LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976 F-35 FOREIGN MILITARY SALES TRAINING FACILITIES 14708 W SUPER SABRE 100% CONSTRUCTION DOCUMENTS LUKE AIR FORCE BASE, ARIZONA 85309 April 28, 2015 SECTION 211300 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: Complete wet-pipe automatic fire sprinkler system as indicated on the Drawings and as specified. 1.02 SUBMITTALS A. Preliminary Shop Drawings: Prior to detailed submission, submit preliminary layout of finished ceiling areas indicating only head locations coordinated with ceiling installation. B. Shop Drawings: Provide hydraulic calculations, detailed pipe layout, hangers and supports, components and accessories. Indicate system controls. C. Product Data: Provide data on sprinkler heads, valves, and specialties, including manufacturers' catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections. D. Submit shop drawings, product data, hydraulic calculations to authority having jurisdiction if required. E. Manufacturer's Certificate: Certify that system has been tested and meets or exceeds specified requirements. 1.03 SYSTEM DESCRIPTION A. System to provide coverage for building areas noted on Drawings. B. Provide system to NFPA 13 ordinary hazard, Group 1 occupancy requirements. C. Determine volume and pressure of incoming water supply from water flow test data. If not available assume [ TBD ] gpm at [ TBD ] psig. Revise design when test data available prior to submittals. Fire sprinkler contractor to perform new fire flow tests prior to design and submittal of fire sprinkler drawings for review. D. Interface system with [building control system] [building fire and smoke alarm system]. E. Provide Fire Department connections as indicated on Drawings. 1.04 RECORD DOCUMENTS A. Record actual locations of sprinkler heads and deviations of piping from drawings. Indicate drain and test locations. 211300 - 1 LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976 F-35 FOREIGN MILITARY SALES TRAINING FACILITIES 14708 W SUPER SABRE 100% CONSTRUCTION DOCUMENTS LUKE AIR FORCE BASE, ARIZONA 85309 April 28, 2015 1.05 OPERATION AND MAINTENANCE DATA A. Maintenance Data: Include components of system, servicing requirements, Record Drawings, inspection data, replacement part numbers and availability, and location and numbers of service depot. 1.06 QUALITY ASSURANCE A. Perform Work in accordance with NFPA 13. B. Equipment and Components: Bear UL and FM label or marking, as applicable. C. Qualifications: 1. Installer: Company specializing in performing work of this Section with minimum 3 years experience. 2. Design sprinkler system under direct supervision of Professional Engineer experienced in design of this work and licensed in the State of Arizona. D. Regulatory Requirements: 1. Hydraulic calculations, product data, shop drawings: Bear stamp of approval of authority having jurisdiction. PART 2 - PRODUCTS 2.01 APPROVED MANUFACTURERS A. The following manufacturers are approved for use subject to the detailed requirements of the Drawings and Specifications. 1. Alarm Check Valves: Viking, Reliable, Gem, Star, Central. 2. Alarm Gong: Viking, Reliable, Grinnell, Star, Central. 3. Hangers: Elcen, Fee & Mason, Grinnell, F&M, Michigan. 4. Fire Department Connections: Standard, Sierra, J&L Industries, Potter Roemer. 5. Check, Gate, and Globe Valves: Jenkins, Crane, Mueller, Kennedy, Grinnell, United, Nibco, Clow, Central. 6. Butterfly Valves: Grinnell, Demco, Keystone, Milwaukee, Kennedy, Watts. 2.02 MATERIALS A. Pipe: 1. Underground Pipe and Fittings: Class 150 centrifugal cast iron or cement-line mechanical joint, "Tyton" joint, conforming to AWWA Specification C-106, or "Permastran" conforming to ASTM D2992 and ASTM D2996. 2. Above Grade Pipe and Fittings: Black steel or wrought iron conforming to ASTM Specifications for black and hot dipped zinc coated (galvanized) welded and seamless steel pipe for ordinary uses, A120 or for welded wrought iron pipe A72. Fittings shall be welded, screwed, or grooved mechanical joint. 3. Minimum wall thickness for piping used for welding or roll grooving shall be as follows: Schedule 10 for sizes up to 5 inches 0.134 for 6 inches 0.188 for 8-inches and 10-inches 211300 - 2 LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976 F-35 FOREIGN MILITARY SALES TRAINING FACILITIES 14708 W SUPER SABRE 100% CONSTRUCTION DOCUMENTS LUKE AIR FORCE BASE, ARIZONA 85309 April 28, 2015 4. Minimum wall thickness for piping used for threaded connections or cut grooves shall be as follows: Schedule 40 for sizes up to 8 inches Schedule 30 for 8 inches and larger B. Valves: 1. O.S. & Y.: Kennedy iron body bronze mounted, double disc with parallel seats. 2. Butterfly: Grinnell IWU-LUG ductile iron body, stainless steel stem, aluminum bronze disc, phenolic ring and Buna N seat. 3. Check: Kennedy Figure 125 for piping 2-1/2 inch through 3 inch screwed ends, or Figure 126 for piping 2-1/2 inch through 8 inch flanged ends; cast iron body bronze mounted with bronze disc. 4. Alarm Valve: Grinnell Model A complete with basic trimmings and standard alarm trimmings. 5. Alarm Gong: Grinnell Model B-3. C. Sprinklers: 1. Pendant and Upright: Grinnell Model F950 Duraspeed sprinklers, 1/2 inch orifice, with SSP-2 and SSU-3 deflector. a. Automatic sprinkler heads shall be suitable for use intended including proper temperature rating as required by NFPA Standards for Installations of Sprinkler Systems Pamphlet No. 13. Heads in finished areas to be chrome plated and heads in unfinished areas to be rough brass. Furnish 23 spare heads of jack type with same ratings and wrench in suitable cabinet or receptacle. D. Piping Hangers: 1. Shall conform to NFPA and UL standards for spacing, number, size, and type. Pipe to be generally supported by clamps and rods secured to overhead construction. E. Fire Department Pumper Connection: 1. Wall Type: Cast bronze, polished chrome plated approved automatic sprinkler connection complete as specified on the Drawings. 2. Sidewalk Type: Cast bronze, polished chrome plated approved automatic sprinkler connection complete as specified on the Drawings. Secure in 18 inch x 18 inch x 10 inch deep concrete pad. 3. Escutcheon Plates and Sleeves: a. Escutcheon plates: Provide chrome plated escutcheon plates wherever pipes pass through finished walls, floors, or ceiling. Provide prime coat painted escutcheon plates wherever pipes pass through walls, floors, or ceilings in unfinished exposed areas. b. Sleeves: Unless otherwise detailed or required by code, provide 20 gauge galvanized sleeves around all pipes passing through walls and floors packed with Thical. PART 3 - EXECUTION 3.01 PREPARATION A. Examine architectural drawings for information pertinent to installation of piping and sprinkler heads. B. Coordinate work of this Section with other affected work. 211300 - 3 LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976 F-35 FOREIGN MILITARY SALES TRAINING FACILITIES 14708 W SUPER SABRE 100% CONSTRUCTION DOCUMENTS LUKE AIR FORCE BASE, ARIZONA 85309 April 28, 2015 3.02 INSTALLATION - PIPING A. Sprinkler piping shall be concealed above ceiling where possible. Sprinkler heads in ceiling shall be chrome plated, unless noted otherwise. Sprinkler heads located in rooms where there is no ceiling may be standard bronze upright or pendant as required. Sprinkler heads located in areas with lay-in acoustical ceilings shall be centered in lay-in acoustical unit. B. Screw Jointed: Cut pipe accurately to measurements established at building. Work into place without springing or forcing. Proper provision shall be made for expansion and contraction of piping. Pipe and fittings shall be free from burrs and fins. All pipe shall be threaded and reamed. Apply lubricant to male threads only. Full cut thread and no more than three threads shall remain exposed on the pipe after threading. C. Protection: Protect materials, fittings and fixtures properly and effectively. Pipe openings shall be closed so as to prevent obstructions and damage. D. Drainage: System drainage shall be provided from alarm valve through line controlled by globe valve and extended to exterior of building. Wherever piping is trapped, an auxiliary draw-off shall be provided. All piping to drain back to alarm valve except where auxiliary drains are provided. E. Welding: On-site welding of sprinkler piping will not be permitted. F. Groove Joining: Pipe joined with mechanical grooved couplings shall be joined by a listed combination of couplings, gaskets and grooves. Grooves cut or rolled on pipe shall be dimensionally compatible with the coupling. G. Freeze Protection: All wet sprinkler system piping and components shall be located inside of building insulation systems so building heating system will prevent piping from freezing or shall be adequately protected by insulation and heat tape with emergency power source as necessary to prevent freezing. H. In general, install sprinkler piping at maximum height throughout the building. Offset piping as required to clear mechanical ductwork, piping, building structure, etc. I. The mechanical systems installation (equipment, ductwork, piping, etc.) shall have priority over space within the building. J. Sprinkler heads located 7 feet or less above finished floor elevation shall be provided with approved guards. 3.03 INSTALLATION - GENERAL A. Install equipment in accordance with manufacturer's instructions. B. Install buried shut-off valves in valve box. Provide post indicator and tamper switch. C. Provide listed double check back-flow device at sprinkler system water source connection, per Clean Water Act 1985. D. Locate Fire Department connection with sufficient clearance from walls, obstructions, or adjacent Siamese connectors to allow full swing of Fire Department wrench handle. E. Locate outside alarm gong on building wall as indicated. 211300 - 4 LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976 F-35 FOREIGN MILITARY SALES TRAINING FACILITIES 14708 W SUPER SABRE 100% CONSTRUCTION DOCUMENTS LUKE AIR FORCE BASE, ARIZONA 85309 April 28, 2015 3.04 FIELD QUALITY CONTROL A. Testing and Flushing: 1. Overhead Sprinkler Piping: Test for a period of two hours at hydrostatic pressure of 200 lbs. All piping, valves, heads, etc. shall be watertight. 2. Underground Piping: Tested for a period of 2 hours at hydrostatic pressure of 200 lbs. in accordance with NFPA Pamphlet No. 13. Leakage shall not exceed quantities indicated. 3. A test shall be made before pipe located in trench is backfilled. 4. Thoroughly flush underground piping in accordance with NFPA Pamphlet No. 13. The flush test must be witnessed by a governing authority. 5. Conduct full quarterly inspection before acceptance. 6. A full test shall be conducted and observed by Base maintenance personnel. 7. Notify the Contracting Officer one week in advance regarding time and date of all tests. END OF SECTION 211300 - 5