Data Bulletin 0600DB0401 05/2005 Cedar Rapids, IA, USA Replaces D-471 09/1987 Push-to-trip Class 0600 Retain for future use. NEMA AB 4 The National Electrical Manufacturers Association (NEMA) Standards Publication No. AB 4 states that “Good practice includes periodic circuit breaker maintenance during plant shutdown or during a regular maintenance procedure.” NEMA AB 4 sets forth a number of basic procedures “that may be used for the inspection and preventive maintenance of molded case circuit breakers used in industrial and commercial applications rated up to and including 1000 V 50/60 Hz AC or AC/DC.” One of these procedures is “For breakers that are provided with mechanical trip provisions (generally indicated by a test button) operate the tripping means according to the manufacturer’s instructions.” Square D recommends that circuit breakers be tripped annually to exercise the circuit breaker mechanism. The frequency should be increased if severe environmental conditions exist. PUSH-TO-TRIP All Square D industrial circuit breakers have an easily identified yellow or red push-to-trip button, found on the circuit breaker cover, to provides a means to mechanically trip the circuit breaker. The push-to-trip button can be conveniently depressed with a pen or pencil. The action will cause the circuit breaker to “trip”, opening the contacts. When the push-to-trip button is depressed, the operating handle on all Square D industrial switches and circuit breakers assume a distinctive tripped position. To reset the circuit breaker, move the handle to the extreme “OFF” position and then to the “ON” position. The entire operation should be repeated several times. This action exercises the latches and tripping portion of the mechanism and allows maintenance checks on the circuit breakers, control circuits, and other associated equipment. The push-to-trip function is the only practical way to check the operation of an optional alarm switch accessory. The alarm switch is activated only when the circuit beaker is tripped. The push-to-trip function exercises the actual latching-delatching components of the mechanism. These are some of the same mechanism components utilized during a tripping operation. Using the push-to-trip function during maintenance activities provides assurance that the circuit breaker mechanism is operational. In many cases, the trim does not need to be removed to use the push-to-trip function. When performing tests on electrical equipment, it is desirable to have the equipment de-energized, disconnected and isolated. I f the circuit breaker being tested is not de-energized, operating the pushto-trip function will break the circuit and interrupt current to all downstream equipment. Steps should be taken to minimize the electrical interruption and to ensure proper start of equipment when the circuit breaker is turned ”ON”. 1 Push-to-trip Data Bulletin 0600DB0401 05/2005 Typical locations of the push-to-trip button is shown in the accompanying illustrations. For more information on inspection and maintenance of circuit breakers, see Square D Bulletin SD363, Field Testing Industrial Molded Case Circuit Breakers. 05200017 06603040 Typical Push-to-trip Locations 05253173 Figure 1: ON OFF Push-to-trip Button Schneider Electric USA 3700 Sixth St. SW Cedar Rapids, IA 52404 USA 1-888-SquareD (1-888-778-2733) www.us.SquareD.com Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2005 Schneider Electric All Rights Reserved