29 CHAPTER 3 STATIC SYNCHRONOUS SERIES COMPENSATOR 3.1 INTRODUCTION Series compensation is a means of controlling the power transmitted across transmission lines by altering or changing the characteristic impedance of the line. The power flow problem may be related to the length of the transmission line. The transmission line may be compensated by a fixed capacitor or inductor to meet the requirements of the transmission system. When the structure of the transmission network is considered, power flow imbalance problems arise. Inadvertent interchange occurs when the power system tie line becomes corrupted. This is because of unexpected change in load on a distribution feeder due to which the demand for power on that feeder increases or decreases. The generators are to be turned on or off to compensate for this change in load. If the generators are not activated very quickly, voltage sags or surges can occur. In such cases, controlled series compensation helps effectively. 3.2 SERIES COMPENSATOR Series compensation, if properly controlled, provides voltage stability and transient stability improvements significantly for post-fault systems. It is also very effective in damping out power oscillations and mitigation of sub-synchronous resonance (Hingorani 2000). 30 3.2.1 Voltage Stability Series capacitive compensation reduces the series reactive impedance to minimize the receiving end voltage variation and the possibility of voltage collapse. Figure 3.1 (a) shows a simple radial system with feeder line reactance X, series compensating reactance Xc and load impedance Z. The corresponding normalized terminal voltage Vr versus power P plots, with unity power factor load and 0, 50, and 75% series capacitive compensation, are shown in Figure 3.1(b). The “nose point” at each plot for a specific compensation level represents the corresponding voltage instability. So by cancelling a portion of the line reactance, a “stiff” voltage source for the load is given by the compensator. (a) Figure 3.1 3.2.2 (b) Transmittable power and voltage stability limit of a radial transmission line as a function of series capacitive compensation Transient Stability Enhancement The transient stability limit is increased with series compensation. The equal area criterion is used to investigate the capability of the ideal series compensator to improve the transient stability. 31 Figure 3.2 Two machine system with series capacitive compensation Figure 3.2 shows the simple system with the series compensated line. Assumptions that are made here are as follows: The pre-fault and post-fault systems remain the same for the series compensated system. The system, with and without series capacitive compensation, transmits the same power Pm. Both the uncompensated and the series compensated systems are subjected to the same fault for the same period of time. Figures 3.3 (a) and (b) show the equal area criterion for a simple two machine system without and with series compensator for a three phase to ground fault in the transmission line. From the figures, the dynamic behaviour of these systems are discussed. Prior to the fault, both of them transmit power Pm at angles s1 1 and respectively. During the fault, the transmitted electric power becomes zero, while the mechanical input power to the generators remains constant (Pm). Hence, the sending end generator accelerates from the steady-state angles 1 and s1 to 2 and s2 respectively, when the fault clears. In the figures, the accelerating energies are represented by areas A1 and As1. After fault clearing, the transmitted electric power exceeds the mechanical input 32 power and therefore the sending end machine decelerates. However, the accumulated kinetic energy further increases until a balance between the accelerating and decelerating energies, represented by the areas A1, As1 and A2, As2, respectively, are reached at the maximum angular swings, 3 and s3 respectively. The areas between the P versus curve and the constant Pm line over the intervals defined by angles and 3 and crit, s1 and scrit, respectively, determine the margin of transient stability represented by areas Amargin and Asmargin for the system without and with compensation. (a) Figure 3.3 (b) Equal area criterion to illustrate the transient stability margin for a simple two-machine system (a) without compensation and (b) with a series capacitor Comparing figures 3.3(a) and (b), it is clear that there is an increase in the transient stability margin with the series capacitive compensation by partial cancellation of the series impedance of the transmission line. The increase of transient stability margin is proportional to the degree of series compensation. 33 3.2.3 Power Oscillation Damping Power oscillations are damped out effectively with controlled series compensation. The degree of compensation is varied to counteract the accelerating and decelerating swings of the disturbed machine(s) for damping out power oscillations. When the rotationally oscillating generator accelerates and angle increases (d /dt > 0), the electric power transmitted must be increased to compensate for the excess mechanical input power and conversely, when the generator decelerates and angle decreases (d /dt < 0), the electric power must be decreased to balance the insufficient mechanical input power. Figure 3.4 Waveforms illustrating power oscillation damping by controllable series compensation (a) generator angle (b) transmitted power and (c) degree of series compensation Figure 3.4 shows the waveforms describing the power oscillation damping by controllable series compensation. Waveforms in figure 3.4(a) show the undamped and damped oscillations of angle around the steady 34 state value 0. The corresponding undamped and damped oscillations of the electric power P around the steady state value P0, following an assumed fault (sudden drop in P) that initiated the oscillation are shown by the waveforms in figure 3.4(b). Waveform 3.4 (c) shows the applied variation of the degree of series compensation, k applied. ‘k’ is maximum when d /dt > 0, and it is zero when d /dt < 0. 3.2.4 Immunity to Sub-synchronous Resonance The sub-synchronous resonance is known as an electric power system condition where the electric network exchanges energy with a turbine generator at one or more of the natural frequencies of the combined system below the synchronous frequency of the system. With controlled series compensation, the resonance zone is prohibited for operation and the control system is designed in such a way that the compensator does not enter that area. Also, an SSSC is an ac voltage source operating only at the fundamental output frequency and its output impedance at any other frequency should be zero. The SSSC is unable to form a series resonant circuit with the inductive line impedance to initiate sub-synchronous system oscillations. 3.2.5 Types of Series Compensators Series compensation is accomplished either using a variable impedance type series compensators or a switching converter type series compensator. 3.2.5.1 Variable impedance type series compensators The thyristor controlled series compensators are the variable type of compensators. The type of thyristor used for the variable type series compensators has an impact on their performance. The types of thyristors 35 used in FACTS devices are Silicon Controller Rectifier (SCR), Gate Turn-Off Thyristor (GTO), MOS Turn-Off Thyristor (MTO), Integrated Gate Commutated Thyristor (GCT or IGCT), MOS Controlled Thyristor (MCT) and Emitter Turn-Off Thyristor (ETO). Each of these types of thyristors has several important device parameters that are needed for the design of FACT devices. These parameters are di/dt capability, dv/dt capability, turn-on time and turn-off time, Safe Operating Area (SOA), forward drop voltage, switching speed, switching losses, and gate drive power. The variable impedance type series compensators are GTO thyristor controlled series compensator (GCSC), Thyristor Switched Series Capacitor (TSSC) and Thyristor Controlled Series Capacitor (TCSC). GTO Thyristor Controlled Series Capacitor (GCSC) A GCSC consists of a fixed capacitor in parallel with a GTO Thyristor as in figure 3.5which has the ability to be turned on or off. The GCSC controls the voltage across the capacitor (Vc) for a given line current. In other words, when the GTO is closed the voltage across the capacitor is zero and when the GTO is open the voltage across the capacitor is at its maximum value. The magnitude of the capacitor voltage can be varied continuously by the method of delayed angle control (max = 0, zero = /2). For practical applications, the GCSC compensates either the voltage or reactance. Figure 3.5 GTO Controlled Series Capacitor 36 Thyristor Switched Series Capacitor (TSSC) Thyristor Switched Series Capacitor (TSSC) is another type of variable impedance type series compensators shown in Figure 3.6. The TSSC consists of several capacitors shunted by a reverse connected thyristor bypass switch. Figure 3.6 Thyristor Switched Series Capacitor In TSSC, the amount of series compensation is controlled in a steplike manner by increasing or decreasing the number of series capacitors inserted into the line. The thyristor turns off when the line current crosses the zero point. As a result, capacitors can only be inserted or deleted from the string at the zero crossing. Due to this, a dc offset voltage arises which is equal to the amplitude of the ac capacitor voltage. In order to keep the initial surge current at a minimum, the thyristor is turned on when the capacitor voltage is zero. The TSSC controls the degree of compensating voltage by either inserting or bypassing series capacitors. There are several limitations to the TSSC. A high degree of TSSC compensation can cause sub-synchronous resonance in the transmission line just like a traditional series capacitor. The TSSC is most commonly used for power flow control and for damping power 37 flow oscillations where the response time required is moderate. There are two modes of operation for the TSSC-voltage compensating mode and impedance compensating mode. Thyristor Controlled Series Capacitor (TCSC) Figure 3.7 shows the basic Thyristor Controlled Series Capacitor (TCSC) scheme. The TCSC is composed of a series-compensating capacitor in parallel with a thyristor-controlled reactor. The TCSC provides a continuously variable capacitive or inductive reactance by means of thyristor firing angle control. The parallel LC circuit determines the steady-state impedance of the TCSC. Figure 3.7 Thyristor Controlled Series Capacitor The impedance of the controllable reactor is varied from its maximum (infinity) to its minimum ( L). The TCSC has two operating ranges; one is when Clim The other range of operation is 0 /2, where the TCSC is in capacitive mode. Llim, where the TCSC is in inductive mode. TCSC can be operated in impedance compensation mode or voltage compensation mode. 38 3.2.5.2 Switching converter type compensator With the high power forced-commutated valves such as the GTO and ETO, the converter-based FACTS controllers have become true. The advantages of converter-based FACTS controllers are continuous and precise power control, cost reduction of the associated relative components and a reduction in size and weight of the overall system. An SSSC is an example of a FACTS device that has its primary function to change the characteristic impedance of the transmission line and thus change the power flow. The impedance of the transmission line is changed by injecting a voltage which leads or lags the transmission line current by 90º. Figure 3.8 Schematic diagram of SSSC If the SSSC is equipped with an energy storage system, the SSSC gets an added advantage of real and reactive power compensation in the 39 power system. By controlling the angular position of the injected voltage with respect to the line current, the real power is provided by the SSSC with energy storage element. Figure 3.8 shows a schematic diagram of SSSC with energy storage system for real and reactive power exchange. The applications for an SSSC are the same as for traditional controllable series capacitors. The SSSC is used for power flow control, voltage stability and phase angle stability. The benefit of the SSSC over the conventional controllable series capacitor is that the SSSC induces both capacitive and inductive series compensating voltages on a line. Hence, the SSSC has a wider range of operation compared with the traditional series capacitors. The primary objective of this thesis is to examine the possible uses of the SSSC with energy storage system with state-of-the-art power semiconductor devices in order to provide a more cost effective solution. 3.2.5.3 Comparison of Series Compensator Types Figure 3.9 shows a comparison of VI and loss characteristics of variable type series compensators and the converter based series compensator. Figure 3.9 Comparison of Variable Type Series Compensators to Converter Type Series Compensator 40 From the figure the following conclusions can be made. The SSSC is capable of internally generating a controllable compensating voltage over any capacitive or inductive range independent of the magnitude of the line current. The GCSC and the TSSC generate a compensating voltage that is proportional to the line current. The TCSC maintains the maximum compensating voltage with decreasing line current but the control range of the compensating voltage is determined by the current boosting capability of the thyristor controlled reactor. The SSSC has the ability to be interfaced with an external dc power supply. The external dc power supply is used to provide compensation for the line resistance. This is accomplished by the injection of real power as well as for the line reactance by the injection of reactive power. The variable impedance type series compensators cannot inject real power into the transmission line. They can only provide reactive power compensation. The SSSC with energy storage can increase the effectiveness of the power oscillation damping by modulating the amount of series compensation in order to increase or decrease the transmitted power. The SSSC increases or decreases the amount of transmitted power by injecting positive and negative real impedances into the transmission line. The variable-type series compensators can damp the power oscillations by modulating the reactive compensation. 3.3 STATIC SYNCHRONOUS SERIES COMPENSATOR (SSSC) The Voltage Sourced Converter (VSC) based series compensators - Static Synchronous Series Compensator (SSSC) was proposed by Gyugyi in 1989. The single line diagram of a two machine system with SSSC is shown in Figure 3.10. The SSSC injects a compensating voltage in series with the 41 line irrespective of the line current. From the phasor diagram, it can be stated that at a given line current, the voltage injected by the SSSC forces the opposite polarity voltage across the series line reactance. It works by increasing the voltage across the transmission line and thus increases the corresponding line current and transmitted power. Figure 3.10 Simplified diagram of series compensation with the phasor diagram. The compensating reactance is defined to be negative when the SSSC is operated in an inductive mode and positive when operated in capacitive mode. The voltage source converter can be controlled in such a way that the output voltage can either lead or lag the line current by 90o. During normal capacitive compensation, the output voltage lags the line current by 90o. The SSSC can increase or decrease the power flow to the same degree in either direction simply by changing the polarity of the injected ac voltage. The reversed (180o) phase shifted voltage adds directly to the reactive voltage drop of the line. The reactive line impedance appears as if it were increased. If the amplitude of the reversed polarity voltage is large enough, the power flow will be reversed. The transmitted power verses transmitted phase angle relationship is shown in Equation (3.1) and the transmitted power verses transmitted angle as a function of the degree of series compensation is shown in Figure 3.11. P= sin + V cos (3.1) 42 Figure 3.11 Transmitted power verses transmitted angle as a function of series compensation 3.4 CONVERTERS 3.4.1 Basic Concept The conventional thyristor device has only the turn on control and its turn off depends on the natural current zero. Devices such as the Gate Turn Off Thyristor (GTO), Integrated Gate Bipolar Transistor (IGBT), MOS Turn Off Thyristor (MTO) and Integrated Gate Commutated Thyristor (IGCT) and similar devices have turn on and turn off capability. These devices are more expensive and have higher losses than the thyristors without turn off capability; however, turn off devices enable converter concepts that can have significant overall system cost and performance advantages. These advantages in principle result from the converter, which are self commutating as against the line commutating converters. The line commutating converter consumes reactive power and suffers from occasional commutation failures in the inverter mode of operation. Hence, the converters applicable for FACTS controllers are of self commutating type (Hingorani and Gyugyi, 2000). There are two basic categories of self commutating converters: 43 Current sourced converters in which direct current always has one polarity and the power reversal takes place through reversal of dc voltage polarity. Voltage sourced converters in which the dc voltage always has one polarity and the power reversal takes place through reversal of dc current polarity. For reasons of economics and performance, voltage sourced converters are often preferred over current sourced converters for FACTS applications. 3.4.2 Voltage Source Inverters for SSSC SSSC is a Voltage Sourced Converter based series compensator. The compensation works by increasing the voltage across the impedance of the given physical line, which in turn increases the corresponding line current and the transmitted power. For normal capacitive compensation, the output voltage lags the line current by 90 o. With Voltage Source Inverters the output voltage can be reversed by simple control action to make it lead or lag the line current by 90o. In the present work, 48-pulse VSI is designed and ideal switches and zig-zag phase shifting transformers are used to build a GTO-type VSI. Figure 3.12 shows the Matlab/Simulink model of 48 pulse VSI. This type of converter is used in high-power Flexible AC Transmission Systems which are used to control power flow on transmission grids. The inverter described is harmonic neutralized. It consists of four 3phase, 3-level inverters and four phase-shifting transformers. The DC bus is connected to the four 3-phase inverters. The four voltages generated by the inverters are applied to secondary windings of four zig-zag phase-shifting transformers connected in Wye (Y) or Delta (D). The four transformer 44 primary windings are connected in series and the converter pulse patterns are phase shifted so that the four voltage fundamental components sum in phase on the primary side. emux + v - Voltage Measurement Goto 1 A1 A+ 2 B1 g a3 A b3 B C+ C1 A- + N B+ 3 Pulses 1 Van_Tr1Yse C c3 - BC- Three-Level Bridge n Zigzag Phase-Shifting Transformer + v - + 7 Vab_Tr1Dse Voltage Measurement1 Goto1 g + A+ B+ a3 A b3 B N C+ B C A ABC- A+ C c3 Zigzag Phase-Shifting Transformer1 c b a Three-Phase Breaker + v - Van_Tr2Yse Voltage Measurement2 Goto2 A- N + A a3 N B b3 C c3 - BC- 8 g B+ C+ - Three-Level Bridge1 Three-Level Bridge2 n Zigzag Phase-Shifting Transformer2 + v - 9 Vab_Tr2Dse Voltage Measurement3 Goto3 g + A+ B+ a3 A b3 B c3 C N C+ 4 A2 5 B2 AA A- BB B- 6 CC C- C2 Imes_SE Zigzag Phase-Shifting Transformer3 - Three-Level Bridge3 Figure 3.12 Matlab/Simulink model of 48 pulse Voltage Source Inverter Each 3-level inverter generates three square-wave voltages which can be +Vdc, 0, -Vdc. The duration of the +Vdc or -Vdc level (Sigma) can be adjusted between 0 and 180 degrees from the sigma input of the firing pulse generator block. Each inverter uses a 3-level bridge block where specified power electronic devices are ideal switches. In this model, each leg of the inverter uses 3 ideal switches to obtain the 3 voltage levels (+Vdc, 0, - Vdc). The phase shifts produced by the secondary delta connections (-30 degrees) and by the primary zig-zag connections (+7.5 degrees for 45 transformers 1Y and 1D, and -7.5 degrees for transformers 2Y and 2D) allow to neutralize harmonics up to 45th harmonic, as explained below: The 30-degree phase-shift between the Y and D secondaries cancels harmonics 5+12n (5, 17, 29, 41, ...) and 7+12n (7, 19, 31, 43, ...). In addition, the 15-degree phase shift between the two groups of transformers (1Y and 1D leading by 7.5 degrees, 2Y and 2D lagging by +7.5 degrees) allows cancellation of harmonics 11+24n (11, 35, ...) and 13+24n (13, 37, ...). Considering the fact that all 3n the harmonics are not transmitted by the Y and D secondaries, the first harmonics which are not cancelled by the transformers are 23rd, 25th, 47th and 49th. By choosing an appropriate conduction angle for the 3-level inverters (sigma = 180 - 7.5 = 172.5 degrees), the 23rd and 25th can be minimized. The first significant harmonics are therefore the 47th and 49th. This type of inverter generates an almost sinusoidal waveform consisting of 48-steps. Also with 48 - pulse VSI, AC filters are not required. The instantaneous values of the phase-to-phase voltage and the phase to neutral voltage of the 48 pulse inverter are expressed as in equations 3.2 and 3.3. V ( t) = 8 V ( t) = V = V = V V sin( m t + 18.75 m + 11.25 t) sin( m t + 18.75 11.25 t) (3.2) (3.3) where, V V cos m ( 1 + cos m) m=48r±i, i=0,1,2,… + for positive sequence harmonics and - for negative sequence harmonics. (3.4) (3.5) 46 The voltages Vbc48 and Vca48 exhibit a similar pattern except the phase shifted by 120o and 240o respectively. Similarly, the phase voltages Vbn48 and Vcn48 are also phase shifted by 120o and 240o respectively. For the input voltage of 20kV at the dc side, the waveform at the ac side of the 48 pulse VSI is shown in Figure 3.13. The THD of the voltage is 1.31% and it is shown in Figure 3.14. 0.1 voltage (pu) 0.05 0 -0.05 -0.1 0 0.01 0.02 0.03 0.04 0.05 time (sec) 0.06 0.07 0.08 0.09 Figure 3.13 Voltage at the ac side of the 48 pulse VSI Figure 3.14 THD of the voltage at the ac side of the 48 pulse VSI 0.1 47 3.5 INTERNAL CONTROL SCHEME FOR SSSC There are two ways in which the voltage source converter can be internally controlled (Hingorani 2000). They are: Indirect control scheme and Direct control scheme 3.5.1 Indirect Control Scheme In order to maintain a quadrature relationship between the converter voltage and the line current, to provide series compensation, and to handle the sub-synchronous resonance, the converter can be internally controlled. Figure 3.15 shows the block diagram of an indirect control scheme. Figure 3.15 Block diagram of an indirect control scheme The inputs to the internal control are the line current, the injected compensating voltage, and the reference voltage. The control is synchronized to the line current through the PLL which, after a + /2 or – /2 phase shift, provides the basic synchronising signal . The output polarity detector determines the positive capacitive or negative inductive reference voltage 48 through which the + /2 or – /2 phase shift is determined. A simple closed loop controller controls the compensating voltage. The absolute value of the reference voltage is compared with the measured magnitude of the injected voltage and the amplified difference is added as a correction angle to the synchronizing signal . The gate signals will be changed accordingly and the compensating voltage will be phase shifted with respect to the line current. 3.5.2 Direct Control Scheme To maintain synchronism with the fundamental frequency, the converter must be directly controlled. Control scheme for directly controlled converter is shown in figure 3.16. The direct control scheme is for providing both real and reactive power compensation if the converter is equipped with a suitable dc power supply. The control is operated from three reference signals - the desired magnitude of the series reactive compensating voltage, the series and real compensating and the operating voltage of the dc capacitor. The references are compared to the corresponding components of the measured voltages. From these error signals, the magnitude of the injected voltage and the phase angles are computed and the gate signals for the converter are generated accordingly. Figure 3.16 Block diagram of direct control scheme 49 3.5.3 Control Scheme Proposed The main function of the SSSC is to dynamically control the power flow over the transmission line. The control scheme proposed by Anil. Pradhan and Lehn (2006) is based on the line impedance control mode in which the SSSC compensating voltage is derived by multiplying the current amplitude with the desired compensating reactance Xqref. Since it is difficult to predict Xqref under varying network contingencies, in the proposed scheme, this controller is modified with power references instead of reactance reference to operate the Static Synchronous Series Compensator in the automatic power flow control mode (Geethalakshmi and Dhananjayan 2007). The phase locked loop determines the frequency and t of the bus1 voltage. Bus2 voltage is converted to d-q components as Vd and Vq. Similarly, current flowing from bus1 to bus2 is also converted to d-q components as Id and Iq using d-q transformations as below. The abc to dq0 transformation computes the direct axis, quadrature axis and zero sequence quantities in a two axis rotating reference frame for a three phase sinusoidal signal. For the three phase voltage, the following equations are used to compute the two axis rotating reference voltages. V = ( V sin ( t ) + V sin( 3) + V sin( t + 2 3)) (3.6) V = ( V cos( t ) + V cos( 3) + V cos( t + 2 3)) (3.7) V = (V + V + V ) (3.8) For obtaining the dq currents from three phase currents, the voltage is replaced with current. 50 The reference inputs to the controller are Pref and Qref, which are to be maintained in the transmission line. The instantaneous power is obtained in terms of d-q quantities of voltages and currents as below: P= V I + V I (3.9) Q= V I + V I (3.10) From equations 3.9 and 3.10, the required current references are calculated as follows: I = P V + Q V / V + V (3.11) I = P V + Q V / V + V (3.12) Series Controller Scope Scope1 PQ Idqref f requency Fre q PQ PQref 1 1/z Va b c( p u ) PQref wt wt Vdq Sin _C o s 2 1/z Vdq Vdq Vabc Reference Computation Vabc_B2 PLL 3 Idqref Idqref Vb1 1/z Idq Iabc Iabc Idq -- Terminator Subsystem Vdq Sigma Sigma 0 D _Alpha Pulses 4 1/z Vdc angle Alpha 1 Pulses VdcPM_SE wt Mag and angle Firi ng Pul ses Generator Scope2 Figure 3.17 Matlab / Simulink model for the generation of firing pulses for the 48 pulse VSI Figure 3.17 shows the Matlab / Simulink model for the generation of firing pulses for the 48 pulse VSI. The desired current references namely Idref and Iqref are compared with actual current components Id and Iq respectively and the error signals are processed in the PI controller. The PI 51 controller parameters are designed by Ziegler Nichols’s PI tuning method. The PI controller parameters set for this process are 0.045 and 16.5 for the proportional and integral gains respectively. Based on these controller parameters set, the required small displacement angle has been derived to control the angle of the injected voltage with respect to the line current. A Phase Locked Loop (PLL) is used to determine the instantaneous angle of the three-phase line voltage V1abc. The current components Id and Iq of the three phase line currents are used to determine the angle r relative to the voltage V1abc. Depending upon the instantaneous reactive power with respect to the desired value either /2 is added (inductive) or subtracted (capacitive) with Thus, the required phase angle is derived as in the equation 3.13. ref 3.6 = r ±( /2) (3.13) SIMULATION RESULTS The details of the test system are given in appendix-1. It is a three area four bus system. Two parallel lines are connected between the two areas with 200 and 280km in length. The SSSC is connected in the second line of 280km in length. The line is divided into two parts of 100km and 180km. SSSC is connected between bus 1 and bus 2 in the 100 km length line. The simulation carried out is as follows: Initially, power flow control of the line is tested. Hence, the real power reference is varied and the results are discussed. Qref is kept constant. SSSC is connected at 0.01sec. Before the insertion of SSSC, the real power flow through the line is 8.85 pu. In case (a) the Pref is set to 8.5 pu and at 0.25 sec, Pref is increased to 10 pu. Figure 3.18 shows the corresponding waveforms for power flow through transmission line 2. It is clear from the figure that the commanded power references are achieved. In case (b) the Pref is increased to a higher value of 52 13 pu. But the final power flow achieved is 12.8 pu which is shown in Figure 3.19. Line power flow (pu) 12 11 10 9 8 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.18 Real power flow through line 2 for case (a) Line power flow (pu) 13 12 11 10 9 8 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.19 Real power flow through line 2 for case (b) The next command is given to Qref. Pref is fixed to a value of 11pu. Before the insertion of SSSC, the reactive power flow is -0.62 pu. Qref is initially commanded to -0.5 pu and at 0.25 sec it is changed to -0.8 pu. Figure 3.20 shows the corresponding waveform. Both the set values are obtained finally. 53 Reactive power flow (pu) 0 -0.2 -0.4 -0.6 -0.8 -1 -1.2 -1.4 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.20 Reactive power flow through line 2 Figure 3.21 shows the quadrature relationship between the line current and the injected voltage. To have a clear waveform, the magnitude of the line current is reduced to 0.25 of the original value. 0.25 of line current (pu) Injected voltage (pu) 3 i 2 1 v 0 -1 -2 -3 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.21 Wave forms for 0.25 of line current and injected voltage For analysing transient stability, a three phase to ground fault is simulated at 0.2 sec in line 2. The fault is cleared at 0.3 sec. The reference real and reactive power values set are 11 pu and -0.67 pu respectively and the results are analysed. Figure 3.22 and 3.23 show the real and reactive power flow through transmission line 2. 54 25 Line power flow (pu) 20 15 10 5 0 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.22 Real power flow through line 2 Reactive power flow (pu) 25 20 15 10 5 0 -5 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.23 Reactive power flow through line 2 150 Line Current (pu) 100 50 0 -50 -100 -150 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 Time (s) Figure 3.24 Current flowing through line 2 0.4 0.45 0.5 55 Figure 3.24 represents the current flow through line 2 and the value is 10 pu during normal operating condition and the peak value goes to 147 pu during fault. Figure 3.25 shows the injected voltage from SSSC and it is 0.06 pu during steady state condition and the oscillations are more during fault period. 0.8 0.6 Injected voltage (pu) 0.4 0.2 0 -0.2 -0.4 -0.6 -0.8 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 0.45 0.5 Figure 3.25 Injected voltage from SSSC Voltage across the capacitor (Volts) 4 6 x 10 5 4 3 2 1 0 -1 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 Figure 3.26 Voltage across the dc capacitor 56 Figure 3.26 shows the waveform of voltage across the capacitor. During faulted period, the value overshoots to 53kV and settles to 21.5 kV in the post fault period. Figure 3.27 and 3.28 show the waveforms of the electrical power output from generator 1 for the cases without and with SSSC respectively. Figures 3.29 and 3.30 show the waveforms of the load angle for the machine and from the figures it is clear that the oscillations are reduced for the system with SSSC. The overshoot and settling time are also less for the system with SSSC. 3 Output active power (pu) 2.5 2 1.5 1 0.5 0 -0.5 -1 0 0.05 0.1 0.15 0.2 0.25 Time (sec) 0.3 0.35 0.4 0.45 0.5 Figure 3.27 Electrical power output from generator 1 for the case without SSSC 2.5 Output active power 2 1.5 1 0.5 0 -0.5 -1 0 0.05 0.1 0.15 0.2 0.25 Time (sec) 0.3 0.35 0.4 0.45 0.5 Figure 3.28 Electrical power output from generator 1 for the case with SSSC 57 60 Load angle (degrees) 50 40 30 20 10 0 -10 -20 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.29 Load angle of machine 1 for the case without SSSC 50 Load angle (degrees) 40 30 20 10 0 -10 -20 0 0.05 0.1 0.15 0.2 0.25 0.3 Time (sec) 0.35 0.4 0.45 0.5 Figure 3.30 Load angle of machine 1 for the case with SSSC Table 3.1 Comparative results for the system without and with SSSC Without SSSC With SSSC Electrical power Peak value (pu) output from 2.54 2.14 52.5 51 generator 1 Load angle Peak value (degrees) 58 3.7 CONCLUSION The objectives of series compensators have been discussed. Variable impedance type series compensators and a switching converter type series compensator have been discussed. A comparative study has been made. The modelling of SSSC has been discussed. The harmonic neutralised 48 pulse voltage source inverter has been realised. The output waveform and the THD of the 48 pulse voltage source inverter have been analysed. The various control schemes used for the control of SSSC have been discussed in detail and the proposed control scheme with PI controller is given. Simulation results have been carried out for real and reactive power commands and three phase fault in line 2 of the proposed system. From the results, the comparison is tabulated for the system without and with SSSC and the results show a good improvement in the transient stability of the system with SSSC.