CHAPTER 8 CHIMNEYS AND VENTS Note: Portions of this chapter have been reproduced in their entirety from NFPA 54-2006 (ANSI Z223.1). 801.0 Scope. The requirements of this chapter shall govern the venting of fuel-burning appliances. 801.1 Venting of Gas Appliances. Low-heat gas appliances shall be vented in accordance with this chapter. Other gas appliances shall be vented in accordance with NFPA 211 or other applicable standards. 801.2 Appliances Fueled by Other Fuels. Appliances fueled by fuels other than gas shall be vented in accordance with NFPA 211 and the appliance manufacturer’s instructions. 802.0 General. 802.1 This section recognizes that the choice of venting materials and the methods of installation of venting systems are dependent on the operating characteristics of the gas utilization equipment. The operating characteristics of vented gas utilization equipment can be categorized with respect to (1) positive or negative pressure within the venting system, and (2) whether or not the equipment generates flue or vent gases that can condense in the venting system. See Section 224.0 for the definition of these vented appliance categories. [NFPA 54:12.2] 802.2 Specification for Venting. 802.2.1 Connection to Venting Systems. Except as permitted in Section 802.2.2 through 802.2.6, all gas utilization equipment shall be connected to venting systems. [NFPA 54:12.3.1] 802.2.2 Equipment Not Required to Be Vented. The following equipment shall not be required to be vented [NFPA 54:12.3.2]: 802.2.2.1 Listed ranges. [NFPA 54:12.3.2(1)] 802.2.2.2 Built-in domestic cooking units listed and marked for optional venting. [NFPA 54:12.3.2(2)] 802.2.2.3 Listed hot plates and listed laundry stoves. [NFPA 54:12.3.2(3)] 802.2.2.4 Listed Type 1 clothes dryers exhausted in accordance with Section 504.3.2. [NFPA 54:12.3.2(4)] 802.2.2.5 A single listed booster-type (automatic instantaneous) water heater, when designed and used solely for the sanitizing rinse requirements of a dishwashing machine, provided that the equipment is installed with the draft hood in place and unaltered, if a draft hood is required, in a commercial kitchen having a mechanical exhaust system; where installed in this manner, the draft hood outlet shall not be less than thirty-six (36) inches (910 mm) vertically and six (6) inches (150 mm) horizontally from any surface other than the equipment. [NFPA 54:12.3.2(5)] 802.2.2.6 Listed refrigerators. [NFPA 54:12.3.2(6)] 802.2.2.7 Counter appliances. [NFPA 54:12.3.2(7)] 802.2.2.8 Room heaters listed for unvented use (see Sections 924.1 and 924.2). [NFPA 54:12.3.2(8)] 802.2.2.9 Direct gas-fired makeup air heaters. [NFPA 54:12.3.2(9)] 802.2.2.10 Other equipment listed for unvented use and not provided with flue collars. [NFPA 54:12.3.2(10)] 8 0 2 . 2 . 2 . 1 1 Specialized equipment of limited input such as laboratory burners or gas lights. [NFPA 54:12.3.2(11)] Where any or all of this equipment in Sections 802.2.2.5 through 802.2.2.11 is installed so the aggregate input rating exceeds 20 Btu/h/ft.3 (207 W/m3) of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for removing the vent gases to the outside atmosphere so the aggregate input rating of the remaining unvented equipment does not exceed 20 Btu/h/ft 3 (207 W/m 3). Where the calculation includes the volume of an adjacent room or space, the room or space in which the equipment is installed shall be directly connected to the adjacent room or space by a doorway, archway, or other opening of comparable size that cannot be closed. [NFPA 54:12.3.1] 802.2.3 Ventilating Hoods. Ventilating hoods and exhaust systems shall be permitted to be 111 802.2 – 802.4 used to vent gas utilization equipment installed in commercial applications (see Section 802.3.5) and to vent industrial equipment, particularly where the process itself requires fume disposal. [NFPA 54:12.3.3] 802.2.4 Well-Ventilated Spaces. The operation of industrial gas utilization equipment such that its flue gases are discharged directly into a large and well-ventilated space shall be permitted. [NFPA 54:12.3.4] 802.2.5 Direct-Vent Equipment. Listed directvent gas utilization equipment shall be considered properly vented where installed in accordance with the terms of its listing, the manufacturers' instructions, and Section 802.8.3. 802.2.6 Equipment with Integral Vents. Gas utilization equipment incorporating integral venting means shall be considered properly vented where installed in accordance with its listing, the manufacturers' instructions, and Sections 802.8.1 and 802.8.2. [NFPA 54:12.3.6] 802.3 Design and Construction. 802.3.1 Minimum Safe Performance. A venting system shall be designed and constructed so as to develop a positive flow adequate to remove flue or vent gases to the outside atmosphere. [NFPA 54:12.1] 802.3.2 Equipment Draft Requirements. A venting system shall satisfy the draft requirements of the equipment in accordance with the manufacturer's instructions. [NFPA 54:12.4.1] 802.3.3 Design and Construction. Gas utilization equipment required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Sections 802.4 through 802.15. [NFPA 54:12.4.2] 802.3.4 Mechanical Draft Systems. 802.3.4.1 Mechanical draft systems shall be listed and shall be installed in accordance with the terms of their listing and both the appliance and the mechanical draft system manufacturers' instructions. [NFPA 54:12.4.3.1] 802.3.4.2 Gas utilization equipment requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. [NFPA 54:12.4.3.2] Exception: Incinerators. 802.3.4.3 Forced draft systems and all portions of induced draft systems under positive pressure during operation shall be 112 2007 CALIFORNIA MECHANICAL CODE designed and installed so as to prevent leakage of flue or vent gases into a building. [NFPA 54:12.4.3.3] 802.3.4.4 Vent connectors serving equipment vented by natural draft shall not be connected into any portion of mechanical draft systems operating under positive pressure. [NFPA 54:12.4.3.4] 802.3.4.5 Where a mechanical draft system is employed, provision shall be made to prevent the flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the equipment for safe performance. [NFPA 54:12.4.3.5] 802.3.4.6 The exit terminals of mechanical draft systems shall be not less than seven (7) feet (2.1 m) above grade where located adjacent to public walkways and shall be located as specified in Sections 802.8.1 and 802.8.2. [NFPA 54:12.4.3.6] 802.3.5 Ventilating Hoods and Exhaust Systems. 802.3.5.1 Ventilating hoods and exhaust systems shall be permitted to be used to vent gas utilization equipment installed in commercial applications. [NFPA 54:12.4.4.1] 802.3.5.2 Where automatically operated gas utilization equipment is vented through a ventilating hood or exhaust system equipped with a damper or with a power means of exhaust, provisions shall be made to allow the flow of gas to the main burners only when the damper is open to a position to properly vent the equipment and when the power means of exhaust is in operation. [NFPA 54:12.4.4.2] 802.3.6 Circulating Air Ducts and Furnace Plenums. No portion of a venting system shall extend into or pass through any circulating air duct or furnace plenum. [NFPA 54:12.4.5.1] 802.4 Type of Venting System to Be Used. 802.4.1 The type of venting system to be used shall be in accordance with Table 8-1. [NFPA 54:12.5.1] 802.4.2 Plastic Piping. Plastic piping used for venting equipment listed for use with such venting materials shall be approved. [NFPA 54:12.5.2] 802.4.3 Special Gas Vent. A special gas vent shall be listed and installed in accordance with the terms of the special gas vent listing and the manufacturers' instructions. [NFPA 54:12.5.3] CHIMNEYS AND VENTS 802.5 Masonry, Metal, and Factory-Built Chimneys. 802.5.1 Listing or Construction. 802.5.1.1 Factory-built chimneys shall be installed in accordance with their listing and the manufacturers' instructions. Factorybuilt chimneys used to vent appliances that operate at positive vent pressure shall be listed for such application. [NFPA 54:12.6.1.1] 802.5.1.2 Metal chimneys shall be built and installed in accordance with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid-Fuel-Burning Appliances. [NFPA 54:12.6.1.2] 802.5.1.3 Masonry chimneys shall be built and installed in accordance with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid-Fuel-Burning Appliances, and lined with an approved clay flue lining, a listed chimney lining system, or other approved material that will resist corrosion, erosion, softening, or cracking from vent gases at temperatures up to 1,800°F (982°C). [NFPA 54:12.6.1.3] Exception: Masonry chimney flues lined with a chimney lining system specifically listed for use with listed gas appliances with draft hoods, Category I appliances, and other gas appliances listed for use with Type B vents shall be permitted. The liner shall be installed in accordance with the liner manufacturer's instructions and the terms of the listing. A permanent identifying label shall be attached at the point where the connection is to be made to the liner. The label shall read: "This chimney liner is for appliances that burn gas only. Do not connect to solid or liquidfuel-burning appliances or incinerators." 802.5.2 Termination. 802.5.2.1 A chimney for residential-type or low-heat gas utilization equipment shall extend at least three (3) feet (0.9 m) above the highest point where it passes through a roof of a building and at least two (2) feet (0.6 m) higher than any portion of a building within a horizontal distance of ten (10) feet (3.0 m). (See Figure 8-1.) [NFPA 54:12.6.2.1] 802.5 – Table 8-1 TABLE 8-1 Type of Venting System to Be Used Gas Utilization Equipment Listed Category I equipment Listed equipment equipped with draft hood Equipment listed for use with Type B gas vent Listed vented wall furnaces Category II equipment Category III equipment Category IV equipment Incinerators, outdoors Type of Venting System Type B gas vent (802.6) Chimney (802.5) Single-wall metal pipe (802.7) Listed chimney lining system for gas venting (802.5.1.3) Special gas vent listed for this equipment (802.4.3) Type B-W gas vent (802.6, 928.0) As specified or furnished by manufacturers of listed equipment (802.4.2, 802.4.3) Single-wall metal pipe (802.7, 802.7.3.3) Incinerators, indoors Chimney (802.5) Equipment that can be Type L vent (802.6) or converted to use of solid fuel chimney (802.5) Unlisted combination gas- and oil-burning equipment Combination gas- and solid-fuelburning equipment Equipment listed for use with chimneys only Unlisted equipment Listed combination gas- and oil-burning equipment Decorative appliance in vented Chimney [907.2(3)] fireplace Gas-fired toilets Single-wall metal pipe (802.7, 926.3) Direct-vent equipment See 802.2.5 Equipment with integral vent See 802.2.6 [NFPA 54: Table 12.5.1] 113 Figure 8-1 – 802.5 2007 CALIFORNIA MECHANICAL CODE 802.5.2.2 A chimney for medium-heat equipment shall extend at least ten (10) feet (3.0 m) higher than any portion of any building within twenty-five (25) feet (7.6 m). [NFPA 54:12.6.2.2] 802.5.2.3 A chimney shall extend at least five (5) feet (1.5 m) above the highest connected equipment draft hood outlet or flue collar. [NFPA 54:12.6.2.3] 802.5.2.4 Decorative shrouds shall not be installed at the termination of factory-built chimneys except where such shrouds are listed and labeled for use with the specific factory-built chimney system and are installed in accordance with manufacturers' installation instructions. [NFPA 54:12.6.2.4] 802.5.3 Size of Chimneys. The effective area of a chimney venting system serving listed gas appliances with draft hoods, Category I appliances, and other appliances listed for use with Type B vents shall be in accordance with one of the following methods [NFPA 54:12.6.3.1]: (1) Section 803.0. [NFPA 54:12.6.3.1(1)] (2) For sizing an individual chimney venting system for a single appliance with a draft hood, the effective areas of the vent connector and chimney flue shall be not less than the area of the appliance flue collar or draft hood outlet or greater than seven times the draft hood outlet area. [NFPA 54:12.6.3.1(2)] (3) For sizing a chimney venting system connected to two appliances with draft hoods, the effective area of the chimney flue shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet, or greater than seven times the smallest draft hood outlet area. [NFPA 54:12.6.3.1(3)] (4) Other approved engineering methods. [NFPA 54:12.6.3.1(5)] (5) Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. [NFPA 54:12.6.3.1(4)] FIGURE 8-1 Typical Termination Locations for Chimneys and Single-Wall Metal Pipes Serving Residential-Type and Low-Heat Equipment. [NFPA 54: Figure 12.6.2.1] 114 802.5.4.1 Where an incinerator is vented by a chimney serving other gas utilization equipment, the gas input to the incinerator shall not be included in calculating chimney size, provided the chimney flue diameter is not less than one (1) inch (25 mm) larger in CHIMNEYS AND VENTS equivalent diameter than the diameter of the incinerator flue outlet. [NFPA 54:12.6.3.2] 802.5.4 Inspection of Chimneys. 802.5.4.1 Before replacing an existing appliance or connecting a vent connector to a chimney, the chimney passageway shall be examined to ascertain that it is clear and free of obstructions and shall be cleaned if previously used for venting solid- or liquidfuel-burning appliances or fireplaces. [NFPA 54:12.6.4.1] 802.5.4.2 Chimneys shall be lined in accordance with NFPA 211, Standard for Chimneys, Fireplaces, Vents and Solid FuelBurning Appliances. [NFPA 54:12.6.4.2] 802.5.4.3 Cleanouts shall be examined to determine they will remain tightly closed when not in use. [NFPA 54:12.6.4.3] 802.5.4.4 When inspection reveals that an existing chimney is not safe for the intended application, it shall be repaired, rebuilt, lined, relined, or replaced with a vent or chimney to conform to NFPA 211, Standard for Chimneys, Fireplaces, Vents, and SolidFuel-Burning Appliances, and shall be suitable for the equipment to be attached. [NFPA 54:12.6.4.4] 802.5.5 Chimney Serving Equipment Burning Other Fuels. 802.5.5.1 Gas utilization equipment shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. 802.5.5.2 Where one chimney serves gas utilization equipment and equipment burning liquid fuel, the equipment shall be connected through separate openings or shall be connected through a single opening where joined by a suitable fitting located as close as practical to the chimney. Where two or more openings are provided into one chimney flue, they shall be at different levels. Where the gas utilization equipment is automatically controlled, it shall be equipped with a safety shutoff device. 802.5.5.3 A listed combination gas and solidfuel-burning appliance connected to a single chimney flue shall be equipped with a manual reset device to shut off gas to the main burner in the event of sustained backdraft or flue gas spillage. The chimney flue shall be sized to properly vent the appliance. 802.5 – 802.6 802.5.5.4 A single chimney flue serving a listed combination gas and oil-burning appliance shall be sized to properly vent the appliance. 802.5.6 Support of Chimneys. All portions of chimneys shall be supported for the design and weight of the materials employed. Listed factory-built chimneys shall be supported and spaced in accordance with their listings and the manufacturers' instructions. 802.5.7 Cleanouts. Where a chimney that formerly carried flue products from liquid-or solid-fuel-burning appliances is used with an appliance using fuel gas, an accessible cleanout shall be provided. The cleanout shall have a tight-fitting cover and be installed so its upper edge is at least six (6) inches (150 mm) below the lower edge of the lowest chimney inlet opening. 802.5.8 Space Surrounding Lining or Vent. The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry chimney flue shall not be used to vent another appliance. Exception: The insertion of another liner or vent within the chimney as provided in this code and the liner or vent manufacturer's instructions. The remaining space surounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal or factorybuilt chimney flue shall not be used to supply combustion air. Exception: Direct vent gas-fired appliances designed for installation in a solid-fuelburning fireplace where installed in accordance with the listing and the manufacturer’s instruction. [NFPA 54:10.5] 802.6 Gas Vents. 802.6.1 A gas vent passing through a roof shall extend through the entire roof flashing, roof jack, or roof thimble and be terminated with a listed termination cap. 802.6.1.1 Type B or Type L vents shall extend in a generally vertical direction with offsets not exceeding 45 degrees, except that a vent system having not more than one 60 degree offset shall be permitted. Any angle greater than 45 degrees from the vertical is considered horizontal. The total horizontal distance of a vent plus the horizontal vent connector serving draft hood equipped appliances shall not be greater than 75 percent of the vertical height of the vent. 115 802.6 Exception: Systems designed and sized as provided in Section 803.0 or in accordance with other approved engineering methods. Vents serving Category I fan-assisted appliances shall be installed in accordance with the appliance manufacturer's instructions and Section 803.0 or other approved engineering methods. 802.6.2 A gas vent shall terminate in accordance with one of the following: (1) Above the roof surface with a listed cap or listed roof assembly. Gas vents twelve (12) inches (300 mm) in size or smaller with listed caps shall be permitted to be terminated in accordance with Figure 8-2, provided they are at least eight (8) feet (2.4 m) from a vertical wall or similar obstruction. All other gas vents shall terminate not less than two (2) feet (0.6 m) above the highest point where they pass through the roof and at least two (2) feet (0.6 m) higher than any portion of a building within ten (10) feet (3.1 m). (2) Industrial gas utilization equipment as provided in Section 802.2.4. 2007 CALIFORNIA MECHANICAL CODE (3) Direct-vent systems as provided in Section 802.2.5. (4) Equipment with integral vents as provided in Section 802.2.6. (5) Mechanical draft systems as provided in Section 802.3.4. (6) Ventilating hoods and exhaust systems as provided in Section 802.3.5. 802.6.2.1 A Type B or a Type L gas vent shall terminate at least five (5) feet (1.5 m) in vertical height above the highest connected equipment draft hood or flue collar. 802.6.2.2 A Type BW gas vent shall terminate at least twelve (12) feet (3.7 m) in vertical height above the bottom of the wall furnace. 802.6.2.3 A gas vent extending through an exterior wall shall not terminate adjacent to the wall or below eaves or parapets, except as provided in Sections 802.2.5 and 802.3.4. 802.6.2.4 Decorative shrouds shall not be installed at the termination of gas vents except where such shrouds are listed for use with the specific gas venting system and are installed in accordance with manufacturers' installation instructions. 802.6.2.5 All gas vents shall extend through the roof flashing, roof jack, or roof thimble and terminate with a listed cap or listed roof assembly. [NFPA 54:12.7.2 (6)] 802.6.2.6 A gas vent shall terminate at least three (3) feet (0.9 m) above a forced air inlet located within ten (10) feet (3.0 m). [NFPA 54:12.7.2 (7)] 802.6.3 Size of Gas Vents. Venting systems shall be sized and constructed in accordance with Section 803.0 or other approved engineering methods and the gas vent and gas equipment manufacturers' instructions. 802.6.3.1 Category I Appliances. The sizing of natural draft venting systems serving one or more listed appliances equipped with a draft hood or appliances listed for use with Type B gas vent, installed in a single story of a building, shall be in accordance with one of the following methods. FIGURE 8-2 Gas Vent Termination Locations for Listed Caps 12 in. (300 mm) or Less in Size at Least 8 ft. (2.4 m) from a Vertical Wall. [NFPA 54: Figure 10.6.2] 116 (1) The provisions of Section 803.0. (2) Vents serving fan-assisted combustion system appliances, or combinations of fan-assisted combustion system and draft hood-equipped appliances shall be CHIMNEYS AND VENTS sized in accordance with Section 803.0 or other approved engineering methods. (3) For sizing an individual gas vent for a single, draft hood-equipped appliance, the effective area of the vent connector and the gas vent shall be not less than the area of the appliance draft hood outlet or greater than seven times the draft hood outlet area. (4) For sizing a gas vent connected to two appliances, with draft hoods, the effective area of the vent shall be not less than the area of the larger draft hood outlet plus 50 percent of the area of the smaller draft hood outlet or greater than seven times the smaller draft hood outlet area. (5) Approved engineering practices. 802.6.3.2 Category II, Category III, and Category IV Appliances. The sizing of gas vents for Category II, Category III, and Category IV gas utilization equipment shall be in accordance with the equipment manufacturers' instructions. 802.6.3.3 Sizing. Chimney venting systems using mechanical draft shall be sized in accordance with approved engineering methods. 802.6 802.6.4 Gas Vents Serving Equipment on More Than One Floor. A common gas vent shall be permitted in multistory installations to vent Category I gas utilization equipment located on more than one floor level, provided the venting system is designed and installed in accordance with approved engineering methods. For the purpose of this section, crawl spaces, basements, and attics shall be considered as floor levels. All gas utilization equipment connected to the common vent shall be located in rooms separated from habitable space. Each of these rooms shall have provisions for an adequate supply of combustion, ventilation, and dilution air that is not supplied from habitable space. (See Figure 8-3.) The size of the connectors and common segments of multistory venting systems for gas utilization equipment listed for use with Type B double-wall gas vent shall be in accordance with Table 8-10, provided: (1) The available total height (H) for each segment of a multistory venting system is the vertical distance between the level of the highest draft hood outlet or flue collar on that floor and the centerline of the next highest interconnection tee. (See Figure 8-4.) (2) The size of the connector for a segment is determined from its gas utilization equipment heat input and available connector rise, and shall not be smaller than the draft hood outlet or flue collar size. (3) The size of the common vertical vent segment, and of the interconnection tee at the base of that segment, shall be based on the total gas utilization equipment heat input entering that segment and its available total height. 802.6.5 Support of Gas Vents. Gas vents shall be supported and spaced in accordance with their listings and the manufacturers' instructions. FIGURE 8-3 Plan View of Practical Separation Method for Multistory Gas Venting. [NFPA 54: Figure 810.6.4] 802.6.6 Marking. In those localities where solid and liquid fuels are used extensively, gas vents shall be permanently identified by a label attached to the wall or ceiling at a point where the vent connector enters the gas vent. The label shall read: "This gas vent is for appliances that burn gas. Do not connect to solid or liquid-fuelburning appliances or incinerators." The Authority Having Jurisdiction shall determine whether its area constitutes such a locality. [NFPA 54:10.6] 117 2007 CALIFORNIA MECHANICAL CODE Table 8-2 – 802.7 Equipment Listed equipment with draft hoods and equipment listed for use with Type B gas vents TABLE 8-2 Clearance for Connectors Minimum Distance from Combustible Material Listed Type B Gas Vent Material As listed Listed Type L Vent Material As listed Single-Wall Metal Pipe 6 in. Factory-Built Chimney Sections As listed Residential boilers and furnaces with listed gas conversion burner and with draft hood 6 in. 6 in. 9 in. As listed Not permitted As listed 9 in. As listed Residential incinerators Not permitted 9 in. 18 in. As listed Unlisted residential appliances with draft hood Not permitted 6 in. 9 in. As listed Residential appliances listed for use with Type L vents Listed gas-fired toilets Residential and low-heat equipment other than those above Medium-heat equipment Not permitted As listed As listed As listed Not permitted 9 in. 18 in. As listed Not permitted Not permitted 36 in. As listed For SI units, 1 in.= 25.4 mm. Note: These clearances shall apply unless the listing of an appliance or connector specifies clearances, in which case the listed clearances shall apply. [NFPA 54: Table 10.7.4.4] 802.7 Single-Wall Metal Pipe. 802.7.1 Construction. Single-wall metal pipe shall be constructed of galvanized sheet steel not less than 0.0304 inch (0.7 mm) thick or of other approved, noncombustible, corrosion-resistant material. 802.7.2 Cold Climate. Uninsulated single-wall metal pipe shall not be used outdoors in cold climates for venting gas utilization equipment in regions where the 99 percent winter design temperature is below 32 degrees Fahrenheit. [NFPA 54:12.8.2] 802.7.3 Termination. The termination of singlewall metal pipe shall comply with the following requirements: 802.7.3.1 Single-wall metal pipe shall terminate at least five (5) feet (1.5 m) in vertical height above the highest connected equipment draft hood outlet or flue collar. 802.7.3.2 Single-wall metal pipe shall extend at least two (2) feet (0.6 m) above the 118 highest point where it passes through a roof of a building and at least two (2) feet (0.6 m) higher than any portion of a building within a horizontal distance of ten (10) feet (3.1 m). (See Figure 8-1.) 802.7.3.3 An approved cap or roof assembly shall be attached to the terminus of a singlewall metal pipe. (Also see Section 802.7.4.3.) 802.7.4 Installation with Equipment Permitted by Section 802.4.1. 802.7.4.1 Single-wall metal pipe shall be used only for runs directly from the space in which the gas utilization equipment is located through the roof or exterior wall to the outer air. A pipe passing through a roof shall extend without interruption through the roof flashing, roof jacket, or roof thimble. 802.7.4.2 Single-wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through CHIMNEYS AND VENTS any attic, inside wall, concealed space, or floor. For the installation of a single-wall metal pipe through an exterior combustible wall see Section 802.10.14.2. 802.7.4.3 Single-wall metal pipe used for venting an incinerator shall be exposed and readily examinable for its full length and shall have suitable clearances maintained. 802.7.4.4 Minimum clearances from singlewall metal pipe to combustible material shall be in accordance with Table 8-2. Reduced clearances from single-wall metal pipe to combustible material shall be as specified for vent connectors in Table 5-3. 802.7.4.5 Where a single-wall metal pipe passes through a roof constructed of combustible material, a noncombustible, nonventilating thimble shall be used at the point of passage. The thimble shall extend at least eighteen (18) inches (460 mm) above and six (6) inches (150 mm) below the roof, with the annular space open at the bottom and closed only at the top. The thimble shall be sized in accordance with Section 802.10.14.2. 802.7.5 Size of Single-Wall Metal Pipe. Singlewall metal piping shall comply with the following requirements: 802.7.5.1 A venting system of a single-wall metal pipe shall be sized in accordance with one of the following methods and the gas equipment manufacturer's instructions: (1) For a draft hood–equipped appliance, in accordance with Section 803.0. (2) For a venting system for a single appliance with a draft hood, the areas of the connector and the pipe each shall not be less than the area of the appliance flue collar or draft hood outlet, whichever is smaller. The vent area shall not be greater than seven times the draft hood outlet area. (3) Other approved engineering methods. 802.7.5.2 Where a single-wall metal pipe is used and has a shape other than round, it shall have an equivalent effective area equal to the effective area of the round pipe for which it is substituted, and the minimum internal dimension of the pipe shall be two (2) inches (50 mm). 802.7.5.3 The vent cap or a roof assembly shall have a venting capacity not less than that of the pipe to which it is attached. 802.7 – 802.9 802.7.6 Support of Single-Wall Metal Pipe. All portions of single-wall metal pipe shall be supported for the design and weight of the material employed. 802.7.7 Marking. Single-wall metal pipe shall comply with the marking provisions of Section 802.6.6. [NFPA 54:10.7] 802.8 Through-the-Wall Vent Termination. 802.8.1 A mechanical draft venting system shall terminate at least three (3) feet (0.9 m) above any forced air inlet located within ten (10) feet (3.1 m). Exception 1: This provision shall not apply to the combustion-air intake of a direct-vent appliance. Exception 2: This provision shall not apply to the separation of the integral outdoor-air inlet and flue gas discharge of listed outdoor appliances. 802.8.2 A mechanical draft venting system of other than direct-vent type shall terminate at least four (4) feet (1.2 m) below, four (4) feet (1.2 m) horizontally from, or one (1) feet (300 mm) above any door, operable window, or gravity air inlet into any building. The bottom of the vent terminal shall be located at least twelve (12) inches (300 mm) above grade. 802.8.3 The vent terminal of a direct-vent appliance with an input of 10,000 Btu/h (3 kW) or less shall be located at least six (6) inches (150 mm) from any air opening into a building, and such an appliance with an input over 10,000 Btu/h (3 kW) but not over 50,000 Btu/h (14.7 kW) shall be installed with a nine (9) inches (230 mm) vent termination clearance, and an appliance with an input over 50,000 Btu/h (14.7 kW) shall have at least a twelve (12) inches (300 mm) vent termination clearance. The bottom of the vent terminal and the air intake shall be located at least twelve (12) inches (300 mm) above grade. 802.8.4 Through-the-wall vents for Category II and Category IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment. Where local experience indicates that condensate is a problem with Category I and Category III appliances, this provision shall also apply. [NFPA 54:10.8] 802.9 Condensation Drain. 802.9.1 Provision shall be made to collect and 119 802.9 – 802.10 dispose of condensate from venting systems serving Category II and Category IV gas utilization equipment and noncategorized condensing appliances in accordance with Section 802.8.4. 802.9.2 Where local experience indicates that condensation is a problem, provision shall be made to drain off and dispose of condensate from venting systems serving Category I and Category III gas utilization equipment in accordance with Section 802.8.4. [NFPA 54:10.9] 802.10 Vent Connectors for Category I Gas Utilization Equipment. 802.10.1 Where Required. A vent connector shall be used to connect gas utilization equipment to a gas vent, chimney, or singlewall metal pipe, except where the gas vent, chimney, or single-wall metal pipe is directly connected to the equipment. 802.10.2 Materials. 802.10.2.1 A vent connector shall be made of noncombustible, corrosion-resistant material capable of withstanding the vent gas temperature produced by the gas utilization equipment and of sufficient thickness to withstand physical damage. 802.10.2.2 Where the vent connector used for gas utilization equipment having a draft hood or a Category I appliance is located in or passes through an unconditioned area, that portion of the vent connector shall be listed Type B, listed Type L, or listed vent material having equivalent insulation qualities. Exception: Single-wall metal pipe located within the exterior walls of the building and located in areas having a local 99 percent winter design temperature of 5˚ F or higher. 802.10.2.3 Where the vent connector used for gas utilization equipment having a draft hood or a Category I appliance is located in or passes through attics and crawl spaces, that portion of the vent connector shall be listed Type B, listed Type L, or listed vent material having equivalent insulation qualities. 802.10.2.4 Vent connectors for residentialtype appliances shall comply with the following: (1) Vent connectors for listed gas appliances having draft hoods and for appliances having draft hoods and equipped with listed conversion burners that are not installed in attics, 120 2007 CALIFORNIA MECHANICAL CODE crawl spaces, or other unconditioned areas shall be one of the following: (a) Type B or Type L vent material. (b) Galvanized sheet steel not less than 0.018 in. (0.46 mm) thick. (c) Aluminum (1100 or 3003 alloy or equivalent) sheet not less than 0.027 in. (0.69 mm) thick. (d) Stainless steel sheet not less than 0.012 in. (0.31 mm) thick. (e) Smooth-interior-wall metal pipe having resistance to heat and corrosion equal to or greater than that of b, c, or d above. (f) A listed vent connector. (2) Vent connectors shall not be covered with insulation. Exception: Listed insulated vent connectors shall be installed according to the terms of their listing. 802.10.2.5 A vent connector for nonresidential low-heat equipment shall be a factory-built chimney section or steel pipe having resistance to heat and corrosion equivalent to that for the appropriate galvanized pipe as specified in Table 8-3. Factory-built chimney sections shall be joined together in accordance with the chimney manufacturer's instructions. [NFPA 54: 12.11.2.5] 802.10.2.6 Vent connectors for mediumheat equipment and commercial and industrial incinerators shall be constructed of factory-built, medium-heat chimney sections or steel of a thickness not less than that specified in Table 8-4, and shall comply with the following: (1) A steel vent connector for equipment with a vent gas temperature in excess of 1000°F (538°C) measured at the entrance to the connector shall be lined with medium-duty fire brick (ASTM C 64, Specification for Refractories for Incinerators and Boilers, Type F) or the equivalent. (2) The lining shall be at least 2-1/2 inches (64 mm) thick for a vent connector having a diameter or greatest cross-sectional dimension of eighteen (18) inches (460 mm) or less. (3) The lining shall be at least 4-1/2 inches (110 mm) thick laid on the 4-1/2 inches (110 mm) bed for a vent connector having CHIMNEYS AND VENTS diameter or greatest cross-sectional dimension greater than eighteen (18) inches (460 mm). (4) Factory-built chimney sections, if employed, shall be joined together in accordance with the chimney manufacturer's instructions. TABLE 8-3 Minimum Thickness for Galvanized Steel Vent Connectors for Low-Heat Appliances Diameter of Connector (in.) Minimum Thickness (in.) Less than 6 0.019 6 to less than 10 0.023 10 to 12 inclusive 0.029 14 to 16 inclusive 0.034 Over 16 0.056 For SI units, 1 in. = 25.4 mm; 1 in.2 = 645 mm2. [NFPA 54: Table 10.10.2.5] TABLE 8-4 Minimum Thickness for Steel Vent Connectors for Medium-Heat Equipment and Commercial and Industrial Incinerators Vent Connector Size Diameter (in.) Up to 14 Over 14 to 16 Over 16 to 18 Over 18 Minimum Area (in. ) Thickness (in.) 154 to 201 0.067 2 Up to 154 201 to 254 Larger than 254 0.053 0.093 0.123 For SI units, 1 in. = 25.4 mm; 1 in.2 = 645 mm2. [NFPA 54: Table 10.10.2.6] 802.10.3 Size of Vent Connector. 802.10.3.1 A vent connector for gas utilization equipment with a single draft hood or for a Category I fan-assisted combustion system appliance shall be sized and installed in accordance with Section 803.0 or other approved engineering methods. 802.10.3.2 For a single appliance having more than one draft hood outlet or flue collar, the manifold shall be constructed according to the instructions of the appliance manufacturer. Where there are no instructions, the manifold 802.10 shall be designed and constructed in accordance with approved engineering practices. As an alternate method, the effective area of the manifold shall equal the combined area of the flue collars or draft hood outlets and the vent connectors shall have a minimum one (1) foot (0.3 m) rise. 802.10.3.3 Where two or more gas appliances are connected to a common vent or chimney, each vent connector shall be sized in accordance with Section 803.0 or other approved engineering methods. As an alternative method applicable only when all of the appliances are draft hood equipped, each vent connector shall have an effective area not less than the area of the draft hood outlet of the appliance to which it is connected. 802.10.3.4 Where two or more gas appliances are vented through a common vent connector or vent manifold, the common vent connector or vent manifold shall be located at the highest level consistent with available headroom and clearance to combustible material and shall be sized in accordance with Section 803.0 or other approved engineering methods. As an alternate method applicable only where there are two draft hood–equipped appliances, the effective area of the common vent connector or vent manifold and all junction fittings shall be not less than the area of the larger vent connector plus 50 percent of the areas of smaller flue collar outlets. 802.10.3.5 Where the size of a vent connector is increased to overcome installation limitations and obtain connector capacity equal to the equipment input, the size increase shall be made at the equipment draft hood outlet. 802.10.4 Two or More Appliances Connected to a Single Vent. 802.10.4.1 Where two or more vent connectors enter a common gas vent, chimney flue, or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material. 802.10.4.2 Vent connectors serving Category I appliances shall not be connected to any portion of a mechanical draft system operating under positive static pressure, such as those serving Category III or Category IV appliances. 802.10.5 Clearance. Minimum clearances from vent connectors to combustible material shall be in accordance with Table 8-2. 121 802.10 Exception: The clearance between a vent connector and combustible material shall be permitted to be reduced where the combustible material is protected as specified for vent connectors in Table 5-3. 802.10.6 Avoid Unnecessary Bends. A vent connector shall be installed so as to avoid turns or other construction features that create excessive resistance to flow of vent gases. 802.10.7 Joints. Joints between sections of connector piping and connections to flue collars or draft hood outlets shall be fastened in accordance with one of the following methods: (1) By sheet metal screws. (2) Vent connectors of listed vent material shall be assembled and connected to flue collars or draft hood outlets in accordance with the manufacturers' instructions. (3) Other approved means. 802.10.8 Slope. A vent connector shall be installed without any dips or sags and shall slope upward toward the vent or chimney at least 1/4 in./ft. (20 mm/m). Exception: Vent connectors attached to a mechanical draft system installed in accordance with the manufacturers' instructions. 802.10.9 Length of Vent Connector. 802.10.9.1 A vent connector shall be as short as practical, and the gas utilization equipment located as close as practical to the chimney or vent. 802.10.9.2 The maximum horizontal length of a single-wall connector shall be 75 percent of the height of the chimney or vent except for engineered systems. The maximum length of an individual connector for a chimney or vent system serving multiple appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent. [NFPA 54:12.11.9.2] 802.10.9.3 The maximum horizontal length of a Type B double-wall connector shall be 100 percent of the height of the chimney or vent, except for engineered systems. The maximum length of an individuall connector for a chimney or vent system serving multiple appliances, from the appliance outlet to the junction with the common vent or another connector, shall be 100 percent of the height of the chimney or vent. [NFPA 54: 12.11.9.3] 802.10.10 Support. A vent connector shall be supported for the design and weight of the 122 2007 CALIFORNIA MECHANICAL CODE material employed to maintain clearances and prevent physical damage and separation of joints. 802.10.11 Chimney Connection. Where entering a flue in a masonry or metal chimney, the vent connector shall be installed above the extreme bottom to avoid stoppage. Where a thimble or slip joint is used to facilitate removal of the connector, the connector shall be firmly attached to or inserted into the thimble or slip joint to prevent the connector from falling out. Means shall be employed to prevent the connector from entering so far as to restrict the space between its end and the opposite wall of the chimney flue. 802.10.12 Inspection. The entire length of a vent connector shall be readily accessible for inspection, cleaning, and replacement. 802.10.13 Fireplaces. A vent connector shall not be connected to a chimney flue serving a fireplace unless the fireplace flue opening is permanently sealed. 802.10.14 Passage Through Ceilings, Floors, or Walls. 802.10.14.1 A vent connector shall not pass through any ceiling, floor, or fire-resistance rated wall. A single-wall metal pipe connector shall not pass through any interior wall. Exception: Vent connectors made of listed Type B or Type L vent material and serving listed equipment with draft hoods and other equipment listed for use with Type B gas vents that pass through walls or partitions constructed of combustible material shall be installed with not less than the listed clearance to combustible material. 802.10.14.2 A vent connector made of a single-wall metal pipe shall not pass through a combustible exterior wall unless guarded at the point of passage by a ventilated metal thimble not smaller than the following: (1) For listed appliances equipped with draft hoods and appliances listed for use with Type B gas vents, the thimble shall be a minimum of four (4) inches (100 mm) larger in diameter than the vent connector. Where there is a run of not less than six (6) feet (1.8 m) of vent connector in the opening between the draft hood outlet and the thimble, the thimble shall be a minimum of two (2) inches (50 mm) larger in diameter than the vent connector. CHIMNEYS AND VENTS (2) For unlisted appliances having draft hoods, the thimble shall be a minimum of six (6) inches (150 mm) larger in diameter than the vent connector. (3) For residential and low-heat appliances, the thimble shall be a minimum of twelve (12) inches (300 mm) larger in diameter than the vent connector. Exception: In lieu of thimble protection, all combustible material in the wall shall be removed from the vent connector a sufficient distance to provide the specified clearance from such vent connector to combustible material. Any material used to close up such opening shall be noncombustible. 802.10.14.3 Vent connectors for mediumheat equipment shall not pass through walls or partitions constructed of combustible material. [NFPA 54:10.10.14.3] 802.11 Vent Connectors for Category II, Category III, and Category IV Gas Utilization Equipment. (See Section 802.4.) [NFPA 54:10.11] 802.12 Draft Hoods and Draft Controls. 802.12.1 Equipment Requiring Draft Hoods. Vented gas utilization equipment shall be installed with draft hoods. Exception: Dual oven–type combination ranges; incinerators; direct-vent equipment; fan-assisted combustion system appliances; equipment requiring chimney draft for operation; single-firebox boilers equipped with conversion burners with inputs greater than 400,000 Btu/h (117 kW); equipment equipped with blast, power, or pressure burners that are not listed for use with draft hoods; and equipment designed for forced venting. 802.12.2 Installation. A draft hood supplied with or forming a part of listed vented gas utilization equipment shall be installed without alteration, exactly as furnished and specified by the equipment manufacturer. If a draft hood is not supplied by the equipment manufacturer where one is required, a draft hood shall be installed, be of a listed or approved type, and, in the absence of other instructions, be of the same size as the equipment flue collar. Where a draft hood is required with a conversion burner, it shall be of a listed or approved type. Where it is determined that a draft hood of special design is needed or preferable for a particular installation, the installation shall be in accordance with the recommendations of the equipment manufac- 802.10 – 802.15 turer and shall be with the approval of the Authority Having Jurisdiction. 802.12.3 Draft Control Devices. Where a draft control device is part of the gas utilization equipment or is supplied by the equipment manufacturer, it shall be installed in accordance with the manufacturer's instructions. In the absence of manufacturer's instructions, the device shall be attached to the flue collar of the equipment or as near to the equipment as practical. 802.12.4 Additional Devices. Gas utilization equipment (except incinerators) requiring controlled chimney draft shall be permitted to be equipped with a listed double-acting barometric draft regulator installed and adjusted in accordance with the manufacturers' instructions. 802.12.5 Location. Draft hoods and barometric draft regulators shall be installed in the same room or enclosure as the equipment in such a manner as to prevent any difference in pressure between the hood or regulator and the combustion air supply. 802.12.6 Positioning. Draft hoods and draft regulators shall be installed in the position for that they were designed with reference to the horizontal and vertical planes and shall be located so that the relief opening is not obstructed by any part of the equipment or adjacent construction. The equipment and its draft hood shall be located so that the relief opening is accessible for checking vent operation. 802.12.7 Clearance. A draft hood shall be located so that its relief opening is not less than six (6) inches (150 mm) from any surface except that of the equipment it serves and the venting system to which the draft hood is connected. Where a greater or lesser clearance is indicated on the equipment label, the clearance shall not be less than that specified on the label. Such clearances shall not be reduced. [NFPA 54:10.12] 802.13 Manually Operated Dampers. A manually operated damper shall not be placed in any equipment vent connector. Fixed baffles shall not be classified as manually operated dampers. [NFPA 54:10.13] 802.14 Automatically Operated Vent Dampers. An automatically operated vent damper shall be of a listed type. [NFPA 54:10.14] 802.15 Obstructions. Devices that retard the flow of vent gases shall not be installed in a vent connector, chimney, or vent. The following shall not be considered as obstructions: (1) Draft regulators and safety controls specifically listed for installation in venting 123 802.15 – 803.1 systems and installed in accordance with the terms of their listing. (2) Approved draft regulators and safety controls designed and installed in accordance with approved engineering methods. (3) Listed heat reclaimers and automatically operated vent dampers installed in accordance with the terms of their listing. (4) Vent dampers serving listed appliances installed in accordance with Sections 803.1 and 803.2.1 or other approved engineering methods. (5) Approved economizers, heat reclaimers, and recuperators installed in venting systems of equipment not required to be equipped with draft hoods, provided the gas utilization equipment manufacturer's instructions cover the installation of such a device in the venting system and performance in accordance with Sections 802.3.1 and 802.3.2 is obtained. [NFPA 54:10.15] 803.0 Sizing of Category I Venting Systems 803.1 These venting tables shall not be used where obstructions (see Section 802.15) are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: (1) The maximum capacity of the vent system shall be determined using the NAT Max column. (2) The minimum capacity shall be determined as if the appliance were a fan-assisted appliance, using the FAN Min column to determine the minimum capacity of the vent system. Where the corresponding FAN Min is NA, the vent configuration shall not be permitted and an alternative venting configuration shall be utilized. 803.1.1 Where the vent size determined from the tables is smaller than the appliance draft hood outlet or flue collar, the use of the smaller size shall be permitted provided that t h e i n s tallation complies with all of the following requirements: (1) The total vent height (H) is at least ten (10) feet (3 m). (2) Vents for appliance draft hood outlets or flue collars twelve (12) inches (300 mm) in diameter or smaller are not reduced more than one table size. 124 2007 CALIFORNIA MECHANICAL CODE (3) Vents for appliance draft hood outlets or flue collars larger than twelve (12) inches (300 mm) in diameter are not reduced more than two table sizes. (4) The maximum capacity listed in the tables for a fan-assisted appliance is reduced by ten (10) percent (0.90 maximum table capacity). (5) The draft hood outlet is greater than four (4) inches (100 mm) in diameter. Do not connect a three (3) inches (80 mm) diameter vent to a four (4) inches (100 mm) diameter draft hood outlet. This provision shall not apply to fan-assisted appliances. 803.1.2 Single-appliance venting configurations with zero (0) lateral lengths in Tables 8-5, 8-6, and 8-9 shall not have elbows in the venting system. For vent configurations with lateral lengths, the venting tables include allowance for two 90 degree turns. For each additional elbow up to and including 45 degrees, the maximum capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees up to and including 90 degrees, the maximum capacity listed in the venting tables shall be reduced by 10 percent. 803.1.3 Zero (0) lateral (L) shall apply only to a straight vertical vent attached to a top-outlet draft hood or flue collar. 803.1.4 Sea level input ratings shall be used when determining maximum capacity for highaltitude installation. Actual input (derated for altitude) shall be used for determining minimum capacity for high-altitude installation. 803.1.5 For appliances with more than one input rate, the minimum vent capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent capacity (FAN Max/NAT Max) determined from the tables shall be greater than the highest appliance rating input. 803.1.6 Listed corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 8-5 or 8-6 for Type B vents, with the maximum capacity reduced by 20 percent (0.80 maximum capacity) and the minimum capacity as shown in Table 8-5 or 8-6. Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Section 803.1.2. The 20 percent reduction for corrugated metallic chimney liner systems includes an allowance for one long radius 90 degree turn at the bottom of the liner. 803.1.7 Where the vertical vent has a larger diameter than the vent connector, the vertical CHIMNEYS AND VENTS vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the vertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods. 803.1.8 Connection to Chimney Liners. Connections between chimney liners and listed double-wall connectors shall be made with listed adapters designed for such purpose. [NFPA 54:13.1.8] 803.1.8.1 Tables 8-5 through 8-9 shall be used for chimneys and vents not exposed to the outdoors below the roof line. A Type B vent or listed chimney lining system passing through an unused masonry chimney flue shall not be considered to be exposed to the outdoors. A Type B vent passing through an unventilated enclosure or chase insulated to a value of not less than R8 shall not be considered to be exposed to the outdoors. Table 8-7 in combination with Table 8-15 shall be used for clay-tile-lined exterior masonry chimneys, provided all of the following are met: (1) The vent connector is Type B double wall. (2) The vent connector length is limited to 1-1/2 feet for each inch (180 mm/mm) of vent connector diameter. (3) The appliance is draft hood equipped. (4) The input rating is less than the maximum capacity given in Table 8-7. (5) For a water heater, the outdoor design temperature shall not be less than 5°F (–15°C). (6) For a space-heating appliance, the input rating is greater than the minimum capacity given by Table 8-15. (7) Where the conditions of 803.1.8.1(1) through (6) cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: Vents serving listed appliances installed in accordance with the appliance manufacturer’s instructions and the terms of the listing. 803.1.9 Corrugated vent connectors shall not be smaller than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 803.1 – 803.2 803.1.9.1 Vertical Vent Upsizing/7 Times Rule. Where the vertical vent has a larger diameter than the vent connector, the vertical vent diameter shall be used to determine the minimum vent capacity, and the connector diameter shall be used to determine the maximum vent capacity. The flow area of the vertical vent shall not exceed seven times the flow area of the listed appliance categorized vent area, flue collar area, or draft hood outlet area unless designed in accordance with approved engineering methods. [NFPA 54: 13.1.9] 803.1.10 Vent connectors shall not be upsized more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. 803.1.11 In a single run of vent or vent connector, more than one diameter and type shall be permitted to be used, provided that all the sizes and types are permitted by the tables. 803.1.12 Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. (See Example 8-1 in Section 803.2.23.) 803.1.13 Extrapolation beyond the table entries shall not be permitted. For SI units, 1 in. = 25.4 mm; 1 ft. = 0.305 m; 1,000 Btu/h = 0.293 kW; 1 in.2 = 645 mm2. 803.1.14 For vent heights lower than six (6) feet and higher than shown in the tables, engineering methods shall be used to calculate vent capacities. [NFPA 54:13.1] 803.1.15 Draft Hood Conversion Accessories. Draft hood conversion accessories for use with masonry chimneys venting listed Category I fanassisted appliances shall be listed and installed in accordance with the listed accessory manufacturers’ installation instructions. [NFPA 54:13.1.10] 803.2 Additional Requirements to Multiple Appliance Vent Tables 8-10 through 8-14 and Tables 8-16 through 8-19. 803.2.1 These venting tables shall not be used where obstructions (see Section 802.15) are installed in the venting system. The installation of vents serving listed appliances with vent dampers shall be in accordance with the appliance manufacturer’s instructions or in accordance with the following: (1) The maximum capacity of the vent connector shall be determined using the NAT Max column. 125 803.2 – Figure 8-4 (2) The maximum capacity of the vertical vent or chimney shall be determined using the FAN+NAT column when the second appliance is a fan-assisted appliance, or the NAT+NAT column when the second appliance is equipped with a draft hood. 2007 CALIFORNIA MECHANICAL CODE (3) The minimum capacity shall be determined as if the appliance were a fan-assisted appliance. (a) The minimum capacity of the vent connector shall be determined using the FAN Min column. (b) The FAN+FAN column shall be used when the second appliance is a fanassisted appliance, and the FAN+NAT column shall be used when the second appliance is equipped with a draft hood, to determine whether the vertical vent or chimney configuration is not permitted (NA). Where the vent configuration is NA, the vent configuration shall not be permitted, and an alternative venting configuration shall be utilized. 803.2.2 The maximum vent connector horizontal length shall be 18 in./in. (180 mm/mm) of connector diameter as follows: Connector Diameter Maximum (in.) Connector Horizontal Length (ft.) 3 4-1/2 5 7-1/2 7 10-1/2 9 13-1/2 12 18 4 6 8 10 14 16 18 20 22 24 6 9 12 15 21 24 27 30 33 36 For SI units, 1 in. = 25.4 mm; 1 ft. = 0.305 m. 126 FIGURE 8-4 Use of Manifolded Common Vent Connector. 803.2.3 The vent connector shall be routed to the vent utilizing the shortest possible route. Connectors with longer horizontal lengths than those listed in Section 803.2.2 are permitted under the following conditions: (A) The maximum capacity (FAN Max or NAT Max) of the vent connector shall be reduced 10 percent for each additional multiple of the length listed in 803.2.2. For example, the maximum length listed for a four (4) inches (100 mm) connector is six (6) feet (1.8 m). With a connector length greater than six (6) feet (1.8 m) but not exceeding twelve (12) feet (3.7 m), the maximum capacity must be reduced by ten (10) percent (0.90 maximum vent connector capacity). With connector length greater than twelve (12) feet (3.7 m) but not exceeding eighteen (18) feet (5.5 m), the maximum capacity must be reduced by 20 percent (0.80 maximum vent capacity). (B) For a connector serving a fan-assisted appliance, the minimum capacity (FAN Min) of the connector shall be determined by referring to the corresponding singleappliance table. For Type B double-wall connectors, Table 8-5 shall be used. For single-wall connectors, Table 8-6 shall be used. The height (H) and lateral (L) shall be measured according to the procedures for a single-appliance vent, as if the other appliances were not present. CHIMNEYS AND VENTS Figure 8-5 – 803.2 803.2.6 For each elbow up to and including 45 degrees in the common vent, the maximum common vent capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees up to and including 90 degrees, the maximum common vent capacity listed in the venting tables shall be reduced by 10 percent. 803.2.7 The vent connector capacities listed in the common vent sizing tables include allowance for two 90 degree elbows. For each additional elbow up to and including 45 degrees, the maximum vent connector capacity listed in the venting tables shall be reduced by 5 percent. For each elbow greater than 45 degrees up to and including 90 degrees, the maximum vent connector capacity listed in the venting tables shall be reduced by 10 percent. 803.2.8 Common Vent Minimum Size. The cross-sectional area of the common vent shall be equal to or greater than the cross-sectional area of the largest connector. [NFPA 54: 13.2.8] 803.2.9 Tee and Wye Fittings. Tee and wye fittings connected to a common vent shall be considered as part of the common vent and constructed of materials consistent with that of the common vent. [NFPA 54:13.2.9] FIGURE 8-5 Multistory Gas Vent Design Procedure for Each Segment of System. 803.2.4 Where the vent connectors are combined prior to entering the vertical portion of the common vent to form a common vent manifold, the size of the common vent manifold and the common vent shall be determined by applying a 10 percent reduction (0.90 x maximum common vent capacity) to the Common Vent Capacity part of the common vent tables. The length of the common vent connector manifold (LM) shall not exceed 18 in./in. (180 mm/mm) of common vent connector manifold diameter (D). (See Figure 8-4.) 803.2.5 Where the common vertical vent is offset, the maximum capacity of the common vent shall be reduced in accordance with Section 803.2.6, and the horizontal length of the common vent offset shall not exceed 18 in./in. (180 mm/mm) of common vent diameter. 803.2.9.1 At the point where tee or wye fittings connect to a common vent, the opening size of the fitting shall be equal to the size of the common vent. Such fittings shall not be prohibited from having reduced size openings at the point of connection of appliance vent connectors. 803.2.10 Sea level input ratings shall be used when determining maximum capacity for highaltitude installation. Actual input (derated for altitude) shall be used for determining minimum capacity for high-altitude installation. 803.2.11 The connector rise (R) for each appliance connector shall be measured from the draft hood outlet or flue collar to the centerline where the vent gas streams come together. 803.2.12 For multiple units of gas utilization equipment all located on one floor, available total height (H) shall be measured from the highest draft hood outlet or flue collar up to the level of the outlet of the common vent. 803.2.13 For multistory installations, available total height (H) for each segment of the system shall be the vertical distance between the highest draft hood outlet or flue collar entering that segment and the centerline of the next higher interconnection tee. (See Figure 8-5.) 127 803.2 – Figure 8-6 803.2.14 The size of the lowest connector and of the vertical vent leading to the lowest interconnection of a multistory system shall be in accordance with Table 8-5 or 8-6 for available total height (H) up to the lowest interconnection. (See Figure 8-6.) 2007 CALIFORNIA MECHANICAL CODE 803.2.15 Where used in multistory systems, vertical common vents shall be Type B doublewall and shall be installed with a listed vent cap. 803.2.20 Tables 8-10 and 8-11 shall be used for chimneys and vents not exposed to the outdoors below the roof line. A Type B vent passing through an unventilated enclosure or chase insulated to a value of not less than R8 shall not be considered to be exposed to the outdoors. Tables 8-16 through 8-19 shall be used for claytile-lined exterior masonry chimneys, provided all of the following conditions are met: (1) The offset angle shall not exceed 45 degrees from vertical. (3) The combined appliance input rating is less than the maximum capacity given by Table 8-16 (for NAT+NAT) or Table 8-18 (for FAN+NAT). 803.2.16 Offsets in multistory common vent systems shall be limited to a single offset in each system, and systems with an offset shall comply with all of the following: (2) The horizontal length of the offset shall not exceed eighteen (18) inches for each inch (180 mm/mm) of common vent diameter of the segment in that the offset is located. (3) For the segment of the common vertical vent containing the offset, the common vent capacity listed in the common venting tables shall be reduced by 20 percent (0.80 x maximum common vent capacity). (1) Vent connector is Type B double-wall. (2) At least one appliance is draft hood-equipped. (4) The input rating of each space-heating appliance is greater than the minimum input rating given by Table 8-17 (for NAT+NAT) or Table 8-19 (for FAN+NAT). (4) A multistory common vent shall not be reduced in size above the offset. 803.2.17 Where two or more appliances are connected to a vertical vent or chimney, the flow area of the largest section of vertical vent or chimney shall not exceed seven times the smallest listed appliance categorized vent areas, flue collar area, or draft hood outlet area, unless designed in accordance with approved engineering methods. 803.2.18 For appliances with more than one input rate, the minimum vent connector capacity (FAN Min) determined from the tables shall be less than the lowest appliance input rating, and the maximum vent connector capacity (FAN Max or NAT Max) determined from the tables shall be greater than the highest appliance input rating. 803.2.19 Listed, corrugated metallic chimney liner systems in masonry chimneys shall be sized by using Table 8-10 or 8-11 for Type B vents, with the maximum capacity reduced by 20 percent (0.80 maximum capacity) and the minimum capacity as shown in Table 8-10 or 8-11. Corrugated metallic liner systems installed with bends or offsets shall have their maximum capacity further reduced in accordance with Sections 803.2.5 and 803.2.6. The 20 percent reduction for corrugated metallic chimney liner systems includes an allowance for one long radius 90 degree turn at the bottom of the liner. 128 FIGURE 8-6 Principle of Design of Multistory Vents Using Vent Connector and Common Vent Design Tables. CHIMNEYS AND VENTS (5) The vent connector sizing is in accordance with Table 8-12. (6) Where these conditions cannot be met, an alternative venting design shall be used, such as a listed chimney lining system. Exception: Vents serving listed appliances installed in accordance with the appliance manufacturer's installation instructions. 803.2.21 Vent connectors shall not be increased more than two sizes greater than the listed appliance categorized vent diameter, flue collar diameter, or draft hood outlet diameter. Vent connectors for draft hood-equipped appliances shall not be smaller than the draft hood outlet diameter. Where a vent connector size(s) determined from the tables for a fan-assisted appliance(s) is smaller than the flue collar diameter, the use of the smaller size(s) shall be permitted provided that the installation complies with all of the following: (1) Vent connectors for fan-assisted appliance flue collars twelve (12) inches (300 mm) in diameter or smaller are not reduced by more than one table size [e.g., 12 in. to 10 in. (300 mm to 250 mm) is a one-size reduction] and those larger than twelve (12) inches (300 mm) in diameter are not reduced more than two table sizes [e.g., 24 in. to 20 in. (610 mm to 510 mm) is a two-size reduction]. (2) The fan-assisted appliance(s) is common vented with a draft hood equipped appliance(s). (3) The vent connector has a smooth interior wall. 803.2.22 All combinations of pipe sizes and single-wall and double-wall metal pipe shall be allowed within any connector run(s) or within the common vent provided ALL of the appropriate tables permit ALL of the desired sizes and types of pipe, as if they were used for the entire length of the subject connector or vent. Where single-wall and Type B double-wall metal pipes are used for vent connectors within the same venting system, the common vent must be sized using Table 8-11 or 8-13, as appropriate. 803.2 Values. An installer has an 80,000 Btu/h. input appliance with a four (4) inches diameter draft hood outlet that needs to be vented into a twelve (12) foot high Type B vent. The vent connector has a five (5) foot lateral length and is also Type B. Can this appliance be vented using a four (4) inch diameter vent? Solution Table 8-5 is used in the case of an all Type B vent system. However, since there is no entry in Table 8-5 for a height of 12 ft., interpolation must be used. Read down the 4 in. diameter NAT Max column to the row associated with 10 ft. height and 5 ft. lateral to find the capacity value of 77,000 Btu/h. Read further down to the 15 ft. height, 5 ft. lateral row to find the capacity value of 87,000 Btu/h. The difference between the 15 ft. height capacity value and the 10 ft. height capacity value is 10,000 Btu/h. The capacity for a vent system with a 12 ft. height is equal to the capacity for a 10 ft. height plus 2/5 of the difference between the 10 ft. and 15 ft. height values, or 77,000 + 2/5 x 10,000 = 81,000 Btu/h. Therefore, a 4 in. diameter vent can be used in the installation. 803.2.25 Extrapolation beyond the table entries shall not be permitted. 803.2.26 For vent heights lower than six (6) feet and higher than shown in the tables, engineering methods shall be used to calculate vent capacities. [NFPA 54:13.2] 803.2.23 Where a table permits more than one diameter of pipe to be used for a connector or vent, all the permitted sizes shall be permitted to be used. 803.2.24 Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table entries. (See Example 8-1.) Example 8-1: Interpolating between Table 129 2007 CALIFORNIA MECHANICAL CODE Table 8-5 Table 8-5 Type B Double-Wall Gas Vent with Single Appliance Connected Directly to Vent [NFPA 54:Table 13.1(a)] Number of Appliances: Single Appliance Type: Appliance Vent Connection: 3 Height Lateral H (ft) 6 8 10 15 20 30 50 100 130 4 5 Vent Diameter — D (in.) 6 Category I Connected Directly to Vent 7 Appliance Input Rating in Thousands of Btu per Hour 8 9 L FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT (ft) Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 0 2 4 6 0 13 21 25 78 51 49 46 46 36 34 32 0 18 30 36 152 97 94 91 86 67 64 61 0 27 39 47 251 157 153 149 141 105 103 100 0 32 50 59 375 232 227 223 205 157 153 149 0 44 66 78 524 321 316 310 285 217 211 205 0 53 79 93 698 425 419 413 370 0 285 63 279 93 273 110 897 543 536 530 470 370 362 354 0 2 5 10 0 12 23 30 88 61 57 51 53 42 40 36 0 17 32 41 175 118 113 104 100 81 77 70 0 23 41 54 295 194 187 176 166 129 124 115 0 26 52 67 447 289 280 267 255 195 188 175 0 40 68 88 631 402 392 376 345 273 263 245 0 48 81 104 847 533 522 504 450 0 1096 355 57 684 346 95 671 330 122 651 585 457 446 427 202 149 143 133 124 116 119 100 96 89 84 78 430 346 337 321 308 295 0 1057 41 711 73 697 95 675 111 654 125 634 0 2 5 8 0 2 5 10 15 0 2 5 10 15 20 0 12 23 28 0 11 22 29 35 0 10 21 28 34 48 84 57 53 49 94 69 65 59 53 97 75 71 64 58 52 50 40 38 35 58 48 45 41 37 61 51 48 44 40 35 0 16 32 39 0 15 30 40 48 0 14 29 38 46 55 0 2 5 10 15 20 30 0 9 21 27 33 56 NA 100 64 0 81 56 13 77 54 28 70 50 37 64 NA 44 58 NA 53 NA NA 73 0 2 5 10 15 20 30 50 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 0 2 5 10 15 20 30 0 8 20 26 59 NA NA 101 86 82 76 70 NA NA 67 61 NA NA NA NA NA NA NA NA NA NA NA NA NA 0 11 27 35 42 50 69 0 10 26 33 40 47 NA NA 165 109 103 98 191 136 130 121 112 94 75 71 66 112 93 87 82 76 0 25 42 51 0 20 39 51 61 0 18 38 50 59 69 213 166 160 150 141 132 113 128 112 108 102 96 90 NA 218 194 189 182 174 166 NA NA NA 0 NA 12 NA 33 NA 43 NA 50 NA 59 NA 78 NA NA 216 183 177 168 158 149 131 134 122 119 114 NA NA NA 0 14 36 48 57 66 88 0 14 35 45 54 63 84 276 178 171 164 327 226 219 206 195 349 250 242 229 217 206 155 120 115 109 187 150 142 135 128 202 166 160 150 142 134 0 28 53 64 0 22 49 64 76 0 20 47 62 73 84 415 263 255 247 502 339 330 315 301 540 377 367 351 337 322 235 180 173 165 285 225 217 208 198 307 249 241 228 217 206 0 42 70 84 0 38 64 84 98 0 33 62 81 94 107 583 365 356 347 716 475 463 445 429 776 531 519 499 481 464 320 247 237 227 390 316 300 288 275 0 50 83 99 0 45 76 99 115 780 483 473 463 970 633 620 600 580 415 0 1006 322 60 619 313 99 607 303 117 596 525 0 1263 414 53 815 403 90 800 386 116 777 373 134 755 575 0 1384 470 50 917 460 86 902 443 112 877 427 129 853 410 145 830 537 418 407 396 682 544 529 507 491 752 612 599 576 557 537 374 283 275 262 249 237 214 220 0 185 18 176 45 171 59 163 70 154 80 NA 104 587 432 421 405 389 374 346 336 280 273 261 249 237 219 0 27 58 77 90 102 131 853 613 600 580 560 542 507 475 394 385 371 357 343 321 0 1173 33 826 69 811 91 788 105 765 119 743 149 702 650 535 524 507 490 473 444 0 42 82 107 124 139 171 1548 1072 1055 1028 1002 977 929 407 354 347 335 321 311 290 NA NA 0 NA 13 NA 40 NA 53 NA 62 NA 71 NA 92 NA 147 665 566 557 542 528 513 483 428 400 375 369 361 353 344 NA NA 0 18 52 68 80 90 115 180 997 831 820 801 782 763 726 651 560 510 504 493 482 471 449 405 0 21 60 80 93 105 131 197 770 700 692 679 666 653 627 575 0 25 71 94 109 122 149 217 1908 1040 1536 935 1519 926 1492 910 1465 895 1438 880 1387 849 1288 787 397 320 312 299 287 275 250 232 206 200 190 180 169 NA 0 15 43 56 66 76 99 633 497 487 471 455 440 410 363 314 308 298 288 278 259 0 22 55 73 85 97 123 932 715 702 681 662 642 605 518 445 438 426 413 401 376 0 1297 26 975 65 960 86 935 100 911 113 888 141 844 1411 1155 1141 1118 1095 1073 1029 944 708 615 605 589 572 556 522 0 33 77 101 117 131 161 1730 1276 1259 1230 1203 1176 1125 855 700 688 668 648 628 594 952 813 798 773 747 722 670 CHIMNEYS AND VENTS Table 8-5 continued Table 8-5 [NFPA 54:Table 13.1(a)] Continued Number of Appliances: Single Appliance Vent Connection: Connected Directly to Vent Appliance Type: Category I Vent Diameter — D (in.) Height Lateral H (ft) L (ft) 8 0 2 5 8 6 10 15 20 30 50 100 0 2 4 6 0 2 5 10 0 2 5 10 15 0 2 5 10 15 20 0 2 5 10 15 20 30 0 2 5 10 15 20 30 0 2 5 10 15 20 30 50 10 FAN 12 NAT FAN NAT 14 16 18 20 Appliance Input Rating in Thousands of Btu per Hour FAN NAT FAN NAT FAN NAT FAN NAT 22 FAN 24 NAT FAN NAT Min Max Max MinMax Max MinMax Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max 0 75 110 128 1121 675 668 661 570 0 1645 455 103 982 445 147 975 435 171 967 850 0 2267 1170 650 138 1346 890 640 191 1338 880 630 219 1330 870 0 178 242 276 2983 1769 1761 1753 1530 1170 1160 1150 0 225 300 341 3802 2250 2242 2235 1960 0 1480 296 1475 390 1470 437 4721 2782 2774 2767 2430 1850 1835 1820 0 360 469 523 5737 3377 3370 3363 2950 0 6853 3520 2220 426 4030 2670 2215 555 4023 2660 2210 618 4017 2650 0 68 112 142 1377 852 839 817 720 0 2036 560 93 1244 547 149 1229 525 187 1204 1060 0 2825 1450 850 124 1713 1130 829 192 1696 1105 795 238 1669 1080 0 161 243 298 3742 2256 2238 2209 1925 1480 1461 1430 0 202 300 364 4782 2868 2849 2818 2450 0 1890 264 1871 382 1840 459 5955 3556 3536 3504 3050 2340 2318 2280 0 319 458 546 7254 4322 4301 4268 3710 0 8682 4450 2840 378 5153 3390 2818 540 5132 3371 2780 641 5099 3340 930 755 738 710 688 665 0 81 135 172 195 217 2637 1694 1674 1641 1609 1578 1350 1100 1079 1045 1018 990 1195 1010 996 972 948 924 876 0 66 118 154 177 195 232 3441 2431 2406 2366 2327 2288 2214 1825 1513 1495 1466 1437 1408 1349 0 71 115 137 0 63 105 135 155 0 59 101 130 150 167 0 54 96 125 143 160 195 0 41 90 118 136 151 183 0 30 82 108 126 141 170 241 1261 770 758 746 1596 1019 1003 977 953 660 0 1858 515 98 1124 503 154 1110 490 180 1097 970 0 2571 1320 745 130 1543 1020 733 199 1528 1010 720 231 1514 1000 840 0 2380 1240 675 86 1495 985 660 140 1476 967 635 177 1446 936 610 202 1418 905 0 114 182 227 257 3323 2062 2041 2009 1976 1720 1350 1327 1289 1250 1977 1351 1332 1301 1272 1243 1189 1060 865 851 829 807 784 745 0 98 164 209 237 260 305 4252 2786 2759 2716 2674 2633 2555 2170 1800 1775 1733 1692 1650 1585 2491 1975 1955 1923 1892 1861 1802 1688 1310 1170 1159 1142 1124 1107 1071 1000 1756 1150 1133 1105 1078 1052 2231 1620 1600 1567 1536 1505 1446 0 74 127 164 187 207 246 0 44 107 142 163 181 215 292 3004 2004 1981 1944 1908 1873 1807 3925 3027 3002 2961 2920 2880 2803 2657 1550 1310 1289 1254 1220 1185 1130 2050 1820 1803 1775 1747 1719 1663 1550 0 107 174 220 248 273 0 86 151 196 222 244 287 0 72 136 180 206 226 265 350 3701 2343 2320 2282 2245 2210 4934 3409 3380 3332 3285 3239 3150 5729 4313 4282 4231 4182 4133 4037 3856 1900 1520 1498 1460 1425 1390 2550 2125 2102 2064 2026 1987 1910 2950 2550 2531 2500 2469 2438 2375 2250 0 168 251 289 0 147 229 283 318 0 139 219 273 306 335 0 127 206 259 292 319 369 0 113 191 243 274 300 347 0 95 172 223 252 277 319 415 3399 2030 2013 2000 4423 2719 2696 2659 2623 4948 3097 3071 3029 2988 2948 5725 3696 3666 3617 3570 3523 3433 6711 4554 4520 4464 4409 4356 4253 7914 5834 5797 5737 5678 5619 5505 5289 1740 1340 1330 1320 2270 1770 1748 1712 1675 2520 2000 1978 1940 1910 1880 2920 2380 2350 2300 2250 2200 2130 3440 2840 2813 2767 2721 2675 2631 4050 3500 3475 3434 3392 3351 3267 3100 0 212 311 354 0 186 283 346 385 0 175 270 334 372 404 0 159 252 316 354 384 440 0 141 234 295 330 361 412 0 120 208 268 304 330 378 486 4333 2584 2563 2552 5678 3467 3442 3402 3363 6376 3955 3926 3880 3835 3791 7420 4734 4701 4647 4594 4542 4442 8774 5864 5826 5763 5701 5641 5523 10485 7591 7548 7478 7409 7341 7209 6956 2220 0 1700 278 1685 398 1670 450 2900 2260 2235 2193 2150 0 239 355 432 479 3770 3050 3020 2970 2920 2870 2785 0 199 312 386 431 467 540 3250 2570 2544 2500 2465 2430 4460 3670 3639 3585 3534 3481 3431 5300 4600 4566 4509 4451 4394 4279 4050 0 220 337 413 459 495 5387 3196 3180 3163 7099 4304 4278 4234 4192 7988 4916 4885 4835 4786 4737 9341 5900 5863 5803 5744 5686 5574 2750 2110 2090 2070 3620 2800 2777 2739 2700 4060 3200 3174 3130 3090 3050 4750 3810 3783 3739 3695 3650 3565 0 11129 5635 171 7339 4630 283 7295 4597 355 7224 4542 396 7155 4511 433 7086 4479 494 6953 4421 0 13454 6700 138 9577 5800 245 9528 5769 318 9447 5717 358 9367 5665 387 9289 5613 446 9136 5509 572 8841 5300 0 336 476 537 0 290 426 510 564 0 269 403 489 541 585 6555 3882 3863 3850 8665 5232 5204 5159 5115 9785 5983 5950 5896 5844 5792 0 241 373 456 507 548 635 11483 7194 7155 7090 7026 6964 6842 0 169 293 374 418 452 514 659 16817 11803 11748 11658 11569 11482 11310 10979 0 209 336 419 465 506 577 13767 8980 8933 8855 8779 8704 8557 3360 0 7838 4010 2560 401 4634 3050 2545 562 4612 3040 2530 630 4602 3030 4410 3410 3385 3343 3300 0 346 501 599 665 10393 6251 6222 6175 6129 5300 4080 4057 4019 3980 5850 4650 4622 4574 4527 4480 4375 0 285 439 535 590 639 739 13848 8617 8574 8505 8437 8370 8239 7060 5600 5552 5471 5391 5310 5225 4980 3910 3880 3830 3795 3760 6940 5695 5654 5585 5546 5506 5444 8600 7200 7162 7100 7037 6975 6850 6600 0 321 475 573 631 689 0 251 394 491 542 586 672 0 204 341 436 487 523 592 752 11753 7154 7119 7063 7007 6953 16694 10788 10737 10652 10570 10488 10328 20578 14264 14204 14105 14007 13910 13720 13354 6000 4700 4662 4600 4575 4550 8430 6860 6818 6749 6710 6670 6603 10300 8800 8756 8683 8610 8537 8391 8100 131 2007 CALIFORNIA MECHANICAL CODE Table 8-6 Table 8-6 Type B Double-Wall Vent with Single Appliance and Single-Wall Metal Connector [NFPA 54:Table 13.1(b)] Number of Appliances: Single Appliance Vent Connection: Vent Diameter — D (in.) Single-Wall Metal Connector Appliance Type: Height Lateral H (ft) 6 8 10 15 20 30 50 100 132 L 3 4 FAN NAT 5 FAN NAT 6 FAN NAT 7 FAN MinMaxMax Min Max Max MinMax Max Min Max 0 2 5 8 37 83 39 56 NANA NANA 123 121 151 175 0 2 5 10 0 2 5 10 15 38 77 39 51 NANA NANA 45 36 33 31 59 60 74 83 151 96 92 89 85 66 63 60 85 85 102 114 249 156 152 147 140 104 102 99 37 87 39 61 52 56 NANA 53 41 39 34 57 59 76 97 174 117 111 100 99 80 76 68 82 82 105 132 293 193 185 171 165 128 122 112 78 78 100 125 155 186 36 93 38 69 51 63 NANA NANA 50 39 37 33 57 47 44 39 NA 58 59 77 90 56 57 75 95 NA 164 108 102 95 190 136 128 116 NA 93 75 69 64 111 93 86 79 72 83 83 107 122 80 80 102 128 158 0 2 5 10 15 20 35 96 37 74 50 68 NANA NANA NANA 60 50 47 41 NA NA 54 56 73 93 NA NA 200 148 140 129 NA NA 118 99 94 86 80 NA 0 2 5 10 15 20 30 33 99 36 84 48 80 NANA NANA NANA NANA 66 61 NA NA NA NA NA 51 53 70 89 112 NA NA 213 181 174 160 148 NA NA 133 73 121 73 117 94 NA 118 NA 145 NA 176 NA NA 0 2 5 10 15 20 30 0 2 5 10 15 20 30 50 34 99 37 80 49 74 NANA NANA NANA NANA NANA NANA NANA NANA NANA NANA NANA NANA 63 56 52 NA NA NA NA NA NA NA NA NA NA NA NA 53 55 72 91 115 NA NA 49 51 67 85 132 NA NA NA 211 164 157 144 131 NA NA 214 192 186 175 162 NA NA NA 273 176 168 161 325 225 216 201 186 346 248 239 223 208 192 154 119 114 107 186 149 140 131 124 201 165 158 146 136 126 126 123 146 163 373 231 225 220 120 119 148 188 444 287 277 261 116 115 144 182 220 114 113 141 177 216 254 412 261 252 243 499 337 326 308 290 537 375 363 344 325 306 NAT 165 159 187 207 522 320 313 307 284 213 208 203 254 194 186 171 158 153 190 237 628 400 388 369 344 272 261 241 234 179 171 163 283 224 217 203 192 9 153 148 182 228 272 580 363 352 342 713 473 459 438 418 319 246 235 225 388 314 298 284 269 NAT 211 201 237 263 695 423 416 409 369 284 277 271 202 193 241 296 844 531 518 497 449 354 344 325 206 197 245 280 195 187 231 284 334 777 482 470 458 966 631 616 592 568 414 321 311 300 523 413 400 381 367 FAN Min Max 267 251 295 327 1002 617 604 591 244 232 287 349 404 1259 812 795 768 742 253 242 299 363 772 528 514 491 469 448 428 344 334 316 301 285 190 1053 182 708 224 692 277 666 325 640 374 616 573 468 457 437 419 400 238 227 279 339 393 448 361 312 305 292 280 267 NA 138 133 164 203 244 285 373 928 712 696 671 646 622 573 515 443 435 420 405 389 NA 176 1292 168 971 204 953 253 923 299 894 345 866 442 809 704 613 602 583 562 543 502 220 209 257 313 363 415 521 584 429 417 397 377 357 NA 334 279 271 257 242 228 NA NA 69 NA 70 NA 90 NA 113 NA 138 NA 168 NA 231 NA NA 403 351 342 324 310 295 264 NA NA NA NA NA NA NA NA NA 100 98 125 153 188 224 301 NA 659 563 551 532 511 487 448 NA 395 373 366 354 343 NA NA NA 144 139 171 213 255 298 389 131 125 156 191 230 270 355 540 849 610 595 570 547 524 477 991 828 813 789 764 739 685 584 472 392 382 367 349 333 305 555 508 501 486 473 458 NA NA 184 1168 175 823 215 806 265 777 312 750 360 723 461 670 166 158 194 238 281 325 418 617 1404 1152 1134 1104 1075 1046 988 866 647 533 521 501 481 461 426 765 698 688 672 656 639 NA NA 894 541 533 526 258 246 305 344 149 144 178 222 264 309 110 109 136 171 208 246 NA 629 495 482 461 441 420 376 161 155 193 223 FAN Min Max Max 306 248 239 224 210 196 219 183 173 168 157 NA NA 105 104 131 162 199 236 315 NAT 204 156 152 148 372 281 271 255 239 223 NA 230 205 198 186 174 NA NA FAN Max Min Max Max 127 76 111 76 106 98 98 122 NA 151 NA 181 NA NA 394 318 308 292 275 257 NA 8 Appliance Input Rating in Thousands of Btu per Hour (ft) 0 2 4 6 Category I 229 219 269 327 379 433 541 207 196 240 293 342 391 491 711 1093 681 667 643 NAT 10 FAN Max Min Max 469 368 360 352 371 347 409 449 1118 673 664 656 584 456 443 423 351 332 409 492 536 417 404 392 681 543 526 501 484 360 339 418 470 336 319 392 470 540 12 NAT 537 498 584 638 1639 979 971 962 1373 849 834 808 718 559 544 520 507 475 584 688 2031 1057 1242 848 1224 825 1194 788 927 754 734 702 677 651 473 443 547 646 730 808 2631 1689 1665 1626 1587 1550 1346 1098 1074 1037 1005 973 3432 2426 2396 2347 2299 2251 2159 1818 1509 1490 1455 1421 1387 1318 1257 768 754 740 1591 1015 997 966 937 658 513 500 486 838 673 657 628 601 750 611 596 570 549 526 326 309 381 457 526 592 1751 1146 1126 1092 1060 1028 1724 1273 1252 1217 1183 1150 1086 948 811 795 765 736 708 649 295 280 347 418 481 544 674 2223 1189 1615 1007 1591 991 1551 963 1512 934 1473 906 1399 848 1900 1532 1511 1477 1443 1410 1343 1205 852 698 684 662 638 615 574 1033 933 921 902 884 864 824 NA 312 296 366 440 507 570 704 273 259 322 389 447 507 631 138 NAT 569 453 443 433 1379 914 896 866 838 810 1542 1069 1049 1017 985 955 895 FAN Max Min Max Max 1971 1056 1346 863 1324 846 1287 821 1251 794 1216 768 1147 720 2479 1970 1945 1905 1865 1825 1747 1591 521 486 598 665 488 457 562 664 750 454 424 524 620 702 780 937 428 401 496 589 668 741 892 1852 1120 1104 1089 849 648 638 627 967 743 730 715 2374 1237 1491 983 1469 963 1433 928 1399 894 2996 1999 1971 1927 1884 1841 1759 1300 395 3912 1168 371 3021 1153 460 2990 1133 547 2938 1110 618 2888 1087 690 2838 1041 834 2739 NA 1138 2547 1545 1308 1283 1243 1205 1166 1101 2042 1817 1796 1763 1730 1696 1627 1489 CHIMNEYS AND VENTS Table 8-7 Table 8-7 Masonry Chimney with Single Appliance and Type B Double-Wall Connector [NFPA 54:Table 13.1(c)] Number of Appliances: Single Appliance Vent Connection: Type B Double-Wall Connector Appliance Type: Category I Type B Double-Wall Connector Diameter — D (in.) Height Lateral H L (ft) (ft) 8 2 5 8 6 10 15 20 30 50 2 5 2 5 10 2 5 10 15 2 5 10 15 20 2 5 10 15 20 30 2 5 10 15 20 30 Minimum Internal Area of Chimney (Square Inches) Maximum Internal Area of Chimney (Square Inches) 3 4 FAN NAT FAN 5 NAT To be used with chimney areas within the size limits at bottom FAN 6 7 8 9 Appliance Input Rating in Thousands of Btu per Hour NAT FAN NAT FAN NAT FAN NAT FAN NAT 10 FAN 12 NAT FAN NAT MinMax Max Min Max Max Min Max Max MinMax Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max NANA 29 NANA 26 NANA 24 84 590 350 NA NA 328 NA NA 318 100 728 446 139 1024 651 149 711 423 201 1007 640 173 695 410 231 990 623 NANA 28 NANA 25 NA NA 52 NA NA 49 NA NA 86 NA NA 82 NA NA NA NA 130 NA NA 180 NA NA 247 117 NA NA 165 NA NA 231 NANA 31 NANA 28 NANA 25 NA NA 61 NA NA 57 NA NA 50 NA NA 103 NA NA NA NA 96 NA NA NA NA 87 NA NA 162 NA NA 221 68 519 298 148 NA NA 204 NA NA 277 139 NA NA 191 NA NA 263 NANA NANA NANA NANA 35 35 28 NA NANA NANA NANA NANA NANA NANA 41 NA NA NA NA NA NANA NANA NANA NANA NANA NANA NANA NANA NANA NANA NANA 12 49 38 36 NA NA NA NA NA NA NA NA NA NA NA 55 NA NA 52 NA NA 48 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 67 62 55 48 NA NA NA NA NA 74 68 60 NA NA NA NA NA NA NA NA 92 NA NA NA NA NA 19 88 82 76 67 NA NA NA NA NA 93 NA NA 88 NA NA 83 NA NA NA NA NA NA NA NA NA NA NA NA NA NA 114 107 97 89 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 137 128 115 107 91 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 28 137 124 116 107 97 83 161 151 138 127 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 38 198 145 NA NA 198 NA NA 266 134 NA NA 183 NA NA 247 127 NA NA 175 NA NA 239 179 53 475 250 64 613 164 NA NA 231 99 594 153 NA NA 216 126 565 141 NA NA 201 NA NA 336 313 296 281 201 51 522 274 61 678 184 80 503 254 95 658 172 NA NA 237 122 627 159 NA NA 220 NA NA 148 NA NA 206 NA NA 375 350 332 314 296 251 230 215 199 185 NA 477 445 424 400 376 327 216 198 184 171 159 NA 47 75 NA NA NA NA NA NA NA NA NA NA 581 561 NA NA NA NA NA NA NA NA NA NA 50 269 303 57 762 421 281 90 741 393 263 115 709 373 243 NA NA 353 227 NA NA 332 188 NA NA 288 351 323 304 282 264 NA 51 840 83 819 NA NA NA NA NA NA NA NA 63 352 NA NA 320 NA NA 298 82 655 388 124 638 365 155 610 347 77 118 148 171 73 113 143 165 186 68 106 135 156 176 NA 61 98 126 146 165 NA 779 759 727 698 867 845 811 780 750 985 962 927 893 860 NA 1106 1083 1047 1010 977 NA 78 445 441 416 394 375 491 463 440 418 397 558 526 500 476 450 416 633 596 567 539 511 468 NA NA 401 NA NA 581 NA NA 376 NA NA 561 98 810 491 136 1144 724 146 791 466 196 1124 712 182 762 444 240 1093 668 92 139 173 198 87 133 167 191 214 81 125 158 181 203 249 72 116 147 170 190 233 968 946 912 880 562 533 567 485 1083 627 1059 597 1022 566 987 541 955 513 1240 717 1216 683 1176 648 1139 621 1103 592 1035 555 1413 812 1387 774 1347 733 1307 702 1269 669 1196 623 95 550 127 186 229 259 121 179 221 251 277 111 169 210 239 264 318 99 155 195 222 246 295 1376 1352 1315 1280 1548 1523 1482 1443 1406 1793 1766 1721 1679 1638 1560 2080 2052 2006 1961 1916 1832 132 841 828 777 742 953 933 879 840 807 1112 1094 1025 981 940 877 1243 1225 1147 1099 1050 984 792 133 2007 CALIFORNIA MECHANICAL CODE Table 8-8 Table 8-8 Masonry Chimney with Single Appliance and Single-Wall Metal Connector [NFPA 54:Table 13.1(d)] Number of Appliances: Single Appliance Vent Connection: Single-Wall Metal Connector Appliance Type: 3 Height Lateral H (ft.) 6 8 10 15 20 FAN 2 NA NA 28 NA NA 52 NA NA 86 2 NA NA 29 NA NA 55 NA NA 93 5 5 8 2 5 NA NA NA NA NA NA NA NA NA NA 10 NA NA 5 NA NA 2 NA NA 10 NA NA 2 NA NA 15 5 25 26 23 31 28 24 35 32 27 NA NA NA NA NA 38 35 10 NA NA NA 20 NA NA NA 2 5 NA NA NA NA NA 41 NA NA NA 10 NA NA NA 20 NA NA NA 30 2 5 NA NA NA NA NA NA NA NA NA NA NA NA 10 NA NA NA 20 NA NA NA 15 30 Minimum Internal Area of Chimney (Square Inches) Maximum Internal Area of Chimney (Square Inches) 134 FAN NAT FAN 6 7 8 9 Appliance Input Rating in Thousands of Btu per Hour L 15 50 NAT 5 Single-Wall Metal Connector Diameter — D (in.) To be used with chimney areas within the size limits at bottom NAT (ft.) Min Max Max Min Max Max Min Max Max 15 30 4 NA NA NA NA NA NA 12 49 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 48 51 47 61 56 49 67 61 54 46 NA NA NA NA NA NA 81 87 82 NA NA 102 NA NA 86 NA NA 95 NA NA 113 NA NA 96 NA NA NA NA 106 87 FAN NAT NA NA NA NA 560 NA NA NA 145 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 116 133 126 161 147 137 178 144 66 NA NA 113 NA NA 182 NA NA NA NA NA 88 NA NA NA NA NA NA NA NA NA NA NA 149 NA NA 91 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 19 88 NA NA NA NA NA NA NA NA NA NA 28 137 NA 211 611 335 230 591 NA NA 349 NA 317 NA NA NA 271 654 334 NA NA 382 NA 400 725 445 NA 408 NA 327 NA NA 387 373 808 NA 375 422 490 NA NA 580 549 1021 650 673 1003 638 747 985 621 536 1142 722 635 364 459 789 465 657 1121 710 776 440 362 965 560 520 1373 840 261 NA NA 312 325 755 264 297 345 414 547 444 758 942 531 771 1088 665 637 1348 825 749 1309 774 520 273 206 675 374 258 864 490 252 1079 625 508 1544 950 NA 235 198 252 NA 255 312 NA 655 622 278 348 330 217 NA NA 311 578 302 200 759 420 NA 260 703 370 NA NA NA 202 279 NA NA NA NA 50 269 NA 245 300 NA 737 806 442 NA NA 281 327 475 370 428 NA 437 873 481 433 1055 594 517 1016 562 623 1518 930 733 1475 875 539 823 1434 835 982 556 340 1237 715 489 1789 1110 920 496 500 1168 644 392 524 663 979 841 1272 738 591 944 510 417 1210 680 911 1394 800 600 1760 1090 708 1713 1020 884 471 572 1128 615 798 1668 975 NA 408 NA 544 1055 1539 865 NA NA 461 606 414 958 249 372 773 306 182 837 382 391 349 191 842 NA NA NA 317 NA NA NA 692 292 240 223 452 907 441 504 301 NA 261 NA 319 NA 531 NA NA NA NA 392 NA 180 297 249 189 212 NA 518 237 276 350 NA 216 NA NA NA 195 NA 246 NA NA NA 265 NA 203 250 38 198 NA NA NA NA 722 NA 155 NA 230 392 NA NA 220 247 NA 294 168 228 NA NA 124 158 174 NA NA NA NA NA 136 NA 182 NA NA NA NA NA NA NA 164 214 196 NA NA 160 163 NA NA NA NA NA NA NA NA 215 105 473 156 NA NA NA NA NA NA NA NA NA 136 NA NA NA NA NA NA 127 166 NA 183 81 NA NA NA NA NA NA NA 75 NA 197 NA NA 170 NA NA NA NA 138 151 NA NA NA NA NA 180 NA 105 NA NA NA NA NA NA NA NA NA NA 163 59 80 FAN NAT NA 130 NA NA NA NA NA NA NA FAN NAT NA NA NA NA 200 95 FAN NAT Min Max Max NA NA NA NA NA NA NA NAT Min Max Max Min Max Max 123 115 FAN Min Max Max NA NA NA NA NAT 12 Max Max 73 67 FAN 10 Min Max Max Min NA NA NA NA Category I 445 238 1103 631 643 1089 585 NA 323 1408 810 883 1624 932 463 2076 1240 321 NA NA 442 293 1078 593 398 1381 770 571 2044 1220 278 NA NA 395 NA NA 533 546 1294 695 761 1945 1090 318 NA NA 458 NA 1009 1805 970 258 NA NA NA NA NA NA NA 63 352 420 370 355 1038 562 NA NA 78 445 504 447 1337 728 616 1251 660 NA 95 550 610 674 1994 1140 844 1898 1040 132 792 CHIMNEYS AND VENTS Table 8-9 Table 8-9 Single-Wall Metal Pipe or Type B Asbestos Cement Vent with Single Appliance [NFPA 54:Table 13.1(e)] Number of Appliances: Single Appliance Vent Connection: Connected Directly to Pipe or Vent Appliance Type: Height H (ft) Lateral L (ft) 8 0 2 5 10 6 10 15 20 30 50 0 2 5 3 Draft Hood-Equipment Diameter - D (in.) To be used with chimney area within the size limits at bottom 4 5 6 7 8 Appliance Input Rating in Thousands of Btu per Hour 10 Maximum Appliance Input Rating in Thousands of Btu per Hour 12 39 31 28 70 55 51 116 94 88 170 141 128 232 194 177 312 260 242 500 415 390 750 620 600 0 2 5 10 15 45 35 32 27 NA 84 67 61 54 46 138 111 104 94 84 202 168 153 143 130 279 233 215 200 186 372 311 289 274 258 606 505 480 455 432 912 760 724 700 666 0 2 5 10 15 20 53 42 38 32 NA NA 0 2 5 10 15 20 0 2 5 10 15 20 30 0 2 5 10 15 20 30 42 32 29 24 49 39 35 30 NA NA 56 44 NA NA NA NA NA NA NA NA NA NA NA NA 76 61 56 49 91 72 67 58 50 NA 101 80 74 65 55 NA 108 84 78 68 NA NA NA 120 95 NA NA NA NA NA 126 102 95 86 151 122 110 103 93 82 163 136 123 115 104 91 183 148 137 125 113 99 NA 210 171 159 146 NA NA NA 185 154 141 131 223 186 170 158 144 132 252 210 192 178 163 149 276 230 210 196 177 163 NA 310 260 234 221 200 185 NA 252 210 194 180 312 260 240 223 207 195 342 286 264 246 228 214 384 320 296 274 258 240 192 443 370 342 318 292 276 222 340 284 264 250 542 451 430 406 420 350 325 308 291 273 684 570 540 514 488 466 529 441 410 388 366 344 295 878 730 694 656 625 596 540 470 392 364 345 326 306 590 492 474 456 407 384 330 770 641 610 571 550 525 980 820 780 730 705 670 605 815 680 648 625 1040 865 825 795 760 726 1190 990 945 910 870 832 1370 1140 1080 1050 1000 960 890 1550 1290 1230 1190 1130 1080 1010 135 2007 CALIFORNIA MECHANICAL CODE Table 8-10 Table 8-10 Type B Double-Wall Vent with Two or More Appliances and Type B Double-Wall Connector [NFPA 54:Table 13.2(a)] Number of Appliances: Two or More Appliance Vent Connection: Type B Double-Wall Connector Appliance Type: 3 4 Category I Type B Double-Wall Vent and Connector Diameter — D (in.) 5 6 7 8 9 Appliance Input Rating in Thousands of Btu per Hour 10 Height Rise FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT FAN NAT H R (ft.) (ft.) Min MaxMaxMin MaxMaxMinMax MaxMin Max MaxMinMax MaxMin Max Max Min Max Max MinMaxMax 6 8 10 15 20 30 50 100 1 2 3 22 23 24 37 41 44 26 31 35 35 37 38 66 46 75 55 81 62 46 106 48 121 49 132 58 164 104 77 225 142 92 296 60 183 124 79 253 168 95 333 62 199 139 82 275 189 97 363 185 220 248 109 376 112 424 114 463 237 128 466 289 282 131 526 345 317 134 575 386 1 2 3 22 23 24 43 47 50 28 33 37 34 36 37 78 50 86 59 92 67 49 123 78 65 189 113 89 257 154 106 341 51 136 93 67 206 134 91 282 182 109 374 52 146 104 69 220 150 94 303 205 111 402 200 238 268 125 436 128 479 131 515 257 146 542 314 305 149 596 372 342 152 642 417 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 22 23 24 21 22 24 21 22 23 20 21 22 19 21 22 18 19 20 40 44 47 50 53 55 54 57 60 62 64 66 71 73 75 82 83 84 27 32 36 30 35 40 31 37 42 33 39 44 36 43 48 37 44 50 35 36 37 33 35 36 89 53 96 63 102 71 31 33 34 113 59 118 70 123 79 33 34 35 30 32 33 28 30 31 Common Vent Capacity Vent Height H (ft) 6 8 10 15 20 30 50 100 136 72 48 80 57 87 64 4 99 56 105 66 110 74 133 64 137 76 141 86 158 66 161 79 163 89 5 72 86 96 49 114 76 64 176 109 84 243 148 100 320 51 128 90 66 195 129 86 269 175 103 356 53 139 101 67 210 145 88 290 198 105 384 47 142 83 64 220 120 88 298 163 110 389 49 153 99 66 235 142 91 320 193 112 419 51 163 111 68 248 160 93 339 218 115 445 46 157 87 62 246 125 86 334 171 107 436 48 167 104 64 259 149 89 354 202 110 463 50 176 116 66 271 168 91 371 228 113 486 45 181 93 60 288 134 83 391 182 103 512 47 190 110 62 299 158 85 408 215 105 535 48 198 124 64 309 178 88 423 242 108 555 43 216 101 57 349 145 78 477 197 97 627 45 223 119 59 358 172 81 490 234 100 645 46 229 134 61 366 194 83 502 263 103 661 40 262 104 53 442 150 73 611 204 91 810 42 267 123 55 447 178 75 619 242 94 822 44 272 138 57 452 200 78 627 272 97 834 194 230 258 214 253 286 224 265 300 238 282 317 257 306 343 266 316 355 118 408 121 454 123 492 134 493 137 532 140 565 131 552 134 587 137 618 125 649 129 679 132 706 120 797 123 820 126 842 7 273 162 609 333 323 165 658 394 365 167 700 444 285 158 681 347 339 161 725 414 383 164 764 466 305 151 802 372 360 155 840 439 405 158 874 494 330 144 984 403 392 148 1014 478 441 151 1043 538 112 1038 341 135 1285 417 115 1054 405 139 1306 494 118 1069 455 142 1327 555 Type B Double-Wall Common Vent Diameter — D (in.) 6 248 138 507 303 294 141 564 358 330 143 612 402 8 9 10 Combined Appliance Input Rating in Thousands of Btu per Hour FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT +FAN+NAT+NAT+FAN +NAT +NAT+FAN+NAT +NAT+FAN +NAT +NAT+FAN +NAT +NAT+FAN+NAT+NAT+FAN+NAT+NAT 92 101 110 125 136 152 167 175 81 65 90 73 97 79 112 91 123 102 138 118 153 134 163 NA 140 155 169 195 215 244 279 311 116 129 141 164 183 210 244 277 103 114 124 144 160 185 214 NA 204 224 243 283 314 361 421 489 161 178 194 228 255 297 353 421 147 163 178 206 229 266 310 NA 309 339 367 427 475 547 641 751 248 275 299 352 394 459 547 658 200 404 223 444 242 477 280 556 310 621 360 720 423 854 479 1025 314 348 377 444 499 585 706 873 260 290 315 365 405 470 550 625 547 602 649 753 842 979 1164 1408 434 480 522 612 688 808 977 1215 335 378 405 465 523 605 705 800 672 740 800 924 1035 1209 1451 1784 520 577 627 733 826 975 1188 1502 410 465 495 565 640 740 860 975 CHIMNEYS AND VENTS Table 8-10 continued Table 8-10 [NFPA 54:Table 13.2(a)] Continued Vent Connector Height Rise H R (ft) (ft) 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 8 10 15 20 30 50 100 12 14 H (ft.) 6 Appliance Type: Appliance Vent Connection: 764 496 897 616 NA NA 822 516 952 644 1050 772 870 536 997 664 1095 792 967 568 1085 712 1181 856 1051 596 1162 748 1253 900 1217 632 1316 792 1400 952 1479 689 1561 860 1631 1031 1923 712 1984 888 2035 1064 223 230 NA 238 244 252 249 256 263 272 279 286 291 298 307 286 294 303 273 281 290 254 263 272 12 16 18 1046 1231 NA 1126 1307 1445 1195 1371 1509 1334 1499 1632 1443 1597 1726 1664 1802 1920 2023 2139 2242 2644 2731 2811 14 653 827 NA 696 884 1072 730 924 1118 790 1006 1222 840 1064 1288 910 1160 1410 1007 1291 1575 1050 1346 1642 281 287 NA 298 305 313 311 318 325 336 344 351 357 365 373 367 376 384 350 359 369 326 336 346 1371 1617 NA 1478 1719 1902 1570 1804 1989 1760 1978 2157 1911 2116 2287 2183 2366 2524 2659 2814 2951 3490 3606 3714 853 1081 NA 910 1150 1390 955 1205 1455 1030 1320 1610 1095 1395 1695 1190 1510 1830 1315 1685 2055 1370 1760 2150 990 815 1735 1336 1065 10 1076 841 712 1542 1200 995 2093 1625 1300 20 1405 1116 916 2006 1588 1290 2722 30 50 100 1247 24 346 352 NA 365 372 380 379 387 395 408 416 424 430 438 450 461 474 485 435 447 461 402 414 426 1772 2069 NA 1920 2211 2434 2049 2332 2556 2317 2579 2796 2533 2778 2984 2891 3110 3299 3548 3730 3893 4707 4842 4968 NAT FAN NAT FAN NAT FAN NAT Max Min Max Max Min Max Max MinMax Max 1080 1370 NA 1150 1460 1770 1205 1535 1865 1305 1665 2025 1385 1765 2145 1540 1920 2340 1665 2135 2605 1740 2220 2700 NA NA NA NA 471 478 NA 486 494 NA 523 533 NA 554 567 NA 619 632 NA 580 594 NA 523 539 FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN +FAN +NAT+NAT+FAN +NAT +NAT +FAN +NAT +NAT 994 22 NA NA NA NA 2737 3018 NA 2887 3169 NA 3197 3470 NA 3447 3708 NA 3840 4080 NA 4601 4808 NA 5982 6143 NA NA NA NA 1800 2180 NA 1890 2290 NA 2060 2510 NA 2180 2650 NA 2365 2875 NA 2633 3208 NA 2750 3350 NA NA NA NA 560 568 NA 581 589 NA 624 634 NA 661 671 NA 728 741 NA 709 724 NA 639 654 NA NA NA NA 3319 3665 NA 3502 3849 NA 3881 4216 NA 4190 4511 NA 4861 4976 NA 5569 5826 NA 7254 7453 NA NA NA NA 2180 2640 NA 2280 2760 NA 2490 3030 NA 2630 3190 NA 2860 3480 NA 3185 3885 NA 3330 4070 Combined Appliance Input Rating in Thousands of Btu per Hour 696 588 1284 15 20 Type B Double-Wall Common Vent Diameter — D (in.) 16 18 20 22 900 8 Category I Type B Double-Wall Vent Connector Appliance Input Rating Limits in Thousands of Btu per Hour FAN NAT FAN NAT FAN NAT FAN Min Max Max Min Max Max Min Max Max Min Max 174 180 NA 186 192 198 196 201 207 214 221 228 223 230 237 216 223 231 206 213 221 192 200 208 Two or More Type B Double-Wall Vent Connector Diameter – D (in.) Common Vent Capacity Vent Height Number of Appliances: 773 652 1423 1103 912 1927 986 825 1794 1410 1158 2440 1658 1327 1025 2373 1892 1525 3220 2024 1640 1280 2911 2347 1863 3964 2569 2131 1670 3732 3076 2450 5125 1491 1190 1910 1510 2147 1690 2558 1990 3183 2430 4202 3200 1660 3488 2677 1970 4206 3226 2390 2665 2030 4241 3278 2400 5123 3957 2920 2507 1936 3162 2439 2727 2113 1645 3184 2484 3561 2798 4197 3326 5184 4149 6749 5509 1510 1910 2140 2520 3075 4050 3444 4026 4548 5303 6567 8597 24 2180 +NAT +NAT 2838 NA NA NA NA 2590 3130 NA 2710 3270 NA 2960 3600 NA 3130 3790 NA 3410 4150 NA 3790 4620 NA 3950 4810 NAT FAN FAN NAT FAN FAN NAT +FAN 1345 NA NA NA NA 3957 4373 NA 4175 4593 NA 4631 5035 NA 5005 5392 NA 5606 5961 NA 6633 6943 NA 8650 8892 FAN +FAN +NAT +NAT 2253 1732 NA NA NA NA 662 669 NA 686 694 NA 734 743 NA 772 785 NA 847 860 NA 851 867 NA 769 786 3133 3552 4193 5240 6986 +FAN+NAT +NAT +FAN +NAT +NAT 1860 3890 2998 2360 4971 3862 2640 5573 4352 3110 6539 5157 3800 8116 6458 5000 10681 8648 2200 4695 3616 2680 2790 6016 4670 3400 3120 6749 5261 3800 3680 7940 6247 4480 4500 9837 7813 5475 5920 13004 10499 7200 137 2007 CALIFORNIA MECHANICAL CODE Table 8-11 Table 8-11 Type B Double-Wall Vent with Two or More Appliances and Single-Wall Metal Connector [NFPA 54:Table 13.2(b)] Number of Appliances: Appliance Type: Two or More Category I Appliance Vent Connection: Single-Wall Metal Connector 3 Vent Connector Height Rise H (ft) 6 8 10 15 20 30 50 100 R 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 FAN NA NA NA NA NA NA NA NA NA NA NA NA 49 52 55 47 51 54 46 49 52 45 48 51 NAT NA NA NA NA NA NA NA NA NA NA NA NA 56 59 62 60 62 64 69 71 72 79 80 81 26 31 34 27 32 35 28 33 36 29 34 39 30 36 40 31 37 42 34 40 45 34 41 46 FAN Height H 4 NAT NA NA NA NA NA NA NA 84 89 79 83 87 78 82 87 77 81 85 75 79 83 71 75 79 NA NA NA NA NA NA NA 85 91 87 94 100 97 103 107 110 115 119 128 132 136 150 153 157 46 55 62 48 57 64 50 59 67 52 62 70 54 64 72 57 67 76 60 72 82 61 73 85 FAN NAT FAN NAT NA NA 121 NA 125 130 119 124 129 116 121 127 115 120 125 112 117 122 109 114 119 104 110 114 NA NA 131 NA 126 138 121 134 144 138 150 160 152 163 172 175 185 193 207 215 221 249 255 260 71 85 95 75 89 100 77 91 102 81 97 109 84 101 113 89 106 120 96 113 123 98 115 129 NA 168 175 NA 184 191 182 189 197 177 185 193 175 182 190 169 177 185 162 170 178 153 160 168 NA 182 198 NA 193 208 186 203 217 214 230 243 238 252 264 278 290 300 336 345 353 424 428 433 102 123 138 106 127 144 110 132 148 116 138 157 120 144 164 129 152 172 137 164 186 140 167 190 FAN Min Max 207 215 222 226 234 241 240 248 257 238 246 255 233 243 252 226 236 244 217 226 235 205 212 222 223 251 273 240 266 287 253 278 299 291 314 333 325 346 363 380 397 412 460 473 486 585 593 603 NAT Max 140 167 188 145 173 197 150 183 203 158 189 215 165 197 223 175 208 235 188 223 252 192 228 256 8 5 10 15 20 30 50 100 138 NA 78 64 NA 113 NA 94 76 163 137 87 71 NA NAT 262 271 279 285 293 302 302 311 320 312 321 331 306 317 326 296 307 316 284 294 304 269 279 289 293 331 361 316 353 381 335 369 398 380 411 438 425 453 476 497 521 542 604 623 640 774 788 801 183 219 247 191 228 256 196 235 265 208 248 281 217 259 294 230 274 309 245 293 331 249 299 339 FAN NAT FAN FAN NAT FAN FAN NAT FAN 99 126 111 218 331 436 120 200 158 144 237 189 174 173 159 304 244 196 357 292 236 269 218 398 467 FAN FAN NAT Min Max Max Min Max Max 325 334 344 352 360 370 372 381 391 397 407 418 390 400 412 378 389 400 364 376 387 345 358 368 373 422 462 403 450 489 429 473 511 482 522 557 538 574 607 630 662 690 768 793 816 993 1011 1027 234 281 316 244 292 328 252 302 339 266 317 360 276 331 375 294 349 394 314 375 423 321 383 431 6 7 8 9 Combined Appliance Input Rating in Thousands of Btu per Hour FAN FAN NAT FAN FAN NAT NA FAN Min Max Max Type B Double-Wall Vent Diameter — D (in.) (ft) +FAN +NAT+NAT +FAN +NAT +NAT +FAN +NAT +NAT +FAN +NAT +NAT +FAN 6 10 Appliance Input Rating Limits in Thousands of Btu per Hour Min Max Max Min Max Max Min Max Max Common Vent Capacity Vent Single-Wall Metal Vent Connector Diameter — D (in.) 5 6 7 8 9 4 Min Max Max (ft) Vent Connector Capacity 447 458 468 481 492 501 506 517 528 556 568 579 546 558 570 528 541 555 507 520 535 476 490 506 463 524 574 502 560 609 534 589 637 596 646 690 664 709 750 779 819 855 951 983 1013 1236 1259 1280 286 344 385 299 355 400 308 368 413 324 387 437 336 403 457 358 425 482 384 458 518 393 469 527 10 NAT FAN FAN NAT FAN FAN NAT +NAT +NAT +FAN +NAT +NAT+FAN +NAT+NAT 310 342 369 257 541 429 332 665 515 309 638 512 398 787 617 285 592 473 373 730 569 407 460 487 121 108 88 189 159 140 275 221 200 416 343 274 544 434 357 738 599 456 905 718 553 145 132 113 236 202 180 350 286 257 533 446 349 703 570 459 958 790 593 1183 952 723 153 NA 131 159 166 118 145 98 128 208 268 297 177 233 263 156 208 NA 305 406 469 247 337 398 223 296 NA 463 622 726 383 529 633 302 410 464 606 833 999 487 686 846 395 535 606 824 1139 1378 673 954 1185 512 1013 689 1418 780 1741 808 1157 1459 626 838 948 CHIMNEYS AND VENTS Table 8-12 Table 8-12 Masonry Chimney with Two or More Appliances and Type B Double-Wall Connector [NFPA 54:Table 13.2(c)] Number of Appliances: Appliance Type: Appliance Vent Connection: Vent Connector Capacity Vent Connector Height Rise H R 6 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 (ft.) (ft.) 8 10 15 20 30 50 100 3 Type B Double-Wall Vent Connector Diameter — D (in.) 4 FAN NAT FAN Two or More Category I Type B Double-Wall Connector 5 6 7 8 Appliance Input Rating Limits in Thousands of Btu per Hour FAN NAT FAN NAT FAN NAT FAN NAT NAT 9 FAN MinMax Max Min Max Max Min Max Max Min Max Max Min Max Max Min Max Max Min 24 26 27 24 26 27 24 26 27 24 25 26 24 25 26 24 25 26 23 24 26 23 24 25 33 43 49 39 47 52 42 50 55 48 55 59 52 58 63 54 60 64 51 59 64 46 53 59 21 28 34 22 29 34 22 29 35 23 31 35 24 31 35 25 32 36 25 32 36 24 31 35 39 41 42 39 40 42 38 40 41 38 39 41 37 39 40 37 38 40 36 37 39 35 37 38 62 79 92 72 87 97 80 93 105 93 105 115 102 114 123 111 122 131 116 127 135 108 120 130 40 52 61 41 53 62 42 54 63 44 55 64 46 56 65 48 58 66 51 61 69 50 60 68 52 53 55 55 57 59 55 57 58 54 56 57 53 55 57 52 54 56 51 53 55 49 51 53 Common Vent Capacity 12 106 133 155 117 140 159 130 153 170 154 174 189 172 190 204 192 208 221 209 225 237 208 224 237 67 85 97 69 86 98 71 87 100 74 89 102 77 91 104 82 95 107 89 102 115 92 105 118 65 67 69 71 73 75 74 76 78 72 74 76 71 73 75 69 72 74 67 70 72 65 67 69 194 230 262 213 246 269 232 261 284 277 299 319 313 335 353 357 376 392 405 421 435 428 444 458 101 124 143 105 127 145 108 129 148 114 134 153 119 138 157 127 145 163 143 161 180 155 174 193 87 89 91 94 97 99 101 103 106 100 103 105 98 101 104 96 99 101 92 95 98 88 92 94 274 324 369 304 350 383 324 366 397 384 419 448 437 467 493 504 531 554 582 604 624 640 660 679 141 173 203 148 179 206 153 184 209 164 192 215 173 199 222 187 209 233 213 235 260 237 260 285 104 107 109 113 116 119 120 123 126 125 128 131 123 126 129 119 122 125 115 118 121 109 113 116 370 436 491 414 473 517 444 498 540 511 558 597 584 625 661 680 715 746 798 827 854 907 933 956 201 232 270 210 240 276 216 247 281 229 260 292 239 270 301 255 287 317 294 326 357 334 368 399 10 124 127 129 134 137 139 142 145 147 153 156 159 150 153 156 145 149 152 140 143 147 134 138 141 NAT FAN 479 562 633 539 615 672 582 652 705 658 718 760 752 805 851 883 928 968 1049 1085 1118 1222 1253 1282 253 300 349 267 311 358 277 321 366 297 339 382 312 354 396 337 378 418 392 433 474 454 497 540 145 148 151 156 160 163 165 168 171 184 187 190 180 184 187 175 179 182 168 172 176 161 165 169 Minimum Internal Area of Masonry Chimney Flue (in.2) 28 38 50 63 78 19 NAT Max Max Min Max Max 599 694 795 682 776 848 739 825 893 824 900 960 943 1011 1067 1115 1171 1220 1334 1379 1421 1589 1626 1661 319 378 439 335 394 452 348 407 463 375 432 486 397 452 505 432 484 535 506 558 611 596 651 705 113 Vent Combined Appliance Input Rating in Thousands of Btu per Hour Height H FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT (ft.) 6 8 10 15 20 30 50 100 +FAN +NAT +NAT +FAN +NAT+NAT +FAN +NAT +NAT +FAN +NAT +NAT +FAN +NAT +NAT +FAN +NAT+NAT+FAN +NAT +NAT +FAN +FAN +NAT NA 74 25 NA 119 46 NA 178 71 NA 257 103 NA 351 143 NA 458 188 NA 582 246 1041 853 NA NA 84 31 NA 138 56 NA 207 90 NA 299 131 NA 409 177 606 538 236 776 686 302 1226 1010 454 419 1513 1286 648 NA 80 NA NA NA NA 28 36 41 NA NA NA NA NA NA NA NA NA NA 130 53 NA 152 67 NA NA 75 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 193 82 233 106 270 137 250 NA NA 122 NA NA NA NA NA NA NA NA 279 334 368 404 119 152 172 198 NA NA NA NA NA 523 565 615 NA NA 384 467 508 564 620 NA 163 212 243 278 328 348 NA 682 742 816 879 NA 501 218 724 611 283 874 668 325 955 747 381 1062 831 461 1165 NA 499 NA 636 781 858 969 278 1144 365 1374 496 1702 1089 606 1905 NA 669 2053 937 408 1156 546 1473 749 1692 922 1921 1058 139 2007 CALIFORNIA MECHANICAL CODE Table 8-13 Table 8-13 Masonry Chimney with Two or More Appliances and Single-Wall Metal Connector [NFPA 54: Table 13.2(d)] Number of Appliances: Appliance Type: Two or More Category I Appliance Vent Connection: 3 Vent Connector Height Rise H R FAN (ft.) 6 8 10 15 20 30 50 100 (ft.) 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NAT FAN 21 28 34 21 28 34 22 29 34 23 30 34 23 30 35 24 31 35 24 31 35 NA NA 23 NA NA 30 NA NA 34 H (ft) 6 8 10 15 20 30 50 100 140 12 5 NAT NA NA NA NA NA NA NA NA 97 NA 92 96 87 91 96 86 91 95 85 89 94 84 88 93 NA NA NA NA NA NA NA NA 102 NA 103 112 99 111 119 108 119 127 113 123 131 39 52 61 40 52 62 41 53 62 43 54 63 45 55 64 47 57 65 50 60 68 104 49 115 59 124 67 19 6 7 8 Appliance Input Rating Limits in Thousands of Btu per Hour FAN Min Max Max Min Common Vent Capacity Vent Height Vent Connector Capacity Single-Wall Metal Vent Connector Diameter — D (in.) 4 Min Max Max Single-Wall Metal Connector NA NA 134 NA 137 143 130 136 143 129 135 141 128 134 140 126 132 138 124 130 136 Max NAT NA NA 153 NA 139 156 151 150 166 151 170 185 167 185 199 187 203 216 204 218 231 122 200 127 215 133 228 FAN Max Min 66 84 97 68 85 98 70 86 99 73 88 101 76 90 103 80 93 105 87 100 112 179 186 193 195 202 210 202 210 217 199 207 215 197 205 213 193 201 209 188 196 205 NAT Max Max 191 227 258 208 240 264 225 255 277 271 295 315 303 325 343 347 366 381 392 408 422 89 182 410 102 190 425 115 199 438 100 123 142 103 125 145 106 128 147 112 132 151 117 136 154 124 142 160 139 158 176 151 169 188 FAN Min Max 243 253 262 617 636 654 231 239 247 250 258 266 267 276 284 268 277 286 265 274 282 259 269 277 252 262 271 271 321 365 298 343 376 316 358 389 376 411 439 425 455 481 492 518 540 567 588 607 NAT Max FAN Min Max 232 315 254 326 279 337 875 899 921 140 172 202 146 177 205 151 181 207 161 189 213 169 195 219 183 205 229 208 230 255 292 301 309 313 323 332 333 343 352 349 359 368 345 355 365 338 348 358 328 339 349 366 432 491 407 465 509 434 489 530 502 548 586 569 610 644 665 699 729 778 806 831 NAT Max 200 231 269 207 238 274 213 244 279 225 256 289 235 266 298 250 282 312 287 320 351 328 361 392 9 FAN Min 10 NAT Max Max FAN NAT Min 362 474 252 499 373 557 299 509 381 634 348 519 387 530 263 529 397 607 309 540 407 663 356 551 410 571 273 558 420 640 317 569 430 694 363 580 445 646 291 623 456 706 334 634 466 755 378 646 439 734 306 614 450 787 348 627 461 831 391 639 430 864 330 600 442 908 372 613 452 946 412 626 417 1022 383 582 429 1058 425 596 440 1090 466 610 38 50 316 376 437 331 391 450 343 403 459 366 424 479 387 443 496 421 473 524 492 545 597 402 1181 444 560 1537 580 415 1210 488 575 1570 634 427 1238 529 589 1604 687 Minimum Internal Area of Masonry Chimney Flue (in.2) 28 Max Max 594 696 793 672 766 838 727 813 880 808 884 945 921 986 1042 1089 1145 1193 1302 1346 1386 63 Combined Appliance Input Rating in Thousands of Btu per Hour 78 113 FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT FAN FAN NAT +FAN +NAT +NAT +FAN +NAT+NAT +FAN+NAT +NAT +FAN +NAT +NAT +FAN +NAT+NAT +FAN +NAT +NAT +FAN+NAT+NAT +FAN+FAN +NAT NA NA 25 NA 118 45 NA NA 31 NA 136 56 NA NA NA NA NA NA NA NA 28 36 NA NA NA NA NA NA NA NA NA 128 52 NA NA NA 176 71 190 81 205 89 NA NA NA 255 276 295 102 118 129 NA 348 142 NA NA 405 175 NA NA 380 162 NA NA 66 NA 230105 NA 335 150 NA 400 210 NA NA NA NA NA135 NA 398 195 NA 558 275 NA NANA NA NA 74 NA NA NA NA NA NA NA NA 247120 NANA NA NA NA 362 NA NA 170 NA NA NA 503 240 NA 612 325 NA NA NA NA 455 497 532 187 217 234 NA 579 245 NA 633 277 771 680 300 846 NA 1216 1000 450 677 602 280 866 808 739 377 1052 957 490 494 NA NA 663 2006 1885 1046 765 NA NA 661 821 NA 321 456 947 772 360 NA 1136 928 405 849 415 1152 1076 600 1359 1139 540 1495 1264 640 1682 1447 740 1879 1672 910 CHIMNEYS AND VENTS Table 8-14 Table 8-14 Single-Wall Metal Pipe or Type B Asbestos Cement Vent with Two or More Appliances [NFPA 54: Table 13.2(e)] Number of Appliances: Two or More Appliance Type: Draft Hood Equipped Appliance Vent Connection: Direct to Pipe or Vent Vent Connector Capacity Total vent Heigh Connector Rise (ft.) (ft.) 15 30 and up 4 21 28 34 23 30 35 25 31 36 40 53 61 44 56 64 49 58 68 5 6 7 8 68 86 98 77 92 102 84 97 107 102 124 147 117 134 155 129 145 164 146 178 204 179 194 216 190 211 232 205 235 275 240 265 298 270 295 321 Maximum Appliance Input Rating in Thousands of Btu per Hour 1 2 3 1 2 3 1 2 3 6-8 3 Vent Connector Diameter – D (in.) Common Vent capacity Total Vent Height 6 8 10 15 20 30 50 4 48 55 59 71 80 NA NA 5 78 89 95 115 129 147 NA Common Vent Diameter – D (in.) 6 111 128 136 168 186 215 NA 7 155 175 190 228 260 300 360 8 205 234 250 305 340 400 490 10 320 365 395 480 550 650 810 12 NA 505 560 690 790 940 1190 141 2007 CALIFORNIA MECHANICAL CODE Table 8-15 Table 8-15 Exterior Masonry Chimney [NFPA 54: Table 13.2(f)] Special Use: Minimum Allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hour Number of Appliances: Single Appliance Type: Appliance Vent Connection: Vent Height (ft) NAT Type B Double-Wall Connector Internal Area of Chimney (Square Inches) 28 38 50 63 37˚F or greater 6 8 10 15 20 30 50 12 19 0 0 0 NA NA NA NA 0 0 0 0 NA NA NA Local 99% winter design temperature: 37˚F or greater 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 123 190 249 184 0 NA NA NA 393 334 NA NA NA NA NA 0 0 0 0 0 0 579 6 8 10 15 20 30 50 0 0 0 NA NA NA NA 0 0 51 NA NA NA NA 68 82 97 NA NA NA NA 116 127 141 NA NA NA NA 156 167 183 233 NA NA NA 180 187 201 253 307 419 NA 212 214 225 274 330 445 NA 266 263 265 305 362 485 763 6 8 10 15 20 30 50 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 197 214 NA NA NA NA 215 226 245 296 352 NA NA 259 264 278 331 387 507 NA 349 352 358 398 457 581 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 312 331 393 450 NA NA 416 423 430 485 547 682 972 27˚F to 36˚F 17˚F to 26˚F 5˚F to 16˚F 6 8 10 15 20 30 50 -10˚F to4˚F 6 8 10 15 20 30 50 –11˚F or Lower 142 NA NA NA NA NA NA NA NA NA NA NA NA NA NA Local 99% Winter Design Temperature: 27 to 36˚F Local 99% Winter Design Temperature: 17 to 26˚F Local 99% Winter Design Temperature: 5 to 16˚F NA NA NA NA NA NA NA NA NA NA NA 289 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Local 99% Winter Design Temperature: –10 to 4˚F NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 78 NA NA NA NA NA NA NA Local 99% Winter Design Temperature: –11˚F or Lower Not recommended for any vent configuration 113 484 494 513 586 650 805 1003 CHIMNEYS AND VENTS Table 8-16 – Table 8-17 Table 8-16 Exterior Masonry Chimney [NFPA 54: Table 13.2(f)] Special Use: Combined Appliance Maximum Input Rating in Thousands of Btu per Hour Number of Applications: Two or More Appliance Type: NAT + NAT Appliance Vent Connection: Type B Double-Wall Connector Vent Height (ft) 12 6 8 10 15 20 30 50 100 25 28 31 NA NA NA NA NA Internal Area of Chimneys (Square Inches) 19 46 53 56 67 NA NA NA NA 28 71 82 90 106 NA NA NA NA 38 50 103 119 131 152 NA NA NA NA 143 163 177 212 NA NA NA NA 63 188 218 236 283 325 NA NA NA 78 113 246 278 302 365 419 496 NA NA NA 408 454 546 648 749 922 NA Table 8-17 Exterior Masonry Chimney [NFPA 54: Table 13.2(g)] Special Use: Combined Appliance Minimum Input Rating in Thousands of Btu per Hour Number of Applications: Two or More Appliance Type: NAT + NAT Appliance Vent Connection: Vent Height (ft) 37˚F or Greater Type B Double-Wall Connector Internal Area of Chimney (Square Inches) 12 19 6 8 10 15 20 30 50 100 0 0 0 NA NA NA NA NA 0 0 0 0 NA NA NA NA 0 0 0 0 NA NA NA NA 6 8 10 15 20 30 50 100 0 0 0 NA NA NA NA NA 0 0 51 NA NA NA NA NA 68 82 NA NA NA NA NA NA 27˚F to 36˚F 28 38 50 Local 99% Winter Design Temperature: 37˚F or Greater 0 0 0 0 NA NA NA NA 63 78 113 0 0 0 0 NA NA NA NA 0 0 0 0 184 393 NA NA 0 0 0 0 0 334 NA NA NA 0 0 0 0 0 579 NA NA NA NA NA NA NA NA NA 180 187 201 253 307 NA NA NA 212 214 225 274 330 445 NA NA NA 263 265 305 362 485 763 NA Local 99% Winter Design Temperature: 27 to 36˚F NA NA NA NA NA NA NA NA 143 2007 CALIFORNIA MECHANICAL CODE Table 8-17 continued – Table 8-18 Table 8-17 [NFPA 54: Table 13.2(g)] Continued 17˚F to 26˚F Local 99% Winter Design Temperature: 6 8 10 15 20 30 50 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 6 8 10 15 20 30 50 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 5 to 16˚F 4˚F or Lower 17 to 26˚F NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA Local 99% Winter Design Temperature: 5 to 16˚F NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 264 278 331 387 NA NA NA NA 352 358 398 457 581 862 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 430 485 547 682 NA NA Local 99% Winter Design Temperature: 4˚F or Lower Not recommended for any vent configurations Table 8-18 Exterior Masonry Chimney with Two or More Appliances, FAN + NAT [NFPA 54: Table 13.2(h)] Special Use: Combined Appliance Maximum Input Rating in Thousands of Btu per Hour Number of Applications: Two or More Appliance Type: FAN + NAT Appliance Vent Connection: Type B Double-Wall Connector Vent Height H (ft) 6 8 10 15 20 30 50 100 144 12 74 80 84 NA NA NA NA NA 19 119 130 138 152 NA NA NA NA 28 178 193 207 233 250 NA NA NA Internal Area of Chimney (Square Inches) 38 257 279 299 334 368 404 NA NA 50 351 384 409 467 508 564 NA NA 63 458 501 538 611 668 747 831 NA 78 582 636 686 781 858 969 1089 NA 113 853 937 1010 1156 1286 1473 1692 1921 CHIMNEYS AND VENTS Table 8-19 Table 8-19 Exterior Masonry Chimney with Two or More Appliances, FAN + NAT [NFPA 54: Table 13.2(i)] Special Use: Minimum Allowable Input Rating of Space-Heating Appliance in Thousands of Btu per Hour Number of Applications: Two or More Appliance Type: FAN + NAT Appliance Vent Connection: Type B Double-Wall Connector Vent Height (ft) Internal Area of Chimney (Square Inches) 12 19 6 8 10 15 20 30 50 100 0 0 0 NA NA NA NA NA 0 0 0 0 NA NA NA NA 0 0 0 0 123 NA NA NA 6 8 10 15 20 30 50 100 0 0 0 NA NA NA NA NA 0 0 51 111 NA NA NA NA 68 82 97 142 187 NA NA NA 37˚F or greater 27˚F to 36˚F 17˚F to 26˚F 28 38 50 63 78 113 0 0 0 0 249 398 NA NA 0 0 0 0 184 393 714 NA 0 0 0 0 0 334 707 NA 0 0 0 0 0 0 579 1600 156 167 183 233 284 319 NA NA 180 187 210 253 307 419 672 NA 212 214 225 274 330 445 705 NA 266 263 265 305 362 485 763 1554 182 197 214 263 316 429 NA NA 215 226 245 296 352 470 723 NA 259 264 278 331 387 507 766 NA 349 352 358 398 457 581 862 1669 252 269 289 346 408 531 797 NA 301 312 331 393 450 580 853 NA 416 423 430 485 547 682 972 1833 296 320 339 404 468 603 NA NA 349 371 397 457 528 667 955 NA 484 494 513 586 650 805 1003 NA Local 99% Winter Design Temperature: 37˚F or Greater 0 0 0 0 190 334 NA NA Local 99% Winter Design Temperature: 27˚F to 36˚F 116 127 141 183 230 330 NA NA Local 99% Winter Design Temperature: 6 8 10 15 20 30 50 100 0 52 NA NA NA NA NA NA 55 74 90 NA NA NA NA NA 6 8 10 15 20 30 50 100 NA NA NA NA NA NA NA NA 78 94 111 NA NA NA NA NA Local 99% Winter Design Temperature: 5 to 16˚F 121 166 214 135 182 230 149 198 250 193 247 305 NA 293 360 NA 377 450 NA NA NA NA NA NA 6 8 10 15 20 30 50 100 NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA 145 159 175 NA NA NA NA NA 5˚F to 16˚F -10˚F to 4˚F -11˚F or Lower 99 111 125 167 212 NA NA NA 17˚F to 26˚F 141 154 169 212 258 362 NA NA Local 99% Winter Design Temperature: –10˚F to 4˚F 196 213 231 283 333 NA NA NA 249 269 292 351 408 NA NA NA Local 99% Winter Design Temperature: –11˚F or Lower Not recommended for any vent configurations 145 2007 CALIFORNIA MECHANICAL CODE 146