Supply Air Temperature Reset Arik Cohen P.E. Principal AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing Education Systems (AIA/CES). Credit(s) earned on completion of this program will be reported to AIA/CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request. This program is registered with AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation. Course Description The course will cover supply air temperature control as it pertains to variable air distribution systems with re-heat at the zone level. The discussion will focus on results from the installation of a trim and respond supply air temperature control strategy recently implemented at three sites on a high technology company campus in Northern California. Learning Objectives At the end of this session, participants will be able to: 1) Understand the energy impacts as they relate to supply air temperature control in variable air volume systems that include reheat at the zone level. Constant and variable supply air temperature control schemes will be compared and discussed. 2) The session will include results and lessons learned from recent field installations of demand based supply air resets controls. Parameters to consider when recommending supply air temperature reset and barriers to successful implementation will be discussed Supply/Discharge Air Temperate Control Basics •1st Stage- economizer •2nd Stage – Dx/Cooling Coil SAT/DAT to zone VAV Boxes SAT/DAT – Supply/Discharge Air Temperature Temperature Resets Example Resets: HHW OAT Reset 200 190 HHW Setpoint [°F] • VAV: supply air temperature (SAT) based on outside air temp or return air temp or zone level information • Hot water supply temperature based on outside air or hw valve position • Condenser water temperature based on ambient wet bulb • Many others 180 170 160 150 140 130 120 20 40 60 OAT [°F] 80 SAT Temperature Resets, Why Do We Care? SAT control must be specified to • Maintain occupant comfort • Meet the conditioning requirements of all zones SAT Temperature Resets, Why Do We Care? ○ Increasing SAT - Increases the number of economizing hours thereby reducing coil load and cooling energy » Level of savings dependent on climate and reset bounds - Decreases reheat energy by increasing temperature at inlet to reheat coil » Level of savings dependent on min VAV box cfm and reset bounds - Increase fan consumption, VAV boxes open as warmer supply air is introduced resulting in high flows at the supply fan Weather Bin Data from San Jose CA OSA Temp (F) 96 94 92 90 88 86 84 82 80 78 76 74 72 70 68 66 64 62 60 58 56 54 52 50 48 46 44 42 40 38 36 34 32 Total Hrs/yr 2 5 4 7 19 11 39 96 93 155 157 226 239 320 170 339 686 719 1,040 887 781 629 487 304 392 326 169 195 104 70 72 15 2 8,760 Variable Air Volume with Reheat Return Air Exhaust Air Outside Air VFD COLD Exterior Zone DAMPER DAMPER REHEAT COIL REHEAT COIL Interior Zone DAMPER DAMPER REHEAT COIL REHEAT COIL Interior Zone DAMPER DAMPER REHEAT COIL REHEAT COIL DAMPER DAMPER Exterior Zone SAT Temperature Resets in Code (VAV with Reheat) ASHRAE Standard 90.1 (Since 2007) • “The air temperature for cooling shall be reset higher by 5°F (2.3°C) under the minimum cooling load conditions” Title 24 (Since 2005?) • “shall include controls that automatically reset supply-air temperatures: ○ 1. In response to representative building loads or to outdoor air temperature; and ○ 2. By at least 25 percent of the difference between the design supply-air temperature and the design room air temperature. The Test Sites • Site Characteristics ○ Mix of private and open office areas ○ Some “labs” ○ DDC down to the zone level ○ 80,000 – 120,000 ft2 • Study Details ○ Performed under PG&E RCx program ○ Completed over the past six months ○ Sites part of high-tech company campus Utility Data – Site 2 Electricity Consumption Rate [kWh/day] Maximum Demand [kW] 7,000 600 6,000 500 400 4,000 300 3,000 200 2,000 100 1,000 0 0 Jul Aug Sep Oct Nov Dec Jan Feb Mar Apr May Mar Apr May Jun Natural Gas Consumption Rate [therms/day] 250 therms/day 200 150 100 50 0 Jul Aug Sep Oct Nov Dec Jan Feb Jun kW kWh/day 5,000 Benchmarking – Site 2 Electricity Benchmarking PG&E CEUS - Large Office SR1 - 10 20 30 40 50 kWh/sf Gas Benchmarking PG&E CEUS - Large Office SR1 - 20 40 kBtu/sf 60 80 Screenshot of Typical Air Handler General Site Recommendations Fix Economizers Take advantage of DDC at Zone level! • Zone level scheduling • Supply Air/Duct SP Reset Estimated (Pre-Retrofit) Annual Energy, Cost and GHG Savings Measure Number Measure Name Peak Savings (kW) Energy Savings (kWh/yr) Energy Savings (therm/yr) Total Cost Savings Project Financials CO2 Emissions Avoided (tons/yr) Estimated Measure Cost Potential 2011 PG&E Incentive Simple Payback (yr) NPV RCx-1 Recommission All Economizers (AC1-8) 46.0 152,332 (22) $ 19,330 39.8 $ 44,000 $ 18,288 1.3 $ 40,000 RCx-2 Fix Zone Temperature Setpoints, Implement SAT and DSP Resets (AC1-8) 23.0 553,991 44,868 $ 103,402 446.8 $ 51,600 $ 25,800 0.2 $ 396,000 RCx-3 Schedule All Non-Essential VAV boxes and Air Handlers to Match Occupancy 0.0 282,840 9,325 $ 42,789 136.8 $ 12,000 $ 6,000 0.1 $ 173,000 Types of SA Temperature Control Constant •SA Temperature setpoint does not change Variable (zone information available to control system) •SA Temperature setpoint changes in response to some variable ○Single variable (OAT or RAT) ○Multiple variable (OAT or RAT plus additional variable such as solar gain or dewpoint) Outside Air Dry Bulb Temperature Supply Air Temperature Reset [°F] 50 [°F] 70 70 55 Types of SA Temperature Control Variable (zone level information available to Control System) • Change supply air temperature to maintain worst case VAV box at 85% (adjustable) using PID control loop • Zone temperature deviation algorithms (VAV boxes with limited info or pneumatics with DDC connected temps sensors • Trim and Respond (T&R) from Taylor Engineering SA Temperature Control T&R Sequence • Set maximum CD DAT setpoint to 68°F (adjustable). • Set minimum CD DAT setpoint to 55°F (adjustable). • Generate a cooling request when the cooling loop output signal at any zone is 95% or above (adjustable). NOTE: The cooling loop output signal is the output signal of the PI loop controlling the terminal box cold deck airflow. A value of 100% would provide the maximum cooling to the zone. SA Temperature Control T&R Sequence (cont.) • If the CD fan is on, trim the setpoint every 3 minutes (adjustable) in the following way: ○ If the number of cooling requests is zero or one (adjustable), INCREASE the DAT setpoint by 0.5°F (adjustable) ○ If the number of cooling requests is greater than two (adjustable), DECREASE the DAT setpoint by 0.3°F (adjustable) times the number of cooling requests less 2 but no more than 1.2ºF (adjustable). ○ If the number of cooling requests is two, then no changes are made to the setpoint. Example: Number of Cooling Requests = 4 Decrease in CD DAT setpoint = (4 - 2) * 0.3°F = 0.6°F SA Temperature Control T&R Sequence (cont.) • During warm-up mode, the CD DAT setpoint shall be set to the maximum CD DAT setpoint. • For each terminal box, a new software point (“cooling request count”) shall be added which counts the number of cooling requests produced by that terminal box. In other words, every time a cooling request is generated the “cooling request count” should increase by 1. This will allow the operator to easily determine which VAV boxes are driving the reset. Site 1 – Pre Retrofit Supply Air Temp AHU1 ‐ SAT Operation (Sept‐2010) 64 62 60 58 56 54 52 50 44 54 64 74 84 Outdoor Air Temperature SAT SP SAT 94 Site 1 – Post Programming Site 1 – Post Programming Issues ○ No variation in SA temperature setpoint observed Solution o Controls contractor elected to start conservative o Max and Min CD DAT setpoint initially set to 60°F Site 1 – Post Commissioning DAT & DAT Setpoint on ACU‐1 (August 2011) 70 SAT Cold Deck Temp 68 SAT SP 66 64 62 60 58 56 54 50 55 60 65 70 75 Outdoor Air Temperature 80 85 90 Site 2 – Pre Retrofit ○ Eight Trane IntelliPak™ units serving VAV with reheat ○ Supply air temperature set constant at 55°F Site 2 – Post Initial Programming ○ The sequence was programmed and went live. Same set points and programming as Site 1 • Issues ○ Next morning dozens of comfort complaints ○ Also Complaints about noisy boxes (too much air flow) • What happened (we think) o Supply air temperature 68 F before occupants arrive o People arrive o VAVs to100% open, SAT from 68 °F to 55 °F in 11 min Site 2 – Post Initial Programming • Initial Solution ○ Adjusted maximum CD DAT setpoint back to 55°F (adjustable) and increased by 1 °F per week while gauging complaint levels • Got conservative: ○ Generate a cooling request when the cooling loop output signal at any zone is 65% instead of 95% or above (adjustable). ○ Added a release cooling request at 45% cooling loop output ○ Slowed update rate from 3 to 5 minutes Site 2 – Post Commissioning SAT Reset AC‐1, 2, 3, 4 (Dec‐2011) AC‐1 70 AC‐2 AC‐3 AC‐4 Base Case 65 75 SAT Setpoint [°F] 68 66 64 62 60 58 56 54 52 50 35 45 55 Outdoor Air Temperature [°F] Site 2 – Post Commissioning SAT Reset AC‐5, 6, 7, 8 (Dec‐2011) AC‐5 70 AC‐6 AC‐7 AC‐8 Base Case SAT Setpoint [°F] 68 66 64 62 60 58 56 54 52 50 35 45 55 65 Outdoor Air Temperature [°F] 75 Site 1 Results Site 1 - Verified Results Verified (Post-Retrofit) Energy Savings and Cost Savings Measure Number Measure Name RCx-1 Project Payback Peak Savings (kW) Energy Savings (kWh) Energy Savings (therms) Delamp Garage T8 Fixtures From 3 Lamps To 1 Lamp Per Fixture 3.2 28,452 0 $ 3,921 $ 2,223 $ 1,112 RCx-2 Schedule Half Garage Lights Off During Daytime 0.0 1,222 0 $ 168 $ 2,774 $ 110 15.8 RCx-3 Photocell Control for Lobby Lights 0.0 1,860 0 $ 256 $ 134 $ 67 0.3 RCx-4 Repair Broken Chilled Water Valve on AHU-2 7.4 43,113 16,605 $ 18,632 $ 5,314 $ 2,657 0.1 RCx-5 Recomission Economizers (All Air Handlers) 20.3 120,613 6,761 $ 21,788 $ 5,749 $ 2,875 0.1 RCx-6 Install VFD on Heating Furnace Fans (HF-1 and HF-2) 14.4 66,903 0 $ 9,219 $ 17,117 $ 6,021 1.2 RCx-7 Implement Supply Air Reset On All Airhandlers 23.6 179,553 33,705 $ 50,503 $ 7,193 $ 3,596 0.1 RCx-8 Schedule Air Handlers and Chilled Water System 0 191,127 1,532 $ 27,508 $ 24,327 $ 12,164 0.4 RCx-9 Implement Chilled Water Setpoint Reset 0 27,010 0 $ 3,722 $ 57,663 $ 2,431 14.8 68.9 659,855 58,603 $ 135,718 $ 122,495 $ 31,032 0.7 RCx-10 Install VFD on Chilled Water Pumps (Not Recommended) RCx-11 Schedule off AH-4 during nights and weekends by installing two split system units TOTALS (Implemented Measures) Total Cost Savings Measure Cost Approved PG&E Incentive Simple Payback (yr) 0.3 Site 2 Results Site 2 - Verified Results Verified (Post-Retrofit) Annual Energy Savings and Cost Savings Measure Number Measure Name Peak Savings (kW) Energy Savings (kWh) Energy Savings (therms) Total Cost Savings Project Financials Measure Cost* Approved Incentive Simple Payback (yr) RCx-1 Recommission All Economizers (AC1-8) 17.0 118,417 11 $ 15,047 $ 12,579 $ 6,289 0.42 RCx-2 Fix Zone Temperature Setpoints, Implement SAT and DSP Resets (AC1-8) 56.0 564,029 34,833 $ 97,286 $ 14,751 $ 7,376 0.08 RCx-3 Schedule All Non-Essential VAV boxes and Air Handlers to Match Occupancy 0.0 250,074 18,998 $ 45,751 $ 3,431 $ 1,715 0.04 73.0 932,520 53,842 $ 158,084 $ 30,761 $ 15,380 0.10 TOTALS (Implemented Measures) Site 3 – Currently being commissioned • Findings ○ Multiple “rogue” VAV boxes are always generating cooling requests and driving resets, not much variation in DAT currently observed ○ Rogue VAV boxes classified into two categories - Low cost: Changes to zone temperature SP and/or maximum CFM setpoint are required so that VAV box is not always generating a request for cooling - High cost: VAV box replacement required: Software setpoint changes alone will not alleviate continued call for cooling; VAV box is undersized Conclusions • T&R control works and can be very cost effective! – performance issues are site specific • Project not complete after programming is finished – Cx very important • Run VAV box report pre implementation to check for rogue zones • T&R very sensitive, alarming, periodic trend reviews and training recommended to insure persistence • Only use when less complicated resets won’t work Modified Trim and Respond Sequence Currently testing modified T&R sequence • Reduce SAT when there are multiple cooling requests • Calculates total energy cost associated with increasing or decreasing SAT before deciding which way to go when there are no cooling requests Thanks Arik Cohen, PE kW Engineering