Carbon Monoxide (CO) Detection Options for Schools Summary of Requirements: There are two types of systems that may be used to detect carbon monoxide and sound an alarm: 1) self-contained carbon monoxide alarms; and, 2) carbon monoxide detection systems. The use of either type of system or both types of systems, are permissible. School districts/BOCES will need to determine for themselves which system (or systems) is best suited to be used in each of their buildings. Carbon Monoxide Alarms Description: Devices that contain both a sensor to detect the presence of carbon monoxide and an integrated audible (and perhaps visual) alarm in one unit. An alarm goes off when the sensor detects CO at or above a certain concentration over a certain period of time. Minimum Requirements for Existing Buildings: Residential-style CO alarms that meet the listing label requirements of the regulation. Cannot be a combination CO/smoke alarm. No interconnection required unless one alarm is used to provide coverage for multiple detection zones served by a CO-producing HVAC system (see above). May be powered solely by at 10-year battery; or primary power from building supply (electrical) with backup from a battery (backup does not need to be a 10 year battery) Audible notification is required. The alarm must be located such that it will be heard by occupants in occupied areas of the building. Carbon Monoxide Detection Systems Description: A system that consists of separate devices (detector, notification device & control unit). One device to detect the presence of CO is interconnected with a notification device to sound an audible (and perhaps visual) alarm. The notification device is activates when the detector (sensor) detects CO at or above a certain concentration over a certain period of time. Minimum Requirement for Existing Buildings: Must comply with NFPA 720 & meet the listing labeling requirements of the regulation. Detectors, notification devices and control units are interconnected. System is interconnected with an off-site location (examples of allowable communication with off-site premises include a fire system alarm, security system, or building management system). Power supply will involve a connection to the primary building power for the system, with backup from a local battery associated with the system, or on-site building power that meets the requirements of NFPA 720. Every building with a CO source shall have a t least one notification appliance. Audible notification is required. Visual notification is required in areas where audible notification devices cannot be heard due to noisy ambient sound levels. Notification devices must be located such that it will be heard by occupants in occupied areas of the building. Any CO detection system that activates a fire signal at the fire alarm control panel must be modified so that the CO notification system does not activate the fire alarm notification devices, nor send a fire signal unless the notification and off-premises signals are distinct from those generated by the activation of a fire alarm. Alarm/Detector Locations In School Buildings Classroom Detection Zones Non-Classroom Detection Zones Every instructional space capable of being occupied by 6 or more occupants is required to be a separate classroom zone. This includes: general use classrooms, labs, shops, gyms, multipurpose rooms, and pools. Spaces may be considered classrooms, depending upon whether they are used for instructional purposes, include cafeterias and auditoriums. Each classroom zone includes any associated spaces such as toilet rooms, storage rooms, offices, locker rooms, prep rooms, and kiln rooms that open directly into classrooms. All non-instructional spaces including: boiler rooms, kitchens, receiving areas, libraries, administrative areas, corridors, offices, toilet rooms, storage rooms, and utility (electric) rooms. In buildings that do not have CO-producing HVAC system(s) serving non-classroom spaces, it is expected there will be one, nonclassroom detection zone (which may be elongated and greater than 10,000 ft2 )(see below). A single, non-classroom zone cannot incorporate more than one floor level. Each classroom zone with a CO source will receive an alarm/detector (i.e. science, home & careers) Each classroom located adjacent to a garage will receive an alarm/detector (i.e. classroom next to auto body) Single classroom spaces greater than 10,000 ft2 served by a CO-producing HVAC system – alarms must be placed so that no point in the space (zone) is greater than 100 feet from an alarm/detector. Classrooms with duplicate types of CO sources (i.e. a science lab with gas outlets also served by a COproducing HVAC system): o an alarm/detector installed in the first space served by a fuel-fired HVAC system will not need to be duplicated by a second alarm/detector in the same space where the first space served has its own CO source o Where a non-fuel fired HVAC system supplies air from a space with a CO source to other spaces without a source, the first space(s) Each non-classroom zone with a CO source (i.e. boiler room, kitchen) will receive an alarm/detector (a nonclassroom zone may contain multiple CO sources). A garage located adjacent to a non-classroom zone will be considered a CO source for that zone. Non-classroom zones greater than 10,000 ft2 with CO sources that are not CO-producing HVAC systems – one detector/alarm will be installed in each space with a CO source, and one detector/alarm will be installed in a location outside of each source area at an approved location (generally the detector/alarm outside the source area will be located between the source and the bulk of the building occupants – i.e. the hallway outside a boiler room). served will be considered to be the space(s) containing the CO sources. A signal will be transmitted, as required for CO-producing HVAC systems (see section below). For spaces served by a Carbon Monoxide-Producing HVAC system (defined as: fuel-fired heating/ventilation systems or makeup air units including rooftop or ground mounted units; or non-fuel-fired heating/ventilating/AC systems that supply air from a space with a CO source to other spaces without a CO source) : Provide an alarm in each space served by the CO-producing HVAC system; or Provide a CO alarm/detector in the first room or area served by the unit/ CO source and signals from the CO alarm/detector in the first room or area are automatically transmitted to an ‘approved location’ (a space in which the alarm/detector is located, and is normally staffed by school personnel during normal school hours, or a corridor in the area of the spaces served by the CO-producing HVAC system). If the CO-producing HVAC system serves: o A single space (classroom or non-classroom), that space is a single detection zone o Multiple classrooms – each classroom is an independent detection zone o Multiple non-classrooms located on the same floor level – all are considered one non-classroom zone o Multiple non-classroom spaces located on different floor levels – spaces on each floor are considered separate non-classroom zones. o A mixture of classroom and non-classroom spaces – all non-classroom spaces are considered single zones by floor; each classroom is considered a separate zone.