rear connection only.
3P
DB400075
4P
F1
DB112081
F1
F2
F3
DB112082
3P
DB111421
On rails
F2
F2
U
E6
X
X
X
E1
E5
3 Ø6
Y
Type
CVS100/160/250
CVS400/630
Type
CVS100/160/250
CVS400/630
A
A1
80.5
161
127.5 255
E2
E3
125
70
200
113.5
A2
94
142.5
E4
140
227
A3
A4
145
178.5
200
237
E5
E6
137.5 200
200
300
A5
155.5
227.5
E7
145
213.5
A6
236
355
E8
215
327
A7
169
242.5
F1
35
45
A8
220
300
F2
17.5
22.5
A9
253.5
337
F3
70
90
Y
6 Ø6
B
52.5
70
G1
95
-
B1
105
140
G2
75
-
Y
B2
140
185
G3
13.5
-
C1
81
95.5
G4
23
-
C2
86
110
G5
17.5
-
C3
126
168
ØT
24
32
6 Ø6
E1
62.5
100
U
y 32
y 35
C-3
Front-panel accessories
Dimensions and
connection
EasyPact CVS100 to 630
IP40 front-panel escutcheons
E21643
E21642
E21641
DB400041
For toggle
M2
M3
A1
D1
D2
A2
DB115012
DB115011
DB115010
DB400089
For rotary handle or module and protection collar
X
A3
X
3.5
6.5
B1
Y
DB115020
DB115019
DB115018
DB400097
For Vigi
79 X
64
69
Y
3.5
X
6.5
Type
A1
A2
A3
B1
M2
M3
CVS100/160/250
CVS400/630
91
123
114
164
101
151
157
189
115
155
102
142
C-4
Front-panel cutouts
EasyPact CVS100 to 630
Bare sheet metal
CVS100 to 250
CVS400/630
DB400117
DB400116
DB400115
DB400034
For toggle
X
X
76
29
Y
P3
116
X
41.5
Y
R
R1
R
R1
Z
DB400121
DB400120
DB400119
DB400118
For toggle with access to trip unit
X
102
54.5
P3
X
175
90
63.5
47.5
127
95
Y
Z
Y
Type
P3
R
R1
CVS100/160/250
CVS400/630
88
112
14.5
31.5
29
63
Bare sheet metal
X
CVS100 to 250
CVS400/630
DB400125
DB400124
DB400123
DB400122
For toggle
X
X
X
85.5
148
38
38
14.5
P3
29
Y
Z
29
32
Y
DB400129
DB400128
DB400127
DB400126
For toggle with access to trip unit
X
X
X
85.5
148
38
38
P3
Z
14.5
29
Y
29
32
Y
C-5
Power connections
Dimensions and
connection
EasyPact and Vigi CVS100 to 630
Connection locations
B1
DB400135
DB400134
C1
B1
B1
A1
X
X
A2
A3
Y
C2
Z
Type
A1
CVS100/160
CVS250
CVS400/630
70
140
70
140
113.5 227
A2
B1
C1
C2
Type
A1
35
35
45
19.5
21.5
26
19.5
19.5
26
CVS100/160 + Vigi
CVS250 + Vigi
CVS400/630 + Vigi
70
215
70
215
113.5 327
A3
B1
C1
C2
35
35
45
19.5
21.5
26
21.5
21.5
26
Front connection without accessories
CVS400/630
DB400138
DB400137
DB400136
CVS100 to 250
Z
Z
10.5
14
70
113.5
X
X
Cables with lugs/bars
Bars/cables with lugs
Connection with accessories
Long and short rear connectors
DB116107
CVS100 to 250
10
DB400137
Z
43 for short RC
88 for long RC
∅8.6
13
18
70
6
∅20
X
DB116108
CVS400/630
50 for short RC
115 for long RC
15
30
∅13
Z
∅23.2
14
113.5
8
X
C-6
Power connections
EasyPact and Vigi CVS100 to 630
Connection with accessories (cont.)
CVS100 to 250
DB115452
DB115451
DB400138
Bare-cable connectors
Z
Z
63
22
70
70
DB400139
X
X
DB115455
DB115454
CVS400/630
Z
Z
46.5
14
113.5
113.5
X
X
Distribution connectors (for CVS100 to 250 only)
DB115456
DB115457
X
70
41
(a) Vigi module
or CVS250.
Z
64.5
66.5 (a)
Right-angle terminal extensions (upstream only)
Z
CVS400/630
37.5
39.5 (b)
DB115460
DB400140
DB115459
CVS100 to 250
4
Z
61
8
20.5
34
70
113.5
(b) CVS250.
X
X
DB115462
DB400141
Straight terminal extensions (for CVS100 to 250 only)
4
Z
30
41
70
X
C-7
Power connections
Dimensions and
connection
EasyPact and Vigi CVS100 to 630
Connection with accessories (cont.)
Spreaders
3P
4P
E2
F2
DB400145
E2
DB400144
DB400143
DB400142
CVS100 to 250
E1
E3
E2
E2
E2
C3
F1
X
X
X
Z
CVS400/630
Y
C4
Y
Type
C3
C4
E1
E2
E3
F1
F2
CVS100/160
23.5
-
114
45
159
100
11
CVS250
25.5
-
114
45
159
100
11
CVS400/630
-
44
135
170
52.5
70
187.5
240
152.5 15
166
15
X
Z
C-8
Power connections
Direct connection to CVS100 to 630
DB115653
DB400013
Connection of insulated bars or cables with lugs to
EasyPact and Vigi CVS100 to 630
I
DB115654
Bar.
Dimensions
Ø
400
Bars
L (mm)
I (mm)
d (mm)
e (mm)
Ø (mm)
L (mm)
Ø (mm)
d
L
e
Lugs
Torque (Nm) (1)
Torque (Nm) (2)
Ø
CVS100
CVS160/250
CVS400/630
y 25
d + 10
y 10
y6
6.5
y 25
6.5
10
5/5
y 25
d + 10
y 10
y6
8.5
y 25
8.5
15
5/5
y 32
d + 15
y 15
3 y e y 10
10.5
y 32
10.5
50
20/11
(1) Tightening torque on the circuit breaker for lugs or bars.
(2) Tightening torque on fixed devices for rear connectors.
L
Lug.
Connection with accessories to CVS100 to 250 (IEC 228)
Pole pitch
Accessories for CVS100 to 250
terminal
35 mm
45 mm
Dimensions
With spreaders or terminal extensions
CVS100
CVS160/250
Bars
DB115655
DB112172
Straight
extensions
Without spreaders
With spreaders
Ø
400
Tinned copper
I
Spreaders:
separate parts
d
L
L
e
L (mm)
l (mm)
d (mm)
Ø
e (mm)
Ø (mm)
L (mm)
Lugs
Ø (mm)
Torque (Nm) (1)
y 25
20 y I y 25
y 10
y6
6.5
y 25
6.5
10
y 25
20 y I y 25
y 10
y6
8.5
y 25
8.5
15
DB112177
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
Spreaders and straight, right-angle, 45°, double-L and edgewise terminal extensions
are supplied with flexible interphase barriers.
Tinned copper
Connection with accessories to CVS400 and 630 (IEC 228)
Pole pitch
Without spreaders
Spreaders made up of separate parts for 52.5 and 70
mm pitch
Tinned copper
With spreaders
With terminal extensions
L (mm)
l (mm)
d (mm)
e (mm)
Ø (mm)
y 40
d + 15
y 20
3 y e y 10
12.5
y 32
30 y I y 34
y 15
3 y e y 10
10.5
L (mm)
y 40
y 32
Ø (mm)
12.5
10.5
50
50
Bars
Ø
I
Right-angle terminal extensions
Ø
d
L
L
e
Lugs
Torque (Nm) (1)
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
Tinned copper
To be mounted on upstream
side.
Spreaders and right-angle, 45° and edgewise terminal extensions are supplied with
flexible interphase barriers.
DB115658
DB112173
52.5 or 70 mm
Dimensions
400
Accessories for CVS100 to 630
45 mm
With spreaders
DB115655
DB115657
Accessories for CVS400 and 630
Mounting detail: 2 cables
with lugs.
C-9
Power connections
Connection of bare cables to EasyPact and
Vigi CVS100 to 630
DB112317
Connection for CVS100 to 250
DB112315
DB400149
Dimensions and
connection
DB115663
1-cable
connector
L
2-cable
connector
1-cable connector Steel
y 160 A
Aluminium
y 250 A
L (mm)
25
25
S (mm2) Cu/Al
1.5 to 95 (1)
25 to 50
70 to 95
120 to 185
150 max. flex.
Torque (Nm)
12
20
26
26
2-cable connector
S
L (mm)
25 or 50
S (mm2) Cu/Al
2 x 50 to 2 x 120
Torque (Nm)
22
(1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrules.
DB111326
DB112316
Connection to CVS400 and 630
DB115663
1-cable connector
L
2-cable connector
1-cable connector
2-cable connector
L (mm)
30
30 or 60
S (mm2) Cu/Al
35 to 300 rigid
240 max. flex.
2 x 35 to 2 x 240 rigid
240 max. flex.
Torque (Nm)
31
31
S
Conductor materials and electrodynamic stresses
EasyPact CVS circuit breakers can be connected indifferently with bare-copper,
tinned-copper and tinned-aluminium conductors (flexible or rigid bars, cables).
In the event of a short-circuit, thermal and electrodynamic stresses will be exerted
on the conductors. They must therefore be correctly sized and held in place by
supports.
Electrical connection points on switchgear devices (switch-disconnectors,
contactors, circuit breakers, etc.) should not be used for mechanical support.
Any partition between upstream and downstream connections of the device must
be made of non-magnetic material.
C-10
Dimension & installation
recommendation
EasyPact CVS 800
Direct Rotary handle EasyPact CVS 800
MCB Type
A
CVS 800
Dimension
B
129
114
Panel Depth 'L'
C
179 ±1
70
Extended rotary Handle
MCB Type
A
2-Ø 4.5
CVS 800
Dimension
B
C
129
114
70
K9
159
240
K10
114
170
CVS 800 F/N
3P
4P
CVS 800 F/N
3P
Connection with accessories
Spreader
4P
Rating
800 A
Dimn. 't'
8.0 mm
Dimensions (mm)
Type
CVS100/160/200/250
CVS400/630
G26
30
52.5
G27
41
67.5
K8
45
70
C-11
Electrical wiring diagram
Dimensions and
connection
EasyPact CVS
3 Phase 3 Wire and 3 Phase 4 Wire operated GFP
EasyPact CVS 100 to 800A
Wiring diagram for shunt release operated GFP
Wiring diagram for under voltage release operated GFP
b Supply to RELAY UNIT & UNDER VOLTAGE RELEASE
shall be taken from SUPPLY SIDE of MCCB.
b Control Voltage supply to RELAY UNIT shall be taken
from LINE SIDE of MCCB.
b Supply to SHUNT RELEASE shall be taken form LOAD
SIDE of MCCB.
Notes:
1. Connections shown in dotted lines shall be made by customer.
2. HRC fises are not in SEIPL’s scope of supply.
3. Remove BOTTOM SIDE SPREADERS (if Fitted) of MCCB before mounting ‘CT’ on MCCB.
E/F Sensitivity Selector
Switch
Current Selector Switch
Ground Fault
Protection
Test Push
Button
Unique
system
Healthy
indication
Earth Fault
Indication
Reset
Push
Button
CT
details
Sealing
Stud
Time Delay Selector
switch (2 step setting)
1. To change any setting switch ‘OFF’ the MCCB. Remove protective cover from Relay Module. Replace cover after changing setting.
2. To test E/F relay press test Push Button. E/F relay will operate according to the time delay selection. Keep the Test Push Button pressed till the
relay trips (indicated by red lamp).
C-12
Additional characteristics
EasyPact CVS
Additional characteristics
Contents
Functions and characteristics
Installation recommendations
Dimensions and connection
Tripping curves
EasyPact CVS100 to 800A Protection of distribution systems
EasyPact CVS100 to 250 Motor protection
Current and energy limiting curves
Catalogue numbers
A-1
B-1
C-1
D-2
D-5
D-6
E-1
D-1
Tripping curves
Additional
characteristics
EasyPact CVS 100 to 800A
Protection of distribution systems
TM magnetic trip units
TM16D/25D
TM32D
t(s)
DB400095
DB400094
10 000
5 000
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
5
t(s)
2
2
TM16D/25D : Im = 12 x In
1
.5
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
2
3 4 5 7 10
20 30
50 70 100
TM32D : Im = 12.5 x In
1
200 300
t < 10 ms
2
I / Ir
DB400101
DB400096
2 000
200 300
10 000
5 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
t(s)
2
TM40D : Im = 12.5 x In
1
.5
5
2
TM63D : Im = 8 x In
1
.5
TM50D : Im = 10 x In
.2
.1
.05
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
2
3 4 5 7 10
I / Ir
D-2
50 70 100
TM63D
10 000
5 000
.2
20 30
I / Ir
TM40D/50D
t(s)
3 4 5 7 10
20 30
50 70 100
200 300
t < 10 ms
2
3 4 5 7 10
I / Ir
20 30
50 70 100
200 300
Tripping curves
EasyPact CVS 100 to 800A
Protection of distribution systems
TM magnetic trip units
TM125D/160D
10 000
5 000
t(s)
DB400103
DB400102
TM80D/100D
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
t(s)
2
TM80D/100D : Im = 8 x In
1
5
2
.5
.2
.2
.1
.05
.1
.05
.02
.01
TM160D : Im = 8 x In
.02
.01
t < 10 ms
.005
.002
.001
.5 .7 1
TM125D : Im = 10 x In
1
.5
2
3 4 5 7 10
20 30
50 70 100
.002
.001
.5 .7 1
200 300
I / Ir
10 000
5 000
DB400106
10 000
5 000
DB400104
TM320D/400D
2 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
10
5
t(s)
2
TM200D/250D :
Im = 10 x In
1
2
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
I / Ir
20 30
50 70 100
200 300
20 30
50 70 100
TM320D/400D :
Im = 5...10 x In
1
.5
3 4 5 7 10
3 4 5 7 10
5
.5
2
2
I / Ir
TM200D/250D
t(s)
t < 10 ms
.005
200 300
t < 10 ms
2
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
D-3
Tripping curves
Additional
characteristics
EasyPact CVS 100 to 800A
Protection of distribution systems
TM500D
TM600D
DB400108
DB400107
10 000
5 000
2 000
10 000
5 000
2 000
1 000
1 000
500
500
200
200
100
100
50
50
20
20
10
t(s)
10
5
5
t(s)
2
2
TM500D :
Im = 5...10 x In
1
.5
TM600D :
Im = 4...8 x In
1
.5
.2
.2
.1
.05
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
2
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
t < 10 ms
2
3 4 5 7 10
I / Ir
ETS 2.3 electronic trip units
TM Magnetic Trip Unit
200 - 400A
TM800D
DB400105
DB400105
315 - 630A
10 000
5 000
2 000
1 000
Ir = 0.5...1 x In
500
200
100
50
20
10
t(s)
5
2
Isd = 2...10 x Ir
1
.5
.2
.1
.05
.02
.01
Reflex tripping :
t < 10 ms
.005
.002
.001
.5 .7 1
I = 11 x In
2
3 4 5 7 10
I / Ir
D-4
20 30
50 70 100
200 300
20 30
50 70 100
200 300
Tripping curves
EasyPact CVS100 to 250
Motor protection
MA magnetic trip units
MA150 and MA220
10 000
5 000
DB115716
DB118546
MA2.5... MA100
10 000
5 000
2 000
2 000
1 000
1 000
500
500
200
200
100
100
Thermal withstand
50
20
10
10
5
t(s)
2
Im = 6 ... 14 x In
Im = 9 ... 14 x In
(MA100 4P)
1
.5
2
.5
.2
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
3 4 5 7 10
20 30
50 70 100
Im = 9 ... 14 x In
1
.1
.05
2
MA150
5
.2
.002
.001
.5 .7 1
MA220
50
20
t(s)
Thermal withstand
t < 10 ms
.005
.002
.001
.5 .7 1
200 300
2
I / Ir
3 4 5 7 10
20 30
50 70 100
200 300
I / Ir
Reflex tripping.
MA500
10 000
5 000
DB400111
DB400110
MA320
2 000
10 000
5 000
2 000
1 000
1 000
500
500
200
200
100
100
Thermal withstand
50
50
20
20
10
10
5
Thermal withstand
5
t(s)
t(s)
2
2
1
1
.5
.5
.2
.2
Im = 6 ...13 x In
.1
.05
Im = 6 ...13 x In
.1
.05
.02
.01
.02
.01
t < 10 ms
.005
.005
.002
.001
.5 .7 1
.002
.001
.5 .7 1
2
3 4 5 7 10
I / In
20 30
50 70 100
200 300
t < 10 ms
2
3 4 5 7 10
20 30
50 70 100
200 300
I / In
D-5
Tripping curves
Additional
characteristics
Current and energy limiting curves
100 to 800A
The limiting capacity of a circuit breaker is its aptitude
to let through a current, during a short-circuit, that is
less than the prospective short-circuit current.
DB115719
(Isc)
Prospective
Isc peak
Prospective
current
Ics = 100 % Icu
The exceptional limiting capacity of the EasyPact CVS range greatly reduces the
forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
the following steps:
b break three times consecutively a fault current equal to 100% of Icu
b check that the device continues to function normally, that is:
v it conducts the rated current without abnormal temperature rise
v protection functions perform within the limits specified by the standard
v suitability for isolation is not impaired.
Longer service life of electrical installations
Prospective
Isc
Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
on installations.
Limited Isc
peak
Thermal effects
Less temperature rise in conductors, therefore longer service life for cables.
Actual
current
Limited
Isc
Mechanical effects
Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
being deformed or broken.
(t)
Electromagnetic effects
Fewer disturbances for measuring devices located near electrical circuits.
300
The exceptional limiting capacity of the EasyPact CVS range is
due to the rotating double-break technique (very rapid natural
repulsion of contacts and the appearance of two arc voltages
in-series with a very steep wave front).
Current and energy limiting curves
The limiting capacity
of a circuit breaker is expressed by two curves which are a
200
function of the prospective short-circuit current (the current which would flow if no
146
protection devices were installed):
100
b the actual peak current
(limited current)
80
b thermal stress (A270
s), i.e. the energy dissipated by the short-circuit in a conductor
60
with a resistance of 1
50Ω.
40
kÂ
N CVS630
F
30
Maximum permissible
cable stresses
CVS400
The table below indicates
the maximum permissible
thermal stresses for cables
F CVS250
20
depending on their insulation, conductor (CuBor Al)CVS100
and their cross-sectional area
CVS160
(CSA). CSA values are given in mm2 and thermal stresses in A2s.
10
CSA
PVC
1.5 8mm2
7
4
2.97x10
6
Cu
5
4
2
Al
PRC
Cu
2.5 mm2
4 mm2
6 mm2
10 mm2
8.26x104
2.12x105
4.76x105
1.32x106
5.41x105
3
4
4
4.10x10
6
10
1.39x10
PVC
PRC
16 mm2
30 40 50 5 70 100
200 5300
6.56x10
25 mm2
35 mm2
50 mm2
3.31x107
Al
CSA
20
2.92x10
5
kA rms
7.52x105
Cu
3.4x106
8.26x106
1.62x107
Al
1.39x106
3.38x106
6.64x106
1.35x107
Cu
4.69x106
1.39x107
2.23x107
4.56x107
Al
10
6
1.93x10
4.70x106
9.23x106
1.88x107
9
5
3
2
Energy-limiting
curves
1.41
Current-limiting curves
10
200
3
2
10
146
2
100
80
70
60
50
kÂ
As
F
30
20
N CVS630
5
10
CVS400
F
6
F
B
5
F CVS250
B
3
2
CVS100
CVS160
10
N
CVS630
CVS400
CVS250
CVS100
CVS160
5
5
3
4
6
10
20
30 40 50 70 100
kA rms
D-6
7
3
2
40
10
8
7
6
5
4
2
8
5
DB116371
DB116369
300
200 300
3
2
2
3
4
6
10
20
30 40 50 70 100 150 200 300
kA rms
1.82x106
Catalogue numbers
EasyPact CVS
Catalogue numbers
Contents
Functions and characteristics
Installation recommendations
Dimensions and connection
Additional characteristics
A-1
B-1
C-1
D-1
EasyPact CVS100 to 250
E-2
EasyPact CVS400 to 630
E-9
EasyPact CVS 800
E-15
E-1
Catalogue numbers
EasyPact CVS100/160/250B/F:
complete fixed/FC device
(25/36 kA 380/415 V)
EasyPact CVS100/160/250B
DB400150
With TM-D thermal-magnetic trip unit
EasyPact CVS100B (25 kA at 380/415 V)
Rating
TM16D
TM25D
TM32D
TM40D
TM50D
TM63D
TM80D
TM100D
EasyPact CVS160B (25 kA at 380/415 V)
Rating
TM100D
TM125D
TM160D
EasyPact CVS250B (25 kA at 380/415 V)
Rating
TM160D
TM200D
TM250D
3P
LV510300
LV510301
LV510302
LV510303
LV510304
LV510305
LV510306
LV510307
4P
LV510310
LV510311
LV510312
LV510313
LV510314
LV510315
LV510316
LV510317
3P
LV516301
LV516302
LV516303
4P
LV516311
LV516312
LV516313
3P
LV525301
LV525302
LV525303
4P
LV525311
LV525312
LV525313
3P
LV510330
LV510331
LV510332
LV510333
LV510334
LV510335
LV510336
LV510337
4P
LV510340
LV510341
LV510342
LV510343
LV510344
LV510345
LV510346
LV510347
3P
LV516331
LV516332
LV516333
4P
LV516341
LV516342
LV516343
3P
LV525331
LV525332
LV525333
4P
LV525341
LV525342
LV525343
EasyPact CVS100/160/250F
DB400150
With TM-D thermal-magnetic trip unit
EasyPact CVS100F (36 kA at 380/415 V)
Rating
TM16D
TM25D
TM32D
TM40D
TM50D
TM63D
TM80D
TM100D
EasyPact CVS160F (36 kA at 380/415 V)
Rating
TM100D
TM125D
TM160D
EasyPact CVS250F (36 kA at 380/415 V)
Rating
TM160D
TM200D
TM250D
+ Vigi module for insulation monitoring
DB112249
Vigi module
ME type for CVS/NSX100/160 (200 to 440 V)
3P
4P
LV429212
LV429213
MH type for CVS/NSX100/160 (200 to 440 V)
LV429210
LV429211
MH type for CVS/NSX250 (200 to 440 V)
LV431535
LV431536
MH type for CVS/NSX100/160 (440 to 550 V)
LV429215
LV429216
MH type for CVS/NSX250 (440 to 550 V)
LV431533
LV431534
Connection for a 4P Vigi on a 3P breaker
LV429214
DB112249
Insulation monitoring module
200 to 440 V AC
Connection for a 4P insulation monitoring
module on a 3P breaker
E-2
3P
4P
LV429459
LV429460
LV429214
EasyPact CVS100/160/250N:
complete fixed/FC device
MA magnetic trip unit (50 kA 380/415 V)
EasyPact CVS100/160/250F
DB400155
With MA magnetic trip unit
EasyPact CVS100N (50 kA at 380/415 V)
Rating
MA2.5
MA6.3
MA12.5
MA25
MA50
MA100
EasyPact CVS160N (50 kA at 380/415 V)
Rating
MA150
EasyPact CVS250N (50 kA at 380/415 V)
Rating
MA220
3P
LV510450
LV510451
LV510452
LV510453
LV510454
LV510455
3P
LV516451
3P
LV525442
Ground Fault Protection
Ref. 32/40/50/63/80/100
Ref. 125/160/200/250
3 PH 3W
GFP11CT13P
GFP12CT23P
3 PH 4W
GFP11CT14P
GFP12CT24P
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection
E-3
Catalogue numbers
Accessories
EasyPact CVS100/160/250
Connection accessories (Cu or Al)
DB112225
Rear connections
2 short
2 long
LV429235
LV429236
DB112226
1 x (1.5 to 95 mm2) ; y 160 A
Set of 3
Set of 4
LV429242
LV429243
DB112225
Aluminium connectors
1 x (25 to 95 mm2) ; y 250 A
Clips for connectors
Set of 3
Set of 4
Set of 3
Set of 4
Set of 10
LV429227
LV429228
LV429259
LV429260
LV429241
Set of 3
Set of 4
LV429218
LV429219
6.35 mm voltage tap for steel or aluminium connectors
Set of 10
LV429348
Edgewise terminal extensions (1)
Set of 4
LV429309
Right-angle terminal extensions (1)
Set of 3
Set of 4
LV429261
LV429262
Straight terminal extensions (1)
Set of 3
Set of 4
LV429263
LV429264
Spreaders from 35 to 45 mm pitch (1)
3P
4P
LV431563
LV431564
DB112724
DB112227
Steel connectors
DB112726
Bare cable connectors
1 x (120 to 185 mm2) ; y 250 A
Aluminium connectors for 2 cables (1)
2 x (50 to 120 mm2) ; y 250 A
DB112235
DB112233
DB112232
DB112231
Terminal extensions
(1) Supplied with 2 or 3 interphase barriers.
E-4
Accessories
EasyPact CVS100/160/250
LV429252
LV429256
LV429253
LV429257
LV429254
LV429258
Set of 3
Set of 4
Set of 3
Set of 4
LV429504
LV429505
LV429506
LV429507
DB400161
1 short terminal shield for breaker
3P
4P
LV429515
LV429516
DB400162
1 long terminal shield for breaker
3P
4P
LV429517
LV429518
DB112241
For cable 120 mm2
Interphase barriers for breaker
Set of 6
LV429329
2 insulating screens for breaker (45 mm pitch)
3P
4P
LV429330
LV429331
DB112237
Set of 3
Set of 4
Set of 3
Set of 4
Set of 3
Set of 4
DB400163
Crimp lugs for copper cable (1)
For cable 150 mm2
For cable 185 mm2
Crimp lugs for aluminium cable (1)
DB112238
For cable 150 mm2
For cable 185 mm2
Insulation accessories
(1) Supplied with 2 or 3 interphase barriers.
E-5
Catalogue numbers
Accessories
EasyPact CVS100/160/250
Electrical auxiliaries
DB112254
Auxiliary contacts (changeover)
OF or SD or SDE or SDV
OF or SD or SDE or SDV low level
SDE adaptor, mandatory for trip unit TM, MA
DB115631
DB111454
Voltage releases
E-6
Voltage
24 V 50/60 Hz
48 V 50/60 Hz
110-130 V 50/60 Hz
220-240 V 50/60 Hz and 208-277 V 60 Hz
380-415 V 50 Hz and 440-480 V 60 Hz
DC
12 V
24 V
30 V
48 V
60 V
125 V
250 V
MN 48 V 50/60 Hz with fixed time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN 220-240 V 50/60 Hz with fixed time delay
Composed of:
MN 250 V DC
Delay unit 220-240 V 50/60 Hz
AC
29450
29452
LV429451
MX
LV429384
LV429385
LV429386
LV429387
LV429388
LV429382
LV429390
LV429391
LV429392
LV429383
LV429393
LV429394
MN
LV429404
LV429405
LV429406
LV429407
LV429408
LV429402
LV429410
LV429411
LV429412
LV429403
LV429413
LV429414
LV429412
LV429426
LV429414
LV429427
Accessories
EasyPact CVS100/160/250
Rotary handles
DB112259
Direct rotary handle
With black handle
LV429337
With black handle
LV429338
DB112260
Extended rotary handle
Locks
DB400164
By removable device
29370
DB400165
Toggle locking device for 1 to 3 padlocks
By fixed device
29371
DB112263
Locking of rotary handle
Keylock adaptor (keylock not included)
Keylock (keylock adaptor not included)
Ronis 1351B.500
Profalux KS5 B24 D4Z
LV429344
41940
42888
E-7
Catalogue numbers
Accessories
EasyPact CVS100/160/250
Interlocking
DB111486
With toggles
29354
DB111487
Mechanical interlocking for circuit breakers
With rotary handles
LV429369
Mechanical interlocking for circuit breakers
DB112268
Keylock kit (keylock not included) (1)
1 set of 2 keylocks
(1 key only, keylock kit not included)
Ronis 1351B.500
Profalux KS5 B24 D4Z
LV429344
41950
42878
Installation accessories
E21641
E21641
Front-panel escutcheons
IP40 toogle escutcheon (small cut-out)
IP40 escutcheon for Rotary handle
IP40 escutcheon for Vigi module
29315
LV429317
LV429316
Bag of accessories
LV429375
1 adaptor
LV429305
10 toggle extensions
Bag of screws
12 snap-in nuts (fixed/FC)
LV429313
LV429312
LV510100
LV516060
LV429226
IP40
DB115615
Lead-sealing accessories
DB112739
Din rail adaptor
E18624
Spare parts
1 set of 10 identification labels
(1) For only 1 device.
E-8
M6 for CVS100B/F
M8 for CVS160/250B/F
CVS400/630:
complete fixed/FC device
EasyPact CVS400/630F/N
EasyPact CVS400/630F
With TM-D thermal-magnetic trip unit
DB400008
EasyPact CVS400F (36 kA at 380/415 V)
Rating
TM320D
TM400D
EasyPact CVS630F (36 kA at 380/415 V)
Rating
TM500D
TM600D
3P
LV540305
LV540306
4P
LV540308
LV540309
3P
LV563305
LV563306
4P
LV563308
LV563309
3P
LV540315
LV540316
4P
LV540318
LV540319
3P
LV563315
LV563316
4P
LV563318
LV563319
EasyPact CVS400/630N
With TM-D thermal-magnetic trip unit
DB400008
EasyPact CVS400N (50 kA at 380/415 V)
Rating
TM320D
TM400D
EasyPact CVS630N (50 kA at 380/415 V)
Rating
TM500D
TM600D
EasyPact CVS400/630N
DB400020
With MA magnetic trip unit
EasyPact CVS400N (50 kA at 380/415 V)
Rating
MA320
EasyPact CVS630N (50 kA at 380/415 V)
Rating
MA500
3P
LV540552
LV563552
6500 3000
6000
5500
3500
4000
5000 4500
EasyPact CVS400/630F
DB400021
ETS 2.3 electronic trip unit (protection)
EasyPact CVS400F (36 kA at 380/415 V)
EasyPact CVS630F (36 kA at 380/415 V)
5
6
4
565
3P
LV540505
LV563505
4P
LV540506
LV563506
400 A
630 A
3P
LV540510
LV563510
4P
LV540511
LV563511
7
8
3
505
400 A
630 A
10
2
630
440
370
315
EasyPact CVS400/630N
DB400021
ETS 2.3 electronic trip unit (protection)
EasyPact CVS400N (50 kA at 380/415 V)
EasyPact CVS630N (50 kA at 380/415 V)
5
4
3
505
565
6
7
8
10
2
630
440
370
315
E-9
Catalogue numbers
CVS400/630:
complete fixed/FC device
EasyPact CVS400/630N (36 kA 380/415 V)
+ Vigi module or insulation monitoring module
DB111464
Vigi module
Type MB
3P
4P
200 to 440 V
LV432455
LV432456
440 to 550 V
LV432453
LV432454
Connection for a 4P Vigi on a 3P breaker
LV432457
DB111464
Insulation monitoring module
200 to 440 V AC
3P
4P
LV432659
LV432660
Connection for a 4P insulation monitoring
module on a 3P breaker
LV432457
Ref. 400/630
3 PH 3W
GFP13CT33P
3 PH 4W
GFP13CT34P
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection
E-10
Accessories
EasyPact CVS400/630
Connection accessories (Cu or Al)
DB112225
Rear connections
2 short
2 long
LV432475
LV432476
E22040
Aluminium connector 1x (35 to 300 mm2)
Set of 3
Set of 4
LV432479
LV432480
E22041
Cable connectors (1)
Aluminium connector 2x (35 to 300 mm2)
Set of 3
Set of 4
LV432481
LV432482
Voltage plug for aluminium connector 1 or 2 cables
Set of 10
LV429348
Right-angle terminal extension
Set of 3
Set of 4
LV432484
LV432485
Edgewise terminal extensions
Set of 3
Set of 4
LV432486
LV432487
E21012
E21276
Terminal extension (1)
Spreaders
52.5 mm 3P
4P
70 mm
3P
4P
LV432490
LV432491
32492
32493
E18602
Crimp lugs for copper cable (1)
For cable 240 mm2
For cable 300 mm2
Set of 3
Set of 4
Set of 3
Set of 4
LV432500
LV432501
LV432502
LV432503
Set of 3
Set of 4
Set of 3
Set of 4
LV432504
LV432505
LV432506
LV432507
3P
4P
3P
4P
Set of 6
52,5 mm 3P
4P
70 mm
3P
4P
LV432591
LV432592
LV432593
LV432594
LV432570
LV432595
LV432596
LV432578
LV432579
Supplied with 2 (or 3) interphase barriers
E30908
Crimp lugs for aluminium cable (1)
For cable 240 mm2
For cable 300 mm2
Supplied with 2 (or 3) interphase barriers
E18606
E18618
Insulation accessories
Short terminal shield, 45 mm (1 piece)
Long terminal shield, 45 mm (1 piece)
Interphase barriers
2 insulating screens (70 mm pitch)
E-11
Catalogue numbers
Accessories
EasyPact CVS400/630
Electrical auxiliaries
E18608
Auxiliary contacts (changeover)
E18609
Voltage releases
E-12
OF or SD or SDE or SDV
OF or SD or SDE or SDV low level
SDE adaptor mandatory for trip unit TM, MA and ETS2.3
Voltage
24 V 50/60 Hz
48 V 50/60 Hz
110-130 V 50/60 Hz
220-240 V 50/60 Hz and 208-277 V 60 Hz
380-415 V 50 Hz and 440-480 V 60 Hz
DC
Voltage
12 V
24 V
30 V
48 V
60 V
125 V
250 V
MN 48 V 50/60 Hz with fixed time delay
Composed of:
MN 48 V DC
Delay unit 48 V 50/60 Hz
MN 220-240 V 50/60 Hz with fixed time delay
Composed of:
MN 250 V DC
Delay unit 220-240 V 50/60 Hz
AC
29450
29452
LV540050
MX
LV429384
LV429385
LV429386
LV429387
LV429388
MN
LV429404
LV429405
LV429406
LV429407
LV429408
LV429382
LV429390
LV429391
LV429392
LV429383
LV429393
LV429394
LV429402
LV429410
LV429411
LV429412
LV429403
LV429413
LV429414
LV429412
LV429426
LV429414
LV429427
Accessories
EasyPact CVS400/630
Rotary handle
E18611
Direct rotary handle
Standard black handle
LV432597
Standard extended rotary handle
LV432598
E18612
Extended rotary handle
Locks
E18621
By removable device
29370
E18613
Toggle locking device for 1 to 3 padlocks
By fixed device
32631
E18620
Locking of the rotary handle
Keylock adaptor (keylock not included)
Keylock (keylock adaptor not included)
Ronis 1351B.500
Profalux KS5 B24 D4Z
LV432604
41940
42888
E-13
Catalogue numbers
Accessories
EasyPact CVS400/630
Interlocking
E21288
With toggles
32614
E18780
Mechanical interlocking for circuit breakers
With rotary handles
LV432621
E26766
Interlocking with key (2 keylocks/1 key) for rotary handles
Keylock kit (keylock not included) (1)
1 set of 2 keylocks (1 key only, keylock kit not included)
LV432604
Ronis 1351B.500
Profalux KS5 B24 D4Z
41950
42878
(1) for only 1 device
Installation accessories
E21641
Front-panel escutcheons
IP40 Toggle escutcheon (small cut-out)
32556
IP40 escutcheon for rotary handle
LV432558
IP40 escutcheon for Vigi module
LV429316
Lead-sealing accessories
LV429375
Spare parts
Toggle extension
LV432553
Bag of screws
LV432552
1 set of 10 identification labels
LV429226
E21290
Mini test kit for STR trip units
43362
E36271
Front-panel escutcheons
Portable test kit for STR trip units
34547
Spare test plug for portable test kit 34547
34503
Wiring kit (spare part)
34546
Test
Test kits
E-14
EasyPact CVS MCCBs and accessories
catalogue nos.
for 800A
EasyPact CVS 800
With TM-D thermal -magnetic trip unit
EasyPact CVS 800 ( 35kA at 380/415 V)
Rating
TM800D
EasyPact CVS 800 ( 50kA at 380/415 V)
Rating
TM800D
3P
LV580300
4P
LV580301
3P
LV580302
4P
LV580303
Auxiliary contacts ON/OFF/Trip (change - over)
Ref.
Auxilary Contact 1 C/O
LV580075
Auxilary Contact 2 C/O
LV580076
Alarm Contact 1 C/O
LV580077
Alarm Contact 2 C/O
LV580078
Alarm Auxilary Contact
LV580079
Shunt/Under voltage coil
Shunt/Under voltage
AC 50Hz
DC
Ref. Shunt (MX)
Ref. Under
Voltage (MN)
110-130 V
LV580060
LV580070
220-240 V
LV580061
LV580071
380-415 V
LV580062
LV580072
440 V
LV580063
voltage
Reference
24 V
LV580064
48 V
LV580065
110 V
LV580066
220 V
LV580067
Rotary handles
Direct rotary handles
Ref.
LV580080
Extended rotary handle
Ref.
LV580081
Ground Fault Protection
Ground Fault Relay + CT
Ref.
3 Phase 3 Wire
GFP14CT43P
3 Phase 4 Wire
GFP14CT44P
Note: Kindly order one nos. shunt coil along with one Ground Fault Protection
Order one auxilliary contact alongwith shunt coil for CVS800.
E-15
Make the most of your energy
For more information visit our website at: www.schneider-electric.co.in
Schneider Electric India Pvt. Ltd. (A 100% subsidiary of Schneider Electric Industries SAS)
Corporate office : 9th Floor, DLF Building No.10, Tower C, DLF Cyber City, Phase II,
Gurgaon - 122002, Haryana, Tel: 0124 3940400, Fax: 0124 4222036
Customer Care Centre : Toll-free numbers: 1800 180 1707, 1800 103 0011,
General number: 0124 4222040, Email: in-care@schneider-electric.com
Download