Medium Voltage Fuses Section Contents Page Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 E-Rated Fuses For transformers & feeders . . . . . . . . . . . . . . . . . . 101-104 CL-14 & bolt-in . . . . . . . . . . . . . . . . . . . . . . . . . . . .105-107 For potential & small power transformers . . . . . . . . 108-110 PT fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111 R-Rated fuses for motor circuit protection . .112-114 British IEC fuses for motor circuit protection . . . 115 DIN IEC fuses for transformer protection . . . . . . 116 Expuision Fuse Links . . . . . . . . . . . . . . . . . . 117-118 EEI-NEMA Type K & T and Type H & N fuses . . . 119 Fuseclips for medium and high voltage fuses . . .120 Medium Voltage Fuses Scan this tag to get the latest product information for Medium Voltage Fuses. 99 Medium Voltage Fuses Medium Voltage Fuses Worldwide Circuit Protection Solutions Bussmann is a world-leading supplier of medium voltage fuses. Each product is backed by an efficient worldwide distribution network with unrivaled service and technical support. Bussmann circuit protection solutions comply with major international standards: ANSI, BS, DIN, IEC and UL. Fuse Types Medium voltage fuses generally fit into two categories – expulsion fuses and current limiting fuses. The definitions per ANSI C37.40 are: Expulsion Fuse: “A vented fuse in which the expulsion effect of the gases produced by internal arcing, either alone or aided by other mechanisms results in current interruption.” Expulsion fuses will limit the duration of an overcurrent event, but they will not limit the magnitude of fault current. Current Limiting Fuse: “A fuse unit that, when in its currentresponsive element is melted by a current within the fuse’s specified current-limiting range, abruptly introduces a high resistance to reduce current magnitude and duration, resulting in subsequent current interruption.” A current limiting fuse will reduce the magnitude a fault current as well as limit the duration of the overcurrent event when operating in its current limiting range. Bussmann offers a broad range of current limiting fuses for protection of feeders, transformers and motor circuits designed to ANSI, BS, DIN and IEC standards. Medium Voltage Current Limiting Fuses Current limiting fuses are classified into three categories: 1. Full Range – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the minimum continuous current that causes the melting of the fusible element(s), when the fuse is applied at the maximum ambient temperature specified by the manufacturer.” It is able to interrupt any current that will melt its element. within this range. It is possible for the fuse to be exposed to an overcurrent lower than the value given by the one hour criteria. In that case, a different overcurrent protection device would be required to interrupt the overcurrent. 3. Back-up – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum interrupting rating current down to the minimum interrupting current.” The minimum interrupting current is the lowest current that the fuse will be able to clear properly. This creates a need to place a low current interrupting device, such as motor overloads, in series with the back-up rated fuse. E- and R-Rated Fuses In North America, current limiting fuses typically fall into the category of E-Rated fuses and R-Rated fuses. Bussmann also offers a wide range of current limiting fuses designed to BS, DIN and IEC standards. E-Rated fuses are used to protect feeder circuits, power transformers and potential transformers. E-Rated fuses have defined current response times specified by ANSI C37.46. E-Rated fuses 100A and below must melt in 300sec at an rms current within the range of 200% to 240% of the continuous current rating. E-Rated fuses above 100A must melt in 600sec at an rms current within the range of 240% to 264% of the continuous current rating of the fuse. Bussmann offers a wide variety of full range and general purpose E-Rated fuses from 2.4kV up to 38kV. R-Rated fuses are back-up fuses that provide short-circuit protection for motor circuits. They are applied with MV motor starters which provide the overload protection for the circuit. R-Rated fuses also have defined current response times specified by ANSI C37.46. R-Rated fuses will melt in a range of 15 – 35sec at a current equal to 100 times the “R” rating. Bussmann offers 2.4kV, 5.08kV, 7.2kV and 8.3kV R-Rated fuses for motor circuit protection. 2. General Purpose – defined by ANSI C37.40 as “a fuse capable of interrupting all currents from the maximum rated interrupting current down to the current that causes melting of the fusible element(s) in one hour.” Not all currents fall 100 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses E-Rated Fuses for Transformers and Feeders Specifications Description: E-rated medium, voltage current-limiting fuses for transformer and feeder protection. Dimensions: See Catalog Numbers table. Construction: Silver ribbon element surrounded by silica filler housed in a fiberglass tube and plated endcaps. An epoxy paint protects the fuse tube from the surrounding environment. Ratings: Volts: — 5.5kV (10-450A) Amps: — 5-450A (5.5kV) IR: — 50kA Sym. Max Agency Information: Meets E requirements per ANSI C37.46, Meets full range requirements per ANSI C37.40. Max Clear I2t 8,000 11,000 23,000 31,000 45,000 45,000 90,000 181,000 8,000 12,000 23,000 31,000 45,000 45,000 90,000 181,000 270,000 580,000 600,000 786,000 1,100,000 1,520,000 2,400,000 3,149,000 4,376,000 6,071,000 9,796,000 Dimensions (in)* Clip Center Barrels Length Dia. 1 15.75 3 12 1 1 12 15.75 2 15.75 3 12 1 15.75 3 12 2 2 Medium Voltage Fuses Features and Benefits • MV055 Standard clip center distance of 12 inches with 2 and 3 inch barrel diameters for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range rating with 50KA Interrupting Rating • Double pulsed at 90% of minimum I2t to establish manufacturing reliability • • • • Min Catalog Amp Melt Numbers Rating I2t MV055F1CAX10E 10 850 MV055F1CAX15E 15 2,070 MV055F1CAX20E 20 2,370 MV055F1CAX25E 25 4,650 MV055F1CAX30E 30 9,490 MV055F1CAX40E 40 9,490 MV055F1CAX50E 50 13,600 MV055F1CAX65E 65 30,700 MV055F1DAX10E 10 850 MV055F1DAX15E 15 2,070 MV055F1DAX20E 20 2,370 MV055F1DAX25E 25 4,650 MV055F1DAX30E 30 9,490 MV055F1DAX40E 40 9,490 MV055F1DAX50E 50 13,600 MV055F1DAX65E 65 30,700 MV055F1DAX80E 80 54,600 MV055F1DAX100E 100 116,200 MV055F1DAX125E 125 167,400 MV055F1DAX150E 150 218,700 MV055F1DAX175E 175 227,900 MV055F1DAX200E 200 297,600 MV055F2DAX250E 250 669,600 MV055F2DAX300E 300 874,800 MV055F2DAX350E 350 911,600 MV055F2DAX400E 400 1,190,400 MV055F2DAX450E 450 1,555,000 1” = 25.4mm Recommended Fuse Clips - see page 120 5.5kV Catalog Numbers MV055 MV055 Typical Applications 5.0kV Transformer Primary Protection 5.0kV Feeder Circuit Protection 5.0kV Voltage Switches 5.0kV Metal-enclosed Switchgear Dimensions - in Diagram 1 Diagram 2 Data Sheet: 6700 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle 101 Medium Voltage Fuses E-Rated Fuses for Transformers and Feeders Data Sheet: 6700 MV155 Features and Benefits • MV155 Standard clip center distance of 15 and 18 inches with 2 and 3 inch barrel diameters for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range rating with 50kA Interrupting Rating • Double pulsed at 90% of minimum I2t to establish manufacturing reliability • • • • Min Melt I2t 180 850 850 2,070 2,370 4,650 9,490 850 2,070 2,370 4,650 9,490 9,490 13,600 15.5kV Catalog Numbers Specifications Description: E-rated medium, voltage current-limiting fuses for transformer and feeder protection. Dimensions: See Catalog Numbers table. Construction: Silver ribbon element surrounded by silica filler housed in a fiberglass tube and plated endcaps. An epoxy paint protects the fuse tube from the surrounding environment. Ratings: Volts: — 15.5kV (5-200A) Amps: — 5-200A (15.5kV) IR: — 50kA Sym. Max Agency Information: Meets E requirements per ANSI C37.46, Meets full range requirements per ANSI C37.40. Catalog Numbers MV155F1CBX5E MV155F1CBX7E MV155F1CBX10E MV155F1CBX15E MV155F1CBX20E MV155F1CBX25E MV155F1CBX30E MV155F1DBX10E MV155F1DBX15E MV155F1DBX20E MV155F1DBX25E MV155F1DBX30E MV155F1DBX40E MV155F1DBX50E MV155F1DBX65E MV155F1DBX80E MV155F1DBX100E MV155F2DBX125E MV155F2DBX150E MV155F2DBX175E Amp Rating 5 7 10 15 20 25 30 10 15 20 25 30 40 50 65 80 100 125 150 175 30,700 54,600 116,200 123,000 218,700 314,700 Max Dimensions* Clear Clip I2t Length Dia. Center Barrels 2,900 18.75 15 1 8,000 8,000 12,000 1 23,000 31,000 45,000 8,000 18.75 3 15 1 1 12,000 23,000 15 31,000 18.75 45,000 45,000 90,000 181,000 270,000 600,000 677,000 18.75 3 2 15 2 181,000 21.75 3 18 1 677,000 21.75 21.75 3 18 18 2 1,287,000 1,689,000 MV155F2DBX200E 200 465,100 2,405,000 MV155F1DCX100E 100 116,200 600,000 MV155F1DCX65E MV155F1DCX80E MV155F2DCX125E MV155F2DCX150E MV155F2DCX175E MV155F2DCX200E *1” = 25.4mm. 65 80 125 150 175 200 30,700 54,600 123,000 218,700 314,700 465,100 Recommended Fuse Clips - see page 120 270,000 1,287,000 1,689,000 2,405,000 MV155 Typical Applications 15.0kV Transformer Primary Protection 15.0kV Feeder Circuit Protection 15.0kV Voltage Switches 15.0kV Metal-enclosed Switchgear Dimensions - in Diagram 1 Diagram 2 102 Data Sheet: 6701 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 2 1 2 Medium Voltage Fuses E-Rated Fuses for Transformer & Feeders JCX, JCY, JCU, JCZ and JDZ Specifications Description: Indoor/enclosure E-rated medium voltage, currentlimiting fuses for feeders and power transformers with blown fuse indication. Dimensions: See Catalog Numbers table. Construction: plated ferrules. Ratings: Volts: — 2750-8300V - See Catalog Numbers table for details Amps: — 1⁄2-750A IR: — 40-63kA Sym — 60-100kA ASYM — See Catalog Numbers table for details Construction Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double Double Single Single Single Single Single Single Single Single Single Single • • • • Typical Applications Medium Voltage Transformer Primary Protection Medium Voltage Feeder Circuit Protection Medium Voltage Switches Medium Voltage Metal-enclosed Switchgear Maximum Interrupting Capacity Amps (Asym.) Amps (Sym.) 60,000 60,000 60,000 60,000 60,000 60,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 60,000 40,000 40,000 40,000 40,000 40,000 40,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 40,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 40,000 Contact Bussmann for the latest product information on E-Rated fuses for transformer and feeder protection. Recommended fuseclips: see page 120 - 1A0065, 9078A67G04, A3354730 Dimensions - in (mm) Length Diameter 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.19 (233.38) 9.5 (241.3) 9.5 (241.3) 9.5 (241.3) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 10.81 (276.35) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 11.19 (284.18) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) Medium Voltage Fuses Catalog Amp Maximum Numbers Rating Design Voltage 2400V; E-Rated; Indoor/Enclosure JCX-1E 1 2750 JCX-2E 2 2750 JCX-3E 3 2750 JCX-5E 5 2750 JCX-7E 7 2750 JCX-10E 10 2750 JCX-15E 15 2750 JCX-20E 20 2750 JCX-25E 25 2750 JCX-30E 30 2750 JCX-40E 40 2750 JCX-50E 50 2750 JCX-65E 65 2750 JCX-80E 80 2750 JCX-100E 100 2750 JCX-125E 125 2750 JCX-150E 150 2750 JCX-200E 200 2750 JCX-225E 225 2750 JCX-250E/280X 250/280 2750 JCX-300E/325X 300/325 2750 JCX-350X 350 2750 JCX-400X 400 2750 JCX-450X 450 2750 5500V; E-Rated; Indoor/Enclosure JCY-1⁄2E 0.5 5500 JCY-1E 1 5500 JCY-2E 2 5500 JCY-3E 3 5500 JCY-5E 5 5500 JCY-7E 7 5500 JCY-10E 10 5500 JCY-15E 15 5500 JCY-20E 20 5500 JCY-25E 25 5500 Catalog Numbers Features and Benefits • Physically dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Full range ANSI classification 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) 2 (50.8) For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 103 Medium Voltage Fuses E-Rated Fuses for Transformer & Feeders Amp Catalog Rating Numbers 5500V; E-Rated; Indoor/Enclosure 10 JCU-10E 15 JCU-15E JCU-20E 20 JCU-25E 25 JCU-30E 30 40 JCU-40E 50 JCU-50E 60 JCU-65E JCU-80E 80 JCU-100E 100 JCU-125E 125 JCU-150E 150 175 JCU-175E 200 JCU-200E 250 JCU-250E JCU-300E 300 JCU-350E 350 JCU-400E 400 JCU-450E 450 600 JCU-600E 750 JCU-750E 8300V; E-Rated; Indoor/Enclosure JCZ-15E 15 JCZ-20E 20 JCZ-25E 25 JCZ-30E 30 JCZ-40E 40 JCZ-50E 50 JCZ-65E 65 JCZ-80E 80 JCZ-100E 100 JCZ-125E 125 JCZ-150E 150 JCZ-200E 200 JDZ-20E 20 JDZ-25E 25 JDZ-30E 30 JDZ-40E 40 JDZ-50E 50 JDZ-65E 65 JDZ-80E 80 JDZ-100E 100 JDZ-125E 125 Maximum Design Voltage Catalog Numbers: E-Rated; Indoor/Enclosure 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 5500 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 8300 Construction Single Single Single Single Single Single Single Single Single Single Single Single Single Single Single Double Double Double Double * * Single Single Single Single Single Single Single Single Single Single Single Double Single Single Single Single Single Single Double Double Double Maximum Interrupting Capacity Amps. (Asym.) Amps. (Sym.) 80,000 80,000 80,000 80,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 100,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 63,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 Recommended fuseclips: see page 120 - 1A0065, 9078A67G04, A3354730 General Notes: 1. All fuses are fitted with a striker pin which can be used for indication or tripping purposes. 2. The fuses are suitable for use either indoors or outdoors. 3. These fuses are interchangeable with corresponding fuses produced by most other leading North American manufacturers. Contact Bussmann for the latest product information on E-Rated fuses for transformer and feeder protection. *Bolt on mounting 104 Dimensions - in (mm) Length Diameter 17.81 12.88 12.88 12.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 28.81 28.81 15.51 15.51 15.51 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle (452.4) (327.0) (327.0) (327.0) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (731.77) (731.77) (393.95) (393.95) (393.95) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (454.15) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) (403.2) 3 (76.2) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 3 (76.20) 4 (101.60) 4 (101.60) 2.1 (53.34) 2.1 (53.34) 2.1 (53.34) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) 3 (76.2) Medium Voltage Fuses E-Rated Fuses: CL-14 & Bolt-In ECL055 Specifications Description: E-rated medium voltage, current-limiting fuses for transformer and feeder protection. Construction: Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration. Ratings: Volts: — 5.5kV Amps: — 10-900A IR: — 63kA Sym. Max Agency Information: Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40. • • • • Typical Applications 5.0kV Transformer Primary Protection 5.0kV Feeder Circuit Protection 5.0kV Voltage Switches 5.0kV Metal-enclosed Switchgear Dimensions - in Single Barrel Double Barrel Amp Rating 10 15 20 25 30 40 50 65 80 100 125 150 200 250 300 400 450 500 600 750 900 Catalog Numbers Catalog Number ECL Voltage 5.5kV – – – – – – – – – – – – – – – – – – – – Voltage Rating 055 055 = 5.5 kV IR Max Sym. 63kA # of Barrels 1 Style Clip-Lock 1 Clip-Lock 2 Clip-Lock 3 Bolt-In Bolt-In 63kA 2 3 Amp Rating 500E Catalog Number Construction (Example) Catalog Number Cross Reference Bussmann Catalog Numbers ECL055-10E ECL055-15E ECL055-20E ECL055-25E ECL055-30E ECL055-40E ECL055-50E ECL055-65E ECL055-80E ECL055-100E ECL055-125E ECL055-150E ECL055-200E ECL055-250E ECL055-300E ECL055-400E ECL055-450E ECL055-500E ECL055-600E ECL055-750E ECL055-900E Mersen New Catalog # A055C1DORO-10E A055C1DORO-15E A055C1DORO-20E A055C1DORO-25E A055C1DORO-30E A055C1DORO-40E A055C1DORO-50E A055C1DORO-65E A055C1DORO-80E A055C1DORO-100E A055C1DORO-125E A055C1DORO-150E A055C1DORO-200E A055C1DORO-250E A055C1DORO-300E A055C1DORO-400E A055C2DORO-450E A055C2DORO-500E A055C2DORO-600E A055B3DORO-750E A055B3DORO-900E Mersen Old Catalog # 225-007-937 225-007-938 225-007-939 225-007-940 225-007-941 225-007-942 225-007-943 225-007-944 225-007-945 225-007-946 225-007-947 225-007-948 225-007-949 225-007-950 225-007-951 225-007-952 225-007-953 225-007-954 225-007-955 A055X750E-4 A055X900E-4 Data Sheet: 9002 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle 105 Medium Voltage Fuses Features and Benefits • Clip-lock and bolt-in style available in double and triple barrel fuse designs for application flexibility • The filament wound, glass epoxy fuse tube provides moisture protection for the fuse. This makes Cooper Bussmann medium voltage fuses suitable for both indoor and outdoor application (outdoor applications require installation inside an appropriate enclosure) • Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60Hz operating frequency make these fuses applicable world-wide Catalog Numbers ECL055-10E ECL055-15E ECL055-20E ECL055-25E ECL055-30E ECL055-40E ECL055-50E ECL055-65E ECL055-80E ECL055-100E ECL055-125E ECL055-150E ECL055-200E ECL055-250E ECL055-300E ECL055-400E ECL055-450E ECL055-500E ECL055-600E ECL055-750E ECL055-900E Medium Voltage Fuses E-Rated Fuses: CL-14 & Bolt-In ECL083 Specifications Description: E-rated medium voltage, current-limiting fuses for transformer and feeder protection. Construction: Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration. Ratings: Volts: — 8.3kV Amps: — 65-350A IR: — 50kA Agency Information: Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40. Features and Benefits • Clip-lock and bolt-in style available in double and triple barrel fuse designs for application flexibility • The filament wound, glass epoxy fuse tube provides moisture protection for the fuse. This makes Cooper Bussmann medium voltage fuses suitable for both indoor and outdoor application (outdoor applications require installation inside an appropriate enclosure) • Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60Hz operating frequency make these fuses applicable world-wide • • • • Typical Applications 8.0kV Transformer Primary Protection 8.0kV Feeder Circuit Protection 8.0kV Voltage Switches 8.0kV Metal-enclosed Switchgear Dimensions - in Catalog Number ECL Voltage Rating 083 083 = 8.3 kV Amp Rating 300E Catalog Number Construction (Example) Electrical Characteristics Part Number ECL083-65E ECL083-80E ECL083-100E ECL083-125E ECL083-150E ECL083-175E ECL083-200E ECL083-250E ECL083-300E ECL083-350E Amps 65 80 100 125 150 175 200 250 300 350 Volts 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV 8.3kV # of IR Max Sym. Barrels 50kA 1 50kA 1 50kA 1 50kA 1 50kA 1 50kA 1 50kA 2 50kA 2 50kA 2 50kA 2 Catalog Number Cross Reference Bussmann Catalog Numbers ECL083-65E ECL083-80E ECL083-100E ECL083-125E ECL083-150E ECL083-175E ECL083-200E ECL083-250E ECL083-300E ECL083-350E Mersen New Catalog # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Single Barrel Double Barrel Data Sheet: 9007 106 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle Figure # 1 1 1 1 1 1 2 2 2 2 Mersen Old Catalog # N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Style Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Clip-Lock Medium Voltage Fuses E-Rated Fuses: CL-14 ECL155 Specifications Description: E-rated medium voltage, current-limiting fuses for transformer and feeder protection. Construction: Filament wound, glass epoxy fuse tube, with silica filler, and silver-plated copper terminals and endcaps containing a silver element in a double concentric helical configuration. Ratings: Volts: — 15.5kV Amps: — 10-300A IR: — 63kA Sym. (10-200A) — 50kA Sym. (250-300A) Agency Information: Meets E requirements per ANSI C37.46, Meets General Purpose requirements per ANSI C37.40. • • • • Typical Applications 15.0kV Transformer Primary Protection 15.0kV Feeder Circuit Protection 15.0kV Voltage Switches 15.0kV Metal-enclosed Switchgear Dimensions - in Single Barrel Double Barrel Amp Rating 10 15 20 25 30 40 50 65 80 100 125 150 200 250 300 Catalog Numbers Catalog Number ECL Voltage 15.5kV 15.5kV IR Voltage Max Sym. 63KA 1 63kA 50kA 50kA Voltage Rating 155 155 = 15.5 kV # of Barrels 1 2 Style Clip-Lock Clip-Lock 2 Medium Voltage Fuses Features and Benefits • Clip-lock double barrel fuse design assures positive installation • The filament wound, glass epoxy fuse tube provides moisture protection for the fuse. This makes Cooper Bussmann medium voltage fuses suitable for both indoor and outdoor application (outdoor applications require installation inside an appropriate enclosure) • Open fuse indication (indicator travel distance is 16mm) easily integrates into automation schemes • 50/60Hz operating frequency make these fuses applicable world-wide Catalog Numbers ECL155-10E ECL155-15E ECL155-20E ECL155-25E ECL155-30E ECL155-40E ECL155-50E ECL155-65E ECL155-80E ECL155-100E ECL155-125E ECL155-150E ECL155-200E ECL155-250E ECL155-300E Amp Rating 300E Catalog Number Construction (Example) Mersen New Catalog # A155C1DORO-10E A155C1DORO-15E A155C1DORO-20E A155C1DORO-25E A155C1DORO-30E A155C1DORO-40E A155C1DORO-50E A155C1DORO-65E A155C1DORO-80E A155C1DORO-100E A155C2DORO-125E A155C3DORO-150E A155C3DORO-200E A155C3DORO-250E A155C3DORO-300E Catalog Number Cross Reference Bussmann Catalog Numbers ECL155-10E ECL155-15E ECL155-20E ECL155-25E ECL155-30E ECL155-40E ECL155-50E ECL155-65E ECL155-80E ECL155-100E ECL155-125E ECL155-150E ECL155-200E ECL155-250E ECL155-300E Data Sheet: 9004 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Mersen Old Catalog # 225-007-967 225-007-968 225-007-969 225-007-970 225-007-971 225-007-972 225-007-973 225-007-974 225-007-975 225-007-976 225-007-977 225-007-978 225-007-979 225-007-980 225-007-981 107 Medium Voltage Fuses E-Rated Fuses for Potential & Small Power Transformers Ratings: Volts: — 5.5-38kV Amps: — 0.5-15A IR: — 40kA-80kA Sym. — See Catalog Numbers table for details AB, AD, AM and CAV Specifications Description: Indicating and non-indicating E-Rated medium voltage, current-limiting fuses for potential and small power transformers. Dimensions: See Catalog Numbers table. Dimension Illustration on the following page Features and Benefits • Sized for retrofitting in existing hardware • Space saving size Typical Applications • Primary protection of medium voltage potential transformers • Primary protection of small medium voltage service transformers • Primary protection of small medium voltage control transformers Catalog Numbers: E-Rated PT Fuses, Indicating & Non-Indicating 3.6kV; E-Rated PT Fuse; Non-indicating Catalog Number 3.6CAV2 3.6ABWNA3.15 3.6ABWNA6.3 3.6ABCNA3.15 3.6ABCNA6.3 3.6ABCNA10 Amp Rating 2 3.15 3.15 3.15 6.3 10 Rated Voltage 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV Length 8.66 (220) 5.6 (142.2) 5.6 (142.2) 7.69 (195.3) 7.69 (195.3) 7.69 (195.3) Dimensions Diameter 1.63 (41.3) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) Clip Centers 7.46 (189.48) 4.42 (112.2) 4.42 (112.2) 6.51 (165.3) 6.51 (165.3) 6.51 (165.3) Spare Parts (Clips) 1A0835 A3354705 A3354705 A3354705 A3354705 A3354705 RMS Sym. 63kA 63kA 63kA 63kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA Length 7.375 (187.3) 7.375 (187.3) 7.375 (187.3) 7.375 (187.3) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) Clip Centers 6.18 (156.84) 6.18 (156.84) 6.18 (156.84) 6.18 (156.84) 4.42 (112.2) 4.42 (112.2) 4.42 (112.2) 4.42 (112.2) 4.42 (112.2) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 A3354705 A3354705 A3354705 A3354705 A3354705 1A1837 1A1837 1A1837 1A1837 1A1837 1A1837 IR RMS Sym. 63kA 63kA 63kA 63kA 45kA 45kA 45kA 45kA 50kA 50kA 50kA 50kA 50kA 50kA Length 8.66 (220) 8.66 (220) 8.66 (220) 8.66 (220) 5.6 (142.2) 5.6 (142.2) 7.69 (195.3) 7.69 (195.3) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) 5.6 (142.2) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1 (25.4) 1 (25.4) 1 (25.4) 1 (25.4) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) 0.81 (20.6) Clip Centers 7.46 (189.48) 7.46 (189.48) 7.46 (189.48) 7.46 (189.48) 4.42 (112.2) 4.42 (112.2) 6.51 (165.3) 6.51 (165.3) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) 4.79 (121.6) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 A3354705 A3354705 A3354705 A3354705 1A1837 1A1837 1A1837 1A1837 1A1837 1A1837 IR RMS Sym. 50kA 50kA 50kA 50kA 50kA 50kA 5.5kV; E-Rated PT Fuse; Indicating & Non-indicating Catalog Amp Rated Number Rating Voltage IR 5.5CAVH0.5E 0.5 5.5kV 5.5CAVH1E 1 5.5kV 5.5CAVH2E 2 5.5kV 5.5CAV15E 15 5.5kV 5.5ABWNA0.5E 0.5 5.5kV 5.5ABWNA1E 1 5.5kV 5.5ABWNA2E 2 5.5kV 5.5ABWNA3E 3 5.5kV 5.5ABWNA5E 5 5.5kV 5.5AMWNA0.5E 0.5 5.5kV 5.5AMWNA1.0E 1 5.5kV 5.5AMWNA2.0E 2 5.5kV 5.5AMWNA3.0E 3 5.5kV 5.5AMWNA4.0E 4 5.5kV 5.5AMWNA5.0E 5 5.5kV Type CAVH are fitted with a striker pin for indication 7.2kV; E-Rated PT Fuse; Non-indicating Catalog Number 7.2CAV2 7.2CAV4 7.2CAV6 7.2CAV10 7.2ABWNA3.15 7.2ABWNA6.3 7.2ABCNA3.15 7.2ABCNA6.3 7.2AMWNA0.5E 7.2AMWNA1.0E 7.2AMWNA2.0E 7.2AMWNA3.0E 7.2AMWNA4.0E 7.2AMWNA5.0E 108 Amp Rating 2 4 6 10 3.15 6.3 3.15 6.3 0.5 1 2 3 4 5 Rated Voltage 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV 7.2kV For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses E-Rated Fuses for Potential & Small Power Transformers Dimension Illustration Length Clip Centers Diameter Catalog Numbers: E-Rated PT Fuses, Indicating & Non-Indicating 12kV; E-Rated PT Fuse; Non-indicating Catalog Number 12CAV2 12ABCNA3.15 Amp Rating 2 3.15 Rated Voltage 12kV 12kV IR RMS Sym. 40kA 45kA Length 8.66 (220) 7.69 (195.3) Dimensions Diameter 1.63 (41.3) 1 (25.4) Clip Centers 7.46 (189.48) 6.51 (165.3) Spare Parts (Clips) 1A0835 A3354705 15.5kV; E-Rated PT Fuse; Indicating & Non-indicating Rated Voltage IR 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV 15.5kV for indication RMS Sym. 80kA 80kA 80kA 80kA 80kA 80kA Length 12.87 (326.9 12.87 (326.9 12.87 (326.9 12.87 (326.9 12.87 (326.9 12.87 (326.9 Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) Clip Centers 1.2 (30.5) 1.2 (30.5) 1.2 (30.5) 1.2 (30.5) 1.2 (30.5) 1.2 (30.5) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 1A0835 1A0835 IR RMS Sym. 40kA 40kA 40kA 40kA 35kA Length 8.66 (220) 8.66 (220) 8.66 (220) 8.66 (220) 14.13 (358.9) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1 (25.4) Clip Centers 7.46 (189.48) 7.46 (189.48) 7.46 (189.48) 7.46 (189.48) 12.95 (328.9) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 A3354705 Length 13.39 (340.1) 13.39 (340.1) 13.39 (340.1) 14.13 (358.9) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1 (25.4) Clip Centers 12.19 (309.62) 12.19 (309.62) 12.19 (309.62) 12.95 (328.9) Spare Parts (Clips) 1A0835 1A0835 1A0835 A3354705 Length 17.32 (439.9) 17.32 (439.9) 14.13 (358.9) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1 (25.4) Clip Centers 16.12 (409.44) 16.12 (409.44) 12.95 (328.9) Spare Parts (Clips) 1A0835 1A0835 A3354705 Length 17.32 (439.9) 17.32 (439.9) 17.32 (439.9) 17.32 (439.9) Dimensions Diameter 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) 1.63 (41.3) Clip Centers 16.12 (409.44) 16.12 (409.44) 16.12 (409.44) 16.12 (409.44) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 Medium Voltage Fuses Catalog Amp Number Rating 15.5CAV(H)0.5E 0.5 15.5CAV(H)1E 1 15.5CAV(H)2E 2 15.5CAV3E 3 15.5CAV5E 5 15.5CAV7E 7 Type CAVH are fitted with a striker pin 17.5kV; E-Rated PT Fuse; Non-indicating Catalog Number 17.5CAV2 17.5CAV4 17.5CAV6 17.5CAV10 17.5ABGNA3.15 Amp Rating 2 4 6 10 3.15 Rated Voltage 17.5kV 17.5kV 17.5kV 17.5kV 17.5kV 24kV; E-Rated PT Fuse; Non-indicating Catalog Number 24CAV2 24CAV3 24CAV4 24ABGNA3.15 Amp Rating 2 3 4 3.15 Rated Voltage 24kV 24kV 24kV 24kV IR RMS Sym. 40kA 40kA 40kA 25kA 36kV; E-Rated PT Fuse; Non-indicating Catalog Number 36CAV2 36CAV4 36ABGNA3.15 Amp Rating 2 4 3.15 Rated Voltage 36kV 36kV 36kV IR RMS Sym. 40kA 40kA 31.5kA 38kV; E-Rated PT Fuse; Indicating & Non-indicating Catalog Number 38CAVH0.5E 38CAVH1E 38CAVH2E 38CAV4E Amp Rating 0.5 1 2 4 Rated Voltage 38kV 38kV 38kV 38kV IR RMS Sym. 40kA 40kA 40kA 40kA For product data sheets, visit www.cooperbussmann.com/DatasheetsEle 109 Medium Voltage Fuses E-Rated, PT Fuses for Potential & Small Power Transformers JCD, JCW, JCQ, JCI & JCT Specifications Description: Indicating and nonindicating E-rated medium voltage, current-limiting fuses for potential and small power transformers. Dimensions: See Catalog Numbers table. Construction: Plated ferrules. Ratings: Volts: — 2.4-15.5kV (See Catalog Numbers table for details) Amps: — 1⁄2-10A IR: — 25-80kA Sym — 40-130kA ASYM — See Catalog Numbers table for details Features and Benefits • Sized for retrofitting in existing hardware • Space saving size Typical Applications • Primary protection of medium voltage potential transformers • Primary protection of small medium voltage service transformers • Primary protection of small medium voltage control transformers 2.4kV; E-Rated PT Fuse; Non-indicating Catalog Number JCD-1-2E JCD-1E JCD-2E JCD-5E Amp Rating 0.5 1 2 5 Rated Voltage 2.4kV 2.4kV 2.4kV 2.4kV Length 4.49 (114) 4.49 (114) 4.49 (114) 4.49 (114) Dimensions Diameter 0.8 (20) 0.8 (20) 0.8 (20) 0.8 (20) Clip Centers 3.86 (98) 3.86 (98) 3.86 (98) 3.86 (98) Spare Parts (Clips) 1A1837 1A1837 1A1837 1A1837 IR RMS Sym. 40kA 40kA 40kA 40kA 40kA 40kA Length 7.31 (185) 7.31 (185) 7.31 (185) 7.31 (185) 7.31 (185) 7.31 (185) Dimensions Diameter 1.56 (39.7) 1.56 (39.7) 1.56 (39.7) 1.56 (39.7) 1.56 (39.7) 1.56 (39.7) Clip Centers 5.93 (150.6) 5.93 (150.6) 5.93 (150.6) 5.93 (150.6) 5.93 (150.6) 5.93 (150.6) Spare Parts (Clips) 1A0835 1A0835 1A0835 1A0835 1A0835 1A0835 IR RMS Sym. 130kA 130kA 130kA Length 9.5 (241.3) 9.5 (241.3) 9.5 (241.3) Dimensions Diameter 1.6 (40.6) 1.6 (40.6) 1.6 (40.6) Clip Centers 8.12 (206) 8.12 (206) 8.12 (206) Spare Parts (Clips) 1A0835 1A0835 1A0835 IR RMS Sym. 80kA 80kA 80kA Length 12.88 (327) 12.88 (327) 12.88 (327) Dimensions Diameter 1.6 (40.6) 1.6 (40.6) 1.6 (40.6) Clip Centers 11.5 (292) 11.5 (292) 11.5 (292) Spare Parts (Clips) 1A0835 1A0835 1A0835 IR RMS Sym. 80kA 80kA 80kA Length 17.5 (444.5) 17.5 (444.5) 17.5 (444.5) Dimensions Diameter 1.6 (40.6) 1.6 (40.6) 1.6 (40.6) Clip Centers 16.12 (409.4) 16.12 (409.4) 16.12 (409.4) Spare Parts (Clips) 1A0835 1A0835 1A0835 IR RMS Sym. 63kA 40kA 40kA 25kA 2.4/5.5kV; E-Rated PT Fuse; Non-indicating Catalog Number JCW-1/2E JCW-1E JCW-2E JCW-3E JCW-4E JCW-5E Amp Rating 0.5 1 2 3 4 5 Rated Voltage 2.4kV/5.5kV 2.4kV/5.5kV 2.4kV/5.5kV 2.4kV/5.5kV 2.4kV/5.5kV 2.4kV/5.5kV 5.5kV; E-Rated PT Fuse; Indicating Catalog Number JCQ-3E JCQ-5E JCQ-10E Amp Rating 3 5 10 Rated Voltage 5.5kV 5.5kV 5.5kV 8.3kV; E-Rated PT Fuse; Indicating Catalog Number JCI-3E JCI-5E JCI-10E Amp Rating 3 5 10 Rated Voltage 8.3kV 8.3kV 8.3kV 15.5kV; E-Rated PT Fuse; Indicating Catalog Number JCT-3E JCT-5E JCT-10E Amp Rating 3 5 10 Rated Voltage 15.5kV 15.5kV 15.5kV Data Sheet: 6002 110 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle Medium Voltage Fuses PT Fuses HVA, HVB, HVJ, HVL, HVR, HVT, HVU, HVW & HVX Basic Catalog Numbers HVA, HVB, HVJ, HVL Test Specifications HVR, HVT, HVU, HVW, HVX Specifications Description: Medium voltage, non-time delay, fast-acting fuses. Dimensions: See Basic Catalog Numbers table. Ratings: Volts: — 1-10kV (See Basic Catalog Numbers table) Amps: — 1⁄16-10A (See Basic Catalog Numbers table) Features and Benefits • Physical size varies with electrical rating of fuse to prevent over-fusing. • Space saving size. Typical Applications • Medium Voltage Instrument Protection • Medium Voltage Circuit Protection HVB HVJ HVL HVR HVW HVT HVU HVX kV 1 2.5 5 10 1 1.2 2.5 5 10 Amp Ratings 1 ⁄16, 1⁄10, 1⁄8, 2⁄10, 1⁄4, 3⁄10, 3⁄8, 1⁄2, 3 ⁄4, 1, 1 1⁄2, 2, 3, 4, 6, 10 1 ⁄2, 3⁄4, 1, 1 1⁄2, 2, 3 1 ⁄16, 1⁄8, 1⁄4, 1⁄2, 3⁄4, 1 1⁄2, 2, 4, 6, 10 1 ⁄16, 1⁄8, 1⁄4, 1⁄2, 1, 1 1⁄2, 2, 3 1 ⁄2, 1, 2, 3, 4, 5 1, 2, 3, 4, 5, 8 1 ⁄2, 1, 2, 3, 5 1 ⁄2, 1, 2, 3, 4, 5 1 ⁄2, 1, 3, 5 Fuse blocks: 4528, 4529 Voltage Rating: 1000 to 10,000V Basic Catalog Numbers HVA, HVR HVB, HVT HVJ, HVU HVL, HVX Fuse Block Catalog Number 4528 4529 N/A N/A Use #8 screws on blocks 4528 and 4529. Maximum S.C. 20kW DC/30kVA AC 20kW DC/30kVA AC 20kW DC/30kVA AC 20kW DC/30kVA AC kVA-500 AC only kVA-12,000 AC only kVA-1250 AC only kVA-2500 AC only kVA-5,000 AC only Fuse Clip Catalog Number 5960 5960 4180 4180 Medium Voltage Fuses Basic Catalog Number HVA Load / Opening Time 110% / 4 Hours (min) 135% / 1 Hour (max) 100% / 4 Hours (min) 150% / 1 Hour (max) Dimensions - in (mm) Diameter Length 0.41 (10.4) 3 (76.1) 0.41 0.81 0.81 0.41 0.41 0.41 0.81 0.41 (10.4) (20.6) (20.6) (10.4) (10.4) (10.4) (20.6) (10.4) 4.5 (114.2) 5 (126.9) 10 (254) 3 (76.2) 2.25 (57.1) 4.5 (114.2) 5 (126.9) 10.0 (253.8) Catalog Number Build-A-Code Basic Catalog Number Amps _____ Data Sheet: 6003 ___ For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 111 Medium Voltage Fuses R-Rated Fuses for Motor Circuit Protection JCG, JCH, JCK, JCK-A, JCK-B, JCL, JCL-A, JCL-B, JCR-A, & JCR-B Specifications Description: Indoor/enclosure R-Rated medium voltage, current-limiting fuses for motor circuit protection. Dimensions: See Dimensions illustrations. Ratings: Volts: — 2.4-7.2kV (See Catalog Numbers table for details) Amps: — 25-450A (See Catalog Numbers table for details) IR: — 50kA Sym — 80kA ASYM — See Catalog Numbers table for details Agency Information: UL Recognized: 2540Vac — JCK, JCK-A, 5080Vac — JCL, JCL-A, UL Recognized (Guide #MSSS2, File #E96676). Features and Benefits • Physically dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Available with optional Cutler Hammer® hookeye for ease of insertion and removal • Classified as back-up fuses for current-limited protection of medium voltage motor controllers Typical Applications • Medium Voltage Motor Controllers Dimensions - mm (in) INDICATOR Showing Fuse is Open Figure 1 C A INDICATOR Showing Fuse is Open 0.38" (9.5mm) B Figure 2 Figure 3 Data Sheet 6001 112 For product data sheets, visit For product data sheets, visit www.cooperbussmann.com/DatasheetsEle Medium Voltage Fuses R-Rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure Catalog Numbers Amp Ratings Maximum Design Voltage 2400V (See Figure 1) JCK-2R JCK-3R JCK-4R JCK-5R JCK-6R JCK-9R JCK-12R JCK-18R JCK-24R 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 A Dimensions - in (mm)* B 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) C 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Construction Single Single Single Single Single Single Single Double Double Max Int. Cap. Amps (Asym.) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Amps (Sym.) 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 Min Int. Cap. Amps (Sym.) 165 220 320 410 480 720 970 1,430 1,880 Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 2400V — Bolt-On (See Figures 2 & 3) 3.56 (90.4) 3.56 (90.4) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 90 170 245 340 430 500 1,000 1,250 1,700 1,210 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 90 170 245 340 430 500 1,000 1,250 1,700 2,100 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 11.24 (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) (285.5) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) JCK-B-30 JCK-B-2R JCK-B-3R JCK-B-4R JCK-B-5R JCK-B-6R JCK-B-9R JCK-B-12R JCK-B-18R JCK-B-24R 25 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 14.18 (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) (360.2) 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 12.81 JCH-30 JCH-2R JCH-3R JCH-4R JCH-5R JCH-6R JCH-9R JCH-12R JCH-18R JCH-24R 25 70 100 130 150 170 200 230 390 450 2540 2540 2540 2540 2540 2540 2540 2540 2540 2540 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 10.81 (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) (275.6) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 JCL-2R JCL-3R JCL-4R JCL-5R JCL-6R JCL-9R JCL-12R JCL-18R JCL-24R 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) 15.76 (400.3) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (325.4) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 2400V — Hermetically Sealed, For Use with Ampguard Motor Starters (See Figure 1) 4800V (See Figure 1) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) 3.0 (76.2) • See previous page Figure 2 for single construction and Figure 3 for double construction information. Recommended fuseclips: see page 120 - 1A0065, A3354730, 9078A67G04. Data Sheet: 6001 For product data sheets, visit www.cooperbussmann.com/DatasheetsEle Medium Voltage Fuses 2400V — With Westinghouse Ampguard Hookeye (See Figure 1) JCK-A-2R JCK-A-3R JCK-A-4R JCK-A-5R JCK-A-6R JCK-A-9R JCK-A-12R JCK-A-18R JCK-A-24R 113 Medium Voltage Fuses R-Rated Fuses for Motor Circuit Protection Catalog Numbers: R-Rated; Indoor/Enclosure Catalog Numbers Amp Ratings Maximum Design Voltage A Dimensions - in (mm) B C Construction Max Int. Cap. Amps (Asym. Amps (Sym.) Min Int. Cap. Amps (Sym.) 4800V — With Westinghouse Ampguard Hookeye (See Figure 1) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 165 220 320 410 480 720 970 1,430 1,880 4800V — Bolt-On (See Figures 2 & 3) 3.31 (84.1) 3.31 (84.1) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 95 180 270 350 450 540 700 1,000 1,450 2,000 4800V — Hermetically Sealed, For Use with Ampguard Motor Starters (See Figure 1) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 95 180 270 350 450 540 700 1,000 1,450 2,000 7200V — With Ampguard Hookeye (See Figure 1) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 160 250 325 390 500 750 1,000 1,450 2,500 7200V — Bolt-On (See Figures 2 & 3) 3.31 (84.1) 3.31 (84.1) Single Single Single Single Single Single Single Double Double 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 50,000 160 250 325 390 500 750 1,000 1,450 2,500 JCL-A-2R JCL-A-3R JCL-A-4R JCL-A-5R JCL-A-6R JCL-A-9R JCL-A-12R JCL-A-18R JCL-A-24R 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 15.76 (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) (400.3) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) JCL-B-30 JCL-B-2R JCL-B-3R JCL-B-4R JCL-B-5R JCL-B-6R JCL-B-9R JCL-B-12R JCL-B-18R JCL-B-24R 30 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 5080 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 19.25 (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) (488.9) 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 JCG-30 JCG-2R JCG-3R JCG-4R JCG-5R JCG-6R JCG-9R JCG-12R JCG-A-18R JCG-A-24R 30 70 100 130 150 170 200 230 390 450 5080 5080 5080 5080 5080 5080 5080 5080 5080 5080 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 15.91 (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) (404.1) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 JCR-A-2R JCR-A-3R JCR-A-4R JCR-A-5R JCR-A-6R JCR-A-9R JCR-A-12R JCR-A-18R JCR-A-24R JCR-B-2R JCR-B-3R JCR-B-4R JCR-B-5R JCR-B-6R JCR-B-9R JCR-B-12R JCR-B-18R JCR-B-24R 70 100 130 150 170 200 230 390 450 70 100 130 150 170 200 230 390 450 8300 8300 8300 8300 8300 7200 7200 7200 7200 8300 8300 8300 8300 8300 7200 7200 7200 7200 15.85 15.85 15.85 15.85 15.85 15.85 15.85 15.85 15.85 (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) (402.6) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 19.25 (488.9) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 114 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) 17.88 (454.1) Recommended fuseclips: see page 120 - 1A0065, A3354730, 9078A67G04. Data Sheet: 6001 (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) (454.1) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) (76.2) For product data sheets, visit www.cooperbussmann.com/DatasheetsEle Medium Voltage Fuses British Standard Dimensioned IEC Fuses for Motor Circuit Protection The Bussmann range of motor fuses are designed to meet the specific requirements necessary for motor protection. During the starting cycle of direct on-line motors, the fuse elements will reach a considerably higher temperature than during normal operation; (this is due to the high amount of current the motor will draw as it starts, typically, six times its normal load current value). This results in expansion and contraction of the fuse elements and could cause premature operation of the fuse. Bussmann motor fuses encompass an advanced design to minimize this effect. This therefore, negates the need to over specify the fuse rating due to high values of motor starting current. Bussmann motor fuses operate extremely quickly under heavy fault currents, resulting from the time / current characteristic. Low power dissipation ensures low temperature rise, important in multi-tier starters for example. Switching (arc), voltages are lower than permitted values, therefore, 5.5kV fuses are also suitable for 4.8kV and 2.4kV circuits. Volts 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 3.6kV 5.5kV 5.5kV 7.2kV 7.2kV 7.2kV 7.2kV Breaking Capacity 50kA 50kA 50kA 50kA 50kA 50kA 50kA 50kA 60kA 60kA 40kA 40kA 63kA 63kA Dimensions - in (mm) Amp Ratings Length Diameter 5, 6.3, 10, 16, 20, 25, 31.5, 40, 50 7.56 (192) 1.4 (35.6) 50, 63, 80, 100, 125 7.56 (192) 2 (50.8) 160, 200 7.56 (192) 3 (76.2) 50, 63, 80, 100, 125 11.5 (292.1) 2 (50.8) 160, 200 11.5 (292.1) 3 (76.2) 50, 63, 80, 100, 125 10 (254) 2 (51) 160, 200 10 (254) 3 (76.2) 250, 315, 355, 400 10 (254) 3 (76.2) 2R-6R 15.86 (402.8) 3 (76.2) 9R-24R 15.86 (402.8) 3 (76.2) 25, 31.5, 40, 50, 63, 80, 100, 125, 160 15.86 (402.8) 3 (76.2) 200, 224, 250, 315 15.86 (402.8) 3 (76.2) 25, 31.5, 40, 50, 63, 80, 125, 160 17.40 (442) 3 (76.2) 200, 224, 250, 315, 355 17.40 (442) 3 (76.2) Catalog Number Build-A-Code kV Basic Catalog Number ___ _____ Dimensional Standard BS 2692 (TA1) Interchangeable with GEC Type K2 PA BS 2692 (TA1) or DIN 43625 BS 2692 (TA1) or DIN 43625 DIN 43625 DIN 43625 BS 2692 (TA2) BS 2692 (TA2) BS 2692 (TA2) ANSI R-Rated ANSI R-Rated BS 2692 (TA4) BS 2692 (TA4) DIN 43625 DIN 43625 Amps ___ For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 115 Medium Voltage Fuses Table of Ratings Basic Cat. Number 3.6WJON6 3.6WDOH6 3.6WFOH6 3.6WDLSJ 3.6WFLSJ 3.6WDFHO 3.6WFFHO 3.6WKFHO 5.5VFNHA 5.5VKNHA 7.2WFNHO 7.2WKNHO 7.2WFMSJ 7.2WKMSJ Medium Voltage Fuses DIN Dimensioned IEC Fuses for Transformer Protection DIN Dimension Fuses To Spec. DIN 43625 Specifications Catalog Symbol: See Basic Catalog Numbers table. Description: DIN dimension fuses to Specification DIN 43625 covering current-limiting fuses with performance in compliance with IEC 60282-1. These are in accordance with the R10 and, in some cases, the R20 series of preferred numbers. Dimensions: See Catalog Numbers table. Catalog Number Build-A-Code kV Basic Catalog Number ___ _____ Amps ___ Volts: — See voltage associated with the Basic Catalog Numbers in the table. Amps: — See amp rating associated with the Basic Catalog Numbers in the table. IR: — See IR associated with the Basic Catalog Numbers in the table. Agency Information: Comply with DIN dimensional standard DIN 43625, VDE 0670 part 4, VDE 0670 part 40Z and with IEC 60282-1 (2005). Features and Benefits • DIN dimensioned for retrofitting in existing hardware • Open fuse indicator for ease in troubleshooting • Designed for use in IEC equipment Typical Applications • Medium Voltage IEC designed equipment Catalog Numbers kV 3.6 7.2 12 17.5 24 36 Catalog Numbers 3.6ADOSJ(amp) 3.6WDOSJ(amp) 3.6WFOSJ(amp) 3.6ADLSJ(amp) 3.6WDLSJ(amp) 3.6WFLSJ(amp) 3.6WKLSJ(amp) 7.2TDLSJ(amp) 7.2TFLSJ(amp) 7.2WKMSJ(amp) 12TDLEJ(amp) 12THLEJ(amp) 12TKLEJ(amp) 12TXLEJ(amp)* 17.5TDLSJ(amp)* 17.5TFLSJ(amp)* 17.5TDMEJ(amp) 17.5THMEJ(amp) 17.5TKMEJ(amp) 24TDMEJ(amp) 24THMEJ(amp) 24TFMEJ(amp) 24TXMEJ(amp)* 36TDQSJ(amp) 36TFQSJ(amp) 36TXQEJ(amp)* Amp Ratings 6.3, 10, 16, 20, 25, 31.5, 40 50, 63, 80, 100, 125 160, 200 25, 40 50, 63, 80, 100, 125 160, 200 250, 315, 400 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100, 125, 160 200, 225, 250, 315, 355 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100 125 160, 200 6.3, 10, 16, 20, 25, 31.5, 40 50 6.3, 10, 16, 20, 25, 31.5, 40, 50, 63 80, 100 125 6.3, 10, 16, 20, 25, 31.5, 40, 50 63 80, 100*1 1252, 160 3.153, 6.3, 10, 16, 20, 25 31.5, 40, 50 63 Dimensions - in (mm) Diameter x Length 2.00 x 7.56 (51 x 192) 2.00 x 7.56 (51 x 192) 3.00 x 7.56 (76 x 192 2.00 x 11.50 (51 x 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 X 292) 3.00 x 11.50 (76 X 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 x 292) 3.00 x 17.41 (76 x 442) 2.00 x 11.50 (51 x 292) 2.52 x 11.50 (64 x 292) 3.00 x 11.50 (76 x 292) 3.50 x 11.50 (88 x 292) 2.00 x 11.50 (51 x 292) 3.00 x 11.50 (76 x 292) 2.00 x 17.41 (51 x 442) 2.52 x 17.41 (64 x 442) 3.00 x 17.41 (76 x 442) 2.00 x 17.41 (51 x 442) 2.52 x 17.41 (64 x 442) 3.00 x 17.41 (76 x 442) 3.46 x 17.41 (88 x 442) 2.00 x 21.16 (51 x 537) 3.00 x 21.16 (76 x 537) 3.46 x 21.16 (88 x 537) IR RMS Sym 40kA 50kA 40kA 63kA 35.5kA 50kA 50kA 31.5kA 35.5kA 20kA Recommended fuseclips for DIN style fuses – 270303, A3354745 see page 120. *Not compliant with VDE 0670, part 402. 1 -IR RMS Sym is 63kA 2 -IR RMS Sym is 40kA 3 -IR RMS Sym is 20kA Striker In Operated Position Diameter Dimensions - In (mm) 1.77" 45.0mm For Diameter and Length Dimensions See Table Above 116 0.59" 15.0mm Length 1.02" 1.34" 34.0mm 26.0mm For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses Expulsion Fuse Links for Use in High Voltage Distribution Cut-Outs Specifications Description: Expulsion fuse links available in a wide range of options from 15kV to 72kV in ANSI T&K characteristics. Ratings: Volts: — 15 to 72kV Amps: — 1 to 100A Breaking Capacity: depends on voltage but is approximately 8kA Agency Information: Type T: complies with ANSI C37-42 Type K: complies with ANSI C37-42 Features and Benefits • Wide range of options available from 15kV to 72kV in ANSI T & K characteristics. • Extra rapid option also available. Packaging: Up to and including 50A: 25 in a carton From 60A to 100A: 10 in a carton To avoid incorrect replacement the fuse links have colour coded labels: Pink label: Type XA Yellow label: Type K Green label: Type T Typical Applications: • Primary side transformer protection • Feeder protection • Capacitor bank protection Use of Application Expulsion fuse links current ratings should be selected on the basis of maximum expected transient no damage currents rather than on full load current. In addition, the selection of higher current ratings will reduce the possibility of supply interruption due to transient surges such as those due to lightning strikes. Links should be handled with a reasonable degree of care when installing. Excessively rough handling may damage the element. It is normal, under certain fault conditions, for arc extinguishing material and/or metal particles to be expelled from the fuse assembly. It is therefore recommended that reasonable precautions be taken to prevent the installation being approached by unauthorised persons. How to order - Parts Referencing System 15 25 46 72 1st Letter Type of Current Characteristics 2nd Letter Type of Termination Medium Voltage Fuses Rated Voltage (kV) Rated Current (A) 1, 2, 3, 4, 5, T = complies with ANSI C 37-42 requirements for slow B = a fixed NEMA button head link 6, 7.5, 8, 10, acting T characteristics U = a universal link, with double tail and slip off 12, 15, 20, NEMA button head 25, 30, 40, K = complies with ANSI C 37-42 requirements for fast 50, 60, 65, D = double tailed link without NEMA button 75, 80, 100 acting K characteristics head XA = this type of expulsion fuse link has an extra rapid BR = as pattern B but the button head is characteristic. It is suitable for applications where a attached via a 1/4 UNF thread to allow use of high degree of system protection is required at the an extension rod. expense of discrimination See outline drawings opposite page for S = Solid links rated at 100A are also available in both reference button head and universal versions for fitting into expulsion fuse carriers where required. These can be ordered in a similar way using the abbreviation S, e.g. 15SB, etc Thus a typical ordering reference for a 15kV NEMA Type K, button head 30A fuse link would be 15KB30 expulsion fuse link. The fuse link assembly for a given range is standard to all rated voltages. The exception is that the tail length is varied to suit the dimensions of expulsion carrier of different ratings. For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 117 Medium Voltage Fuses Expulsion Fuse Links for Use in High Voltage Distribution Cut-Outs Dimensions - mm (in) Type kV A 15kV 533 (21”) 25kV 660 (26”) 46kV 787 (31”) 72kV 1016 (40”) Notes: Type BR is similar to button head shown, except that the button head is attached via a 1⁄4 UNF thread. Tails can be cut to any length. 1-50A 60-100A 118 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com Medium Voltage Fuses EEI-NEMA Type K & T and Type H & N FL: Type H and EEI-NEMA Type K & T Fuses Specifications Description: Medium voltage fuses: Type H (high surge), EEI-NEMA Type K (fast-acting), EEI-NEMA Type T (slow-acting). Ratings: Amps: — 1-200A (See Catalog Numbers tables) Features and Benefits • Wide range of EEI-NEMA type fuse links for use in open fuse cutouts • Voltage ratings up to 27kV. • Can be coordinated with other overcurrent protective devices for sectionalizing to isolate feeder branches. Typical Applications • Medium Voltage Fused Cutouts High-surge, Type H fuses are manufactured in ratings of 1, 2, 3, 5, and 8A. They have been developed principally for primary fusing of small-sized transformers. Type H links are manufactured in the universal buttonhead design. Type N Fuses Type N fuses conform to previous NEMA standards and have been superseded by Type K and T links. Type N fuses are manufactured in the universal button design in ratings of 5 through 200A for use in NEMA standard dimensioned cutouts rated through 27kV. EEI-NEMA and High-Surge Universal Tin Element Fuses for Cutouts — Rated to 27kV Non-Removable Button-Head For Standard Open or Enclosed Cutouts Catalog Numbers EEI-NEMA Type H Type K (High (Fast) Surge) FL11H1 FL11K1 FL11K2 FL11H2 FL11H3 FL11K3 FL11H5 FL11K5 FL11K6 — FL11H8 FL11K8 FL11K10 — — FL11K12 FL11K15 — FL11K20 — — FL11K25 — FL11K30 FL11K40 — — FL11K50 FL11K65 — — FL11K80 FL11K100 — — FL11K140 — FL11K200 EEI-NEMA Type T (Slow) FL11T1 FL11T2 FL11T3 FL11T5 FL11T6 FL11T8 FL11T10 FL11T12 FL11T15 FL11T20 FL11T25 FL11T30 FL11T40 FL11T50 FL11T65 FL11T80 FL11T100 FL11T140 FL11T200 Amps 1 2 3 5 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 Removable Button-Head For Cutouts Requiring Removable-Button Links Catalog Numbers EEI-NEMA EEI-NEMA Type K Type T (Fast) (Slow) FL3K1 FL3T1 FL3K2 FL3T2 FL3K3 FL3T3 FL3K5 FL3T5 FL3K6 FL3T6 FL3K8 FL3T8 FL3K10 FL3T10 FL3K12 FL3T12 FL3K15 FL3T15 FL3K20 FL3T20 FL3K25 FL3T25 FL3K30 FL3T30 FL3K40 FL3T40 FL3K50 FL3T50 FL3K65 FL3T65 FL3K80 FL3T80 FL3K100 FL3T100 FL3K140 FL3T140 FL3K200 FL3T200 Amps 1 2 3 5 6 8 10 12 15 20 25 30 40 50 65 80 100 140 200 Medium Voltage Fuses High-Surge Type H Fuses Catalog Numbers Adapter-type removable-button links with ferrule adapter to convert to double-leader links are available in K and T types. Order by description. EEI-NEMA Type K Universal Silver-Element Fuses for Cutouts — Rated through 27kV Non-Removable Button-Head For Standard Open or Enclosed Cutouts Catalog Numbers EEI-NEMA Type K Amps FL12K8 8 FL12K10 10 FL12K12 12 FL12K15 15 FL12K25 25 FL12K50 50 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com 119 Medium Voltage Fuses Fuseclips for Medium & High Voltage Fuses Fuse Diameter in (mm) 2 (50.8) 3 (76) 1.77 (45) Recommended Fuseclips for Medium Voltage Fuses Catalog Numbers A3354710 A3354730 A3354745 A 3.749 4.139 3.50 B 1.979 2.449 2.50 Clip Dimensions (in) C D E 2.009 1.189 4.539 3.009 1.189 5.639 1.77 1.19 4.50 Fuseclips are for single barrel applications only. Are not sold in pairs. F 1.509 1.509 1.50 G 0.399 0.399 0.38 C A G F E D B 1A0065 3˝ Diameter Clip 270303 DIN Fuseclip A 0.99" 25.0mm 4.06" 103mm A 0.43" 10.8mm 9078A67G04 3˝ Diameter Clip 2 Cup assemblies per package. Dimensions shown are for reference only. 120 For detailed information, visit the Electrical IEC section at www.cooperbussmann.com