TECHNICAL INFORMATION
Cable Gland ATEX marking
Equipment Form of Protection
Code
Protection Method
IEC BASED STANDARD
Ex‘d’
Flameproof
EN60079-1:2004 (IEC60079-1:2003)
Ex‘e’
Increased Safety
EN60079-7:2003 (IEC60079-7:2001)
Ex‘i’
Intrinsic Safety
EN60079-11:2006 (IEC60079-11:2006)
Ex‘o’
Oil immersion
IEC60079-6 : 1995
Ex‘p’
Pressurisation
EN60079-2:2004 (IEC60079-2:2001)
Ex‘m’
Encapsulation
EN60079-18:2004 (IEC60079-18:2004)
Ex‘q’
Sand/Quartz Filled
Ex‘nW’
Enclosed Break
Ex‘nA’
Non-Sparking
Ex‘nR’
Restricted Breathing
Ex‘nL’
Energy Limitation
IEC60079-5 : 1997
EN60079-15:2005 (IEC60079-15 : 2005)
Temperature Classification (IEC60079-20)
Max, surface temperature
Temperature Class
Remarks
(℃)
T1
450 ℃
T2
300 ℃
Its maximum temperature will not reach
T3
200 ℃
the ignition temperature of gas or vapors.
T4
135 ℃
T5
100 ℃
T6
85 ℃
The apparatus is only for use in service
temperature of -20℃ to 40℃.
Relative Standards
IEC Standards
A4
CENELEC Standrds (EN)
Ex‘d’
Ex‘e’
Ex‘o’
60079-1
60079-7
60079-6
Ex‘d’
Ex‘e’
Ex‘o’
50018
50019
50015
www.dongabestech.com
동아내지1수(A~E)-수정2
2015.4.9 11:38 AM
페이지A5
MAC2 Lower-2540-color 2540DPI 175LPI
TECHNICAL INFORMATION
Gas Group (IEC & NEC)
IEC Gas Group
Typical Gas
N.America Gas Group
ⅡA
Propane,Butane,Petrolium,Amonia
Class Ⅰ , Group D
ⅡB
Ethylene,Ether
Class Ⅰ , Group C
Acethylene
Class Ⅰ , Group A
Hydrogen
Class Ⅰ , Group B
ⅡC
Ⅰ
Methane, Firedamp
Hazards
IEC
North America
Gas & Vapor
Gas Group Ⅱ
Class Ⅰ
Dust
Gas Group Ⅰ
Class Ⅱ
CABLE GLAND SEALING TEST
The requirements for thermal endurance to heat and thermal endurance to cold prescribed in IEC60079-0 shall
be applied on samples assembled according to the manufacturer's instructions either with a mandrel or a cable
as required.
This test shall be carried out using, for each type of cable gland sealing device, one sealing ring from each of
the different permitted sizes. In the case of elastomeric sealing rings, each ring is mounted on a clean, dry,
polished mild steel cylindrical mandrel of diameter, equal to the smallest cable diameter permissible in the ring,
as specified by the manufacturer
of the cable gland.
In the case of metalic or composite sealing rings, each ring is mounted on the metal sheathof a clean dry
sample of cable, of diameter equal to the smallest diameter permissible in the ring, as specified by the
manufacturer of the cable gland.
The assemble is then fitted into the entry and torgue is applied to the screw or nut to obtain a seal under a
hydraulic pressure of 2000 kPa for Group I and 3000 kPa for Group II.
The seling is considered satisfactory if the blotting paper is free from any trace of leakage when the pressure
has been maintained at 2000 kPa for Group I or 3000 kPa for Group II for at least 10s.
1
2
3
4
5
6
7
8
9
hydraulic pump
pressure gauge
hose
blotting paper
adapter
sealing ring
mandrel/metal-sheathed cable
compression component
retaining clamp
www.dongabestech.com
A5
동아내지1수(A~E)-수정2
2015.4.9 11:38 AM
페이지A6
MAC2 Lower-2540-color 2540DPI 175LPI
TECHNICAL INFORMATION
Area Classification(IEC EN 60079-10)
Flammable Gases & Vapors
Zone 0
An area in which an explosive atmosphere occurs constantly present,
or over long periods.
Zone 1
An area in which an explosive atmosphere occurs in normal operations.
Zone 2
An area in which an explosive atmosphere occurs in normal operations
and It will exist for a short time if it occurs.
Combustible Dusts
Zone 20
An area in which combustible dust, as a cloud, is present continuously or
frequently, during normal operation, in sufficient quantity to be capable of
producing an explosive concentration of combustible dust mixture with air.
Zone 21
An area in which combustible dust, as a cloud, is occasionally present during
normal operation, in sufficient quantity to be capable of producing an
explosive concentration of combustible dust in a mixture with air.
Zone 22
An area in which combustible dust, as a cloud, may occur infrequently and
combustible dust may give rise to an explosive concentration of combustible
dust in mixture with air.
North America Hazardours Areas
Hazardous areas in the U.S.A, are sub divided into Class I,II,III, as belows ;
Zone 0
Zone 2
Division 2
Class I
Division 1
Division 2
Zone 1
Division 1
Class II
Class III
Division 1
Division 2
Class I
Class II
Class III
Division 1
: Flammable Gases, Vapors or Liquids
: Combustible Dusts
: Ignitable Fibres and Flyings
: Where ignitable concentrations of flammable gases,vapors or liquids
can exist all of the time or some time under normal operating conditions.
Division 2 : Where ignitable concentrations of flammable gases,vapors or liquids
are not likely to exist under normal operating.
Zone 0
: Where ignitable concentrations of flammable gases,vapors or liquids
can exist all of the time or for long periods at time under normal operation conditions.
Zone 1
: Where ignitable concentrations of flammable gases,vapors or liquids
can exist some of the time under normal operating conditions.
Zone 2
: Where ignitable concentrations of flammable gases,vapors or liquids
are not likely to exist under normal operating.
(*) : There is no Zone classification for dusts,fibes or flyings at present in the NEC.
A6
www.dongabestech.com
Zone 2
Division 1
Division 2
Zone 0
Division 1
Zone 1
no Zone(*)
동아내지1수(A~E)-수정2
2015.4.9 11:38 AM
페이지A7
MAC2 Lower-2540-color 2540DPI 175LPI
TECHNICAL INFORMATION
IP(Ingress Protection class of enclosure) according to IEC-60529 standard
The test shall be carried out in accordance with IEC60529 as below, using one cable-sealing ring of each of the different
permitted sizes for each type of cable gland.
Group I - IP54 minimum
Group II - IP54 minimum
Group III - IP6X minimum
Group IIIC - IP6X minimum
Group IIIA or IIIC - IP5X minimum
For sealing tests, each sealing ring shall be mounted on a sample of clean, dry cable; or a clean, dry, polished, metal
mandrel, with a maximum surface roughness of 1,6 ㎛ Ra. Of a diameter equal to the smallest diameter allowable in the
ring as specified by the manufacturer of the cable gland. For the purpose of this test, the cable gland with cable or mandrel
shall be tested after being fixed to a suitable enclosure ensuring that the sealing method at the interface between the
gland and enclosure does not compromise the test results.
Second #
First #
0
Non-potected
0
Non-protected
1
Protected against
objects of 50mm dia
and greater
1
Protected against
vertically falling water
drops
2
Protected against
objects of 50mm dia
and greater
2
Protected against
vertically falling water
drops when enclosure
tilted up to 15°
3
Protected against
solid foreign objects
of 12.5mm dia
and greater
3
Protected against
spraying water.
4
Protected against
of 1.0mm dia
and greater
4
Protected against
splashing water.
5
Dust-protected
5
Protected against
water jet
6
Dust-tight
6
Protected against
powered jets
7
Protected against the
effects of temporary
immersion in water
for 30 min,
15cm min
8
Protected against the
effects of continuous
immersion in water.
eg. IP68 - No ingress of dust and protection against the effects of continuous immersion in water.
www.dongabestech.com
A7
동아내지1수(A~E)-수정2
2015.4.9 11:38 AM
페이지A8
MAC2 Lower-2540-color 2540DPI 175LPI
TECHNICAL INFORMATION
COLD FLOW CHARACTERISTICS
IEC 60079 - 14 Clause 9.1.4 states that The connection of cables and conduits to the electrical appartus shall be made in
accordance with the requirements of the relevant type of protection.
Care should be taken when selecting a suitable cable entry devise in conjunction with certain types of cable employing
materials which can exhibit "cold flow" characteristics.
By way of example "cable entry devices not employing compression seals which act upon parts(s) of the cable having cold
flow characteristics" should be employed.
"Low smoke and/or fire-resistant cables usually exhibit cold flow characteristics".
"Cold flow can be more fully described as thermoplastic materials which flow when subjected to pressure at ambient
temperature".
Compound Barrier Cable Gland for Direct Cable Entry.
Ex 'd' & Ex'e' IIC & Class I Division I
Cable Glands to maintain integrity of type of protection Flameproof Enclosures Ex'd' using
"Direct Cable Entry" into the flameproof enclosures as defined in IEC60079-14 "Electrical apparatus for explosive gas
atmospheres Part 14 : Electrical installations in hazardous areas".
Sealing Compound (Epoxy Resin)
EARTH TAG-Correct Installation Configurations
Installed without Adaptor or Reducer
EARTH TAG
Installed with Adaptor or Reducer
Installed threaded hole
Installed clearance hole
EARTH TAG
EARTH TAG
A8
www.dongabestech.com
동아내지1수(A~E)-수정2
2015.4.9 11:38 AM
페이지A9
MAC2 Lower-2540-color 2540DPI 175LPI
CABLE GLAND INSTRUCTION
General description of DEX-A type(E1FW & E1FX) Cable Gland
Armour Clamp Ring Installation
1. Armour Clamp Ring “X” or “W” : Gland Size M16 to M32 : 20 mm
1. Armour Clamp Ring “X” or “W” : Gland Size M40 to M75 : 25 mm
2. Support Ring :
”on the ring for SWA cable
Marked“W”
”on the ring for Wire Braided Armour cable
Marked“X”
1. Back Nut
2. Outer Seal Clamp
3. Outer Seal
4. Outer Seal Stay
5. Middle Nut
6-1. Armour Clamp Ring“X”or“W”
6-2. Support Ring
7. Armour Cone
8. Inner Seal
9. Entry Adapter (Metric, NPT, PG)
10. Lock Nut
9-(*)
8
7
6-(1)
2
6-(2)
4
3
A
1
2
A
In case of support ring(6-2),
This ring is only used for DEX type
cable gland.
Other types of cable Glands will not
use 6-2 support ring.
NOTE :
Assembly Instruction of Cable glands for safe installation EC Declation of Conformity shall be provided with each package of
cable gland.
www.dongabestech.com
A9