High Speed Fuses

advertisement
May 2003
High Speed Fuses
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC*
700Vac / 800Vdc
ULà
25-350A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
000FU/70
2
I t [A s]
Pre-arc
25
32
40
50
63
80
100
125
160
200
250
315
350
Watt Loss
[W]
25
45
75
135
260
460
795
1.300
2.550
4.350
7.400
12.500
17.000
Ordering Information
Curves
Ref. No.
Without indicator
Data sheet
170M1750
170M1751
170M1752
170M1753
170M1754
170M1755
170M1756
170M1757
170M1758
170M1759
170M1760
170M1761
170M1762
170K6422-23
Clearing at 690V
135
240
395
695
1.350
2.350
4.000
6.800
13.500
22.000
37.500
65.000
88.000
12
13
14
16
17
20
25
29
34
40
48
60
65
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 800Vdc
- Low inductance < 15 nH
- Watt Loss provided at rated current
* Tested at 863Vdc acc. to IEC 60269-4
à Tested at 800Vdc acc. to UL 248-1 (Pending)
170Q0501E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC
700Vac / 800Vdc
UL
High Speed Fuses
25-350A
Total clearing It2
The total clearing It2 at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
E,g (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage E,g (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,8
0,7
0,4
3
0,5
10
0,3
8
0,4
7
6
0,3
0,2
5
0,15
0,2
4
200
300
400
500
600
700
3
200
300
400
500
600
700
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
High Speed Fuses
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC*
700Vac / 800Vdc
ULà
25-350A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
000FN/70
2
I t [A s]
Pre-arc
25
32
40
50
63
80
100
125
160
200
250
315
350
Watt Loss
[W]
25
45
75
135
260
460
795
1.300
2.550
4.350
7.400
12.500
17.000
Ordering Information
Curves
Ref. No.
With indicator
Data sheet
170M1730
170M1731
170M1732
170M1733
170M1734
170M1735
170M1736
170M1737
170M1738
170M1739
170M1740
170M1741
170M1742
170K6422-23
Clearing at 690V
135
240
395
695
1.350
2.350
4.000
6.800
13.500
22.000
37.500
65.000
88.000
12
13
14
16
17
20
25
29
34
40
48
60
65
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 800Vdc
- Low inductance < 15 nH
- Watt Loss provided at rated current
* Tested at 863Vdc acc. to IEC 60269-4
à Tested at 800Vdc acc. to UL 248 -1 (Pending)
170Q0503E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
690Vac / 750Vdc IEC
High Speed Fuses
700Vac / 800Vdc UL
25-350A
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
200
300
400
500
600
700
3
200
300
400
500
600
700
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
High Speed Fuses
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC*
700Vac / 800Vdc
ULà
100-630A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
2
I t [A s]
Pre-arc
230FU/70
Ordering Information
Watt Loss
[W]
100
125
160
200
250
315
350
400
450
500
550
630
380
645
1.350
2.550
4.950
9.350
12.000
18.500
27.000
37.500
48.500
69.500
Ref. No.
Without indicator
Curves
Data sheet
Clearing at 690V
1.950
3.300
7.000
13.500
25.000
47.500
61.000
94.500
140.000
190.000
245.000
355.000
35
42
47
54
62
72
78
80
85
90
95
105
170M1770
170M1771
170M1772
170M1773
170M1774
170M1775
170M1776
170M1777
170M1778
170M1779
170M1780
170M1781
170K6426-27
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 800Vdc
- Low inductance < 15 nH
- Watt Loss provided at rated current
* Tested at 863Vdc acc. to IEC 60269-4
à Tested at 800Vdc acc. to UL 248-1
170Q0502E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC
700Vac / 800Vdc
UL
High Speed Fuses
100-630A
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
200
300
400
500
600
700
3
200
300
400
500
600
700
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
High Speed Fuses
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC*
700Vac / 800Vdc
ULà
100-630A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
2
I t [A s]
Pre-arc
230FN/70
Watt Loss
[W]
100
125
160
200
250
315
350
400
450
500
550
630
380
645
1.350
2.550
4.950
9.350
12.000
18.500
27.000
37.500
48.500
69.500
Ordering Information
Curves
Ref. No.
With indicator
Data sheet
Clearing at 690V
1.950
3.300
7.000
13.500
25.000
47.500
61.000
94.500
140.000
190.000
245.000
355.000
35
42
47
54
62
72
78
80
85
90
95
105
170M1785
170M1786
170M1787
170M1788
170M1789
170M1790
170M1791
170M1792
170M1793
170M1794
170M1795
170M1796
170K6426-27
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 800Vdc
- Low inductance < 15 nH
- Watt Loss provided at rated current
* Tested at 863Vdc acc. to IEC 60269-4
à Tested at 800Vdc acc. to UL 248-1
170Q0504E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
690Vac / 750Vdc
IEC
700Vac / 800Vdc
UL
High Speed Fuses
100-630A
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
200
300
400
500
600
700
3
200
300
400
500
600
700
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
Typower Zilox IGBT Fuse
1000Vac / 1000Vdc*
25-250A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
000FU/90
2
I t [A s]
Pre-arc
25
32
40
50
63
80
100
125
160
200
225
250
Watt Loss
[W]
19
34
61
135
245
505
1.050
1.900
4.050
8.500
12.000
16.000
High Speed Fuses
Ordering Information
Curves
Ref. No.
Without indicator
Data sheet
170M1802
170M1803
170M1804
170M1805
170M1806
170M1807
170M1808
170M1809
170M1810
170M1811
170M1812
170M1813
170K6680-81
Clearing at 1000V
95
170
300
675
1.200
2.500
5.150
9.500
20.000
42.000
59.000
79.500
14
17
20
21
22
27
32
34
37
43
45
48
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Watt Loss provided at rated current
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 1000Vdc .
- Low inductance < 20 nH
- UL dc recognized
* Tested at 1150Vdc acc. to IEC 60269-4
Tested at 1000Vdc acc. to UL 248-1
170Q0507E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
High Speed Fuses
25-250A
1000Vac / 1000Vdc
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
500
600
700
800
900
1000
3
500
600
700
800
900
1000
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
Typower Zilox IGBT Fuse
1000Vac / 1000Vdc*
25-250A
Electrical Characteristics
Type
Rated
current
RMS-amp
2
000FN/90
2
I t [A s]
Pre-arc
25
32
40
50
63
80
100
125
160
200
225
250
Watt Loss
[W]
19
34
61
135
245
505
1.050
1.900
4.050
8.500
12.000
16.000
High Speed Fuses
Ordering Information
Curves
Ref. No.
With indicator
Data sheet
170M1842
170M1843
170M1844
170M1845
170M1846
170M1847
170M1848
170M1849
170M1850
170M1851
170M1852
170M1853
170K6680-81
Clearing at 1000V
95
170
300
675
1.200
2.500
5.150
9.500
20.000
42.000
59.000
79.500
14
17
20
21
22
27
32
34
37
43
45
48
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Watt Loss provided at rated current
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 1000Vdc .
- Low inductance < 20 nH
- UL dc recognized
* Tested at 1150Vdc acc. to IEC 60269-4
Tested at 1000Vdc acc. to UL 248-1
170Q0508E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
High Speed Fuses
25-250A
1000Vac / 1000Vdc
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
500
600
700
800
900
1000
3
500
600
700
800
900
1000
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
Typower Zilox IGBT Fuse
1000Vac / 1000Vdc*
100-500A
Electrical Characteristics
Type
Rated
current
RMS-amp
I2t [A2s]
Pre-arc
230FU/90
100
125
160
200
250
315
350
400
450
500
Watt Loss
[W]
600
1.200
2.550
4.650
9.300
18.500
24.500
37.500
52.000
69.500
High Speed Fuses
Ordering Information
Curves
Ref. No.
Without indicator
Data sheet
Clearing at 1000V
3.050
6.050
13.000
23.000
45.500
91.500
125.000
185.000
260.000
340.000
38
42
48
55
62
68
75
80
85
90
170M1824
170M1825
170M1826
170M1827
170M1828
170M1829
170M1830
170M1831
170M1832
170M1833
170K6682-83
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Watt Loss provided at rated current
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 1000Vdc .
- Low inductance < 20 nH
* Tested at 1150Vdc acc. to IEC 60269-4
Tested at 1000Vdc acc. to UL 248-1
170Q0505E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
High Speed Fuses
100-500A
1000Vac / 1000Vdc
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
500
600
700
800
900
1000
3
500
600
700
800
900
1000
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
May 2003
Typower Zilox IGBT Fuse
1000Vac / 1000Vdc*
100-500A
Electrical Characteristics
Type
Rated
current
RMS-amp
I2t [A2s]
Pre-arc
230FN/90
100
125
160
200
250
315
350
400
450
500
Watt Loss
[W]
600
1.200
2.550
4.650
9.300
18.500
24.500
37.500
52.000
69.500
High Speed Fuses
Ordering Information
Curves
Ref. No.
With indicator
Data sheet
Clearing at 1000V
3.050
6.050
13.000
23.000
45.500
91.500
125.000
185.000
260.000
340.000
38
42
48
55
62
68
75
80
85
90
170M1860
170M1861
170M1862
170M1863
170M1864
170M1865
170M1866
170M1867
170M1868
170M1869
170K6682-83
- Interrupting rating 200kA RMS Symmetrical (Estimated)
- Watt Loss provided at rated current
- Optimized for use in IGBT inverter circuits with DC-link voltages up to 1000Vdc .
- Low inductance < 20 nH
- UL recognized
* Tested at 1150Vdc acc. to IEC 60269-4
Tested at 1000Vdc acc. to UL 248-1
170Q0506E
2003.05.01 MA
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Typower Zilox IGBT Fuse
High Speed Fuses
100-500A
1000Vac / 1000Vdc
Total clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL , which may appear across the fuse
during its operation as a function of the
applied working voltage Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current. The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current.
1,5
3
2,5
1,0
1,0
2
1,8
1,6
1,4
1,2
0,6
0,5
0,4
3
0,5
10
0,4
8
7
6
0,3
0,8
0,7
0,3
0,2
5
0,15
0,2
4
500
600
700
800
900
1000
3
500
600
700
800
900
1000
0,1
30
40
50
60
70
80
90
100%
Dimensions
Dimensions in mm
1mm = 0,0394"
1" = 25,4mm
For complete specification data, please contact Cooper Bussmann
on bussmann@bussmann.dk
Download