Protection Coordination Serge Beauzile Chair IEEE FWCS Ch i Power Chair P &E Energy S Society i t serge.beauzile@ieee.org June, 10, June 10 2014 8:30 -12:30 Florida Electric Cooperatives Association Clearwater, Florida Seminar Objective • Distribution Circuit Protection – Fuse to Fuse Coordination – Recloser to Fuse Coordination – Breaker to Recloser Coordination • Transmission Line Protection – Distance Protection – Pilot Protection Schemes – Current Differential Protection IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 2 Art & Science of System Protection • Not an exact science, coordination schemes will vary based on: – Company Philosophy – Protection engineer preference – System requirements IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 3 C Coordinating di ti D Devices i Basic concept: All protective devices are able to detect a fault do so at the same instant. If each h device d i that th t sensed d a fault f lt operated t d simultaneously, large portions of the system g every y time a fault needed would be de-energized to be cleared. This is unacceptable. A properly designed scheme will incorporate time delays into the protection system, allowing certain devices to operate before others. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 4 C Coordinating di ti D Devices i Timing of device operation is verified using timetime current characteristics or TCCs – device response curves plotted on log-log graph paper. Devices have inverse TCCs. They operate quickly for g magnitude g overcurrents,, and more slowly y large for lower-magnitude overcurrents. Operating time is plotted on the vertical axis, axis and current magnitude is plotted on the horizontal scale. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 5 C Coordinating di ti D Devices i Four different TCCs are shown h on the th left. Device “D” is the fastest to operate, and device “A” is the slowest. 100 1 .25 25 sec A 0.1 For a given current value, the operating ti time can be b found. f d B C D 3 kA 100,000 1000 100 10 0.01 10,000 Time in Seconds 10 Current in Amperes IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 6 Coordinating g Devices In this example, Device A is clearly l l faster than Device B for low ((400-700 A)) fault currents. 100 Uncertain Coordination 1 0.1 A B 100,000 1 10,000 1000 100 0.01 10 Time in Seconds 10 Device B is clearly faster for high (>1000 A) fault currents, t but b t iin the th 700-1000 A region, g is uncertain. timing Current in Amperes IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 7 Coordinating Devices Expulsion Fuse to Expulsion Fuse 100 Minimum Melt Average Melt + tolerance Time in Seconds 10 Total Clear 1 Average Melt + tolerance + arcing time 0.1 Curves are developed at 25ºC With no preloading 10 00,000 10,000 1000 100 10 0.01 Current in Amperes IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 8 Coordinating Devices Expulsion Fuse to Expulsion Fuse 100 In this example, the red TCCs represent the downstream (protecting) fuse, and the blue TCCs represent the upstream (protected) fuse. 1 The protected fuse should not be damaged by y a fault in the protecting fuse’s zone of protection. 0.1 100,,000 10,,000 1000 1 100 0.01 10 Time in Seconds 10 Current in Amperes IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 9 Coordinating Devices Expulsion Fuse to Expulsion Fuse 100 Four factors need to be considered: 10 2. Ambient temperature. p 1 3. Preloading effects. 0.1 4. Predamage effects. 100 0,000 10 0,000 1000 1 100 0.01 10 Time in Seconds 1. Tolerances. Current in Amperes IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 10 Coordinating Devices Expulsion Fuse to Expulsion Fuse 100 Consideration of these four factors can be quite involved. Practically, the “75% Method” can be used: the maximum clearing g time of the protecting link shall be no more than 75% of the minimum melting time of the protected link. 1 0.1 Current in Amperes IEEE/ FECA Protection Coordination 100,000 10,000 1000 1 100 0.01 10 Time in Seconds 10 June 2014 Serge Beauzile 11 Coordinating Devices Expulsion Fuse to Expulsion Fuse 100 Minimum melting time of protected link at 5 kA is 0.3 seconds. Total clearing time of the protecting link at 5 kA is 0.22 seconds. 1 0.22 < 0.3 × 75% = 0.225, so coordination is assured for current magnitudes ≤ 5 kA. 0.1 Current in Amperes IEEE/ FECA Protection Coordination 100 0,000 10 0,000 1000 100 0.01 10 Time in Seconds 10 June 2014 Serge Beauzile 12 Utility y Distribution Feeders Multiple Feeder Segments Segments are defined as sectionalizable pieces of a feeder that can be automatically or manually separated from the rest of the feeder. feeder Segments are delineated by reclosers, fuses, sectionalizers or switches. switches Two primary concerns: number of customers per segment and d time to isolate l segment. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 13 Utility y Distribution Feeders Number of Customers per Segment The number of customers per segment has a major impact on reliability indices. As the number of segments per feeder increases, reliability y can also be adversely y impacted, p and construction cost will increase. A optimum An ti point i t mustt b be sought ht tto d determine t i th the best segment size. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 14 Utility Distribution Feeders Present and Future Load Requirements Even the best load forecasts are full of errors. You must continuously monitor your fuse coordination due changes in the load. It is impossible to predict everything, so versatility is the key. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 15 Coordination Goal IEEE/ FECA Protection Coordination 1. Maximum Sensitivity. 2. Maximum Speed. 3. Maximum Security. 4. Maximum Selectivity. June 2014 Serge Beauzile 16 Basic Coordination Strategy gy IEEE/ FECA Protection Coordination 1. Establish a coordination pairs. 2. Determine maximum load of each segment and the pickup of all delayed overcurrent devices. 3. Determine the pickup current of all instantaneous overcurrent devices, based on short-circuit studies. 4 4. Determine D t i remaining i i overcurrent device characteristics starting g to from the load and moving the source. June 2014 Serge Beauzile 17 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 18 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 19 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 20 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 21 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 22 Fuse Peak Load Capability IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 23 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 24 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 25 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 26 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 27 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 28 Fuse Blow Vs. Fuse Save • Fuse Blow – Eliminates Instantaneous trip of the breaker or recloser (1st) by having the fuse blow for all permanent and temporary faults. – Minimizes momentary interruptions and increases SAIDI. SAIDI Improves power quality but decreases reliability. • Fuse Save – Minimizes customer interruption time by attempting to open the breaker or recloser faster than it takes to melt the fuse. fuse – This saves the fuse and allows a simple momentary interruption. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 29 Fuse Blow FUSE is BLOWN Lateral experiences sustained interruption 30 Fuse Blow – Used primarily to minimize momentary interruptions (reduces MAIFI) – Increases interruption duration (SAIDI) – Very successful in high short circuit areas – More suitable for industrial type customers having very sensitive loads IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 31 Fuse Save Entire Feeder trips Momentary occurs FUSE is SAVED IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 32 Fuse Save – – – – – – Minimize customer interruption time Reduce SAIDI Increase MAIFI May not work in high short circuit areas Work well in most areas Not suitable for certain industrial customers that cannot tolerate immediate reclosing – Works best for residential and small commercial customers IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 33 Both ((Fuse Save & Fuse Blow)) • Many utilities use both schemes for a variety of reasons – Fuse Blow for high short circuit current areas and Fuse Save where it will work. – Fuse Save on overhead and Fuse Blow on underground taps. – Fuse Save on rural and Fuse Blow on urban – Fuse Save on stormy days and Fuse Blow on nice days. – Fuse F Save S on some circuits i it and d Fuse F Blow Bl on others depending on customer desires IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 34 Fast Bus Trip IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 35 SEL-351S SEL 351S Protection and Breaker Control Relay IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 36 Modern Microprocessor Relay Protection and Breaker Control Relay Extremely versatile, many applications Most commonly used on distribution feeders Communicates with EMS system (DNP 3.0 Protocol) Key element of “Substation Integration” Provides many “traditional” features Provides new capabilities IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 37 SEL-351S Protection and Breaker Control Relay Protection Features: P f Performs att lleastt 18 different diff t protection t ti functions. f ti = IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 38 SEL-351S Protection and Breaker Control Relay Protection Features: B U Bus Undervoltage d lt (27) Phase Overvoltage (59P) G Ground d Overvoltage O lt (59G) Sequence Overvoltage (59Q) O Overfrequency f (81O) Underfrequency (81U) IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 39 Modern Microprocessor Relay Protection and Breaker Control Relay Protection Features (continued): Ph Phase Di Directional ti l Overcurrent O t (67P) Ground Directional Overcurrent (67G) S Sequence Di Directional ti l Overcurrent O t (67Q) Instantaneous Phase Overcurrent (50P) I t t Instantaneous Ground G d Overcurrent O t (50G) Instantaneous Sequence Overcurrent (50Q) IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 40 SEL-351S Protection and Breaker Control Relay Protection Features (continued): Ti Time Ph Phase Overcurrent O t (51P) Time Ground Overcurrent (51G) Ti Time S Sequence Overcurrent O t (51Q) Directional Neutral Overcurrent (67N) I t t Instantaneous N t l Overcurrent Neutral O t (50N) Time Neutral Overcurrent (51N) IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 41 SEL-351S Protection and Breaker Control Relay Breaker Control Features: S Synchronism h i Ch Check k (25) Automatic Circuit Reclosing (79) TRIP/CLOSE Pushbuttons Enable/Disable Reclosing Enable/Disable Supervisory Control IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 42 SEL-351S Protection and Breaker Control Relay Other Features: E Event t Reporting R ti and dR Recording di Breaker Wear Monitor St ti Battery Station B tt M Monitor it High-Accuracy Metering F lt Locator Fault L t IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 43 SEL-351S Protection and Breaker Control Relay IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 44 • Advantages of microprocessor relays Extremely flexible Have many different elements (UF, UV, Directionality, etc…) One relay can protect on zone of protection Inexpensive and require much less maintenance Alarm if they fails and don’t need calibration Provide fault information Provide oscillography and SER data Can provide analog data to SCADA • Disadvantages of microprocessor relays Can be very complex to program due to given flexibility Require R i more training t i i to t Relay R l T Technicians h i i Require more training to Relay Engineers IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 45 Relays • Basic relay settings: Phase overcurrent elements must be set above maximum possible loads Ground overcurrent elements must be set above maximum anticipated p unbalanced loads Must be coordinated with downstream protective devices Under Frequency elements must be set according to the predetermined set point • TAGGING NORMAL mode – 2 reclosing g attempts p WORK mode – HOT LINE TAG COLD mode IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 46 Relay Curves 100 10 S e c o n d s Moderately Inverse 1 Inverse Very Inverse Extremely Inverse 0.1 0.01 0.1 1 10 Multiple of Pick Up IEEE/ FECA Protection Coordination 100 June 2014 Serge Beauzile 47 Very Inverse Curve Time Dial 0.29s 100 In this example p Multiple of Pickup = 3. SECONDS 10 TD=0.5 1 TD=2 TD=6 TD 6 TD = 0.5 05 TD = 2 TD = 6 TD = 15 Time = 0.3s 0 3s Time = 1.1s Time = 3.4s Time = 7.0s TD=15 0.1 0.01 0.1 1 10 Multiples Of Pick Up 100 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 48 Very Inverse Curve Time Dial 0.29s In this example, 100 Pickup Pi k = 600 A A. Fault Current = 1800 A. SECONDS 10 TD=0.5 1 TD=2 T = 0.5 TD TD = 2 TD = 6 TD = 15 Time = 0.29s 0. 9s Time = 1.16s Time = 3.48s Time = 8.72s TD=6 TD 6 TD=15 0.1 0.01 0.1 1 10 Multiples Of Pick Up 100 IEEE/ FECA Protection Coordination Pickup = 900 A. Fault Current = 1800 A. TD = 0.5 TD = 2 TD = 6 TD = 15 June 2014 Time = 0.69s Time = 2.78s Time = 8.33s Time = 20.8s 20 8s Serge Beauzile 49 Pickup p Current of Delayed y Ground OC Devices Source Side Backup Load Side Primary Single g Phase to Ground Fault IMU<IPU<I MIN Fault IMU = Maximum Unbalance IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 50 Pickup p Current of Delayed y Phase OC Devices Source Side IML<IPU<Imin Ø‐Ø Fault Load Side Phase to Phase Fault IML = Maximum Load IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 51 Typical Pickup Setting TB > TR + CTI CTI = Coordination Time Interval (Typically 0.2-0.5sec) Recloser Ct ratio 600:1 IPU = 1 A IPU Primary= 600 A IEEE/ FECA Protection Coordination Breaker Ct ratio 240:1 IPU = 3.75 A IPU Primary= 900 A June 2014 Serge Beauzile 52 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 53 Trip Logic TR = OC + PB9 + 51P1T + 51G1T * (LT6 + LT7) + (50P3 + 50G3) * LT7 + (50P2 + 50G2) * SH1 OC: OPEN COMMAND (SCADA TRIP) PB9: FRONT PUSH BUTTON 51P1T: PHASE TIME OC ELEMENT 51G1T: GROUND TIME OC ELEMENT LT6: TAGGING IS IN NORMAL MODE LT7: TAGGING IS IN WORK MODE 50P2/50P3: PHASE INSTANTANEOUS OC ELEMENT 50G2/50G3: GROUND INSTANTANEOUS OC ELEMENT SH1: RECLOSING SHOT #1 (FIRST RECLOSE ATTEMPT) CTR = 600.0 INSTANTANEOUS ENABLED ONLY AFTER FIRST RECLOSE ATTEMPT 50P2P = 2.5 (1500 AMPS PRIMARY) 50G2P = 1.6 1 6 (960 AMPS PRIMARY) INSTANTANEOUS ENABLED ONLY DURING WORK/HOT LINE TAG 50P3P = 1.35 (810 AMPS PRIMARY) 50G3P = 0 0.50 50 (300 AMPS PRIMARY) – NORMAL UNBALANCE GROUND CURRENT ~20 TO 30 AMPS IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 54 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 55 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 56 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 57 SEL-351S History Summary (HIS Command) Sample output: IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 58 SEL-351S Sequence of Events Recording (SER) IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 59 SEL-351S Metering Data (MET Command) Sample output - Metering Data (MET): IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 60 SEL-351S Metering Data (MET Command) Sample output - Metering Demand (MET D): IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 61 SEL-351S Metering Data (MET Command) Sample output - Metering Energy (MET E): IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 62 SEL-351S Metering Data (MET Command) Sample output - Metering Max/Min (MET M): IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 63 Differential Relays Protection of a Delta‐Wye Transformer Ia‐IIb A B C Ib‐Ic Ic‐Ia Ia‐IIb Ia‐Ib Ib‐Ic Ib‐Ic 52 Ic‐Ia Ia Ib Ic Ic‐Ia Ia Ia Ia I b 52 Ib Ib I c Ic a b c Ic Ia‐Ib Ia‐Ib Ib‐Ic Ic‐Ia Power System Protection R OP R Ia‐Ib R OP R Ib‐Ic Ib‐IIc R OP R Ic‐Ia -64- Ic‐Ia Ralph Fehr, Ph.D., P.E. – October 28, 2013 Distance Relays y Protection Features – Four zones of distance protection – Pilot schemes – Phase/Neutral/Ground TOCs – Phase/Neutral/Ground IOCs Phase/Neutral/Ground IOCs Power System Protection -65- Ralph Fehr, Ph.D., P.E. – October 28, 2013 Distance Relays y Protection Features ‐ continued – Negative sequence TOC – Negative sequence IOC – Phase directional OCs – Neutral directional OC – Negative sequence directional OC – Phase under‐ and overvoltage – Power swing blocking – Out of step tripping Power System Protection -66- Ralph Fehr, Ph.D., P.E. – October 28, 2013 Distance Relays Control Features Control Features – Breaker Failure (phase/neutral amps) B k F il ( h / t l ) – Synchrocheck – Autoreclosing Power System Protection -67- Ralph Fehr, Ph.D., P.E. – October 28, 2013 Distance Relays Metering Features Metering Features − Fault Locator F lt L t − Oscillography − Event Recorder − Data Logger − Phasors / true RMS / active, reactive and apparent power, power factor and apparent power, power factor Power System Protection -68- Ralph Fehr, Ph.D., P.E. – October 28, 2013 Distance Relays Zones of Protection Zone 2 Zone 2 X 3 Zone 1 2 1 Line Impedance (Line A) Line Impedance (Line A) Zone 2 1 A1 Z Zone 3 3 Bus 1 Zone 3 Power System Protection Bus 2 Normal Load Normal Load R Distance Relay at Bus 1 to protect Line A 4 A2 3 4 Zone 1 2 Line A Zone 1 – fastest (80% of line) Zone 2 – slower (120% of line) Zone 3 –(backwards Use in Pilot Protection for current Reversal logic) -69- Ralph Fehr, Ph.D., P.E. – October 28, 2013 Zone of Protection Zone 2 Zone 1 1 ∆t 2 ∆t ∆t Zone 2 Zone 1 4 3 Zone 1 Zone 2 Zone 3 Zone 1 Zone 2 Zone 3 Zone 1: Under reaches the remote line end Typically 0.7 Z1L to 0.9 Z1L With no intentional time delay. Zone 2: Z 2 Over O reaches h the th remote t line li end d Typically T i ll 1.2 1 2 Z1L with definite time delay. Zone 3: Over reaches the longest adjacent line with i h definite d fi i time i d delay l greater than h Z Zone2. 2 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 70 Unconventional Zone 2 & Zone 3 Settings Zone 2 Zone 1 Long Line ∆t Short Line Be Mindful when Applying General Rules IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 71 Step Distance Relay Coordination Exercise Setting the relay at breaker 3 protecting Circuit 2. Set the Zones of Protection. The maximum expected load is about 600A. CTR = 1200:5 or 240:1 IEEE/ FECA Protection Coordination PTR = 600:1 June 2014 Serge Beauzile 72 Distance Relay Coordination Exercise Circuit 2 & Circuit 5 Impedances Circuit 3 & Circuit 6 Impedances Z1 = 35.11 83.97˚ Ω primary Z1 = 17.56 83.72˚ Ω primary Z0 = 111.58 81.46˚ Ω primary Z0 = 53.89 81.56˚ Ω primary Circuit 1& Circuit 4 Impedances Z1 = 35.21 83.72˚ Ω primary Z0 = 187.80 81.56˚ Ω primary IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 73 Distance Relay Coordination Exercise Zone 1 Reach = 0.8 * (35.11 83.97˚) Ω primary Z Zone 2R Reach h=1 1.2 2 * (35.11 35 11 83.97˚) 83 97˚) Ω primary i Zone 1 Reach = 28.09 83.97˚) Ω primary Z Zone 2R Reach h = 42.13 42 13 83.97˚) 83 97˚) Ω primary i Check Zone 2 reach does not overreach = Circuit 2 Impedance + (Zone 1 of Circuit 3) or (Zone 1of Circuit 6). General rule = p protected Circuit Impedance p + Zone 1 of the Shortest Circuit p past the p protected circuit. Check for Zone 2 Overreach = 35.11. + (0.8 * 17.56) = 49.16 Ω primary Zone 2 Reach = 42.13 < 49.16 no overreach Zone 4 Reach = (35.11 83.97˚) + (17.56 83.72˚) ( Ω primary) Zone 4 Reach = 52.55 83.35˚) Ω primary IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 74 Primary / Secondary Impedance Relay Input 75 Relay Input Zone 1 Reach = 28.09 Ω x 240 = 11.24 Ω secondary 600 Zone 2 Reach = 42.43 Ω x 240 = 16.97 Ω secondary 600 Zone 4 Reach = 28.09 Ω x 240 = 21.02 Ω secondary 600 IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 76 Overcurrent Supervision Setting Criteria Zone 1 Phase Fault detector: 1) Find the lowest Ø – Ø fault seen by relay 3 for a remote end bus (4 (4, 10 10, 5 5, 11) 11). Set above (maximum load) and 60% of min fault. Zone 2 Phase Fault detector: 1) Find the lowest Ø – Ø fault seen by relay 3 for a remote end bus ((6,, 12). ) Set above (maximum load) and 60% of min fault. Zone 4 Fault detector same as Zone 2 Repeat same process for Ground Fault detector. IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 77 Current Infeed IL =0.5 A ZL =2 Ω IR =1 A ZR =1 Ω IT =0.5 A ZT =1 Ω Actual Impedance from L to the Fault is 3Ω Apparent Impedance = EL IL Apparent Impedance = ( IL x ZL) + (IR x ZR) IL IEEE/ FECA Protection Coordination Apparent Impedance = 4Ω June 2014 Serge Beauzile 78 Thank You IEEE/ FECA Protection Coordination June 2014 Serge Beauzile 79