® DSX Access Systems, Inc. DSX Controller Addressing Controller Addressing Each Controller has an 8 position dipswitch to set its address. The Master Controller is addressed as the Location number and has switch 8 turned on. Turn on switches 1-7 to set the Location number. Each switch has a binary value and when added together equal the Location number. Add the values of each switch turned on. To set the Master address above 127 set switches 1-7 off and program the address using KB2CW.exe from the WinDSX directory. Set the Slave device address starting at 2. Both Devices of all controllers must be defined in the database but only the even number is programmed by the dipswitches. Side A = even number set by the switches. Side B = next highest odd number. The Master is always device address 0 & 1 in the database. Switch 8 is only turned on at the Master Controller. DSX-1048 Controller Addressing Communications Method 32,000 Locations per Host PC / Comm Server 1 Location Can Include: (Up to 64 Controllers) (1 Master and 63 Slaves) (128 Devices) S N WI U T M C BE H R First Controller is Location Master Devices 0 & 1 (Master controller) 104x Devices 2 & 3 (1st Slave controller) 104x Devices 4 & 5 (2nd Slave controller) 104x Devices 6 & 7 (3rd Slave controller) 104x Communications Distribution Module 1040CDM IN OUT DIP Switch setting for Master Controller Switch 1 value = 1 Switch 8 = Master Total value = Loc 1s Master Controller 1 2 3 4 5 6 7 8 1 2 4 8 16 32 64 MAS/SLV ON DIP Switch setting for first Slave Switch 2 value = 2 Total value = 2 Switch 3 value = 4 Total value = 4 1 2 4 8 16 32 64 MAS/SLV Switch 2 value = 2 Switch 3 value = 4 Total value = 6 OFF 1 2 3 4 5 6 7 8 1 2 4 8 16 32 64 MAS/SLV ON DIP Switch setting for third Slave OFF 1 2 3 4 5 6 7 8 ON DIP Switch setting for second Slave SW VA IT LU CH E Equals ON Equals OFF Note /// Dip Switch Down on the Left Side = ON Note /// Dip Switch Down on the Right Side = OFF OFF 1 2 3 4 5 6 7 8 1 2 4 8 16 32 64 MAS/SLV ON OFF Note /// Dip Switch at a Master panel must equal the Location #. Note /// Dip Switch at a Slave panel must equal Device Address of Side A. DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238 / 888-419-8353 / www.dsxinc.com 8/2011 DSX-1022 Controller Addressing Comm Method 32,000 Locations per Host PC / Comm Server 1 Location Can Include: (Up to 64 Controllers) (1Master and 63 Slaves) (128 Devices) Note /// Dip Switch Down on the Left Side = ON Device Address: Location # S N WI U T M C BE H R First panel is Location Master DIP Switch setting for Master Controller Location 1 Master Devices 0&1 (MASTER) Switch 1 value = 1 Switch 8 = Master Total Value = Loc 1s Master RS-485 1 2 3 4 5 6 7 8 ON Device Address: 2 Devices 2&3 (SLAVE 1) DIP Switch setting for first Slave Switch 2 value = 2 Total value = 2 RS-485 4 Devices 4&5 (SLAVE 2) DIP Switch setting for second Slave Switch 3 value = 4 Total value = 4 RS-485 Device Address: 6 Devices 6&7 (SLAVE 3) Switch 2 value = 2 Switch 3 value = 4 Total value = 6 To addional Slave Controllers OFF 1 2 4 8 16 32 64 MAS/SLV OFF 1 2 3 4 5 6 7 8 1 2 4 8 16 32 64 MAS/SLV ON DIP Switch setting for third Slave 1 2 4 8 16 32 64 MAS/SLV 1 2 3 4 5 6 7 8 ON Device Address: SW VA IT LU CH E Equals ON Equals OFF Note /// Dip Switch Down on the Right Side = OFF OFF 1 2 4 8 16 32 64 MAS/SLV 1 2 3 4 5 6 7 8 ON OFF Note /// Dip Switch at a Master panel must equal the Location #. Note /// Dip Switch at a Slave panel must equal Device Address of Side A. DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238 / 888-419-8353 / www.dsxinc.com 8/2011