Technical Data Power Packs PART No. FEATURES WP-PP20-D 1-Pole 120-277VAC • Designed for use with Diversa Load Voltage occupancy sensors and • 120-277 VAC Diode Pulse relays. or • 347 VAC • Single pole or 2 pole units WP-PP20-2P-D 2-Pole 120/277VAC • 120-277 VAC or 347 VAC available WP-PP20-347-D 1-Pole 347VAC SPECIFICATION • Class 1 Source • 60 Hz Switching Load • 120-277 VAC or • 347 VAC Operation The WP-PP20-D series of Power Packs work in conjunction with the Diversa Low Voltage Sensors by providing power to the sensors and receiving on/off commands from the sensor. Line-voltage ratings include 120-277 and 347. Contact Load Rating Contact Rating (1P PPK & each pole of 2P PPKs) Voltage General Tungsten Ballast 120V 20A 20A 20A 277V 20A 20A 20A 347V 20A - 15A All Power Packs provide a 24 VAC Class 2 source for use with the Low Voltage Diversa Sensors and other Diode Pulse devices. All switches or loads required to be supported by the sensor must be included in the loading capacity of the Power Pack. Maximum Load Per Input Voltage Ckt Class Max # of linked sensors 24VAC Class 2 12 • See Table for contact rating • Use #14 AWG Wire Inputs • Diode Pulse • #18AWG wire Output Power Source • 24 VAC, 150 mA • Class 2 • #18AWG wire Approvals • FCC • Title 24 Environment • Indoors, stationary, non-vibrating, noncorrosive atmosphere and noncondensing humidity • Ambient Operating Temperature: 14°F to 140°F (-10°C to 60°C) • Storage Temperature: -14°F to 140°F (-25°C to 60°C) Typical Low Voltage Loads Device Part # Ceiling Mounted Sensor WOR/WVR Wall Switch Sensor WOS/WVS Wall Mount sensor WOW/WVW Diode Pulse Switch WR-8501 Current (mA) 9.5 mA Standard 14.0 mA w/ Aux Relay 4 mA R1.3 Occupancy Sensor www.DouglasLightingControls.com Details Power Packs Wiring Instructions Terminating wire shall be a minimum of #22 AWG for control power connections and shall be suitably sized to handle the load ratings below. Electrical Connections Power Pack Connections Dimensions & Mounting The power pack can be mounted as an appendage to a standard electrical box with an integral, ½” electrical hub. The unit may also mount within a 4” square deep electrical box. WP-PP20-D / WP-PP20-347-D WP-PP20-2P-D * Application and Performance Specification Information Subject to Change without Notification R1.3 Occupancy Sensor www.DouglasLightingControls.com