Low Voltage EasyPact CVS Moulded-case circuit breakers from 100 to 800 A Catalogue 2011 Do you strain to find a high quality circuit breaker that is simple, flexible, and safe? Have tight project budgets restricted you from choosing the best technology products? Do you need the reach, support and accessibility of a global leader, with the value of a local supplier? Buildings 2 Industry Energy & Infrastructure Residential Compact CVS has helped our customers with a value system focused on Safety , Simplicity & Reliability. Schneider Electric has always believed in customer satisfaction and ensures that we renovate our offers to meet the changing needs of our customers. Now Schneider Electric is happy to announce that Compact CVS is now EasyPact CVS More Safe , Simple & Reliable A global environment friendly range from Schneider Electric. 3 EasyPact CVS brings more functionalities, options and features which make it more 4 Environmentally responsible n EasyPact CVS is part of the Schneider Electric energy efficiency approach. Designed for easy disassembly and recycling at end of life, EasyPact CVS complies with environmental directives RoHS* and WEEE**, and with ISO 14001 standards, thanks to non - polluting factories. @ @ @ @ Schneider Electric fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: the materials used for EasyPact CVS are not potentially dangerous to the environment the production facilities are non-polluting in compliance with the ISO 14001 standard the energy dissipated per pole is low, making energy losses insignificant the materials are marked to facilitate sorting for recycling at the end of product service life. EasyPact CVS moulded case circuit breakers and accessories can be recycled and reused optimally. * RoHS = Restriction of Hazardous Substances ** WEEE = Waste Electrical and Electronic Equipment 5 Gain peace of mind and optimized cost for every installation 6 EasyPact CVS from 100 to 800A Frame 1 CVS 100 CVS 160 CVS 250 Frame 2 CVS 400 CVS 630 Frame 3 CVS 800* N 50KA F 36KA B 25KA *35kA for EasyPact CVS 800A Breaking performance at 415 V A.C EasyPact CVS 100 - 800A Adjustable version n Various breaking capacities level are available as per the need of electrical distribution network 25/36/50kA. n Available in 3P and 4P Variants. n Entire range is Ics=100% Icu. Safe Reliable Simple 7 EasyPact CVS is...Safe Isolation Class II front Face n EasyPact CVS circuit breakers are suitable for Isolation* as defined in IEC standards 60947-2 .The aim of isolation is to separate a circuit or apparatus from the remainder of a system which is energized in order the personnel may carry out work on the isolated part with complete safety. n MCCB locking with external pad locks* enables user to isolate and undertake maintenance with utmost safety. n All EasyPact CVS* MCCBs are class II Front face devices, they may be installed through the door of class II switchboards without downgrading the switchboard insulation. Installation requires no special operation, even when the Circuit Breaker is equipped with a rotary handle. Class II front face Class II panel with circuit breaker having a class II front face Isolation Locking in OFF position n Key locks enables to lock* the breaker in OFF position ensuring safety and better control on installation. n It also helps in interlocking multiple circuit breakers in an installation. * 100 to 630 A 8 Class II enclosure EasyPact CVS is...Reliable IEC 60947-2 Conforms to IEC 60947-2 for circuit breaker Fault current limitation technology nTested at renown international laboratories like KEMA nComplete range with Ics = 100% Icu n EasyPact CVS Double break* mechanism ensures high fault current limitation @ Reduces thermal stresses on the electrical distribution network @ Increases the life of cables and installation High electrical & Mechanical endurance n 30000 mechanical operations for 100A n 12000 electrical operations for 100A Reliable accessories n Continuous rated shunt coils n Multifunctional Aux./Alarm contact n Unique electrical fault trip indication (SDE) Current limitation technology EasyPact CVS offer protection for human as well as Electrical installation nEarth leakage protection through Vigi Module to protect human against leakage current nEarth Fault protection (UMGFP) to protect Electrical distribution network against fire * 100 to 630 A EasyPact Double break Roto mechanism 9 EasyPact CVS is...Simple Only three frame sizes Frame - I Frame – II Frame – III 100 - 250 A 400 - 630A 800A Spreaders Terminal Shields Line load reversibility for entire EasyPact CVS range System upgradeability n Compact NSX/EasyPact CVS upto 630A have the same foot print & mounting dimensions, helps easy retrofitting and system upgradeability. Electrical auxiliaries * Auxiliaries and accessories are common for MCCBs upto 630A. Compact NSX CVS Stands for Compact Value System Insulation Monitoring EasyPact CVS Rotary Operating handles EasyPact CVS/Compact CVS and Compact NS/NSX MCCBs share the same value system. Schneider Electric has a rich experience in MCCBs with more than 25 million circuit breakers installed base world wide (more than 100 countries). 10 Control accessories Earth fault protection (UMGFP) EasyPact CVS stands for customer value EasyPact CVS 100 to 630 A Panel builders nOnly two frame sizes up to 630A nCommon accessories for complete range (ON/OFF/Trip Auxiliaries/Shunt/UV etc) nLine load reversibility for entire range nSuitable for class II switchboards End Users nIsolation as a standard feature enhances safety n Excellent current limiting capability reduces stresses on cables, busbars and loads n Continuous rated accessories increase system reliability n Moduler earth leakage and earth fault protection ensure human/installation protection OEMs n High endurance’s and maintenance free operation assure continuous performance of machines n Unique common accessories help standardisation of components Contractors n Sufficient pole pitch helps to terminate Copper and Aluminum busbars or cables n Easy availability of the product due to less number of frame size n Designed to perform in demanding applications 11 The easy choice for quality and value EasyPact CVS LV circuit breakers from 100 to 800A EasyPact CVS 12 EasyPact CVS General contents Functions and characteristics A-1 Installation recommendations B-1 Dimensions and connection C-1 Additional characteristics D-1 Catalogue numbers E-1 13 Functions and characteristics EasyPact CVS Functions and characteristics Introduction General characteristics Protection of distribution systems TM-D thermal-magnetic trip units ETS 2.3 Microprocessor trip unit and accessories Earth-leakage protection Add-on protection againes insulation faults using a Vigi module Ground fault protection EasyPact CVS Motor protection MA instantaneous trip units Introduction Characteristics and performance Functions & Characteristics Protection of distribution systems for EasyPact CVS 800 Accessories and auxiliaries A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-10 Overview Device installation Connection of devices Selection of auxiliaries Indication contacts Remote tripping Rotary handles Locks and sealing accessories A-11 A-12 A-13 A-14 A-15 A-16 A-17 A-18 Installation recommendations Dimensions and connection Additional characteristics Catalogue numbers B-1 C-1 D-1 E-1 A-1 Introduction Functions and characteristics General characteristics 100 to 630A DB400000 1 2 7 8 3 4 5 6 cat.A 9 Standardised characteristics indicated on the rating plate: 1 Type of device: frame size and breaking capacity class 2 Ui: rated insulation voltage. 3 Uimp: rated impulse withstand voltage. 4 Ics: service breaking capacity. 5 Icu: ultimate breaking capacity for various values of the rated operational voltage Ue 6 Ue: operational voltage. 7 Colour label indicating the breaking capacity class. 8 Suitable for Isolation symbol. 9 Reference standard. Note: when the circuit breaker is equipped with an extended rotary handle, the door must be opened to access the rating plate. Frame 1 CVS 100 CVS 160 CVS 250 Frame 2 CVS 400 CVS 630 Frame 3 CVS 800* N 50KA F 36KA B 25KA Breaking performance at 415 V A.C Compliance with standards EasyPact CVS circuit breakers and auxiliaries comply with the following international recommendations: b IEC 60947-1: general rules b IEC 60947-2: circuit breakers b IEC 60947-3: switch-disconnectors Pollution degree EasyPact CVS circuit breakers are certified for operation in pollution-degree III environments as defined by IEC standards 60947-1 and 60664-1 (industrial environments). Climatic withstand EasyPact CVS circuit breakers have successfully passed the tests defined by the following standards for extreme atmospheric conditions: b IEC 60068-2-1: dry cold (-55°C) b IEC 60068-2-2: dry heat (+85°C) b IEC 60068-2-30: damp heat (95 % relative humidity at 55°C) b IEC 60068-2-52 severity level 2: salt mist. Environment EasyPact CVS respects the European environment directive EC/2002/95 concerning the restriction of hazardous substances (RoHS). All EasyPact CVS production sites have set up an ISO 14001 certified environmental management system. Ambient temperature EasyPact CVS circuit breakers can be used between -25°C and +70°C. For temperatures higher than 40°C (65°C for circuit breakers used to protect motor feeders), devices must be derated (see page B-2). b Circuit breakers should be put into service under normal ambient, operatingtemperature conditions. Exceptionally, the circuit breaker can be put into service when the ambient temperature is between -35°C and -25°C. b The permissible storage-temperature range for EasyPact CVS circuit breakers in the original packing is -50°C and +85°C. *35kA for EasyPact CVS 800A Suitable for isolation with positive contact indication All EasyPact CVS circuit breakers are suitable for isolation as defined in IEC standard 60947-2: b The isolation position corresponds to the O (OFF) position. b The operating handle cannot indicate the OFF position unless the contacts are effectively open. b Padlocks cannot be installed unless the contacts are open. Installation of a rotary handle does not alter the reliability of the position-indication system. The isolation function is certified by tests guaranteeing: b The mechanical reliability of the position-indication system b The absence of leakage currents b Over voltage withstand capacity between upstream and downstream connections. The tripped position does not ensure isolation with positive contact indication. Only the OFF position guarantees isolation. IEC 60947-2 Installation in class II switchboards All EasyPact CVS circuit breakers are class II front face devices. They can be installed through the door of class II switchboards (as per IEC standards 61140 and 60664-1) without downgrading switchboard insulation. Installation requires no special operations, even when the circuit breaker is equipped with a rotary handle. Degree of protection The following indications are in accordance with standards IEC 60529 (IP degree of protection) and IEC 62262 (IK protection against external mechanical impacts). Bare circuit breaker: b with toggle: IP40, IK07 front face b with extended rotary handle: IP 55, IK08 Circuit breaker installed in a switchboard: b with toggle: IP40, IK07 front face b with extended rotary handle: IP 55, IK08 A-2 Protection of distribution systems TM-D thermal-magnetic trip units TM-D thermal-magnetic trip units DB400003 TM-D thermal-magnetic trip units can be used on EasyPact CVS100-630 circuit breakers with performance levels B/F/N. Protection ........................................................................................... TM-D trip units are used mainly in electrical distribution applications for protection of cables supplied by transformers. Thermal protection (Ir) Thermal protection operates according to: b Ir that can be adjusted in amps from 0.7 to 1 times the rating of the trip unit (16 A to 250 A), corresponding to settings from 11 to 250 A for the range of trip units b a non-adjustable time delay. Magnetic protection (Im) Short-circuit protection with a fixed or adjustable pick-up Im that initiates instantaneous tripping if exceeded. b TM-D: fixed pick-up, Im, for 16 to 250 A ratings and adjustable from 5 to 10 x In for 400 A ratings, 4 to 8 x In for 600 A rating. Protection versions b v b v v Thermal-magnetic trip units 3-pole: 3P 3D: 3-pole frame (3P) with detection on all 3 poles (3D) 4-pole: 4P 3D: 4-pole frame (4P) with detection on 3 poles (3D). 4P 4D: 4-pole frame (4P) with detection on all 4 poles (same threshold for phases and neutral). TM16D to 250D TM320D to 630D Ratings (A) In at 40 °C (1) 16 25 32 40 50 63 80 100 125 160 200 250 Circuit breaker CVS100 b b b b b b b b - - - - CVS160 - - - - - - CVS250 - - - - - - - b b b - - - - - b b b 320 400 500 630* CVS400 b b - - CVS630 - - b b Magnetic protection Pick-up (A) Im fixed accuracy ± ±20 % CVS100 190 adjustable 300 400 500 500 500 640 800 CVS160/250 800 1250 1250 2000 2500 CVS400 5 to 10 x In CVS630 4 to 8 x In Thermal protection Pick-up (A) Ir = In x ... adjustable in amps from 0.7 to 1 x In Unprotected neutral 4P 3D no detection Fully protected neutral 4P 4D 1 x Ir tripping between 1.05 and 1.20 Ir Neutral protection (1) For temperatures greater than 40°C, the thermal protection characteristics are modified. See the temperature derating table on page B-2. * 630 A @ 30°C Note: All the trip units have a transparent lead-sealable cover that protects access to the adjustment dials. A-3 Functions and characteristics Protection of distribution systems ETS 2.3 electronic trip unit and accessories 100 to 630A DB400166 ETS 2.3 electronic trip unit Protection ........................................................................................... The protection functions can be set using the adjustment dials. Overload protection Long-time protection with an adjustable threshold and fixed tripping delay: b Ir base setting (6-position dial from 0.5 to 1) Short-circuit protection Short-time and instantaneous protection: b short-time protection with an adjustable pick-up and fixed tripping delay b instantaneous protection with fixed pick-up. Protection of the fourth pole On 4-pole circuit breakers, neutral protection is set using a three-position switch to 4P 3D (neutral unprotected), 4P 3D + N/2 (neutral protection at 0.5 In) or 4P 4D (neutral protection at In). Trip units Ratings (A) of circuit breaker Circuit breaker ETS 2.3 In 20 to 70 °C CVS400 F/N CVS630 F/N 400 b - Ir = In x … 0.5...1 adj., 6 settings fixed 90...180 5...7.5 3.2...5.0 Overload protection (Long time) Current setting Time delay (s) (min.…max.) at 1.5 x Ir at 6 x Ir at 7.2 Ir Short-circuit protection (Short time) Pick-up (A) accuracy ± 15 % Time delay (ms) Isd = Ir x … max. resettable time max. break time 2... 10 adj, 8 settings fixed y 40 y 60 Ii = In x … 11 Short-circuit protection (instantaneous) Pick-up (A) Protection of the fourth pole Neutral unprotected Neutral protection at 0.5 In Neutral protection at In Thermal memory 630 b 4P 3D 4P3D + N/2 4P 4D no protection 0.5 x Ir 1 x Ir CVS400 F/N CVS630 F/N Yes Yes Test equipment for ETS electronic trip unit Mini test kit The mini test kit is a portable unit requiring no external power supply, used to check operation of the electronic trip unit and circuit breaker tripping. It connects to the test connector on the front of the circuit breaker. Required power source: five 9 V alkaline batteries (not supplied). Portable test kit The portable test kit is used to check all aspects of the protection functions: b long time protection b short time protection b instantaneous protection b earth-fault protection. Required power source: 110 or 220 V AC, 50/60 Hz. Spare test plug and wiring kit A spare test plug and wiring kit are available for this offer. A-4 Earth-leakage protection Add-on protection againes insulation faults using a Vigi module PB106449 A Vigi module can be added to any three or four-pole CVS100 to 630 circuit breaker to form a Vigi CVS. Circuit breaker with add-on Vigi module (Vigi CVS) b For general characteristics of circuit breakers, see pages A-2 and A-3. b Add-on Vigi modules: Earth-leakage protection is achieved by installing a Vigi module (characteristics and selection criteria on next page) directly on the circuit breaker terminals. It directly actuates the trip unit (magnetic, thermal-magnetic or ETS). Vigi CVS100 to 630 circuit breakers with earth-leakage protection Addition of the Vigi module does not alter circuit-breaker characteristics: b compliance with standards b degree of protection, class II front-face insulation b positive contact indication b electrical characteristics b trip-unit characteristics b installation and connection modes b indication, measurement and control auxiliaries b installation and connection accessories. PB103580-36 Vigi CVS100 to 630 Dimensions and weights Vigi CVS100/160/250 Vigi CVS400/630 Dimensions 105 x 236 x 86 135 x 355 x 110 3-pole W x H x D (mm) 4-pole 140 x 236 x 86 180 x 355 x 110 Weight (kg) 3-pole 2.5 8.8 4-pole 3.2 10.8 Vigi earth-leakage protection modules Compliance with standards b b b b IEC 60947-2, annex B. Decree dated 14 November 1988 (for France). IEC 60755, class A, immunity to DC components up to 6 mA operation down to -25 °C as per VDE 664. Vigi module selection 2 3 4 5 6 DB112147 1 Type Vigi ME Vigi MH Number of poles 3, 4 (1) 3, 4 (1) Vigi MB 3, 4 (1) CVS100 b b - CVS160 b b - CVS250 - b - CVS400 - - b CVS630 - - b adjustable 0.3 0.03 - 0.3 - 1 - 3 - 10 adjustable 0.3 - 1 - 3 - 10 - 30 adjustable Protection characteristics 1 2 3 4 Sensitivity setting Time-delay setting (for selective earth-leakage protection). Lead-seal fixture for controlled access to settings. Test button simulating an earth-fault for regular checks on the tripping function 5 Reset button (reset required after earth-fault tripping). 6 Rating plate Sensitivity In (A) fixed Time delay fixed adjustable Intentional delay (ms) < 40 0 - 60 (2) - 150 (2) - 310 (2) 0 - 60 - 150 - 310 Max. break time (ms) < 40 < 40 < 140 < 300 < 800 < 40 < 140 < 300 < 800 Rated voltage V AC 50/60 Hz 200...440 200... 440 - 440...550 200...440 - 440...550 (1) Vigi 3P modules may also be used on 3P circuit breakers used for two-phase protection. (2) If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting. Operating safety The Vigi module is a user safety device. It must be tested at regular intervals (every 6 months) via the test button. A-5 Ground Fault Protection Functions and characteristics EasyPact CVS 100 to 800A EasyPact CVS Ground Fault Protection is meant for human safety and to prevent fires due to low level f aults resulting from a deterioration of electrical insulation or high resistive faults. Ground Fault Protection should be installed in the following installations b b b b Building housing inflammable or explosive material Line voltage to ground exceeds 150V AC Electrical equipments like welding sets Electrical equipments used in close Proximity of water/other liquids and metallic object b Cable protection when distance between source and load is high Protect electrical distribution network against fire Selection for Ground Fault Protection is based on following: b b b b Current sensitivity required Rated voltage, Rated current and frequency Operation time Detection device and protection device co-ordination Unique Modular Ground Fault (UMGFP) system is suitable for EasyPact CVS / Compact NSX MCCBs n n n n n n Adjustable earth fault sensitivity selection 10 to 60% Adjustable time delay lnst / 0.5 - 3 Sec. System healthiness check through LED indication Individual fault indication for OL, SC, EF when used with Compact NSX (Optional) Individual fault indication for OL/SC, EF when used with EasyPact CVS (Optional) Test facility to check healthiness of earth fault protection system without tripping MCCB n Suitable for 3P3W & 3P4W electrical distribution network Ground Fault Protection relay setting details Relay GFP11 GFP12 GFP13 GFP14 Overload setting Ir selection in RM 32, 40, 50, 63, 80, 100 125, 160, 200, 250 400, 630 800 Sensitivity selection Time delay selection 10 - 60% of In 10 - 60% of In 10 - 60% of In 10 - 60% of In 0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous 0.5 to 3 Sec. /Instantaneous Short circuit setting Overload and short circuit protection E/F Sensitivity Selector Switch Current Selector Switch Ground Fault Protection Test Push Button A-6 Unique system Healthy indication Earth Fault Indication Reset Push Button CT details Sealing Stud Time Delay Selector switch (2 step setting) Motor protection MA instantaneous trip units MA magnetic trip up units for EasyPact CVS100-630A Motor protection to 250 kW DB400006 E26988 Motor protection rating (kW) CVS 100/160/250 CVS 400/630 Breaking capacity (kA rms) 380/415V 1.1...110 18.5...250 B F N 25 36 - 25 36 - 36 50 Circuit breakers with an MA trip unit are combined with a thermal relay and a contactor or a starter. Protection …………………………………………………………………… Magnetic protection (Im) Short-circuit protection with an adjustable pick-up Im that initiates instantaneous tripping if exceeded. b Im = In x ... is set on an adjustment dial in multiples of the rating: v 6 to 14 x In (2.5 to 100 A ratings) v 9 to 14 x In (150 to 220 A ratings) v 6 to 13 x In (320 to 500 A ratings) Protection version CVS100 to 630 circuit breakers, equipped with an MA magnetic trip unit with adjustable thresholds, offer: - short-circuit protection - suitability for isolation. CVS100 to 630 circuit breakers with trip unit are supplied ready-assembled. b 3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D). Motor protection up to 250 kW Motor protection rating (kW) CVS 100/160/250 CVS 400/630 380/415V N 1.1...110 18.5...250 - N - 50 MA trip units Ratings (A) In at 65 °C CVS100 Circuit breaker 2.5 6.3 12.5 25 50 100 150 220 320 500 b b b b b b - - - - CVS160 - - - - - b b - - - CVS250 - - - - - - b b - - CVS400 - - - - - - - - b - CVS630 - - - - - - - - - b Short-circuit protection (magnetic) Pick-up (A) CVS100 CVS160/250 CVS400/630 Im = In x ... setting 6...14 x ln - setting 9...14 x ln - setting 6...13 x ln A-7 Functions and characteristics Introduction Characteristics and performance 100 to 630A PB106447 Common characteristics Rated voltages Insulation voltage (V) Impulse withstand voltage (kV) Operational voltage (V) Suitability for isolation Utilisation category Pollution degree Ui Uimp Ue 690 8 415 yes A 3 AC 50/60 Hz IEC/EN 60947-2 IEC 60664-1 Circuit breakers Performance Electrical characteristics as per IEC 60947-2 Rated current (A) In 40 °C lcu AC 50/60 Hz 220/240 V 380/415 V lcs AC 50/60 Hz 220/240 V 380/415 V Mechanical Electrical 415V Number of poles Breaking capacity levels EasyPact CVS100/160/250 Breaking capacity (kA rms) PB106448 Service breaking capacity (kA rms) Durability (C-O cycles) In/2 In Protection Short-circuit protection Overload/short-circuit protection Earth fault protection Earth-leakage protection Magnetic only Thermal magnetic electronic Micro processor with neutral protection (Off-0.5-1) By UMGFP By Vigi module Installation/connections Dimensions and weights EasyPact CVS400/630 Dimensions (mm) WxHxD Fixed, front connections Weight (kg) Fixed, front connections Connections Connection terminals Pitch Without/With spreaders Large Cu or Al cables Cross-section mm2 * 630 A @ 30°C A-8 3P 4P 3P 4P CVS100 CVS160 CVS250 CVS400 CVS630 100 160 250 400 630 3, 4 B F 3, 4 B F 3, 4 B F 3, 4 F N 3, 4 F N 40 25 40 25 40 25 40 36 40 36 70 36 70 36 70 36 70 50 70 50 40 70 25 36 30000 30000 12000 40 70 25 36 25000 25000 12000 40 70 25 36 20000 20000 10000 40 70 36 50 15000 12000 6000 40 70 36 50 15000 8000 4000 b b b b b b b b b b b b b b b b b b b b* b b b b 105 x 161 x 86 140 x 161 x 86 2.05 2.4 105 x 161 x 86 140 x 161 x 86 2.2 2.6 105 x 161 x 86 140 x 161 x 86 2.4 2.8 140 x 255 x 110 185 x 255 x 110 6.05 7.90 140 x 255 x 110 185 x 255 x 110 6.2 8.13 35/45 mm 35/45 mm 35/45 mm 300 300 300 45/52.5 mm 45/70 mm 4 x 240 45/52.5 mm 45/70 mm 4 x 240 A-9 Functions & Characteristics Functions and characteristics Protection of distribution systems for EasyPact CVS 800 800A EasyPact CVS 800A MCCBs are available in 3P/4P version with 35/50kA breaking performances with Ics = 100% Icu. EasyPact CVS comes with host of features including adjustable overload, short circuit setting, line load reversibility. b Ics=100% Icu. b Adjustable over load setting (0.8 to 1 x In) b Adjustable short circuit setting for individual phase (3.5 to 10 In) b Line load reversibility CVS 800 Overload protection (thermal) Tripping threshold (A) In Adjustable 0.8...1 x In Short-circuit protection (magnetic) Tripping threshold (A) Im EasyPact CVS 800 Adjustable 3.5...10 In Accessories and Auxiliaries b b b b b b Auxiliary contact with 1C/O & 2 C/O options. Alarm contact with 1C/O & 2 C/O options. Shunt trip coil. Under voltage coil. Direct and Extended Rotary Handle. Unique modular ground fault protection for 3 phase 3 wire and 3 phase 4 wire systems. Function and characteristics Protection of distribution system EasyPact CVS 800 A EasyPact CVS Circuit breakers Number of Poles Control/manual/toggle CVS 800 3/4 b b Direct or extended rotary handle Electrical characteristics as per IEC 60947- 2 Rated current(A) Rated insulation voltage(V) Impulse withstand voltage(kV) Rated operational voltage(V) In Ui Uimp Ue 40°C AC 50/60 Hz Icu Ics AC 415V 50/60HZ %Icu mechanical electrical In Type of circuit Breaker Ultimate Breaking Capacity(kA) Service Breaking Capacity (KA) Utilisation category Durability (C-O cycles) F Protection N 50 35 100% A 8000 2500 Thermal Magnetic Overload release setting (A) Adjustable Ir(In x ...) Short Circuit Protection Short Circuit Release setting Earth Fault Protection* 800 690 8 415 Isd (Ir x...) By UMGFP GFP Release setting = 10-60% of In b Centralised 0.8…..1 b 3.5 to 10 (independent adjustment of each phase) b b b Time Delay Setting (0.5 - 3 Sec./Inst.) Additional indication & control auxiliaries Indication Contacts Alarm Contacts 1 C/O 2 C/O 1 C/O 2 C/O 1 C/O each Auxiliary Contacts Alarm - Auxiliary Contacts MX shunt and MN under voltage Release b b b b b b b Installation and Connection Bus Bar Max. Cable Crimped lugs AL/CU (mm)2 width (mm) 40 300*2 Installation Accessories b b Spreaders Phase Barriers Dimensions & Weight Overall dimensions WXHXD Weight(kg) A-10 (mm) (mm) 3 /4Pole 3Pole 4Pole 210 x 274 x 103 280 x 274 x 103 10.3/13.7 Accessories and auxiliaries Overview CVS 100 to 630 Insulation accessories DB400001 Connection Cable connectors Interphase barriers Sealable terminal shields Rear connectors Terminal extensions Cable connectors Electrical auxiliaries Indication contact Voltage release Insulation Monitoring cat.A Control accessories Earth leakage protection (VigiCVS) Direct rotary handle Extended rotary handle Earth fault protection (UMGFP) A-11 Accessories and auxiliaries Functions and characteristics Device installation 100 to 630A Fixed circuit breakers DB400010 DB400012 Mounting on a backplate. Mounting on a Prisma mounting plate. DB400011 Fixed circuit breakers are designed for standard connection using bars or cables with lugs. Bare-cable connectors are available for connection to bare copper or aluminium cables. DB400009 CVS circuit breakers may be installed horizontally, vertically or flat on their back, without derating performance levels. Mounting on rails. Mounting on DIN rail (with adaptor). Front connection DB112169 DB400013 Fixed circuit breakers are designed for standard front connection using bars or cables with lugs. Cable connectors are available for bare cables. Rear connection is also possible. Bars or cables with lugs Standard terminals EasyPact CVS100 to 630 come with terminals comprising snap-in nuts with screws: b EasyPact CVS100: M6 nuts and screws. b EasyPact CVS160/250: M8 nuts and screws b EasyPact CVS400/630: M10 nuts and screws. These terminals may be used for: b direct connection of insulated bars or cables with lugs b terminal extensions. Interphase barriers or terminal shields are recommended. They are mandatory for certain connection accessories (in which case the interphase barriers are provided). Bars When the switchboard configuration has not been tested, insulated bars are mandatory. Insulated bar. DB112170 Maximum size of bars Small lug for copper cables. EasyPact CVS circuit breaker Without spreaders pitch (mm) maximum bar size (mm) With spreaders pitch (mm) maximum bar size (mm) 100/160/250 35 20 x 2 45 32 x 2 400/630 45 32 x 6 52.5 40 x 6 Crimp lugs DB112171 There are two modules of lugs, for aluminium and copper cables. Interphase barriers or long terminal shields must be used with narrow lugs. The lugs are supplied with interphase barriers. Straight terminal extensions. Right-angle terminal extensions EasyPact CVS circuit breaker Copper cables size (mm2) crimping Aluminium cables size (mm2) crimping 100/160/250 400/630 150, 185 240, 300 hexagonal barrels or punching 150, 185 240, 300 hexagonal barrels Terminal extensions DB112177 DB112173 DB112172 Small lug for Al cables. Spreaders. Extensions with anti-rotation ribs can be attached to the standard terminals to provide numerous connection possibilities in little space: b straight terminal extensions b right-angle terminal extensions Spreaders Spreaders may be used to increase the pitch: b CVS100 to 250: the 35 mm pitch can be increased to 45 mm b CVS400/630: the 45 mm pitch can be increased to 52 or 70 mm. Bars, cable lugs or cable connectors can be attached to the ends. Pitch (mm) depending on the type of spreader EasyPact CVS circuit breaker Without spreaders With spreaders A-12 CVS100 to 250 35 45 CVS100 to 630 45 52.5 or 70 Accessories and auxiliaries Bare cables DB112314 DB400014 Connection of devices Bare-cable connectors may be used for both copper and aluminium cables. 1-cable connectors for EasyPact CVS100 to 250 The connectors snap directly on to the device terminals or are secured by clips to right-angle and straight terminal extensions as well as spreaders. 1-cable connectors for EasyPact CVS400 to 630 The connectors are screwed directly to the device terminals. Bare cable. 2-cable connectors for EasyPact CVS100 to 250 and 400/630 The connectors are screwed to device terminals or right-angle terminal extensions. Four positions. EasyPact CVS circuit breaker 100/160 Steel connectors 1.5 to 95 mm2 b Aluminium connectors 25 to 95 mm2 DB111326 2-cable connector for CVS400/630. CVS100 to 250 DB111330 DB400015 1-cable connector for CVS100 to 250 DB112317 DB112315 DB112316 Maximum size of cables depending on the type of connector 250 400 630 2 cables 35 to 240 mm2 b b 35 to 300 mm2 b b b b 120 to 185 mm2 b b 2 cables 50 to 120 mm2 b b CVS400/630. Two lengths. Rear connection Device mounting on a backplate with suitable holes enables rear connection. Bars or cables with lugs Rear connections for bars or cables with lugs are available in two lengths. Bars may be positioned flat, on edge or at 45° angles depending on how the rear connections are positioned. The rear connections are simply fitted to the device connection terminals. All combinations of rear connection lengths and positions are possible on a given device. Escutcheon for toggle without and with access to the trip unit. IP40 escutcheons for fixed devices There are three types of escutcheon with a gasket which are screwed to the door cut-out: b three escutcheons for all control types (toggle, handle or motor mechanism) b a wide model for Vigi modules that can be combined with the above. DB400032 DB400031 DB400030 Escutcheons are an optional feature mounted on the switchboard door. They increase the degree of protection to IP40, IK07. Protection collars maintain the degree of protection, whatever the position of the device (connected, disconnected). Escutcheon for Vigi module. A-13 Accessories and auxiliaries Functions and characteristics Selection of auxiliaries 100 to 630A DB115583 EasyPact CVS100/160/250 Standard Rotary handle OF1 SD OF2 SDE MN / MX SDV All EasyPact CVS100/160/250 circuit breakers have slots for the electrical auxiliaries listed below. 5 indication contacts (see page A-15) b 2 ON/OFF (OF1 and OF2) b 1 trip indication (SD) b 1 fault-trip indication (SDE) b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module. 1 remote-tripping release (see page A-16) b either 1 MN undervoltage release b or 1 MX shunt release. All these auxiliaries can be installed with a rotary handle. The illustration shown (TMD, MA standard) indicates auxiliary possibilities depending on the type of trip unit. DB115590 EasyPact CVS400/630 Standard Rotary handle OF1 OF2 OF3 Reserved MN / MX SD SDE OF4 SDV A-14 All EasyPact CVS400/630 circuit breakers have slots for the electrical auxiliaries listed below. 6 indication contacts (see page A-15) b 4 ON/OFF (OF4) b 1 trip indication (SD) b 1 fault-trip indication (SDE) b 1 earth-fault indication (SDV), when the device is equipped with a Vigi module. 1 remote-tripping release (see page A-16) b either 1 MN undervoltage release b or 1 MX shunt release. All these auxiliaries can be installed with a rotary handle. The illustration shown (TMD, MA and ETS 2.3 standard) indicates auxiliary possibilities depending on the type of trip unit. Accessories and auxiliaries Indication contacts One contact model provides circuit-breaker status indications (OF - SD - SDE - SDV). These common-point changeover contacts provide remote circuit-breaker status information. They can be used for indications, electrical locking, relaying, etc. They comply with the IEC 60947-5 international recommendation. DB125549 Functions Indication contacts. Breaker-status indications, during normal operation or after a fault A single type of contact provides all the different indication functions: b OF (ON/OFF) indicates the position of the circuit breaker contacts b SD (trip indication) indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth fault (Vigi) v operation of a voltage release v operation of the “push to trip” button v disconnection when the device is ON. The SD contact returns to de-energised state when the circuit breaker is reset. b SDE (fault-trip indication) indicates that the circuit breaker has tripped due to: v an overload v a short-circuit v an earth fault (Vigi) b SDV indicates that the circuit breaker has tripped due to an earth fault. It returns de-energised state when the Vigi module is reset. Installation b OF, SD, SDE and SDV functions: a single type of contact provides all these different indication functions, depending on where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker (or the Vigi module for the SDV function). The SDE function on a CVS100 - 630 A equipped with a magnetic, thermal-magnetic or ETS2.3 trip unit requires the SDE adaptor. Electrical characteristics of auxiliary contacts Contacts Standard Types of contacts All Low level OF, SD, SDE, SDV Rated thermal current (A) 6 5 1 mA at 4 V DC Minimum load 100 mA at 24 V DC Utilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14 Operational 24 V current (A) 48 V AC/DC 6 6 6 1 5 3 5 1 AC/DC 6 6 2.5 0.2 5 3 2.5 0.2 AC/DC 6 5 0.6 0.05 5 2.5 0.6 0.05 220/240 V AC 6 4 - - 5 2 - - 250 V DC - - 0.3 0.03 5 - 0.3 0.03 380/440 V AC 6 2 - - 5 1.5 - - 110 V A-15 Accessories and auxiliaries Functions and characteristics Remote tripping 100 to 630A DB125550 MN undervoltage release b This release trips the circuit breaker when the control voltage drops below a tripping threshold b The tripping threshold is between 0.35 and 0.7 times the rated voltage b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated voltage. Characteristics DB115605 MX or MN voltage release. Failsafe opening 0 Possible opening 0.35 0.7 1.1 Un DB115606 Opening conditions of the MN release. Failsafe closing 0 0.85 1.1 Un PB103752-32 DB115607 Closing conditions of the MN release. Delayed trip order 10 12 3 6 Time-delay unit Instantaneous trip order V AC Operating threshold V DC Opening Closing Operating range Consumption (VA or W) Response time (ms) 50/60 Hz: 24 - 48 - 100/130 - 200/240 50 Hz: 380/415 60 Hz: 208/277 12 - 24 - 30 - 48 - 60 - 125 -250 0.35 to 0.7 Un 0.85 Un 0.85 to 1.1 Un Pick-up: 10 - Hold: 5 50 Time-delay unit for an MN release A time delay unit for the MN release eliminates the risk of nuisance tripping due to a transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping. The correspondence between MN releases and time-delay units is shown below. Power supply Unit with fixed delay 200 ms 48 V AC 220 / 240 V AC Unit with adjustable delay y 200 ms 48 - 60 V AC/DC 100 - 130 V AC/DC 220 - 250 V AC/DC Corresponding MN release 48 V DC 250 V DC 48 V DC 125 V DC 250 V DC MX shunt release The MX release opens the circuit breaker via an impulse-type (u 20 ms) or maintained order. Opening conditions D2 When the MX release is supplied, it automatically opens the circuit breaker. Opening is ensured for a voltage U u 0.7 x Un. MN Characteristics D1 MN release with a time-delay unit. Power supply Power supply Wiring diagram for emergency-off function with MN + time-delay unit. V AC V DC Operating range Consumption (VA or W) Response time (ms) 50/60 Hz: 24 - 48 - 100/130 - 200/240 50 Hz: 380/415 60 Hz: 208/277 12 - 24 - 30 - 48 - 60 - 125 -250 0.7 to 1.1 Un Pick-up: 10 50 DB115608 Circuit breaker control by MN or MX Possible opening 0 Failsafe opening 0.7 1.1 Un Opening conditions of the MX release. Note: circuit breaker opening using an MN or MX release must be reserved for safety functions. This type of tripping increases wear on the opening mechanism. Repeated use reduces the mechanical endurance of the circuit breaker by 50 %. A-16 When the circuit breaker has been tripped by an MN or MX release, it must be reset before it can be reclosed. MN or MX tripping takes priority over manual closing. In the presence of a standing trip order, closing of the contacts, even temporary, is not possible. Connection using wires up to 1.5mm2 to integrated terminal blocks. Accessories and auxiliaries Rotary handles PB106453 There are two types of rotary handle: b direct rotary handle b extended rotary handle. Direct rotary handle Standard handle Degree of protection IP40, IK07. The direct rotary handle maintains: b b b b visibility of and access to trip-unit settings suitability for isolation indication of the three positions O (OFF), I (ON) and tripped access to the "push to trip" button. Device locking The rotary handle facilitates circuit-breaker locking. b Padlocking: v standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to 8 mm, not supplied EasyPact CVS with a rotary handle. Extended rotary handle PB106454 Degree of protection IP56, IK08. The extended rotary handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front. It maintains: b visibility of and access to trip-unit settings b suitability for isolation b indication of the three positions O (OFF), I (ON) and tripped. Device and door padlocking PB106455 EasyPact CVS with an extended rotary handle installed at the back of a switchboard, with the keylock option and key. Padlocking locks the circuit-breaker handle and disables door opening: b standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5 to 8 mm, not supplied Parts of the extended rotary handles b A unit that replaces the front cover of the circuit breaker (secured by screws). b An assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontally. b An extension shaft that must be adjusted to the distance. The min/max distance between the back of circuit breaker and door is: v 185…600 mm for EasyPact CVS100 to 250 v 209…600 mm for EasyPact CVS 400/630. Manual source-changeover systems PB106456 An additional accessory interlocks two devices with rotary handles to create a sourcechangeover system. Closing of one device is possible only if the second is open. This function is compatible with direct or extended rotary handles. Up to three padlocks can be used to lock in the OFF or ON position. A-17 Functions and characteristics Accessories and auxiliaries Locks and sealing accessories 100 to 630A DB400025 DB400026 Locks Toggle locking using padlocks and an accessory: Removable device Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied). Certain locking systems require an additional accessory. Fixed device attached to the case. Control device Function Means Required accessories Toggle Lock in OFF position Padlock Lock in OFF or ON Padlock position Direct handle rotaryStandard Lock in b OFF position b OFF or ON position (1) DB400027 Extended rotary handle - Keylock Locking device + keylock Padlock Lock in b OFF position (1) b OFF or ON position with door opening prevented (2) - Lock in OFF position Padlock UL508 control accessory b OFF or ON position (1) Keylock Locking device + keylock (1) Following a simple modification of the mechanism. (2) Unless door locking has been voluntarily disabled. DB400029 Sealing accessories A-18 Rotary handle DB400018 Access to Vigi-module settings DB400019 DB115033 Sealing accessories. DB400017 DB400028 Rotary-handle locking using a keylock. Toggle control Fixed device Padlock inside the switchboard Rotary-handle locking using a padlock or a keylock. Removable device Types of seals Protection cover for settings Protected operations b modification of settings. Installation recommendations EasyPact CVS Installation recommendations Contents Functions and characteristics A-1 Operating conditions and temperature derating B-2 Installation in switchboards Safety clearances and minimum distances Installation example B-3 B-4 Dimensions and connection Additional characteristics Catalogue numbers C-1 D-1 E-1 B-1 Operating conditions and temprature derating Installation recommendations 100 to 630A When thermal-magnetic trip units are used at ambient temperatures other than 40 °C, the Ir pick-up is modified. DB400035 (m) 2000 Altitude derating Altitude does not significantly affect the characteristics of EasyPact CVS circuit breakers up to 2000 m. Above this altitude, it is necessary to take into account the decrease in the dielectric strength and cooling capacity of air. Vibrations CVS devices resist electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 60068-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyds, etc.): b 2 to 13.2 Hz: amplitude ±1 mm b 13.2 to 100 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts. Degree of protection CVS circuit breakers have been tested for degree of protection (IP) and mechanical impact protection (IK). See page A-2. DB115053 Electronic trip units are not affected by variations in temperature. If the trip units are used in hightemperature environments, the ETS setting must nevertheless take into account the temperature limits of the circuit breaker. (A) 110 Settings of CVS100 to 630 equipped with TM-D trip units as a function of the temperature 100 The table indicates the real Ir (A) value for a given rating and temperature. 90 Rat. Temperature (°C) (A) 10 15 20 25 80 35 40 45 50 18.4 18 18 18 17 16.6 16 15.6 25 28.8 28 27.5 27 26.3 25.6 25 24.5 24 32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 40 46 45 44 43 42 41 40 39 50 57.5 56 55 54 53 51 50 63 73 72 70 68 67 65 80 92 90 88 86 84 82 100 114 112 110 107 105 500 125 144 141 138 134 200 10 DB400102 30 16 20 30 40 50 60 70 (°C) Temperature derating curve for CVS100. DB400102 The overload protection is calibrated at 40 °C in the lab. This means that when the ambient temperature is less than or greater than 40 °C, the Ir protection pick-up is slightly modified. To obtain the tripping time for a given temperature: b see the tripping curves for 40 °C (see pages D-2 and D-3) b determine tripping times corresponding to the Ir value (thermal setting on the device), corrected for the ambient temperature as indicated in the tables below. 10 000 5 000 2 000 1 000 55 15.2 14.8 60 65 70 14.5 14 13.8 23.5 23 21 30 29.5 29 28.5 38 37 36 35 33.5 49 47 46 44 43 41 63 61 59 57 55 53 50 80 78 75.5 73 70.7 68 65 102.5 100 97 95 92.0 89 86 83 131 128 125 122 119 116 113 109 106 22 160 184 180 176 172 168 164 160 156 152 148 144 140 136 50 200 230 225 220 215 210 205 200 195 190 185 180 175 170 20 250 288 281 277 269 263 256 250 244 238 231 225 219 213 100 10 5 t(s) 2 TM80D/100D : Im = 8 x In 1 .5 .2 .1 .05 .02 .01 320 364.9 357.8 350.5 343.2 335.6 327.9 320 311.9 303.6 295 400 456.6 447.7 438.6 429.2 419.7 410 390 400 379.3 368.5 357.3 345.8 333.9 500 558.6 549.2 539.7 530.1 520.3 510.2 500 489.6 478.9 468 600 672 587.2 574 660.5 648.9 637 630 612.6 600 286.2 277.1 267.7 456.8 445.4 433.6 560.6 546.8 532.7 518.2 t < 10 ms .005 .002 .001 .5 .7 1 CVS400 and 630 (equipped with ETS2.3 electronic trip unit) 2 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir values. Thermal-protection curve with minimum and maximum Note: For 800A please contact sales office B-2 The table below indicates the maximum long-time (LT) protection setting Ir (A) depending on the ambient temperature. Type of Rating (A) Temperature (°C) device 40 45 50 55 60 65 70 CVS400 Fixed CVS630 Fixed 400 400 400 400 390 380 370 360 630 630 615 600 585 570 550 535 Installation in switchboards Safety clearances and minimum distances General rules When installing a circuit breaker, minimum distances (safety clearances) must be maintained between the device and panels, bars and other protection devices installed nearby. These distances, which depend on the ultimate breaking capacity, are defined by tests carried out in accordance with standard IEC 60947-2. If installation conformity is not checked by type tests, it is also necessary to: b use insulated bars for circuit-breaker connections b segregate the busbars using insulating screens. For CVS100 to 630 devices, terminal shields and interphase barriers are recommended and may be mandatory depending on the operating voltage of the device and type of installation (fixed, withdrawable, etc.). Power connections The table below indicates the rules to be respected for CVS100 to 630 devices to ensure insulation of live parts for fixed devices. CVS100 to 630: rules to be respected to ensure insulation of live parts Fixed, rear connection DB400040 Fixed, front connection DB400039 Type of connection operating voltage Long terminal shields (1) Short terminal shields DB115061 With: y 440 V Interphase barriers DB115060 No insulating accessory DB115059 Possible, recommended or mandatory accessories: type of conductor Insulated bars Extension terminals Cables + crimp lugs Bare cables + connectors Possible Possible Possible Recommended No Mandatory (supplied) Possible (instead of ph. Recommended barriers) Possible for CVS100 to 250 Possible for CVS100 to 250 Possible for CVS100 to 250 No Mandatory (supplied) Possible (instead of ph. barriers) Recommended (1) Long terminal shields provide a degree of protection of IP40 (ingress) and IK07 (mechanical impact). B-3 Installation in switchboards Installation recommendations Installation example 100 to 630A Safety clearance Minimum distance between circuit breaker and front or rear panels F Front panel DB400047 DB400046 Minimum distance between two adjacent circuit breakers A1 B=0 F Note: if F < 8 mm: an insulating screen or long terminal shield is mandatory. Bare or painted sheet metal D1 D2 DB400050 DB400049 DB400048 Minimum distance between circuit breaker and top, bottom or side panels D1 D1 D1 C1 Devices without accessories. Devices with interphase barriers or long terminal shields. Minimum safety clearances for CVS100 to 630 Operating voltage U y 440 V for devices equipped with: b no accessories b interphase barriers b long terminal shields A1 C1 D1 D2 C1 D1 D2 0 0 0 0 0 0 30 0 0 30 0 0 5 5 0 40 0 0 40 0 0 Spacing > 60 mm Spacing y 60 mm DB400051 Clearance (mm) Between Between device and sheet metal devices Painted sheet metal Bare sheet metal Bars F1 Clearances with respect to live bare busbars F1 Minimum clearances for CVS100 to 630 Operating voltage F2 Live busbars. B-4 Clearances with respect to live bare busbars spacing > 60 mm spacing y 60 mm F1 F2 F1 F2 U < 440 V 350 350 80 80 These clearances can be reduced for special installations as long as the configuration is checked by tests. F2 Bars Dimensions and connection EasyPact CVS Dimensions and connection Contents Functions and characteristics Installation recommendations Dimensions and mounting EasyPact CVS100 to 630 Vigi CVS100 to 630 Front-panel accessories EasyPact CVS100 to 630 Front-panel cutouts EasyPact CVS100 to 630 Power connections EasyPact and Vigi CVS100 to 630 Connection of insulated bars or cables with lugs to EasyPact and Vigi CVS100 to 630 Connection of bare cables to EasyPact and Vigi CVS100 to 630 Dimension & installation recommendation EasyPact CVS 800 Electrical wiring diagram EasyPact CVS 3 Phase 3 Wire and 3 Phase 4 Wire operated GFP Additional characteristics Catalogue numbers A-1 B-1 C-2 C-3 C-4 C-5 C-6 C-9 C-10 C-11 C-12 D-1 E-1 C-1 Dimensions and mounting Dimensions and connection EasyPact CVS100 to 630 3P 4P DB400058 DB400057 DB400056 DB400055 Dimensions A4 A3 A2 A A1 X X A X A2 A3 A4 C1 C2 B B1 C3 B B2 Y Y Long terminal shields (also available for CVS400/630 spreaders with 52.5 mm pitch: B1 = 157.5 mm, B2 = 210 mm). Z Mounting CVS100 to 250 CVS400/630 CVS100 to 630 On backplate 3P 3P 4P DB400059 DB111411 Interphase barriers. Short terminal shields. F2 F1 F1 F1 F2 F1 F1 F1 F2 X X E1 F1 F3 E4 E2 DB112067 F1 DB112066 F1 X E3 2 Ø6 ØT(1) Y 4 Ø6 Y 4 Ø6 Y (1) The ØT holes are required for rear connection only. 3P DB400063 4P DB112069 F1 F2 F1 DB112070 3P DB111412 On rails F2 F3 F2 U X E2 X X E1 Y 2 Ø6 Y DB400169 DB400168 On DIN rail with adaptor plate (CVS100 to 250) G4 G5 G3 X G2 G1 Z C-2 4 Ø6 Y 4 Ø6 Dimensions and mounting Vigi CVS100 to 630 3/4P CVS100 to 250 DB400070 DB400068 DB400069 3/4P DB400067 Dimensions CVS400/630 A4 A3 A2 A X A6 A5 X X A8 A7 A9 C1 C2 C3 B B1 B2 Z B B1 B2 Y Y Mounting CVS100 to 250 CVS400/630 CVS100 to 630 On backplate 3P 3P 4P E1 F1 F2 F3 X X E6 F1 F1 DB112079 DB112078 DB400071 DB111420 F1 F1 F2 F1 F1 F1 F2 F1 X E8 E5 E7 ØT(1) Y 6 Ø6 Y 3 Ø6 6 Ø6 Y (1) The ØT holes are required for rear connection only. 3P DB400075 4P F1 DB112081 F1 F2 F3 DB112082 3P DB111421 On rails F2 F2 U E6 X X X E1 E5 3 Ø6 Y Type CVS100/160/250 CVS400/630 Type CVS100/160/250 CVS400/630 A A1 80.5 161 127.5 255 E2 E3 125 70 200 113.5 A2 94 142.5 E4 140 227 A3 A4 145 178.5 200 237 E5 E6 137.5 200 200 300 A5 155.5 227.5 E7 145 213.5 A6 236 355 E8 215 327 A7 169 242.5 F1 35 45 A8 220 300 F2 17.5 22.5 A9 253.5 337 F3 70 90 Y 6 Ø6 B 52.5 70 G1 95 - B1 105 140 G2 75 - Y B2 140 185 G3 13.5 - C1 81 95.5 G4 23 - C2 86 110 G5 17.5 - C3 126 168 ØT 24 32 6 Ø6 E1 62.5 100 U y 32 y 35 C-3 Front-panel accessories Dimensions and connection EasyPact CVS100 to 630 IP40 front-panel escutcheons E21643 E21642 E21641 DB400041 For toggle M2 M3 A1 D1 D2 A2 DB115012 DB115011 DB115010 DB400089 For rotary handle or module and protection collar X A3 X 3.5 6.5 B1 Y DB115020 DB115019 DB115018 DB400097 For Vigi 79 X 64 69 Y 3.5 X 6.5 Type A1 A2 A3 B1 M2 M3 CVS100/160/250 CVS400/630 91 123 114 164 101 151 157 189 115 155 102 142 C-4 Front-panel cutouts EasyPact CVS100 to 630 Bare sheet metal CVS100 to 250 CVS400/630 DB400117 DB400116 DB400115 DB400034 For toggle X X 76 29 Y P3 116 X 41.5 Y R R1 R R1 Z DB400121 DB400120 DB400119 DB400118 For toggle with access to trip unit X 102 54.5 P3 X 175 90 63.5 47.5 127 95 Y Z Y Type P3 R R1 CVS100/160/250 CVS400/630 88 112 14.5 31.5 29 63 Bare sheet metal X CVS100 to 250 CVS400/630 DB400125 DB400124 DB400123 DB400122 For toggle X X X 85.5 148 38 38 14.5 P3 29 Y Z 29 32 Y DB400129 DB400128 DB400127 DB400126 For toggle with access to trip unit X X X 85.5 148 38 38 P3 Z 14.5 29 Y 29 32 Y C-5 Power connections Dimensions and connection EasyPact and Vigi CVS100 to 630 Connection locations B1 DB400135 DB400134 C1 B1 B1 A1 X X A2 A3 Y C2 Z Type A1 CVS100/160 CVS250 CVS400/630 70 140 70 140 113.5 227 A2 B1 C1 C2 Type A1 35 35 45 19.5 21.5 26 19.5 19.5 26 CVS100/160 + Vigi CVS250 + Vigi CVS400/630 + Vigi 70 215 70 215 113.5 327 A3 B1 C1 C2 35 35 45 19.5 21.5 26 21.5 21.5 26 Front connection without accessories CVS400/630 DB400138 DB400137 DB400136 CVS100 to 250 Z Z 10.5 14 70 113.5 X X Cables with lugs/bars Bars/cables with lugs Connection with accessories Long and short rear connectors DB116107 CVS100 to 250 10 DB400137 Z 43 for short RC 88 for long RC ∅8.6 13 18 70 6 ∅20 X DB116108 CVS400/630 50 for short RC 115 for long RC 15 30 ∅13 Z ∅23.2 14 113.5 8 X C-6 Power connections EasyPact and Vigi CVS100 to 630 Connection with accessories (cont.) CVS100 to 250 DB115452 DB115451 DB400138 Bare-cable connectors Z Z 63 22 70 70 DB400139 X X DB115455 DB115454 CVS400/630 Z Z 46.5 14 113.5 113.5 X X Distribution connectors (for CVS100 to 250 only) DB115456 DB115457 X 70 41 (a) Vigi module or CVS250. Z 64.5 66.5 (a) Right-angle terminal extensions (upstream only) Z CVS400/630 37.5 39.5 (b) DB115460 DB400140 DB115459 CVS100 to 250 4 Z 61 8 20.5 34 70 113.5 (b) CVS250. X X DB115462 DB400141 Straight terminal extensions (for CVS100 to 250 only) 4 Z 30 41 70 X C-7 Power connections Dimensions and connection EasyPact and Vigi CVS100 to 630 Connection with accessories (cont.) Spreaders 3P 4P E2 F2 DB400145 E2 DB400144 DB400143 DB400142 CVS100 to 250 E1 E3 E2 E2 E2 C3 F1 X X X Z CVS400/630 Y C4 Y Type C3 C4 E1 E2 E3 F1 F2 CVS100/160 23.5 - 114 45 159 100 11 CVS250 25.5 - 114 45 159 100 11 CVS400/630 - 44 135 170 52.5 70 187.5 240 152.5 15 166 15 X Z C-8 Power connections Direct connection to CVS100 to 630 DB115653 DB400013 Connection of insulated bars or cables with lugs to EasyPact and Vigi CVS100 to 630 I DB115654 Bar. Dimensions Ø 400 Bars L (mm) I (mm) d (mm) e (mm) Ø (mm) L (mm) Ø (mm) d L e Lugs Torque (Nm) (1) Torque (Nm) (2) Ø CVS100 CVS160/250 CVS400/630 y 25 d + 10 y 10 y6 6.5 y 25 6.5 10 5/5 y 25 d + 10 y 10 y6 8.5 y 25 8.5 15 5/5 y 32 d + 15 y 15 3 y e y 10 10.5 y 32 10.5 50 20/11 (1) Tightening torque on the circuit breaker for lugs or bars. (2) Tightening torque on fixed devices for rear connectors. L Lug. Connection with accessories to CVS100 to 250 (IEC 228) Pole pitch Accessories for CVS100 to 250 terminal 35 mm 45 mm Dimensions With spreaders or terminal extensions CVS100 CVS160/250 Bars DB115655 DB112172 Straight extensions Without spreaders With spreaders Ø 400 Tinned copper I Spreaders: separate parts d L L e L (mm) l (mm) d (mm) Ø e (mm) Ø (mm) L (mm) Lugs Ø (mm) Torque (Nm) (1) y 25 20 y I y 25 y 10 y6 6.5 y 25 6.5 10 y 25 20 y I y 25 y 10 y6 8.5 y 25 8.5 15 DB112177 (1) Tightening torque on the circuit breaker for spreaders or terminal extensions. Spreaders and straight, right-angle, 45°, double-L and edgewise terminal extensions are supplied with flexible interphase barriers. Tinned copper Connection with accessories to CVS400 and 630 (IEC 228) Pole pitch Without spreaders Spreaders made up of separate parts for 52.5 and 70 mm pitch Tinned copper With spreaders With terminal extensions L (mm) l (mm) d (mm) e (mm) Ø (mm) y 40 d + 15 y 20 3 y e y 10 12.5 y 32 30 y I y 34 y 15 3 y e y 10 10.5 L (mm) y 40 y 32 Ø (mm) 12.5 10.5 50 50 Bars Ø I Right-angle terminal extensions Ø d L L e Lugs Torque (Nm) (1) (1) Tightening torque on the circuit breaker for spreaders or terminal extensions. Tinned copper To be mounted on upstream side. Spreaders and right-angle, 45° and edgewise terminal extensions are supplied with flexible interphase barriers. DB115658 DB112173 52.5 or 70 mm Dimensions 400 Accessories for CVS100 to 630 45 mm With spreaders DB115655 DB115657 Accessories for CVS400 and 630 Mounting detail: 2 cables with lugs. C-9 Power connections Connection of bare cables to EasyPact and Vigi CVS100 to 630 DB112317 Connection for CVS100 to 250 DB112315 DB400149 Dimensions and connection DB115663 1-cable connector L 2-cable connector 1-cable connector Steel y 160 A Aluminium y 250 A L (mm) 25 25 S (mm2) Cu/Al 1.5 to 95 (1) 25 to 50 70 to 95 120 to 185 150 max. flex. Torque (Nm) 12 20 26 26 2-cable connector S L (mm) 25 or 50 S (mm2) Cu/Al 2 x 50 to 2 x 120 Torque (Nm) 22 (1) For flexible cables from 1.5 to 4 mm2, connection with crimped or self-crimping ferrules. DB111326 DB112316 Connection to CVS400 and 630 DB115663 1-cable connector L 2-cable connector 1-cable connector 2-cable connector L (mm) 30 30 or 60 S (mm2) Cu/Al 35 to 300 rigid 240 max. flex. 2 x 35 to 2 x 240 rigid 240 max. flex. Torque (Nm) 31 31 S Conductor materials and electrodynamic stresses EasyPact CVS circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors (flexible or rigid bars, cables). In the event of a short-circuit, thermal and electrodynamic stresses will be exerted on the conductors. They must therefore be correctly sized and held in place by supports. Electrical connection points on switchgear devices (switch-disconnectors, contactors, circuit breakers, etc.) should not be used for mechanical support. Any partition between upstream and downstream connections of the device must be made of non-magnetic material. C-10 Dimension & installation recommendation EasyPact CVS 800 Direct Rotary handle EasyPact CVS 800 MCB Type A CVS 800 Dimension B 129 114 Panel Depth 'L' C 179 ±1 70 Extended rotary Handle MCB Type A 2-Ø 4.5 CVS 800 Dimension B C 129 114 70 K9 159 240 K10 114 170 CVS 800 F/N 3P 4P CVS 800 F/N 3P Connection with accessories Spreader 4P Rating 800 A Dimn. 't' 8.0 mm Dimensions (mm) Type CVS100/160/200/250 CVS400/630 G26 30 52.5 G27 41 67.5 K8 45 70 C-11 Electrical wiring diagram Dimensions and connection EasyPact CVS 3 Phase 3 Wire and 3 Phase 4 Wire operated GFP EasyPact CVS 100 to 800A Wiring diagram for shunt release operated GFP Wiring diagram for under voltage release operated GFP b Supply to RELAY UNIT & UNDER VOLTAGE RELEASE shall be taken from SUPPLY SIDE of MCCB. b Control Voltage supply to RELAY UNIT shall be taken from LINE SIDE of MCCB. b Supply to SHUNT RELEASE shall be taken form LOAD SIDE of MCCB. Notes: 1. Connections shown in dotted lines shall be made by customer. 2. HRC fises are not in SEIPL’s scope of supply. 3. Remove BOTTOM SIDE SPREADERS (if Fitted) of MCCB before mounting ‘CT’ on MCCB. E/F Sensitivity Selector Switch Current Selector Switch Ground Fault Protection Test Push Button Unique system Healthy indication Earth Fault Indication Reset Push Button CT details Sealing Stud Time Delay Selector switch (2 step setting) 1. To change any setting switch ‘OFF’ the MCCB. Remove protective cover from Relay Module. Replace cover after changing setting. 2. To test E/F relay press test Push Button. E/F relay will operate according to the time delay selection. Keep the Test Push Button pressed till the relay trips (indicated by red lamp). C-12 Additional characteristics EasyPact CVS Additional characteristics Contents Functions and characteristics Installation recommendations Dimensions and connection Tripping curves EasyPact CVS100 to 800A Protection of distribution systems EasyPact CVS100 to 250 Motor protection Current and energy limiting curves Catalogue numbers A-1 B-1 C-1 D-2 D-5 D-6 E-1 D-1 Tripping curves Additional characteristics EasyPact CVS 100 to 800A Protection of distribution systems TM magnetic trip units TM16D/25D TM32D t(s) DB400095 DB400094 10 000 5 000 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 10 5 5 t(s) 2 2 TM16D/25D : Im = 12 x In 1 .5 .5 .2 .2 .1 .05 .1 .05 .02 .01 .02 .01 t < 10 ms .005 .005 .002 .001 .5 .7 1 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 TM32D : Im = 12.5 x In 1 200 300 t < 10 ms 2 I / Ir DB400101 DB400096 2 000 200 300 10 000 5 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 10 5 t(s) 2 TM40D : Im = 12.5 x In 1 .5 5 2 TM63D : Im = 8 x In 1 .5 TM50D : Im = 10 x In .2 .1 .05 .1 .05 .02 .01 .02 .01 t < 10 ms .005 .005 .002 .001 .5 .7 1 .002 .001 .5 .7 1 2 3 4 5 7 10 I / Ir D-2 50 70 100 TM63D 10 000 5 000 .2 20 30 I / Ir TM40D/50D t(s) 3 4 5 7 10 20 30 50 70 100 200 300 t < 10 ms 2 3 4 5 7 10 I / Ir 20 30 50 70 100 200 300 Tripping curves EasyPact CVS 100 to 800A Protection of distribution systems TM magnetic trip units TM125D/160D 10 000 5 000 t(s) DB400103 DB400102 TM80D/100D 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 10 5 t(s) 2 TM80D/100D : Im = 8 x In 1 5 2 .5 .2 .2 .1 .05 .1 .05 .02 .01 TM160D : Im = 8 x In .02 .01 t < 10 ms .005 .002 .001 .5 .7 1 TM125D : Im = 10 x In 1 .5 2 3 4 5 7 10 20 30 50 70 100 .002 .001 .5 .7 1 200 300 I / Ir 10 000 5 000 DB400106 10 000 5 000 DB400104 TM320D/400D 2 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 10 5 t(s) 2 TM200D/250D : Im = 10 x In 1 2 .2 .2 .1 .05 .1 .05 .02 .01 .02 .01 t < 10 ms .005 .005 .002 .001 .5 .7 1 .002 .001 .5 .7 1 I / Ir 20 30 50 70 100 200 300 20 30 50 70 100 TM320D/400D : Im = 5...10 x In 1 .5 3 4 5 7 10 3 4 5 7 10 5 .5 2 2 I / Ir TM200D/250D t(s) t < 10 ms .005 200 300 t < 10 ms 2 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir D-3 Tripping curves Additional characteristics EasyPact CVS 100 to 800A Protection of distribution systems TM500D TM600D DB400108 DB400107 10 000 5 000 2 000 10 000 5 000 2 000 1 000 1 000 500 500 200 200 100 100 50 50 20 20 10 t(s) 10 5 5 t(s) 2 2 TM500D : Im = 5...10 x In 1 .5 TM600D : Im = 4...8 x In 1 .5 .2 .2 .1 .05 .1 .05 .02 .01 .02 .01 t < 10 ms .005 .005 .002 .001 .5 .7 1 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir t < 10 ms 2 3 4 5 7 10 I / Ir ETS 2.3 electronic trip units TM Magnetic Trip Unit 200 - 400A TM800D DB400105 DB400105 315 - 630A 10 000 5 000 2 000 1 000 Ir = 0.5...1 x In 500 200 100 50 20 10 t(s) 5 2 Isd = 2...10 x Ir 1 .5 .2 .1 .05 .02 .01 Reflex tripping : t < 10 ms .005 .002 .001 .5 .7 1 I = 11 x In 2 3 4 5 7 10 I / Ir D-4 20 30 50 70 100 200 300 20 30 50 70 100 200 300 Tripping curves EasyPact CVS100 to 250 Motor protection MA magnetic trip units MA150 and MA220 10 000 5 000 DB115716 DB118546 MA2.5... MA100 10 000 5 000 2 000 2 000 1 000 1 000 500 500 200 200 100 100 Thermal withstand 50 20 10 10 5 t(s) 2 Im = 6 ... 14 x In Im = 9 ... 14 x In (MA100 4P) 1 .5 2 .5 .2 .1 .05 .02 .01 .02 .01 t < 10 ms .005 3 4 5 7 10 20 30 50 70 100 Im = 9 ... 14 x In 1 .1 .05 2 MA150 5 .2 .002 .001 .5 .7 1 MA220 50 20 t(s) Thermal withstand t < 10 ms .005 .002 .001 .5 .7 1 200 300 2 I / Ir 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir Reflex tripping. MA500 10 000 5 000 DB400111 DB400110 MA320 2 000 10 000 5 000 2 000 1 000 1 000 500 500 200 200 100 100 Thermal withstand 50 50 20 20 10 10 5 Thermal withstand 5 t(s) t(s) 2 2 1 1 .5 .5 .2 .2 Im = 6 ...13 x In .1 .05 Im = 6 ...13 x In .1 .05 .02 .01 .02 .01 t < 10 ms .005 .005 .002 .001 .5 .7 1 .002 .001 .5 .7 1 2 3 4 5 7 10 I / In 20 30 50 70 100 200 300 t < 10 ms 2 3 4 5 7 10 20 30 50 70 100 200 300 I / In D-5 Tripping curves Additional characteristics Current and energy limiting curves 100 to 800A The limiting capacity of a circuit breaker is its aptitude to let through a current, during a short-circuit, that is less than the prospective short-circuit current. DB115719 (Isc) Prospective Isc peak Prospective current Ics = 100 % Icu The exceptional limiting capacity of the EasyPact CVS range greatly reduces the forces created by fault currents in devices. The result is a major increase in breaking performance. In particular, the service breaking capacity Ics is equal to 100 % of Icu. The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising the following steps: b break three times consecutively a fault current equal to 100% of Icu b check that the device continues to function normally, that is: v it conducts the rated current without abnormal temperature rise v protection functions perform within the limits specified by the standard v suitability for isolation is not impaired. Longer service life of electrical installations Prospective Isc Current-limiting circuit breakers greatly reduce the negative effects of short-circuits on installations. Limited Isc peak Thermal effects Less temperature rise in conductors, therefore longer service life for cables. Actual current Limited Isc Mechanical effects Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars being deformed or broken. (t) Electromagnetic effects Fewer disturbances for measuring devices located near electrical circuits. 300 The exceptional limiting capacity of the EasyPact CVS range is due to the rotating double-break technique (very rapid natural repulsion of contacts and the appearance of two arc voltages in-series with a very steep wave front). Current and energy limiting curves The limiting capacity of a circuit breaker is expressed by two curves which are a 200 function of the prospective short-circuit current (the current which would flow if no 146 protection devices were installed): 100 b the actual peak current (limited current) 80 b thermal stress (A270 s), i.e. the energy dissipated by the short-circuit in a conductor 60 with a resistance of 1 50Ω. 40 k N CVS630 F 30 Maximum permissible cable stresses CVS400 The table below indicates the maximum permissible thermal stresses for cables F CVS250 20 depending on their insulation, conductor (CuBor Al)CVS100 and their cross-sectional area CVS160 (CSA). CSA values are given in mm2 and thermal stresses in A2s. 10 CSA PVC 1.5 8mm2 7 4 2.97x10 6 Cu 5 4 2 Al PRC Cu 2.5 mm2 4 mm2 6 mm2 10 mm2 8.26x104 2.12x105 4.76x105 1.32x106 5.41x105 3 4 4 4.10x10 6 10 1.39x10 PVC PRC 16 mm2 30 40 50 5 70 100 200 5300 6.56x10 25 mm2 35 mm2 50 mm2 3.31x107 Al CSA 20 2.92x10 5 kA rms 7.52x105 Cu 3.4x106 8.26x106 1.62x107 Al 1.39x106 3.38x106 6.64x106 1.35x107 Cu 4.69x106 1.39x107 2.23x107 4.56x107 Al 10 6 1.93x10 4.70x106 9.23x106 1.88x107 9 5 3 2 Energy-limiting curves 1.41 Current-limiting curves 10 200 3 2 10 146 2 100 80 70 60 50 k As F 30 20 N CVS630 5 10 CVS400 F 6 F B 5 F CVS250 B 3 2 CVS100 CVS160 10 N CVS630 CVS400 CVS250 CVS100 CVS160 5 5 3 4 6 10 20 30 40 50 70 100 kA rms D-6 7 3 2 40 10 8 7 6 5 4 2 8 5 DB116371 DB116369 300 200 300 3 2 2 3 4 6 10 20 30 40 50 70 100 150 200 300 kA rms 1.82x106 Catalogue numbers EasyPact CVS Catalogue numbers Contents Functions and characteristics Installation recommendations Dimensions and connection Additional characteristics A-1 B-1 C-1 D-1 EasyPact CVS100 to 250 E-2 EasyPact CVS400 to 630 E-9 EasyPact CVS 800 E-15 E-1 Catalogue numbers EasyPact CVS100/160/250B/F: complete fixed/FC device (25/36 kA 380/415 V) EasyPact CVS100/160/250B DB400150 With TM-D thermal-magnetic trip unit EasyPact CVS100B (25 kA at 380/415 V) Rating TM16D TM25D TM32D TM40D TM50D TM63D TM80D TM100D EasyPact CVS160B (25 kA at 380/415 V) Rating TM100D TM125D TM160D EasyPact CVS250B (25 kA at 380/415 V) Rating TM160D TM200D TM250D 3P LV510300 LV510301 LV510302 LV510303 LV510304 LV510305 LV510306 LV510307 4P LV510310 LV510311 LV510312 LV510313 LV510314 LV510315 LV510316 LV510317 3P LV516301 LV516302 LV516303 4P LV516311 LV516312 LV516313 3P LV525301 LV525302 LV525303 4P LV525311 LV525312 LV525313 3P LV510330 LV510331 LV510332 LV510333 LV510334 LV510335 LV510336 LV510337 4P LV510340 LV510341 LV510342 LV510343 LV510344 LV510345 LV510346 LV510347 3P LV516331 LV516332 LV516333 4P LV516341 LV516342 LV516343 3P LV525331 LV525332 LV525333 4P LV525341 LV525342 LV525343 EasyPact CVS100/160/250F DB400150 With TM-D thermal-magnetic trip unit EasyPact CVS100F (36 kA at 380/415 V) Rating TM16D TM25D TM32D TM40D TM50D TM63D TM80D TM100D EasyPact CVS160F (36 kA at 380/415 V) Rating TM100D TM125D TM160D EasyPact CVS250F (36 kA at 380/415 V) Rating TM160D TM200D TM250D + Vigi module for insulation monitoring DB112249 Vigi module ME type for CVS/NSX100/160 (200 to 440 V) 3P 4P LV429212 LV429213 MH type for CVS/NSX100/160 (200 to 440 V) LV429210 LV429211 MH type for CVS/NSX250 (200 to 440 V) LV431535 LV431536 MH type for CVS/NSX100/160 (440 to 550 V) LV429215 LV429216 MH type for CVS/NSX250 (440 to 550 V) LV431533 LV431534 Connection for a 4P Vigi on a 3P breaker LV429214 DB112249 Insulation monitoring module 200 to 440 V AC Connection for a 4P insulation monitoring module on a 3P breaker E-2 3P 4P LV429459 LV429460 LV429214 EasyPact CVS100/160/250N: complete fixed/FC device MA magnetic trip unit (50 kA 380/415 V) EasyPact CVS100/160/250F DB400155 With MA magnetic trip unit EasyPact CVS100N (50 kA at 380/415 V) Rating MA2.5 MA6.3 MA12.5 MA25 MA50 MA100 EasyPact CVS160N (50 kA at 380/415 V) Rating MA150 EasyPact CVS250N (50 kA at 380/415 V) Rating MA220 3P LV510450 LV510451 LV510452 LV510453 LV510454 LV510455 3P LV516451 3P LV525442 Ground Fault Protection Ref. 32/40/50/63/80/100 Ref. 125/160/200/250 3 PH 3W GFP11CT13P GFP12CT23P 3 PH 4W GFP11CT14P GFP12CT24P Note: Kindly order one nos. shunt coil along with one Ground Fault Protection E-3 Catalogue numbers Accessories EasyPact CVS100/160/250 Connection accessories (Cu or Al) DB112225 Rear connections 2 short 2 long LV429235 LV429236 DB112226 1 x (1.5 to 95 mm2) ; y 160 A Set of 3 Set of 4 LV429242 LV429243 DB112225 Aluminium connectors 1 x (25 to 95 mm2) ; y 250 A Clips for connectors Set of 3 Set of 4 Set of 3 Set of 4 Set of 10 LV429227 LV429228 LV429259 LV429260 LV429241 Set of 3 Set of 4 LV429218 LV429219 6.35 mm voltage tap for steel or aluminium connectors Set of 10 LV429348 Edgewise terminal extensions (1) Set of 4 LV429309 Right-angle terminal extensions (1) Set of 3 Set of 4 LV429261 LV429262 Straight terminal extensions (1) Set of 3 Set of 4 LV429263 LV429264 Spreaders from 35 to 45 mm pitch (1) 3P 4P LV431563 LV431564 DB112724 DB112227 Steel connectors DB112726 Bare cable connectors 1 x (120 to 185 mm2) ; y 250 A Aluminium connectors for 2 cables (1) 2 x (50 to 120 mm2) ; y 250 A DB112235 DB112233 DB112232 DB112231 Terminal extensions (1) Supplied with 2 or 3 interphase barriers. E-4 Accessories EasyPact CVS100/160/250 LV429252 LV429256 LV429253 LV429257 LV429254 LV429258 Set of 3 Set of 4 Set of 3 Set of 4 LV429504 LV429505 LV429506 LV429507 DB400161 1 short terminal shield for breaker 3P 4P LV429515 LV429516 DB400162 1 long terminal shield for breaker 3P 4P LV429517 LV429518 DB112241 For cable 120 mm2 Interphase barriers for breaker Set of 6 LV429329 2 insulating screens for breaker (45 mm pitch) 3P 4P LV429330 LV429331 DB112237 Set of 3 Set of 4 Set of 3 Set of 4 Set of 3 Set of 4 DB400163 Crimp lugs for copper cable (1) For cable 150 mm2 For cable 185 mm2 Crimp lugs for aluminium cable (1) DB112238 For cable 150 mm2 For cable 185 mm2 Insulation accessories (1) Supplied with 2 or 3 interphase barriers. E-5 Catalogue numbers Accessories EasyPact CVS100/160/250 Electrical auxiliaries DB112254 Auxiliary contacts (changeover) OF or SD or SDE or SDV OF or SD or SDE or SDV low level SDE adaptor, mandatory for trip unit TM, MA DB115631 DB111454 Voltage releases E-6 Voltage 24 V 50/60 Hz 48 V 50/60 Hz 110-130 V 50/60 Hz 220-240 V 50/60 Hz and 208-277 V 60 Hz 380-415 V 50 Hz and 440-480 V 60 Hz DC 12 V 24 V 30 V 48 V 60 V 125 V 250 V MN 48 V 50/60 Hz with fixed time delay Composed of: MN 48 V DC Delay unit 48 V 50/60 Hz MN 220-240 V 50/60 Hz with fixed time delay Composed of: MN 250 V DC Delay unit 220-240 V 50/60 Hz AC 29450 29452 LV429451 MX LV429384 LV429385 LV429386 LV429387 LV429388 LV429382 LV429390 LV429391 LV429392 LV429383 LV429393 LV429394 MN LV429404 LV429405 LV429406 LV429407 LV429408 LV429402 LV429410 LV429411 LV429412 LV429403 LV429413 LV429414 LV429412 LV429426 LV429414 LV429427 Accessories EasyPact CVS100/160/250 Rotary handles DB112259 Direct rotary handle With black handle LV429337 With black handle LV429338 DB112260 Extended rotary handle Locks DB400164 By removable device 29370 DB400165 Toggle locking device for 1 to 3 padlocks By fixed device 29371 DB112263 Locking of rotary handle Keylock adaptor (keylock not included) Keylock (keylock adaptor not included) Ronis 1351B.500 Profalux KS5 B24 D4Z LV429344 41940 42888 E-7 Catalogue numbers Accessories EasyPact CVS100/160/250 Interlocking DB111486 With toggles 29354 DB111487 Mechanical interlocking for circuit breakers With rotary handles LV429369 Mechanical interlocking for circuit breakers DB112268 Keylock kit (keylock not included) (1) 1 set of 2 keylocks (1 key only, keylock kit not included) Ronis 1351B.500 Profalux KS5 B24 D4Z LV429344 41950 42878 Installation accessories E21641 E21641 Front-panel escutcheons IP40 toogle escutcheon (small cut-out) IP40 escutcheon for Rotary handle IP40 escutcheon for Vigi module 29315 LV429317 LV429316 Bag of accessories LV429375 1 adaptor LV429305 10 toggle extensions Bag of screws 12 snap-in nuts (fixed/FC) LV429313 LV429312 LV510100 LV516060 LV429226 IP40 DB115615 Lead-sealing accessories DB112739 Din rail adaptor E18624 Spare parts 1 set of 10 identification labels (1) For only 1 device. E-8 M6 for CVS100B/F M8 for CVS160/250B/F CVS400/630: complete fixed/FC device EasyPact CVS400/630F/N EasyPact CVS400/630F With TM-D thermal-magnetic trip unit DB400008 EasyPact CVS400F (36 kA at 380/415 V) Rating TM320D TM400D EasyPact CVS630F (36 kA at 380/415 V) Rating TM500D TM600D 3P LV540305 LV540306 4P LV540308 LV540309 3P LV563305 LV563306 4P LV563308 LV563309 3P LV540315 LV540316 4P LV540318 LV540319 3P LV563315 LV563316 4P LV563318 LV563319 EasyPact CVS400/630N With TM-D thermal-magnetic trip unit DB400008 EasyPact CVS400N (50 kA at 380/415 V) Rating TM320D TM400D EasyPact CVS630N (50 kA at 380/415 V) Rating TM500D TM600D EasyPact CVS400/630N DB400020 With MA magnetic trip unit EasyPact CVS400N (50 kA at 380/415 V) Rating MA320 EasyPact CVS630N (50 kA at 380/415 V) Rating MA500 3P LV540552 LV563552 6500 3000 6000 5500 3500 4000 5000 4500 EasyPact CVS400/630F DB400021 ETS 2.3 electronic trip unit (protection) EasyPact CVS400F (36 kA at 380/415 V) EasyPact CVS630F (36 kA at 380/415 V) 5 6 4 565 3P LV540505 LV563505 4P LV540506 LV563506 400 A 630 A 3P LV540510 LV563510 4P LV540511 LV563511 7 8 3 505 400 A 630 A 10 2 630 440 370 315 EasyPact CVS400/630N DB400021 ETS 2.3 electronic trip unit (protection) EasyPact CVS400N (50 kA at 380/415 V) EasyPact CVS630N (50 kA at 380/415 V) 5 4 3 505 565 6 7 8 10 2 630 440 370 315 E-9 Catalogue numbers CVS400/630: complete fixed/FC device EasyPact CVS400/630N (36 kA 380/415 V) + Vigi module or insulation monitoring module DB111464 Vigi module Type MB 3P 4P 200 to 440 V LV432455 LV432456 440 to 550 V LV432453 LV432454 Connection for a 4P Vigi on a 3P breaker LV432457 DB111464 Insulation monitoring module 200 to 440 V AC 3P 4P LV432659 LV432660 Connection for a 4P insulation monitoring module on a 3P breaker LV432457 Ref. 400/630 3 PH 3W GFP13CT33P 3 PH 4W GFP13CT34P Note: Kindly order one nos. shunt coil along with one Ground Fault Protection E-10 Accessories EasyPact CVS400/630 Connection accessories (Cu or Al) DB112225 Rear connections 2 short 2 long LV432475 LV432476 E22040 Aluminium connector 1x (35 to 300 mm2) Set of 3 Set of 4 LV432479 LV432480 E22041 Cable connectors (1) Aluminium connector 2x (35 to 300 mm2) Set of 3 Set of 4 LV432481 LV432482 Voltage plug for aluminium connector 1 or 2 cables Set of 10 LV429348 Right-angle terminal extension Set of 3 Set of 4 LV432484 LV432485 Edgewise terminal extensions Set of 3 Set of 4 LV432486 LV432487 E21012 E21276 Terminal extension (1) Spreaders 52.5 mm 3P 4P 70 mm 3P 4P LV432490 LV432491 32492 32493 E18602 Crimp lugs for copper cable (1) For cable 240 mm2 For cable 300 mm2 Set of 3 Set of 4 Set of 3 Set of 4 LV432500 LV432501 LV432502 LV432503 Set of 3 Set of 4 Set of 3 Set of 4 LV432504 LV432505 LV432506 LV432507 3P 4P 3P 4P Set of 6 52,5 mm 3P 4P 70 mm 3P 4P LV432591 LV432592 LV432593 LV432594 LV432570 LV432595 LV432596 LV432578 LV432579 Supplied with 2 (or 3) interphase barriers E30908 Crimp lugs for aluminium cable (1) For cable 240 mm2 For cable 300 mm2 Supplied with 2 (or 3) interphase barriers E18606 E18618 Insulation accessories Short terminal shield, 45 mm (1 piece) Long terminal shield, 45 mm (1 piece) Interphase barriers 2 insulating screens (70 mm pitch) E-11 Catalogue numbers Accessories EasyPact CVS400/630 Electrical auxiliaries E18608 Auxiliary contacts (changeover) E18609 Voltage releases E-12 OF or SD or SDE or SDV OF or SD or SDE or SDV low level SDE adaptor mandatory for trip unit TM, MA and ETS2.3 Voltage 24 V 50/60 Hz 48 V 50/60 Hz 110-130 V 50/60 Hz 220-240 V 50/60 Hz and 208-277 V 60 Hz 380-415 V 50 Hz and 440-480 V 60 Hz DC Voltage 12 V 24 V 30 V 48 V 60 V 125 V 250 V MN 48 V 50/60 Hz with fixed time delay Composed of: MN 48 V DC Delay unit 48 V 50/60 Hz MN 220-240 V 50/60 Hz with fixed time delay Composed of: MN 250 V DC Delay unit 220-240 V 50/60 Hz AC 29450 29452 LV540050 MX LV429384 LV429385 LV429386 LV429387 LV429388 MN LV429404 LV429405 LV429406 LV429407 LV429408 LV429382 LV429390 LV429391 LV429392 LV429383 LV429393 LV429394 LV429402 LV429410 LV429411 LV429412 LV429403 LV429413 LV429414 LV429412 LV429426 LV429414 LV429427 Accessories EasyPact CVS400/630 Rotary handle E18611 Direct rotary handle Standard black handle LV432597 Standard extended rotary handle LV432598 E18612 Extended rotary handle Locks E18621 By removable device 29370 E18613 Toggle locking device for 1 to 3 padlocks By fixed device 32631 E18620 Locking of the rotary handle Keylock adaptor (keylock not included) Keylock (keylock adaptor not included) Ronis 1351B.500 Profalux KS5 B24 D4Z LV432604 41940 42888 E-13 Catalogue numbers Accessories EasyPact CVS400/630 Interlocking E21288 With toggles 32614 E18780 Mechanical interlocking for circuit breakers With rotary handles LV432621 E26766 Interlocking with key (2 keylocks/1 key) for rotary handles Keylock kit (keylock not included) (1) 1 set of 2 keylocks (1 key only, keylock kit not included) LV432604 Ronis 1351B.500 Profalux KS5 B24 D4Z 41950 42878 (1) for only 1 device Installation accessories E21641 Front-panel escutcheons IP40 Toggle escutcheon (small cut-out) 32556 IP40 escutcheon for rotary handle LV432558 IP40 escutcheon for Vigi module LV429316 Lead-sealing accessories LV429375 Spare parts Toggle extension LV432553 Bag of screws LV432552 1 set of 10 identification labels LV429226 E21290 Mini test kit for STR trip units 43362 E36271 Front-panel escutcheons Portable test kit for STR trip units 34547 Spare test plug for portable test kit 34547 34503 Wiring kit (spare part) 34546 Test Test kits E-14 EasyPact CVS MCCBs and accessories catalogue nos. for 800A EasyPact CVS 800 With TM-D thermal -magnetic trip unit EasyPact CVS 800 ( 35kA at 380/415 V) Rating TM800D EasyPact CVS 800 ( 50kA at 380/415 V) Rating TM800D 3P LV580300 4P LV580301 3P LV580302 4P LV580303 Auxiliary contacts ON/OFF/Trip (change - over) Ref. Auxilary Contact 1 C/O LV580075 Auxilary Contact 2 C/O LV580076 Alarm Contact 1 C/O LV580077 Alarm Contact 2 C/O LV580078 Alarm Auxilary Contact LV580079 Shunt/Under voltage coil Shunt/Under voltage AC 50Hz DC Ref. Shunt (MX) Ref. Under Voltage (MN) 110-130 V LV580060 LV580070 220-240 V LV580061 LV580071 380-415 V LV580062 LV580072 440 V LV580063 voltage Reference 24 V LV580064 48 V LV580065 110 V LV580066 220 V LV580067 Rotary handles Direct rotary handles Ref. LV580080 Extended rotary handle Ref. LV580081 Ground Fault Protection Ground Fault Relay + CT Ref. 3 Phase 3 Wire GFP14CT43P 3 Phase 4 Wire GFP14CT44P Note: Kindly order one nos. shunt coil along with one Ground Fault Protection Order one auxilliary contact alongwith shunt coil for CVS800. E-15 Make the most of your energy For more information visit our website at: www.schneider-electric.co.in Schneider Electric India Pvt. Ltd. (A 100% subsidiary of Schneider Electric Industries SAS) Corporate office : 9th Floor, DLF Building No.10, Tower C, DLF Cyber City, Phase II, Gurgaon - 122002, Haryana, Tel: 0124 3940400, Fax: 0124 4222036 Customer Care Centre : Toll-free numbers: 1800 180 1707, 1800 103 0011, General number: 0124 4222040, Email: in-care@schneider-electric.com