Indoor Analog Photocell Sensor for the Lighting Integrator Panel Installation and Operation SPECIFICATIONS: Footcandle range HPSA-I . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 - 500 fc HPSA-IX . . . . . . . Custom range, see product label Calibration . . . . . .None, controlled by system software Input voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12VDC Sensor output . . . . . . . . . . . . . . . . . . . . . . . . .0 - 4.4VDC Peak current . . . . . . . . . . . . . . . . . . . .4.5 mA Maximum Slew rate . . . . .1 minute full scale response time filter Operating temperature -40˚F to 140˚F (-40˚C to 60˚C) Wire color code Red . . . . . . . . . . . . . . . . . . . . . . . . . . .+12 VDC input Black . . . . . . . . . . . . . . .0 - 4.4VDC signal to panel White . . . . . . . . . . . . . . . . . . . . . . . . . . DC common Housing . .Indoor, UV stabilized plastic with dome lens Mounting . . . . . . . . . . . . . . . . . . . . . . . 0.5" x 0.64" stem Exposed unit . . . . . . . . . . . 2.60"H x 1.23" diameter DESCRIPTION The HPSA-I is an indoor daylight sensor specifically designed to be used in conjunction with a Lighting Integrator Complete Control level panel and WinControl user software only. Consult the factory for information on photocell sensors to be used with other Watt Stopper/Legrand lighting control panels. Wiring Connect the sensor to the lighting control panel as shown making sure to maintain the color code of the conductors between the sensor pigtails and the color coded connector within the panel. The sensor can be connected to any of the available terminals on the panel’s group switching card (see panel installation instructions for the location of these terminals). However, if factory documentation was supplied with the system, the sensor must be connected to the specified terminal in order for the programming to work correctly. For an overview of the entire system, refer to the Lighting Integrator Installation and Operation Manual. INSTALLATION Install the sensor on the ceiling half way between the window and the first row of light fixtures. Drill a ½" hole through the ceiling. Peel off the film on the bottom of the sensor to expose the adhesive. Press the sensor firmly into place. If using a junction box for the installation, the box must have a ½" hole to accept the sensor's stem. Ceiling Light Fixture HPSA-I Sensor Located half way between window and first row of lights #20 AWG up to 250 feet Class 2 wiring Group Switching Card inside LI Panel Window Wiring Terminals In rooms with indirect luminaries providing uplight, it may be necessary to mask the sensor lens for proper operation. Use the included masking film to cover approximately one third of the lens facing the luminaire. R B Y W A R B Y W B R B Y W C R B Y W D E R B Y W R B Y W R B Y W R B Y W F G H If you have any questions, call our Service Team at: 800.879.8585. Please Recycle Santa Clara, CA 95050 www.wattstopper.com Call 800.879.8585 for Technical Support 08192r1 3/2007 Installation Instructions HPSA-I/HPSA-IX