B4-208 21, rue d'Artois, F-75008 Paris http://www.cigre.org Session 2004 © CIGRÉ System Benefits derived from the 500MW Back to Back HVDC scheme at Sasaram, India R N Nayak1, D Kumar1, B N Kayibabu3*, R Gulati2, M H Baker3 1 PowerGrid Corporation of India Ltd (India) 2 AREVA T&D (India) 3 AREVA T&D Power Electronic Activities (UK) Abstract - The paper describes the Sasaram HVDC back-to-back scheme which connects the northern and eastern electrical regions in India. Reactive power and AC voltage support, overload control, frequency control and power modulation are among the functions available from this scheme to support the two AC systems. Keywords- HVDC, Modulation, Interconnection, Frequency control. SASARAM EAST SASARAM N ORTH 400kV 400kV 507.4MW 205kV 112Mvar Double Frequency 112Mvar Double Frequency 112Mvar Double Frequency * 112Mvar Double Frequency Figure 1: 112Mvar Double Frequency BIHARSHARIFF BIHARSHARIFF LINE 1 LINE 2 112Mvar Double Frequency 112Mvar Double Frequency 57.1Mvar Reactor 112Mvar Double Frequency 57.1Mvar Reactor 57.1Mvar Reactor ALLAHABAD LINE 57.1Mvar Reactor SARNATH LINE Simplified Single Line Diagram bruno.kayibabu@areva-td.com 1 SCHEME DESCRIPTION The Sasaram Back-to-Back HVDC transmission scheme links the northern and eastern 400kV AC networks in India, each of which terminates in a breaker-and-a-half busbar on the Sasaram site. One 400kV line to Allahabad and one 400kV line to Sarnath form the points of connection to the northern network and two 400kV lines to Biharshariff form the connection point to the eastern network, as shown in Figure 1. A bypass link is provided via the two filter busbars, whereby the two AC networks can be connected together if required. The continuous rating of the scheme at maximum ambient temperature is 500 MW. 550MW can be carried for up to 2 hours, or 667 MW for up to 5 seconds. During low ambient temperature, the continuous capability increases to a maximum of 650 MW. The thyristor valves are rated for 205kV, each valve containing 50 thyristors rated 5.2kV. The converter transformers are of single phase, 3 winding type, and are rated for 234MVA each. The thermal capacity of the equipment is monitored continuously and utilised to achieve these power transfers, starting from any steady state operating condition. Currents greater than the steady state maxima are employed during the time required to reposition the converter transformer tap-changer. There is no DC reactor1. Discontinuous current operation may occur for brief periods (during disturbances), but not for long enough to dictate the design of the on-valve electronics, which are well able to provide the necessary additional firing pulses to maintain conduction for short times. Multiple Pulse Resistor protection (MPRP) is provided to prevent the damping resistors of BOD fired levels in the thyristor valves from experiencing thermal overload under these rare events. The settings of this protection depend on initial conditions and the number of pulses per cycle experienced by the thyristor valves. These settings are within the withstand capabilities of the thyristor valve components, which have thermal time-constants sufficiently long to accommodate this operating condition. Valve hall fault currents are limited, mainly by the converter transformer reactance, to values for which records of valve proving tests are already available. To protect the converter equipment from exposure to externally applied overvoltage, the switchyard is protected from direct lightning strokes by shielding, and the voltage between the terminals of all major equipment such as converter transformers is limited by the presence of gapless zinc oxide surge arresters. To protect the environment from the action of the converter station, the screened valve hall is treated as a "containment" for high frequency noise generated by converter switching. The converter transformer 400kV bushings are connected to the main busbars via high frequency filters, which limit the exposure of the 400kV network to the effects of converter-generated interference in the power line carrier and higher frequency ranges. CONTROL SYSTEM AND OPERATIONAL FACILITIES The Sasaram HVDC back-to-back scheme uses ALSTOM T&D’s latest state-of-the-art fully digital controller, which is fully redundant, the dual lanes being based on VME technology using DSPs for fast data acquisition and processing and Pentium processors for general control. The HVDC control system is responsible for the operation of the main scheme equipment (thyristor valves, transformer tapchangers and breakers for filters and shunt reactors). It ensures that the equipment is operated within its limits to achieve the desired power transfer within the specified control parameters. It is also responsible for the start up and shutdown sequences of the scheme. 2 The operator interface is provided by an integrated and duplicated SCADA system and a control mimic, which allow the station operator to apply station level commands to the control system and to observe salient system conditions. This allows the operator to initiate start or stop sequences, request power demands and amend operating conditions (e.g. voltage or reactive power exchange target). The primary interface is a control mimic situated in the control room. In addition SCADA workstations are installed which provide a back-up to the mimic and data logging facilities. The SCADA system also allows some operational functions to be carried out remotely via telecommunications links to either of the two Regions load despatch centres. Each lane contains a set of control system equipment and two redundant sets of pole protection equipment, thus providing quadruplicate protection of the key functions. Although the protection functions are grouped in with the lane concept, they are physically and electrically separated from the equipment associated with the control system. The primary outputs from the control and protection functions within each lane are a Firing Word and Thermal Word (temperature information), which are connected optically to the Valve-based Electronics (VBE). VBE consists of two decoders/drivers and up to 18 transceiver cards. The VBE decoders/drivers operate as a duplicate system. Both VBE decoders/drivers receive both Firing and Thermal Words. Only one set of lane firing and thermal words are used, determined by the Lane Select signals from the Changeover Unit. Both VBE decoders/drivers issue firing commands to the appropriate thyristor valves. The firing commands from the VBE decoders/drivers are put in parallel through an OR gate before being issued to the valves via the transceiver cards. Therefore, in the event of a VBE decoder/driver failure an alarm is issued but scheme operation can continue with the remaining single channel decoder/driver, until the next normally scheduled shut down. Since there are two converters, a rectifier and an inverter, and most control functions are specific to an individual converter on one side of the scheme. Separate Converter Control and Protection (CCP) functions are provided for each converter. Main Control System Functions Station Control is responsible for controlling the influence of the scheme on each AC system. Such control features are station power transfer, system voltage, system frequency, and reactive power exchange. Sub-synchronous damping is included as a secondary control function. Detailed functions of pole and phase controls are as earlier described for similar schemes 2,3,4 and robust methods are used5. DC Protection independently oversees the system and ensures equipment safety. Within each CCP lane there are two parallel DC protection systems with the same functionality and both are always active. If either system detects a condition where equipment integrity may be at risk, protective actions are performed. Ultimately, a protective action can result in a converter block and a main breaker trip. Valve Base Electronics (VBE) contains the functions of firing pulse encoding, optical transmission of firing information to the valves, optical reception of valve monitoring information, and decoding of the monitoring information (databack). VBE receives the firing information (“firing word”) from Phase Control in both CCP lanes but only uses the information from the active control lane. VBE also receives the thyristor junction temperature information from Thermal Model in CCP. Databack information from both decoders is sent to the active CCP lane for thyristor level fault monitoring. 3 BENEFITS TO THE AC NETWORKS The Sasaram HVDC link provides an asynchronous link between the two systems to enable power to be exchanged at will in a reliable and controlled manner. Although both AC networks to which the Sasaram HVDC back-to-back link is connected operate at the same frequency, they are not always in synchronism. However synchronised operation is possible with limited power transfer capability and security between the two. Apart from this traditional capability of HVDC links, the Sasaram HVDC back-to-back scheme incorporates a number of features which enhance and reinforce the networks to which it is connected. These are summarised below. Reactive Power and AC Voltage Support The link is designed to provide extra reactive power capability to support both networks when the need arises. This reactive power capability allows for the minimum number of AC filters required to meet the harmonic performance and is dependent on the transmitted power as shown in Figure 2 below. This capability can also be used to control the network voltage. 500 Reactive Power Capability (MVAr) (Power into AC System) 400 300 200 100 0 0 20 40 60 80 100 -100 -200 -300 -400 Transmitted Power (%) Maximum Figure 2: Minimum Station Reactive Power Capability The minimum continuous power for the Sasaram scheme is 10% of the rated power. Below this level the converter is not available for the control of reactive power and therefore the capability of the station is purely determined by the sizes of the reactive power elements (absorption capability of 114MVAr, generation capability up to 448MVAr). The AC filters for Sasaram have been designed such that only two filters are required to meet the reactive power requirements over the full range of the transmitted power. Therefore at low power levels, the converter needs to absorb extra reactive power if the target of the reactive power exchange with the system is low or negative. For power levels below approximately 60% of rated power, the reactive power absorption capability of the converter station is about 100MVAr. Above this, the absorption capability increases with increased transmitted power. This capability is achieved by operating the converter with higher control 4 angle and low direct voltage, maintaining the ordered power by increasing the direct current. The limiting factors being the valve surge arrester PCAV (peak continuous applied voltage), harmonics injected into the system and the thermal capability of the thyristor valves. The Reactive Power Controller (RPC) incorporated in the HVDC control system can operate in one of the two main control modes: Reactive power exchange mode (RPEM) or AC voltage control mode (ACVCM). Under RPEM, the operator selects a reactive power exchange target and the RPC will switch the reactive power elements (ac filters and shunt reactors) as necessary to ensure that the reactive power exchange with the network is within set limits, which are determined by the target value. Generally this requires switching of reactive power elements. However when the target is low, the minimum number of filters is reached and all available shunt reactors are energised, the converter is used to absorb the surplus, by operating at reduced direct voltage. Under ACVCM, the RPC controls the AC voltage to within a range around a target value selected by the operator, subject to the inherent capability of the converter equipment, by also using the reactive power elements and the converters as necessary. ACVCM is only available on one side at any time with the other side normally operating in RPEM so that tight voltage control using the converter firing angle control can be targeted at the priority Region, normally the weaker region. Manual control of reactive power elements is possible but the controller will automatically ensure that the minimum number of filters that are required for harmonic performance remain energised. Both these control features are available even when the converters are not transmitting any real power. Therefore the converter station can be used as a pure reactive power or AC voltage controller even when the converters are shut down. If the AC voltage passes the steady state limits, the RPC will act automatically, regardless of which control mode it is in, to minimise the voltage excursion by switching reactive power elements or using the converters as necessary. The RPC overvoltage control is co-ordinated with the busbar overvoltage protection and ensures that control actions are taken first. Power Order (out of ac system) Power Order (into ac system) . Po Po fo-'f fo fo 'f Rectifier Figure 3: Frequency f o -'f fo f o 'f Frequency Inverter Frequency Control Characteristics 5 Frequency Control The HVDC control system for Sasaram incorporates a frequency control function which is always active in the background. The operator can set a target frequency (fo), the control deadband (±∆f) and frequency slopes as shown in Figure 3. The converter station is normally in power control where the power order (Po) is set by the operator. If the frequency on one side of the scheme passes the limits determined by the frequency target and the control deadband, then the scheme will automatically go into frequency control The frequency slope allows the operator to apply a droop characteristic to the HVDC link similar to that exhibited by the generators within the AC system. The frequency slope is defined as the change in frequency corresponding to 1pu change in power. Thus, the variations in frequency of the system will give rise to corresponding changes in the power transfer through the link, thereby contributing to the power generation in the AC system. Power Modulation Generator Rotor Angle (degrees) 100 80 60 40 20 0 0 1 2 3 4 5 6 Time (s) 7 8 9 10 4 5 6 Time (s) 7 8 9 10 Generator Real Power (MW) 500 400 300 200 100 0 0 1 2 3 Figure 4: System Recovery without DC Power Modulation Rotor angles of generators in the North system (upper two traces) and the East system (lower traces) are shown to have little or no effective damping when there is no modulation applied. 6 The power modulation control is available within the HVDC control system and can be selected by the operator to damp low frequency power swings within one or both networks. Parameters are determined by system studies. Power Modulation operates through the measurement of the changes in absolute phase angle of the connected network busbar voltages. It produces an incremental change to the station power order corresponding to the changes in the voltage phase angle in a sense to correct the changes. The contributions arising from any power swings within both AC networks are summed to achieve optimum damping. Figures 4 and 5 give the post-fault oscillations after two similar fault events near the eastern side of the link without and with modulation applied. Generator Rotor Angle (degrees) 100 80 60 40 20 0 0 1 2 3 4 5 6 7 8 Time (s) 9 10 Generator Real Power (MW) 500 400 300 200 100 0 0 1 2 3 4 5 6 7 8 Time (s) 9 10 Figure 5: System Recovery with DC Power Modulation Damping is introduced and the oscillations have faded within 4 to 6 seconds. Overload Control The control system includes an overload controller, which works out continuously the steady state and short term overload capabilities of the converter station and makes this information available to the operator and automatic controls through the mimic panel and the SCADA. The overload capability of the scheme depends on many factors including the ambient temperature, the availability of the redundant cooling, the loading history etc. This overload capability can be utilised to support any demand by either AC system. 7 CONCLUSIONS The connection of the northern and eastern electrical networks in India using the Sasaram HVDC back-to-back link allows secure and controlled transfer of high levels of power. Furthermore, the Sasaram link includes features designed to support the connected AC systems during steady state and transient conditions. These features include reactive power/AC voltage control, overload control, frequency control and power modulation. Power Modulation minimises power swings following clearance of major disturbance in the AC systems. ACKNOWLEDGEMENT The authors wish to thank both PowerGrid Corporation of India Ltd and AREVA T&D for permission to publish this paper and they wish to record that the views expressed herein are their own and do not necessarily reflect those of the management of either company. REFERENCES [1] [2] [3] [4] [5] R P Burgess, R Kothari, Design features of the Back-to-back HVDC converter connecting the Western and Eastern Canadian systems (IEEE paper 89 SM 793-1 PWRD, July 1989). B A Rowe, N M Kirby, H K Yu, Control system design at Chandrapur Back-to-back HVDC station (CIGRE Colloquium on HVDC and FACTS, Montreal September 1995). B R Andersen, D R Monkhouse, R S Whitehouse, J D G Williams, V K Prasher, D Kumar, Commissioning the 1000 MW back-to-back HVDC link at Chandrapur, India, (CIGRE Paper 14-114, Paris 1998). K M Abbott, M Aten, Two HVDC schemes in close proximity; a coordination study (CIGRE paper 14-109, Paris, 2000). M Aten, H Werner, Robust multivariable control design for HVDC back to back schemes (Proc. IEE Generation Transmission and Distribution, Vol 150, No 6, November 2003). 8