Denver Public Schools Purchasing Department 1617 S. Acoma St. Denver, Colorado 80223 INVITATION TO BID 15-BS-2478 ADDENDUM NUMBER FOUR July 15, 2015 THIS ADDENDUM MUST BE ACKNOWLEDGED. THIS ADDENDUM SHALL BECOME A PART OF THIS SOLICITATION. Amend Invitation to Bid 15-BS-2478 as follows: Please see attached documents that were to be part of addendum 3. Please note that the bid due date and time have been changed. Bids will now be due on August 4, 2015 at 10:00 AM. If your proposal has been submitted and you wish to amend it, please modify your proposal on company letterhead. The amended proposal must be received prior to or included at the time and date set for the proposal opening. Each modification submitted to the District's Purchasing Office located at 1617 S. Acoma St. Denver, CO 80223. It must have Vendor’s name and return address and the applicable RFP number and title of the RFP clearly marked on the face of the envelope. If more than one modification is submitted, the modification bearing the latest date of receipt by the District's Strategic Sourcing Office will be considered the valid modification. *****This addendum must be acknowledged, whether or not you amend your proposal.***** This Addendum must be included in your submittal or proposal, providing you do not need to amend your proposal. PRINT OR TYPE YOUR INFORMATION Name of Company: ____________________________________________ Fax: _____________ Address: ________________________ City/State: ________________ Zip: ______________ Contact Person: ___________________ Title: _____________________ Phone: ___________ Authorized Representative’s Signature: ____________________________ Phone: ___________ Printed Name: ____________________ Title: _____________________ Date: _____________ Approved by: ______________ Date: _____________ Reviewed by: ______________ Date: _____________ 15-BS-2478 Addendum # 4 MECHANICAL UNIT UNISTRUT FRAME SET 1' O.C. TO SUPPORT UNIT - DO NOT FASTEN THROUGH TOP OF CURB 24 GA. GALV. SHEET METAL CURB CAP W/SOLDERED SEAMS 60 MIL EPDM WRAP SCREW W/NEOPREEN WASHER 18" O.C. WOOD MECHANICAL CURB REINFORCED RUBBER FLASHING STRIP ADHERED 60 MIL EPDM MEMBRANE 0.5" WOOD FIBER INSUL. BD. 3.0" ISO. FOAM BD. INSUL. 2.0" ISO. FOAM INSUL. BD. METAL DECKING 5 MECHANICAL CURB FLASHING/EQUIPMENT MOUNT 3" = 1'-0" 3-A2.03 3-A9.02 Addendum #3 SKA-01 (C) 2015 LOA ARCHITECTS, P.C. DATE: JOB NO.: DRAWN: APPROVED: REF. DWG: CADDFILE: 07/15/14 1102 THolk TH STAPLETON NORTHFIELD CAMPUS COMMONS 9100 E. 56TH AVE ADDENDUM #3 3-A4.02 NOTES: 1 3 AV6.1-MIX 3-A5.02 2 1 1 2 3-A5.02 3 4 4.5 5 1. BUILDING ELEVATION 100'-0" = 5,238' ABOVE SEA LEVEL 2. REFERENCE SHEETS 3-A6.1A, 3-A6.1B, 3-A6.1C FOR ENLARGED FLOOR \ PLANS AND DIMENSIONS 3. REFERENCE SHEETS 3-A4.01, 3-A4.02 FOR EXTERIOR ELEVATIONS 4. REFERENCE SHEETS 3-A3.11 FOR EXTERIOR DOOR FRAMES AND SHEET 3-A3.32 FOR DOOR SCHEDULE 5. REFERENCE SHEETS 3-A3.31 FOR WINDOWS AND STOREFRONT INFORMATION 6. REFERENCE SHEETS 3-I2.1A, 3-I2.1B, 3-I2.1C FOR INTERIOR FINISH INFORMATION 7. REFERENCE S SHEETS FOR STRUCTURAL SCOPE OF WORK. 8. REFERENCE M, P, E, T, AV, AND W SHEETS RESPECTIVELY FOR MECHANICAL, PLUMBING, ELECTRICAL, TECHNOLOGY, AUDIO/VISUAL, AND FOOD SERVICE SCOPE OF WORK. 9. ALL WOOD PROVIDED FOR THIS PROJECT SHALL BE FIRE RESISTANT TREAT WOOD (FRTW) 1 3-A5.02 6 12' - 0" 1' - 9" NORTH ELEVATION 7 8 9 134' - 0" 12' - 0" 14' - 0" 20' - 0" 14' - 4" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 18' - 3" 65' - 4" 20' - 0" 9' - 4" 4' - 0" 2' - 8" 4' - 0" 5' - 4" 2' - 8" 18' - 3" 20' - 0" 9' - 4" 2' - 8" 5' - 4" 4' - 0" 2' - 8" 4' - 0" 5' - 8" 10' - 0" 9' - 4" 1' - 9" 3' - 4" 5' - 4" 6' - 0 7/8" 10' - 0" WINDOW D ABOVE 5' - 4" 3-104A 3-100CB UP PLATFORM CIRCULATION 3-110A - UP 10' - 0" 10' - 0" WINDOW D ABOVE 13 3-A9.05 2 34' - 6" 2' - 8" 2' - 8" B EAST ELEVATION 20' - 0" 3-101A B B 124' - 0" 13' - 4" D VESTIBULE 3-102.1 3-A4.01 2 3-A5.01 SEATING 3-100 WOMENS TOILET 3-101 PERFORMANCE PLATFORM 3-110 E 26' - 8" 5' - 3" 14' - 8" 160' - 3" E 20' - 0" FEC 1 2' - 8" 2 3-A5.01 26' - 8" 3-106CA 3-108A 3-106AA C 3-100F 2' - 8" VESTIBULE 3-106D 3-106DA 8 3-A9.05 UP 3-100CA 2' - 8" 29' - 3" 2 CORRIDOR 3-106 3-106DB 1 3-A5.03 8 3-A9.05 3-104C 3-103A 13' - 4" VESTIBULE 3-100C 74' - 0" 74' - 0" WEST ELEVATION 3-A4.02 3-104B FE 1 VESTIBULE 3-103.1 10' - 0" C 1 AV6.1-SL FE 1 CUST 3-106B 3-106BA SERVING 3-104 3-102A B FAMILY ASSIST TOILET 3-106A CUST. 3-104A MEN TOILET 3-102 IDF 3-106C 52' - 0" 3-107A KNOX BOX, TYPE OF 2. 3-104AA B B 3 3-A5.01 3-109A 3-105D 3-105E 3-104BA LAUNDRY 3-104B A FEC 2 3-100G 2' - 8" 2' - 8" 3-105C B 2' - 8" 26' - 0" 1 FEC 2 TABLE & CHAIR STORAGE 3-103 2' - 8" 2' - 8" 3 3-A5.01 ELECTRICAL 3-109 WATER ENTRY 3-108 TOILET 3-105A 6' - 0" B WINDOW D ABOVE THEATER STORAGE 3-107 3-105BA SECURITY ACCESS DOOR OFFICE 3-105B 3-105AA D C 3-105B C KITCHEN PANTRY 3-105 16' - 0" 16' - 0" A A 1' - 9" A 3-109B C 1' - 9" C SIDEWALK 3-108B WINDOW D ABOVE 3-105A WINDOW D ABOVE 5 3-A3.11 FEC 1 F 3-100D A UP WINDOWS 3-100E 34' - 0" 20' - 0" 5' - 4" 8' - 0 " WIND OW E AB OVE 3-100AA 3-100AB 2' - 0" 6' - 7" 20' - 0" 14' - 0" 48' - 0" 1 07/15/15 05/29/15 05/04/15 04/06/15 NO. DATE KNOX BOX, TYPE OF 2. 1 3-A5.05 7 3-A5.04 20' - 0" COLUMN, SEE STRUCT 20' - 0" 12' - 0" 20' - 0" 3 4 4.5 5 18' - 3" 18' - 3" 7 8 9 SCHOOL DISTRICT NO. 1 3 1 AV6.1-MIX 3-A5.02 2 3-A5.02 1 DENVER PUBLIC SCHOOLS 1 3-A5.02 DEPARTMENT OF FACILITY MANAGEMENT 7/14/2015 3:21:26 PM N 3-A4.01 APPROVED CONTRACT DOCUMENT FIRST FLOOR PLAN 3-A4.01 3-A2.01 SCHOOL NO. 985 DRAWN BY: DATE: DENVER, CO CHECKED BY: SCALE: TH NLM, TH, TT GA 05/29/15 FIRST FLOOR PLAN AS NOTED ASSOCIATE ARCHITECT ARCHITECT OF RECORD H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 1/8" = 1'-0" SITE NO. 983 5500 CENTRAL PARK BOULEVARD - SLC BUILDING DATE: 1 APPR'D STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DESIGNED BY: SOUTH ELEVATION MADE DEPARTMENT OF FACILITY MANAGEMENT c 2015 LOA Architecture 1' - 9" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. 6 AUTHORITY DENVER PUBLIC SCHOOLS 134' - 0" 2 Addendum #3 For Construction Progress Set Schematic Design DESCRIPTION OF REVISION DWG. NO. 3-A2.01 SHEET: OF: 983_2478_985 _OR_ 3-A2.01 20' - 0" 6' - 7" 5' - 4 " 10 1/4" ROOFLINE ABOVE 2' - 0" 14' - 0" 2 3-A5.05 1' - 7 3/4" 3-100AC 1' - 10" ENTRY WALL 6' - 7" 6 K 14' - 0" VESTIBULE 3-100A TIME CAPSULE PLAQUE SEE SHEET 3-A9.07 22' - 8" 28' - 0" 13' - 4" ENTRY WALL ELEVATION 8' - 0" 3-A5.04 12' - 0" SECURITY 3-100B 6' - 7" 2' - 0" PAUL SANDOVAL PLAQUE SEE SHEET 3-A9.07 H COMMONS 3-100AF 2' - 0" 1 3-A5.06 5' - 4 " 6' - 7" 14' 8" 2' - 0" G WINDOW D ABOVE 5' - 4 " - 21' - 9" 2 3-A5.04 17' - 4" J 1 UP 3 3-A5.05 3' - 4" 4 3-A5.04 1' - 9" 5° 10 3-100BA 6' - 7" 3-100AE 3 3-A5.04 1' - 10" 13' - 4" C:\Users\tholk\Documents\A_DPS_COMMON-II Core Shell_tholk.rvt 10' - 8" 7' - 1" 3-100B 3' - 4" WINDOWS ABOVE A 3-100AD 3-100C 3-100A 6' - 9" 13' - 4" 10' - 0" H 1 3-A5.01 UP 6' - 7" G PLATFORM CIRCULATION 3-110B 1' - 9" 17' - 4" 17' - 4" 44' - 0" 1 3-A5.04 ABOVE - 1 3-A5.01 WINDOW D ABOVE 34' - 0" 13' - 4" F NOTES: BUILDING ELEVATION 100'-0" = 5,238' ABOVE SEA LEVEL F-B A A 40 NOT USED 3-A3.11 5/8" GYPSUM BOARD SHEATHING 1" = 1'-0" FACE BRICK: SEE EXTERIOR ELEVATIONS 6" METAL STUDS @ 16" O.C AIR SPACE R-19 BATT INSULATION VENEER ANCHORS @ 16" x 16" O.C AIR SPACE 8" 2" CONT. CAVITY WALL INSULATION 6" METAL STUDS @ 16" O.C 2 FLUID -APPLIED WEATHER BARRIER 5/8" GYPSUM BOARD 4" FRY (OR EQUAL) REGLET DRMF -.625 - .625 10" FACE BRICK - SEE EXTERIOR ELEVATIONS 1' - 9" R-19 BATT INSULATION 5/8" GYP. BD. WEEP SYSTEM W/ THRU-WALL FLASHING 3" FLUID-APPLIED WEATHER BARRIER 1/4" SAFETY GLASS 2" CONT. CAVITY WALL INSUL. 2" X 6" ALUM. STOREFRONT SHIM TO SEPARATE METALS 5/8" GYP. BD. SHEATHING 8 1/4" 3" BACKER ROD & SEALANT ALL SIDES 4" 2" INSULATED HM DOOR 16" X 8" X 1/4" HSS TUBE W/ HIGH PERFORMANCE PAINT 8 1/4" HM DOOR W/ FIBERGLASS INSECT SCREEN W GASKET ON EXTERIOR SIDE, AND W4.0 x W4.0 W.W.F. 4" X 8" 1/4" HM DOOR HEAD W/ HIGH PERFORMANCE PAINT 7'-0" DOOR 10" x 4" HM FRAME VENEER ANCHORS @ 16" x 16" O.C 6" METAL STUDS @ 16" O.C. SHIM BACKER ROD & SEALANT ALL SIDES 1' - 4" BACK ROD IN SEALANT FRY (OR EQUAL) REGLET DRMF-625-625 4" X 5 3/4" HM DOOR HEAD W/ HIGH PERFORMANCE PAINT HM/ GLASS DOOR W/ HIGH PERFORMANCE PAINT INSULATED HM/ GLASS DOOR W/ HIGH PERFORMANCE PAINT Section 30 5 TRANSOM HEADER 1 4 3-A2.01 3-A3.11 3 3-A3.11 3-A3.11 1" = 1'-0" DOOR HEAD 3 DOOR HEAD 2 2 3-A3.11 3-A3.11 1" = 1'-0" DOOR HEAD 1 1 3-A3.11 3-A3.11 1" = 1'-0" 3-A3.11 3-A3.11 1" = 1'-0" NOT USED 1" = 1'-0" 9 1/4" 2" 4" 10" 4" JAMB 8 1/4" 2" HEAD 4" 5 3/4" 2" 4 3/4" 4 1/2" 2" 2" 6 1/2" A B C HM DOOR FRAME PROFILES 1" = 1'-0" 4.5 4.5 1 NOTE: PROVIDE 1/4" CLEAR SAFETY GLASS @ INTERIOR IG3 SEE SHEET 3-A3.21 FOR STOREFRONT SIM 14/3-A9.04 IG3 STEEL COLUMN W/ HIGH PERFORMANCE PAINT NOTE: PROVIDE 1" INSULATED LOW-E GLASS @ EXTERIOR IG3 IG1 15/3-A9.11 15/3-A9.11 5 3-A3.11 J 2/3-A3.11 IG5 IG3 10' - 8" 1' - 7" IG3 IG3 IG3 IG3 5/3-A9.11 IG3 IG3 IG3 IG3 IG3 1/3-A9.11 3' - 0" 3' - 0" 1' - 9" 3' - 0" DG 10' - 8" 3' - 0" DG 6' - 4" 1' - 9" 2' - 3" 3' - 0" DG 6' - 4" 3' - 0" DG 1' - 9" 9" 9" IG3 IG3 1" INSULATED SAFETY GLASS IG3 IG3 3/3-A9.11 IG3 IG3 DOOR STOPS SEE DETAILS, TYP @ ALL DOORS IG3 IG3 2' - 1" 3' - 0" IG3 IG3 IG3 IG3 IG3 5' - 4" IG3 7" 7" 6" 6" 2' .. - 9" 9" IG3 KNOX BOX .. 1' -..10" 7" MFGR'S STANDARD ALUM PANELS 14/3-A9.04 6" 7" IG3 DENVER PUBLIC SCHOOLS IG3 IG3 IG3 IG3 IG3 2015 IG3 8/3-A9.11 1'8"- 1" IG5 IG5 IG3 1'..- 1" IG5 IG5 3' - 5" IG5 IG3 2"X5 3/4" HM FRAME @ JAMB 4"X5 3/4" HM FRAME TOP & BOTTOM 6" 7" 7' - 4" 2/3-A9.11 HSS 8"X3"X3/8" W/ HIGH PERFORMANCE PAINT, SEE STRUCT DWGS 7" 6" 8' - 8" IG5 7" 7" 6" 6" 2' ..- 9" IG5 .. 1' -..10" 7" IG5 7' - 4" 2/3-A9.11 7" 6" 9/3-A9.11 8' - 8" 8' - 0" SECTIONAL OVERHEAD DOOR 9" IG5 5 3-A3.11 IG1 J T.O. BUMP OUT @ OH DOOR 14/3-A9.11 111' - 4" HSS 16"X8"3/8" W/ HIGH PERFORMANCE PAINT, SEE STRUCT DWGS 13' - 8" 11' - 11" IG5 IG1 14/3-A9.11 6/3-A9.04 IG5 SIM 14/3-A9.04 3' - 0" 2' - 3" 3 3-A9.07 GLASS TYPES: 4/3-A9.11 6' - 4" 2' - 3" IG1 = 1" INSULATED LOW-E GLASS IG2 = 1" INSULATED SPANDREL GLASS IG3 = 1/4" SAFETY GLASS IG4 = 1" INSULATED LOW-E GLASS (FROSTED) *ALL GLASS, THIS SHEET, AT DOORS & SIDELIGHTS TO BE (IG3). *ALL GLASS, THIS SHEET, TO BE IG1 UNLESS NOTED OTHERWISE IG5 = 5/8" INSULATED CLEAR GLASS 6' - 4" 1 DOOR FRAME F DOOR FRAME E DOOR FRAME D 1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0" 1 IG3 9/3-A9.12 INSULATED HM DOORS W/ HIGH PERFORMANCE PAINT INSULATED HM DOORS W/ HIGH PERFORMANCE PAINT 3' - 4" 9/3-A9.12 3' - 2" 3' - 2" DOOR STOPS SEE DETAILS 6&8/3-A9.07 2" HSS 8" X 2" X 3/8" FRAME W/ HIGH PERFORMANCE PAINT 9" 9" 6" 7" 6" 6" 7" 7" IG3 2' ..- 9" IG3 5" 3" 6" 7" IG3 11/3-A9.11 1' -..10" 7" .. 9" 2' - 8" 7' - 0" 7' - 4" 6" 6" 7" 7" 7' - 4" 9" 9" 2' ..- 9" 7' - 0" DOOR STOPS SEE DETAILS 6&8/3-A9.07 3" 5" HSS 16"X 8"X 3/8" W/ HIGH PERFORMANCE PAINT, SEE STRUCT DWGS IG3 2" INSULATED HM DOORS W/ HIGH PERFORMANCE PAINT IG3 3' - 0" 2" 3' - 0" 2" 6' - 8" 1/4" = 1'-0" SCREEN DOOR FRAME G 1/4" = 1'-0" DOOR FRAME C 1/4" = 1'-0" 07/15/15 05/29/15 05/04/15 04/06/15 NO. DATE Addendum #3 For Construction Progress Set Schematic Design DESCRIPTION OF REVISION DOOR FRAME B DOOR FRAME A 1/4" = 1'-0" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT 7/14/2015 3:21:38 PM 4 SCHOOL NO. 985 DRAWN BY: CHECKED BY: SCALE: TH THolk GA SCALE: 1/4" = 1'-0" DATE: DENVER, CO 0529/15 AS NOTED EXTERIOR DOOR ELEVATIONS AND DETAILS ASSOCIATE ARCHITECT ARCHITECT OF RECORD H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 8 SITE NO. 983 5500 CENTRAL PARK BOULEVARD - SLC BUILDING DATE: 0 APPR'D STAPLETON NORTHFIELD CAMPUS DESIGNED BY: DENVER PUBLIC SCHOOLS APPROVED CONTRACT DOCUMENT 2 MADE DEPARTMENT OF FACILITY MANAGEMENT c 2015 LOA Architecture 1/4" = 1'-0" 4 AUTHORITY DENVER PUBLIC SCHOOLS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. 6' - 8" SCREEN DOOR FRAME H 1 DWG. NO. 3-A3.11 SHEET: OF: 983_2478_985 _OR_ 3-A3.11 2" IG3 2"X8 1/4" HM FRAME W/ HIGH PERFORMANCE PAINT 1/3-A3.11 COMMONS 3' - 8" 2" 3' - 8" 3" 7" 5" 6" 3' - 4" IG3 11/3-A9.11 1' -..1" 2" 7" .. SCREEN 1' - 1" .. 7' - 0" IG3 3/4" x 3/4" ALUMINUM SCREEN TRACK ALL SIDES W/ FIBERGLASS INSECT SCREEN W/ GASKET ON INTERIOR SIDE AND W4.0 x W4.0 W.W.F, SPOT WELD EACH STRAND TO 3/4" x 3/4" x 1/4" ANGLE ON EXTERIOR 8" 1'1'--10" GLASS 8/3-A9.12 7' - 4" 7" 6" IG3 2" 7" 6" 7' - 0" 7" 6" 7' - 4" 5/3-A9.12 5/3-A9.12 7" 6" 2' ..- 9" 9" 9" 4' - 0" 5/3-A3.11 2" x 5 3/4" HM FRAME @ JAMB, 4" X 5 3/4" HM FRAME @ TOP W/ HIGH PERFORMANCE PAINT 3/3-A3.11 4" 4' - 0" 5/3-A3.11 8 1/4" HM FRAME W/ HIGH PERFORMANCE PAINT 10' - 0" 3/3-A3.11 1' - 4"1' - 4" 3' - 4" 7' - 4" C:\Users\tholk\Documents\A_DPS_COMMON-II Core Shell_tholk.rvt (INTERIOR VESTIBULE) 2" 2" 2" 2" RE: SCH. 2" 2 5/8" RE: SCH. 2" 1'-4" 2" TYPE S4 IG-3 TYPE M2 1 8" AT WOOD DOORS 8" AT WOOD DOORS RE: SCH. RE: SCH. TYPE T2 6" 8" 2'-8" 8" 3'-7" (ADA) 2'-8" RE: SCHED. 3'-6" (ADA) RE: SCHED. 1 3'-7" (ADA) VARIES VARIES EQ 9" EQ 9" VARIES 9" 6" VARIES 5" 2'-1 3/4" 6 1/2" 11" RE: SCHED. 9" 3'-6" (ADA) RE: SCH. 2'-9" 9" 2'-8" 8" VARIES RE: SCHED. 5" 9" 6" VARIES 3'-7" (ADA) RE: SCH. G1 RE: SCH. 3'-10" H1 8" AT WOOD DOORS RE: SCHED. 6" 6" RE: SCH. RE: PLANS 3'-10" RE: PLANS HOLLOW METAL FRAME (NO STOP) 8" AT WOOD DOORS TYPE TM2 RE: SCHED. 4'-0" G1 TYPE DE2 1/4" = 1'-0" RE: SCH. G1 TYPE M4 IG-3 HOLLOW METAL DOOR FRAME TYPES CRL PASS-THRU WINDOWS DAISY MODEL PASS-THRU, D6 OVERHEAD TRACK, JAMBS, SATIN ANODIZED, & LOCKABLE (INSTALL PASS-THRU WINDOW IN HOLLOW METAL FRAME) 3'-0" RE: SCH. RE: SCH. RE: SCH. RE: SCH. RE: SCH. TYPE S2 2" RE: SCH. 2" 2" RE: SCH. 2" 2" 4" 2" 1'-4" 2" RE: SCH. 2" 2" 4" 2" RE: SCH. 2" 2" 2 5/8" 2" RE: SCH. 1 H2 F - FLUSH HOLLOW METAL WINDOW TYPES DOOR TYPES 1/4" = 1'-0" 1/4" = 1'-0" Level DOOR NO. LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1 3-100A 3-100AA 3-100AB 3-100AC 3-100AD 3-100AE 3-100AF 3-100B 3-100BA 3-100C 3-100CA 3-100CB 3-100D 3-100E 3-100F 3-100G 3-101A 3-102A 3-103A 3-104A 3-104AA 3-104B 3-104BA 3-104C 3-105A 3-105AA 3-105B 3-105BA 3-105C 3-105D 3-105E 3-106AA 3-106BA 3-106CA 3-106DA 3-106DB 3-107A 3-108A 3-108B 3-109A 3-109B ROOM NAME SEATING VESTIBULE VESTIBULE VESTIBULE SEATING VESTIBULE SEATING VESTIBULE SEATING VESTIBULE SEATING SECURITY SEATING VESTIBULE VESTIBULE SEATING SEATING SEATING CORRIDOR WOMENS TOILET MEN TOILET TABLE & CHAIR STORAGE SERVING CUST. SERVING LAUNDRY SERVING KITCHEN PANTRY TOILET KITCHEN PANTRY OFFICE KITCHEN PANTRY KITCHEN PANTRY KITCHEN PANTRY FAMILY ASSIST TOILET CUST IDF VESTIBULE VESTIBULE THEATER STORAGE WATER ENTRY WATER ENTRY ELECTRICAL ELECTRICAL N - NARROW LITE S/PR WIDTH HEIGHT THICKNESS OVHD PR PR PR PR PR PR PR S 10' - 8" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 6' - 0" 3' - 0" 6' - 0" 6' - 0" 6' - 0" 10' - 8" 3' - 0" 3' - 0" 6' - 0" 3' - 0" 3' - 0" 6' - 0" 27' - 6" 3' - 0" 4' - 0" 3' - 0" 3' - 0" 3' - 8" 3' - 0" 8" 3' - 6" 3' - 0" 3' - 0" 4' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 6' - 0" 6' - 0" 6' - 0" 3' - 0" 6' - 4" 3' - 0" 3' - 0" 8' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 8' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 12' 13' - 0" 9" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 5/8" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" 1 3/4" PR PR PR OVHD S S PR S S PR OVHD S S S S S S S S S PR S S S S PR PR PR S PR S S G - HALF GLASS DG - DOUBLE GLASS COMMON DOOR AND FRAME SCHEDULE DOOR DOOR FRAME FRAME TYPE MATERIAL TYPE MATERIAL DG DG DG DG DG DG DG F DG DG DG N N N F F F F N F F STD F G F STD TD STD F F F DG DG F F TD F STD 1 Alum HM HM HM HM HM HM HM WD HM HM HM Alum WD WD HM WD WD WD HM HM HM WD HM WD HM WD HM HM HM WD HM WD HM HM HM HM HM HM HM 1 F D E E D D E E E E A S2 A A S2 F S2 S2 S2 S2 S2 S2 S2 S2 S2 S2 G S2 H S2 S2 S2 S2 S2 S2 S2 A S2 S2 S2 B S2 C E HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM HM GLASS TYPE IG-5 IG-3 IG-3 IG-3 IG-3 IG-3 IG-3 IG-3 IG-3 IG-3 G2 IG-5 G2 G2 1 G2 G2 SCREEN IG-3 IG-3 G2 G2 G2 IG-3 G2 IG-3 - HEAD DETAIL 1 6/3-A9.04 21/3-A3.11 21/3-A3.11 21/3-A3.11 2/3-A3.11 2/3-A3.11 2/3-A3.11 31/3-A3.11 1 1/3-A3.31 31/3-A3.11 31/3-A3.11 1/3-A3.31 6/3-A9.04 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 5/3-A9.32 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 5/3-A3.11 1 1/3-A3.31 5/3-A3.11 1/3-A3.31 2/3-A3.31 2/3-A3.31 2/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 1 3 1/3-A3.11 1/3-A3.31 1/3-A3.31 1/3-A3.31 5 4/3-A3.11(SIM) 1 1/3-A3.31 3/3-A3.11 DOOR LEGEND UEG - UNEQUAL GLASS JAMB DETAIL TD - TRAFFIC DOOR FIRE RATING 2/3-A9.11 4/3-A9.11 8/3-A9.11 3/3-A9.11 9/3-A9.11 5/3-A9.11 1/3-A9.11 12/3-A9.11 1/3-A3.31 12/3-A9.11 11/3-A9.11 1/3-A3.31 2/3-A9.11 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 8/3-A9.21 1/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 4 5/3-A9.12 1/3-A3.31 4 5/3-A9.12 1/3-A3.31 2/3-A3.31 2/3-A3.31 2/3-A3.31 1/3-A3.31 1/3-A3.31 1/3-A3.31 11/3-A9.11 1/3-A3.31 1/3-A3.31 1/3-A3.31 8 9/3-A9.12 1/3-A3.31 7 8/3-A9.12 HDWR GROUP 001 002 002 003 003 003 002 104 002 006 004 113 113 114 101 101 116 108 103 105 102 009 107 117 106 117 118 117 107 108 110 005 004 116 109 008 112 007 ----------------------------------------------------------------------------------- STD - SINGLE TRAFFIC DOOR REMARKS Base Bid NOTE: FOR EXTERIOR DOOR & FRAME ELEVATIONS AND VESTIBULE 3-100A, SEE SHEET 3-A3.11 S = SINGLE DOOR PR = PAIR OF DOORS OVHD = OVERHEAD ROLLING DOOR 1 INTERIOR GLAZING TYPES PARTITION WIDTH LINE OF INTERSECTING WALL WHERE OCCURS LINE OF INTERSECTING WALL WHERE OCCURS 1 PARTITION WIDTH NO. 7/15/15 Addendum 3 5/29/15 FOR CONSTRUCTION DATE DESCRIPTION OF REVISION MADE APPR'D 2" DOOR 5/8" 1/2" MIN HOLLOW METAL FRAME VARIES DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture CONT SEALANT, TYP HOLLOW METAL FRAME DOOR This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. 2" VARIES SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: 2 3-A3.31 HM JAMB_SWING FREE FRAME @ GWB (SIM @ HEAD CONDITION) 3" = 1'-0" 1 3-A3.31 HM JAMB @ GWB PARTITION - TYP (SIM @ HEAD CONDITION) Designer Author Checker 05/29/2015 AS NOTED DOOR SCHEDULE, DOOR & FRAME TYPES AND DETAILS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 3" = 1'-0" DATE: DENVER, CO 9100 E. 56th AVE DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SITE NO. 983 NORTHFIELD HIGH SCHOOL Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. 2" SCHOOL NO. 985 DWG. NO. 3-A3.31 SHEET: COMMONS 4" UNO 1/2" MIN CONT SEALANT, TYP 2" 4" UNO DENVER PUBLIC SCHOOLS DENVER PUBLIC SCHOOLS 7/14/2015 1:36:43 PM AUTHORITY OF: 983_2478_985 _OR_ 3-A3.31 C:\Users\sdangel\Desktop\A_DPS_COMMON-II Interior.rvt G1 = 1/4" CLEAR FLOAT GLASS G2 = 1/4" CLEAR TEMPERED FLOAT GLASS NOTES: BUILDING ELEVATION 100'-0" = 5,238' ABOVE SEA LEVEL A B C D E 3 3-A5.01 F G H J 1 3-A5.01 2 3-A5.01 K HORIZONTAL METAL SIDING OVER FLUID APPLIED WEATHER BARRIER METAL SOFFIT PANELS ROOF LADDER, SEE DETAIL 3/3-A9.06 TYPE #1 FACE BRICK W/ VENEER ANCHORS AT 16" X 16" O.C. 3 3-A5.04 T.O. FASCIA 130' - 10" B.O. FASCIA 126' - 8" 4 3-A5.04 L T.O. PARAPET 122' - 0" T.O. ENTRY PARAPET 118' - 2" A A A A A Gb T.O. BUMP OUT @ OH DOOR 111' - 4" B 16' - 0" B DOOR FRAME A 32' - 8" 16' - 0" B B 11' - 4" B 15' - 4" Ga B CJ 8x8 OVERFLOW SCUPPERS, SEE ROOF PLAN FOR EXACT LOCATION DOOR FRAME F 17' - 4" CJ 41' - 4" 13' - 4" 74' - 0" CJ DOOR FRAME A 6' - 7" 6' - 9" 19' - 4" 44' - 0" LEVEL 1 100' - 0" STEEL COLUMN W/ HIGH PERFORMANCE PAINT, SEE STRUCT DWGS 8' - 8" 28' - 0" CAST-IN-PLACE CONCRETE INSULATED HM DOORS TYPE #2 FACE BRICK W/ VENEER ANCHORS AT 16" X16" O.C." 3/4" REVEAL @ CONC WALL WEST ELEVATION 2 3-A2.01 3-A4.02 1/8" = 1'-0" NOTE: CONDUCTOR HEADS BEHIND SCREEN 9 ROOF LADDER, SEE DETAIL 3&4/3-A9.06 8 HORIZONTAL METAL SIDING OVER FLUID APPLIED WEATHER BARRIER 7 6 1 AV6.1-SL 1 3-A5.02 5 FOR TRANSLUSCENT WALL PANEL 'M' SEE SHEET 3 -A3.21 4.5 4 3 2 1 3 1 AV6.1-MIX 3-A5.02 TYPE #1 FACE BRICK W/ VENEER ANCHORS AT 16" X 16" O.C. 2 3-A5.02 OVERFLOW SCUPPER OVERFLOW SCUPPER OVERFLOW SCUPPER METAL SOFFIT PANELS T.O. FASCIA 130' - 10" B.O. FASCIA 126' - 8" 16" HIGH CAST ALUMINUM NUMBERS PER DENVER FIRE DEPARTMENT, SEE SPECS 2' - 8" 3/3-A9.03 T.O. PARAPET 122' - 0" 2' - 8" 1 20' - 0" CONTROL JOINS @ 20'-0" O.C UON 20' - 0" D 20' - 0" D 13 3-A9.05 C D 5 3-A3.11 C C A H 6' - 8" 7' - 4" A H C CJ 2' - 8" 14' - 4" CJ DOOR FRAME B 14' - 8" CJ 2' - 8" 4' - 0" 2' - 8" 4' - 0" 2' - 8"2' - 8"2' - 8" 20' - 0" 1' - 4" 22' - 8" DOOR FRAME G 4' - 0" 20' - 0" CJ CJ LEVEL 1 100' - 0" CJ 2' - 8" 2' - 8" 2' - 8" 4' - 0" 2' - 8" 4' - 0" 1' - 4" 22' - 8" 20' - 0" 1 14' - 4" NORTH ELEVATION C:\Users\aelmore\Documents\A_DPS_MONUMENT SIGNS_AElmore.rvt 3-A2.01 3-A4.02 1/8" = 1'-0" 3-A4.02 1 1 3-A4.02 07/15/15 05/29/15 05/04/15 04/06/15 NO. DATE 2 Addendum #3 For Construction Progress Set Schematic Design DESCRIPTION OF REVISION AUTHORITY MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2015 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT KEY PLAN DRAWN BY: CHECKED BY: DATE: 3/64" = 1'-0" APPROVED CONTRACT DOCUMENT 8 4 0 8 16 DATE: DENVER, CO SCALE: TH THolk, TT GA 05/29/15 EXTERIOR ELEVATIONS AS NOTED ASSOCIATE ARCHITECT ARCHITECT OF RECORD H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 SCALE: 3/32" = 1'-0" SITE NO. 983 5500 CENTRAL PARK BOULEVARD - SLC BUILDING DESIGNED BY: DENVER PUBLIC SCHOOLS SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. N 7/14/2015 12:59:06 PM TYPE #2 FACE BRICK W/ VENEER ANCHORS AT 16" X16" O.C." DWG. NO. 3-A4.02 SHEET: OF: 983_2478_985 _OR_ 3-A4.02 FOR CONTINUATION OF WALL: SEE CIVIL DRAWINGS DOOR FRAME C COMMONS 10' - 0" T.O. BUMP OUT 117' - 4" 1' - 4" LENGTH OF NORTH WALL TO BE 190'-0" FLOOR PLAN NOTES 20'-0" 7 20'-0" 8 20'-0" 18'-3" 18'-3" H2 3-105AA A6S 3-A6.42 2'-5" 7'-0" CLEAR 9" 3-104A 1'-3" FEC1 8 3-A9.21 A6S 8 3-A9.21 5 3-A7.01 O.H. 13'-3" 14'-3" 27'-6" (CLEAR OPENING) OVERHEAD ROLLING DOOR 5'-9" C6 6 3-A9.21 LINE OF BEAM FURRING HEADER ABOVE 4. ALL SPOT ELEVATIONS SHOWN ON THE FLOOR PLANS OUTSIDE THE BUILDING RELATE TO USGS ELEVATIONS. ALL SPOT ELEVATIONS INSIDE THE BUILDING REFER TO BUILDING REFERENCE ELEVATIONS. NOTIFY ARCHITECT IMMEDIATELY SHOULD CONDITIONS BE FOUND CONTRADICTORY TO THESE DRAWINGS. 100'-0" = 5238.0' 5. ALL ANGLES SHOWN ON THE FLOOR PLANS ARE 90 DEGREES UNLESS OTHERWISE NOTED. 6. ALL DIMENSIONS ARE TO GRID LINE, FACE OF CONCRETE OR MASONRY, OR FACE OF GYPSUM BOARD, UNLESS OTHERWISE NOTED. 7. FURNISHINGS (SHOWN DASHED) ARE SHOWN FOR GENERAL COORDINATION ONLY. 8. ALL FLOOR PLAN DIMENSIONS TO MASONRY ARE NOMINAL DIMENSIONS, UNLESS NOTED AS ACTUAL. A3S CORRIDOR A6S 3-106 1. COORDINATE ALL ELECTRICAL AND MECHANICAL ITEMS AND EQUIPMENT THAT ARE INCORPORATED IN THE MILLWORK. NO OUTLETS, DEVICES, SWITCHES OR OTHER EXPOSED ELECTRICAL OR MECHANICAL ITEMS SHALL BE CONCEALED BY MILLWORK. 2. REQUIRED FILLER PIECES SHALL BE EVENLY DISTRIBUTED (INSTALLED) TO ALLOW PROPER OPERATION OF DRAWERS AND DOORS UNLESS NOTED OTHERWISE. 26'-0" A3S 3-109A 3'-0" FE1 7" 7'-10" A3S 5'-0" CLEAR A3S A3S FE1 3'-0" 2'-1" 1'-8" 6'-11" FIRE EXTINGUISHER LEGEND 5'-11" VESTIBULE 3-106DB 3-106D FE1 FEC1 FEC2 3-106DA 10 POUND DRY CHEMICAL FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET (SEMI-RECESSED) FIRE EXTINGUISHER CABINET (SEMI-RECESSED) - TYPE K C UP A6S MARKER BOARD (MB) 1' - 7" UP UP 3-100F MB-3 8'-0"W x 4'-0"H MB-3 7 3-A9.21 A6 PLATFORM CIRCULATION 3-110A A6 TACK BOARD (TB) 1'-9" LEG LEG A3S 8'-3" A3S TB-1 39'-3" 1'-7" S6 3-104B 8'-0" 3-A6.43 SERVING 3-104 2 A3S IDF 3-106C A3S FD 3'-0" 4 3-A9.21 C3 4 FD ROOF ACCESS STEEL LADDER RE: SPEC. A3S A3S 3-106BA 3 A3S A3S 3'-0" CUST 3-106B 3-106AA SIM 5 3-104C 3-103A 3-A6.43 A3S BOTTLE FILLER 5'-0" CLEAR 3-101A VESTIBULE 3-102.1 A3S 3-A6.43 4 3-A9.21 6 6'-9" D 4'-2" 7'-10" 15'-10" - S6 EQUIPMENT (SHOWN DASHED) IS SHOWN FOR GENERAL COORDINATION ONLY. MILLWORK NOTES A3S FAMILY ASSIST TOILET 3-106A D3S B3S A3S - 1 1'-6" 5'-0" CLEAR 3-100CB 3-100CA C3 C3 VESTIBULE 3-100C C3 15'-10" FLOOR SINKS A3S 10'-6" A3S A3 C3 4'-2" FEC2 3" 3'-4" 1'-7" 3'-1" C6 14'-3" 8'-0" 7'-3" D3S 3-102A C 10'-0" CUST. 3-104A MEN TOILET 3-102 VESTIBULE 3-103.1 4'-4" FD 7'-5" 26'-0" FD 14'-3" C3 3-104AA 1'-9" 3'-4" 7 3-A6.31 7 3/4" A3 LAUNDRY 3-104B 3-104BA 3" ELECTRICAL 3-109 B 3-107A D B3S 3. 6'-8" 8'-3 1/2" 3-100G A3S GG3S A3S A3S FD 7 A3S WATER ENTRY 3-108 FEC2 - 7'-4" HH3S W 10'-5" 10'-11 1/2" 1'-4" ALIGN 3'-3" 1'-10" TOILET 3-105A B 3'-3" A3S THEATER STORAGE 3-107 3-105D S3S 6" FD 10'-5" 3-105C 1'-8" A3S 3'-2" 3-105BA TB-1 IN ROOMS WITH FLOOR DRAINS, SLOPE CONCRETE SURFACE WITHIN 18" RADIUS AT 1/4" PER FOOT TOWARD FLOOR DRAIN, UNLESS OTHERWISE INDICATED. A3S 3-105E A3S FLOOR SINK 1'-8" A3S 5 KITCHEN PANTRY 3-105 FLOOR SINK 2. A 6" 3' - 4" 3'-2" 4'-5 5/8" 10 3-A6.31 6 3-A6.31 3-A6.42 A3S 6'-6" 16'-0" TABLE & CHAIR STORAGE 3-103 OFFICE 3-105B 8" 10'-0" 6 3-108B 3-105B 2'-1" A 9 DO NOT SCALE DRAWINGS. 16'-0" 20'-0" 6 3-109B 14'-0" 5 3-105A 12'-0" 4 11" 3 3-106CA 2 3-108A 1 1. 4'-0"W x 4'-0"H 1 3-A6.41 GG3S 2 1 2 3-A6.42 5'-3" E FEC1 HH3S SEATING 3-100 6698 SF F PERFORMANCE PLATFORM 3-110 1 3-A9.21 2' - 6" E 20'-0" ALIGN REAR BLACK CYCLORAMA 3-A6.42 FRONT CURTAIN 1 FD 20'-0" 3 WOMENS TOILET 3-101 40'-0" PROSCENIUM OPENING 29'-3" TORMENTOR 1 3-A7.01 3-100D LINE OF BEAM FURRING HEADER ABOVE 11'-1 5/8" O.H. 7 3-A9.21 - PLATFORM CIRCULATION 3-110B A6 A6 UP UP 8'-1 3/8" 3-100E 39'-3" LEG 34'-0" LEG TORMENTOR 1' - 7" UP A6S G G 10'-0" 3-A6.41 4 A6S 3-100C FIRE RESISTANCE RATING LEGEND 3-100BA A3S 1-HOUR FRR FIRE BARRIER 3-A6.42 8" 31'-9" 3-100AF 3-100AE 3-100A 3-100B H 3-100AD 2'-7" H2 3 21'-9" VESTIBULE 3-100A 3-A6.42 8 SECURITY 3-100B H1 3' - 4" 3-100AA 1'-6" G6 J 8'-0" 3-100AB 3-100AC 4 J TV WALL MOUNT (CFCI) G6 3-A6.42 1 12'-0" 14'-0" 20'-0" 8'-11" 11'-1" 20'-0" 20'-0" 18'-3" 18'-3" NO. 7/15/15 Addendum 3 5/29/15 FOR CONSTRUCTION DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS 1 2 3 4 4.5 5 6 7 8 9 DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 1 3-A6.10 LEVEL 1 FLOOR PLAN - AREA A DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: 1/8" = 1'-0" N DENVER, CO Designer Author Checker 05/29/2015 LEVEL 1 FLOOR PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56th AVE DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 NORTHFIELD HIGH SCHOOL Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 1:37:34 PM AUTHORITY DWG. NO. 3-A6.10 SHEET: OF: 983_2478_985 _OR_ 3-A6.10 K COMMONS C:\Users\sdangel\Desktop\A_DPS_COMMON-II Interior.rvt A3S 8" 3' - 4" 2-HOUR FRR FIRE BARRIER INTERIOR ELEVATION NOTES WALL ART, BY OWNER TV WALL MOUNT (CFCI) 2'-0" PLAQUE 1'-6" PLAQUE 3-A6.42 3. ALL DIMENSIONS ARE TO GRID LINE, FACE OF CONCRETE OR MASONRY, OR FACE OF GYPSUM BOARD, UNLESS OTHERWISE NOTED. 4. EQUIPMENT (SHOWN DASHED) IS SHOWN FOR GENERAL COORDINATION ONLY. 5. FURNISHINGS (SHOWN DASHED) ARE SHOWN FOR GENERAL COORDINATION. 6. REFER TO SHEET 3-A3.02 FOR TYPICAL MOUNTING HEIGHTS. 7. COORDINATE FLOOR DRAIN LOCATIONS WITH EMERGENCY SHOWER LOCATIONS WHERE INDICATED ON ELEVATIONS. OFFICE 3-105B - NORTH 6 1/4" = 1'-0" OFFICE 3-105B - EAST 5 1/4" = 1'-0" 3-A6.42 10'-0" STRUCTURE 10'-0" STRUCTURE 1/4" = 1'-0" SCREEN HOUSING 10'-0" STRUCTURE 10'-0" STRUCTURE 9'-1 1/2" STRUCTURE 9'-1 1/2" STRUCTURE 9'-2" STRUCTURE 2'-6" 1'-0" 2'-0" BLACK DROP VALANCE LIGHT, TYP. CEILING MOUNTED PROJECTOR PERFORMANCE PLATFORM 3-110 1 2'-6" 2'-8" 18'-9" PROSCENIUM OPENING 22'-0" PROGRAM SPEAKER BEYOND, RE: AV SEATING 3-100 3'-0" MIN FROM STAGE FRONT ° .00 135 21'-0" B.O. SCHEDULE 40 PIPING 1 13'-4" PROJECTION SCREEN, RE: AV 35'-0" FRONT OF LENS TO SCREEN CONTRACTOR TO CONFIRM DISTANCE WITH PROJECTOR/LENS COORDINATE SCREEN LOCATION WITH FRONT CURTAIN FORESTAGE CANOPY 24'-0" SUBWOOFER, RE: AV 1 18'-0" PROJECTOR, RE: AV 3-100B SECURITY - SOUTH 1 1/2" DIA. SCHEDULE 40 PIPING (PAINTED P3 FOR SEATING AREA AND P5 FOR PERFORMANCE PLATFORM) FOR HANGING LIGHTS. SUPPORTED FROM TRUSSES BY UNISTRUT SYSTEM. PENDANT SPEAKER, SEE RCP FOR LOCATIONS, RE: AV CEILING FAN BASIS OF DESIGN: "BIG ASS FAN: ESSENCE" RE: MECH 3 1/4" = 1'-0" 1 3-A9.31 6'-0" PROGRAM SPEAKER JOG PROJECTOR SUPPORT AS REQ'D AROUND MECHANICAL DUCT STEEL SUPPORT BRACKET, TYP. (PAINTED TO MATCH WALL) 3-A6.42 - 1 1/2" DIA. SCHEDULE 40 PIPING (PAINTED P3 FOR SEATING AREA AND P5 FOR PERFORMANCE PLATFORM) FOR HANGING LIGHTS. SUPPORTED FROM TRUSSES BY UNISTRUT SYSTEM. 10" 3-100A VESTIBULE - EAST 4 3-A6.42 1/4" = 1'-0" 3-A6.42 2'-6" 2'-6" 2'-6" 3-105 KITCHEN PANTRY - SOUTH 3'-6" REAR BLACK CYCLORAMA 1/4" = 1'-0" BRACE AS REQ'D BRACE AS REQ'D 7 VERIFY EQUIPMENT ROUGH-IN DIMENSIONS WITH MANUFACTURER 3' - 4" RECESSED CABINET UNIT HEATER TEASER 3-100A VESTIBULE - WEST 2. 5'-6" 6'-4" 4'-7" FEC2 TIME CAPSULE NICHE IN CONCRETE WALL, COVERING PLAQUE. (RE: SPEC) COORDINATE CONCRETE RECESS WITH PLAQUE AND TIME CAPSULE REQUIREMENTS. 1'-1 1/4" 8 H1 FIRE ALARM ANNUNCIATOR PANEL 3' - 4" 4" 5'-1" 4'-5" 3-A6.42 H2 L1 L1 L1 L1 L1 DO NOT SCALE DRAWINGS. TEASER CONCRETE REVEAL 1. 2 3-A6.42 SECTION THRU PERFORMANCE PLATFORM AND SEATING AREA 1/4" = 1'-0" MECHANICAL DUCT IN THE FOREGROUND 10'-0" AP1 10'-0" AP2 10'-0" AP1 AP1 10'-0" EQ AP1 AP1 AP1 AP2 AP2 ACOUSTIC PANELS, TYP. 2 3-A9.31 CENTER SCONCE BELOW ACOUSTIC PANEL, TYP. 1 8'-0" OPENING NO. 7/15/15 Addendum 3 5/29/15 FOR CONSTRUCTION DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture OPEN TO BEYOND This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: 1 3-A6.42 Designer Author Checker 05/29/2015 INTERIOR ELEVATIONS AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 3-100 SEATING - WEST 1/4" = 1'-0" DATE: DENVER, CO 9100 E. 56th AVE DESIGNED BY: 33'-0" SITE NO. 983 NORTHFIELD HIGH SCHOOL Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DWG. NO. 3-A6.42 SHEET: COMMONS FEC1 10'-0" OPENING PT6 6'-0" PT5 DENVER PUBLIC SCHOOLS 7/14/2015 1:39:37 PM AUTHORITY OF: 983_2478_985 _OR_ 3-A6.42 AP1 3 1/2" AP1 3 1/2" AP2 C:\Users\sdangel\Desktop\A_DPS_COMMON-II Interior.rvt 10'-0" 2'-0" LINE OF WINDOW BEHIND BEAM FURRING HEADER 10'-0" 4'-0" EQ 3' - 0" 6" 6" 6" 6" 6" G 6" HORIZONTAL METAL PANELS 1 1/2" 5/8" GYPSUM BOARD 24 GA. PRE-FINISHED COPING 12 2" CONT CAVITY WALL INSULATION 6 5/8" WEEP SYSTEM W/THRU-WALL FLASHING TAPERED EDGE STRIP GLUED TO TOP NAILER 118' - 0" BRICK LEDGE COLD FORMED CEE GIRT C8x5.4 22 GA. CONT. CLEAT NAILED @ 8" O.C METAL DRIP EDGE SET IN SEALANT 5/8" GYPSUM SHEATHING 22 GA. VERTICAL METAL WALL PANEL 22 GA. PRE-FINISHED METAL WALL PANEL TO MATCH EXISTING @ SLC & GYMNASIUM ( FIRESTONE VRCLASSIC OMEGA) 11 6" METAL STUDS @ 6" O.C. R-19 BATT INSULATION WALL SECTION DETAIL 4 2 PIECE 24 GA. GALVANIZED COUNTERFLASHING w/ SEALANT @ TOP HEM. SET RECEIVER ON COMPRESSED BUYTL RUBBER SEALANT TAPE 3-A5.06 3-A9.05 1 1/2" = 1'-0" FACE BRICK: SEE EXTERIOR ELEVATIONS 5/8" GYPSUM BOARD SHEATHING 60 MIL EPDM OVER 1/2" PROTECTION BOARD ROOF TOP SCREEN DETAIL. 3-A5.01 3-A9.05 FACE BRICK: SEE EXTERIOR ELEVATIONS TERM BAR PIN TO WALL @ 12" O.C 8" x 8" STEEL TUBE w/ HIGH PERFORMANCE PAINT SEE STRUCTURAL DWGS NOTE: PROVIDE ADDITIONAL GIRTS. AS REQUIRED BY ENGINEERED SPAN OF METAL WALL PANELS 10 COURSES @ 6'-8" 22 GA. CONT. CLEAT NAILED @ 8" O.C GRACE "ULTRA" OR EQUAL UNER METAL CAP 24 GA. PRE-FINISHED METAL CAP 2" CONT. CAVITY WALL INSULATION VENEER ANCHORS @ 16" x 16" O.C AIR SPACE 1' - 9" GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING (1/2" BACK FROM BRICK FACE 10 COURSES @ 3'-4" VENEER ANCHORS @ 16" x 16" O.C BASE FLASHING TO MATCH HORIZONTAL METAL PANELS TAPERED EDGE STRIP GLUED TO TOP NAILER VENEER ANCHORS @ 16" O.C. 24 GA. PRE-FINISHED METAL CAP AIR SPACE TERM BAR PIN TO WALL @ 12" O.C R-19 BATT INSULATION BITUTHENE LIQUID MEMBRANE 1 1/2" = 1'-0" 22 GA. CONT. CLEAT NAILED 8" O.C TYPE 1 FACE BRICK 5/8" GYPSUM BOARD SHEATHING 5/8" GYPSUM SHEATHING PANEL PROFILE 3-A2.02 3-A9.05 6" METAL STUDS @ 16" O.C FACE BRICK SEE EXT. ELEVATION AIR SPACE TYPICAL METAL PANEL PROFILE FOR ROOF TOP MECHANICAL SCREENS TO MATCH EXISTING PANELS @ SLC & GYMNASIUM (FIRESTONE VR-CLASSIC OMEGA) TAPERED EDGE STRIP GLUED TO TOP OF NAILER FLUID-APPLIED WEATHER BARRIER FLUID-APPLIED WEATHER BARRIER R-19 BATT INSUALTION 2" CONT. CAVITY WALL INSULATION AIR SPACE BRICK LEDGE DETAIL- INTERIOR 7 1 1/2" = 1'-0" 6" METAL STUDS @ 16" O.C 3-A5.05 3-A9.05 VENEER ANCHORS @ 16" x 16" O.C 1 1/2" = 1'-0" GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING (1/2" BACK FROM BRICK FACE) STEEL TUBE: SEE STRUCTURAL DWGS. WEEP SYSTEM w/ THRU-WALL FLASHING METAL DRIP EDGE SET IN SEALANT 5/8" GYP. BD. 8" CMU WALL W/ #5 @ 24" CENTER W/ MATCHING DOWELS 5 COURSES @ 3'-4" BITUTHENE LIQUID MEMBRANE 22 GA. VERTICAL METAL WALL PANEL 22 GA. VERTICAL METAL WALL PANEL GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING (1/2" BACK FROM BRICK FACE 5/8" GYPSUM BOARD R-19 BATT INSULATION WEEP SYSTEM W/THRU-WALL FLASHING 2" CONT CAVITY WALL INSULATION 6" METAL STUDS @ 16" O.C 5/8" GYPSUM BOARD SHEATHING WEEP SYSTEM W/ THRU-WALL FLASHING 118' - 0" BRICK LEDGE 8" x 8" STEEL TUBE w/ HIGH PERFORMANCE PAINT SEE STRUCTURAL DWGS CONT. BOND BEAM TOP AND BOTTOM FULLY GROUTED BELOW GRADE 10 3-A5.01 3-A9.05 1 1/2" = 1'-0" WALL SECTION DETAIL 3 3-A5.05 3-A9.05 1 1/2" = 1'-0" STEEL ANGLE: SEE STRUCTURAL DWGS. TERM BAR PIN TO WALL @ 12" O.C 6" METAL STUDS @ 16" O.C R-19 BATT INSULATION 1" INSULATED LOW-E GLASS 3" ALUMINUM STOREFRONT SHIM 5/8" GYP. BD. BACKER ROD IN SEALANT .090 ALUMINUM SILL TO MATCH STOREFRONT 5/8" GYPSUM BOARD SHEATHING 60 MIL EPDM OVER 1/2" PROTECTION BOARD 3 1/2" X 3 1/2" X 5/16" STEEL ANGLE STEEL TUBE: SEE STRUCTURAL DWGS. VENEER ANCHORS @ 16" x 16" O.C FLUID-APPLIED WEATHER BARRIER 6" METAL STUDS @ 16" O.C NOTE: FOR METAL WALL PANEL PROFILE; SEE DETAIL 12 ON THIS SHEET 2' - 0" 1" INSULATED LOW-E GLASS METAL STUDS @ 24" O.C. METAL DRIP EDGE SET IN SEALANT 2 PIECE 24 GA. GALVANIZED COUNTERFLASHING w/ SEALANT @ TOP HEM. SET RECEIVER ON COMPRESSED BUYTL RUBBER SEALANT TAPE ROOF TOP SCREEN DETAIL BACKER ROD IN SEALANT ALUMINUM STOREFRONT AIR SPACE COLD FORMED CEE GIRT C8x5.4 BASE TRIM SHIM FACE BRICK SEE EXTERIOR ELEVATIONS COLD FORMED CEE GIRT C8x5.4 3-A5.05 3-A9.05 22 GA. TRIM COVER 2" CONT. CAVITY WALL INSULATION BRICK LEDGE DETAIL-EXTERIOR 6 1 1/2" = 1'-0" AIR SPACE R-19 BATT INSULATION (4) #5 CONT. FACE BRICK: SEE EXTERIOR ELEVATIONS 8" x 8" STEEL TUBE: SEE STRUCTURAL DWGS. 1' - 0" COLD FORMED CEE GIRT C8x5.4 2 WALL SECTION DETAIL 3-A5.05 3-A9.05 22 GA. CORNER TRIM #5 @ 12" O.C 1 1/2" = 1'-0" G FACE BRICK: SEE EXTERIOR ELEVATIONS 5/8" GYPSUM BOARD SHEATHING FLUID-APPLIED WEATHER BARRIER VENEER ANCHORS @ 16" x 16" O.C 22 GA. PRE-FINISHED METAL WALL PANEL TO MATCH EXISTING @ SLC & GYMNASIUM (FIRESTONE VR-CLASSIC OMEGA) 4' - 0" 6" METAL STUDS @ 16" O.C 9 13 SCREEN WALL CAP 3-A2.01 3-A9.05 9 1 1/2" = 1'-0" R-19 BATT INSULATION AIR SPACE LEVEL 1 100' - 0" ROOF TOP SCREEN 3-A2.02 3-A9.05 2" CONT. CAVITY WALL INSULATION WEEP SYSTEM w/ THRU-WALL FLASHING 1 1/2" = 1'-0" 5/8" GYPSUM BOARD SLAB-ON-GRADE: SEE STRUCTURAL DWGS METAL DRIP EDGE SET IN SEALANT 6" METAL STUDS @ 16" O.C 2" AIR SPACE 6" METAL STUDS @ 16" O.C 1 EXTRA STRONG PIPE BOLLARD 8" DIA x 3'-6" x 0.5", FILL FULL HEIGHT WITH CONC. GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING OVER BITUTHENE LIQUID MEMBRANE UNDER-SLAB VAPOR BARRIER DAMPPROOFING 4" GRAVEL FILL 2" (R-10) PERIMETER INSULATION ELEVATED PERFORMANCE PLATFORM: SEE STRUCTURAL DWGS. 5/8" GYPSUM BOARD SHEATHING WALL SECTION DETAIL 1 3'-6" HIGH PERFORMANCE PAINT 3-A5.06 3-A9.05 1 1/2" = 1'-0" UNDER-SLAB VAPOR BARRIER FLUID-APPLIED WEATHER BARRIER SEALANT DAMPPROOFING 2" CONT. CAVITY WALL INSULATION 3'-0" AIR SPACE WEEP SYSTEM w/ THRU-WALL FLASHING LEVEL 1 100' - 0" 07/15/15 Addendum #3 05/29/15 For Construction 05/04/15 Progress Set NO. DATE DESCRIPTION OF REVISION METAL DRIP EDGE SET IN SEALANT 2" (R-10) PERIMETER INSULATION DAMPPROOFING This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT 3-A2.01 3-A9.05 WALL SECTION DETAIL 3-A5.03 3-A9.05 BOLLARD DETAIL APPR'D SCHOOL NO. 985 1 1/2" = 1'-0" DATE: DENVER, CO 5500 CENTRAL PARK BOULEVARD - SLC BUILDING DESIGNED BY: TH DRAWN BY: AE CHECKED BY: SCALE: GA 05/29/15 SECTION DETAILS AS NOTED ASSOCIATE ARCHITECT ARCHITECT OF RECORD H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 1 1/2" = 1'-0" SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. APPROVED CONTRACT DOCUMENT 8 MADE DEPARTMENT OF FACILITY MANAGEMENT c 2015 LOA Architecture DATE: 5 AUTHORITY DENVER PUBLIC SCHOOLS FACE BRICK: SEE EXTERIOR ELEVATIONS GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING OVER BITUTHENE LIQUID MEMBRANE 7/14/2015 12:59:28 PM 1 DWG. NO. 3-A9.05 SHEET: OF: 983_2478_985 _OR_ 3-A9.05 VENEER ANCHORS @ 16" x 16" O.C COMMONS 1/2" EXPANSION MATERIAL 2' - 6" 4" SLAB-ON-GRADE SEE: STRUCTURAL DWGS. 6" C:\Users\aelmore\Documents\A_DPS_MONUMENT SIGNS_AElmore.rvt 4" GRAVEL FILL DOOR STOP 2" x 2" x 1/4" STEEL TUBE BOLLARD w/ 1/4" FULLY WELDED TOP CAP. 42" TALL ABOVE GRADE AND 30" BELOW GRADE 2' - 7 5/8" FIELD VERIFY INCISED 1/8" DEEP MIN. 3/8" 1' - 3 5/8" 2 7/8" FLUID-APPLIED WEATHER BARRIER 0° 10 4" 6" 2015 2" CONT. CAVITY WALL INSULATION 45 DEGREE BEVEL 1' - 2 7/8" DENVER PUBLIC SCHOOLS 3 5/8" 1' - 3 5/8" 3'-0" x 7'-0" INSULATED HM DOOR NOTE: SEE DETAIL 8 ON THIS SHEET FOR ADDITIONAL INFORMATION 3/8" 3 1/4" 1 1/4" 3/8" 1 3/8" 45 DEGREE BEVEL TYP. ON ALL SIDES 12" DIA. x 36" DEEP CONCRETE PIER 45 DEGREE BEVEL INCISED 1/4" DEEP MIN. NOTE: WALL CONDTIONS VARY @ EACH DOOR. SEE PLAN DETAILS LEVEL 1 100' - 0" DOOR STOP DETAIL PLAN VIEW 6 3-A9.10 3-A9.07 CORNERSTONE DETAIL 3 1 1/2" = 1'-0" 3-A3.11 3-A9.07 1 1/2" = 1'-0" 3-A3.11 C. R. LAURENCE (OR EQUAL) BRUSHED STAINLESS STEEL GLASS STANDOFF BASE & CAP CAT # RSOB2134BS. TYPE OF 6 DOOR STOP 2" 1' - 8" 8" X 10" PHOTO OR ART WORK PROVIDED BY DPS SEE INSCRIPTION BELOW NOTE: TIME CAPSULE TO BE PLACED BEHIND BOARD OF EDUCATION PLAQUE 1' - 4" 3'-6" 3/4" TEMEPERED SAFETY GLASS SEALANT 2'-6" 1" PROVIDE AIRTIGHT SILICONE TO SEAL LID AFTER CONTENTS ARE PLACED INSIDE BRAISED CORNERS 5 1'- 5/8 " " 5/8 3 1/2" 1'3 2" 1/2" RADIUS, TYPICAL ALL CORNERS 1/2" EXPANSION MATERIAL Paul Sandoval described himself as a humble tamale maker. In reality he built a thriving business while positively impacting K-12, graduate and postgraduate education in the State of Colorado. He served as a Colorado State Senator, a Denver School Board member, and a Colorado Commission on Higher Education member. NOTE: WORDS SHOWN ARE BY ARCHITECT. DPS TO PROVIDE EXACT WORDING, GRAMMAR AND CAPITALIZATION Senator Sandoval passed the first laws governing education equity and bilingual education. He worked toward a quality education for all students and established policy for Colorado Colleges and universities. He recieved a Presidential appointment to serve as Vice Chairman of the National Association of Bilingual Education. 6" 14 GA. x 18 A366 COLDROLLED CARBON STEEL PANELS 3-A3.11 1' - 4" Paul Sandoval ETCHED GLASS 1/2" DIA. x 36" DEEP CONCRETE PIER 1' - DOOR STOP DETAIL SECTION 8 1' - 4" 2" 2" x 2" x 1/4" STEEL TUBE BOLLARD w 1/4" FULLY WELDED TOP CAP. 42" TALL ABOVE GRADE 30" BELOW GRADE 3' - 0" 2" 3-A9.07 31 1' /2" 5 1 1/2" = 1'-0" 3-A9.07 51 /2" Countless students in the United States benefited from the opportunities and guidance provided by this Denver leader. Paul Sandoval's name and campus will inspire future DPS Students and help them realize their dreams. TIME CAPSULE BOX 3-A9.07 PAUL SANDOVAL PLAQUE 2 1 1/2" = 1'-0" 3-A2.01 3-A9.07 1 1/2" = 1'-0" 2' - 0" 3" 1' - 6" 3" 2" 1" 45 DEGREE BEVEL TYP. ON ALL SIDES SPUN ALUMINUM BALL BOARD OF EDUCATION Happy Haynes, President Anne Rowe, Vice President Rosemary Rodriguez, Secretary Michael Johnson, Treasurer Landri Taylor Barbara O'Brien Arturo Jimenez 1/2" TIME CAPSULE BOX (BEHIND) Tom Boasberg, Superintendent 2" HALYARD COVER BRONZE ALLOY PLAQUE, DARK OXIDE, LEATHERED FACE, CLEAR COATED 1" 2 FLAG SNAPS 35' @ US FLAG 30' @ STATE FLAG 25' @ DPS FLAG ONE HALYARD CLEAT COVER BOX M O FR D CT E T JE E L O E D PR 5/8" GYPSUM BOARD WEEP SYSTEM w/ THRU-WALL FLASHING METAL DRIP EDGE SET IN SEALANT BITUTHENE LIQUID MEMBRANE GRACE "ULTRA" OR EQUAL @ CAP GRACE PERM-A-BARRIER (OR EQUAL) WALL FLASHING 6 5/8" 4 3/4" 4 X 6 CLOSED 24 GA PREFINISHED SHEET METAL DOWNSPOUT HARDWOOD WEDGES 1 22 GA. CONT. CLEAT NAILED @ 8" O.C DRY TAMPED SAND BITUTHENE LIQUID MEMBRANE 5' - 0" STEEL LINTEL: SEE STRUCTURAL DWGS. STEEL CENTERING WEDGES WELDED IN PLACE 24 GA. PRE-FINISHED CAP OVER WATERPROOFING 5/8" GYPSUM BOARD SHEATHING NOTE: TREAT ALL GYPSUM BOARD SHEATHING JOINTS w/ SILICONE SEALANT APPROVED BY WEATHER BARRIER MFGR. P1 (PLATE) 3/16 x 16 x 1'-4" MIN STEEL FOUNDATION SLEEVE PLATE FLUID-APPLIED WEATHER BARRIER GRAVEL FILL 2" CONT. CAVITY WALL INSULATION P1 (PLATE) 3/16" x 6 x 0'-6" MIN STEEL FOUNDATION SUPPORT PLATE VENEER ANCHORS @ 16" x 16" O.C AIR SPACE 9 COLLECTOR HEAD DETAIL 1 1/2" = 1'-0" 7 ENLARGED FLASHING DETAIL 3-A9.03 3-A9.07 3" = 1'-0" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. 1' - 4" 3' - 0" DENVER PUBLIC SCHOOLS 4 APPROVED CONTRACT DOCUMENT SCHOOL NO. 985 APPR'D 3/4" = 1'-0" DATE: SITE NO. 983 DENVER, CO STAPLETON NORTHFIELD CAMPUS 5500 CENTRAL PARK BOULEVARD - SLC BUILDING DESIGNED BY: TH DRAWN BY: AE CHECKED BY: SCALE: GA 05/29/15 MISC. DETAILS AS NOTED ASSOCIATE ARCHITECT ARCHITECT OF RECORD H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 FLAG POLE DETAIL 3-A9.07 SCHOOL DISTRICT NO. 1 DATE: 4' - 0" 3-G2.01 MADE DEPARTMENT OF FACILITY MANAGEMENT Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT 3/4" DIA. STEEL LIGHTING GROUND SPIKE WELDED TO PLATES AUTHORITY DENVER PUBLIC SCHOOLS c 2015 LOA Architecture FACE BRICK: SEE EXTERIOR ELEVATIONS 3-A4.01 3-A9.07 07/15/15 Addendum #3 05/29/15 For Construction NO. DATE DESCRIPTION OF REVISION FOUNDATION SLEEVE 16 GA. CORRUGATED AND GALVANIZED STEEL TUBE MIN. 3000 PSI CONCRETE 4" 10 3/4" 2" 6 3/4" TEM BAR w/ FASTENERS @ 12" O.C 2" 24 GA PRE-FINISHED SHEET METAL HEADER BOX 3" = 1'-0" SEALANT OR WATERPROOF COMPOUND 2" DEEP 1' - 0" 3" 2" OVERLAP (MIN) 10" 1" 3" TIME CAPSULE PLAQUE 3-A9.07 ALUMINUM FLASH COLLAR 2 PC 24 GA. GALVANIZED COUNTERFLASHING w/ SEALANT @ TOP HEM. SET RECEIVER ON COMPRESSED BUTYL RUBBER SEALANT TAPE 2" OVERLAP (MIN) 1' - 4" 1 3-A2.01 DWG. NO. 3-A9.07 SHEET: OF: 983_2478_985 _OR_ 3-A9.07 7/14/2015 3:35:21 PM C:\Users\tholk\Documents\A_DPS_COMMON-II Core Shell_tholk.rvt R-19 BATT INSULATION 6" METAL STUDS @ 16" O.C CAST ALUMINUM CLEATS VENEER ANCHORS @ 16" x 16" O.C REFERENCE SPECIFICATION SECTION 10 14 00 1' - 6" DEDICATED TO THE CITIZENS OF DENVER 1 1/4" 3/4" 3/4" 1 1/4" 1 3/4" 1 1/4" 1" 1" SATIN RAISED LETTER FAVES (HELVETICA OR SIMILAR) CENTER JUSTIFIED, CLEAR COATED 2 3/4" 2015 INCISED 1/8" DEEP MIN. TYP. 1 3/4" NORTHFIELD HIGH SCHOOL 1'-6" X 1'-4" x 4" BLOCK -OUT FOR TIME CAPSULE CAST ALUMINUM STATIONARY TRUNK FACE BRICK: SEE EXTERIOR ELEVATONS MOUNTED WITH CONCEALED STUDS AT ALL CORNERS TYP. EDGE 1/2" FINISH NOTES 1 2 3 4 5 6 7 8 9 1. ALL CORNER GUARDS TO BE 4'-0" HIGH CG1, UNLESS NOTED OTHERWISE. 2. ALL CORNER GUARDS TO BE INSTALLED ABOVE FLOOR BASE. FINISH LEGEND CPT1 FLOOR FINISH (TRANSITION) FLOOR FINISH CPT1 A A OFFICE 3-105B WC1 P1E RB1 SC1 CG2 PT4 P1E PT1 PT1 B P1 RB1 SC1 PT2/P1E PT1 PT1 VESTIBULE 3-103.1 C WP1: FRP Panels (floor to 4'-0" AFF) on all walls 1 WATER ENTRY 3-108 ELECTRICAL 3-109 SERVING 3-104 PROVIDE A 6'-0" TALL WAINSCOT (PT5 & PT6) AROUND THE ENTIRE WALL. MATCH RANDOM PATTERN ON ADJACENT WALLS P1 RB1 SC1 P1 RB1 SC1 1 P1E PT1 PT1 WINDOW COVERING LEGEND CORRIDOR 3-106 P1 RB1 SC1 ALIGN EDGE OF FLOOR COLOR TRANSITION WITH EDGE OF WALL/TILE VESTIBULE 3-106D UP P5 RB1 SC1 WWP1: WOOD WALL PANEL, SUSTAINABLE FLOORING, TEXTURA RECYCLED, 3/8" THICK X 53.5" WIDE X 13.5" HIGH, COLOR: WALNUT. PROVIDE TRIM AND ACCESSORIES AS REQUIRED. TILE: G1: CUSTOM BUILDING PRODUCTS, GROUT COLOR TBS PT1: PORCELAIN TILE, 2" X 2" X .25" UNGLAZED PLAIN FACE FLOOR TILE, DALTILE KEYSTONES, GROUP 1 KEYSTONES ELEMENTAL DESERT GRAY SPECKLE D200 AS FIELD (FLOORS), PROVIDE ALL TRIM PIECES SUCH AS INSIDE AND OUTSIDE CORNER COVE BASE (BUILT-UP COVE, MB-5A), STRAIGHT COVE BASE (BUILT-UP COVE, MB-5A), BULLNOSE BUILT-UP COVE AT PAINTED WALLS. PT2: CERAMIC TILE, 4.25" X 4.25" X 5/16" TILE DALTILE MATTE GROUP 1 URBAN PUTTY (WALLS) PT3: CERAMIC TILE, 4.25" X 4.25" X 5/16" TILE DALTILE SEMI-GLOSS GROUP 4 MUSTARD Q012 (WET WALL ONLY) PT4: CERAMIC TILE, 4.25" X 4.25" X 5/16" TILE DALTILE SEMI-GLOSS, FESTIVA WILLOW QF42 (WET WALL ONLY) PT5: PORCELAIN TILE, 12" X 24" (WALLS) TILE, NOVABELL, MILANO SERIES, MONTENAPOLEONE MATTE PT6: PORCELAIN TILE, 12" X 24" (WALLS) TILE, NOVABELL, MILANO SERIES, SCALA MATTE TRC: SCHLEUTER, ANNODIZED ALUMINUM AT ALL TILE FLOORING TRANSITIONS PT2/P1E PT1 PT1 WC2 P1 PT5&6 RTP1 P5 RB1 WD1 AT CLERESTORY PT4 PERFORMANCE PLATFORM 3-110 MOTORIZED ROLLER SHADES - BLACKOUT WD1: WOOD PERF. PLATFORM FLOOR SYSTEM, RE: 1/3-A9.21 1 SEATING 3-100 WC2 SS1: SOLID SURFACE, CORIAN, WHISPER, WINDOW SILLS, UNO UP ALIGN EDGE OF FLOOR COLOR TRANSITION WITH EDGE OF DOOR FRAME WOMENS TOILET 3-101 METAL SLAT HORIZONTAL BLINDS INTERIOR ARCHITECTURAL WOODWORK: PL1: PLASTIC LAMINATE, FORMICA, NEUTRAL WEFT, 5875-58, HORIZONTAL SURFACES THROUGHOUT, UNO PL2: PLASTIC LAMINATE, FORMICA, CHERRY BIRCH, 7484-58, VERTICAL SURFACES THROUGHOUT, UNO C PLATFORM CIRCULATION 3-110A WC1 FINISH SCHEDULE P1 RB1 WOM1 UP E FLOOR FINISH GRAIN DIRECTION CORNER GUARDS (CG1 & CG2) P1 RB1 SC1 P1E RB1 SC1 FAMILY ASSIST TOILET 3-106A P1 PT5&6 RTP2 AT CLERESTORY P1 PT5&6 RTP2 WALL ACCENT FINISH CUST 3-106B P1 PT5&6 RTP2 P1 RB1 RTP2 VESTIBULE P1 3-102.1 RB1 RTP2 FLOOR FINISH SV01 IDF 3-106C P1 RB1 WOM1 D WP1: FRP Panels (floor to 4'-0" AFF) on all walls 1 WC2 VESTIBULE 3-100C SV1 ACCENT THEATER STORAGE 3-107 PT4 P1E RB1 SC1 BASE FINISH B CUST. 3-104A PT3 RB1 FINISH EXTENTS P1 RB1 SC1 1 LAUNDRY 3-104B P1E RB1 SC1 TABLE & CHAIR STORAGE 3-103 MEN TOILET 3-102 TOILET 3-105A WALL FINISH KITCHEN PANTRY 3-105 WP1: FRP Panels (floor to 4'-0" AFF) on all walls P1 RB1 SC1 P1 CARPET: CPT1: TANUDS, 6' ROLL, POWERBOND, PARADIGM 04316, PARTICOLOR 13508 (OFFICE) WOM1: TANDUS, CARPET TILE, 24" X 24" ABRASIVE ACTION II 02578, WINTER GRAY 19103 (ENTRIES) ER3 MODULAR BACKING E CONCRETE: SC1: SEALED CONCRETE PER SPECIFICATION RTP1: RETROPLATE CONCRETE POLISHING SYSTEM, LARGE AGGREGATE GRIND, MEDIUM SHEEN, COLOR - SLATE BLUE RTP2: RETROPLATE CONCRETE POLISHING SYSTEM, LARGE AGGREGATE GRIND, MEDIUM SHEEN, COLOR - SAND F RESILIENT WALL AND BASE ACCESSORIES: RB1: RESILIENT COVE BASE, JOHNSONITE THERMOSET BASEWORKS, COLOR #44 DARK BROWN, 4" HIGH RUBBER STAIR TREAD: (PERFORMANCE PLATFORM STAIRS), JOHNSONITE, INTEGRAL TREAD/RISER, #44 DARK BROWN, U.N.O. TRR: RESILIENT TRANSITION, JOHNSONITE PROFILES AS NEEDED, TMOULD PREFERRED BY DISTRICT, PROVIDE TRANSITION STRIPS AT EACH DOOR INTERIOR PAINTING ( 'E' SUFFIX = EPOXY IN LIEU OF SEMI-GLOSS): P1: KWAL PAINT, CLW1038W (MAIN) P2: SHERWIN WILLIAMS, PEPPERCORN SW7674 (DOOR FRAME) P3: SHERWIN WILLIAMS, PEPPERCORN SW7674 (HIGH PERFORMANCE PAINT FOR BEAMS, JOISTS, AND COLUMNS. DOES NOT INCLUDE EXPOSED DECK, U.N.O.) P4: PURE WHITE, EXPOSED DECK AS NOTED ON DRAWINGS, U.N.O. P5: BLACK, FLAT LINE OF BEAM FURRING HEADER ABOVE UP UP AT CLERESTORY PLATFORM CIRCULATION 3-110B WC2 G UP CORNER GUARDS: CG1: CORNER GUARD, GALVANIZED STEEL PAINTED TO MATCH ADJACENT, 2-1/2" X 2-1/2" WINGS, 4'-0" TALL CG2: CORNER GUARD, STAINLESS STEEL EMBOSSED PATTERN #4 SATIN FINISH (WARMING PANTRY), 4'-0" TALL P5 RB1 SC1 G METAL TOILET COMPARTMENTS: MTC1: BRADLEY, BAKED ENAMEL, #2123 CHARCOAL, PER SPECIFICATION ACOUSTIC PANELS: AP1: COMMON SEATING, 1" THICK, DECOUSTICS - AP, FR701 2100, FLANNEL 795 AP2: COMMON SEATING, 1" THICK, DECOUSTICS - AP, FR701 2100, SILVER NEUTRAL 406 6'-0" P1 PT5&6 RTP2 H H 1 P1 RB1 CPT1 SECURITY 3-100B VESTIBULE 3-100A LOCKERS: L1: BASIS OF DESIGN: LYONS, 12"X12"X72" DOUBLE TIER, COLOR: T.B.D. P1 RB1 WOM1 WALL PROTECTION: WP1: FRP, CRANE COMPOSITES, 4 X 8 SHEETS, 4'-0" WAINSCOT TALL. COLOR: T.B.D. J 1 NO. 7/15/15 Addendum 3 5/29/15 FOR CONSTRUCTION DATE DESCRIPTION OF REVISION AUTHORITY MADE APPR'D DENVER PUBLIC SCHOOLS 1 2 3 4 4.5 5 6 7 8 9 DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 1 3-I2.10 FINISH PLANS LEVEL 1 - AREA A DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: 1/8" = 1'-0" N Designer Author Checker 05/29/2015 FINISH PLAN LEVEL 1 AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: DENVER, CO 9100 E. 56th AVE DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SITE NO. 983 NORTHFIELD HIGH SCHOOL Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS SCHOOL NO. 985 DWG. NO. 3-I2.10 SHEET: OF: 983_2478_985 _OR_ 3-I2.10 K COMMONS C:\Users\sdangel\Desktop\A_DPS_COMMON-II Interior.rvt J 7/14/2015 1:40:14 PM WINDOW COVERING: WC1: METAL SLAT HORIZONTAL BLINDS, BASIS OF DESIGN: SWF CONTRACT, COLOR: NATURAL STONE 181 WC2: MOTORIZED ROLLER SHADE, MECHOSHADE, ELECTRO/2, BLACKOUT SHADECLOTH COLLECTION, EQUINOX BLACKOUT, 0100 SERIES (OPAQUE) WINTER 0118 COMMONS - DESIGN LOAD CRITERIA: 2 1 3 12'-0" 4 14'-0" 5 20'-0" 6 20'-0" 7 20'-0" 8 20'-0" A. DEAD LOADS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AS SHOWN ON PLANS C. ROOF LIVE LOADS . . . . . . . . . . . SEE SNOW AND WIND LOADS BELOW (30 PSF MINIMUM) D. BUILDING OCCUPANCY CATEGORY (IBC 1604.5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . III E. SNOW LOADS: GROUND SNOW LOAD, Pg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 . .PSF FLAT ROOF SNOW LOAD, Pf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30. PSF . SNOW EXPOSURE FACTOR, Ce . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 SNOW LOAD IMPORTANCE FACTOR, Is . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 THERMAL FACTOR, Ct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.0 SEISMIC LOADS: SEISMIC IMPORTANCE FACTOR, Ie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.25 Ss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.173 . S1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.057 . SITE CLASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D Sds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.184 . Sd1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.091 . SEISMIC DESIGN CATEGORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B DESIGN SEISMIC FORCE RESISTING SYSTEM (S) . . . 9 18'-3" 18'-3" RE: CIVIL 9" 1' - 0" 6' - 8" 2' - 1" 17' - 11" 4' - 7" 6' - 0" 5' - 0" 6' - 4" 3' - 4" 3' - 7" DESIGN BASE SHEAR . . . . . . . . . . . SEISMIC RESPONSE COEFFICIENT, Cs . RESPONSE MODIFICATION FACTOR, R . ANALYSIS PROCEDURE USED . . . . . . 3-S4.35 4 2 3-S4.31 3-S4.31 3-S4.31 1 6 3 4 3 3-S4.31 3-S4.33 3-S4.31 3-S4.33 8" HSS6X6X1/4 BP6 6 4 3-S4.31 3-S4.31 A 7" FH HSS6X6X1/4 BP6 15' - 4" HSS6X6X1/4 BP6 FH FH HSS6X6X1/4 BP6 3 3-S4.33 6' - 11" 3-S4.32 6" HSS10X10X5/16 BP5 7 1 102' - 6" T.O. WALL 3-S3.30 6 6 3-S4.31 3-S4.32 6' - 8" HSS10X10X5/16 BP5 1' - 5 1/2" HSS10X10X5/16 BP5 HSS6X6X1/4 HSS10X10X5/16 BP5 2' - 1" HSS6X6X1/4 BP6 3-S4.00 TYP 1' - 8 1/4" 1' - 11 1/2" 1' - 6" 3 2' - 4 1/2" 4 3-S4.31 10' - 0 1/2" 4 3-S3.30 3' - 0" FC FE 3-S4.31 5' - 10" COILING DOOR SUPPORT POST ~ RE: SUPPLIER (TYP. OF 2) 4' - 10" UP 8 3-S4.32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 k . . . . . . . . . . . . . . . . . . . . . .0.077 . . . . . . . . . . . . . . . . . . . . . . . . .EQUIVALENT LATERAL FORCE ANALYSIS ( ASCE-7 12.8) UP UP 8 3 3-S4.32 3-S4.32 2 3 4 5 ROOF NOT AT EDGES/CORNERS ROOF AT EDGES ROOF AT CORNERS WALLS NOT AT CORNERS WALLS AT CORNERS WIND PRESSURE N/A N/A - N/A - 23.4 -PSF 23.4 PSF - WIND SUCTION -32.9 PSF -70.3- PSF -51.6- PSF -22.5-PSF -41.2 -PSF I. 1' - 7" FC SPECIAL LOAD REQUIREMENTS ARE DESCRIBED IN PLAN NOTES OR SPECIFIC LOCATIONS ON THE CONTRACT DRAWINGS. HSS10X10X5/16 (TYP OF 3) 1' - 2" D 106' - 6" T.O. WALL 1 100' - 0" 102' - 6" 9' - 0 3/4" FC 8" 6 FK 1' - 11 1/2" 1' - 10" 10'-0" FH 7 1/2" 3-S4.32 C . . . . NOTES: 1. VALUES GIVEN ABOVE ARE FOR EFFECTIVE WIND AREAS OF 10 SQUARE FEET OR LESS. VALUES MAY BE REDUCED FOR AREAS GREATER THAN 10 SQUARE FEET IN ACCORDANCE WITH PROCEDURES GIVEN IN ASCE 7 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STABILITY OF THE COMPLETED STRUCTURE ARE AS FOLLOWS: STRUCTURES", METHOD 2. 2. VALUES GIVEN ABOVE WERE DETERMINED AT A MEAN ROOF HEIGHT OF 30 FT. WIND PRESSURE VALUES MAY BE REDUCED FOR COMPONENTS AT LOWER ELEVATIONS IN ACCORDANCE WITH PROCEDURES GIVEN IN ASCE 7 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", METHOD 2. 2. PRESSURE INDICATES LOAD ACTING TOWARDS SURFACES. SUCTION INDICATES LOAD ACTING AWAY FROM SURFACES. 3. REFER TO ASCE 7 "MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES", FIGURES 6-11 THROUGH 6-17, AS APPLICABLE, FOR DEFINITION OF ZONES. 4. THE VALUES ABOVE DO NOT APPLY TO CHIMNEYS, TANKS ROOFTOP EQUIPMENT, SIGNS OR OTHER SIMILAR STRUCTURES. 5. CLADDING AND COMPONENTS SHALL BE DESIGNED FOR MAXIMUM PRESSURE AND SUCTION ACTING INDEPENDENTLY. b. ALL PARAPETS AND OTHER FEATURES WITH WIND EXPOSURE ON OPPOSITE SIDES SHALL BE DESIGNED FOR ± 52.7 PSF. c. CANOPIES AND OVERHANGS: REFER TO ASCE 7 FOR DESIGN PROCEDURES TO DETERMINE COMPONENT AND CLADDING WIND LOADING REQUIREMENTS. 6" 7" 26'-0" 8" . . . . 1 LOCATION/ DESCRIPTION 7 6" 3-S4.31 . . . . ZONE HSS6X6X1/4 3'BP6 - 8 1/2" FE 4 . . . . 12' - 0" HSS6X6X1/4 BP6 1' - 1" HSS6X6X1/4 BP6 HSS6X6X1/4 7" 6" 3' - 7" 7" 1' - 10" 8" 16'-0" FH 3' - 9" FH 11' - 9" 3' - 0" 7" FH 10' - 1 1/4" 6" HSS6X6X1/4 BP6 B HSS6X6X1/4 BP6 15' - 8" 8" 3-S4.31 FH 5' - 3" 4 ? FH 6" FH . . . . G. WIND LOADS: BASIC WIND SPEED (3-SECOND GUST) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 . MPH WIND IMPORTANCE FACTOR, I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.15 WIND EXPOSURE CATEGORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C INTERNAL PRESSURE COEFFICIENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+- 0.18 (ENCLOSED) w H. COMPONENTS AND CLADDING WIND PRESSURES: a. PRESSURE AND SUCTION VALUES: 4' - 3" 3 3-S4.33 3' - 0" 1 . . . . 3-S4.32 RE: CIVIL 6' - 3 1/2" 102' - 6" T.O. WALL 3-S4.31 6" 8" 7" 4 FH FH 13' - 4" 2 FJ 3-S4.32 FE Type Mark 7 FH 102' - 2" FA FB FC FD FE FF FG FH FJ FK FL 3-S4.32 HSS10X10X5/16 BP5 F 1' - 2" 8" 1' - 7 3/4" 8" FH 8" 6" 3' - 0" 1' - 2 1/2" 3' - 0" 10' - 10" 106' - 6" T.O. WALL 102' - 6" 3-S4.31 3-S4.36 4 4 HSS6X6X1/4 BP6 3-S4.31 FH FH HSS6X6X1/4 BP6 HSS6X6X1/4 BP6 FH FH HSS10X10X5/16 BP5 FC HSS10X10X5/16 BP5 10 3-S4.31 HSS6X6X1/4 BP6 FH 7 3-S4.32 7 FH 13' - 4" 3-S4.32 3-S4.36 4' - 0" 6 4 3-S4.31 3-S4.31 1' - 10" 6' - 7" HSS6X6X1/4 BP6 3-S4.32 102' - 6" T.O. WALL HSS10X10X5/16 1 2 3-S3.30 2' - 0" 1' - 10 1/2" 10' - 8" HSS6X6X1/4 BP6 3' - 0" 3' - 0" 8" 3-S4.31 21'-9" 3-S4.36 6' - 7" 2' - 0" 1 1/2" 2' - 8 1/2" 5 3-S4.31 1' - 4 3/4" HSS6X6X1/4 BP6 1' - 4" 8'-0" 3' - 2 3 3-S4.33 9 3-S4.36 1' - 7 " J 1 3-S4.33 FL 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION 1' - 4" 1' - 4" 9' - 1" 1' - 4" FH HSS7.625X0.375 BP6 7' - 2 1/2" 7" 11 3 /4" 4' - 6" 6' - 11" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 APPR'D SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED COMMON - FOUNDATION PLAN ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT 1/8" = 1'-0" MADE DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture DENVER PUBLIC SCHOOLS COMMON - FOUNDATION PLAN AUTHORITY DENVER PUBLIC SCHOOLS 8" K 1/2" 2' - 8" 4" 11" 13' - 1' - 9" 4' - 0" 1' - 7" 2' - 1" TYP 2 6 5' - 4" 7 (TYP OF 3) 1' - 8 1/2" 4 3-S4.00 7 3-S3.00 UP 4' - 3" FC 5 3/8" HSS10X10X5/16 BP5 1' - 0 5/8" FJ FH FC UP 100' - 0" T.O.W. 7" HSS6X6X1/4 BP6 HSS10X10X5/16 BP5 6" 1' - 8" 4' - 10" 6' - 8" 1' - 8" 10'-0" 13' - 8 1/2" 1 3-S4.32 18' - 8 1/4" 3 3-S3.30 UP C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt 1'-6" 1'-6" 1'-6" 2'-0" 1'-6" 2'-0" 2'-0" 1'-0" 1'-0" 1'-0" 1'-0" NOTES: XXXX'-X 1. TOP OF SLAB ELEVATION = 100'-0 (5238.00 USGS), UNLESS NOTED THUS: ON PLAN. SLAB SHALL SLOPE UNIFORMLY BETWEEN POINTS OF UNEQUAL ELEVATION. 2. SLAB ON GRADE SHALL BE 4" THICK NORMAL WEIGHT CONCRETE CONSTRUCTED OVER A VAPOR BARRIER. PLACE THE VAPOR BARRIER OVER A 4" THICK LAYER OF GRANULAR MATERIAL, RE: SPECIFICATIONS. REINFORCE SLAB WITH 6x6W4.0xW4.0 W.W.F., UNLESS NOTED OTHERWISE ON PLAN. WELDED WIRE FABRIC TO BE PLACED AT THE CENTER OF SLAB THICKNESS USING SLAB BOLSTERS OR EQUIVALENT AT 4'-0 O.C. 3. REFER TO GENERAL NOTES AND DETAIL 1/S4.00 FOR OVEREXCAVATION REQUIREMENTS. 4. RE: DETAIL 5/S4.00 FOR SLAB ON GRADE JOINTING REQUIREMENTS. 5. RE: DETAIL 6/S4.00 FOR SLAB ON GRADE DETAILS AT SLAB STEPS AND MASONRY PARTITION WALLS. 6. RE: DETAIL 4/S4.00 FOR SLAB ON GRADE JOINTING REQUIREMENTS AT COLUMNS. 7. ON PLAN INDICATES FOOTING TYPE/MARK. 8. TYPICAL TOP OF INTERIOR FOOTING ELEVATION = 99'-0 U.N.O. TYPICAL TOP OF PERIMETER FOOTING ELEVATION = 98'-0 U.N.O. 9. FOOTINGS SHALL BE CENTERED ON GRID LINES OR UNDER COLUMNS AND WALLS UNLESS DIMENSIONED OTHERWISE ON PLAN. 10. RE: 7/S4.22 FOR BASE PLATE AND ANCHOR BOLT INFORMATION. 11. COLUMNS SHALL BE CENTERED ON GRIDS UNLESS DIMENSIONED OTHERWISE ON PLAN. 12. RE: CONCRETE REINFORCING SPLICE SCHEDULE ON SHEET S1.01 13. RE: F/S4.22 FOR VENEER SUPPORT FRAMING. 14. WX INDICATES MASONRY WALL TYPE. RE: WALL SCHEDULE ON S6.00. 102' - 6" T.O. WALL 6 7/14/2015 12:25:26 PM 5' - 6" 5' - 6" 7' - 0" 8' - 6" 7' - 0" 8' - 6" 9' - 6" 4' - 0" 5' - 0" 5' - 6" 7' - 2 1/4" 7" 34'-0" 3-S4.31 H 5' - 6" 5' - 6" 7' - 0" 8' - 6" 7' - 0" 8' - 6" 9' - 6" 4' - 0" 5' - 0" 5' - 6" 7' - 2 1/4" 4 3-S4.31 G (5)-#6 E.W. (6)-#6 E.W. T&B (7)-#6 E.W. (10)-#6 E.W. (7)-#6 E.W. T&B (10)-#6 E.W. T&B (12)-#6 E.W. T&B (4)-#6 E.W. (5)-#6 E.W. (5)-#6 E.W. (4)-#6 E.W. THICKNESS DWG. NO. 3-S2.01 SHEET: OF: 983_2478_985 _OR_ 3-S2.01 4 12' - 8 3/4" HSS10X10X5/16 SPREAD FOOTING SCHEDULE REINFORCEMENT LENGTH WIDTH COMMONS HSS6X6X1/4 BP6 7" 5'-3" HSS6X6X1/4 BP6 HSS6X6X1/4 BP6 6" 160'-3" 3-S4.32 E? 2 3-S4.35 11' - 7 3/4" 29'-3" 4 2 1 3 12'-0" 4 14'-0" 5 20'-0" 6 20'-0" 7 20'-0" 8 20'-0" 9 18'-3" NOTES: XXXX'-X 1. BOTTOM OF ROOF DECK ELEVATION INDICATED THUS: ON PLAN. STRUCTURE SHALL SLOPE UNIFORMLY BETWEEN POINTS OF UNEQUAL ELEVATION. 2. TYPICAL ROOF DECK: A. TYPICAL ROOF DECK SHALL BE 1.5" TYPE 'B', 20 GAGE, GALVANIZED METAL DECK, 3 SPAN MINIMUM (SEE TABLE IN STRUCTURAL GENERAL NOTES). B. WELD TO SUPPORTS SHALL BE 5/8" PUDDLE WELDS IN A 36/7 PATTERN. C. SIDELAP FASTENERS SHALL BE 6-#10 BUILDEX TRAXX SCREWS (OR EQUIVALENT) PER SPAN, PROVIDED BY THE DECK SUPPLIER UNO ON PLAN. D. WELD DECK EDGES TO THE SUPPORTS WITH 5/8" PUDDLE WELDS AT 6" O.C. E. DECK SHALL DEVELOP A MINIMUM DIAPHRAGM SHEAR CAPACITY OF 597 PLF. ALTERNATE CONNECTION SCHEMES MAY BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO USE ON THE PROJECT. 2. ACOUSTIC ROOF DECK: A. ACOUSTIC ROOF DECK SHALL BE 3" TYPE 'NA', 20 GAGE, GALVANIZED METAL DECK, 3 SPAN MINIMUM (SEE TABLE IN STRUCTURAL GENERAL NOTES) AT HIGH ROOF. ACOUSTIC ROOF DECK SHALL BE 1.5" TYPE 'BA', 20 GAGE, GALVANIZED METAL DECK, 3 SPAN MINIMUM (SEE TABLE IN STRUCTURAL GENERAL NOTES) AT LOW ROOF. B. WELD TO SUPPORTS SHALL BE 5/8" PUDDLE WELDS IN A 36/7 PATTERN. C. SIDELAP FASTENERS SHALL BE 8-#10 BUILDEX TRAXX SCREWS (OR EQUIVALENT) PER SPAN, PROVIDED BY THE DECK SUPPLIER. D. WELD DECK EDGES TO THE SUPPORTS WITH 5/8" PUDDLE WELDS AT 6" O.C. E. DECK SHALL DEVELOP A MINIMUM DIAPHRAGM SHEAR CAPACITY OF 640 PLF. ALTERNATE CONNECTION SCHEMES MAY BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO USE ON THE PROJECT. 3. FRAMING NOMENCLATURE: 18'-3" 4.6 PROVIDE 9-#10 BUILDEX TRAXX SCREW SIDELAP FASTENERS PER SPAN AT ROOF DECK BETWEEN GRIDS 2-5 PROVIDE 9-#10 BUILDEX TRAXX SCREW SIDELAP FASTENERS PER SPAN AT ROOF DECK BETWEEN GRIDS 7-9 . 1 3-S5.32 6" 36' -6" A W16X26 W16X26 15 25 6" W27X84 W16X26 W27X84 25 25 25 W16X26 W16X26 15 15 1 3-S5.31 1 5 3-S5.32 5 7/8" 3-S5.33 3-S5.30 TYP @ POST W12X14 BEAM SIZE 1 30KCS3 W30X90 30KCS3 30KCS3 30KCS3 W30X90 30KCS3 W30X90 30KCS3 W18X50 3-S5.31 30KCS3 1 3-S5.31 W30X90 1 3-S5.31 30KCS3 30KCS3 30KCS3 W30X90 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 30KCS3 W30X90 3-S5.31 30KCS3 3-S5.31 30KCS3 3-S5.31 W30X90 1 3-S5.31 W30X90 1 30KCS3 1 30KCS3 1 30KCS3 W30X90 30KCS3 30KCS3 RE:7/3-S5.31 FOR SIM DRAG CONNECTION 30KCS3 _ 30KCS3 B 7 30KCS3 16'-0" 3-S5.32 W14X30 3 W18x40 (2") 4. W18X50 20K4 5. 5 7/8" 6. FUTURE MEP AREA (ALLOWABLE LOAD OF 50PSF 36'-0" 26' - 0" W14X22 17K 3-S5.31 3 7 7. 3-S5.32 TYP. GRIDS 3-9 8. 6 9 10 3-S5.31 3-S5.31 9. 3-S5.32 3-S5.31 W24X55 W27X84 25 25 25 25 25 TYP. GRIDS 3-9 7 W24X55 W27X84 W24X55 15 15 TYP. GRIDS 3-8 7 3-S5.31 HSS14X10X5/8 D W24X55 6" W12X26 10' - 0" C 28K9 28K9 3-S5.31 SIM 10. W24X55 1 W24X68 28K9 W16X26 RE:7/3-S5.31 FOR SIM DRAG CONNECTION 11. 2 3-S4.35 29'-3" 3-S5.31 3 7 3-S5.32 3-S5.31 SIM 12. 160'-3" 7 13. 3-S5.31 14. 15. 16. W12X26 _ 10K1 5'-3" F W12X14 W12X14 E BEAM REACTION IN KIPS (FACTORED LOADS) REACTION APPLIES AT EACH BEAM CAMBER (IN.) END OF BEAM UNLESS INDICATED OTHERWISE. IF BEAM REACTIONS ARE NOT SHOWN ON PLAN, DESIGN CONNECTIONS FOR 15 KIPS MINIMUM (FACTORED LOADS). SEE SPECIFICATIONS FOR CONNECTION DESIGN REQUIREMENTS. BEAMS SHALL BE FABRICATED SUCH THAT AFTER ERECTION ANY CAMBER DUE TO ROLLING OR SHOP FABRICATION IS UPWARD. SEE SPECIFICATIONS AND GENERAL NOTES FOR CONNECTION DESIGN REQUIREMENTS. MOMENT CONNECTIONS ARE NOTED THUS: ON PLAN. RE: X/SX.X FOR TYPICAL BEAM TO BEAM MOMENT CONNECTION. BEAMS AND/OR JOISTS ARE EQUALLY SPACED BETWEEN GRIDS OR COLUMNS UNLESS DIMENSIONED OTHERWISE. STEEL BAR JOISTS: A. RE: SJI STANDARD SPECIFICATION AND OSHA FOR BRIDGING SIZE AND LOCATION REQUIREMENTS. CONTRACTOR TO COORDINATE BRIDGING LOCATIONS W/ MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR. B. DESIGN JOISTS TO RESIST UPLIFT PRESSURE = 19 PSF WITHIN 14' OF EXTERIOR WALLS AND 14 PSF ELSEWHERE. C. XXXSPXX ON PLAN INDICATES STEEL BAR JOIST WITH SPECIAL LOADING. MAXIMUM LIVE LOAD DEFLECTION IS L/360 UNLESS NOTED OTHERWISE (MAXIMUM TOTAL DEFLECTION IS L/240). D. OFFSET JOISTS AS REQUIRED TO SATISFY JOIST BEARING LENGTH REQUIREMENTS AT INTERIOR GIRDERS WITH FLANGE WIDTHS THAT ARE NARROWER THAN SJI REQUIREMENTS. E. RE: DETAILS 2/S5.02 AND 3/S5.02 FOR STRUCTURAL REQUIREMENTS WHEN SUPPORTING EQUIPMENT FROM STEEL JOISTS. INDICATES ROOF PENETRATION. COORDINATE OPENING SIZE AND LOCATION WITH ARCHITECTURAL AND MECHANICAL DRAWINGS AND MECHANICAL CONTRACTOR. RE: DETAILS AND GENERAL NOTES FOR STRUCTURAL REQUIREMENTS. THE CONTRACTOR SHALL SUBMIT DRAWINGS OF ALL MISCELLANEOUS ROOF PENETRATIONS NOT SHOWN ON PLAN FOR ARCHITECT'S AND ENGINEER'S APPROVAL. MECHANICAL: A. RE: MECHANICAL DRAWINGS FOR EXACT SIZE AND LOCATION OF MECHANICAL EQUIPMENT. B. MECHANICAL EQUIPMENT WEIGHT SHALL BE AS INDICATED ON PLAN. ANY DEVIATION IN EQUIPMENT WEIGHT SHALL BE REPORTED TO THE ARCHITECT AND STRUCTURAL ENGINEER AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REDESIGN OF THE FRAMING SUPPORTING THE UNIT. C. PROVIDE SUPPORT FRAMING UNDER ALL MECHANICAL UNIT CURBS AND AROUND ALL ROOF PENETRATIONS. RE: DETAILS 1/S5.02 INDICATES 4" THICK (MIN.) NORMAL WEIGHT CONCRETE PAD UNDER MECHANICAL EQUIPMENT. REINFORCE PAD WITH #4 BARS AT 12" O.C. EACH WAY CENTERED IN PAD. RE: 7/S5.02 FOR CONTINUOUS EDGE ANGLE SPLICE DETAIL. ANGLE TO BE CONTINUOUS ALONG EACH PERIMETER WALL. LX REFERS TO LINTEL TYPE. RE: SHEET S6.00 FOR LINTEL SCHEDULE. INDICATES BOTTOM FLANGE BRACE. RE: DETAIL 1/S5.31 INDICATES AREAS WITH ACOUSTIC ROOF DECK. RE: SPECS _ 6" 7 17 W12X14 7 3-S5.31 SIM 1 5 3-S5.32 3-S5.32 28K9 28K9 W24X55 34'-0" W16X26 3 3-S5.32 HSS14X10X5/8 8 3-S4.36 4 7 3-S5.31 W24X55 W24X55 W12X14 W24X55 HSS14X10X5/8 HSS14X10X5/8 W12X14 W14X22 W12 X14 10K1 W12X14 10K1 W12X14 10K1 6'-8" 3-S5.31 TYP. GIRDS 3-9 W16X26 LIVE LOADS: SNOW ................................................................................................... 30 PSF (NON-REDUCIBLE) OR 25.2 PSF (NON-REDUCIBLE) + DRIFTING 8 3-S3.00 118' - 5 17/32" B.O.D. ROOF LOADS - MECHANICAL DEAD LOADS: HOUSEKEEPING PAD (7 1/2" AVG).................................................. 94 PSF ROOFING AND INSULATION............................................................... 5 PSF METAL ROOF DECK........................................................................... 3 PSF MECHANICAL, LIGHTS, CEILING, SPRINKLERS................................ 10 PSF TOTAL = 112 PSF + STRUCTURE LIVE LOADS: MECHANICAL UNIT.............................................................................. ACTUAL WEIGHT W12X14 W12X14 21'-9" 115'-5 3/4" B.O.D. SLOPE 9 W10X22 3-S4.36 3-S5.32 W16X26 3-S4.36 W16X26 3-S5.31 3-S5.32 W16X26 W12X14 2 2 W12X14 1 W10X22 W16X 26 5 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION 1' - 0" 3-S5.31 3-S5.31 APPR'D DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture 116'-5 3/4" B.O.D. This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED COMMON - ROOF FRAMING PLAN ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. 1/8" = 1'-0" MADE DENVER PUBLIC SCHOOLS 3 COMMON - ROOF FRAMING PLAN AUTHORITY DWG. NO. 3-S2.02 SHEET: OF: 983_2478_985 _OR_ 3-S2.02 3-S4.36 W16X26 W12X14 3 COMMONS K W12X14 8'-0" 3-S4.33 9 W12X14 W18X35 J DENVER PUBLIC SCHOOLS 7/14/2015 12:25:29 PM 8 PSF 3 PSF 10 PSF 21 PSF + STRUCTURE HSS14X10X5/8 1 118'-5 1/2" B.O.D. C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt W12X14 10K1 W12X14 10K1 10K1 W12X14 10K1 10K1 W12X14 10'-0" H DEAD LOADS: BALLAST, ROOFING AND INSULATION............................................. METAL DECK........................................................................................ MECHANICAL, LIGHTS, CEILING, SPRINKLERS................................ TOTAL = 7 6'-8" W12X14 ROOF LOADS - TYPICAL 3-S5.31 TYP. GIRDS 3-9 3-S5.32 10K1 W12X14 G 9 5 3-S3.00 2 1 3 12'-0" 4 14'-0" 5 20'-0" 6 20'-0" 7 20'-0" 20'-0" 8 18'-3" 9 4.6 18'-3" 10 TYP @ EACH COLUMN 3-S5.32 W16X36 W16X36 20 20 9 7 3-S5.31 3-S5.32 W16X36 W16X36 20 10'-0" C NOTE: ROOF DECK FOR HIGH ROOF AREA IS 3NA 20 GAUGE DECK. W16X36 20 W16X36 20 20 W24X76 26'-0" B 128'-2 1/2" B.O.D. D 8 35 W24X76 3-S5.32 1 29'-3" 3-S5.31 9 W24X76 3-S5.31 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 52DLH15 SP1 5'-3" (BENT) E 52DLH15 SP1 129'-5 1/8" B.O.D. W24X76 F 9 W24X76 34'-0" 3-S5.31 35 3-S5.31 1 8 3-S5.32 W16X36 20 W16X36 20 20 10'-0" 20 W16X36 H 4' - 10" W16X36 G W24X76 128'-2 1/2" B.O.D. W16X36 4' - 10" W16X36 20 20 10 9 7 3-S5.31 3-S5.32 3-S5.32 TYP @ EACH COLUMN COMMON - HIGH ROOF FRAMING PLAN MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED COMMON - HIGH ROOF FRAMING PLAN ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 12:25:31 PM AUTHORITY DWG. NO. 3-S2.03 SHEET: OF: 983_2478_985 _OR_ 3-S2.03 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION COMMONS C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt 1/8" = 1'-0" CL COL. ~RE: PLAN CL STEEL COLUMN ~ RE: PLAN SHEAR CONNECTION GRID CL STEEL BEAM 1/2" CAP PLATE CONCRETE SLAB ON METAL DECK OR METAL ROOF DECK NOT SHOWN FOR CLARITY 3/8" GUSSET PLATE 1/4 1/4 . 6 6 4 SIDES TOTAL TYP. BASE PL TO PL 5/16 2' - 2" CL. BEAM 3/8" FULL-DEPTH STIFFENER PLATES EACH SIDE PL 1 3/4" 7" 7" 6" 4" 1/4 1/4 TYP. STEEL BEAM ~ RE: PLAN W.P. 1" MIN. 1' - 0" . IN M 1" 5/16 5/16 B 1/4 1/4 B CLASS B LAP LENGTH 1/4 1/4 6 6 . 2" 3/8" GUSSET PLATE 3/4"ø A325N ERECTION BOLT WORK POINT 3/16 3/16 2" 3 - #4 U-BAR ~EXTEND CLASS B LAP PAST EMBED ~ RE: 8/3-S4.32 FOR ADDITIONAL REINFORCEMENT AROUND ANCHOR BOLTS GUSSET PL. 3/8" 2" 1 1/2" 2" 1 1/2" RE: PLAN GUSSET TO BEAM 3/16 3/16 . PL 1/2"X4"X4" B-B T.O.C. 4 SIDES TOTAL 2" PL 1/2x4x0'-6" 1" MIN. 2 1/2" . 3 1/2" 3 1/2" 3/4"ø A325N ERECTION BOLT (6) ASTM F1554 1"ø GRADE 55 THREADED RODS W/ 1'-0" EMBEDMENT 1" SHIM AND GROUT 2 1/2" CL SLOTTED STEEL BRACE 1" MIN. 2" GUSSET TO COL 3/16 3/16 . 1/4 1/4 TYP. 6 6 3/4"ø A325N ERECTION BOLT STEEL BRACE ~ RE: ELEVATION ~ TYP. 1 1/2" TYP. 5" WORK POINT CL EMBED PL3/4x8x0'-8" W/ 4 - 3/4"Ø x0'-6" H.A.S CL STEEL BRACE 1' - 7" 1 LOWER GUSSET PLATE DETAIL 3 1-S3.10 3-S3.00 1 1/2" = 1'-0" GUSSET PLATE DETAIL 4 2-S3.20 3-S3.00 1 1/2" = 1'-0" SECTION AT INVERTED-V BRACE 1-S3.10 3-S3.00 3/4" = 1'-0" CL COL. ~RE: PLAN PL 1/2"X4"X4" CL STEEL COLUMN ~ RE: PLAN 1/4 1/4 GRID BEAM TO COLUMN TYP. 1/4 1/4 BEAM TO COLUMN 1/4 1/4 CL STEEL BEAM CL STEEL BEAM BEAM TO COLUMN 3/8" GUSSET PLATE . IN M 1" PL 1 1/4" 4 SIDES TOTAL 1' - 9" 2" 5" 5" 5" 4" 1/4 1/4 2" RE: 1/3-S3.00 FOR ADDITIONAL INFORMATION TYP. 1" MIN. TYP. 2" T.O.C. GUSSET TO COL 3 1/2" 3 1/2" 3/16 3/16 6" 7" 7" 2" 2" . . 2 1/2" 4 SIDES TOTAL ~TYP. 1/4 1/4 6 6 GUSSET TO COL 3/16 3/16 . CL STEEL BRACE 2" 1' - 4" 7 1 1/2" = 1'-0" BASE PLATE DETAIL FOR COLUMN AT G/9 3-S2.01 3-S3.00 8 1 1/2" = 1'-0" GUSSET PLATE DETAIL AT HSS BEAM 3-S2.02 3-S3.00 1 1/2" = 1'-0" 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION AUTHORITY MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: DAM 05/29/15 BRACED FRAME DETAILS AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 12:25:32 PM GUSSET TO BEAM 3/16 3/16 DWG. NO. 3-S3.00 SHEET: OF: 983_2478_985 _OR_ 3-S3.00 C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt 2" 3/8" GUSSET PLATE CL STEEL BRACE LOWER GUSSET PLATE DETAIL 3-S3.30 3-S3.00 . 2" COMMONS 5 2' - 2" 7" 2 1/2" CL EMBED PL3/4x8x0'-8" W/ 4 - 3/4"Ø x0'-6" H.A.S 4" 10" . 3/4"ø A325N ERECTION BOLT 2" 2 1/2" 1 1/2" 1 1/2" 1 1/2" TYP. WORK POINT 3/16 3/16 3/8" GUSSET PLATE RE: PLAN 5" GUSSET TO BEAM 7" 5/16 W.P. 1/ 2" 6" 2 1/2" B-B CLASS B LAP LENGTH 3 1/2" 3 1/2" PL 1/2"X4"X4" 1/4 1/4 B 1' - 0" PL 1/2x4x0'-6" B 3 1/2" 3 1/2" 5/16 5/16 2" . 2" 1/ . IN M 1" 11" 3/4"ø A325N ERECTION BOLT 1" MIN. 4" (6) ASTM F1554 1"ø GRADE 55 THREADED RODS W/ 1'-0" EMBEDMENT 1" SHIM AND GROUT 6 6 TYP. BASE PL TO PL 5/16 CL SLOTTED STEEL BRACE 1" MIN. 3 - #4 U-BAR ~EXTEND CLASS B LAP PAST INSIDE EMBED ~ RE: 7/3S4.32 FOR ADDITIONAL REINFORCEMENT AROUND ANCHOR BOLTS 5/16 5/16 1/4 1/4 . BEAM TO COLUMN 9 8 7 7 11 F-9 8 9 F-9 11 HIGH ROOF 128' - 0" F-11 HIGH ROOF 128' - 0" F-10 F-10 F-11 SIM. 3 3-S3.00 8 3-S3.00 MID ROOF 121' - 4 21/32" MID ROOF 121' - 4 21/32" LOW ROOF LEVEL SECOND LOWFLOOR ROOF 114'114' - 1 1/2" - 0" LOW ROOF LEVEL SECOND LOWFLOOR ROOF 114'114' - 1 1/2" - 0" 1 3-S3.00 1 3-S3.00 1 3-S3.00 O.H. O.H. 1 3-S3.00 FIRST FLOOR Level 1 100' - 0" COMMON - BRACE FRAME AT LINE C 1 FIRST FLOOR Level 1 100' - 0" 2 3-S2.01 3-S3.30 1/4" = 1'-0" G 3-S2.01 3-S3.30 F F-L COMMON - BRACE FRAME AT LINE G F-J 1/4" = 1'-0" E F-G HIGH ROOF 128' - 0" C MID ROOF 121' - 4 21/32" 8 3-S3.00 B 4 3-S3.00 1 3-S3.00 LOW ROOF 114' - 0" O.H. 5 3-S3.00 5 3-S3.00 FIRST FLOOR Level 1 100' - 0" O.H. 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 7/14/2015 12:25:35 PM DEPARTMENT OF FACILITY MANAGEMENT 3-S2.01 3-S3.30 1/4" = 1'-0" COMMONS BRACED FRAME GRID 2 3-S2.01 3-S3.30 DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM DATE: DENVER, CO 05/29/15 AS NOTED COMMON - BRACE FRAME ELEVATIONS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56th AVE APPROVED CONTRACT DOCUMENT SCALE: 1/4" = 1'-0" SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS DENVER PUBLIC SCHOOLS 4 APPR'D DEPARTMENT OF FACILITY MANAGEMENT Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. COMMON - BRACE FRAME AT LINE 9 MADE DENVER PUBLIC SCHOOLS Level FIRST1 FLOOR 100' - 0"100' - 0" c 2013 LOA Architecture 3 AUTHORITY DWG. NO. 3-S3.30 SHEET: OF: 983_2478_985 _OR_ 3-S3.30 1 3-S3.00 COMMONS C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt LOW ROOF LEVEL SECOND LOWFLOOR ROOF 114'114' - 1 1/2" - 0" GRID GRID RE: PLAN RE: PLAN 600S162-54 @ 18" O.C. SLAB-ON-GRADE ~ RE: PAN 600S162-54 @ 18" O.C. 600S162-54 @ 18" O.C. SLAB-ON-GRADE STUD WALL BEYOND T.O. SLAB RE: PLAN SLAB-ON-GRADE RE: PLAN BRICK VENEER ~ RE: ARCH. BRICK VENEER ~ RE: ARCH. 2' - 6" 1" SLAB-ON-GRADE ~RE: PLAN #4xCONT. T.O. SLAB T.O. SLAB #5 @ 12" O.C. EACH WAY VARIES GROUT SOLID BELOW GRADE RE: PLAN #5 @ 12" O.C. EACH WAY, EACH FACE T.O. GRADE T.O. GRADE VARIES VARIES 2' - 0" 2' - 0" SLAB-ON-GRADE ~RE: PLAN #5 @ 12" O.C. 8" #5 @ 12" O.C. RE: PLAN RE: PLAN [100'-0"] 6" (4) #5 CONT. T.O. FOOTING (6) #5 CONT. 7" T.O. SLAB T.O. FOOTING RE: PLAN RE: PLAN [99'-0"] 1' - 0" RE: PLAN T.O. FOOTING 1' - 0" RE: PLAN RE: PLAN RE: PLAN [103'-0"] GROUT SOLID BELOW GRADE #5 @ 12" O.C. EACH WAY, EACH FACE T.O. SLAB @ 12" O.C. VARIES #5 @ 12" O.C. EACH WAY 2'-0 #4x2'-0 2'-0 T.O. SLAB RE: PLAN RE: PLAN EQ. 1 FOUNDATION SECTION 3-S2.01 3-S4.32 2 3/4" = 1'-0" 8" 1' - 1" 11" RE: PLAN EQ. FOUNDATION SECTION FOUNDATION SECTION 3 3-S2.01 3-S4.32 3/4" = 1'-0" FOUNDATION SECTION 4 3-S2.01 3-S4.32 3/4" = 1'-0" 3-S2.01 3-S4.32 3/4" = 1'-0" GRID GRID COLUMN ~RE: PLAN (3) #5 HORIZONTAL BOTTOM BARS AT BOTTOM OF STEM WALL T.O. SLAB VARIES GUSSET ~RE: BRACED FRAME ELEVATIONS RE: PLAN FOR BASEPLATE 1" SHIM AND GROUT 2" 2" 2" #5 HORIZ. @ 12" O.C. VARIES RE: PLAN COLUMN ~RE: PLAN (4) 1" DIA. F1554 - 55 KSI ANCHOR BOLTS (4) #5 VERTICAL BARS @ EACH CORNER OF TIE. PROVIDE STANDARD HOOK ON TOP AND BOTTOM AS SHOWN IN DETAIL 8/3-S4.32. T.O. SLAB RE: PLAN GUSSET ~RE: BRACED FRAME ELEVATIONS RE: PLAN FOR BASEPLATE #5 @ 12" O.C. EACH WAY, EACH FACE RE: PLAN (4) 1" DIA. F1554 - 55 KSI ANCHOR BOLTS 1" SHIM AND GROUT (4) #5 VERTICAL BARS @ EACH CORNER OF TIE. PROVIDE STANDARD HOOK ON TOP AND BOTTOM AS SHOWN. ~MAINTAIN TOP COVER TO REBAR (4) #5 HORIZONTAL TOP BARS WITH STANDARD HOOKS ON EACH END. ENSURE (2) BARS ARE POSITIONED BETWEEN ANCHOR BOLTS. #5 HORIZ. @ 12" O.C. #4 ENCLOSED TIES WITH 135DEGREE HOOKS AT 8" O.C. PROVIDE (3) TIES AT 2" O.C. AT TOP. (4) #5 HORIZONTAL TOP BARS WITH STANDARD HOOKS ON EACH END. ENSURE (2) BARS ARE POSITIONED BETWEEN ANCHOR BOLTS. 2" 2" 2" RE: PLAN GRID #4 ENCLOSED TIES WITH 135DEGREE HOOKS AT 8" O.C. PROVIDE (3) TIES AT 2" O.C. AT TOP. (3) #5 HORIZONTAL BOTTOM BARS #5 DOWELS @ 12" O.C. FOOTER ~RE: PLAN #6 HORIZ. @ 12" O.C. T&B #5 DOWELS @ 12" O.C. T.O. FOOTING RE: PLAN #5 @ 9" O.C. T&B 2' - 0" T.O. FOOTING #6 @ 12" O.C. X CONT. T&B 2' - 0" RE: PLAN #5 @ 9" O.C. T&B RE: PLAN RE: PLAN RE: PLAN RE: PLAN RE: PLAN C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt 3-S2.01 3-S4.32 7 3/4" = 1'-0" BRACED FRAME ON CONCRETE STEM WALL DETAIL 3-S2.01 3-S4.32 BRACED FRAME STEM WALL DETAIL 8 3/4" = 1'-0" 3-S2.01 3-S4.32 3/4" = 1'-0" 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED FOUNDATION DETAILS COMMONS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 12:25:36 PM AUTHORITY DWG. NO. 3-S4.32 SHEET: OF: 983_2478_985 _OR_ 3-S4.32 FOUNDATION SECTION COMMONS 6 11 88 77 F-9 66 F-8 55 F-7 4.5 44 F-6 33 F-5 F-4 22 F-10 2 2 2 2 2 2 3-S5.33 3-S5.33 3-S5.33 3-S5.33 3-S5.33 3-S5.33 114' - 2" T.O.S. 114' - 2" T.O.S. HSS9X5X3/8 114' - 2" T.O.S. HSS9X5X3/8 HSS9X5X3/8 3/16 3/16 TYP TYP HSS5X5X3/8 TYP HSS5X5X3/8 3/16 3/16 TYP HSS5X5X3/8 TYP HSS9X5X3/8 3/16 3/16 TYP HSS5X5X3/8 HSS9X5X3/8 HSS5X5X3/8 HSS9X5X3/8 HSS5X5X3/8 111' - 4" T.O.S. 111' - 4" T.O.S. 111' - 4" T.O.S. 3 3 3 3 3 3 3-S4.33 3-S4.33 3-S4.33 3-S4.33 3-S4.33 3-S4.33 HSS FRAME ELEVATIONS GRID A 1 3-S2.01 3-S4.35 1/4" = 1'-0" G G F F F-L F-J E E D D C C F-G B B F-E A A F-D F-B 2 6 6 6 3-S5.33 3-S5.33 3-S5.33 6 114' - 2" T.O.S. F-A 2 3-S5.33 3-S5.33 114' - 2" T.O.S. 3-S5.33 114' - 2" T.O.S. HSS9X5X3/8 HSS9X5X3/8 HSS9X5X3/8 111' - 4" T.O.S. 3 3 3-S4.33 3-S4.33 3-S4.33 3-S4.33 SIM HSS5X5X3/8 HSS5X5X3/8 HSS5X5X3/8 HSS9X5X3/8 3 SIM 111' - 4" T.O.S. SIM 2 2 3-S4.33 3-S4.33 HSS FRAME ELEVATIONS GRID 9 1/4" = 1'-0" 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56th AVE DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: DAM 05/29/15 HSS FRAME ELEVATIONS AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 12:25:39 PM AUTHORITY DWG. NO. 3-S4.35 SHEET: OF: 983_2478_985 _OR_ 3-S4.35 3-S2.01 3-S4.35 COMMONS C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt HSS9X5X3/8 3 SIM 2 HSS5X5X3/8 HSS9X5X3/8 HSS5X5X3/8 HSS5X5X3/8 111' - 4" T.O.S. SPECIAL JOIST LOADING SCHEDULE L1 L2 PD3 PD4 PD2 PD1 GRID PM GRID SL DL NOTE: DECK MAY BE PERPENDICULAR TO WHAT IS SHOWN 3/16 3/16 TAB TO STRUCTURE L3"x3"x1/4" BRACE AT BEAM MIDSPAN OR THIRD POINTS AS SHOWN ON PLAN. IF LENGTH OF BRACE IS GREATER THAN 8'-0", USE L4x4x5/16. WT6x17.5 x CONT. 600S162-54 @ 16" O.C. 600S162-54 @ 16" O.C. 3/16 3/16 L3"x3"x1/4" L3"x3"x1/4" EA. STUD TYP. DL = UNIFORM DEAD LOAD (LBS/SF) SL = UNIFORM SNOW LOAD (LBS/SF) PD = SNOW DRIFT LOAD (LBS/SF) PM = CONCENTRATED MECHANICAL UNIT LOAD - SEE PLANS L = WIDTH OF SNOW DRIFT (FT) WT6x17.5 x CONT. 1/8 1/8 1/8 1/8 EA. STUD PL. 1/4"x4"x0'-4" TYP. 1 BRACE DETAIL 2 3-S2.02 3-S5.31 1" = 1'-0" 600S162-54 @ 16" O.C. GRID WT6x17.5 x CONT. PD2 (PSF) PD3 (PSF) PD4 (PSF) L1 (FT) L2 (FT) MIN I (IN4) REMARKS 52DLH15SP1 21.0 30.0 -- -- -- -- -- -- -- 1, 3, 9 SPECIAL JOIST LOADING SCHEDULE 4 3/4" = 1'-0" . 3-S5.32 3/4"=1'-0 GRID WP OF KICKER TYP @ COL L4x4x1/4 BETWEEN JOISTS, NOTCH VERTICAL LEG AT JOIST AND EXTEND HORIZONTAL LEG AS REQ'D (2" MIN.) ANGLE HORIZ. LEG TO JOIST 3/16 3/16 PD1 (PSF) NOTE: DECK NOT SHOWN FOR CLARITY HSS 2 1/2x2 1/2x3/16xCONT. BETWEEN JOISTS IF 2 1/2" JOIST SEAT DEPTH HSS 3 1/2x3 1/2x3/16xCONT. BETWEEN JOISTS IF 3 1/2" JOIST SEAT DEPTH 3-12 3-12 ENTRY VESTIBULE PARAPET FRAMING 3-S2.02 3-S5.31 WELD DECK TO HSS PER PLAN NOTES 1/8 1/8 EA. STUD 3 3/4" = 1'-0" TAB TO STRUCTURE 3/16 3/16 ENTRY VESTIBULE PARAPET FRAMING 3-S2.02 3-S5.31 3/16 TAB TO STRUCTURE 3/16 3/16 SL (PSF) NOTES: 1. DESIGN JOISTS FOR CURTAINS, LIGHTING AND SOUND RIGGING AND OTHER EQUUIPMENT WHERE APPLICABLE. GC TO COORDINATEWEIGHTS, LOCATIONS AND CONNECTION BETWEEN EQUIPMENT SUPPLIERS AND JOIST FABRICATOR. 2. PROVIDE 1/2 OF STANDARD CAMBER AND DESIGN JOISTS FOR L/480 LIVE LOAD DEFLECTIONS. 3. DEAD LOADS DO NOT INCLUDE THE WEIGHT OF THE JOISTS. SUPPLIER SHALL INCLUDE THE JOIST WEIGHT IN THE JOIST DESIGN. 4. DIMENSIONS SHOWN ARE FROM CENTERLINE OF SUPPORT. 5. LOADS SHOWN ARE UNFACTORED SERVICE LOADS. 6. DRIFT OVER ENTIRE LENGTH OF JOIST. 7. LIMIT SNOW LOAD DEFLECTION TO 1 1/2" MAX. 8. ALIGN JOIST PANEL POINTS TO ACCOMMODATE DUCT WORK. RE: MECH. DWG'S. FOR DUCT SIZES AND LOCATION. 9. REFER TO DETAILS FOR TOP CHORD EXTENSION LOADS PL. 1/4"x4"x0'-4" AT EACH END OF BRACE 3/16 DL (PSF) PL. 1/4"x4"x0'-4" 3/16 TYP. JOIST HSS3 1/2"x3 1/2"x3/16xCONT. BETWEEN JOIST IF 3 1/2" JOIST SEAT. HSS2 1/2"x2 1/2"x3/16xCONT. BETWEEN JOIST IF 2 1/2" JOIST SEAT. TYP. 3" MAX 3/16 3/16 RE: ARCH FOR SCREEN WALL SIDING L4x4x3/8 x 0'-10", TYP. NOTE: DECK MAY BE PERPINDUCLAR TO WHAT IS SHOWN 9" U.N.O T.O. WALL 1/4 1/4 RE: ARCH TYP @ beam HSS8x8x1/4 POST, TYP. TYP. 3/16 3/16 3/16 STEEL BEAM ~ RE: PLAN 3/8" STIFFENER PLATE E.S. 3/4" CAP PLATE WITH (4) A325 BOLTS 3-12 3-12 TYP. TYP. 2" RETURNS TYP. 1/4 B.O. DECK 1/4 RE: PLANS HSS COL RE: PLAN L6x4x5/16x0'-6" (LLH) TYP. 1" BASE PL W/ (4) 3/4"Ø F1554 BOLT W/ 1'-0" MIN. EMBEDMENT PL 1/4x5"x0'-5" W BEAM ~RE: PLAN (HSS @ SIM.) 1/4 1/2" SHIM AND GROUT STANDARD SHEAR CONN., TYP. RE: 3-S5.00 MAY BE A KCS JOIST OR STEEL BEAM L3x3x1/4 BRACE AT BEAM THIRD-POINTS 3/16 3/16 2 2 HSS COLUMN TO HIGH ROOF ~RE: PLAN TYP. PLATE 1/4"x4"x0'-4" AT EACH END OF BRACE 5 ENTRY VESTIBULE COLUMN DETAIL 6 3-S2.02 3-S5.31 3/4" = 1'-0" 3/16 BEAM BOTTOM FLANGE BRACE 7 3-S2.02A 3-S5.31 1 1/2" = 1'-0" HIGHROOF TO LOW ROOF DRAG CONNECTION 3-S2.02 3-S5.31 TYP. EACH END SCREEN WALL DETAIL 8 1 1/2" = 1'-0" 4" MIN. 3-S5.31 3/4" = 1'-0" NOTE: DECK NOT SHOWN FOR CLARITY NOTE: THIS BLOCKING REQUIRED WHERE CUT ON PLAN FROM BEAM SUPPORT TO BEAM SUPPORT GRID L4x4x3/8 x 0'-8", TYP. WELD DECK TO HSS PER PLAN NOTES TYP @ beam HSS 3 1/2x3 1/2x3/16xCONT. BETWEEN JOISTS IF JOIST SEAT DEPTH IS 3 1/2" HSS 2 1/2x2 1/2x3/16xCONT. BETWEEN JOISTS IF JOIST SEAT DEPTH IS 2 1/2 1/4 1/4 C:\Users\dam2\Documents\S_DPS SNC - STRUCTRAL MASTER_dam2.rvt 3-12 3-12 2 07/15/15 Addendum 3 1 05/29/15 FOR CONSTRUCTION NO. DATE DESCRIPTION OF REVISION HSS COLUMN TO HIGH ROOF ~RE: PLAN This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DESIGNED BY: DHK DRAWN BY: DHK CHECKED BY: DAM 7/14/2015 12:25:40 PM 3-S2.02 3-S5.31 3" = 1'-0" APPROVED CONTRACT DOCUMENT SCALE: LOW ROOF DRAG CONNECTION 3-S2.02 3-S5.31 DATE: DENVER, CO 05/29/15 AS NOTED ROOF FRAMING DETAILS COMMONS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 1 1/2" = 1'-0" SITE NO. 983 9100 E. 56th AVE DATE: 10 SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT DRAG BEAM BLOCKING APPR'D DEPARTMENT OF FACILITY MANAGEMENT DENVER PUBLIC SCHOOLS 9 MADE DENVER PUBLIC SCHOOLS c 2013 LOA Architecture W BEAM ~RE: PLAN (HSS @ SIM.) AUTHORITY DWG. NO. 3-S5.31 SHEET: COMMONS STANDARD SHEAR CONN., TYP. RE: 3-S5.00 OF: 983_2478_985 _OR_ 3-S5.31 STEEL BEAM ~RE: PLAN GENERAL NOTES: 1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE. THE CONTRACTOR IS RESPONSIBLE FOR ALL OFFSETS, TRANSITIONS, ELBOWS, ETC. AS REQUIRED IN DUCTWORK, PIPING, SUPPORTS, ETC. TO COMPLETE THE WORK IN A CLEAN FUNCTIONAL INSTALLATION THAT IS FULLY COORDINATED WITH ALL OTHER TRADES. ANY PRICING EFFORT SHALL TAKE THESE FACTORS INTO ACCOUNT. 2. MAINTAIN A MINIMUM OF 25'-0" SEPARATION FROM OUTSIDE AIR INTAKES TO TERMINATIONS OF EXHAUST, COMBUSTION AIR, PLUMBING VENTS, ETC. AS REQUIRED BY CODE. 1 2 3 4 5 6 7 8 9 3. PROVIDE MANUAL BALANCE DAMPERS IN ALL EXHAUST DUCT BRANCH TAPS. 4. COORDINATE SPACE TEMPERATURE SENSORS AND THERMOSTAT LOCATIONS TO ALIGN VERTICALLY WITH LIGHT SWITCHES. MOUNT AT HEIGHT IN ACCORDANCE WITH ADA REQUIREMENTS. 8. TEMPERATURE CONTROLS CONTRACTOR SHALL SUBMIT PLANS INDICATING ALL SPACE TEMPERATURE SENSORS, T-STATS, HUMIDITY SENSORS, ETC. AS PART OF SUBMITTAL PROCESS FOR A/E REVIEW. A 8" DRYER VENT UP TO ROOF A 8"ø 150 10" DIA OA UP THRU ROOF TO GOOSENECK 6" EA DUCT UP TO ROOF (TYP 2) 6" EA DUCT UP TO ROOF (TYP 2) T D UH 12"X6" (2) 375 8"ø A 210 2 10. NO SERVICEABLE EQUIPMENT SHALL BE LOCATED WITHIN 10' OF THE EDGE OF ROOF. T FCU (6) A UH TF UH C1.02 C1.02 C1.01 T C1.01 B 24"X24" 150 14"øSA B TOILET 3-105A B 8"ø 220 (2) 10"øSA C1.01 12"ø B --- B 2 C EF CUST. 3-104A C1.01 EF C1.03 18"X12" (2) 590 B C1.04 12"ø 400 C 1 SA SERVING PROVIDE 5' SOUND 3-104 ATTENUATOR 10"ø (7) 275 B C1.02 FAMILY ASSIST TOILET 3-106A 1 (TYP 2) 1 8"ø 150 36"x30"RA 4 10"x10"EA CUH C C C1.03 C1.02 D T B 4 16"ø --- (4) 6'-0"x1'-0"x3'-0"DEEP ACOUSTICALLY LINED PLENUM BOX (TYP 4) 12"x12"SA B 16" DIA (TYP 8) 72"X12" E 1875 C1.01 3-M6.02 24"X24" --- 32"X16" SA THRU EXTERIOR WALL ABOVE LOWER ROOF 42"X24" C 4400 PROVIDE 10' SOUND ATTENUATOR SEE SHEET 3-M2.02 FOR CONTINUATION 42"X36" DIA SA THRU EXTERIOR WALL ABOVE LOWER ROOF (2) C 1 CD SEE SHEET 3-M2.02 FOR SA DUCTWORK CONTINUATION 22"X6" 600 CUH 1 C1.01 T SEE SHEET 3-M2.02 FOR RA DUCTWORK CONTINUATION (2) ERV-C2.01 28"øSA 2 D MECHANICAL KEYED NOTES: D CD PROVIDE WALL MOUNTED VFD CONTROLLER FOR STAGE-HAND CONTROL OF AHU-C2.01 DURING EVENTS 1'-4"x20'-0" STAGE CUSTOM SUPPLY. RE: DETAIL B/M6.01. T 14"X14" EA UP TO EF-C2.01 C 24"X24" RA THRU EXTERIOR WALL ABOVE LOWER ROOF T 20"øSA 30"X8" (8) 690 AHU-C2.01 10"x14"EA 12"øSA SA SEE SHEET 3-M2.02 FOR SA DUCTWORK CONTINUATION G 46"x20"RA CORRIDOR 3-106 1 18"X10" (2) C 750 CUH T 18"X10" 750 18"X6" 400 CUST 3-106B B 14"ø 600 IDF 3-106C B EF 46"x30"RA 12"X8" C 150 F/S 10"ø (5) 275 24"øRA T 8"øSA (2) TF (4) 20"øRA 12"X8" C 250 LAUNDRY 3-104B 12"X8" D 50 ELECTRICAL 3-109 18"øRA 8" DRYER VENT DN TO DRYER 8"ø A 300 8"ø 175 16"ø (4) 875 F/S C1.02 4 (TYP 2) B (TYP 3) EF 12"ø B 32"x16"SA MEN TOILET 3-102 10"X10" (2) 150 28"øRA C B 24"X24" (3) 330 12"X12" C 400 MIXING BOX 14"ø B 12"ø A 400 18"øSA 18"øRA C1.03 1 PROVIDE OPEN ENDED DUCT ABOVE CEILING. STUB DUCT THROUGH WALL / PARTITION FOR RETURN / TRANSFER AIR PATH. 2 ROUTE DUCT THROUGH JOIST WEBBINGS. COORDINATE FINAL LOCATIONS WITH STRUCTURE. 3 PROVIDE MANUFACTURER REQUIRED CLEARANCE ENVELOPE AROUND ENTIRE MECHANICAL UNIT. ENSURE ALL ACCESS PANELS & DOORS CAN BE COMPLETELY OPENED FOR MAINTENANCE. 4 PROVIDE REMOTE REGULATORS FOR MANUAL BALANCE DAMPERS ABOVE ACCESSIBLE CEILINGS. STF C1.01 42"øSA 4 (TYP 3) (3) 12"ø A 400 PERFORMANCE PLATFORM 3-110 22"øSA WOMENS TOILET 3-101 28"øSA 2 D F E 30"X8" (8) 690 F SEATING 3-100 STAGE ROOF VENT ABOVE. TYPICAL 4. PROVIDE APPROVED HEAT-ACTIVATED CONTROL DEVICES AND MANUAL OPERATION PER IBC 410.3.7 42"øSA E 8"ø 220 26"øRA B STF C1.02 40" RETURN AIR INTAKE AT 1'0" AFF. PROVIDE DUCT SUPPORT FROM FLOOR. 22"øSA 28"øSA 2 D ERV-C2.01 30"X8" (8) 690 CD G G 4.5 C 12"X12" (2) 20 H H T SECURITY 3-100B SSAC 2 4" DIA. OA UP THRU ROOF TO GOOSENECK CUH C1.04 T J J 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS 1 2 3 4 4.5 5 6 7 8 9 N 1 LEVEL 1 MECHANICAL PLAN 1/8" = 1'-0" DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: DENVER, CO JS GP JJS 05/29/15 LEVEL 1 MECHANICAL PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:00:30 PM AUTHORITY DWG. NO. 3-M2.01 SHEET: OF: 983_2478_985 _OR_ 3-M2.01 2 COMMONS C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt C1.01 AO CD DI TWO-POSITION, LOW-LEAK, MOTORIZED DAMPER WITH END SWITCH AT TOP OF EACH SHAFT. ES N.O. DI SD WHERE SCHEDULED AND/OR LOCATED ON PLANS TA/OA NC CONTACT IN SD TO SF STARTER CIRCUIT WIRED BY DIV. 23. WIRING TO FIRE COMMAND TO BE BY LIFE SAFETY. HARDWIRED TO FAN 2ND SET OF CONTACTS FOR BMS OUTPUT AO CD DI AI AI AI ES A. PROVIDE DIFFERENTIAL PRESSURE SENSOR OR CURRENT TRANSDUCER FOR ALARM IF FAN FAILURE IS DETECTED. N.C. EXHAUST FAN ES AI ES DX PDI PDT PDT AI TT PT SA FE M AO FT INTERLOCK ANY REQUIRED MAKE UP AIR CONTROL DAMPERS FOR PROPER VENTILATION OF SPACE (AS SCHEDULED). SC C. FAN SHALL ENGAGE BASED ON CALL FOR COOLING VIA SENSOR THERMOSTAT LOCATED WITH THE ASSOCIATED SPACE. FAN SHALL REMAIN OPERATIONAL UNTIL SPACE TEMPERATURE IS SATISFIED. SPACE SETPOINT TO SET AT 78F (ADJ.). DI DO FI AI MISCELLANEOUS DO START/STOP THE DX COOLING CONTROL, GAS HEATING, AND ECONOMIZER DAMPERS SHALL MODULATE IN SEQUENCE TO MAINTAIN DISCHARGE AIR TEMPERATURE (DAT). 2. 3. 4. THE RELIEF FAN VFD SHALL BE CONTROLLED FROM SPACE STATIC PRESSURE (0.05" W.C.). IF SPACE STATIC PRESSURE EXCEEDS SETPOINT FOR 5 MINUTES (ADJ.), ASSOCIATED EXHAUST DAMPER SHALL STROKE OPEN. ONCE END SWITCH IS MADE, RELIEF FAN VFD SHALL SLOWLY RAMP FAN SPEED UP. IF SPACE PRESSURE DROPS BELOW (0.02" WC) DIFFERENTIAL FROM OUTDOORS FOR 10 MINUTES (ADJ.), RELIEF FAN VFD SHALL START TO RAMP DOWN RELIEF FAN AND SHUT DOWN ACCORDINGLY. WITH A TIME DELAY (10 MINS) AFTER THE FAN HAS BEEN DEACTIVATED. RELIEF/EXHAUST DAMPERS SHALL SLOWLY CLOSE. G. DUCT STATIC PRESSURE SETPOINT SHALL BE RESET USING TRIM & RESPOND LOGIC WITHIN THE RANGE OF MIN. 0.5" WC (ADJ.) UP TO SCHEDULED ESP (ADJ.). THE UNIT SHALL STOP IF THE STATIC PRESSURE SENSOR FAILS AND ALARMS BMS. MANUAL RESET OF UNIT SHALL BE REQUIRED. D. 3. E. AI STATUS 2. 3. 4. 5. 6. 7. X X X INTERLOCKED DAMPERS (2-POSITION) NOTES CONTROL PER SCHEDULE AND SEQUENCE SEE PLANS X MISCELLANEOUS: a. THE SMOKE DETECTORS AND THE FAN FAILURES REQUIRE A MANUAL RESET. b. FIRST STAGE OF FREEZE PROTECTION SHALL BE AUTOMATICALLY RESET AFTER TEMPERATURE IS MET. SECOND STAGE OF FREEZE PROTECTION SHALL REQUIRE A MANUAL RESET. DOMESTIC WATER HEATERS X X DOMESTIC HOT WATER RECIRC PUMP X KW USAGE X DE-ENERGIZE THE SUPPLY FAN WHEN THE DISCHARGE STATIC PRESSURE HIGH-LIMIT REACHES 2.0" WC (ADJ). DE-ENERGIZE THE SUPPLY FAN UPON SIGNAL FROM FIRE COMMAND CENTER FOR SHUT DOWN. ALARM THE BMS WITH THE APPROPRIATE ALARM MESSAGE. DOMESTIC WATER USAGE - FROM METER X BUILDING WATER METER X X X X X X X X X EACH UNIT X ENTIRE BUILDING KW USAGE X PROVIDE TOTAL GALLONS USED X PULSE METER X OUTSIDE AIR DB X OUTSIDE AIR WB OUTSIDE CO2 REFERENCE X UNIT / CABINET HEATER X X TEMPERING VALVES X X ELECTRIC HEAT TRACE X X X X X X EACH UNIT X X EACH VALVE - HIGH TEMP ALARMS UPSTREAM AND DOWNSTREAM X EACH CONTROL PANEL ( REFER TO ELECTRICAL PLANS) DISCHARGE AIR TEMPERATURE: 1. MAINTAIN 55F (ADJ.) DAT WITH SETBACK CONTROL: 2. WHEN THE RTU IS IN THE UNOCCUPIED MODE. THE SUPPLY AND RELIEF FANS SHALL BE OFF. THE OUTSIDE AIR AND EXHAUST DAMPERS SHALL BE CLOSED. THE SUPPLY FAN, DX COOLING AND GAS HEATING SHALL REMAIN OFF UNLESS OVERRIDDEN BY NIGHT SETBACK CONTROL. I. IF D.A.T. DROPS BELOW 40°F (ADJ.), DE-ENERGIZE ALL FANS AND CLOSE THE OUTSIDE AIR AND EXHAUST AIR DAMPERS. GAS FIRED FURNACE CONTROL: 1. THE GAS FIRED FURNACE SHALL MODULATE TO MAINTAIN THE DAT (ADJ.). COOLING SHALL BE LOCKED OUT DURING HEATING MODE. J. WHEN THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY, AND COOLING IS REQUIRED, THE ECONOMIZER CONTROL SHALL BE ENABLED. THE OUTSIDE AIR DAMPERS SHALL MODULATE BETWEEN THE ADJUSTABLE MINIMUM POSITION AND FULL OPEN TO MAINTAIN THE DAT AT THE ECONOMIZER SETPOINT (2F BELOW DAT SETPOINT, BASED ON DAT RESET). MECHANICAL COOLING CONTROL SHALL BE ALLOWED WITH THE OUTSIDE AIR DAMPERS FULLY OPEN AS LONG AS OUTSIDE AIR ENTHALPY IS LESS THAN RETURN AIR ENTHALPY. HEATING SHALL BE LOCKED OUT UNTIL OUTSIDE AIR DAMPER HAS RETURNED TO THE MINIMUM VENTILATION POSITION. WHEN OUTSIDE AIR ENTHALPY EXCEEDS RETURN AIR ENTHALPY, ECONOMIZER CONTROL SHALL BE DISABLED. 2. NIGHT FREE COOLING: THE NIGHT FREE COOLING MODE SHALL TURN ON THE FAN AND ENABLE FREE COOLING DURING UNOCCUPIED HOURS TO COOL ZONES USING COOL NIGHT OUTDOOR AIR. THROUGH THE BMS TIME OF DAY SCHEDULING, THE OPERATOR SHALL SPECIFY THE NIGHT FREE COOLING MODE SCHEDULED HOURS. THE SUPPLY FAN TO BE ENERGIZED ONE HOUR (ADJ.) PRIOR TO SCHEDULED OCCUPIED MODE START TIME (OR PROVIDE OPTIMAL START (PREFERRED)) AND SHALL RUN CONTINUOUSLY. ENERGIZE HEAT FULLY UNTIL SETPOINT(S) ARE SATISFIED; MAINTAIN A 95°F (ADJ.) DAT. OA DAMPER SHALL BE CLOSED. EA DAMPER SHALL BE CLOSED. RA DAMPER SHALL BE OPEN. COOLING SHALL BE LOCKED OUT. REVERT TO OCCUPIED MODE WHEN EACH SPACE STAT HAS REACHED OCCUPIED HEATING SETPOINT. VAV TERMINAL BOXES SHALL FUNCTION AS DETAILED IN VAV BOX CONTROL SEQUENCE. RELIEF AIR FAN SHALL REMAIN OFF AND RELIEF AIR DAMPER SHALL BE CLOSED. MISCELLANEOUS DDC CONTROL: 1. COOLING VALVE CONTROL / ECONOMIZER: 1. THE COMPRESSORS SHALL BE STAGED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE AT THE DISCHARGE COOLING SETPOINT. THE COMPRESSORS SHALL BE OFF IF THE ROOFTOP UNIT IS IN THE HEATING MODE, THE FANS ARE OFF, OR THE DISCHARGE AIR SENSORS HAVE FAILED. NIGHT SETBACK TEMPERATURE CONTROL: DURING UNOCCUPIED HOURS, THE ROOFTOP UNIT SHALL BE CONTROLLED BY THE BMS TO MAINTAIN USER-DEFINED (ZONE AVERAGING) UNOCCUPIED HEATING (60F) AND COOLING SETPOINTS (80F). THE FAN SHALL OPERATE IN THE AUTOMATIC CONTROL MODE. THE RELIEF FAN SHALL REMAIN OFF, THE OUTDOOR AIR AND RELIEF AIR DAMPERS SHALL BE CLOSED, UNLESS IN FREE COOLING MODE. WARM-UP MODE: 1. ALARMS a. IF SPACE TEMPERATURE IS WITHIN 2 DEGREES (ADJ.) OF SETPOINT, THE HIGH SUPPLY AIR TEMPERATURE OF 60F (ADJ.) SHALL BE MAINTAINED. b. IF SPACE TEMPERATURE REACHES 3 DEGREES (ADJ.) OR HIGHER ABOVE SETPOINT, LOW SUPPLY AIR TEMPERATURE OF 55F (ADJ.) SHALL BE MAINTAINED. NIGHT SETBACK MODE: 1. GENERAL: WHEN THE BMS INITIATES THE UNOCCUPIED MODE, THE ROOFTOP UNIT SHALL ASSUME THE UNOCCUPIED HEATING AND COOLING SETPOINTS. IF THE UNOCCUPIED SETPOINTS ARE EXCEEDED, THE UNIT SHALL HEAT AND COOL UNTIL THE AVERAGE ZONE TEMPERATURES ARE WITHIN THE UNOCCUPIED SETPOINTS. 2. OUTPUT BINARY INPUT OUTPUT DI ALARM VFD CONTROL: 1. WHEN THE SUPPLY FAN IS ENABLED, THE VFD SHALL SLOWLY RAMP UP TO SETPOINT AND MODULATE TO MAINTAIN THE PROPER SETPOINTS. 2. SENSING DEVICE SHALL BE MULTIPLE POINT, NON-PULSATING STATIC SENSING SECTION WITH SELF AVERAGING MANIFOLD. H. ANALOG INPUT AO SPEED-SET FAN SAFETY CONTROLS: 1. DE-ENERGIZE THE SUPPLY AND RELIEF FANS WHENEVER THE FREEZE STAT IS TRIPPED, EITHER SMOKE DETECTOR HAS TRIPPED OR A FAN STATUS INDICATES A FAILURE (AFTER A TWO-MINUTE DELAY). UNOCCUPIED MODE: 1. EXHAUST FAN CONTROL DO START/STOP SYSTEM POINTS LIST GENERAL EXHAUST FANS F. a. THE DUCT STATIC PRESSURE SENSOR SHALL BE LOCATED BY THIS DIVISION. SUBMIT FINAL SENSOR LOCATION TO ENGINEER FOR REVIEW. REFER TO PLANS FOR PROPOSED LOCATIONS. b. TRIM AND RESPONSE LOOP TIMES AND ADJUSTMENT ITERATION VALUES SHALL BE SUBMITTED TO ENGINEER FOR REVIEW.. C. ALARM HOA SC SYSTEM POINT DESCRIPTION OCCUPIED MODE: 1. WHEN THE RTU IS IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY THE SUPPLY FAN VFD SHALL. MODULATE TO MAINTAIN THE DUCT STATIC PRESSURE. 4. DO START/STOP ALARM VFD INTERNAL CONTROLS AND SAFTY SWITCHES FURNISHED W/ UNIT. MODULATION OF BURNER BY DDC. MODE OF OCCUPANCY SHALL BE SCHEDULED THROUGH THE BMS CALENDAR AND TIME CLOCK. 3. D. FANS SHALL BE COORDINATED WITH AHU OPERATION. WHEN AHU IS OFF, FANS SHALL BE OFF. DI LOCATE 2/3 DOWN DUCTWORK. SUBMIT LOCATION FOR REVIEW. SEQUENCE OF OPERATION: 2. C. FANS SHALL NORMALLY OPERATE CONTINUOUSLY DURING BUILDING OCCUPIED HOURS AND BE OFF DURING BUILDING UNOCCUPIED HOURS, COORDINATE SCHEDULE OF EACH FAN. TEMPERATURE VENTILATION FAN CONTROLS A. IF COMMUNICATION WITH THE BMS IS LOST, THE AIR HANDLER CONTROLLERS SHALL USE THEIR DEFAULT SETPOINTS AND OPERATE IN THE OCCUPIED MODE. B. RTU CONFIGURATION, RE: SCHEDULE B. M B. GENERAL NOTES: A. EA PROVIDE CURRENT TRANSDUCER FOR ALARM IF FAN FAILURE IS DETECTED. M AI INDIRECT GAS-FIRED FURNACE AI PS EA SC STATUS ON/OFF ALARM STATUS STATUS OPEN/CLSD. STATUS RELAY TIMED OVERRIDE OFF/ON OPEN/CLOSED LOCK OUT ENABLE/DISABLE LIMIT WARNING HIGH ANALOG LOW ANALOG BINARY PROOF SENSOR FAIL FLOW FAIL COMM FAIL DIAGNOSTICS FLOW OVERRIDE FULL MODULATING, LOW-LEAK, MOTORIZED DAMPER WITH END SWITCH AT TOP OF EACH SHAFT. PDI DI A. EA SETPOINT ADJ. OUTDOOR HUMIDITY AI SF NG OUTSIDE AIR DI EA TE MERV 13 FILTER HT TSL FILTER MERV 7 OA T HARDWIRED TO FAN 2ND SET OF CONTACTS FOR BMS OUTPUT TE AI N.C. AI AI AI SEQUENCE OF OPERATIONS: SPACE HUMIDITY GRAPHIC TEMPERATURE PRESSURE RELATIVE HUMIDITY KW GPM/GALLONS CFM PPM PERCENT PERCENT RLA CUBIC FEET DDC (4-20 MA, 0-10 VDC) AO CD DI AI HT HARDWIRED TO FAN 2ND SET OF CONTACTS FOR BMS OUTPUT N.C. TE SP CARBON SPACE DIOXIDE STATIC P (MULTIPLE) SPACE TEMP. AO CD DI CD TS RA EXHAUST FAN B. PROVIDE ON-OFF-AUTO FUNCTION THROUGH DDC SYSTEM FOR ALL FANS. AI EA GLOBAL POINTS SEQUENCE OF OPERATIONS: K. TIMED OVERRIDE: 1. PROVIDE A TWO HOUR (ADJ.) TIMED OVERRIDE VIA SWITCH AT SPACE SENSORS TO RETURN RTU TO OCCUPIED MODE. L. FREEZE PROTECTION: 1. FREEZE STAT SHALL BE PROGRAMMED FOR TWO STAGES (42/37 F, ADJ.). a. FIRST STAGE (42F) OF FREEZE PROTECTION SHALL ALLOW FOR AUTOMATIC RESET AFTER TEMPERATURE IS MET. b. SECOND STAGE (37F) OF FREEZE PROTECTION SHALL REQUIRE A MANUAL RESET. 2. DURING RESET, THE OA AND EA DAMPERS ARE CLOSED. M. SHUTDOWN: 1. THE BMS PRIORITY CONTROL PROGRAM SHALL BE ABLE TO PUT THE ZONE IN EITHER THE SHUTDOWN, OCCUPIED MODE OR UNOCCUPIED. BOTH ROOFTOP UNITS WHICH ARE MEMBERS OF THE THAT ZONE SHALL BE IMMEDIATELY PUT IN THE SHUTDOWN OR OCCUPIED MODE. IN THE SHUTDOWN MODE, THE UNIT SHALL TURN OFF AS RAPIDLY AS POSSIBLE WITH ALL COOLING AND HEATING DISABLED, AND THE OUTDOOR AND EXHAUST AIR DAMPERS CLOSED. 2. EXHAUST FANS: 5. SEE THE POINTS LIST FOR ADDITIONAL REQUIRED ALARM AND STATUS POINTS WHICH SHALL BE MONITORED BY THE BMS. 1.1. TO BE CONTROLLED AS INDICATED ON FAN SCHEDULE (WHICH MAY REQUIRE ADDITIONAL POINTS). 2. 1.2. FANS INTERLOCKED TO OCCUPANCY OR TEMPERATURE SHALL BE CONTROLLED THROUGH THE BMS SYSTEM. 6. REFERENCE MECHANICAL EQUIPMENT SCHEDULES (ESPECIALLY "FANS") FOR ADDITIONAL CONTROL SEQUENCES. 1.3. PROVIDE A CURRENT SENSOR STATUS ON ALL EXHAUST FANS FOR DDC SYSTEM MONITORING. 7. DOMESTIC WATER SERVICE ANTI-FLOOD BASIN ALARM. DESTRATIFICATION FANS: 2.1 TO BE CONTROLLED THROUGH MANUFACTURER CONTROL PANEL. 2.2 FANS INTERLOCKED TO OCCUPANCY OR TEMPERATURE SHALL BE CONTROLLED THROUGH THE BMS SYSTEM. 2.3 PROVIDE A CURRENT SENSOR STATUS ON ALL EXHAUST FANS FOR DDC SYSTEM MONITORING. MISCELLANEOUS NON-DDC CONTROL: 1. DOMESTIC WATER HEATERS: SELF-CONTAINED CONTROLS FOR MAINTAINING SYSTEM TEMPERATURE. 3. DOMESTIC HOT WATER RECIRCULATION PUMPS ) SHALL BE MONITORED BY THE BMS SYSTEM FOR ON/OFF STATUS AND GENERAL ALARM AND STATUS. 4. DOMESTIC WATER HEATERS (DWH-X, DWH-X) SHALL BE MONITORED BY BMS FOR GENERAL ALARM AND STATUS. MISCELLANEOUS CONTROL SEQUENCES WHEN THE RETURN AIR SMOKE DETECTOR IS ACTIVATED. DETECTOR SHALL BE HARD WIRED TO FAN STARTERS. COURTESY SIGNAL SHALL BE SENT FROM FIRE COMMAND SYSTEM TO THE BMS. SYSTEM POINTS LIST X X X X PROGRAMS TIME SCHEDULING OPT. START STOP SETPOINT ADJUST ALARM EMERGENCY STOP NIGHT SETBACK MORNING WARM-UP OCCUPIED/UNOCCUPIED TIMED OVERRIDE OPEN/CLOSED LOCK OUT ENABLE/DISABLE LIMIT WARNING HIGH ANALOG LOW ANALOG HIGH BINARY LOW BINARY PROOF SENSOR FAIL FLOW FAIL COMM FAIL DIAGNOSTICS OFF/ON FILTER STATUS STATUS OPEN/CLSD. STATUS ALARM TIMED OVERRIDE REFRIGERANT SETPOINT ADJ. DDC (4-20 MA, 0-10 VDC) ALARMS X X X X X X X X X X X X X X X X X X X X X CALCULATED X X X X X X X X X X ECONOMIZIER ACUATOR OA (W/ END SWITCH) ECONOMIZIER ACUATOR RA (W/ END SWITCH) FILTERS SUPPLY AIR STATIC SUPPLY AIR HIGH STATIC SPACE PRESSURE RTU ALARM STATUS FREEZE STAT TIMED OVERRIDE OUTSIDE AIR TEMPERATURE OUTSIDE AIR HUMIDITY GENERAL NOTES: NOTES X X X COMMON SIGNAL W RA DAMPER COMMON SIGNAL W OA DAMPER X X X X X X X X X 2 X X X X X MANUAL RESET REQUIRED X X 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION X X X 1. SEE SCHEDULES FOR QUANTITIES 2. POINTS ABOVE ARE NOT NECESSARILY REFLECTED IN CONTROL DIAGRAMS. APPR'D X DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 AHU CONTROL SEQUENCE OF OPERATION DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: JS GP JJS DENVER, CO 05/29/15 AS NOTED MECHANICAL CONTROL DIAGRAMS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS DENVER PUBLIC SCHOOLS 7/14/2015 3:00:30 PM MADE DENVER PUBLIC SCHOOLS X Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. 2 AUTHORITY DWG. NO. 3-M5.01 SHEET: OF: 983_2478_985 _OR_ 3-M5.01 AHU GRAPHIC SUPPLY FAN SUPPLY FAN MODULATION SUPPLY AIR TEMPERATURE RETURN AIR TEMPERATURE RETURN AIR CFM RETURN AIR HUMIDITY MODULATING GAS HEAT DX COOLING CONTROL MIXED AIR TEMPERATURE BINARY INPUT OUTPUT COMMONS C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt GRAPHIC SYSTEM POINT DESCRIPTION TEMPERATURE PRESSURE HUMIDITY KW GPM CFM PPM PERCENT PERCENT RLA ANALOG INPUT OUTPUT STATUS ON/OFF ROOFTOP VAV ~ SPRING ISOLATORS PER 23 0548, TYPICAL. MAINTAIN CLEARANCE IN ACCORDANCE WITH MFR. INSTRUCTIONS. PACK WITH FIREPROOF MINERAL FIBER. 16 GAUGE STEEL SLEEVE BLADES OUT OF AIR STREAM HANGER RODS TO STRUCTURE ABOVE, TYPICAL ~ BACKDRAFT DAMPER FLEXIBLE CONNECTION. FLEXIBLE CONNECTION TRANSITION WHERE REQUIRED. BREAKAWAY JOINT BOTH SIDES OF DAMPER SLEEVE NOTE: VERTICAL TYPE FIRE DAMPER SHOWN. FOR HORIZONTAL TYPE, TURN ASSEMBLY 90 AND PROVIDE W/SPRING NEGATOR EXTENSION. FIRE DAMPER ACCESS DOOR 30 DEG. MAXIMUM. TRANSITION WHERE REQUIRED. FASTENERS 8" O. C. SECURE TO STEEL SLEEVE ONLY 1-1/2"X1-1/2"X1/8" RETAINING ANGLES ALL AROUND BOTH SIDES OF WALL INTAKE DUCT. 30 DEG MAXIMUM ACCESS DOOR. INSTALL FAN TO ALLOW DOOR TO BE COMPLETELY OPENED. DISCHARGE DUCT. NOTE: INSTALL FAN WITH PROPER SERVICE CLEARANCE TO MOTOR AND ALL PARTS FOR PROPER AIR MOVEMENT AS RECOMMENDED BY THE MANUFACTURER. M - I NO SCALE - E NO SCALE A FIRE DAMPER INSTALLATION DETAIL INLINE FAN DETAIL NO SCALE NO SCALE GENERAL NOTES: 1. COORDINATE FLASHING REQUIREMENTS AND CURB INSTALLATION WITH ROOFING CONTRACTOR AND ARCHITECTURAL ROOF REQUIREMENTS. 6" MAX (TYP ALL SIDES) 2. PROVIDE DRAIN PLUG IN ALL UPBLAST FANS ON GREASE FANS. PIPE DRAIN TO A RECEIVER TO CATCH GREASE. 10 GA SLEEVE (TYP) 1-1/2"x1-1/2" ANGLE SUPPORTS (TYP ALL SIDES) DO NOT ATTACH TO WALL DOME OR UPBLAST EXHAUST FAN INSULATION WHERE NOTED BIRDSCREEN ON DOME FANS OPERATOR/ACTUATOR 24V OR 120V AUXIARY OPERATING JACK SHAFT FUSIBLE LINK WITH LOCK FLASH AND COUNTERFLASH FUSABLE ROD NEGATOR SPRING ROOF MEMBRANE CANT STRIP ROOF CURB INSULATION ACCESS DOOR 1" MIN OVERLAP 1/4" MIN CLEARANCE 14" MIN. SUPPORT ANGLE FOR DAMPER ATTACHED TO CURB GRAVITY/MOTORIZED BACKDRAFT DAMPER DECK EXHAUST DUCT SEE PLANS FOR SIZE NOTES: 1. ALL WOOD CURBS AND CANT STRIPS TO BE FIRE RETARDANT TREATED WOOD. N - J NO SCALE - F NO SCALE COMBINATION FIRE/SMOKE DAMPER DETAIL B ROOF MOUNTED EXHAUST FAN DETAIL NO SCALE NO SCALE 2 PROVIDE MIN. AIR FLOW & MAINTENANCE ACCESS , PER MFR DIRECTIONS: TYPICAL ALL SIDES & TOP OF UNIT 12 1 CONDENSING UNIT 2 COMPRESSOR ACCESS 3 REFRIGERANT GAUGE CONNECTIONS 4 BACK-SEATED REFRIGERANT VALVE. 5 SIGHT GLASS WITH MOISTURE INDICATOR. SUCTION LINE WITH INSULATION. 1 6 2 9 4 10 36"x30"RA 11 EQUIPMENT RAIL W/ COUNTERFLASHING SHEETMETAL CAP.* CONDENSER COIL 12 FAN GUARD. 9 13 VIBRATION ISOLATORS* 6 14 FLASH PENETRATION WATER TIGHT SEE DETAIL* 14 NOTE: 1. REFRIGERANT LIQUID LINE & SUCTION LINE TO BE SIZED PER MANUFACTURER'S RECOMMENDATIONS. 2. PROVIDE OIL TRAPS AT RS LOW POINTS AND/OR PITCH HORIZONTAL PIPING FOR PROPER OIL RETURN. - K G NO SCALE CAFETERIA RETURN AIR SOFFIT SECTION NO SCALE C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt NO SCALE - C 7 8 10 * CONDENSING UNITS TO BE MOUNTED IN COMPLIANCE WITH DPS STANDARD 07533. RE: DPS STANDARDS FOR COMPLETE DETAILS. 8 AIR COOLED CONDENSING DETAIL NO SCALE 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION AUTHORITY MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: NO SCALE L NO SCALE H NO SCALE JS GP JJS 05/29/15 MECHANICAL DETAILS AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: P SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DWG. NO. 3-M6.02 SHEET: COMMONS This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. OF: 983_2478_985 _OR_ 3-M6.02 2 DENVER PUBLIC SCHOOLS 7/14/2015 3:00:31 PM CONDUIT - POWER AND CONTROL. REFRIGERANT LIQUID LINE 3 5 O 8 3 13 72"X12" E 1875 ROOF CAP AND CURB* 11 18'-0"x1'-0"x3'-0"DEEP PLENUM BOX (4) 7 COMMONS BUILDING - ENERGY RECOVERY VENTILATOR SCHEDULE SUPPLY FAN MIN. CODE AREA (ERV) SERVED LOCATION MODEL NO. C2.01 CAFETERIA ROOF ANNEXAIR ERP-E-16-SW-C-HG-AM46 MANUFACTURER/ OSA CFM TYPE (CFM) 16,560 6,550 DD EXHAUST FAN FAN TSP ESP DISCH. "W.C. "W.C. FAN ELECTRICAL FAN CONFIG. (ALT.) (ALT.) HP QTY. END 4.79 0.90 15 2 VOLT PH 460 3 CFM TYPE 15,600 HEAT RECOVERY TSP ESP "W.C. "W.C. FAN (ALT.) (ALT.) HP QTY. 2.44 0.75 7.5 2 DD ELECTRICAL COOLING VOLT PH 460 3 OA (F) HEAT RECOVERY COOLING CAPACITY (DX) EAT (F) RA (F) HX DB DB WB APD DB WB APD EFF. 89 60 0.49 76.0 62.0 0.44 71% 77.5 WB 60.1 LAT TOTAL SENS (F) MBH MBH 527.0 52.0 COMPRESSOR FLA 36.7 363.0 HEATING QTY OA (F) RA (F) LAT (F) HX DB/WB APD CFM DB/WB APD CFM DB EFF -3.0 0.40 6,550 68.0 0.33 5,580 48.0 72% 2.0 ELECTRICAL HEATING CAP (GAS FIRED) EAT LAT INPUT OUTPUT (F) (F) MBH MBH 59.9 90.0 800 512 COMB FAN HP 1/4 QTY 2.0 CONDENSER DISC. V PH FLA QTY. FLA MCA SWITCH FUSE FEEDER 460 3 27 2 134 203 400A,3P 250A LPS-RK RE:ONE-LINE AHU UNIT CONFIG APPROX. REMARKS WEIGHT I 17,000 A,B,C,D,E,F 2 2 2 GENERAL NOTES: 1. PROVIDE HIGH EFFICIENCY MOTORS (RELIANCE E+ OR EQUIVALENT) 2. COMPRESSORS AND CONDENSER FANS TO BE VARIABLE SPEED CONTROLLED. 3. PROVIDE FACTORY MOUNTED NON-FUSED DISCONNECT 4. INSTALL UNITS WITH ADEQUATE CLEARANCE FOR COIL PULL , FILTER REPLACEMENT AND TO FULLY OPEN ACCESS DOORS. PROVIDE A MINIMUM OF 3 FEET CLEARANCE IN FRONT OF DISCONNECT SWITCHES AND CONTROL PANELS. COMPLY FULLY WITH NEC. 5. UNIT STATIC PRESSURE CAPABILITY SHALL INCLUDE SCHEDULED EXTERNAL STATIC PRESSURE PLUS ALL SCHEDULED INTERNAL PRESSURE DROPS. INCLUDE VALVES FOR WETTED COILS AND DIRTY FILTERS. 6. 7-14" W.C. GAS FIRED BURNER 76. PROVIDE DUCT SMOKE DETECTOR IN THE RETURN AIR DUCT OF ALL UNITS. 8. PROVIDE INTERNAL SPRING ISOLATION. 9. PROVIDE 14" INSULATED ROOF CURB 10. PROVIDE SENSIBLE ENERGY RECOVERY WHEEL. 11. PROVIDE FACTORY MOUNTED DISCONNECT WIRED TO MOTORS 12. SCHEDULED FAN VALUES (CFM, SP AND HP) ARE ACTUAL AT ALTITUDE. MOTOR HP HAS BEEN ADJUSTED FROM SEA LEVEL CONDITIONS FOR OPERATION AT JOBSITE ELEVATION. 13. JOB SITE ELEVATION =5280 FT. 14. FACTORY MOUNTED CONTROLS BY OTHERS. RE: SPECIFICATION SECTION 23 75 13 2 REMARKS: A. SENSIBLE RECOVERY ENERGY RECOVERY WHEEL B. PROVIDE BYPASS FOR 100% RECIRCULATION DURING UNOCCUPIED MODE. C. SENSIBLE WHEEL SHALL BE SELECTED TO MAINTAIN SCHEDULED LAT FOR 8 HOURS OF CONTINOUS OPERATION. EA LAT = 17.4/17.4 D. DIRECT DRIVE PLENUM FANS E. PROVIDE MINIMUM 35K AIC RATED CONNECTION TO UNIT. F. PROVIDE SINGLE POINT ELECTRICAL CONNECTION TO UNIT. CONFIGURATION: I. CONSTANT VOLUME UNIT WITH BOTTOM RETURN, EXHAUST AIR FAN, OA PREFILTER, MERV 13 FILTER, RECIRCULATION DAMPER, SENSIBLE RECOVERY WHEEL, HEATING SECTION, ACCESS, DX COOLING , SUPPLY FAN AND FRONT SIDE DISCHARGE COMMONS BUILDING - PACKAGED DX W/ GAS FIRED HEATING ROOF TOP UNIT SCHEDULE SUPPLY FAN CODE MANUFACTURER / AREA (AHU) MODEL SERVED CFM ESP TSP (IN.) (IN.) MIN. OSA TYPE QUANTITY HP CFM COOLING CAP. EAT (F) DB WB HEATING (MBH) PRE FILTER TOTAL SENS MAT LAT INPUT OUTPUT MBH MBH (F) (F) MBH MBH COMB FAN HP FINAL FILTER APD (" WC) QTY MERV INITIAL FINAL ELECTRICAL APD (" WC) MERV INITIAL FINAL CONDENSER COMPRESSOR RLA V PH 1B 1A 2A 2B FLA QUANTITY DISC. MCA SWITCH WEIGHT FUSE FEEDER LBS. REMARKS 2 C2.01 2 AAON / RN-013 PERFORMANCE PLATFORM 4,500 0.93 2.85 VFD 1 5 2,500 86.7 62.3 134.0 134.0 28.1 90.0 390 260 0.3 1 7 0.10 0.25 13 0.2 0.4 460 3 GENERAL NOTES 1. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13. 2. PROVIDE 2" (30% EFF) PRE-FILTER AND 4" (85% EFF) FINAL FILTERS, RE: SPECS. 3. JOBSITE ELEVATION= 5280 FT. 4. UNIT TO HAVE SINGLE POINT ELECTRICAL CONNECTION WITH NON-FUSED DISCONNECT. 5. MCA LISTED IS TOTAL FOR UNIT. COORDINATE WITH ELECTRICAL. 6. PROVIDE MANUFACTURERS RECOMMENDED SERVICE CLEARANCE AROUND ENTIRE UNIT. 7. HEATING AND COOLING CAPACITIES AND FAN STATIC PRESSURES ARE AT JOBSITE ALTITUDE. 8. PROVIDE INTAKE RAIN HOOD AND 100% OSA MODULATING ECONOMIZER. 9. CAPACITY BASED ON 105F AMBIENT TEMPERATURE. 10. PROVIDE MODULATING GAS HEAT. 11. PROVIDE DIRECT DIRVE PLENUM SUPPLY FAN. 12. FACTORY MOUNTED CONTROLS BY OTHERS. RE: SPECIFICATION SECTION 23 74 00 2 2 -- 9.7 10.6 -- 1.8 2 34.0 60A,3P 40A LPS-RK RE: ONE-LINE DIAGRAM 2,050 A, B, C, D, E, F, G, H, I, J, K, L REMARK NOTES A. PROVIDE FAN WITH VFD. B. 7-14" WC GAS FIRED BURNER SECTION C. PROVIDE INSULATED PLENUM CURB WITH SIDE DUCT CONNECTIONS. D. PROVIDE INTERNAL VIBRATION ISOLATION. E. PROVIDE UNIT CONTROLLER WITH BACNET COMMUNICATION CAPABILITY. F. PROVIDE WITH DIGITAL COMPRESSOR FOR REFRIGERATION CONTROLS (HOT GAS BYPASS NOT ACCEPTED DUE TO ENERGY INEFFICIENCY) G. PROVIDE BAROMETRIC RELIEF DAMPER. H. PROVIDE CONTROLS WITH DEMAND CONTROL VENTILATION AND UNOCCUPIED MINIMUM OUTSIDE AIR SET POINT OF 1000CFM. I. PROVIDE SMOKE DETECTION IN RETURN AIR INTAKE TO UNIT. J. PROVIDE OA MEASURING STATION. K. PROVIDE WITH VARIABLE SPEED CONDENSER FANS FOR HEAD PRESSURE CONTORL AND REDUCED FAN NOISE AT PARTIAL LOAD L. PROVIDE MINIMUM 35K AIC RATED CONNECTION TO UNIT. COMMONS BUILDING - ENVIRONMENTAL FAN SCHEDULE ESP ELECTRICAL CODE MANUFACTURER / (EF) MODEL NO. SERVICE LOCATION TYPE CFM (ALT.) DRIVE HP/W VOLT PH FLA DISC. FUSE FEEDER MTG CTRL REMARKS C1.01 GREENHECK / SP-A200 CUSTODIAN CUSTODIAN CEILING CABINET 150 0.30 D 48 W 120V 1 0.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 3 II C C1.02 GREENHECK / SP-A200 TOILET ROOM TOILET ROOM CEILING CABINET 150 0.30 D 48 W 120V 1 0.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 3 I C C1.03 GREENHECK / SP-A200 TOILET ROOM TOILET ROOM CEILING CABINET 150 0.30 D 48 W 120V 1 0.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 3 I C C1.04 GREENHECK / SP-A200 CUSTODIAN CUSTODIAN CEILING CABINET 150 0.30 D 48 W 120V 1 0.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 3 II C C2.01 GREENHECK / G-123-VG MAIN MENS & WOMENS RESTROOMS ROOF CENTRIFUGAL DOWNBLAST 1100 0.55 D 1/2 HP 120V 1 9.8 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 2 I A, B C1.01 GREENHECK / SQ-95-VG STORAGE STORAGE INLINE CENTRIFUGAL 750 0.25 D 1/6 HP 120V 1 4.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 1 I A C1.02 GREENHECK / SQ-80-VG STORAGE STORAGE INLINE CENTRIFUGAL 400 0.25 D 1/6 HP 120V 1 4.4 THERMAL OVERLOAD (2#12,1#12G) 3/4"C 1 I A FAN "W.C. (TF) CONTROL (CTRL): I. RUN CONTINUOUSLY DURIED OCCUPIED SCHEDULES, CONTROL VIA DDC SYSTEM. II. INTERLOCK WITH LIGHT SWITCH BY DIVISION 26 GENERAL NOTES: 1. DRIVE TYPE: D=DIRECT-PROVIDE RHEOSTAT SPEED CONTROLLER IN FAN HOUSING UNLESS OTHERWISE NOTED. 2. ALL CURBS SHALL BE FACTORY MADE, 14 INCH HIGH INSULATED UNLESS OTHERWISE NOTED. 3. SCHEDULED FAN VALUES (CFM, SP AND HP) ARE ACTUAL AT ALTITUDE. MOTOR HP HAS BEEN ADJUSTED FROM SEA LEVEL CONDITIONS FOR OPERATION AT JOBSITE ELEVATION. JOBSITE ELEVATION = 5280 FT. 4. PROVIDE MAGNETIC STARTER WITH AUXILARY CONTACTS AND HOA SWITCH ON ALL THREE PHASE UNITS EXCEPT WHEN SERVED FROM MOTOR CONTROL CENTER. 5. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13. REMARK NOTES: A. PROVIDE ECM VARIGREEN MOTOR WITH POTENTIOMETER DIAL PRE-MOUNTED ON MOTOR B. PROVIDE GRAVITY BACKDRAFT DAMPER C. PROVIDE ROOF TERMINATION KIT MOUNTING (MTG): 1. INSTALL FAN WITH FLEXIBLE CONNECTIONS AT DUCT INLET AND OUTLET AND WITH HANGING VIBRATION ISOLATORS. 2.PROVIDE WITH FACTORY MANUFACTURED 14" HIGH ROOF CURB SUITABLE FOR ROOFING SYSTEM BEING USED. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ALSO PROVIDE FACTORY BACKDRAFT DAMPER. 3. CEILING MOUNTED CABINET FAN COMMONS BUILDING - GRILLE REGISTER DIFFUSER SCHEDULE CODE MODEL NO. SERVICE TYPE A TITUS / TDCA SUPPLY LOUVERED 24X24 B TITUS / PAR RETURN/EXHAUST PERFORATED 24X24 C TITUS / 350 RL EXHAUST / TRANSFER 35 DEG. DEFLECTION ACCESSORIES DUCT + 1-3/4" FACE SIZE REMARKS SEE PLANS D TITUS / 272 RS SUPPLY LOUVERED NECK + 1-3/4" E TITUS / CT-580 RETURN LINEAR BAR SEE PLANS 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: JS GP JJS DENVER, CO 05/29/15 AS NOTED MECHANICAL, ELECTRICAL & PLUMBING SCHEDULES ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:00:32 PM AUTHORITY DWG. NO. 3-MEP.01 SHEET: OF: 983_2478_985 _OR_ 3-MEP.01 GENERAL NOTES 1. SEE PLANS FOR CFM AND NECK SIZE. 2. MAXIMUM NOISE CRITERIA (NC) SHALL BE 30 UNLESS OTHERWISE NOTED. 3. COLOR TO BE COORDINATED WITH ARCHITECT. 4. MATERIAL IS STEEL UNLESS OTHERWISE NOTED. 5. PROVIDE BALANCING DEVICE FOR ALL GRD'S UNLESS OTHERWISE NOTED. COMMONS C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt MANUFACTURER/ COMMONS BUILDING - DESTRATIFICATION FAN SCHEDULE ELECTRICAL COMMONS BUILDING - AIR COOLED CONDENSING UNIT SCHEDULE 2 ELECTRICAL CODE MANUFACTURER/ MATCHING (ACCU) MODEL NO. INDOOR UNIT(S) COOLING HEATING W VOLT PH MCA DISC FUSE C2.01 CARRIER / 38MBQB48---3 FCU-C1.01 46.3 45.1 - 208/230 1 35 60A/3P CARRIER / 38MAQB09---3 SSAC-C1.01 6.7 6.2 - 208/230 1 15 30A/3P C2.02 CAPACITY (MBH) FEEDER REMARKS 55A LPN-RK (3#4,1#8G.)1-1/4"C. A, B, C, D 20A LPN-RK (3#12,1312G.)3/4"C. A, B, C D CODE MANUFACTURER & (STF) MODEL NO. SERVICE TYPE AIRFOILS DIAMETER RPM DRIVE HP VOLT PH FLA DISC. FUSE FEEDER MTG CTRL REMARKS C2.01 BIG ASS FANS 14 FT ESSENCE CAFETERIA PROPELLER 8 14'-0" 55 VSD 2 120 1 10.0 30A,2P 20A LPN-RK (2#12,1#12G) 3/4"C 1 I A, B C2.02 BIG ASS FANS 14 FT ESSENCE CAFETERIA PROPELLER 8 14'-0" 55 VSD 2 120 1 10.0 30A,2P 20A LPN-RK (2#12,1#12G) 3/4"C 1 I A, B FAN GENERAL NOTES 1. VSD=VARIABLE SPEED DRIVE. 3. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13. 4. REFER TO SPEC SECTION 230501 AND 260501 FOR EQUIPMENT DISCONNECTING RESPONSIBILITY. GENERAL NOTES 1. PROVIDE MANUFACTURER'S REQUIRED CLEARANCE AROUND UNIT FOR AIRFLOW AND MAINTENANCE. CONTROL (CTRL) I. MANUFACTURUER CONTROL PANEL W/ CONTROL AT BMS & LOCKABLE DISCONNECT. REMARK NOTES A. WALL MOUNTED SPEED CONTROLLER WITH CAT5 CABLE INTERNAL FUSING, LOAD REACTOR, AND POTENTIOMETER ON OUTSIDE OF CONTROLLER. B. PROVIDE ANODIZED AIRFLOILS AND (SILVER OR BLACK)WINGLETS. MOUNTING (MTG) 1. PROVIDE MANUFACTURER FAN MOUNT AND EXTENSION TUBE SUPPORTED FROM STRUCTURE ABOVE. SUGGESTED MOUNTING HEIGHT OF 32" BELOW CEILING 2. CAPACITY LISTED IS NOMINAL. DERATING FOR ALTITUDE HAS BEEN ACCOUNTED FOR IN DESIGN. 3. PROVIDE QUICK-SLING MOUNTING RAILS TO ELEVATE UNITS A MINIMUM OF 12" FROM ROOF TO AVOID SNOW COLLECTION. 4. CONDENSING UNITS TO BE MOUNTED ON A CURB (OR PAD) WITH AN ELASTOMERIC MOUNT. 5. PROVIDE VIBRATION ISOLATION PACKAGE. 6. PROVIDE ANTI-SHORT CYCLE TIMER ON COMPRESSORS. REMARK NOTES A. PROVIDE WIND BAFFLE B. PROVIDE MANUFACTURER SNOW HOOD C. PROVIDE MANUFACTURER HAIL GUARD D. PROVIDE LOW AMBIENT CONTROLS COMMONS BUILDING - SOUND ATTENUATOR SCHEDULE COMMONS BUILDING - DX SPLIT SYSTEM SCHEDULE FAN CODE 2 MANUFACTURER/ MIN. OA COOLING ESP MAT (F) HEATING (MBH) TOTAL ELECTRICAL AREA SERVED CFM CFM (IN.) DB WB MBH EAT LAT MBH W VOLT PH MCA DISCON. FUSE FEEDER REMARKS FCU-C1.01 CARRIER / 40MBQB48D--3 KITCHEN 1460 310 0.3 78.9 61.5 35 50.9 76.5 34 - 208/230 1 35 60A/3P 55A LPN-RK (3#4,1#8G.)1-1/4"C. A, C, D SSAC-C1.01 CARRIER / 40MBQB09C--3 SECURITY 260 20 0.1 76.4 61.6 6.5 59.9 75.9 6.0 - 208/230 1 15 30A/3P 20A LPN-RK (3#12,1312G.)3/4"C. B, C, E CODE (SA) MANUFACTURER SYSTEM CFM 63 C1.01 C1.02 C2.01 C2.02 POTTORFF RFN-12F VIBRO-ACOUSTICS RD-HV-F1 POTTORFF RXFN-12G POTTORFF RXFN-12E SEATING AREA SUPPLY SEATING AREA RETURN PERFORMANCE PLATFORM SUPPLY PERFORMANCE PLATFORM RETURN 16,500 -16,500 4,500 -4,500 6 14 31 50 52 51 39 24 5 11 17 19 19 16 14 11 10 18 37 51 53 51 38 24 7 15 26 41 54 45 29 20 8K W (IN) SIZE H LENGTH (IN) (IN) 42 46 32 24 36 30 16 24 120 60 120 84 VELOCITY (FPM) PRESS. DROP (IN WC) REMARKS 1575 -1720 1270 -1125 0.26 0.17 0.26 0.17 A, B A, B A, B A, B REMARK NOTES A. SILENCERS ARE SCHEDULED BASED ON SCHEDULED EQUIPMENT. CONTRACTOR SHALL PROVIDE SOUND POWER LEVEL DATA FOR EACH ITEM REQUIRING AN ATTENUATOR AND SHALL BE RESPONSIBLE FOR PROVIDING ANY ADDITIONAL ATTENUATION REQUIRED BY ANY APPROVED EQUIPMENT SUBSTITUTIONS. B. SUBMIT CALCULATIONS TO DEMONSTATE AN ACCEPTABLE OCCUPIED SPACE NOISE LEVEL TO BE APPROVED BY ACOUSTICAL CONSULTANTS AND ME ENGINEERS. TOTAL MODEL NO. OCTAVE BAND Hz MINIMUM DYNAMIC INSERTION LOSS, DB 125 250 500 1K 2K 4K GENERAL NOTES 1. PROVIDE FILTER BOX WITH 1" THROW AWAY FILTERS 2. CAPACITIES & ASSOCIATED INFORMATION (LAT) HAVE BEEN DERATED FOR ALTITUDE UNLESS OTHERWISE NOTED. 3. JOBSITE ELEVATION = 5280FT. 4. LISTED CFM IS AT DESIGN FAN SPEED 5. PROVIDE WALL MOUNTED CONTROLLER. CONNECT TO BAS. COMMONS BUILDING - CABINET UNIT HEATER SCHEDULE (ELECTRIC) REMARK NOTES A. CONNECT TO ACCU-C2.01 B. CONNECT TO ACCU-C2.02 C. PROVIDE OUTSIDE AIR INTAKE CONNECTION/MIXING BOX D. GRAVITY DRAIN CONDENSATE AS SHOWN ON PLUMBING PLANS. E. PROVIDE CONDENSATE PUMP & OVERFLOW ALARM. CONDENSATE PIPING SHOWN ON PLUMBING PLANS. CODE MANUFACTURER/ AREA (CUH) MODEL NO. SERVED CONFIG CFM KW HP VOLT PH DISC FUSE FEEDER REMARKS C1.01 MARKEL 6300 VESTIBULE - EAST CEILING RECESSED 250 5 - 480 3 30A,3P 10A LPS-RK (4#12,1#12G) 3/4"C A, B C1.02 MARKEL 6300 VESTIBULE - WEST CEILING RECESSED 250 5 - 480 3 30A,3P 10A LPS-RK (4#12,1#12G) 3/4"C A, B C1.03 TRANE / FFCB060 MENS & WOMENS RESTROOMS CONCEALED DUCTED 700 10.5 1/6 480 3 20A,3P 10A LPS-RK (4#12, 1#12G) 3/4"C B, C, D C1.04 MARKEL 6300 VESTIBULE - SOUTH WALL RECESSED 500 10 - 480 3 30A,3P 20A LPS-RK (4#12,1#12G) 3/4"C A, B ELECTRICAL GENERAL NOTES 1. EAT=50 F, LAT=100 F. REMARK NOTES A. PROVIDE INTEGRAL THERMOSTAT B. PROVIDE DEAD FRONT DISCONNECT SWITCH C. PROVIDE UNIT WITH DUCT COLLARS. D. PROVIDE HIGH STATIC MOTOR. CFM IS SCHEDULED AT 0.2" ESP. COMMONS BUILDING - WATER HEATER SCHEDULE MANUFACTURER/ RECOVERY (100 TR) RECOVERY (100 TR) INPUT (BTUH) OUTPUT (BTUH) OUTPUT (BTUH) REMARKS ELECTRICAL CODE MODEL NO. SERVICE STORAGE (GALS) @ SEA LEVEL @ ALTITUDE @ SEA LEVEL @ SEA LEVEL @ ALTITUDE VOLT PH FLA FUSE DISC FEEDER DWH-1 AERCO INNOVATION 800 COMMONS 24.5 - - 800,000 771,000 585,960 120 1 9 20A LPN-RK 30A,2P (2#12,1#12G) 3/4"C 1-5,8,9 GENERAL NOTES: A. CAPACITIES SHOWN AT 6,000 FT. B. PROVIDE EPO SWITCH AT EVERY EXIT FROM MECH ROOM IN ACCORDANCE WITH ALL CURRENT ADOPTED CODES. C. ROUTE PRESSURE RELIEFVALVE PIPING TO OVER NEAREST FLOOR SINK. DO NOT ROUTE OVER WALKWAYS. REMARK NOTES 1. MANUAL DISCONNECT SWITCH FOR WATER HEATER PROVIDED BY CONTRACTOR. 2. MANUAL DISCONNECT SWITCH FOR FACTORY MOUNTED RECIRC PUMP, PROVIDED BY CONTRACTOR. 3. ELECTRONIC IGNITION. 4. PROVIDE AERCO CONDENSATE NEUTRALIZER KIT. 5. PROVIDE VERTICAL/HORIZONTAL DIRECT VENT OPTION. 6. 120V TO 24V TRANSFORMER, PROVIDED BY CONTRACTOR. 7. SEPARATED COMBUSTION, TERMINATION KIT. 8. FULLY MODULATING, 24:1 ENERGY INPUT. 9. NOX EMISSIONS: 12.4 PPM @ 3% O2. COMMONS BUILDING - UNIT HEATER SCHEDULE (ELECTRIC) CODE MANUFACTURER/ OUTPUT EAT LAT (UH) MODEL NO. SERVICE (KW) C1.01 MARKEL 5100 STORAGE C1.02 MARKEL 5100 C1.03 MARKEL 5100 ELECTRICAL CFM (F) (F) HP VOLT PH FUSE DISCON. FEEDER REMARKS 5 400 55 95 - 480 3 10A LPS-RK 30A,3P (4#12,1#12G) 3/4"C A STORAGE 5 400 55 95 - 480 3 10A LPS-RK 30A,3P (4#12,1#12G) 3/4"C A STORAGE 5 400 55 95 - 480 3 10A LPS-RK 30A,3P (4#12,1#12G) 3/4"C A GENERAL NOTES 1. JOB SITE ELEVATION = 5,280 FT. 2. PROVIDE INTEGRAL THERMOSTAT 3. PROVIDE DEAD FRONT DISCONNECT SWITCH REMARK NOTES A. HORIZONTAL DISCHARGE. COMMONS BUILDING - DOMESTIC WATER PUMP SCHEDULE HEAD MANUFACTURER/ ELECTRICAL SUCTION DISCHARGE OPER. NOTES CODE MODEL NO. SERVICE LOCATION GPM (FT) RPM HP/WATTS VOLT PH FLA FUSE DISC FEEDER SIZE SIZE WT. LBS. A B C D E F RCP-1 ARMSTRONG ASTRO2 290 DOMESTIC DWH ROOM 8 12 - 218 120 1 1.9 THERMAL OVERLOAD (2#12,1#12G) 3/4" C. 1-1/4'' 1-1/4'' 15 1 1 1 1 1 1,2 C. TYPE 1. WET ROTOR CIRCULATOR E. DUTY 1. THREE SPEED, SET TO MIDDLE SPEED B. FLUID TEMPERATURE 1. 140° F D. MOUNTING 1. SUPPORT FROM STRUCTURE F. MISCELLANEOUS 1. ALL BRONZE OR STAINLESS STEEL CONSTRUCTION 2. TIME CLOCK. PUMP ENERGIZED 6:00AM - 10:00PM, AQUASTAT START/STOP 2 1 07/15/15 09.26.20 14 05/29/15 04/06/15 NO. DATE ADDENDUM 3 PR#6 FOR CONSTRUCTION SCHEMATIC DESIGN DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: JS GP JJS DENVER, CO 05/29/15 AS NOTED MECHANICAL, ELECTRICAL & PLUMBING SCHEDULES ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:00:32 PM AUTHORITY DWG. NO. 3-MEP.02 SHEET: OF: 983_2478_985 _OR_ 3-MEP.02 NOTES A. FLUID 1. WATER COMMONS C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt GENERAL NOTES 1. REFER TO DRAWINGS TO DETERMINE REQUIRED PUMP ROTATION. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING. 2. NON-OVERLOADING AT HORSEPOWER CURVE UNLESS NOTED OTHERWISE. AIR BALANCE SCHEDULE ASHRAE STANDARD 62.1-2007 VENTILATION RATE PROCEDURE CALCULATIONS - AHU-C2.01 AIR HANDLER ZONE/ROOM NAME REQUIRED OUTDOOR OUTDOOR AIRFLOW RATE AIRFLOW RATE ZONE AREA PER PERSON PER UNIT POPULATION ZONE TYPE (Az) (Rp) AREA (Ra) PER TABLE 6-1 (SQ.FT.) CFM / PERSON CFM / SQ.FT. AIRFLOWS MINIMUM ZONE ZONE PRIMARY ROOM NAME OUTDOOR AIR ZONE AIR ZONE REQUIRED AT DISTRIBUTION ZONE OUTDOOR PRIMARY OUTDOOR PEOPLE/1000 POPULATION BREATHING ZONE EFFECTIVENESS AIRFLOW RATE AIRFLOW FRACTION TABLE AND CHAIR STORAGE SQ.FT. (Pz) CFM (Vbz) (Ez) TABLE 6-2 CFM (Voz) CFM (Vpz) (Zp) OFFICE AHU-C2.01 2 ROOM NUMBER TOILET 3-105A STAGES, STUDIOS 2350 10 0.06 70 165 1786 1.0 1786 4300 0.42 LAUNDRY 3-104B RAMP CORRIDOR - NORTH CORRIDORS 350 0 0.06 0 0 21 1.0 21 100 0.21 CUSTODIAN 3-104A RAMP CORRIDOR - SOUTH CORRIDORS 320 0 0.06 0 0 19 1.0 19 100 0.19 OCCUPANT DIVERSITY 100.0% 165 1,826 System Ventilation Efficiency (Ev) ASHRAE 62.1-2007 Required Outdor Air Intake (Vot) ASHRAE 62.1-2007 Required Outdor Air Intake for 30% Increase over Baseline (Vot30) AHU Design Outdoor Air Percentage Outdoor Air Scheduled RETURN TRANSFER IN TRANSFER OUT TOTAL 750 750 0 0 150 50 150 150 0 300 250 0 150 150 0 1260 KITCHEN 2 0.42 CRITICAL ZONE Zp EXHAUST 150 PERFORMANCE PLATFORM AHU-C2.01 TOTAL SUPPLY 1700 590 150 0 3300 4290 990 0 SERVING 3-104 MEN'S TOILET 3-102 300 440 140 0 WOMEN'S TOILET 3-101 400 660 260 0 SECURITY 3-100B 200 ELECTRICAL 3-109 3500 3500 0 IDF 3-106C 600 600 0 CUSTODIAN 3-106B 150 150 0 FAMILY ASSIST TOILET 3-106A 150 150 0 0.74 2,468 CFM 3,208 CFM 56% 2,500 CFM 180 0 20 WATER ENTRY 400 400 0 THEATER STORAGE 400 400 0 4800 4800 0 1770 10540 2 CORRIDOR * 3-106 SEATING AREA 3-100 PERFORMANCE PLATFORM 3-110 16560 7500 4500 290 1000 3500 0 ASHRAE STANDARD 62.1-2007 VENTILATION RATE PROCEDURE CALCULATIONS - ERV-C2.01 AIR HANDLER ZONE/ROOM NAME OUTDOOR OUTDOOR TOTAL BUILDING REQUIRED MINIMUM 1290 * CORRIDOR IS NOT USED AS A RETURN AIR PATH. TRANSFER AIR LISTED IS IN PLENUM. ZONE AIRFLOW RATE AIRFLOW RATE ZONE OUTDOOR AIR ZONE AIR ZONE PRIMARY AREA PER PERSON PER UNIT POPULATION ZONE REQUIRED AT DISTRIBUTION ZONE OUTDOOR PRIMARY OUTDOOR ZONE TYPE (Az) (Rp) AREA (Ra) PEOPLE/1000 POPULATION BREATHING ZONE EFFECTIVENESS AIRFLOW RATE AIRFLOW FRACTION PER TABLE 6-1 (SQ.FT.) CFM / PERSON CFM / SQ.FT. SQ.FT. (Pz) CFM (Vbz) (Ez) TABLE 6-2 CFM (Voz) CFM (Vpz) (Zp) GENERAL NOTES: 1.THIS AIR-BALANCE TABLE REFLECTS THE WORST CASE SCENARIO IN WHICH THERE IS MINIMUM OUTSIDE AIR INTAKE TO THE BUILDING AND MAXIMUM EXHAUST. THE BUILDING IS KEPT SLIGHTLY POSITIVE AT THIS CONDITION BY THE STAGE AIR HANDLING UNIT AND THE ERV UNIT SERVING THE SEATING AREA. IF THE STAGE UNIT IS IN FULL ECONOMIZER MODE, RELIEF WILL BE PROVIDED THROUGH THE STAGE AHU BAROMETRIC RELIEF DAMPER. ERV-C2.01 SEATING AREA MULTIPURPOSE ASSEMBLY 8220 5 ERV-C2.01 TOTAL System Ventilation Efficiency (Ev) ASHRAE 62.1-2007 Required Outdor Air Intake (Vot) ASHRAE 62.1-2007 Required Outdor Air Intake for 30% Increase over Baseline (Vot30) AHU Design Outdoor Air Percentage Outdoor Air Scheduled 0.06 120 986 5425 OCCUPANT DIVERSITY 100.0% 986 5,425 1.0 5425 16500 2.OUSTIDE AIR INTAKE EXCEEDS EXHAUST FROM BUILDING. ERV UNIT PROVIDES MAKE-UP AIR FOR EXHAUST THROUGH ERV AND ENVIRIONMENTAL FANS. 0.33 CRITICAL ZONE Zp AHU PROVIDES POSITIVE PRESSURE AT ALL OPERATING CONDITIONS, AND SERVES AS RELIEF AIR PATH THROUGH BAROMETRIC RELIEF DAMPER. 0.33 0.83 6,536 CFM 8,497 CFM 40% 6,550 CFM ASHRAE STANDARD 62.1-2007 VENTILATION RATE PROCEDURE CALCULATIONS - FCU-C1.01 OUTDOOR REQUIRED MINIMUM ZONE AIRFLOW RATE AIRFLOW RATE ZONE OUTDOOR AIR ZONE AIR ZONE PRIMARY AREA PER PERSON PER UNIT POPULATION ZONE REQUIRED AT DISTRIBUTION ZONE OUTDOOR PRIMARY OUTDOOR ZONE TYPE (Az) (Rp) AREA (Ra) PEOPLE/1000 POPULATION BREATHING ZONE EFFECTIVENESS AIRFLOW RATE AIRFLOW FRACTION ZONE/ROOM NAME PER TABLE 6-1 (SQ.FT.) CFM / PERSON CFM / SQ.FT. SQ.FT. (Pz) CFM (Vbz) (Ez) TABLE 6-2 CFM (Voz) CFM (Vpz) (Zp) WARMING KITCHEN KITCHEN (COOKING) 975 7.5 0.12 20 20 263 1.0 263 1260 0.21 OFFICE OFFICE SPACE 111 5 0.06 5 1 9 1.0 9 150 0.06 LAUNDRY LAUNDRY ROOMS WITHIN DWELLING UNIT 70 5 0.12 10 1 12 1.0 12 50 0.24 OCCUPANT DIVERSITY 100.0% 21 285 AIR HANDLER OUTDOOR FCU-C1.01 2 FCU-C1.01 TOTAL System Ventilation Efficiency (Ev) ASHRAE 62.1-2007 Required Outdor Air Intake (Vot) ASHRAE 62.1-2007 Required Outdor Air Intake for 30% Increase over Baseline (Vot30) AHU Design Outdoor Air Percentage Outdoor Air Scheduled CRITICAL ZONE Zp 0.24 0.92 309 CFM 402 CFM 21% 310 CFM ASHRAE STANDARD 62.1-2007 VENTILATION RATE PROCEDURE CALCULATIONS - SSAC-C1.01 OUTDOOR OUTDOOR AIRFLOW RATE AIRFLOW RATE ZONE AREA PER PERSON PER UNIT POPULATION ZONE TYPE (Az) (Rp) AREA (Ra) ZONE/ROOM NAME PER TABLE 6-1 (SQ.FT.) CFM / PERSON SECURITY OFFICE SPACE 65 5 AIR HANDLER REQUIRED MINIMUM ZONE ZONE PRIMARY ZONE OUTDOOR PRIMARY OUTDOOR EFFECTIVENESS AIRFLOW RATE AIRFLOW FRACTION CFM (Vbz) (Ez) TABLE 6-2 CFM (Voz) CFM (Vpz) (Zp) 1 9 0.8 11 260 0.04 1 9 OUTDOOR AIR ZONE AIR ZONE REQUIRED AT DISTRIBUTION PEOPLE/1000 POPULATION BREATHING ZONE CFM / SQ.FT. SQ.FT. (Pz) 0.06 5 OCCUPANT DIVERSITY 100.0% SSAC-C1.01 SSAC-C1.01 TOTAL 0.04 1.00 9 CFM 12 CFM 8% 20 CFM 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DRAWN BY: CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: JS GP JJS DENVER, CO 05/29/15 AS NOTED MECHANICAL, ELECTRICAL & PLUMBING SCHEDULES ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:00:33 PM AUTHORITY DWG. NO. 3-MEP.03 SHEET: OF: 983_2478_985 _OR_ 3-MEP.03 C:\Revit Projects\2013\Project Path\M_DPS_COMMON_M13_mendez.rvt System Ventilation Efficiency (Ev) ASHRAE 62.1-2007 Required Outdor Air Intake (Vot) ASHRAE 62.1-2007 Required Outdor Air Intake for 30% Increase over Baseline (Vot30) AHU Design Outdoor Air Percentage Outdoor Air Scheduled CRITICAL ZONE Zp COMMONS 2 2. THE DISCONNECTING MEANS FOR ALL MECHANICAL EQUIPMENT SHALL BE ACCESSIBLE AND HAVE THE CLEARANCE IN FRONT AS REQUIRED BY NEC AMENDMENTS. 3. ALL CEILING ATTACHED OBJECTS AND FLOOR ATTACHED EQUIPMENT INCLUDING BUT NOT LIMITED TO PENDANT LIGHTING FIXTURES, GENERAL LIGHTING, MULTIPLE RACEWAYS, GENERATOR, TRANSFORMER ELECTRICAL SWITCHGEAR, AND SWITCHBOARDS SHALL BE INSTALLED IN ACCORDANCE WITH SUPPORTING OBJECTS FOR SEISMIC ZONE AS REQUIRED BY STATE AND LOCAL CODES. 4. ALL SWITCHGEAR, SWITCHBOARDS AND TRANSFORMERS SHALL HAVE A 4 INCH HOUSE KEEPING PAD. UNDER NO CONDITION SHALL THE HIGHEST SWITCH OR BREAKER EXCEED 6'-6" AFF. AMPERE MC MECHANICAL CONTRACTOR AC ABOVE COUNTER MCC MOTOR CONTROL CENTER AF AMPERE FUSE/FRAME MCP MOTOR CIRCUIT PROTECTOR AFF ABOVE FINISHED FLOOR MDF MAIN DISTRIBUTION FRAME AFG ABOVE FINISHED GRADE MDP MAIN DIXTRIBUTION PANEL WALL MOUNTED LINEAR FLOREXCENT MOTOR AND DISCONNECT DUPLEX WALL RECEPTACLE RECESSED 2'X4' MOTOR AND FUSED DISCONNECT AMMETER MFR MANUFACTURER ANN ANNUNCIATOR MG MOTOR GENERATOR SURFACE MOUNTED 2'X4' ANT ATS ANTENNA AUTOMATIC TRANSFER SWITCH MH MIN MAN HOLE OR METAL HALIDE MINIMUM SURFACE MOUNTED 2'X2' AUX AUXILIARY MOV MOTOR OPERATED VALVE AWG AMERICAN WIRE GAUGE MPOE MAIN POINT OF ENTRY BCST BROADCAST MTG MOUNTING HEIGHT BFC BELOW FINISHED CEILING MS MOTOR STARTER BFG BELOW FINISHED GRADE MSB MAIN SWITCHBOARD 6. COORDINATE AND ADJUST ALL WORK BETWEEN TRADES AND EXISTING CONDITIONS IN ORDER TO ACCOMPLISH A NEAT, INTEGRATED AND EFFICIENT INSTALLATION WHICH INCLUDE BUT ARE NOT LIMITED TO: BKR BREAKER MTB MAIN TERMINAL BOARD C CONDUIT MTD MOUNTED CAB CABINET MTG MOUNTING CAM CAMERA MTGB MAIN TELECOMMUNICATION GROUND BUS FLUSH MOUNTED DUPLEX FLOOR-BOX MAG-MSTR AM MAIN LUGS ONLY FOURPLEX WALL RECEPTACLE MOTOR STARTER RECESSED 1'X4' MECHANICAL MLO RECESSED 2'X2' FLUSH MOUNTED COMBO DUPLEX/DATA FLOOR-BOX CB UN-FUSED DISCONNECT FLUSH MOUNTED FOURPLEX FLOOR-BOX FUSED DISCONNECT CIRCUIT BREAKER BRANCH CIRCUIT OR POWER PANEL FLUSH MOUNTED COMBO FOURPLEX /DATA FLOOR-BOX CB/6 LIGHTING CONTROL PANEL SURFACE MOUNTED 1'X4' M RECESSED STEP LIGHT FLUSH MOUNTED COMBO FOURPLEX /DATA FLOOR-BOX CB/8 METER RECESSED FOURPLEX FLOOR-BOX CURRENT TRANSFORMER WALL MOUNTED FLOODLIGHT CB GROUND WALL MOUNTED SCONCE RECESSED COMBO FOURPLEX/DATA FLOOR-BOX COMBO POWER/DATA FURNITURE FEED J CB DELTA/WYE WITH GROUND SURFACE MOUNTED DOWN LIGHT J CB SURFACE MOUNTED WALL WASH POWER TRANSFORMER T SPECIAL RECEPTACLE (FOR "X" SEE TABLE BELOW) X RECESSED DOWN LIGHT FUSE & SWITCH COMBO POWER/DATA FURNITURE FEED b. COORDINATE NECESSARY EQUIPMENT, FIXTURES, ETC. SO THAT THE FINAL INSTALLATION IS COMPATIBLE WITH THE MATERIALS AND EQUIPMENT OF THE OTHER TRADES. CB CIRCUIT BREAKER MV MEDIUM VOLTAGE CCTV CLOSED CIRCUIT TELEVISION N NEUTRAL RECESSED WALL WASH CIRCUIT BREAKER c. THIS CONTRACTOR SHALL ASSIST THE DIVISION 23 CONTRACTOR IN PREPARING SHOP DRAWINGS FOR COORDINATING INSTALLATION OF ALL WORK (IE. LOCATING ALL LIGHTING FIXTURES IN CEILING WITH CEILING CLEARANCES, RACEWAYS, PIPING, EQUIPMENT FOR CLEARANCE THROUGHOUT). CKT CIRCUIT NEC NATIONAL ELECTRICAL CODE RECESSED 1X4 WALL WASH DRAWOUT CIRCUIT BREAKER CEILING FOURPLEX RECEPTACLE CO CONDUIT ONLY NF NON FUSED COMB COMBINATION NIC NOT IN CONTRACT PENDANT LIGHT KIRK-KEY INTERLOCK CEILING RECEPTACLE COMP COMPUTER NC NORMALLY CLOSED MONOPOINT TRACKHEAD GROUND FAULT INTERRUPTER BREAKER CLOCK RECEPTACLE LINEAR QUARTZ LIGHT STRIP CIRCUIT MONITORING DEVICE EMERGENCY RECEPTACLE 7. DEFINITIONS: a. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT. b. "INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL OPERATIONAL ORDER". COND CONDUCTOR NO NORMALLY OPEN CT CURRENT TRANSFORMER NTS NOT TO SCALE CU dB COPPER DECIBEL OC OD ON CENTER OUTSIDE DIAMETER POLE MOUNTED LUMINAIRE WITH ARM DEMARC DEMARCATION P POLE POLE MOUNTED LUMINAIRE POST TOP MOUNTING DISC DISCONNECT PA PUBLIC ADDRESS CEILING MOUNTED EXIT SIGN c. "PROVIDE" MEANS TO "FURNISH AND INSTALL". DL DAMP LABEL PB PUSH BUTTON d. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN ALL SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS SHALL BE DETERMINED BY THE ENGINEER. DWG DRAWING PBX PRIVATE BRANCH EXCHANGE DVR DIGITAL VIDEO RECORDER PE PHOTOELECTRIC e. "RE: DIVISION", AND SIMILAR EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTORS SOLE RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN HIS/HER SUPPLIERS, SUBCONTRACTORS, AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT ARCHITECT. EA EACH PF POWER FACTOR EC ELECTRICAL CONTRACTOR PH PHASE EF EXHAUST FAN PNL PANEL EG EQUIPMENT GROUND PR PAIR EHC ELECTRIC HEATING COIL PRI PRIMARY ELEC ELECTRIC OR ELECTRICAL PT POTENTIAL TRANSFORMER 8. "FIRESTOPPING" REQUIREMENT. ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM-E-814. ALL PENETRATIONS SHALL MEET F AND T RATINGS AS REQUIRED BY THE BUILDING CODE. 9. WHERE DISCONNECTS ARE INDICATED ON DRAWINGS CONTRACTOR SHALL PROVIDE FINAL CONNECTION TO EQUIPMENT BEING SERVED BY DISCONNECT. 10. CONTRACTOR PROVIDE ALL MISCELLANEOUS SUPPORTS AS REQUIRED FOR A COMPLETE OPERABLE ELECTRICAL INSTALLATION INCLUDING MISCELLANEOUS STEEL, UNI-STRUT, ALL-THREAD, AIRCRAFT CABLE, ETC. ELECTRICAL BID ALTERNATE PRICING: 1. BID ALTERNATE #1 - THEATER LIGHT FIXTURES ELEVATOR PVC POLYVINYL CHLORIDE EMERG EMERGENCY PWR POWER DIMMER SWITCH EMT ELECTRIC METALLIC TUBING QR QUARTZ RESTRIKE SINGLE POLE SWITCH ENG ELECTRONIC NEWS GATHERING R REMOVE EOL F/A END OF LINE RESISTOR REC RECEPTACLE EQUIP EQUIPMENT RGS RIGID GALVANIZED STEEL ER EXISTING TO BE REMOVED/RELOCATED RM ROOM EWC ELECTRIC WATER COOLER RPM REVOLUTIONS PER MINUTE 3 3-WAY SWITCH 4 4-WAY SWITCH LV EXISTING SECT SECTION F FUSE SHT SHEET F/A FIRE ALARM SMPOE SECONDARY MAIN POINT OF ENTRY FACP FIRE ALARM CONTROL PANEL SP SERVICE PROVIDER FBO FURNISHED BY OTHERS SPD SURGE PROTECTIVE DEVICE FC FOOTCANDLES SPDT SINGLE POLE, DOUBLE THROW FDR FEEDER ST SHUNT TRIP FLEX FLEXIBLE STD STANDARD BR FLR FLOOR SW SWITCH BT FLUOR FLUORESCENT SWBD SWITCHBOARD GALV GALVANIZED T TWIST LOCK GEN GENERATOR TBB TELECOMMUNICATIONS BONDING BACKBONE GFCI GROUND FAULT CIRCUIT INTERRUPTER TC TIME CLOCK GND GROUND TTB TELEPHONE TERMINAL BOARD HC HORIZONTAL CROSS CONNECT TTC TELEPHONE TERMINAL CABINET OR CLOSET HD HEAVY DUTY TEL TELEPHONE HH HAND HOLE TELCO TELEPHONE COMPANY HOA HAND-OFF-AUTO TELCOM TELECOMMUNICATIONS HP HORSE POWER TEMP TEMPERATURE HPF HIGH POWER FACTOR TGB TELECOMMUNICATIONS GROUND BUS HPS HIGH PRESSURE SODIUM TR TEMPER RESISTANT HTR HEATER UC UNDER COUNTER IC ID IDF INTERMEDIATE CROSS CONNECT INSIDE DIAMETER INTERMEDIATE DISTRIBUTION FRAME U/G UNDER GROUND IMC INTERMEDIATE GRADE METALLIC CONDUIT UH UL UNO UNIT HEATER UNDERWRITER LABORATORIES UNLESS NOTED OTHERWISE INCAND INCANDESCENT UPS UNINTERRUPTIBLE POWER SUPPLY J-BOX JUNCTION BOX UTP UNSHIELDED TWISTED PAIR KCMIL THOUSAND OF CIRCULAR MILLS V VOLT KVA KILOVOLT AMPERE VFD VARIABLE FREQUENCY DRIVE KW KILOWATT VM VOLTMETER KWH KILOWATT HOUR W WATT FINISHED FLOOR NOTES: 1. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. 2. CONTRACTOR SHALL ENSURE THAT ALL MOUNTING HEIGHTS COMPLY WITH CURRENT ADA REQUIREMENTS. 3. WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE. 4. ALL ABOVE COUNTER DEVICES SHALL BE MOUNTED 5. ALL ABOVE COUNTER (DESIGNATED BY "AC") SHALL BE MOUNTED 8" ABOVE COUNTER OR MAXIMUM HEIGHT OF 44" TO TOP OF DEVICE. VERIFY HEIGHTS WITH ARCHITECT. 6. FOR CEILINGS BELOW 7'-4", FIRE ALARM STROBE OR HORN/STROBES SHALL BE WALL MOUNTED 6" BELOW FINISHED CEILING. LA LIGHTNING ARRESTOR W/ LOCAL AREA NETWORK WH WATT HOUR LFC LIQUID TIGHT FLEXIBLE CONDUIT WHM WATT HOUR METER LTG LIGHTING WLAN WIRELESS-LOCAL AREA NETWORK LV LOW VOLTAGE WP WEATHERPROOF MA MILLIAMPERE WPL WEATHERPROOF LOCKABLE ENCLOSURE MAX MAXIMUM WT WATERTIGHT MB MAIN BREAKERS XFMR TRANSFORMER XP EXPLOSION PROOF CEILING TV OUTLET TV POWER POLE MOTOR AND THERMAL OVERLOAD SINGLE TOGGLE SWITCH PLUG MOLD AUTOMATIC TRANSFER SWITCH SINGLE PUSH BUTTON WALL BUZZER RACEWAY LEGEND BRANCH CIRCUIT HOMERUN TO PANELBOARD, NUMBER OF ARROWS INDICATES NUMBER OF CIRCUITS, NUMERICAL INDICATES CIRCUIT NUMBER. BRANCH CIRCUIT HOMERUN CONTROLLED BY LIGHTING CONTROL SYSTEM. FIRST HEXAGON LETTER CORRESPONDS TO FIRST CIRCUIT NUMBER. (ie. CIRCUIT #2 IS ON ZONE A) A:2,4 FIRE ALARM A UNDERGROUND FEEDER SMOKE DETECTOR UNDERGROUND BRANCH CIRCUIT HOMERUN HEAT DETECTOR CONDUIT UP DUCT DETECTOR CONDUIT DOWN BEAM DETECTOR RECEIVER CONDUIT RUNS UNDERFLOOR OR BELOW GRADE BEAM DETECTOR TRANSMITTER CONDUIT RUN CONCEALED IN WALLS OR CEILING, OR EXPOSED WHEN CEILING ARE NOT PRESENT. EMERGENCY POWER OFF EVAC ESR VOICE EVAC PANEL MOTOR CONNECTION ELEVATOR STATUS PANEL CEILING MOUNTED HORN [SPEAKER] WALL MOUNTED HORN [SPEAKER] OUTLET RATING NEMA/CAT NO FEEDER (NOTE 1) WIRING NOTES A NON-LOCKING, 20A, 125V, 1PH 5-20R 2#12,#12G,3/4"C (50FT) DEDICATED, SINGLE OUTLET B NON-LOCKING, 30A, 125V, 1PH 5-30R 2#10,#10G,3/4"C (60FT) HOT-NEUT-GND C NON-LOCKING, 20A, 250V, 1PH 6-20R 2#12,#12G,3/4"C (100FT) HOT-HOT-GND D NON-LOCKING, 30A, 250V, 1PH 6-30R 2#10,#10G,3/4"C (120FT) HOT-HOT-GND E NON-LOCKING, 50A, 250V, 1PH 6-50R 2#6,#10G,3/4"C (150FT) HOT-HOT-GND F TBD - - - G NON-LOCKING, 20A, 125/250V, 1PH 14-20R 3#12,#12G,3/4"C (100FT) HOT-HOT-NEUT-GND H TBD - - - I NOT USED - - - J LOCKING, 20A, 125V, 1PH L5-20R 2#12,#12G,3/4"C (50FT) HOT-NEUT-GND K LOCKING, 30A, 125V, 1PH L5-30R 2#10,#10G,3/4"C (60FT) HOT-NEUT-GND L LOCKING, 20A, 250V, 1PH L6-20R 2#12,#12G,3/4"C (100FT) HOT-HOT-GND M LOCKING, 30A, 250V, 1PH L6-30R 2#10,#10G,3/4"C (120FT) HOT-HOT-GND N TBD - - - O NOT USED - - - CEILING MOUNTED REMOTE INDICATOR LIGHT P LOCKING, 20A, 125/250V, 1PH L14-20R 3#12,#12G,3/4"C (100FT) HOT-HOT-NEUT-GND WALL MOUNTED REMOTE INDICATOR LIGHT Q LOCKING, 30A, 125/250V, 1PH L14-30R 3#10,#10G,3/4"C (120FT) HOT-HOT-NEUT-GND R TBD - - - S WALL MOUNTED HORN [SPEAKER]/STROBE WALL MOUNTED SILENTONE FIRE SERVICE PHONE H FIREMAN'S PHONE JACK J ROTATING BEACON DH MANUAL PULL STATION MAGNETIC DOOR HOLD OPEN DEVICE TAMPER SWITCH FLOW SWITCH RTS RTS RECEPTACLE MODIFIER TAGS TAG CEILING MOUNTED HORN [SPEAKER]/STROBE WITH LAN CEILING JUNCTION BOX LOW VOLTAGE SWITCH WALL MOUNTED ADA STROBE S LOCKING, 20A, 208Y/120V, 3PH L21-20R 4#12,#12G,3/4"C (120FT) HOT-HOT-HOT-NEUT-GND CEILING MOUNTED STROBE T LOCKING, 30A, 208Y/120V, 3PH L21-30R 4#10,#10G,3/4"C (130FT) HOT-HOT-HOT-NEUT-GND IM MAGNETIC DOOR HOLD OPEN DEVICE U LOCKING, 50A, 250V, 3PH HBL CS8365C 3#6,#10G,1"C (175FT) HOT-HOT-HOT-GND FR FIRE ALARM ADDRESSABLE RELAY V NOT USED - - - W PIN & SLEEVE, 60A, 208Y/120V, 3PH HBL 560R9W 4#4,#10G,1-1/4"C (200FT) HOT-HOT-HOT-NEUT-GND X PIN & SLEEVE, 100A, 208Y/120V, 3PH HBL 5100R9W 4#1,#8G,1-1/2"C (250FT) HOT-HOT-HOT-NEUT-GND Y TBD - - - Z TBD - - - ALARM BELL FIRE SMOKE DAMPER FR TYPICAL DEVICE MOUNTING HEIGHTS NO SCALE 16" AFF U.N.O. -GYP -BLOCK 18"AFF U.N.O. -BLOCK (6") BOTTOM OF DEVICE TOP OF DEVICE 48" (4'-0") U.N.O. 64" (5'-4") U.N.O. 72" (6'-0") U.N.O. 78" (6'-6") U.N.O. TOP OF CABINET FAAP CONTROL PANELS J A:2,4 EX FACP TO THERMAL OVERLOAD SHADED SYMBOLS DENOTE EMERGENCY FIXTURES PROVIDE QUARTZ RESTRIKE FOR ALL METAL HALIDE EMERGENCY FIXTURES. B. ALTERNATE 1A: PROVIDE TYPE T1, T2 FIXTURES AND ITS CONTROL SYSTEM ON PERFORMANCE STAGE AS SHOWN ON PLANS. C. ALTERNATE 1B: PROVIDE LED SOURCE FIXTURES (TYPE T3,T4) ON PERFORMANCE STAGE, IN LIEU OF 'PAR' (TYPE T1,T2) AS INDICATED ON FLOOR PLANS. BID ALTERNATE PRICING SHALL INCLUDE DMX. REFER TO ELECTRICAL DRAWINGS ON SHEET 3-E0.02 , 3-E0.07 3-E0.08 3-E0.09, AND 3-E3.01. FIXTURE SHALL ETC SOURCE 4 LED SERIES 2. D. ALTERNATE 1C: PROVIDE LED SOURCE FIXTURES (TYPE T3,T4) ON PERFORMANCE STAGE, IN LIEU OF 'PAR' (TYPE T1,T2) AS INDICATED ON FLOOR PLANS. BID ALTERNATE PRICING SHALL INCLUDE DMX. REFER TO ELECTRICAL DRAWINGS ON SHEET 3-E0.02 , 3-E0.07 3-E0.08 3-E0.09, AND 3E3.01. FIXTURE SHALL ALTMAN LIGHTING PHOENIX LED. E. ALTERNATE 1D: PROVIDE LED SOURCE FIXTURES (TYPE T3,T4) ON PERFORMANCE STAGE, IN LIEU OF 'PAR' (TYPE T1,T2) AS INDICATED ON FLOOR PLANS. BID ALTERNATE PRICING SHALL INCLUDE DMX REFER TO ELECTRICAL DRAWINGS ON SHEET 3-E0.02 , 3-E0.07 3-E0.08 3-E0.09, AND 3-E3.01. FIXTURE SHALL ETC D40 SERIES. TOP OF CABINET TO OCCUPANCY SENSOR - COMBINATION DUAL LEVEL WALL SWITCH ELEV SECONDARY/SECOND NOTE: ALL DEVICES INDICATED TO BE INSTALLED AT DIFFERENT MOUNTING HEIGHTS AND LOCATED WITHIN ONE STUD SPACE FROM EACH OTHER SHALL ALIGN VERTICALLY, ON THE SAME SIDE OF THE STUD. WHERE WALL MOUNTED TELEPHONES OCCUR OVER LIGHT SWITCHES, VOLUME CONTROLS, ETC. OFFSET ONE STUD SPACE. FLOOR JUNCTION BOX DUPLEX PUSH BUTTON SEC TOP OF CABINET J TRANSIENT VOLTAGE SURGE SUPPRESSION OCCUPANCY SENSOR - WALL MOUNTED EXHAUST B. ALTERNATE: PROVIDE ELECTRICAL CONNECTION AND CONTROL WIRING FOR MOTORIZED SHADES AND ITS CONTROLLERS PER MANUFACTURER REQUIREMENTS. WALL JUNCTION BOX COMBINATION OCCUPANCY SENSOR - WALL SWITCH DL EXH A. BASE BID: PROVIDE ROUGH-IN/CIRCUITING AND CONTROL STATION LOCATION FOR FUTURE MOTORIZED SHADES FOR SEATING AREA CLERESTORY AS INDICATED ON PLANS. TVSS OCCUPANCY SENSOR - CEILING MOUNTED SECURITY CONTROL PANEL 3. BID ALTERNATE #3 - MOTORIZED SHADES COMBINATION TV / POWER OUTLET EMERGENCY LIGHTING UNIT SCP B. ALTERNATE: PROVIDE CONTROL CONSOLE AS INDICATED ON SHEET 3-E0.02. ETC #SMARTFADE 1248 OR APPROVED EQUAL. TV MECHANICAL EQUIPMENT IDENTIFICATION TAG WALL MOUNTED EXIT SIGN ELECTRIC WATER HEATER A. BASE BID: NONE D EXIT SIGN WITH DIRECTIONAL ARROWS (CHEVRONS) EWH 2. BID ALTERNATE #2 - THEATER CONTROL CONSOLE G TRACK WITH TRACKHEADS A. BASE BID: NONE 2 K CEILING DUPLEX RECEPTACLE J d. THE ELECTRICAL DRAWINGS INDICATE THE ELECTRICAL REQUIREMENTS FOR A SIGNIFICANT PORTION OF THE MECHANICAL AND PLUMBING SYSTEMS. ADDITIONAL MECHANICAL AND PLUMBING EQUIPMENT IS INDICATED ON THE DIVISION 23 DRAWINGS. REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FORADDITIONAL INFORMATION. PROVIDE COMPLETE WIRING AND FUSIBLE DISCONNECTING MEANS FOR ALL MECHANICAL AND PLUMBING EQUIPMENT. THE ENTIRE LENSE NOT LESS THAN 80" AND NOT GREATER THAN 96" AFF TO BOTTOM OF DEVICE WALL RECEPTACLE MECH AUTOMATIC EQUIPMENT MOTOR ALUMINUM AUTO EQUIPMENT STRIP LIGHT AL 5. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO ACTUAL CONDITIONS AT THE BUILDINGS. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. HOWEVER THIS DOES NOT RELIEVE ANY SUB-CONTRACTOR FROM COORDINATING HIS WORK WITH ALL OTHER TRADES AND FROM ADJUSTING HIS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF THE PROJECT. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING COSTS TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT. a.EXAMINE THE CONTRACT DOCUMENTS OF ALL TRADES (IE. THE ARCHITECTURAL REFLECTED CEILING PLAN, MECHANICAL HVAC DRAWINGS, ELECTRICAL LIGHTING PLAN, FIRE PROTECTION PLAN, ETC.). C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt A,AMP LIGHTING SMOKE CONTROL DAMPER CO CARBON MONOXIDE DETECTOR FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL NOTE 1: DISTANCE NOTED IS MAXIMUM RUN LENGTH FOR WIRE SIZE. INCREASE PER NEC, INCLUDING GROUND, FOR LONGER RUNS OR FOR DERATING FACTORS (AMB TEMP, EXTERIOR, ETC.) 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED ELECTRICAL LEGEND & ABBREVIATIONS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:17 PM AUTHORITY DWG. NO. 3-E0.00 SHEET: OF: 983_2478_985 _OR_ 3-E0.00 1. ALL EXPOSED RACEWAYS ARE TO BE INSTALLED PARALLEL OR PERPENDICULAR TO WALLS OR STRUCTURAL MEMBERS SUCH THAT THEY FOLLOW STRUCTURAL SURFACE CONTOURS AND SHALL BE INSTALLED SUCH THAT THEY DO NOT OBSTRUCT PASSAGEWAYS OR ACCESS TO EQUIPMENT. MULTIPLE RACEWAYS SHOULD BE INSTALLED GROUPED TOGETHER. THE LOCATION OF PUBLICLY VISIBLE RACEWAYS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. (EXTRA TIME SHOULD BE ALLOWED FOR THIS REVIEW AND APPROVAL.) ABBREVIATIONS COMMONS ABBREVIATIONS NOTES: C1-MSB BUS: MAINS: VOLTAGE: 2000AMP 2000 AMP MAIN BKR 480Y/277 Bkr/OCPD 20 30 40 50 50 60 70 80 90 100 100 100 110 125 150 150 175 200 225 250 250 250 300 350 400 400 450 500 500 600 700 750 800 800 1000 1000 1200 1200 1600 1600 1600 2000 2000 2500 2500 2500 3000 3500 3500 4000 4000 LOAD SUMMARY 56th AVE BRANCH CKTS ON C1-MSB C1-RIG C1-RDS1 C1-L1 C1-HM1 C1-EDS1 E E E S T S T E TRANS E E E TRANS LIMIT OF WORK XCEL PAD MOUNTED TRANSFORMER 17 FUTURE CONNECTED TOTALS FUTURE TENNIS COURTS TENNIS COURTS CALCULATED TOTALS FUTURE FUTURE T LIMIT OF WORK COMMONS COMMONS T T T TOTAL KVA 301 24 241 10 68 47 TOTAL AMPS 692 710 832 - 362 28 290 13 81 57 854 T C1-RDS1 BUS: MAINS: VOLTAGE: MATCH LINE B MATCH LINE B 1000AMP 1000 AMP MAIN BKR 208Y/120 LOAD SUMMARY BRANCH CKTS ON C1-RDS1 C1-R2 C1-R1 C1-FS1 CONNECTED TOTALS SLC CENTRAL PARK BLVD FFE 5238.00 CALCULATED TOTALS TOTAL AMPS 241 218 670 - 358 25 103 184 606 H LINE A GYM TOTAL KVA 129 9 37 66 MATC FFE 5241.00 FUTURE GYM C1-EDS1 MULTI USE FIELD (RE: LSCAPE) FUTURE SLC 225AMP M.L.O. 480Y/277 BUS: MAINS: VOLTAGE: LOAD SUMMARY BRANCH CKTS ON C1-EDS1 C1-SR1 C1-EL1 FUTURE PARKING CONNECTED TOTALS CALCULATED TOTALS MATCH LINE D MATCH LINE D TOTAL KVA 20 23 5 TOTAL AMPS 47 44 57 - 23 27 6 53 TAG F1 F2 F3 F4 F5 F5 F6 F7 F8 F8A F9 F9 F10 F11 F12 F13 F14 F15 F16 F17 F18 F19 F20 F20 F21 F22 F23 F23C F24 F24C F25 F25C F26 F26C F27 F28 F28C F29 F29C Sets 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 4 3 5 4 6 5 7 6 8 10 9 11 10 PIPE 3/4" 3/4" 3/4" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 2-1/2" 2-1/2" 3" 3" 2" 2-1/2" 2-1/2" 3" 3" 3" 3" 3" 3" 3-1/2" 3" 3-1/2" 3" 4" 3-1/2" 4" 3-1/2" 3-1/2" 4" 4" 4" FEEDER TABLE - CONDUCTORS COPPER FDR/PIPE [3W] TAG 3#12,#12G FA1 3#10,#10G FA2 3#8,#10G FA3 3#6,#10G FA4 FA4A 3#4,#8G FA5 3#4,#8G FA5 3#3,#8G FA6 3#2,#8G FA7 3#1,#8G FA8 FA8A FA8B 3#1,#6G 3#1/0,#6G FA9 3#1/0,#6G FA9 FA9A 3#2/0,#6G FA10 3#3/0,#6G FA11 3#4/0,#4G FA12 3#250,#4G FA13 FA13A FA13B 3#350,#4G FA14 3#500,#3G FA15 3#3/0,#3G FA16 FA16A 3#4/0,#2G FA17 3#250,#2G FA18 FA18A 3#350,#1G FA19 3#500,#1/0G FA20 3#500,#1/0G 3#300,#1/0G FA21 FA21A 3#400,#2/0G FA22 FA22A 3#350,#3/0G FA23 3#600,#3/0G FA23C 3#400,#4/0G FA24 FA24A 3#600,#4/0G FA24C 3#400,#250G FA25 3#600,#250G FA25C 3#500,#350G FA26 FA26A 3#600,#350G FA26C 3#500,#400G FA27 3#500,#500G FA28 3#600,#500G FA28C 3#500,#500G FA29 3#600,#500G FA29C GENERAL NOTES: Sets 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3 4 3 5 5 4 6 5 7 7 6 8 10 9 11 10 COPPER FDR/PIPE [4 W] 4#12,#12G 4#10,#10G 4#8,#10G 4#6,#10G 4#6,#8G 4#4,#8G 4#4,#8G 4#3,#8G 4#2,#8G 4#1,#8G 4#1,#6G 5#1,2#8G 4#1/0,#6G 4#1/0,#6G 5#1/0,2#6G 4#2/0,#6G 4#3/0,#6G 4#4/0,#4G 4#250,#4G 4#250,#2G 5#250,2#2G 4#350,#4G 4#500,#3G 4#3/0,#3G 4#3/0,#1/0G 4#4/0,#2G 4#250,#2G 4#250,#1/0G 4#350,#1G 4#500,#1/0G 4#300,#1/0G 4#300,#2/0G 4#400,#2/0G 4#400,#3/0G 4#350,#3/0G 4#600,#3/0G 4#400,#4/0G 4#400,#250G 4#600,#4/0G 4#400,#250G 4#600,#250G 4#500,#350G 4#500,#500G 4#600,#350G 4#500,#400G 4#500,#500G 4#600,#500G 4#500,#500G 4#600,#500G PIPE 3/4" 3/4" 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 2" 2" 2-1/2" 2" 2" 2-1/2" 2" 2-1/2" 2-1/2" 3" 3" 3" 3" 3-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3" 3" 3-1/2" 3" 3" 3-1/2" 3-1/2" 3" 4" 3-1/2" 3-1/2" 4" 3-1/2" 4" 3-1/2" 4" 4" 4" 4" 4" 4" 4" ALL CONDUCTORS ARE WITH THHN/THWN WIRE WITH 60DEG TERMINATIONS UP TO #1AWG AND 75DEG FOR LARGER SIZES. CONDUIT SIZES MAY BE ALTERED BY CONTRACTOR WHEN IN ACCORDANCE WITH NEC ERV C2.01 6 AHU C2.01 VFD 6 200A,3P NEMA 3R VFD 40A, 3P NEMA 3R ROOF ROOF C1-SR1 C1-EL1 KEY AVAILABLE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 47,500A* 817-15 KVA 1572 - 30 KVA 2551 - 45 KVA 3858 - 75 KVA 6378 - 112.5 KVA NOT USED 40084.05A 37640.98A 30615.14A 20917.15A 37307.86 31897.35A 12419.39A 10832.45A 7851.92A ALL CONDUIT RUNS SHALL BE RAN PERPENDICULAR AND PARALLEL TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT RUNS SHALL BE COORDINATED WITH ARCHITECT PRIOR TO INSTALLATION. 4. FOR CALCULATION PURPOSES THE FOLLOWING TRANSFORMER IMPEDANCES WERE USED: 15 KVA-5.1%Z,30 KVA-5.3%Z, 45 KVA-4.9%Z,75 KVA-5.4%Z, 112.5 KVA-4.9%Z,150 KVA-5.3%Z, 225 KVA-5.3%Z,300 KVA-5.7%Z, 500 KVA-5.8%Z 5. PROVIDE FULL BUSSING FOR ALL SPACES INDICATED ON PANEL BOARDS AND DISTRIBUTION BOARDS. 6. CONNECT ALL TRANSFORMER GROUNDING ELECTRODE TO GROUND BUS RISER. 7. ALL 208V/120 PANELBOARDS SHALL BE TWO SECTION WITH 42 BREAKERS EACH SECTION, UNLESS OTHERWISE NOTED. PANELBOARDS SHALL MAINTAIN 20% SPARE BREAKERS. 8. ALL 480V/277 PANELBOARDS SHALL BE SINGLE SECTION WITH 42 BREAKERS, UNLESS OTHERWISE NOTED. PANELBOARDS SHALL MAINTAIN 20% SPARE BREAKERS. 9. REFER TO FEEDER TABLE FOR FEEDER SIZE CORRESPONDING TO OVERCURRENT PROTECTION DEVICE (BREAKER OR FUSE) SHOWN ON ONE-LINE. USE TRANSFORMER FEEDERS AND OVERCURRENT PROTECTION DEVICE. 1 LOCATE LIGHTING CONTROL RELAY PANEL ADJACENT TO 480/277V LIGHTING PANEL. PROVIDE A MINIMUM OF 48-RELAYS PER PANEL. 2 NEUTRAL AND GROUND BOND. 3 CONNECT TO MAIN SERVICE SWITCHBOARDS GROUND BUS WITH 4/0 AWG. COPPER IN A 1" CONDUIT. PVC PERMITTED BELOW GRADE. 4 PROVIDE BUILDING GROUNDING SYSTEM WITH CONNECTION TO PERIMETER GROUND LOOP, BUILDING STEEL, COLD WATER PIPE, AND ROOM GROUND BUS. 5 MOUNT TVSS UNIT ON TOP OF SWITCHBOARD ENCLOSURE. LOCATE CIRCUIT BREAKER ON THE TOP TO ACHIEVE THE SHORTEST FEEDER LENGTH POSSIBLE. 6 REFER TO MEP SCHEDULE SHEETS FOR EQUIPMENT SIZES VFD IS PROVIDED BY MANUFACTURER. EC SHALL COORDINATE WITH FOR WIRING REQUIREMENTS 10 PROVIDE DIMMING PANEL WITH (24) 20A/1P DIMMERS. PROVIDE (1) DIMMING CONTROLLER AND (2) 4-BUTTON SCENE STATION. 13 PROVIDE LSI TYPE CIRCUIT BREAKER 17 7244.36A 18 THIS CONTRACTOR SHALL PROVIDE TRANSFORMER PAD AND PRIMARY CONDUITS PER XCEL REQUIREMENTS. 20 A. PROVIDE IN CONJUNCTION WITH EACH AND EVERY TRANSFER SWITCH THE FOLLOWING: 1. 2# 12-1/2”C FROM AUXILIARY CONTACT (CLOSED WHEN SWITCH IN EMERGENCY POSITION) ON TRANSFER SWITCH TO EACH ELEVATOR MACHINE ROOM WHICH IS SERVED VIA THAT TRANSFER SWITCH. TERMINATE AS AND WHERE REQUIRED BY THE ELEVATOR VENDOR. 2. 2# 12-1/2”C FROM AUXILIARY CONTACT (CLOSED BEFORE SWITCH RETURNS TO NORMAL POWER) ON TRANSFER SWITCH SERVING ELEVATORS TO EACH ELEVATOR MACHINE ROOM WHICH IS SERVED VIA THAT TRANSFER SWITCH. TERMINATE AS AND WHERE REQUIRED BY THE ELEVATOR VENDOR. 3. 2# 12-1/2”C FROM ENGINE START CONTACT ON TRANSFER SWITCH TO RESPECTIVE EMERGENCY GENERATOR CONTROL PANEL AND REMOTE ANNUNCIATOR PANELS WITH START AND STOP CONTROLS. 4. 2# 12-1/2”C FROM AUXILIARY CONTACTS ON FIRE PUMP CONTROLLER FOR GENERATOR START. 5. WIRING AS NECESSARY FROM TRANSFER SWITCH TO REMOTE ANNUNCIATOR PANELS AND ENGINE CONTROL PANEL FOR TRANSFER SWITCH POSITION INDICATOR LIGHTS. B. PROVIDE ALL NECESSARY WIRING AND CONDUIT TO EACH REMOTE ALARM PANEL LOCATED AT THE BUILDING ENGINEER OFFICE. FA5 FA8 3. 16 PROVIDE 15KVA, 480/277V, 3PH, 4W, 42,000AIC EMERGENCY LIGHTING INVERTER SYSTEM WITH A MINIMUM 90 MINUTES BATTERY BACKUP FOR EMERGENCY LIGHTING AND EXIT SIGNS. EQUIPMENT SHALL BE PROVIDED WITH UL924 RATED DEVICE. REFER TO SPEC SECTION 26.52.10. PROVIDE BATTERY ALARM MONITORING SYSTEM AS REQUIRED BY DENVER AMENDMENT TO IFC. ALARM SYSTEM SHALL BE TIED INTO FIRE ALARM SYSTEM. INVERTER SHALL BE PROVIDED WITH SPILL CONTAINMENT UNIT AS REQUIRED BY LOCAL AHJ. 11 3 FEEDER LENGTHS ARE INDICATED FOR CALCULATION PURPOSES ONLY. CONTRACTOR SHALL NOT BASE ACTUAL FEEDER LENGTHS ON QUANTITIES INDICATED ON THIS DRAWING. 15 PROVIDE FUSED CIRCUIT BREAKER PANELBOARDS (BUSMANN #QUIK-SPEC OR PRE-APPROVED EQUAL BY LITTLE FUSE). * Based on 5.75% Infinite Impedence Transformer Impedence 15 2. 14 PROVIDE EMON DMON TYPE SUBMETERING DEVICE WITH INTEGRAL CT FOR EMERGENCY MONITORING FUNCTION. EQUIPMENT SHALL BE TIED-IN TO BMS SYSTEM OF THID PARTY ENERGY MANAGEMENT SOFTWARE. SERIES RATING IS NOT PERMITTED. ELECTRICAL SITE PLAN 1" = 100'-0" ALL FEEDERS SHALL BE COPPER 75 DEGREE RATED INSULATION. KEY NOTES: FAULT CALCULATION TABLE ALL EQUIPMENT MUST BE FULLY RATED FOR SHORT CIRCUIT / FAULT VALUES SHOWN BELOW. 2 1. 21 PROVIDE PROVISION FOR FUTURE BUILDING ADDITION. TRANSFORMER 30KVA 480-208/120V 3PH, 4W. C1-FS1 INVERTER 16 T #6CU C1-R2 C1-R1 (3) 15 16 FA12 17 FA8 FA12 3 FA5 F4 10 F3 F13 1000/3 FA13B #2CU 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION SPACE 400/3 SPACE 400/3 SPACE 225/3 SPACE 225/3 225/3 225/3 21 400/3 SPARE 125/3 21 FA25 BLDG STEEL CW PIPE GROUND RODS #3/0CU 8 #3/0CU CONDUCTORS BY XCEL 1 #3/0CU TO XCEL ENERGY SUBSTATION (1#4/0, 1-1/4"C) TO GROUND RISER BUS 2 N 18 4 AUTHORITY MADE APPR'D DENVER PUBLIC SCHOOLS 2 SPARE 50/3 M 14 40/3 M 14 450/3 M 14 K-13 TRANSFORMER 75 KVA 480-208/120V 3PH, 4W. 250/3 TRANSFORMER 300 KVA 480-208/120V 3PH, 4W. DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DESIGNED BY: AW DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: UFER GROUND 1ST FLOOR 05/29/15 AS NOTED ELECTRICAL ONE-LINE DIAGRAM ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: DENVER, CO 9100 E. 56TH AVE. DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. COMMONS BUILDING MAIN DISTRIBUTION SWITCHBOARD "C1-MSB" 480/277V,3PH,4W 2000A BUS 65,000 AIC SCHOOL NO. 985 DWG. NO. 3-E0.01 SHEET: OF: 983_2478_985 _OR_ 3-E0.01 2 T 125/3 FA8 13 F17 T FA13B C1-L1 100/3 70/3 225/3 #3/0CU M 14 225/3 FA8 5 13 400A/3P 250A LPN-RK COMMONS 1ST FLOOR D #3/0CU G MAIN ROOM GROUND BUS GFI #6CU M G #3/0CU. TO TELE. ROOM GROUND RISER. 24"X3"X1/4" COPPER BUS BAR ON STAND-OFF INSULATORS M 14 100/3 TO XFMR 2000/3 4 1 12 5 FA22A FA9 TVSS VERIFY CT AND METERING REQUIREMENT WITH XCEL ENERGY C1-HM1 FA12 5 F5 FA12 K-13 TRANSFORMER 45 KVA 480-208/120V 3PH, 4W. G 10 T F5 TRANSFORMER 45 KVA 480-208/120V 3PH, 4W. T #6CU #3/0CU. TO GENERATOR GROUNDING ELECTRODE. C1-DIM FA9A FA9A 200/3 150A LPS-RK 2 (PERFORMANCE STAGE) C1-LM1 4 TEMPORARY GENERATOR CONNECTION XCEL PAD MOUNTED TRANSFORMER 225/3 SPARE PWR DIST "C1-RDS1" 1000 AMPS 208/120V, 3PH, 4W 42,0000 AIC C1-RIG 9 DOUBLE THROW 3-POLE MANUAL DISCONNECT 225A/4P 20 480/277V 65,000A NEMA 3R 3 7/14/2015 2:49:18 PM 21 100/3 21 FA12 C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt . 60/3 21 225/3 21 60/3 SPARE 225/3 SPARE 400/3 SPARE 225/3 SPARE 400/3 SPACE 21 F9 C1-EDS1 225 AMPS 480/277V, 3PH, 4W 65,0000 AIC 225/3 SPACE SPACE 100/3 60/3 30/3 50/3 M 14 SPACE 14 GENERAL NOTES TYPICAL CLASSROOM LCP WIRING B R WR-6161 Relay #4 R R WR-6161 Relay #6 R WR-6161 Relay #8 Class 1 - LINE VOLTAGE Class 2 - LOW VOLTAGE b.3 a.3 B b.4 a.4 WR-6161 Relay #1 Relays 1 - 4 to 4 Zones of Luminaires in Classroom #1. Relays 5-8 to 4 Zones of Luminaires in Classroom #2. a.2 B WR-6161 Relay #5 b.1 b.2 R WR-6161 Relay #3 WR-6161 Relay #7 WRD-3408 a.1 Data 24VAC B B WR-6161 Relay #2 B R B R A B A B A 24 V WR-6161 Relay #2 Dialog Relay Controller B R Typical Relay Panel 120/277 V WR-6161 Relay #1 CLASSROOM #2 120/277:24VAC Transformer 24 V 120/277 V Relays 1 - 4 to 4 Zones of Luminaires in Classroom #1. Relays 5-8 to 4 Zones of Luminaires in Classroom #2. Typical Relay Panel 120/277:24VAC Transformer Class 1 - LINE VOLTAGE CLASSROOM #1 Dialog Relay Controller B R R WR-6161 Relay #4 R a.2 B b.3 a.3 B WR-6161 Relay #5 R WR-6161 Relay #6 R WR-6161 Relay #7 R WR-6161 Relay #8 R To Next Panel Switches b.1 b.2 R WR-6161 Relay #3 b.4 a.4 Data 24VAC B B B B Panels From Previous Panel DATA SIGNAL B Sensors To Next Panel A B Switches A B Panels From Previous Panel DATA SIGNAL (1) Belden 8471 (1) #14 AWG Stranded U D (1) Belden 9729 2. REFER TO ONE-LINE DIAGRAMS, PANEL SCHEDULES, AND FLOOR PLANS FOR QUANTITY RELAYS AND DIMMING MODULES ON EACH PANELS. N (1) Belden 1583A 3. PROVIDE AND INSTALL SOFTWARE FOR CONTROL SYSTEM INTO BMS COMPUTER STATION. (by others) (Unison) (1) Belden 8471 (1) #14 AWG Stranded (2) #16 AWG Stranded UV 4. MASTER (PRIMARY) CONTROL PANEL SHALL BE PROVIDED WITH NETWORK CARD (ETHERNET). PROVIDE PATCH CORD BETWEEN PANEL TO NEAREST DATA OUTLET IN THE ELECTRICAL ROOM. 5. EACH EMERGENCY LIGHTING LOAD CONTROLLED BY THIS LIGHTING CONTROL SYSTEM SHALL BE ROUTED THROUGH A UL924 RATED DEVICE - UPON LOSS OF NORMAL POWER THESE LOADS SHALL RETURN TO "ON" VIA THE UL924 DEVICE ONCE EMERGENCY POWER IS PRESENT. PANEL BASE OR INDIVIDUAL DEVICE WOULD BE ACCEPTABLE. IF INDIVIDUAL DEVICE IS PROVIDED, PROVIDE ENCLOSURE AND GROUP MOUNT DEVICES IN THE ELECTRICAL ROOMS OR MECHANICAL CHASES. CLEAR IDENTIFICATION SHALL BE PROVIDED FOR EACH DEVICE. (by others) (Unison) Notes: 1.Total combined length of Belden 8471 wiring runs cannot exceed 1640 feet. 2. Total single run length of Belden 9729 wiring runs cannot exceed 1640 feet. MANUFACTURER SERVICES: AS PART OF THIS SCOPE CONTRACTOR SHALL CARRY THE SERVICES OF A FACTORY AUTHORIZED SERVICE TECHNICIAN TO ENERGIZE AND PROVIDE INITIAL SYSTEM CHECKOUT AND PROGRAMMING. AS PART OF THIS SERVICE THE TECHNICIAN SHALL BE AVAILABLE TO MEET THE LIGHTING DESIGNER ON SITE TO SET THE 4 BASIC HOUSE LIGHT SCENES AND DEMONSTRATE PROGRAMMING ATTRIBUTES OF THE LCD CONTROL STATION TO INCLUDE ELECTRONIC LOCKOUTS AND NETWORK LIGHTING CONTROL SYSTEM SWEEP OVER-RIDE. THE CONTRACTOR SHALL SECURE THE SERVICES OF A FACTORY AUTHORIZED SERVICE TECHNICIAN TO PERFORM UP TO 16 HOURS OF OWNER TRAINING OVER THE O & M OF THIS SYSTEM IN UP TO 4 VISITS OVER THE COURSE OF THE FIRST YEAR OF OWNER POSESSION. B A Sensors WRD-3408 a.1 B 1. REFER TO SHEET E0.04 FOR MORE INFORMATION ON ZONING, SWITCHING, SCHEDULES, AND INTENDED CONTROL SCHEME. CONTROL WIRING LEGEND DIMMING SYSTEM NOTES: BASIS OF DESIGN - ETC UNISON PARADIGM CONTROL SYSTEM - BASIS OF DESIGN IS THE MINIMAL ACCEPTABLE TECHNICAL AND PERFORMANCE CRITERIA FOR THE PROJECT CONTRACTOR TO PROVIDE A COMPLETE AND OPERATIONAL SYSTEM ALTHOUGH EVERY COMPONENT MAY NOT BE MENTIONED IN THIS DIAGRAM. MINIMUM ACCEPTABLE RATING FOR DIMMER PANEL MODULES IS 100% DUTY CYCLE AT OVER-CURRENT RATED AMPACITY - SYSTEMS REQUIRING DE-RATING ARE NOT ACCEPTABLE. CONTRACTOR SHALL UTILIZE #10 AWG LOAD WIRE FOR ALL STAGE DIMMER CIRCUIITS. THIS SYSTEM SHALL BE CONNECTED TO THE BUILDING DOUGLAS NETWORK LIGHTING CONTROL SYSTEM FOR MASTER OFF SWEEPS VIA DRY CONTACT CLOSURE. BASIS OF OPERATION IS LOCAL ON VIA LOCAL CONTROL DEVICES AND LOCAL OFF VIA LOCAL CONTROL DEVICES OR OFF SWEEP VIA BUILDING LIGHTING CONTROL SYSTEM. SYSTEM SHALL BE PROGRAMMED TO ALLOW OPERATOR TO OVER-RIDE BUILDING SWEEP ON SHOW DAYS. RETURN BUILDING SWEEP CONTROL AT 2AM EACH MORNING. SYSTEM SHALL BE PROGRAMMED TO ALLOW INDIVIDUAL LOCKOUT OF THE ENTRY STATION AND THE STAGE CONTROL STATION FROM THE LCD STATION DURING SHOWS. SYSTEM SHALL BE PROGRAMMED TO RETURN CONTROL TO LOCKED OUT STATIONS EACH MORNING AT 2AM. Class 2 - LOW VOLTAGE ART CLASSROOM REMOTE LCP WIRING DAYLIGHT SENSOR DAYLIGHT SENSOR DAYLIGHT SENSOR 8 8 8 6. CONTRACTOR TO FEED CONTROL TRANSFORMER IN EACH RELAY PANEL FROM NORMAL POWER. 7. WHERE CONTACT OUTPUTS ARE SHOWN TO DIMMING SYSTEMS PROVIDE LOW VOLTAGE DRY CONTACT OUTPUTS. LINE VOLTAGE CONTACTS ARE NOT ACCEPTABLE. IF THIS REQUIRES A LARGER RELAY PANEL CHASSIS, MANUFACTURER TO PROVIDE LARGER CHASSIS. STAGE DISTRIBUTION STRIPS SHALL BE SUPPLIED WITH SINGLE PIPE HANGER BRACKETS, 50' OF 1.5" ID (2" OD) SCHEDULE 40 BLACK STEEL PIPE PAINTED FLAT BLACK. ALL PIPE JUCTIONS SHALL UTILIZE A 4' DRIVE FIT INTERIOR SLEVE WITH (2) BOLTS OFFSET 90 DEGREES THROUGH EACH HALF OF JUNCTION (4 TOTAL). THE FINAL LOCATIONS OF THE DISTRIBUTION STRIPS AND THE INSTALLATION HEIGHT SHALL BE COORDINATED DURING SUBMITTAL WITH THE STAGE CURTAIN PACKAGE. CONTRACTOR SHALL INCLUDE ALL NECESSARY RIGGING HARDWARE TO LOCATE THE DISTRIBUTION STRIPS IN FINAL LOCATION. SEE SSRC WEBSITE FOR SINGLE PIPE HANGER BRACKET ACCESSORY WWW.SSRCONLINE.COM 8. PHOTOCELLS OR DAY LIGHT SENSORS SHALL PROVIDE AT MINIMUM 16 TRIP POINTS WHICH ARE SET THROUGH DESKTOP COMPUTER CONTROL SYSTEM. PHOTO CELLS REQUIRING TRIP POINTS TO BE SET MANUALLY AT AN INTERFACE CARD ARE NOT ACCEPTABLE. SYSTEM SHALL BE INTERFACED TO THE DOUGLAS LIGHTING CONTROL BUILDING LIGHTING CONTROL SYSTEM VIA (4) DRY CONTACT INTERFACES. PROGRAM ETC SYSTEM TO TRIGGER A PRESET WHEN EACH CONTACT INPUT IS TRIGGERED. ETC SYSTEM SHALL EXECUTE PRESET ON CONTACT CLOSURE, ETC SYSTEM SHALL NOT ACTION ON CONTACT OPENING. COORDINATE PROGRAMMING WITH DOUGLAS LIGHTING CONTROL TECHNICIAN. INPUT #1 SHALL TRIGGER WALK THROUGH PRESET #1 WITH ONLY TYPE B AND BB FIXTURES INPUT #2 SHALL TRIGGER SCENE #2 - COORDINATE SCENE WITH LIGHTING DESIGNER INPUT #3 SHALL TRIGGER SCENE #3 - COORDINATE SCENE WITH LIGHTING DESIGNER INPUT #4 SHALL TRIGGER OFF SWEEP WITH BLINK WARN FUNCTION LOW VOLTAGE DATALINE LOCAL OVERRIDE STATION "LVX-X" REFER TO SHEET 2-E0.11 LOW VOLTAGE DATALINE LOCAL OVERRIDE STATION "LVX-X" REFER TO SHEET 2-E0.11 DIGITAL 2-ZONE DIMMERS (TYP OF 2) LOW VOLTAGE DATALINE LOCAL OVERRIDE STATION "LVX-X" REFER TO SHEET 2-E0.11 9. EACH RELAY IN EACH PANEL SHALL HAVE A 14,000 AMP SHORT CIRCUIT CURRENT RATING TO COMPLY WITH LATEST EDITION OF NEC. 10. EACH RELAY SHALL HAVE A FULLY MANUAL OVER-RIDE CONTROL ON THE RELAY - FURNISH A MINIMUM 48 POLES PER PANEL. WHERE MORE RELAYS ARE REQUIRED - PROVIDE ADDITIONAL PANELS. 11. 48 POLE RELAY PANELS SHALL BE SURFACE OR FLUSH MOUNT AS REQUIRED WITH HINGED LOCKING DOOR. ETC SYSTEM WILL CONTROL TYPE L10 FIXTURES IN VESTIBULE VIA DMX - COORDINATE SUCH THAT VESTIBULE L10 FIXTURES CAN REMAIN ON DURING STAGE SHOWS. 12. MANUFACTURER TO PROVIDE ALL NECESSARY HARDWARE AND SERVICES TO PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM PER THIS ONE LINE AND SPECIFICATION. MANUFACTURER SHALL ASSUME MULTIPLE SITE VISITS TO COMPLETE COMMISSIONING, AND TRAINING PORTIONS OF THIS PROJECT. ADDRESS DMX CONTROLLED RELAYS AT DMX ADDRESS 480 - HOUSELIGHT RELAYS AND L10 DMX ADDRESSES TO BE AT END OF DMX STREAM - TO ALLOW DMX ADDRESSES 49 THROUGH 400 FOR FOR FUTURE STAGE LIGHTING FIXTURES. DOUGLAS RELAY PANEL TO BE SUPPLIED WITH DMX CONTROL CARD FOR HOUSELIGHT LOADS (MAX 24 RELAYS) IN ROOM 1-100 AND TYPE L10 IN ROOM 1-100A. ETC SYSTEM SHALL CONTROL THESE RELAYS. 13. BASIS OF LIGHTING CONTROL SYSTEM LAYOUT IS DOUGLAS LIGHTING CONTROL. ETC SYSTEM SHALL CONTROL TYPE B AND BB BY DAYLIGHT SENSOR - LIGHTING DESIGNER SHALL SPECIFY LIGHT LEVEL REQUIREMENTS FOR DAYLIGHT CONTROL. 14. REFER TO POWER PLANS FOR 120V POWER CIRCUITS THAT WOULD NEED TO BE CONTROLLED VIA THIS SYSTEM. CONNECT CIRCUIT TO NEAREST RELAY PANEL. 15. PROVIDE CONTACT CLOSURE INTERFACE TO TIE IN LIGHTING CONTROL RELAY SYSTEM TO DIMMING SYSTEM. BOTH SYSTEM SHALL UTILIZE A SINGLE TIME-CLOCK SETTING. CONTACT CLOSURE INTERFACE SHALL RECALL "SCENE 1" OF DIMMING SPACES. REFER TO NARRATIVE AND DRAWINGS FOR MORE INFORMATION ON DIMMING AREAS. EXTERIOR PHOTOSENSOR North Facing: 2 feet above snow line: Clear view of North Sky Vault N 16. PROVIDE A MINIMUM OF (4) TIME-CLOCK SETTINGS FOR INTERIOR LIGHTING AND (2) SETTINGS FOR EXTERIOR LIGHTING. 17. PROVIDE COMPLETE SHOP DRAWINGS INCLUDING ONE-LINE DIAGRAM, RELAY SCHEDULES, DIMMING PANEL SCHEDULES, SWITCHING SCHEDULES, SCENE SELECTOR BUTTON SCHEDULES, TIME-CLOCK SCHEDULES, PHOTOCELL SCHEDULES, AND FLOOR PLANS INDICATING RELAY PANELS, SWITCHES, AND SENSORS LOCATION. ROOF KEY NOTES 1 NOT USED 2 PROVIDE NEW 72-RELAY LIGHTING CONTROL PANEL. PROVIDE CONTROLLERS FOR 48-RELAY BY DOUGLAS SYSTEM FOR GENERAL BUILDING LIGHTING AND CONTROLLER FOR 24-RELAY FOR DMX CONTROL. PROVIDE BARRIER AS REQUIRED. 3 RS-485 DATA BUS WIRING TO BE BELDEN 9729 OR APPROVED EQUAL AS PER MANUFACTURER FOR NETWORK TIE INTO CAMPUS SYSTEM. UNISON PARADIGM INDOOR DAYLIGHT SENSOR 4 REFER TO LIGHTING CONTROL SWITCH SCHEDULES FOR QUANTITY OF BUTTONS REQUIRED AND ZONE ASSIGNMENT. REFER TO DRAWINGS FOR EXACT QUANTITY. PROVIDE A MINIMUM OF 4-BUTTON STATION WITH MASTER ON/OFF. 3 14 TO OTHER DEVICES AS REQUIRED 14 5 REFER TO PLAN DRAWINGS FOR OCCUPANCY SENSOR TYPES, LOCATIONS, AND QUANTITIES FOR MORE INFORMATION. 12 UL924 UV LOW VOLTAGE DATALINE OVERRIDE STATION "LV1-X" 6 6 PROVIDE UL924 RATED INTERFACE SO THAT EMERGENCY FIXTURES CAN BE CONTROLLED WITH NORMAL FIXTURES WITHIN THE SAME ZONE. DAYLIGHT SENSOR LCD TOUCHSCREEN CONTROLLER 12 MODULES LCD MONITOR 8 4 Line Voltage 3 12 MODULES 7 10 PRESET BUTTON CONTROLLER UL924 7 3 15 U BACnet/ MS/ TP 72 RELAYS DMX PLUG-IN STATION DMX 1 INPUT 9 DMX 1 INPUT D D RACK #1 RACK #2 DIMMING PANEL - "C1-DIM" 25' DMX CABLE CONTROL CONSOLE POWER FEED (RE: ONE-LINE DIAGRAM) 2 DOUGLAS GLOBAL SERVER 2 ETHERNET SWITCH DMX PLUG-IN STATION 9 6 Low Voltage MASTER PANEL LCP# C1-L1 3 Line Voltage 10 6 Panel LCP-# Low Voltage REMOTE LCP WITH 8 RELAYS CONTROLS TWO 8 PROVIDE INTERIOR DAYLIGHT SENSOR WITH MULTI-LEVEL LIGHT READING. TO OTHER DEVICES AS REQUIRED UV LCD MONITOR EQUIPMENT SHALL BE PROVIDED AS PART OF ELECTRICAL BID ALTERNATE #2 7 PROVIDE REMOTE UL924 RATED DEVICE FOR MULTI-ROOM CIRCUITS (LVS#EPC SERIES OR APPROVED EQUAL). LOW VOLTAGE DATALINE OVERRIDE STATION "LV1-X" 3 4 9 PROVIDE (1) 20A, 120V CIRCUIT TO RELAY PANELS FOR PANEL POWER. DAYLIGHT SENSOR 8 TO ELECTRIC CONNECTOR STRIPS AS SHOWN ON PLANS . . . . TO L10 SERIES FIXTURES 10 PROVIDE BID ALTERNATE #10: PROVIDE ADDITIONAL (1) 0-10V DIMMING BALLAST CONTROLLER CARD WITH (4) OUTPUTS FOR EACH CLASSROOM. LOCATE ADDITIONAL CARD WITHIN BASE BID REMOTE LIGHTING CONTROL ENCLOSURE. PROVIDE LARGER SIZE ENCLOSURE AS REQUIRED. 11 REFER TO PLAN DRAWINGS FOR EXACT LOCATION AND QUANTITY OF REMOTE LIGHTING CONTROL PANELS SERVING CLASSROOMS. PANEL SHALL BE LOCATED ABOVE CEILING WITHIN CLASSROOMS AND PLENUM RATED ENCLOSURE. TO NEXT REMOTE LCP 12 PROVIDE ELECTRICAL GUTTER AS REQUIRED FOR ROUTING CONTROL CIRCUITS. GUTTER SHALL HAVE A MINIMUM EQUAL DEPTH AS DIMMING PANELS. 13 11 DMX OPTO-SPLITTER (8 CHANNELS) 13 PROVIDE DMX CONTROLLER FOR LED COLOR CHANGING FIXTURES AND ALTERNATE LED THEATRICAL FIXTURES. LOCATE ABOVE DIMMING PANELS. 5 14 DIMMING CIRCUIT TO CONNECTOR STRIPS AS SHOWN ON PLANS. 15 PROVIDE DRY CONTACTS FOR A MINIMUM OF (4) SCENE RECALL FOR RELAY SYSTEM. TO NEXT BUILDING 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED LIGHTING CONTROL ONE-LINE DIAGRAM ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:19 PM AUTHORITY DWG. NO. 3-E0.02 SHEET: OF: 983_2478_985 _OR_ 3-E0.02 2 COMMONS C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt 1ST FLOOR GENERAL NOTES DENVER PUBLIC SCHOOL - STAPLETON NORTHFIELD CAMPUS 1. CONNECT ALL ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, TOP OF SHAFT AND ELEVATOR PIT SMOKE DETECTORS TO ELEVATOR CONTROLLER FOR ELEVATOR RECALL. PROVIDE SHUNT TRIP DEVICE TO DISCONNECT ALL ELEVATOR CONTROLLERS. VERIFY SHUNT TRIP LOCATION REQUIREMENTS WITH AHJ. PROVIDE A HEAT DETECTOR AT THE TOP OF ELEVATOR SHAFT AND WITHIN TWO FEET OF EACH SPRINKLER HEAD IN ALL ELEVATOR MACHINE ROOMS. ACTIVATION OF HEAT DETECTOR TO INITIATE SHUNT-TRIP. FIRE ALARM FUNCTIONAL MATRIX FIRE ALARM SYSTEM NOTES: 1. FIRE ALARM CONTRACTOR SHALL PROVIDE COMPLETE SYSTEM WIRING AND INSTALLATION DIAGRAMS. INITIATING DEVICE REPORT TO ACTIVATE AUXILLARY FUNCTIONS CLOSE STAIRWELL DOORS SMOKE DETECTORS X X X X X X X DROP OVERHEAD DOORS X RELEASE MAG HOLD DOORS X X ACTIVATE ELEV SHUNT TRIP OVERRIDE SECURED DOORS SHUT DOWN AHU/FCU - over 2kcfm TEST ACTIVATE IN-CAR NOTIFICATION X X RECALL ELEV NOTIFICATION APPLIANCES X X NOTICIFACTION CIRCUITS DIAL OUT TO MONITORING CO. ACTIVATE STAIR AND ELEVATOR X X ANNUN SUPERV AT FAAP X X ANNUN TRBLE AT FAAP X X ANNUN ALARM AT FAAP X MANUAL PULL STATION (IN FIRE CONTROL RM) ANNUNCIATE ALARM AT FACP ELEVATOR LOBBY SMOKE DETECTORS IN FRONT OF EACH ELEVATOR. (COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR TO INSTALLATION.) SMOKE DETECTION TO MEET CITY OF DENVER REQUIREMENTS. HEAT AND SMOKE DETECTION IN EACH ELEVATOR MACHINE ROOM. ASSUME (6) HEAT DETECTORS PER MACHINE ROOM. MANUAL PULL STATIONS THROUGHOUT AS REQUIRED BY THE CITY OF DENVER. AREAS SHALL HAVE AUDIBLE AND VISUAL ANNUNCIATION. SMOKE AND HEAT DETECTION AT THE TOP AND BOTTOM OF ALL ELEVATOR SHAFTS. SMOKE DETECTORS AND DUCT DETECTORS AT EACH FIRE/SMOKE DAMPER. REFER TO MECHANICAL/PLUMBING AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION. CONNECTION OF ALL FIRE SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES. FULL SMOKE DETECTOR COVERAGE IN ALL CLASSROOMS. VERIFY INSTALLATION OF CEILING MOUNTED STROBES WITHIN EACH SPACE. PROVIDE INTERCONNECTION TO PUBLIC ADDRESS SYSTEM FOR VOICE OVERRIDE. 2. PROVIDE #18 AWG MINIMUM WIRING FOR ALL SIGNAL AND INITIATION DEVICES. WATER FLOW PROVIDE A COMPLETE CLASS B FIRE ALARM SYSTEM COMPLIANT WITH NFPA, CITY OF DENVER AND DENVER FIRE DEPARTMENT REQUIREMENTS INCLUDING BUT NOT LIMITED TO: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. ANNUN SUPERVISORY AT FACP 3. COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR ALL INTERFACE REQUIREMENTS WITH PRE-ACTION SYSTEMS AND FLOW AND TAMPER SWITCHES (LOCATIONS / QUANTITIES) ANNUNCIATE TROUBLE AT FACP 2. PROVIDE COMPLETE BATTERY AND POWER SUPPLY CALCULATIONS. 3. ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR AND PARALLEL TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO THE OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO LACK OF COORDINATION WITH THE ARCHITECT. 4. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS OTHERWISE NOTED. CONTRACTOR SHALL COORDINATE INSTALLATION OF CONDUIT AND BACK BOXES IN POURED CONCRETE, PRE-CAST CONCRETE, MASONRY AND GYP. WALLS. COMMONS - FIRST FLOOR 5. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT QUANTITY AND LOCATIONS OF ALL FIRE SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES WITH CONSTRUCTION MANAGER AND FIRE PROTECTION PRIOR TO BID. CONNECT ALL TAMPER AND FLOW SWITCHES TO FIRE ALARM SYSTEM. COMMON INPUTS REMOTE LED, TYPICAL ELEVATOR RM AREA SMOKE DETECTOR X X X X X X ELEVATOR RM HEAT DETECTOR X X X X X X ELEV LOBBY SMOKE DETECTOR X X X X X X ELEV - SHUNT TRIP POWER DICONNECTED X X X X X X ZONE TAMPER SWITCH X X X X DRY & PREACTION SYS LOW AIR X X X X DRY & PREACTION SYS HIGH AIR X X X X X X X X X AHU DUCT DETECTOR INTERLOCK DUCT DETECTOR WITH AIR HANDLER UNIT STARTER FOR AUTOMATIC SHUTDOWN TYPICAL. X X X 6. CONTRACTOR SHALL COORDINATE EXACT LOCATION AND QUANTITY OF ALL DUCT TYPE SMOKE DETECTORS WITH MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL HARD WIRE TO RELAY STARTER. X 7. PROVIDE (1) DUCT TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR HANDLING UNIT, SUPPLY FAN, AND HEAT PUMP OF 2,000 CFM AND GREATER. PROVIDE (2) DUCT TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR HANDLING UNIT, HEAT PUMP AND SUPPLY FAN OF 15,000 CFM AND GREATER. X MISCELLANEOUS INPUTS ROOF ROOF MAIN WATER FLOW X X X MAIN SUPPLY TAMPER SWITCH X X X FACP CIRCUIT TROUBLE X X X FACP POWER LOSS X X X FACP LOW BATTERY X X X NAC CIRCUIT TROUBLE X X X NAC POWER LOSS X X X NAC LOW BATTERY X X FIRE DOOR SMOKE DETECTOR X X X 8. PROVIDE CONNECTION OF FA SYSTEMS TO ALL MAGNETIC DOOR HOLD-OPEN DEVICES TO AUTOMATICALLY CLOSE DOORS (INCLUDING OVERHEAD STORAGE DOORS) DURING ALARM CONDITIONS. X X X X 9. DEVICES INDICATED ON FIRE ALARM ONE-LINE ARE FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS AND SPECIFICATIONS FOR QUANTITIES. REFER TO ARCHITECTURAL DOOR SCHEDULE FOR MAGNETIC DOOR HOLDER REQUIREMENTS. X NOTE: WHERE THERE ARE AREA SMOKE DETECTORS FOR THE CLOSING OF FIRE RATED DOORS, REMOVAL OF SMOKE DETECTOR FROM BASE 10. PROVIDE DUCT DETECTOR AND FIRE ALARM RELAY MODULE FOR EVERY FIRE-SMOKE DAMPER. LOCATE DUCT DETECTOR WITHIN FIVE FEET OF FIRE-SMOKE DETECTOR. WILL ACTIVATE THE DOOR RELEASE. FOR AUXILLARY FUNCTIONS REQUIRING THE RELAEASE, DROPPING, OR OVERRIDING OF SECURITY DOORS, IT IS INTENDEND TO BE FOR DOORS 11. ALL VISUAL DEVICES SHALL BE SYNCHRONIZED. ON THE EMERGENCY EGRESS PATH ONLY. 2 KEY NOTES 1 PROVIDE A DEDICATED CIRCUIT TO EACH TRANSPONDER, NETWORK OR NAC PANEL AS REQUIRED. 2 PROVIDE UDACT FOR CAMPUS COMMUNICATION SYSTEM WITH NETWORK CONNECTION, AS WELL AS ANALOG LINE AND FIBER OPTIC FOR BACK-UP. 3 PROVIDE SUSTAINABLE 2-HR FIRE RATED CABLE BETWEEN EACH TRANSPONDER, NETWORK PANEL, FAAP OR FACP PER NFPA 72. SPEAKER STROBE TYPICAL REMOTE LED, TYPICAL VERIFY QUANTITY AND LOCATION WITH FIRE SPRINKLER CONTRACTOR (TYP.) INTERLOCK DUCT DETECTOR WITH AIR HANDLER UNIT STARTER FOR AUTOMATIC SHUTDOWN TYPICAL. DH DH DH 4 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS SHALL BE PROVIDED AND DESIGNED ACCORDING TO DENVER AMENDMENTS TO IFC, SECTION 907.6.2.2. DH MAGNETIC DOOR HOLD (TYPICAL) ELEVATOR LOBBY SMOKE DETECTORS CONNECT TO ELEVATOR RECALL STROBE TYPICAL MANUAL PULL STATIONS FIRE SMOKE DAMPER WITH SMOKE DETECTOR, TYPICAL IM IM 2 5 CITY OF DENVER APPROVED GRAPHIC MAP. 6 PROVIDE NETWORK TIE IN TO OTHER FACP PANELS ON ON CAMPUS. 7 FIRE ALARM CONTROL PANEL SHALL BE PROVIDED WITH PROVISION FOR FUTURE EXPANSION OF CLASSROOMS, OFFICE AREAS, AND COOKING KITCHEN. CONNECT TO DAMPERS ASSOCIATED WITH THE SMOKE CONTROL SYSTEM, BUILDING MANAGEMENT SYSTEM, STAIR DOORS, ETC. THIS CONTRACTOR TO PROVIDE QUANTITIES NECESSARY FOR A COMPLETE WORKING SYSTEM NETWORK FIRE ALARM MASTER CONTROL PANEL VOICE COMMUNICATION CENTER TIE INTO PUBLIC ADDRESS SYSTEM, SOUND SYSTEMS, & SECURITY SYSTEM. PROVIDE INPUT MODULES EMER CKT 1 GRAPHIC MAP 5 80 CHARACTER LCD READOUT FAAP 7 2 DIRECT TELEPHONE COMMUNICATION TO A LISTED CENTRAL MONITORING STATION. MANUAL PULL STATION 6 FIRST FLOOR 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED FIRE ALARM ONE-LINE DIAGRAM ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:19 PM AUTHORITY DWG. NO. 3-E0.03 SHEET: OF: 983_2478_985 _OR_ 3-E0.03 2 COMMONS C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt FIRST FLOOR NOTES: PANEL: BUS: PROVIDE FUSED CIRCUIT BREAKERS PANELBOARD SECTION: LOCATION: OPTIONS: DATE: FED FROM : MOUNTING : C1-EL1 STAPLETON NORTHFIELD - COMMONS 1 OF 1 MAIN ELEC RM 1-124A 208Y/120 3PHASE,4WIRE+GND 10K AIC 05/29/15 C1-EDS1 SURFACE M-E Engineers Inc. 225 Amps M.L.O. MAINS: PANEL: BUS: NOTES: COPPER SECTION: LOCATION: OPTIONS: DATE: FED FROM : MOUNTING : ID DESCRIPTION V-A P BKR CKT PH CKT BKR P V-A DESCRIPTION ID L L L P P P P P P P P P P P P P P P P P L NORTH EM LIGHTING SOUTH VEST EM LIGHTING ELECTRICAL AND IDF LIGHTING --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-EXTERIOR LIGHTS 832 1 20 1 A 2 20 1 245 410 1 20 3 B 4 20 1 2352 512 1 20 5 C 6 20 1 294 1 20 7 A 8 20 1 1 20 9 B 10 20 1 1 20 11 C 12 20 1 1 20 13 A 14 20 1 1 20 15 B 16 20 1 1 20 17 C 18 20 1 1 20 19 A 20 20 1 1 20 21 B 22 20 1 1 20 23 C 24 20 1 1 20 25 A 26 20 1 1 20 27 B 28 20 1 1 20 29 C 30 20 1 1 20 31 A 32 20 1 1 20 33 B 34 20 1 1 20 35 C 36 20 1 1 20 37 A 38 20 1 1 20 39 B 40 20 1 1 20 41 C 42 20 1 CORRIDOR AND VESTIBULE LIGHTING SEATING AREA RESTROOM LIGHTING --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-EXIT SIGNS L L L P P P P P P P P P P P P P P P P P L 420 300 N N COMMONS PANEL SCHEDULES.xls LOAD SUMMARY WITH DOWNSTREAM LOADS INCLUDED CONNECTED (DOWNSTREAM LOADS INCLUDED) PHASE VA C AMPS DOWNSTREAM LOADS A-B-C TOTALS CATEGORY CONNECTED 1077 - 2762 - 1526 4 - 10 - 6 5,365 6 LIGHTING 5,365 FACTOR 125% RECEPT 100% RECEPT 50% MOTOR 100% LRGST MTR CONDUCTOR COLORS (EC TO LABEL IN PANEL) PH A B C N G BROWN ORANGE YELLOW WH/GRAY STRIPE GREEN CALC'D V-A AMPS @ 480Y/277 VOLTS 6,706 8 100% KITCHEN 100% ELEC HEAT 100% CKT PH CKT BKR P V-A DESCRIPTION ID K K K K K K K K K K P K K K K K P K K K K K K K K K K W7 - MOBILE SALAD W34 - REACH-IN FREEZER W28 - WORK TABLE WITH SINK W28 - WORK TABLE WITH SINK W23 - HEAT/HOLDING CABINET --------W7 - MOBILE SALAD W21 - ROLL-THRU REFRIGERATOR W21 - ROLL-THRU REFRIGERATOR --SPARE-W2 - COLD PAN SERVING CNTR W3 - HOT FOOD SERVING CNTR W23 - HEAT/HOLDING CABINET ----------SPARE-W17 - ROLL-THRU HEATED CABINET ----W17 - ROLL-THRU HEATED CABINET ----W3 - HOT FOOD SERVING CNTR W2 - COLD PAN SERVING CNTR W8 - MOBILE MILK COOLER W8 - MOBILE MILK COOLER W10 - POS STATION W10 - POS STATION 576 1 20 1 A 2 15 2 750 1044 1 20 3 B 4 > 750 2400 1 20 5 C 6 20 1 2400 1 20 7 A 8 20 1 6000 3 50 9 B 10 20 1 6000 < 11 C 12 20 1 6000 < 13 A 14 20 1 720 576 1 20 15 B 16 20 1 540 2000 1 20 17 C 18 20 1 2000 1 20 19 A 20 20 1 1 20 21 B 22 20 1 576 1 20 23 C 24 20 1 3000 1 50 25 A 26 20 1 6000 3 50 27 B 28 20 1 6000 < 29 C 30 20 1 6000 < 31 A 32 20 1 W37 - ICE MAKER WITH BIN & FILTER ------SPARE---SPARE---SPARE---SPARE-KITCHEN RECEPT KITCHEN RECEPT --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-- K K P P P P K K P P P P P P P P P P P P P P P P P P P PHASE VA C AMPS DOWNSTREAM LOADS 33 B 34 20 1 1000 2 20 35 C 36 20 1 1000 < 37 A 38 20 1 1000 2 39 B 40 20 1 1000 < 41 C 42 20 1 3000 1 20 43 A 44 20 1 576 1 20 45 B 46 20 1 816 1 20 47 C 48 20 1 20 816 1 20 49 A 50 20 1 1800 1 20 51 B 52 20 1 1800 1 20 53 C 54 20 1 A-B-C CATEGORY 26262 - 18286 - 21592 219 - 152 - 180 66,140 184 LIGHTING 125% RECEPT 100% RECEPT 50% MOTOR 100% CONDUCTOR COLORS (EC TO LABEL IN PANEL) 480Y/277 3PHASE,4WIRE+GND 35K AIC NOTES: PANEL: COPPER SECTION: LOCATION: OPTIONS: DATE: FED FROM : MOUNTING : A B C N G 66,140 STAPLETON NORTHFIELD - COMMONS 1 OF 1 MAIN ELEC RM 1-124A 208Y/120 3PHASE,4WIRE+GND 10K AIC 119 CKT PH CKT BKR P V-A DESCRIPTION ID L L L L P L L L P P P P P P P P P P P P P THEATER ST, WATER ENTRY LTG MORNING PANTRY LTG SERVING LTG SEATING AND UP LIGHTS --SPARE-SEATING CORRIDOR LTG LAUNDRY, CUST, SECURITY LTG SITE LIGHTING --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-- 540 1 20 1 A 2 20 1 624 1024 1 20 3 B 4 20 1 768 468 1 20 5 C 6 20 1 291 PLATFORM CIRCULATION 110 LTG PERFOMANCE PLTFRM LTG CORRIDOR AND VESTIBULE LTG SOUTH 'VESTIBULE/ CANOPY LTG RESTROOM LTG SEATING BUBBLE LTG TABLE AND CHAIR STRG LTG --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-- L L L L L L L P P P P P P P P P P P P P P 1 20 7 A 8 20 1 349 1 20 9 B 10 20 1 640 672 1 20 11 C 12 20 1 624 1280 1 20 13 A 14 20 1 576 1117 1 20 15 B 16 20 1 1 20 17 C 18 20 1 1 20 19 A 20 20 1 1 20 21 B 22 20 1 1 20 23 C 24 20 1 1 20 25 A 26 20 1 1 20 27 B 28 20 1 1 20 29 C 30 20 1 1 20 31 A 32 20 1 1 20 33 B 34 20 1 1 20 35 C 36 20 1 1 20 37 A 38 20 1 1 20 39 B 40 20 1 1 20 41 C 42 20 1 N N 2 2 2 2 COMMONS PANEL SCHEDULES.xls VA C AMPS DOWNSTREAM LOADS LOAD SUMMARY WITH DOWNSTREAM LOADS INCLUDED CATEGORY CONNECTED 4805 - 3549 - 2055 17 - 13 - 7 10,409 13 LIGHTING 10,409 CONDUCTOR COLORS (EC TO LABEL IN PANEL) A B C N G BROWN ORANGE YELLOW WH/GRAY STRIPE GREEN 125% RECEPT 100% RECEPT 50% MOTOR 100% LRGST MTR PH FACTOR CALC'D V-A AMPS @ 480Y/277 VOLTS 13,011 16 25% MISC 100% KITCHEN 100% ELEC HEAT 100% 66,140 42,991 119 M-E Engineers Inc. 225 Amps COPPER 150 AMP MAIN BKR MAINS: PANEL: SECTION: LOCATION: OPTIONS: DATE: ID DESCRIPTION V-A P BKR CKT PH CKT BKR P M M M M M M M P M M M M M M M M P P M M M P P P P P P P M P DWH-1 DWH-2 DWH-3 TF C1.02 UH C1.02 FCU C 1.01 ------SPARE-STF C1.01 STF C1.02 EF C2.01 SSAC C1.01 ----EF-C1.03 AND EF-C1.04 ACCU C2.01 ------SPARE---SPARE-EF C1.01/EF C1.02 ACCU C2.02 ------SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-TF C1.01 --SPARE-- 1080 1 20 1 A 2 20 1 1080 1 20 3 B 4 20 1 1080 1 20 5 C 6 20 1 180 1 20 7 A 8 20 1 460 1 30 9 B 10 20 1 3640 2 55 11 C 12 20 1 3640 < 13 A 14 20 1 10,409 1 20 15 B 16 20 1 1500 1 30 17 C 18 20 1 1500 1 30 19 A 20 20 1 450 1 20 21 B 22 20 1 1560 2 20 23 C 24 20 1 1560 < 25 A 26 20 1 100 1 20 27 B 28 20 1 3640 2 55 29 C 30 20 1 3640 < 31 A 32 20 1 1 20 33 B 34 20 1 1 20 35 C 36 20 1 100 1 20 37 A 38 20 1 1560 2 20 39 B 40 20 1 1560 < 41 C 42 20 1 43 A 44 20 1 1 45 B 46 20 1 1 47 C 48 20 1 1 49 A 50 20 3 1 51 B 52 1 53 C 54 1 55 A 56 57 B 58 > 59 C 60 > 1 1 180 20 20 1 CONNECTED (DOWNSTREAM LOADS INCLUDED) V-A > > 20 3 PH CKT BKR P V-A DESCRIPTION ID E E E E E E E E E P P P P P P P P P S S S UH-C1.01 --------UH-C1.02 --------UH-C1.03 ----------SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-C1-LM1 --------- 1666 3 20 1 A 2 30 3 1666 1666 < 3 B 4 > 1666 1666 < 5 C 6 > 1666 1666 3 7 A 8 3 1666 1666 < 9 B 10 > 1666 1666 < 11 C 12 > 1666 1666 3 13 A 14 3 3500 1666 < 15 B 16 > 3500 1666 < 17 C 18 > 3500 3 3333 CUH C1.01 --------CUH C1.02 --------CUH C1.03 --------CUH C1.04 --------SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE SPACE M M M M M M M M M M M M C C C C C C C C C 20 20 30 30 1 20 19 A 20 1 20 21 B 22 > 3333 1 20 23 C 24 > 3333 1 20 25 A 26 1 20 27 B 28 1 20 29 C 30 1 20 31 A 32 1 20 33 B 34 1 20 35 C 36 6129 3 70 37 A 38 7442 < 39 B 40 8657 < 41 C 42 30 13,011 16 VA C AMPS DOWNSTREAM LOADS PH PHASE VA C AMPS DOWNSTREAM LOADS LOAD SUMMARY WITH DOWNSTREAM LOADS INCLUDED A-B-C TOTALS CATEGORY 21292 - 22605 - 23820 77 - 82 - 86 67,717 81 LIGHTING 125% RECEPT 100% ^ C1-LM1 CONNECTED RECEPT BROWN ORANGE YELLOW WH/GRAY STRIPE GREEN CALC'D V-A AMPS @ 480Y/277 VOLTS 50% MOTOR 52,723 100% 52,723 63 LRGST MTR 10,500 25% 2,625 3 14,994 18 70,342 85 MISC A B C N G FACTOR 100% 100% ELEC HEAT 14,994 TOTAL 67,717 100% C1-LM1 1 OF 1 ELECT ROOM 1-124A 07/08/15 C1-HM1 SURFACE DESCRIPTION ID --SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE---SPARE-----------SPARE---------- P P P P P P P P P P P P P P P P P P P P P P P P P P P P P P N A B C N G BLACK RED BLUE WHITE GREEN CALC'D V-A AMPS @ 208Y/120 VOLTS 100% 28,510 79 25% 1,820 5 30,330 84 TOTALS CATEGORY 11700 - 3830 - 12980 98 - 32 - 108 28,510 79 LIGHTING 125% RECEPT 100% CONNECTED RECEPT FACTOR 50% MOTOR 28,510 LRGST MTR 7,280 MISC 100% KITCHEN 100% ELEC HEAT 100% TOTAL 28,510 2 C1-EL1 C1-FS1 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION C1-HM1 This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. C1-LM1 MADE APPR'D DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture C1-L1 AUTHORITY DENVER PUBLIC SCHOOLS SCHOOL DISTRICT NO. 1 Designer DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: DENVER, CO 05/29/15 AS NOTED ELECTRICAL PANEL SCHEDULES ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 9100 E. 56TH AVE. DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:20 PM N LOAD SUMMARY WITH DOWNSTREAM LOADS INCLUDED A-B-C CONDUCTOR COLORS (EC TO LABEL IN PANEL) C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt CKT COMMONS PANEL SCHEDULES.xls PHASE TOTAL BKR ISSUE: BKR TOTALS P 100% MOUNTING : P A-B-C V-A AMPS @ 208Y/120 VOLTS 42,991 FED FROM : V-A PHASE DESCRIPTION CONNECTED (DOWNSTREAM LOADS INCLUDED) PH BUS: NOTES: 05/28/15 C1-MSB SURFACE DESCRIPTION CONNECTED (DOWNSTREAM LOADS INCLUDED) ID KITCHEN 65% 05/29/15 C1-MSB SURFACE DATE: COMMONS PANEL SCHEDULES.xls 25% TOTAL C1-L1 ID 1436 N CONDUCTOR COLORS (EC TO LABEL IN PANEL) ISSUE: N N 100% ELEC HEAT BLACK RED BLUE WHITE GREEN CALC'D V-A FACTOR CONNECTED MISC PH M-E Engineers Inc. 100 Amps BUS: M.L.O. MAINS: OPTIONS: LOAD SUMMARY WITH DOWNSTREAM LOADS INCLUDED TOTALS 8 6,706 LOCATION: ISSUE: BKR 20 1 OF 1 MAIN ELEC RM 1-124A SECTION: MOUNTING : P 1 C1-HM1 PANEL: COPPER FED FROM : V-A CONNECTED (DOWNSTREAM LOADS INCLUDED) 5,365 M-E Engineers Inc. 225 Amps M.L.O. MAINS: BUS: NOTES: DESCRIPTION KITCHEN STAPLETON NORTHFIELD - COMMONS 05/28/15 C1-RDS1 RECESSED ID LRGST MTR TOTAL 480Y/277 3PHASE,4WIRE+GND 42K AIC COMMONS PANEL SCHEDULES.xls 25% MISC STAPLETON NORTHFIELD - COMMONS 1 OF 1 KITCHEN 1-108 ISSUE: ISSUE: N C1-FS1 DWG. NO. 3-E0.05 SHEET: OF: 983_2478_985 _OR_ 3-E0.05 M-E Engineers Inc. 100 Amps COPPER 60 AMP MAIN BKR MAINS: 480Y/277 3PHASE,4WIRE+GND 18K AIC COMMONS STAPLETON NORTHFIELD - COMMONS GENERAL NOTES: 1. REFER TO SPECIFICATION APPENDIX A FOR "LIGHTING FIXTURE CUTS". 2. MOUNTING HEIGHTS INDICATED ARE TYPICAL MOUNTING HEIGHTS. REFER TO LIGHTING PLAN DRAWINGS FOR ATYPICAL MOUNTING HEIGHTS. 3. ALTERNATE MANUFACTURERS LISTED SHALL PROVIDE LUMINAIRE PHOTOMETRY AND FOOT-CANDLE CALCULATIONS TO VERIFY CONSISTENT ILLUMINATION LEVELS. 4. CONTRACTOR SHALL AIM ALL ADJUSTABLE FIXTURES WITH ARCHITECT AND ENGINEER PRIOR TO JOB CLOSE OUT. 5. ALL MANUFACTURERS SHALL PROVIDE LUMINAIRE PHOTOMETRY AND/OR FOOT-CANDLE CALCULATIONS UPON REQUEST FOR ANY AREA. MANUFACTURER SHALL COORDINATE WITH ENGINEER TYPICAL AREAS OF ANALYSIS, ROOM CHARACTERISTICS, AND ALL ASSUMPTIONS FOR CALCULATIONS. 6. TANDEM WIRING MAY BE UTILIZED FOR FIXTURES WHICH: A. OFFER TANDEM WIRING AS A STANDARD OPTION AND ARE UL LISTED FOR THAT APPLICATION. B. ARE LOCATED ON LIGHTING PLANS AS END TO END MOUNT. 7. ALL FIXTURE FINISHES AND PAINT COLORS ARE TO BE VERIFIED WITH ARCHITECT. CC: CUSTOM COLOR. 8. FIELD VERIFY EXACT FIXTURE LENGTHS FOR CONTINUOUS ILLUMINATION FOR COVES AND LINEAR RUNS. PROVIDE CONTINUOUS ILLUMINATION WITH NO MORE THAN A 6" GAP BETWEEN THE END OF THE EDGE OF THE WALL AND THE FIXTURE. LIGHTING FIXTURE SCHEDULE Finish Mounting Voltage Manufacturer QUARTZ T1 PIPE MOUNTED THEATRICAL LIGHT, DIE CAST ALUMINUM HOUSING, ANTI VIBRATION SHOCK MOUNTS, INTERCHANGEABLE LENS, THERMALLY INSULATED (1) 575 W HPL, 7300 LUMENS, 3000K WHITE PIPE 120 V ETC T2 PIPE MOUNTED THEATRICAL LIGHT, DIE CAST ALUMINUM HOUSING, ANTI VIBRATION SHOCK MOUNTS, INTERCHANGEABLE LENS, THERMALLY INSULATED (1) 575 W HPL, 9600 LUMENS, 3000K WHITE PIPE 120 V ETC T3 ALTERNATE FOR T1 - LED PIPE MOUNTED THEATER LIGHT, DIE CAST ALL METAL HOUSING, SLOT FOR GLASS OR LENS PATTERNS, C-CLAMP, IP20 RATED 111W, 5309 LUMENS, CRI 86, 3200K BLACK PIPE 120 V ETC Model Alt 1 436J-C-450JL-436JL-426JL-400CC-400SC-400 ALTMAN JRS-400CF-400PH-M LIGHTING PHEONIX PAR-EA-C-407CF-400SC-400CC-400-LS4-400 ALTMAN PTH6-400BD LIGHTING PAR 64 BID ALTERNATE #2A - ETC BID #S4LEDS2LSS-0-DPA-C-S4LED-SFD-436EDL ALTERNATE T-1-400CC-400SC-400PH-A-400RS-400CF #2B - ALTMAN LIGHTING 6-CFB-510-SC36-BK-10-CFB510-HD-435-SN -PHC-PH T4 ALTERNATE FOR T2 - LED PIPE MOUNTED THEATER LIGHT, DIE CAST ALL METAL HOUSING, IP20 RATED 101W, 2705 LUMENS, CRI 87, 3200K BLACK PIPE 120 V ETC BID ALTERNATE #2C - ETC #SELD40VI, DPA-C,SELD40FSY-400BD-411PTH6-400CC400SC LED L1 EXTERIOR WALL SCONCE, TYPE 4 DISTRIBUTION, DOOR FRAME TO EXCLUDE DUST, INSECTS AND POLLUTANTS, IP66 RATED 35W LED, 3904 LUMENS, 4000K, 150000 HRS BLACK WALL 277 V GARDCO 101L-4-55LA-NW-UNIV L2 12' PED LIGHT FOR SIDEWALK ILLUMINATION, DIRECT HEAD TOWARDS EXPOSED SIDEWALK, TYPE 3 DISTRIBUTION BLACK POLE 277 V GARDCO L3 25' TOTAL HEIGHT LED POLE TOP FIXTURE, 3' CONCRETE BASE WITH A 22' POLE, PARKING LOT AND ROADWAY LIGHTING, SINGLE HEAD FORWARD ILLUMINANCE BLACK POLE 277 V GARDCO L3A SIMILAR TO L3 EXCEPT TWO HEADS MOUNTED ON POLE AT 180 DEGREES BLACK POLE 277 V GARDCO L4 42" LED BOLLARD, BEVEL TOP, 360 DEGREE LIGHT COVERAGE LED ARRAY, NEUTRAL WHITE, TYPE 3 DISTRIBUTION, 4000K, 70CRI, 86 WATTS, 350mA DRIVE CURRENT, 7143 LUMENS LED ARRAY, NEUTRAL WHITE, TYPE 3 DISTRIBUTION, 200 WATTS, 4000K, 70 CRI, 530mA DRIVE CURRENT, 15529 LUMENS LED ARRAY, NEUTRAL WHITE, TYPE 3 DISTRIBUTION, 200 WATTS, 4000K, 70 CRI, 530mA DRIVE CURRENT, 15529 LUMENS LED ARRAY, NEUTRAL WHITE, 41 WATTS, 250mA DRIVER, 4000K, 75 CRI BLACK SURFACE 277 V GARDCO GL13-1-3-85LA-NW-UNIV-XX-RPA2, POLE #SRS-14-4-D1-XX-MOD GL18-1-3-200LA-NW-UNIV-XX-RPA2, POLE #SRS-25-5-D1-XX-MOD GL18-2-3-200LA-CW-UNIV-XX-RPA2, POLE #SRS-25-5-D2-XX-MOD BRM836-42-CWL-NW-360-UNIV L5 LED 6" DOWNLIGHT, 50 DEGREE CUTOFF REFLECTOR CONE, CLEAR REFLECTOR FINISH 39W LED, 2000 LUMENS, 4000K, 60000 HRS WHITE RECESSED 277 V LIGHTOLIER L8 IN GROUND UPLIGHT, ASYMMETRIC DISTRIBUTION ON EXTERIOR WALL, FLUSH WITH GROUND, SSTAINLESS STEEL BODY, PROVIDE WATERPROOF POWER SUPPLY BOX 50.6W LED, 3831 LUMENS, 4000K, 50000 HRS WHITE IN GRADE 277 V BEGA C6X6L1520-DL-40K-CL-W, FRAME-IN KIT #C6X6L20-N-120/277 7647LED L10 63" DIAMETER, ROUND METAL HOUSING, OPAL POLYCARBONATE DIFFUSERS, COORDIANTE COLORS OF LED WITH ARCHITECT 156W LED, RGB VERIFY WITH ARCHITECT SUSPENDED 277 V BETA CALCO D15SD165AE-BCDMX18/IN-MEC2112AE L10A 31.5" DIAMETER, ROUND METAL HOUSING, OPAL POLYCARBONATE DIFFUSERS, COORDIANTE COLORS OF LED WITH ARCHITECT 80W LED, RGB VERIFY WITH ARCHITECT SUSPENDED 277 V BETA CALCO L10B 17.3" DIAMETER, ROUND METAL HOUSING, OPAL POLYCARBONATE DIFFUSERS, COORDIANTE COLORS OF LED WITH ARCHITECT 45W LED, RGB VERIFY WITH ARCHITECT SUSPENDED 277 V BETA CALCO L20 RECESSED LIENAR SLOT LED WITH 4" APERATURE, FLUSH WITH CEILING, CONTINOUS OR STNADARD LENGTHS PER PLANS, EXTRUDED ALUMINUM HOUSING LED ARRAY, 400 LUMENS/FT, 4W/FT, 4000K, 25000 HOURS WHITE RECESSED 277 V FLUORESCENT F1 INDUSTRIAL STRIPLIGHT, PENDANT OR SURFACE MOUNT, 4' OR 8' LENGTHS PER PLAN DRAWINGS, PROVIDE WIREGUARD (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION WHITE F2B RECESSED LENSED 2X4 TROFFER, HIGH PERFORMANCE, ACRYLIC DIFFUSER, PROVIDE MOUNTING HARDWARE FOR GYP OR ACT CEILINGS AS REQUIRED, PROVIDE MULTIPLE BALLASTS FOR DUAL LEVEL SWITCHING RECESSED LINEAR SLOT LIGHT WITH 4" APERTAURE, FLUSH WITH CEILING, CONTINUOUS OR STANDARD LENGTHS PER PLAN DRAWINGS, EXTRUDED ALUMINUM HOUSING, LENS FLUSH WITH CEILING, PROVIDE MOUNTING HARDWARE FOR GYP OR ACT CEILINGS AS REQUIRED (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION F4D F4H F7 Alt 2 Control PRE-APPROVED DIMMING EQUAL SEATING AREA PRE-APPROVED DIMMING EQUAL SEATING AREA DIMMING SEATING AREA 9. FIXTURES REQUIRING PENDANT MOUNTING SHALL BE PENDANT MOUNTED WITH THE APPROVED MANUFACTURER'S SWIVEL STEM HANGER, CEILING SPACER, OR UNISTRUT. PENDANTS WITH A LENGTH GREATER THAN 18" SHALL ACCOMODATE A SWIVEL BASE. 10. PROVIDE SAFETY CABLE FROM FIXTURE TIED TO STRUCTURE FOR ALL PENDANT FIXTURES IN PUBLIC AREAS. 11. ALL ACRYLIC LENSES SHALL HAVE A MINIMUM THICKNESS OF 0.125" UNLESS OTHERWISE NOTED. 12. ALL FLUORESCENT AND METAL HALIDE BALLASTS SHALL BE ELECTRONIC PROGRAM START (EB). LITHONIA WSQ 14. ALL FIXTURES SHALL BE LISTED FOR THE ENVIRONMENT IN WHICH THEY ARE INSTALLED. DL = DAMP UL APPROVED LABEL. WL = WET UL APPROVED LABEL. SEATING AREA 15. ALL LINEAR FLUORESCENT FIXTURES SHALL BE PROVIDED WITH 4', 32W T8 LAMPS. EXTERIOR DOORS 16. PROVIDE 2 YEAR WARRANTY ON ALL FIXTURES. EXTERIOR DOORS EXTERIOR DOORS EXTERIOR DOORS EXTERIOR DOORS SERVING, STAGE RAMPS OUTSIDE D15SD164AE-BCDMX10/IN-MEC1745AE DELRAY CYLINDRO PRE-APPROVED DIMMING EQUAL VESTIBULE D15SD163AE-BCDMX6/IN-MEC1745AE DELRAY CYLINDRO PRE-APPROVED DIMMING EQUAL VESTIBULE AXIS LIGHTING BBRLED-B3-400-40-SO-FL-S#-W-277-D-1-DF SELUX M100 NEORAY 23DR RESTROOMS LITHONIA Z-2-32W T8-MVOLT-GEB1PS-WG COLUMBIA CH COLUMBIA WHTIE SURFACE/SUS 277 V PENDED RECESSED 277 V LITHONIA 2-AV-G/F-2-32-ADP-MVOLT-GEB10PS (1) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION WHITE RECESSED 277 V AXIS LIGHITNG BBR-S-FL-4-NL4-T8-1-W-UNIV AXIS LIGHTING HE WILLIAMS DAY 2X4 DIL SELUX M100 NEORAY 23DR WALL MOUNTED, INDIRECT/DIRECT, EXTRUDED ALUMINUM HOUSING SIMILAR TO F4 EXCEPT 2 LAMPS IN CROSS SECTION SURFACE MOUNTED INDUSTRIAL FLUORESCENT HIGH BAY. 13.25 INCH WIDTH X 48 INCH LENGTH, 2 3/8 INCH DEPTH, CHAIN SUSPENSION MOUNTING, MOUNT FIXTURE AT 22' AFF (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION (4) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION WHITE WHITE WHITE WALL RECESSED SUSPEND 277 V 277 V 277 V AXIS LIGHTING BBWD-A-NO-4-NL4-T8-1-1-W-UNV AXIS LIGHTING BBR-S-FL-4-NL4-T8-2-W-UNV LITHONIA IBZ-432L-WD-120-GEB10PS F10 F10B F13A 2'x4' RECESSED LENSED TROFFER, STEEL HOUSING, PROVIDE .156" LENS, PROVIDE MOUNTING HARDWARE FOR GYP OR ACT CEILINGS AS REQUIRED SIMLIAR TO F10 EXCEPT 4 LAMPS IN CUT SECTION PENDANT MOUNTED CYLINDER DOWNLIGHT, SEMI SPECULAR, 16" DIAMETER, ALZAK REFLECTOR, SUSPEND WITH STEM TUBE. PROVIDE GLASS DECORATIVE RING, AND HALF REFLECTOR/OPAL DIFFUSER. (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION (4) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION (2) 42 W PL-T, 3200 LUMENS, 82 CRI, 4100K, 16000 HRS WHITE WHITE VERIFY WITH ARCHITECT RECESSED RECESSED SUSPENDED 277 V 277 V 277 V LITHONIA LITHONIA BETA CALCO 2SP8-G-2-32-A19-120-GEB10PS 2SP8-G-4-32-A19-120-GEB10PS 201732-HG-277-DS-TS4(MOD) F13B SIMILAR TO F13A, EXCEPT 22" DIAMETER AND 4 LAMPS. (4) 42 W PL-T, 3200 LUMENS, 82 CRI, 4100K, 16000 HRS VERIFY WITH ARCHITECT SUSPENDED 277 V BETA CALCO 202213-HG-277-DS-TS4 (MOD) F16 WALL MOUNTED DIRECT UPLIGHT, EXTRUDED ALUMINUM HOUSNG, (2) UPLIGHT LAMP, ASSYMETRIC (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION WHITE WALL 277 V AXIS LIGHTING BBW-NO-A-4-NL4-T8-0-2-120 SELUX M100 SELUX M100 HOLOPHANE HB SERIES DAYBRITE TG8 DAYBRITE TG8 JESCO ARCHITECTUR AL PENDANTS JESCO ARCHITECTUR AL PENDANTS SELUX M100 F17 EXIT X1 RECESSED MOUNTED WEST LISTED, 4" APERATURE, EXTRUDED ALUMINUM HOUISNG, SATIN LENS, PROVIDE PROGRAMMED START BALLAST (2) 32W T8, 2800 LUMENS, 4100K, 30000 HOURS, PER 4' SECTION WHITE RECESSED 277 V AXIS LIGHTING WBR-S-4-T8-2-W-UNV EDGE LIT EXIT SIGN, WHITE BACK, PROVIDE SINGLE OR DOUBLE FACE ARROWS PER PLANS, PROVIDE MOUNTING FOR CEILING RECESSED, WALL, OR PENDANT MOUNT AS REQUIRED LED, GREEN LETTER ON WHITE BACKGROUND WHITE BACK UNIVERSAL 277 V LITHONIA LRP SERIES Comments 13. PROVIDE COLD WEATHER BALLASTS WITH A MINIMUM -20 DEGREE START TEMPERATURE FOR FIXTURES NOTED, (CWB). DIMMING KIM LIGHTING WALL DIRECTOR KIM LIGHTING WARP9 KIM LIGHTING WARP9 KIM LIGHTING WARP9 KIM LIGHTING VRB GOTHAM ECSS Location PRE-APPROVED EQUAL PRE-APPROVED EQUAL PRE-APPROVED EQUAL PRE-APPROVED EQUAL PORTFOLIO DIMMING LDSQ6A SOLID- STATE LIGMAN W60335-W LUMINARIES INFLECT SERIES DELRAY PRE-APPROVED DIMMING CYLINDRO EQUAL F4 C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt Lamp (Use) VESTIBULE PROVIDE COLOR CHANGING CONTROLLER PROVIDE COLOR CHANGING CONTROLLER PROVIDE COLOR CHANIGN CONTROLLER PROVIDE PROGRAM START BALLAST SERVICE ROOMS OFFICES BASE BID RESTROOMS PROVIDE PROGRAM START BALLAST NEORAY 23DW NEORAY 23DR DAYBRITE ALUMABAY METALUZ GR8 METALUX GR8 EUREKA COSMOS VESTIBULE CORRIDOR STAGE EUREKA COSMOS SEATING AREA SELUX M100 NEORAY GEO 80-IW NEORAY 23DR SEATING AREA EXTERIOR HUBBELL ISOLITE MULTIPLE STORAGE KITCHEN SEATING AREA 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: AW DATE: APPROVED CONTRACT DOCUMENT SCALE: 05/29/15 AS NOTED LIGHTING FIXTURE SCHEDULES ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:33:41 PM AUTHORITY DWG. NO. 3-E0.07 SHEET: OF: 983_2478_985 _OR_ 3-E0.07 2 Description COMMONS Type Mark GENERAL NOTES: 22 22 L1 1. ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO THE LACK OF COORDINATION WITH ARCHITECT. 22 L1 L1 22 C1-MSB C1-L1:15a (#10, 1"C) V1 FUTURE L1 COMMONS MAIN ELECTRICAL ROOM 2. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS NOTED OTHERWISE. ALL VERTICAL SECTIONS OF CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL COORDINATE INSTALLATION OF CONDUIT AND BACK BOXES IN CONCRETE, MASONRY AND GYP. WALLS. EXCEL PAD MOUNTED TRANSFORMER 3. REFER TO E0.1 FOR LIGHTING FIXTURE SCHEDULE. LIMIT OF WORK FUTURE COMMONS T L1 22 T 22T L1 T T 4. REFER TO LANDSCAPE & CIVIL DRAWINGS FOR ALL SITE FIXTURE LOCATIONS MOUNTED IN HARDSCAPE OR SOFTSCAPE. FIXTURE LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN, CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL AND LANDSCAPE ELEMENTS. T 5. ALL LANDSCAPE OR EXTERIOR BUILDING LIGHTING SHALL BE CONTROLLED VIA THE LIGHTING CONTROL SYSTEM. (AUTOMATIC TIME CLOCK AND PHOTO CELL) 6. REFER TO ARCHITECTURAL EXTERIOR ELEVATIONS FOR ALL FIXTURE LOCATIONS ON THE EXTERIOR OF THE BUILDING. FIXTURE LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN, CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL AND STRUCTURAL ELEMENTS. 7. PROVIDE A MINIMUM 1” PVC CONDUIT FOR ALL UNDERGROUND BRANCH CIRCUITS. ALL 90DEGREE ELBOWS SHALL BE PVC COATED RIGID. 8. CONTRACTOR SHALL STAKE LIGHT POLE LOCATIONS FOR REVIEW AND APPROVAL BY THE OWNERS REPRESENTATIVE 9. SEE DETAIL 10/LD1.1 FOR INFORMATION ABOUT CONCRETE MOWSTRIPS AROUND LIGHT POLE BASE L2 C1-L1:15c V2 (#10, 1"C) L2 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 C1-L1:15b V3 (#10, 1"C) KEY NOTES L4 L4 22 PROVIDE UL924 AUTOMATIC TRANSFER SWITCH TO BE LOCATED AT PANEL RELAY. 47 PROVIDE IN-GROUND ELECTRICAL PULL-BOX WITH ABOVE GROUND 30A, 3P, 480V, 3P DISCONNECT FOR FUTURE LED MESSAGE BOARD SIGNAGE. PROVIDE CONCRETE PAD AND UNI-STRUT SUPPORT AS REQUIRED FOR THIS UNIT. ROUTE (1) 1” CONDUIT WITH PULLSTRING BACK TO ELECTRICAL ROOM FOR CONTROL WIRING. 48 PROVIDE DEDICATED 120V, 20A CIRCUIT FOR IRRIGATION CONTROLLER. COORDINATE LOCATION WITH IRRIGATION CONTRACTOR. FFE 5238.00 GYM FFE 5241.00 FUTURE GYM RELOCATE FIXTURE AS REQUIRED TO ACCOMODATE NEW SIDEWALK 2 L3 (EX) L3A (EX) 2 CONNECT NEW FIXTURES TO EXISTING POLE CIRCUITING. 2 L3A (EX) L3A (NEW) FUTURE PARKING L3 (EX) 2 2 L3A (NEW) 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION 2 L3A (EX) MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture L3A (EX) 2 2 L3 (EX) This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 KM CHECKED BY: AW DATE: 1 Designer DRAWN BY: APPROVED CONTRACT DOCUMENT SCALE: COMMONS SITE LIGHTING PLAN 1" = 30'-0" DATE: DENVER, CO 05/29/15 AS NOTED COMMONS ELECTRICAL SITE PLAN ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 N SITE NO. 983 9550 E. 56TH AVENUE DESIGNED BY: DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 3:04:43 PM AUTHORITY DWG. NO. 3-E1.00 SHEET: OF: 983_2478_985 _OR_ 3-E1.00 2 L3 (EX) COMMONS C:\Revit Projects\2013\Project Path\E_DPS_SITE_E13_Pete.Johnson.rvt 2 GENERAL NOTES: 1. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL MECHANICAL UNITS WITH MECHANICAL CONTRACTOR. 2. ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR, PARALLEL, AND TIGHT TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH ENGINEER AND ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO THE LACK OF COORDINATION WITH ARCHITECT. 3. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS NOTED OTHERWISE. ALL VERTICAL SECTIONS OF CONDUIT SHALL BE CONCEALED. CONTRACTOR SHALL COORDINATE INSTALLATION OF CONDUIT AND BACK BOXES IN CONCRETE, MASONRY AND GYP. WALLS. 4. THIS CONTRACTOR SHALL REFER TO "MEP" SERIES DRAWINGS FOR ALL MECHANICAL EQUIPMENT ELECTRICAL CONNECTIONS. 1 2 3 4 5 6 7 8 5. CIRCUITS TO ALL MECHANICAL EQUIPMENT SHALL BE DEDICATED UNLESS NOTED OTHERWISE. 9 6. PROVIDE DEDICATED NEUTRAL FOR ALL BRANCH CIRCUIT WIRING. 7. ROUTE ALL POWER CONDUITS THROUGH EQUIPMENT CURBS AS MUCH AS POSSIBLE TO MINIMIZE ROOF PENETRATIONS. ALL PENETRATIONS SHALL BE COORDINATED AND WATERPROOFED AS SPECIFIED. A A C1-R1:53 (PART) WP GFCI WP GFCI B AHU ERV ACCU C2.01 C1-R1:49 NEMA 3R J 32 WP C2.01 NEMA 3R RE: ONE-LINE WP GFCI C1-R1:47 (PART) C1-R1:51 C2.01 32 WP J B NEMA 3R WP GFCI RE: ONE-LINE KEY NOTES C1-R1:53 (PART) C1-LM1:29,31 32 PROVIDE 120V, 20A DEDICATED CIRCUIT FOR MECHANICAL CONTROLS 2 C C C1-LM1:21 D D EF C2.01 WP GFCI NEMA 3R C1-R1:47 (PART) E E F F C1-LM1:39,41 NEMA 3R ACCU C1-R1:47 (PART) WP GFCI C2.02 2 G G 4.5 H H J J K K 3 4 4.5 5 6 7 8 9 2 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION N MADE APPR'D DENVER PUBLIC SCHOOLS ROOF ELECTRICAL PLAN 1 3/32" = 1'-0" DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: AW 05/29/15 ROOF ELECTRICAL PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:23 PM AUTHORITY DWG. NO. 3-E2.02 SHEET: OF: 983_2478_985 _OR_ 3-E2.02 2 COMMONS C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt 1 1 2 3 4 5 6 7 8 GENERAL NOTES: KEY NOTES 9 142 PROVIDE WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL OVERRIDE SWITCHES. SENSOR SHALL HAVE (2) RELAYS. (1) TO BE CONNECTED TO LIGHTING FIXTURES, AND (1) TO BE CONNECTED TO CEILING EXHAUST FAN.(DOUGLAS DIVERSA#WOSSDV2-P-VW OR APPROVED EQUAL BY WATTSTOPPER OR COOPER GREENGATE.)SENSOR SHALL BE SET UP AS VACANCY SENSOR. L1 L1 103 C1-L1:13 (PART) A F10 F1 F10B a,b F10 B a,b OFFICE 3-105B Not Enclosed a,b a,b 29 F1 TABLE & CHAIR STORAGE 3-103 Not Enclosed F1 F1 L20 TOILET B 3-105A 52 SF F1 142 30 30 29 L5 F10B a,b LV-5 87 LV-2 87 F10 135 F4H 135 C1-EL1:1d H1b 103 C1-L1:5a,5b H1aH1b F10 F16 185 (TYP) F16 F16 C1-L1:7a L2 87 30 135 30 C1-L1:11 X1 LV-12 87 L5 13 F13B 185 C1-L1:12 (PART) L4 C1-L1:12 (PART) L4 185 C1-L1:10 L5 UL924 103 L5 30 X1 DMX 174 E1 185 C1-L1:7b L3 L10 L10 LV-14 103 11. PROVIDE DEDICATED NEUTRAL FOR ALL BRANCH CIRCUIT WIRING 13 CONNECT EXIT SIGNS TO UN-SWITCHED EMERGENCY CIRCUIT. CIRCUIT TO ‘C1-EL1:42’ 22 PROVIDE UL924 AUTOMATIC TRANSFER SWITCH TO BE LOCATED AT PANEL RELAY. 29 PROVIDE WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL OVERRIDE SWITCHES. SENSOR SHALL HAVE (2) RELAYS FOR BI-LEVEL SWITCHING (DOUGLAS DIVERSA#WOSSDV2-P-VW OR APPROVED EQUAL BY WATTSTOPPER OR COOPER GREENGATE.)SENSOR SHALL BE SET UP AS VACANCY SENSOR. 30 PROVIDE CEILING MOUNTED LOW VOLTAGE 360 DEGREE DUAL TECHNOLOGY OCCUPANCY SENSOR WITH REMOTE LOW VOLTAGE OVERRIDE SWITCHES. REFER TO DETAIL F ON SHEET 3-E6.01. PROVIDE QUANTITY OF POWER PACKS AND SENSORS AS REQUIRED. (DOUGLAS DIVERSA#WORSDD2-DPR-L OR APPROVED EQUAL BY WATTSTOPPER OR COOPER GREENGATE). SENSOR SHALL BE SET UP AS VACANCY SENSOR. J1 F7 C1-L1:4 185 J1 L5 C1-DIM:36 (PART) 186 186 2ND ELEC 3RD ELEC FL2 J 189 WOMENS TOILET 3-101 31 PROVIDE WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH INTEGRAL OVERRIDE SWITCH. (DOUGLAS DIVERSA# WOSSDV1-P-VW OR APPROVED EQUAL BY WATTSTOPPER OR COOPER GREENGATE.)SENSOR SHALL BE SET UP AS VACANCY SENSOR. 87 PROVIDE LOW VOLTAGE OVERRIDE SWITCHES (MINIMUM OF 4 BUTTONS). REFER TO SHEET 3-E0.09 FOR LOW VOLTAGE SWITCH STATION SCHEDULES. 101 INTERIOR DAYLIGHT SENSOR (DOUGLAS #WPS-3711 OR APPROVED EQUAL BY WATTSTOPPER FOR COOPER GREENGATE). LOWER CASE LETTERS INDICATE ZONES CONTROLLED BY DAYLIGHT SENSORS. PLACEMENT OF SENSOR SHALL BE FIELD COORDINATED PER MANUFACTURER RECOMMENDATION. FOH SEATING 3-100 C1-EL1:6 (PART) L5 PERFORMANCE PLATFORM 3-110 APRON F16 L1 L2 L3 UL924 103 F7 101 F7 F7 E L5 F13A F16 F F13B F13B 103 PROVIDE UL924 DEVICE AND NORMAL SENSING CIRCUIT TO ALLOW FOR (1) ZONE OF FIXTURE TO BE SWITCHED WITH NORMAL LIGHTING. REFER TO DETAIL J ON SHEET 3-E6.01. SENSING CIRCUIT SHALL BE CONNECTED AHEAD OF ANY SWITCHING. 109 PROVIDE COLOR DIAL CONTROL FOR COLOR CHANGING FIXTURE TYPE L10 SERIES. PROVIDE CONTROL WIRING AS REQUIRED SO THAT EACH FIXTURE CAN BE CONFIGURED TO A DIFFERENT COLOR (OSRAM E:CUE # LIGHT DRIVE ELITE OR APPROVED EQUAL) 110 RGB FIXTURES SHALL BE CONTROLLED BY LOCAL COLOR DIAL AND BUILDING CONTROL SYSTEM 111 LOCATE REMOTE LIGHTING CONTROL RELAY PANEL FOR (1) OR (2) CLASSROOMS ABOVE ACCESSIBLE CEILING ABOVE DOOR. REFER TO LIGHTING CONTROL ONE-LINE ON SHEET 3-E0.02 FOR MORE DETAILS. (DOUGLAS REMOTE RELAY ENCLOSURE WITH DOUGLAS DIALONG #WRD-3408 CONTROLLER OR APPROVED EQUAL BY COOPER GREENGATE OR WATTSTOPPER). F13B 174 (TYP) 185 F16 T2 181 (TYP. OF 6) L5 L10 L10 T1 181 F7 F13A 185 C1-L1:12 185 (PART) L4 L1 189 C1-L1:12 (PART) L4 189 F13B F13B J F13B F13B 185 C1-DIM:1 THRU 12 F16 F16 F16 F16 F16 F16 F16 F16 L1 (TYP. OF 12) F7 C1-DIM:25 (PART) F7 J FL1 J C1-DIM:47,48 J J 189 J 189 C1-DIM:13 THRU 24 FL1 J 13 L5 X1 30 J1 87 LV-11 L5 C1-DIM:25 (PART) L5 X1 13 103 L5 UL924 7. ALL EXIT LIGHTS OF ALL TYPES SHALL BE MOUNTED AT 8'-0" AFF UNLESS OTHERWISE NOTED. PROVIDE EXIT SIGNS IN ALL PATH OF EGRESS. THERE SHOULD NOT BE MORE THAN 80' SPACING BETWEEN EXIT SIGNS. 10. ALL AREAS SHALL BE CONTROLLED VIA THE LIGHITNG CONTROL SYSTEM. LOCATE A 48 RELAY LIGHTING CONTROL PANEL ADJACENT TO EACH LIGHITNG PANEL. C1-EL1:41 22 C1-EL1:2a F7 1ST ELEC 6. ELECTRICAL CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR FOR PLACEMENT OF FIXTURES WITHIN MECHANICAL ROOMS. KEY NOTES F13B F13B 5. ELECTRICAL CONTRACTOR SHALL BE FIELD VERIFY EXACT FIXTURE LENGTHS FOR ALL CONTINUOUS LINEAR FLUORESCENT AND QUARTZ FIXTURES. FOR COVES, PROVIDE CONTINUOUS ILLUMINATION WITH 6" MAXIMUM DISTANCE BETWEEN END OF FIXTURE AND WALL. L5 UL924 F7 87 L5 L5 L5 J1 PLATFORM CIRCULATION 3-110A L5 L5 103 X1 13 FL2 J F16 F13B E X1 C1-L1:2 (PART) 4. ALL FLUORESCENT BALLASTS SHALL BE PROGRAMMED START ELECTRONIC. ALSO PROVIDE DIMMABLE BALLASTS WHERE NOTED PER LIGHTING CONTROL. 9. THE LIGHTING CONTROL SYSTEM SHALL INCLUDE PROVISIONS FOR SERVING THE FACILITY’S EGRESS/EXIT LIGHTING AND SHALL BE PROVIDED WITH DEVICE, AND UL 924 LISTED. L1 13 186 F13A 13 F10 C1-DIM:36 (PART) F16 S2 F4 135 L5 87 LV-15 F1 VESTIBULE 3-106D Not Enclosed X1 3. ALL SURFACE MOUNTED CONDUIT SHALL BE ROUTED PERPENDICULAR AND PARALLEL TO BEAMS AND COLUMNS. ALL CONDUIT ROUTING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION AND INSTALLED IN A NEAT AND CONSISTENT MANNER. ALL SURFACE MOUNTED CONDUIT WHERE EXPOSED TO PUBLIC AREAS SHALL BE PAINTED. PAINT COLOR TO BE DETERMINED BY THE ARCHITECT. a. COMPUTER CONTROLLED LIGHTING CONTROL SYSTEM PER THE SPECIFICATIONS. b. LOW VOLTAGE OVERRIDES READILY ACCESSIBLE FOR NORMALLY OCCUPIED SPACES. ONE CONTROL FOR EVERY 5000 SF OF SPACE. c. ALL FLUORESCENT FIXTURES TO HAVE FREQUENCY ELECTRICAL BALLASTS OR FIXTURES SHALL BE TANDEM WIRED. d. ALL CONFERENCE ROOMS, OFFICES, BREAK ROOMS AND MEETING ROOMS SHALL HAVE DUAL TECHNOLOGY OCCUPANCY SENSORS. LV-9 3 87 IDF 3-106C C1-EL1:6 (PART) 184 C1-EL1:2a S3 A 30 LV-13 F16 13 22 C1-EL1:4 F13B F13B F13B 3 F10 LV-3 F16 D1 F1 F1 FAMILY ASSIST TOILET CUST 31 C1-EL1:2b 3-106A 3-106B 142 S1 C1-L1:6b CORRIDOR F10 S1 UL924 103 3-106 F10 87 F16 F1 E1 30 SERVING 3-104 1257 SF F1 135 2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR ALL FIXTURE LOCATIONS WITHIN A CEILING OR CEILING GRID. FOR AREAS WITHOUT CEILINGS, FIXTURE LOCATIONS ARE DIAGRAMMATIC. THE INTENT IS TO ALIGN, CENTER, OR SPACE FIXTURES BETWEEN ARCHITECTURAL AND STRUCTURAL ELEMENTS. 8. PROVIDE A LIGHTING CONTROL SYSTEM WHICH MEETS THE REQUIREMENTS OF THE ADOPTED ENERGY CODE, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: C1-L1:1 L20 L1 UL924 L5 B F1 C1-EL1:1c H1a 2 D F1 30 F10 F4H 135 F13A F1 D1 30 L5 LV-8 87 VESTIBULE 3-102.1 L5 103 ELECTRICAL 3-109 A 103 UL924 F16 F1 C1-EL1:5 22 F1 C1-L1:6a S3 F1 184 PROVIDE DMX PLUG-IN STATION FOR CONTROL CONSOLE. 185 CONNECT CIRCUIT TO DMX CONTROLLED SECTION OF RELAY PANEL 186 PROVIDE THEATRICAL PRE-WIRE FIXED INSTALLATION CONNECTOR STRIPS FOR PIPE GRID POWER. (SSRC #SL-50-12/24-L520R-DMX OR APPROVED EQUAL) PROVIDE MOUNTING BRACKETS FOR A SINGLE CONNECTOR STRIP AND A SINGLE PIPE TYPE. 189 PROVIDE THEATRICAL PRE-WIRE FIXED INSTALLATION CONNECTOR STRIPS FOR PIPE GRID POWER. (SSRC #SL-30-2/12-L520R-DMX OR APPROVED EQUAL) PROVIDE MOUNTING BRACKETS FOR A SINGLE CONNECTOR STRIP AND A SINGLE PIPE TYPE. D1 F1 C VESTIBULE 3-100C F4 F4 F1 F4H 31 A 3 WATER ENTRY 3-108 F10 30 L1 103 F1 F10 THEATER STORAGE 3-107 C1-L1:14 L5 C1-EL1:6 (PART) UL924 F10B a,b LV-1 87 30 VESTIBULE 3-103.1 L5 F1 F10 C1-L1:3a,3b G1a G1b LV-4 UL924 F1 F10B a,b F10B a,b UL924 103 C1-EL1:6 (PART) 30 3 F10B a,b F10B a,b F10B a,b 87 CUST. 3-104A B 71F10 SF D2 30 F1 F1 E1 13 X1 LV-6 UL924 a,b F4 L1 F10B a,b LAUNDRY 3-104B F1 F1 a,b70BSFa,b 30 F10B C1-EL1:1b G1b a,b C1-EL1:1a G1a 103 B MEN TOILET 3-102 UL924 174 PROVIDE RECESSED MOUNTED WALL TOUCH SCREEN & CONTROL STATION FOR DIMMING SYSTEM IN THIS AREA. (UNISON PARADIGM TOUCHSCREEN #UPLCD-WM OR APPROVED EQUAL). COORDINATE FINISH COLOR WITH ARCHITECT PRIOR TO ORDERING. 181 PROVIDE THEATRICAL LIGHT FIXTURE TYPE “T1” AND “T2” AS INDICATED. FIXTURES WILL BE MOUNTED ON PIPE GRID PLUG IN TO OUTLETS. FINAL LOCATION SHALL BE FIELD COORDINATED WITH ARCHITECTS AND ENGINEERS PRIOR TO TURN OVER. FIXTURES WILL BE UTILIZED TO TEST ALL DIMMING OUTLETS FOR PIPE GRIDS. 1. REFER TO SHEET E0.05 FOR LIGHT FIXTURE SCHEDULE. 189 123 BID ALTERNATE #1D: PROVIDE 0-10V 4-CHANNEL DIMMING CONTROLLER FOR BID ALTERNATE. LOCATE WITHIN EXISTING RELAY CABINET. 135 PROVIDE CONTINUOUS FIXTURE RUN. REFER TO ARCHITECTURAL DRAWINGS FOR LENGTH. C1-DIM:37,39 C1-DIM:26 THRU 35 C1-EL1:6 (PART) L5 L5 L5 L5 C1-L1:2 (PART) 30 L5 PLATFORML5 CIRCULATION 3-110B G G F13A X1 F13A F13A F13A X1 13 13 H 13 109 LV-7 L1 L1 LV-10 22 C1-EL1:3b U2 C1-L1:8b 87 L8 H C1-L1:13 (PART) F2B F4D NL 110 C1-L1:8a U4 29 L10 185 U1 F4D NL L10A 185 101 110 VESTIBULE 3-100A Not Enclosed 2 U1 U2 L10B 185 110 L5 NL LV-16 87 J J F17 F17 F17 F17 C1-EL1:3a 22 U3 K 1 2 3 4 4.5 5 6 7 8 9 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture N 1 LEVEL 1 LIGHTING PLAN 1/8" = 1'-0" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: AW 05/29/15 LEVEL 1 LIGHTING PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:27 PM AUTHORITY DWG. NO. 3-E3.01 SHEET: OF: 983_2478_985 _OR_ 3-E3.01 2 COMMONS C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt 87 X1 GENERAL NOTES: 1 2 3 4 5 6 7 8 1. CONNECT ALL ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, TOP OF SHAFT AND ELEVATOR PIT SMOKE DETECTORS TO ELEVATOR CONTROLLER FOR ELEVATOR RECALL. PROVIDE SHUNT TRIP DEVICE TO DISCONNECT ALL ELEVATOR CONTROLLERS. VERIFY SHUNT TRIP LOCATION REQUIREMENTS WITH AHJ. PROVIDE A HEAT DETECTOR AT THE TOP OF ELEVATOR SHAFT AND WITHIN TWO FEET OF EACH SPRINKLER HEAD IN ALL ELEVATOR MACHINE ROOMS. ACTIVATION OF HEAT DETECTOR TO INITIATE SHUNT-TRIP. 9 2. PROVIDE #18 AWG MINIMUM WIRING FOR ALL SIGNAL AND INITIATION DEVICES. 3. ALL EXPOSED CONDUIT SHALL BE ROUTED PERPENDICULAR AND PARALLEL TO COLUMNS AND BEAMS. ALL EXPOSED CONDUIT ROUTING SHALL BE COORDINATED WITH THE ARCHITECT PRIOR TO INSTALLATION. NO ADDITIONAL COST TO THE OWNER WILL BE ALLOWED FOR RELOCATING CONDUIT DUE TO LACK OF COORDINATION WITH THE ARCHITECT. A 4. ALL BACK BOXES SHALL BE FLUSH MOUNTED UNLESS OTHERWISE NOTED. CONTRACTOR SHALL COORDINATE INSTALLATION OF CONDUIT AND BACK BOXES IN POURED CONCRETE, PRE-CAST CONCRETE, MASONRY AND GYP. WALLS. A FACP OFFICE 3-105B 5. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT QUANTITY AND LOCATIONS OF ALL FIRE SPRINKLER SYSTEM TAMPER AND FLOW SWITCHES WITH CONSTRUCTION MANAGER AND FIRE PROTECTION PRIOR TO BID. CONNECT ALL TAMPER AND FLOW SWITCHES TO FIRE ALARM SYSTEM. WATER ENTRY 3-108 ELECTRICAL 3-109 THEATER STORAGE 3-107 TABLE & CHAIR STORAGE 3-103 TOILET 3-105A 6. CONTRACTOR SHALL COORDINATE EXACT LOCATION AND QUANTITY OF ALL DUCT TYPE SMOKE DETECTORS WITH MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL HARD WIRE TO RELAY STARTER. KITCHEN PANTRY 3-105 B B LAUNDRY 3-104B 7. PROVIDE (1) DUCT TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR HANDLING UNIT, SUPPLY FAN, AND HEAT PUMP OF 2,000 CFM AND GREATER. PROVIDE (2) DUCT TYPE SMOKE DETECTORS FOR EACH FAN COIL UNIT, AIR HANDLING UNIT, HEAT PUMP AND SUPPLY FAN OF 15,000 CFM AND GREATER. IDF 3-106C 8. PROVIDE CONNECTION OF FA SYSTEMS TO ALL MAGNETIC DOOR HOLDOPEN DEVICES TO AUTOMATICALLY CLOSE DOORS (INCLUDING OVERHEAD STORAGE DOORS) DURING ALARM CONDITIONS. 2 2 MEN TOILET 3-102 CUST. 3-104A FAMILY ASSIST TOILET 3-106A CUST 3-106B SERVING 3-104 9. DEVICES INDICATED ON FIRE ALARM ONE-LINE ARE FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS AND SPECIFICATIONS FOR QUANTITIES. REFER TO ARCHITECTURAL DOOR SCHEDULE FOR MAGNETIC DOOR HOLDER AND BLOW OPEN DOOR REQUIREMENTS. 10. PROVIDE SMOKE DETECTOR (AREA OR DUCT) AND FIRE ALARM RELAY MODULE FOR EVERY FIRE-SMOKE DAMPER FOR DAMPER POSITION INDICATION. LOCATE DUCT DETECTOR WITHIN FIVE FEET OF FIRE-SMOKE DAMPER. VESTIBULE 3-106D CORRIDOR 3-106 VESTIBULE 3-103.1 11. ALL VISUAL DEVICES SHALL BE SYNCHRONIZED. C C 12. PROVIDE FIRE ALARM RELAY MODULE FOR ALL CARD READERS. 13. PROVIDE FIRE ALARM RELAY MODULE AT ALL LOCAL FIRE SUPPRESSION SYSTEMS FOR GREASE EXHAUST HOODS IN FOOD SERVICE AREAS. PLATFORM CIRCULATION 3-110A VESTIBULE 3-100C D 14. PROVIDE FIRE ALARM RELAY TO INTERLOCK WITH AV SYSTEM, SO THAT ALL SOUNDS SYSTEMS WOULD BE SHUT OFF DURING AN ALARM. D VESTIBULE 3-102.1 2 KEY NOTES 2 E SEATING 3-100 PERFORMANCE PLATFORM 3-110 E WOMENS TOILET 3-101 F F 2 2 PLATFORM CIRCULATION 3-110B G G 2 H H SECURITY 3-100B J J K 1 2 3 4 4.5 5 6 1 7 N 8 9 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS LEVEL 1 FIRE ALARM PLAN 1/8" = 1'-0" DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: AW DRAWN BY: KM CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: AW 05/29/15 LEVEL 1 FIRE ALARM PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:49:33 PM AUTHORITY DWG. NO. 3-E4.01 SHEET: OF: 983_2478_985 _OR_ 3-E4.01 2 COMMONS C:\Revit Projects\2013\Project Path\E_DPS_COMMON_E13_Pete.Johnson.rvt FAA P ? ? GENERAL NOTES: ROOF LEVEL ROOF LEVEL IDF 3-110C 1. REFER TO SYMBOL LEGEND FOR ADDITIONAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO, INSTALLATION OF COMMUNICATIONS, AUDIO/VISUAL, AND SECURITY RACEWAY, CABLING, AND DEVICES. 2. CONTRACTOR SHALL COORDINATE ROUTING AND STUB-UP LOCATIONS FOR ALL LOW VOLTAGE SYSTEMS RISER CONDUIT DURING SHOP DRAWING PROCESS. REFER TO ENLARGED COMMUNICATIONS ROOM PLANS FOR ADDITIONAL REQUIREMENTS. 3. CABLE TRAY IS INDICATED ON THIS DRAWING FOR REFERENCE ONLY. REFER TO PLAN DRAWINGS FOR ADDITIONAL REQUIREMENTS. 4. REFER TO TELECOM GROUNDING DETAILS FOR ADDITIONAL REQUIREMENTS. 5. ALL CONDUIT, CABLE TRAY, LADDER RACK, AND EQUIPMENT CABINETS/RACKS WITHIN COMMUNICATIONS ROOMS SHALL BE GROUNDED TO THE TELECOM GROUNDING BUSBAR WITHIN THAT RESPECTIVE ROOM. 6. GROUNDING CONDUCTORS SHALL BE INSULATED AND INSTALLED IN CABLE TRAY OR CONTINUOUS METALLIC CONDUIT WITH PULL-BOXES AS REQUIRED. 7. ALL CONDUIT USED FOR GROUNDING CONDUCTORS SHALL BE BONDED TO GROUND. 8. PROVIDE BUILDING ENTRANCE TERMINALS (BET) ON ALL INTER-BUILDING COPPER BACKBONE CABLES. IDF 3-110C 1 IC FIRST FLOOR FIRST FLOOR 12 MM TYPE OM3 INDOOR/OUTDOOR (OFNR) FIBER FROM SLC BLDG. (2) 4" C. TO CAMPUS HAND-HOLE (1) 2" C. TO CAMPUS HAND-HOLE C A TECHNOLOGY FIBER OPTIC ONE-LINE DIAGRAM NO SCALE TECHNOLOGY RACEWAY ONE-LINE DIAGRAM NO SCALE KEY NOTES: (SOME KEY NOTES MAY NOT APPLY TO THIS SHEET.) ROOF LEVEL 1 IC-ROOM: INTERMEDIATE CROSSCONNECT ROOM. 2 TERMINATE 18/4 CABLES ON WALL MOUNTED 66-BLOCKS. PROVIDE DEDICATED BLOCKS. LOCATE WITH PAGING EQUIPMENT. 3 25-PAIR BET WITH 66 TYPE IN/OUT WITH GAS TUBE MODULES PORTA SYSTEMS #24100-66-M66PC OR EQUIVALENT. 4 LOCAL SECURITY PANEL. 5 INTERMEDIATE CROSS-CONNECT: PROVIDE 66-BLOCK ADJACENT TO BET. FROM 66-BLOCK PROVIDE 25-PAIR TIE CABLE TO RACK MOUNTED PATCH PANEL. AT PATCH PANEL TERMINATE 25-PAIR CABLE USING 1-PAIR PER PORT. ROOF LEVEL IDF 3-110C 4 1 5 IDF 3-110C 2 1 IC 3 TMGB FIRST FLOOR FIRST FLOOR #3/0 AWG 25-PAIR CAT. 3 OSP CABLE FROM SLC (3) OSP RATED 18 AWG, 4 CONDUCTOR, SHIELDED CABLES FROM SLC (2) OSP RATED 18 AWG, 6 CONDUCTOR, STRANDED, SHIELDED CABLES FROM SLC D B TECHNOLOGY GROUNDING ONE-LINE DIAGRAMS NO SCALE TECHNOLOGY COPPER ONE-LINE DIAGRAM NO SCALE C:\Revit Projects\2013\Project Path\T_DPS_COMMON_T13_mendez.rvt ROOF LEVEL CAT.6 UTP (CMP) IDF 3-110C FIRST FLOOR 1 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS CAT. 6 (OSP RATED) DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture SCHOOL DISTRICT NO. 1 DESIGNED BY: JH DRAWN BY: JM CHECKED BY: DATE: NO SCALE M-E 05/29/15 AS NOTED TECHNOLOGY ONE-LINE DIAGRAMS ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 TECHNOLOGY HORIZONTAL ONE-LINE DIAGRAMS DATE: DENVER, CO 9100 E. 56TH AVE. APPROVED CONTRACT DOCUMENT SCALE: E SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DWG. NO. 3-T0.10 SHEET: COMMONS This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:51:48 PM AUTHORITY OF: 983_2478_985 _OR_ 3-T0.10 HC GENERAL NOTES: 1 2 3 4 5 6 7 8 1. REFER TO SYMBOL LEGEND FOR ADDITIONAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO, INSTALLATION OF COMMUNICATIONS AND SECURITY RACEWAY, CABLING, AND DEVICES. 9 2. CABLE TRAY INSTALLER SHALL COORDINATE ALL CABLE TRAY SEGMENTS WITH ALL CONTRACTOR TRADES PRIOR TO INSTALLATION TO ENSURE PROPER MINIMUM CLEARANCES ARE OBTAINED FOR CABLE TRAY ACCESSIBILITY WITH RESPECT TO ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, STRUCTURE, CEILINGS, DUCTWORK AND PIPING. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL COORDINATE THIS DURING THE SHOP DRAWING PROCESS AND SUBMIT TO ARCHITECT/ENGINEER FOR FINAL REVIEW AND APPROVAL. REFER TO TECHNOLOGY DETAILS AND WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. SEC:03 86 SEC:01 CAM:01 M A 2 M 3-105A 2 3. CONTRACTOR(S) RESPONSIBLE FOR PROVIDING TELE/DATA RACEWAY AND/OR CABLING SHALL ENSURE THAT THE PATHWAY (AND CABLE) TO EACH DEVICE LOCATION DOES NOT EXCEED THE HORIZONTAL CABLE LENGTH LIMITATIONS OF 295-FEET, PER WRITTEN SPECIFICATIONS AND TIA/EIA STANDARDS. SEC:02 M M 3-108B A 83 3-109B 53 C WLAN THEATER STORAGE 3-107 PA OFFICE 3-105B PA 4. WHERE COMMUNICATIONS AND/OR SECURITY DEVICES ARE LOCATED IN AREAS WITHOUT ACCESSIBLE CEILING, SUCH AS GYP CEILINGS OR AREAS OPEN TO STRUCTURE, RACEWAY INSTALLER SHALL PROVIDE CONDUIT FROM THE OUTLET BOX TO THE NEAREST COMMUNICATIONS CABLE TRAY OR IC ROOM. PA PA PA KITCHEN PANTRY 3-105 1 WATER ENTRY 3-108 TOILET 3-105A ELECTRICAL 3-109 PA PA B PA IC PA POS/2 PA 81 CORRIDOR 3-106 SEC:07 PA VESTIBULE 3-103.1 C WLAN REX M M EL KP SEC:06 SEC:04 82 SEC:05 PA 92 69 KEY NOTES 3-106DA C CAM +144" 1 1 88 SEC:17 CAM:06 ? 92 1 80 1 1 +144" * +144" 1 1 1 * +144" PA 1 77 D PA WLAN +144" 56 1 2 ? ? 1 1 J WLAN R 1 SEC:16 W PA POS/2 MEN TOILET 3-102 61 REX EL M R 3-106CA R WLAN 92 EL M 1 FAMILY ASSIST TOILET 3-106A M 1 PA 8. PROVIDE WHITE SPEAKERS IN ALL AREAS WITH EXCEPTION OF THE PERFORMANCE PLATFORM. PROVIDE BLACK SPEAKERS AT PERFORMANCE PLATFORM. REX PA PA D 7. PROVIDE WHITE FACEPLATES FOR COMMUNICATIONS DEVICES IN ALL AREAS WITH THE EXCEPTION OF THE PERFORMANCE PLATFORM. PROVIDE BLACK FACEPLATES AT PERFORMANCE PLATFORM. 1 3-T3.01 SCP PA PA 6. WIRELESS ACCESS POINT LOCATIONS ARE SHOWN FOR QUANTITY ONLY. FINAL LOCATIONS WILL BE DETERMINED ONCE WIRELESS SURVEY IS COMPLETE. 85 LAUNDRY 3-104B 69 B 62 TABLE & CHAIR STORAGE 3-103 3-100CA 5. COMMUNICATIONS PATHWAYS INCLUDING CABLE TRAY, CONDUITS AND J-HOOKS ARE DEDICATED PATHWAYS FOR COMMUNICATIONS AND SHALL NOT BE SHARED WITH OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO AV, FIRE ALARM, LIGHTING CONTROL, PAGING, AND BUILDING CONTROLS. 1 C PA 72 1 1 73 1 1 1 WOMENS TOILET 3-101 1 1 12" x 4" WIRE MESH CABLE TRAY AT 11'-0" U.N.O. 1 1 1 PA * 1 E PERFORMANCE PLATFORM 3-110 2 1 +144" 1 1 1 E 78 SEATING 3-100 F F 1 1 1 WLAN 1 1 2 +144" 53 WIRELESS CLOCK: PROVIDE 12" BATTERY OPERATED WIRELESS CLOCK IN ALL CLASSROOMS AND AREAS SHOWN. 56 PROVIDE 1" CONDUIT FROM OUTLET BOX TO IC ROOM FOR (1) 18 AWG, 4-CONDUCTOR, SHIELDED CABLE FOR CONNECTION TO PAGING SYSTEM. 61 FIRE RATED PATHWAY: PROVIDE EZ-PATH SERIES 44 OR EQUAL. PROVIDE QUANTITY SHOWN. 62 (2) 4" AND (1) 2" CONDUITS FROM CAMPUS MANHOLE/HANDHOLE. 63 WEATHERPROOF J-BOX FOR OUTDOOR WIRELESS ACCESS POINT ANTENNA MOUNTED AT 144" U.N.O. PROVIDE 1-1/2" CONDUIT FROM BOX STUBBED THROUGH EXTERIOR WALL ABOVE CEILING. 64 OUTDOOR WIRELESS ACCESS POINT. LOCATE DATA OUTLET FOR WAP WITHIN 2-FEET OF WAP J-BOX ON EXTERIOR WALL. COORDINATE LOCATION WITH DPS-IT. 69 PROVIDE QUICK DISCONNECT FOR ELECTRIC STRIKES USED IN DOORS WITH REMOVEABLE MULLIONS. 72 LARGE WIRELESS CLOCK: PROVIDE 15" BATTERY OPERATED WIRELESS CLOCK IN GYM AND COMMONS. 73 12” X 4” WIRE MESH CABLE TRAY (BASKET TYPE). PROVIDE DIVIDER STRIP TO SEPARATE COMMUNICATIONS CABLE FROM SECURITY CABLE. 74 (2) 2” CONDUITS FROM SECURITY OFFICE ABOVE CEILING TO CABLE TRAY. AT CABLE TRAY TURN CONDUITS DOWN TO STOP APPROX. 6” ABOVE TRAY. 75 ANALOG VOICE FOR FACP. COORDINATE TERMINATION WITH FA INSTALLER. 77 LOCATE DATA OUTLET AND J-BOX FOR PAGING CONNECTION BEHIND AV RACK. REFER TO AV DRAWINGS FOR RACK LOCATION. 78 LOCATE DATA FACEPLATE INSIDE AV WALL BOX. COORDINATE LOCATION INSIDE BOX WITH AV CONTRACTOR. 80 MOTION SENSOR: PROVIDE BOSCH (ADEMCO) DS9360. 81 MOTION SENSOR: PROVIDE BOSCH (ADEMCO) DS778. 82 ALARM KEYPAD. PROVIDE BOSCH (ADEMCO) 6160. 83 INTERCOM CALL STATION: VIDEO CALL STATION AIPHONE #AX-DV WITH SBX-AXDV30 ANGLED SURFACE MOUNT BOX MOUNTED AT 48" AFF U.O.N. 84 MASTER STATION: AUDIO VIDEO MASTER STATION AIPHONE #AX-8MV. 85 INTERCOM EXCHANGE UNIT: AIPHONE #AX-084C. COORDINATE EQ. RACK LOCATION WITH DPS SECURITY. 86 EXTERIOR CORNER MOUNT SECURITY CAMERA: PROVIDE CAMERA WITH CORNER MOUNT AT 144" U.O.N. 88 INTERIOR WALL MOUNTED SECURITY CAMERA. 92 DATA OUTLET FOR ACCESS CONTROL SYSTEM: PROVIDE DATA AT SECURITY J-BOX LOCATED ABOVE DOOR. 1 78 1 1 PA * +144" 1 COORDINATE ROUTING OF CONDUIT WITH VERTICAL DUCT C 1 72 O 1 PLATFORM CIRCULATION 3-110B 1 80 SEC:12 SEC:18 3-100B SEC:14 WP G +144" WLAN O H 3-100A M 86 1 J SECURITY 3-100B 2 M WLAN 63 CAM:02 64 PA 63 CAM CAM CAM 1 74 M M CAM:05 86 CAM 1 88 3-100C 64 1 SEC:19 CAM:04 PA SEC:15 1 H +144" * +144" WLAN 3-100D G 1 1 J 1 WP 1 1 1 WLAN 1 SEC:11 SEC:13 D DR IC P VM 4 84 PA SEC:10 75 92 KP 69 REX M M M 3-100AC M 3-100AB SEC:20 M EL M 3-100AA SEC:09 SEC:08 J 82 R IC 83 K 1 2 3 4 4.5 5 6 7 8 9 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture N 1 LEVEL 1 TECHNOLOGY PLAN 1/8" = 1'-0" This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. SCHOOL DISTRICT NO. 1 DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. 985 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: JH DRAWN BY: JM CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: M-E 05/29/15 LEVEL 1 TECHNOLOGY PLAN AS NOTED ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:51:50 PM AUTHORITY DWG. NO. 3-T2.01 SHEET: OF: 983_2478_985 _OR_ 3-T2.01 1 COMMONS C:\Revit Projects\2013\Project Path\T_DPS_COMMON_T13_mendez.rvt J 2 V CAM:03 GENERAL NOTES: 1. REFER TO SYMBOL LEGEND FOR ADDITIONAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO, INSTALLATION OF COMMUNICATIONS AND SECURITY RACEWAY, CABLING, AND DEVICES. 2. CABLE TRAY INSTALLER SHALL COORDINATE ALL CABLE TRAY SEGMENTS WITH ALL CONTRACTOR TRADES PRIOR TO INSTALLATION TO ENSURE PROPER MINIMUM CLEARANCES ARE OBTAINED FOR CABLE TRAY ACCESSIBILITY WITH RESPECT TO ALL OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, STRUCTURE, CEILINGS, DUCTWORK AND PIPING. MECHANICAL AND ELECTRICAL CONTRACTORS SHALL COORDINATE THIS DURING THE SHOP DRAWING PROCESS AND SUBMIT TO ARCHITECT/ENGINEER FOR FINAL REVIEW AND APPROVAL. REFER TO TECHNOLOGY DETAILS AND WRITTEN SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. 3. CONTRACTOR(S) RESPONSIBLE FOR PROVIDING TELE/DATA RACEWAY AND/OR CABLING SHALL ENSURE THAT THE PATHWAY (AND CABLE) TO EACH DEVICE LOCATION WITHIN EACH BOUNDARY DOES NOT EXCEED THE HORIZONTAL CABLE LENGTH LIMITATIONS OF 295FEET, PER WRITTEN SPECIFICATIONS AND TIA/EIA STANDARDS. 4. RACEWAY INSTALLER SHALL PROVIDE CONDUIT THROUGH WALLS AND ACROSS INACCESSIBLE CEILING SPACES TO ENSURE UNOBSTRUCTED CABLING PATHWAYS ARE PROVIDED FROM EACH DEVICE LOCATION BACK TO THE APPROPRIATE IC-ROOM (AS INDICATED BY DIVIDER LINES). 5. ALL TELE/DATA CABLE ROUTED IN J-HOOKS SHALL BE ROUTED IN DEDICATED J-HOOKS, SEPARATE FROM ALL OTHER LOW VOLTAGE CABLING SYSTEMS INCLUDING, BUT NOT LIMITED TO, AV, FIRE ALARM, SECURITY, AND CONTROLS CABLING. 6. EQUIPMENT SHOWN IN RACK ELEVATIONS IS DEPICTED FOR DESIGN INTENT AND NOT INTENDED TO CONVEY EXACT QUANTITIES. CONTRACTOR SHALL DETERMINE EXACT QUANTITIES OF PATCH PANELS AND WIRE MANAGERS FOR EACH COMMUNICATONS ROOM. KEY NOTES 1 1 1 38 PLYWOOD BACKBOARD: PROVIDE 4' X 8' X 3/4" FIRE RESISTANT MARINE GRADE PLYWOOD BACKBOARD MOUNTED ON WALLS AT 6" AFF TO 102" AFF. 40 VERTICAL CABLE TRAY: PROVIDE 12-INCH LADDER RACK MOUNTED VERTICALLY ON WALL FOR CABLE SUPPORT. 41 HORIZONTAL CABLE TRAY: PROVIDE 18"W X 1-1/2"D LADDER RACK TYPE CABLE TRAY AROUND ROOM PERIMETER AND ABOVE EQUIPMENT RACKS. LADDER RACK SHALL BE MOUNTED AT 90" AFF AROUND ROOM PERIMETER (OFFSET 6" FROM WALL) AND ABOVE EQUIPMENT RACKS. 43 VERTICAL CABLE MANAGERS: PROVIDE 12-INCH WIDE VERTICAL CABLE MANAGERS IN BETWEEN RACKS AND 8-INCH VERTICAL CABLE MANAGERS ON THE ENDS OF EACH EQUIPMENT RACK. 44 COPPER BACKBONE CROSS-CONNECT: PROVIDE RACK MOUNTED RJ-45 PATCH PANELS IN RACK FOR TERMINATION OF COPPER BACKBONE CABLING. 45 FIBER OPTIC BACKBONE CROSS-CONNECT: PROVIDE RACK MOUNTED FIBER OPTIC TERMINATION SHELF (WITH ACCESSORIES) IN "RACK XX" FOR TERMINATION OF FIBER BACKBONE CABLE. 46 HORIZONTAL CROSS-CONNECT: PROVIDE RACK MOUNTED RJ-45 PATCH PANELS IN RACK FOR TERMINATION OF ALL HORIZONTAL VOICE/DATA CABLES. 47 TELECOM GROUNDING BUSBAR (TMGB, TGB OR I-TGB): PROVIDE TELECOM GROUNDING BUSBAR FOR GROUNDING OF EQUIPMENT WITHIN COMM ROOM. REFER TO TELECOM GROUNDING ONE-LINE AND DETAILS FOR ADDITIONAL REQUIREMENTS. 60 EQUIPMENT RACK: PROVIDE 19" X 84" 2-POST EQUIPMENT RACK. 61 FIRE RATED PATHWAY: PROVIDE EZ-PATH SERIES 44 OR EQUAL. PROVIDE QUANTITY SHOWN. 62 (2) 4" AND (1) 2" CONDUITS FROM CAMPUS MANHOLE/HANDHOLE. 66 PROVIDE 24-PORT CAT6 PATCH PANEL IN EQ. RACK WITH (6) CAT 6 CABLES TO WALL MOUNTED 6-PORT SURFACE BOX. 67 WALL MOUNTED 66-BLOCKS FOR PAGING SYSTEM. 76 LOCATE DATA ADJACENT TO SECURITY PANEL. 8 62 47 1 66-BLK TMGB 66 44 76 SCP HCIC IC 67 38 45 60 46 43 TYP. 41 W TYP. 61 40 8 BLDG 3 ENLARGED IDF PLAN 1/4" = 1'-0" 07/15/15 ADDENDUM 3 05/29/15 FOR CONSTRUCTION 04/06/15 SCHEMATIC DESIGN NO. DATE DESCRIPTION OF REVISION MADE APPR'D DENVER PUBLIC SCHOOLS DEPARTMENT OF FACILITY MANAGEMENT c 2013 LOA Architecture SCHOOL DISTRICT NO. 1 DENVER, CO 9100 E. 56TH AVE. DESIGNED BY: JH DRAWN BY: JM CHECKED BY: DATE: APPROVED CONTRACT DOCUMENT SCALE: M-E 05/29/15 AS NOTED ENLARGED TECHNOLOGY PLAN ARCHITECT OF RECORD ASSOCIATE ARCHITECT H+L ARCHITECTURE LOA ARCHITECTURE 1755 BLAKE STREET, SUITE 400 480 EAST 20TH AVENUE DENVER, CO 80202 DENVER, CO 80205 P 303.298.4700 P 303.863.9080 DATE: SITE NO. 983 STAPLETON NORTHFIELD CAMPUS Submission or distribution of this drawing to meet official or regulatory requirements or for other purposes in connection with the project is not to be construed as publication in derogation of any of the rights of LOA Architecture. DEPARTMENT OF FACILITY MANAGEMENT SCHOOL NO. DWG. NO. 3-T3.01 SHEET: OF: 983_2478 This drawing is an instrument of service and shall remain the property of LOA Architecture. This drawing and the concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of LOA Architecture. DENVER PUBLIC SCHOOLS 7/14/2015 2:51:51 PM AUTHORITY _OR_ 3-T3.01 1 COMMONS C:\Revit Projects\2013\Project Path\T_DPS_COMMON_T13_mendez.rvt 1