Electrical Power and Energy Systems 32 (2010) 416–420 Contents lists available at ScienceDirect Electrical Power and Energy Systems journal homepage: www.elsevier.com/locate/ijepes A novel error compensation algorithm for three-current transformer connection Qing-quan Jia a,*, Chun-xia Dou a, Chun Wang a, Ning Wang a, Jie Tian a, Zhi-qian Bo b a b Institute of Electrical Engineering, Yanshan University, Qinhuangdao 066004, China AREVA Protect/Control Ltd., Stafford ST17 4LX, UK a r t i c l e i n f o Article history: Received 30 October 2007 Received in revised form 30 July 2009 Accepted 25 September 2009 Keywords: Current transformer Error compensation Saturation EMTP Current protection a b s t r a c t Under fault condition, primary current of a current transformer (CT) has high magnitude and may include decaying dc offset. This can result in saturation of magnetizing core of the CT and the secondary current is thus distorted. The distorted current is likely to cause malfunction of protection relays or control devices. Therefore error compensation methods are studied. Most attentions are paid to a single CT. However, CTs are usually connected together for different protections and control devices. For example, three CTs are linked for three-phase current protection and zero-sequence current protection of transmission lines. This paper proposes a novel error compensation algorithm for 3-CT connection. Due to the existence of neutral circuit, the three CTs are affected each other and error compensation methods for a single CT cannot be applied. The error compensation algorithm is derived based on the physical configuration of the 3-CT connection. It is evaluated by EMTP simulation data and case studies are included. Protection relays and control devices can achieve better performance using the compensated current measurements. Ó 2009 Elsevier Ltd. All rights reserved. 1. Introduction Although novel protection and fault location schemes for power systems were investigated widely [1,2], CT saturation and the resulting distortion of the secondary current waveform have been of concern to protection engineers. One approach of reducing the impact of CT saturation is to use waveform compensation or restructuring algorithms that attempt to reconstruct the secondary current waveform. A compensation algorithm [3] using LeastSquare (LS) curve fitting method is introduced to convert a sampled current waveform distorted by CT saturation to a compensated current waveform. Another algorithm [4] for compensating the distortion in the secondary current caused by saturation and remanence in a CT is described. A second-difference function applied to the current signal was used to detect the start of first saturation. A busbar current differential protection relay suitable for use with measurement type current transformers is described [5,6]. The relay operates in conjunction with a saturation algorithm, which detects the start and end of each saturation period using a technique based on the third-difference function applied to the current signal. A blocking signal is activated after the onset of saturation and is maintained active until the saturation period plus an additional delay of one cycle has expired. Another scheme for error compensation of current transformers is presented [7]. * Corresponding author. Tel.: +86 03358047169. E-mail address: jiaqingquan@sina.com (Q.-q. Jia). 0142-0615/$ - see front matter Ó 2009 Elsevier Ltd. All rights reserved. doi:10.1016/j.ijepes.2009.09.024 The method is to apply Hall Current Transducers (HCTs) based on magnetic force balance to detect and compensate the error current so as to eliminate the error of CT caused by its exciting current. This compensation scheme is oriented to improve measuring precise and is applied for metering CT. Papers [8,9] describe an algorithm for detecting CT saturation using the third-difference function. Kang presents a technique [10] of estimating the secondary current corresponding to the CT ratio under CT saturation. Marti described a current transformer model with fast solution algorithms [11]. But this fast and non-iterative solution calculates saturated secondary current from known primary current referred to the secondary side. The above mentioned contributions for CT error compensation are concentrated on single CT. However, CTs are usually connected together for different protections and control function. 3-CT connection is very common in power systems for protection purpose. Due to the existence of neutral circuit, the three CTs are affected each other and error compensation methods for a single CT cannot be applied. This paper presents an error compensation algorithm for 3-CT connection considering saturation. CT model in [11] is referred to, but the proposed algorithm estimates the primary current from the measuring secondary current. The process of secondary current compensation is shown in Fig. 1. The remainder of this paper is organized as follows. Section 2 describes the derivation of the error compensated algorithm in details. Evaluation results including EMTP simulation are presented in Section 3. Conclusion is drawn in Section 4. 417 Q.-q. Jia et al. / Electrical Power and Energy Systems 32 (2010) 416–420 2.3. Core loss branches For CT-1 shown in Fig. 3, the voltage cross the core loss resistance is v m1 ¼ RFe1 iFe1 ð1Þ and v m1 ¼ d k1 dt ð2Þ where k1 represents the magnetic linkage. Putting (1) and (2) together in new sample and old sample form: 1 1 ðk1:new k1:old Þ ¼ RFe1 ðiFe1:new þ iFe1:old Þ 2 Dt Fig. 1. The process of secondary current compensation. 2. Derivation of error compensation algorithm or iFe1:new ¼ C Fe1 k1:new þ hFe1:old ð3Þ where 2.1. 3-CT connection scheme hFe1:old ¼ C Fe1 k1:old iFe1:old ; C Fe1 ¼ 2 RFe1 Dt 3-CT connection scheme for current protection is shown in Fig. 2, where Relay-1, Relay-2 and Relay-3 are phase current relays; Relay-0 is zero-sequence current relay; is1 ; is2 and is3 are the secondary currents; is0 is the zero-sequence current through the coil of the neutral relay; Z 1 ¼ R1 þ jxL1 ; Z 2 ¼ R2 þ jxL2 and Z 3 ¼ R3 þ jxL3 are the total phase impedances of CT and phase current relay in each phase and Z 0 ¼ R0 þ jxL0 is the total impedance of zero-sequence current relay and neutral leads. iFe2:new ¼ C Fe2 k2:new þ hFe2:old ð4Þ iFe3:new ¼ C Fe3 k3:new þ hFe3:old ð5Þ hFe2:old ¼ C Fe2 k2:old iFe2:old ; C Fe2 ¼ 2.2. The equivalent circuit of CT hFe3:old ¼ C Fe3 k3:old iFe3:old ; C Fe3 The equivalent circuit of CT-1 can be expressed in Fig. 3. It is 0 0 0 identical of CT-2 and CT-3, where ip1 ; ip2 and ip3 are the primary currents of CT-1, CT-2 and CT-3 referred to the secondary side; iFe1 ; iFe2 and iFe3 are the currents through resistance RFe1 , RFe2 and RFe3 which represent the losses of iron core; im1 ; im2 and im3 are the magnetizing currents through the non-linear inductance Lm1 , Lm2 and Lm3 , which represent the magnetizing behavior of the iron core; v m1 ; v m2 and v m3 are the voltages across the magnetizing branches. 2.4. Magnetizing branches Similarly, the current in the core loss branches in CT-2 and CT-3 are where 2 RFe2 Dt 2 ¼ RFe3 Dt The flux–current relationship of the magnetizing branch can be represented by the piecewise linear curve. There is following relation of magnetizing current and flux in the iron core: im1:new im1:old ¼ im1:new ¼ 1 ðk1:new k1:old Þ Lm1 1 k1:new þ km1 Lm1 ð6Þ where km1 ¼ im1:old 1 k1:old Lm1 Similarly, the magnetizing currents in CT-2 and CT-3 are 1 k2:new þ km2 Lm2 1 ¼ k3:new þ km3 Lm3 im2:new ¼ ð7Þ im3:new ð8Þ where Fig. 2. 3-CT connection scheme. 1 k2:old Lm2 1 ¼ im3:old k3:old Lm3 km2 ¼ im2:old km3 According to Fig. 3, the voltage on the secondary branch is dis1 dðis1 þ is2 þ is3 Þ þ R0 ðis1 þ is2 þ is3 Þ þ L0 dt dt dis1 dðis2 þ is3 Þ þ R0 ðis2 þ is3 Þ þ L0 ¼ ðR1 þ R0 Þis1 þ ðL1 þ L0 Þ dt dt dðis2 þ is3 Þ 0 0 dis1 ¼ R1 is1 þ L1 þ R0 ðis2 þ is3 Þ þ L0 dt dt v m1 ¼ R1 is1 þ L1 Fig. 3. Equivalent circuit of CT-1. ð9Þ ID 400583 Title Anovelerrorcompensationalgorithmforthree-currenttransformerconnection http://fulltext.study/article/400583 http://FullText.Study Pages 5