Transformers Faraday’s Law of Induction 60:1 30:1 26:1 15:1 7200 V 120 V 240 V 277 v 480 v • The only relationship between the primary and secondary winding is the ratio and polarity. • Either winding can be left ungrounded, or grounded at any point without affecting the grounding or the voltage of the other winding. Transformers can be interconnected together in a variety of ways on both the primary and secondary sides to get a variety of three phase secondary voltages. A Phase Phase BBPhase C Phase A Phase B Phase C Phase A Phase B Phase C Phase Distribution Systems Typical Substation Transformer A BCN 7200V 7200V 7200V 24 Multi-Grounded Wye Distribution – Most common Type Neutral – Phase Voltage 7200V and 14,400V most common Delta Distribution System Various Transformer Connections May Be Used On Multi-Grounded Distribution System. Four Wire Multi-Grounded System Allowable Transformer Connections • Ungrounded Wye Primary Transformer Bank • Grounded Wye Primary Transformer Bank • Delta Primary Transformer Bank • Open Wye (Primary) – Open Delta (Secondary) Transformer Bank Grounded Wye Ungrounded Wye Transformer Transformer 4 Wire Multigrounded Wye Ungrounded – Delta Transformer 4 Wire Wye Multigrounded Wye Ungrounded Wye – Delta Transformer 4 Open Wire Multigrounded Wye Primary Phase Grounded Wye –Delta Transformer 4 Wire Multigrounded Wye Grounding Bank 4 Wire Multigrounded Wye Delta Connected Transformer 4 Wire Multigrounded Wye Delta Connected Transformer Open Wye-Open Delta Transformer 4 Wire Multigrounded Wye Bank The secondary (low voltage) side of the three phase banks can be interconnected in a variety of manners, independently of the connection on the primary (high voltage) side. Probability of Ferroresonance From Westinghouse Distribution Transformer Guide. Intended to examine the condition of the distribution primary neutral and the farm grounding system by measuring the resistance of the farm grounding system and primary neutral. It also measures the cow contact voltage in response to the primary neutral voltage. Inject a current into the neutral system, measure the voltage rise, measure the current into the farm and the primary, and determine the resistance of each with the formula R=V/I LOAD BOX CURRENT + RPRI REMOTE Vp _ RFARM One Bushing Single Phase Transformer Load Box 3 Phase Delta - Delta 120/240 Volt Load Box Load Box 3 Phase Floating Wye - Delta 120/240 Volt (4 wire) Load Box Load Box 3 Phase Delta - Grd Wye 120/208 Volt Load Box Load Box 3 Phase Grd Wye - Grd Wye 120/208 Volt Load Box Load Box 2 Phase Open Wye - Open Delta 120/240 Volt (4w) Load Box Load Box 2 Phase Open Wye - Open Delta 240 Volt (3w) Load Box Load Box Important Considerations are: • A balanced three phase load on any system using three transformers will NOT cause any neutral current in the primary • If the transformer bank has no primary winding connection to the primary neutral, the load (at the farm) CAN NOT cause a primary neutral current. • On most systems, with the exception of open wye/open delta connection, a balanced three phase load box will do nothing to load up the primary neutral. • Rf = Δ Vs / Δ Isec(farm) • Rp = Δ Vp / Δ Ip ? • Rt = Δ Vp / Δ Itotal ? • K = Vcc (hi) / Vs(hi) x 100 • ΔCR = (IPrimary Neutral / ITotal)x 100 ? Rupstream Rdownstream LOAD BOX CURRENT + RPRI REMOTE Vp _ RFARM • Δ ITotal = Δ Iload box /transformer ratio • Δ Inet = Δ I sec(farm) • Δ Ipri neutral = Δ Itotal - Δ Inet OR Δ Ipri neutral = Δ Ipri n upstream +/- Δ Ipri n downstream • Rt = Δ Vp / Δ Itotal • Rf = Δ Vs / Δ Isec(farm) • Rp = Δ Vp / Δ Ipneutral • K = Vcc (hi) / Vs(hi) x 100 • ΔCR = (IPrimary Neutral / ITotal)x 100 OR Rp = Parallel Combination of Δ Vp / Δ Ipneutral In Each Direction I(net) LOAD BOX CURRENT + RPRI REMOTE Vp _ RFARM • Δ ITotal = Iload box /xfrmr ratio • Δ Inet = Δ I sec(farm) • Δ Ipri n = Δ Itotal - Δ Isec(farm) 5 • Rt = Δ Vtotal / Δ Ipri • Rf = Δ Vs / Δ Isec(farm) • Rp = Δ Vp / Δ Ipneutral • K = Vcc (hi) / Vs(hi) x 100 • ΔCR = (IPrimary Neutral / IPhase)x 100 Itotal Ifarm A Phase B Phase C Phase Single phase 20A 20A Substation 90 3 Wire Ungrounded Delta