AC Leakage current transformers - yuanxing electronics transformers

advertisement
AC Leakage current transformers
YUANXING TA25LXX Series of AC
Leakage current transformers Base
theory of zero flux, TA25LXX series
is used for online insulation monitoring
device of high-voltage electric equipment
in electric substation, which can exactly
transit mA AC leakage current.
YUANXING can designe and manufacture to meet the specific design challenges of the client’s specific application.
The following models are only a small sampling of the many
different products which have been and are currently
being manufactured.
FEATURES
• Center hole-through, easy installation,on the safe side.
• Metal casing,better capacity of resisting disturbance,be
adequate for inside and outside surroundings. • High-sensitivity/accuracy,good linearity. • Two series for selection: passive and active
APPLICATIONS
• Used in high voltage electric power equipment insulation
monitoring plant, which is stalled in transformers station.
Provide exact measurement for mA leakage current of
high voltage power equipment, such as transformers
sleeve, current transformers
TA25XL
PART NUMBERS
SPECIFICATIONS
• Frequency:50Hz
• Rated current:10mA、20mA、30mA
• Measuring range:0.5~700mA
• Output signal:mV/mA
• Amplitude error:±0.1%
• Phase error:±1'
• Environmental temperature:一30º C~+75º C
Influence on phase error by temperature
change is<1’
• Diameter of primary center hole:Φ13mm,
25mm, 40mm, 50mm
.
Rated Output Current
Rated Input Current
AC Leakage current transformers
Casing Number
YUANXING Electronics Co., Ltd.
Yifan Road, Science & Technology Industry Park
Zibo, Shandong 255000, P.R.C.
7-1
www.yuanxing.net
sales@yuanxing.net
AC Leakage CT’s
Phone: +86-533-381-8450
Fax: +86-533-381-8724
TA 25XL
元星电子
YUANXING
AC Leakage current transformers
PERFORMANCES
Rated Input
(mA)
Number
Frequency
( Hz)
Ratio
Rated burden
(ohms)
Accuracy
class
Outline dimension (mm)
ID-L-W-H
TA25L
10~100
1000 :1
2000 :1
50/60
0
0.02
0.05
12.4-58-43-56
TA25BL
10~100
1000 :1
2000 :1
50/60
0
0.02
0.05
16.0-50-44-54.8
TA25CL
10~1000
1000 :1
2000 :1
50/60
0
0.02
0.05
25.5-68-65.5-72
10~1000
1000 :1
2000 :1
50/60
0
0.02
0.05
40.5-88-48-91
10~1000
1000 :1
2000 :1
50/60
0
0.02
0.05
50-105-86-100
TA25DL
TA25EL
OUTLINE DRAWING
4-
4-
6.5
5x2.5
45
34 ±0.2
45.5 ±0.2
2-
W
46
W
56 ±0.2
W
6.5X1.5
21 ±0.2
75 ±0.2
H
H
H
A
B
A
A
B(L
L)
B(
)
4
L
TA25DL
TA25CL
8
AC Leakage CT’s
TA25L
2
L
A
H
A
W
H)
B(
L
W
76 ±0.2
48 ±0.2
76
95 ±0.2
TA25EL
Phone: +86-533-381-8450
Fax: +86-533-381-8724
.
TA25BL
6
YUANXING Electronics Co., Ltd.
Yifan Road, Science & Technology Industry Park
Zibo, Shandong 255000, P.R.C.
7-2
www.yuanxing.net
sales@yuanxing.net
元星电子
YUANXING
AC Leakage current transformers
OUTLINE DIMENTION
Unit:mm (inch)
Part number
TA25L
TA25BL
TA25CL
TA25DL
TA25EL
L
W
A
H
B
58.0
43.0
56.0
12.4
53.0
(2.283)
(1.693)
(2.205)
(0.488)
(2.087)
50.0
44.0
54.8
12.4
53.0
(1.969)
(1.732)
(2.157)
(0.488)
(2.087)
72.0
(2.835)
25.5
(1.004)
(2.677)
68.0
(2.677)
65.5
(2.579)
68.0
88.0
48.0
91.0
40.5
88.0
(3.465)
(1.890)
(3.583)
(1.594)
(3.465)
100.0
(3.937)
50.0
100.0
(1.969)
(3.937)
105.0
(4.134)
86.0
(3.386)
AC Leakage CT’s
Phone: +86-533-381-8450
Fax: +86-533-381-8724
.
YUANXING Electronics Co., Ltd.
Yifan Road, Science & Technology Industry Park
Zibo, Shandong 255000, P.R.C.
7-3
www.yuanxing.net
sales@yuanxing.net
Download