LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
100% CONSTRUCTION DOCUMENTS
LUKE AIR FORCE BASE, ARIZONA 85309
April 28, 2015
SECTION 211300
WET-PIPE SPRINKLER SYSTEMS
PART 1 - GENERAL
1.01
SUMMARY
A. Section Includes: Complete wet-pipe automatic fire sprinkler system as indicated on the
Drawings and as specified.
1.02
SUBMITTALS
A. Preliminary Shop Drawings: Prior to detailed submission, submit preliminary layout of finished
ceiling areas indicating only head locations coordinated with ceiling installation.
B. Shop Drawings: Provide hydraulic calculations, detailed pipe layout, hangers and supports,
components and accessories. Indicate system controls.
C. Product Data: Provide data on sprinkler heads, valves, and specialties, including manufacturers'
catalog information. Submit performance ratings, rough-in details, weights, support
requirements, and piping connections.
D. Submit shop drawings, product data, hydraulic calculations to authority having jurisdiction if
required.
E. Manufacturer's Certificate: Certify that system has been tested and meets or exceeds specified
requirements.
1.03
SYSTEM DESCRIPTION
A. System to provide coverage for building areas noted on Drawings.
B. Provide system to NFPA 13 ordinary hazard, Group 1 occupancy requirements.
C. Determine volume and pressure of incoming water supply from water flow test data. If not
available assume [ TBD ] gpm at [ TBD ] psig. Revise design when test data available
prior to submittals. Fire sprinkler contractor to perform new fire flow tests prior to design and
submittal of fire sprinkler drawings for review.
D. Interface system with [building control system] [building fire and smoke alarm system].
E. Provide Fire Department connections as indicated on Drawings.
1.04
RECORD DOCUMENTS
A. Record actual locations of sprinkler heads and deviations of piping from drawings. Indicate drain
and test locations.
211300 - 1
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
100% CONSTRUCTION DOCUMENTS
LUKE AIR FORCE BASE, ARIZONA 85309
April 28, 2015
1.05
OPERATION AND MAINTENANCE DATA
A. Maintenance Data: Include components of system, servicing requirements, Record Drawings,
inspection data, replacement part numbers and availability, and location and numbers of service
depot.
1.06
QUALITY ASSURANCE
A. Perform Work in accordance with NFPA 13.
B. Equipment and Components: Bear UL and FM label or marking, as applicable.
C. Qualifications:
1. Installer: Company specializing in performing work of this Section with minimum 3 years
experience.
2. Design sprinkler system under direct supervision of Professional Engineer experienced in
design of this work and licensed in the State of Arizona.
D. Regulatory Requirements:
1. Hydraulic calculations, product data, shop drawings: Bear stamp of approval of authority
having jurisdiction.
PART 2 - PRODUCTS
2.01
APPROVED MANUFACTURERS
A. The following manufacturers are approved for use subject to the detailed requirements of the
Drawings and Specifications.
1. Alarm Check Valves: Viking, Reliable, Gem, Star, Central.
2. Alarm Gong: Viking, Reliable, Grinnell, Star, Central.
3. Hangers: Elcen, Fee & Mason, Grinnell, F&M, Michigan.
4. Fire Department Connections: Standard, Sierra, J&L Industries, Potter Roemer.
5. Check, Gate, and Globe Valves: Jenkins, Crane, Mueller, Kennedy, Grinnell, United, Nibco,
Clow, Central.
6. Butterfly Valves: Grinnell, Demco, Keystone, Milwaukee, Kennedy, Watts.
2.02
MATERIALS
A. Pipe:
1. Underground Pipe and Fittings: Class 150 centrifugal cast iron or cement-line mechanical
joint, "Tyton" joint, conforming to AWWA Specification C-106, or "Permastran" conforming to
ASTM D2992 and ASTM D2996.
2. Above Grade Pipe and Fittings: Black steel or wrought iron conforming to ASTM
Specifications for black and hot dipped zinc coated (galvanized) welded and seamless steel
pipe for ordinary uses, A120 or for welded wrought iron pipe A72. Fittings shall be welded,
screwed, or grooved mechanical joint.
3. Minimum wall thickness for piping used for welding or roll grooving shall be as follows:
Schedule 10 for sizes up to 5 inches
0.134 for 6 inches
0.188 for 8-inches and 10-inches
211300 - 2
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
100% CONSTRUCTION DOCUMENTS
LUKE AIR FORCE BASE, ARIZONA 85309
April 28, 2015
4. Minimum wall thickness for piping used for threaded connections or cut grooves shall be as
follows:
Schedule 40 for sizes up to 8 inches
Schedule 30 for 8 inches and larger
B. Valves:
1. O.S. & Y.: Kennedy iron body bronze mounted, double disc with parallel seats.
2. Butterfly: Grinnell IWU-LUG ductile iron body, stainless steel stem, aluminum bronze disc,
phenolic ring and Buna N seat.
3. Check: Kennedy Figure 125 for piping 2-1/2 inch through 3 inch screwed ends, or Figure 126
for piping 2-1/2 inch through 8 inch flanged ends; cast iron body bronze mounted with bronze
disc.
4. Alarm Valve: Grinnell Model A complete with basic trimmings and standard alarm trimmings.
5. Alarm Gong: Grinnell Model B-3.
C. Sprinklers:
1. Pendant and Upright: Grinnell Model F950 Duraspeed sprinklers, 1/2 inch orifice, with SSP-2
and SSU-3 deflector.
a. Automatic sprinkler heads shall be suitable for use intended including proper temperature
rating as required by NFPA Standards for Installations of Sprinkler Systems Pamphlet
No. 13. Heads in finished areas to be chrome plated and heads in unfinished areas to be
rough brass. Furnish 23 spare heads of jack type with same ratings and wrench in
suitable cabinet or receptacle.
D. Piping Hangers:
1. Shall conform to NFPA and UL standards for spacing, number, size, and type. Pipe to be
generally supported by clamps and rods secured to overhead construction.
E. Fire Department Pumper Connection:
1. Wall Type: Cast bronze, polished chrome plated approved automatic sprinkler connection
complete as specified on the Drawings.
2. Sidewalk Type: Cast bronze, polished chrome plated approved automatic sprinkler
connection complete as specified on the Drawings. Secure in 18 inch x 18 inch x 10 inch
deep concrete pad.
3. Escutcheon Plates and Sleeves:
a. Escutcheon plates: Provide chrome plated escutcheon plates wherever pipes pass
through finished walls, floors, or ceiling. Provide prime coat painted escutcheon plates
wherever pipes pass through walls, floors, or ceilings in unfinished exposed areas.
b. Sleeves: Unless otherwise detailed or required by code, provide 20 gauge galvanized
sleeves around all pipes passing through walls and floors packed with Thical.
PART 3 - EXECUTION
3.01
PREPARATION
A. Examine architectural drawings for information pertinent to installation of piping and sprinkler
heads.
B. Coordinate work of this Section with other affected work.
211300 - 3
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
100% CONSTRUCTION DOCUMENTS
LUKE AIR FORCE BASE, ARIZONA 85309
April 28, 2015
3.02
INSTALLATION - PIPING
A. Sprinkler piping shall be concealed above ceiling where possible. Sprinkler heads in ceiling shall
be chrome plated, unless noted otherwise. Sprinkler heads located in rooms where there is no
ceiling may be standard bronze upright or pendant as required. Sprinkler heads located in areas
with lay-in acoustical ceilings shall be centered in lay-in acoustical unit.
B. Screw Jointed: Cut pipe accurately to measurements established at building. Work into place
without springing or forcing. Proper provision shall be made for expansion and contraction of
piping. Pipe and fittings shall be free from burrs and fins. All pipe shall be threaded and reamed.
Apply lubricant to male threads only. Full cut thread and no more than three threads shall remain
exposed on the pipe after threading.
C. Protection: Protect materials, fittings and fixtures properly and effectively. Pipe openings shall
be closed so as to prevent obstructions and damage.
D. Drainage: System drainage shall be provided from alarm valve through line controlled by globe
valve and extended to exterior of building. Wherever piping is trapped, an auxiliary draw-off shall
be provided. All piping to drain back to alarm valve except where auxiliary drains are provided.
E. Welding: On-site welding of sprinkler piping will not be permitted.
F. Groove Joining: Pipe joined with mechanical grooved couplings shall be joined by a listed
combination of couplings, gaskets and grooves. Grooves cut or rolled on pipe shall be
dimensionally compatible with the coupling.
G. Freeze Protection: All wet sprinkler system piping and components shall be located inside of
building insulation systems so building heating system will prevent piping from freezing or shall
be adequately protected by insulation and heat tape with emergency power source as necessary
to prevent freezing.
H. In general, install sprinkler piping at maximum height throughout the building. Offset piping as
required to clear mechanical ductwork, piping, building structure, etc.
I.
The mechanical systems installation (equipment, ductwork, piping, etc.) shall have priority over
space within the building.
J.
Sprinkler heads located 7 feet or less above finished floor elevation shall be provided with
approved guards.
3.03
INSTALLATION - GENERAL
A. Install equipment in accordance with manufacturer's instructions.
B. Install buried shut-off valves in valve box. Provide post indicator and tamper switch.
C. Provide listed double check back-flow device at sprinkler system water source connection, per
Clean Water Act 1985.
D. Locate Fire Department connection with sufficient clearance from walls, obstructions, or adjacent
Siamese connectors to allow full swing of Fire Department wrench handle.
E. Locate outside alarm gong on building wall as indicated.
211300 - 4
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
100% CONSTRUCTION DOCUMENTS
LUKE AIR FORCE BASE, ARIZONA 85309
April 28, 2015
3.04
FIELD QUALITY CONTROL
A. Testing and Flushing:
1. Overhead Sprinkler Piping: Test for a period of two hours at hydrostatic pressure of 200 lbs.
All piping, valves, heads, etc. shall be watertight.
2. Underground Piping: Tested for a period of 2 hours at hydrostatic pressure of 200 lbs. in
accordance with NFPA Pamphlet No. 13. Leakage shall not exceed quantities indicated.
3. A test shall be made before pipe located in trench is backfilled.
4. Thoroughly flush underground piping in accordance with NFPA Pamphlet No. 13. The flush
test must be witnessed by a governing authority.
5. Conduct full quarterly inspection before acceptance.
6. A full test shall be conducted and observed by Base maintenance personnel.
7. Notify the Contracting Officer one week in advance regarding time and date of all tests.
END OF SECTION