Element C Interiors Interior Finishes C3020 Floor Finishes PART 1 - GENERAL 1.01 OVERVIEW A. Includes carpet, terrazzo, stone, resilient flooring, quarry tile, ceramic tile, concrete, and, hardeners and sealers. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. The following table indicates finishes for various room types within Owner’s facilities. Confirm finishes with Owner’s Project Manager/Planner Designers Room Type Conference Rooms, Corridors, Offices, Waiting Areas, Family Lounges, Break Rooms Dining Areas Public Lobbies Toilet Rooms, Shower Rooms, Patient Toilets/Showers, Public/Staff Toilets Storage, Building Services, Security, Mechanical/Electrical Equipment Rooms, Shops, Telecommunications Rooms Food Preparation Nurse Station Corridors, Public Corridors in Clinical Areas Patient Rooms, Nurse Stations, Clean Workrooms/Clean Supply, Soiled Workrooms/Soiled Holding, Storage, The University of Texas MD Anderson Cancer Center ODG041712 Floor Finish Carpet tile. (Provide seamless sheet vinyl flooring adjacent to counters in Break Rooms) Confirm with Owner’s Project Manager/ Planner Designer. Confirm with Owner’s Project Manager /Planner Designer. Porcelain ceramic tile with solid surface material door threshold. Refer to Typical Restroom Door Threshold detail located on the Owner’s Design Guidelines website. At patient toilets, provide a seamless floor system in toilet rooms for radioactive patients. Provide non-slip flooring at patient shower areas. At Shower Rooms and Patient Toilets/Showers, provide a waterproof membrane under the floor finish in the entire room. Vinyl composition tile (VCT). Sealed concrete. (Antistatic sealer at Telecommunications Rooms) Quarry tile. Seamless sheet vinyl flooring with heat welded seams. Accent colors of same seamless sheet vinyl used for wayfinding purposes. Confirm with Owner’s Project Manager/ Planner Designer. Seamless sheet vinyl flooring with heat welded seams. Confirm with Owner’s Project Manager/ Planner Designer FLOOR FINISHES C3020 1 OF 4 Element C Interiors Interior Finishes C3020 Floor Finishes Room Type Locker Rooms, Staff Corridors, Staff Elevator Lobbies, Service Elevator Lobby, Janitor Closets, Work Rooms, Clinical Corridors, Isolation Rooms, Procedure Rooms, Pharmacy, Clinical Areas, Operating Rooms Freight Elevator Lobby, Dock Receiving, Material Movement Corridor Laboratories, Lab Support Areas, Tissue Culture Rooms, Dark Rooms, Flex Rooms and Shared Equipment Areas Research Laboratory Special Function Rooms (Glasswash, Liquid Nitrogen Storage Rooms) Vivarium and Vivarium Support Functions Shell Space Selected Imaging Equipment Rooms Floor Finish Fluid-applied epoxy resin or sealed concrete. Seamless sheet vinyl flooring with heat welded seams Fluid applied epoxy resin Fluid applied epoxy resin No finish Raised access flooring vinyl finish. PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. In addition to incorporating all applicable life safety and building code requirements, provisions described within this Element shall be included within the Project Contract Documents. B. Where terrazzo is the scheduled finish for an area occupying more than one structural bay, a “sand cushion” terrazzo system with depressed floor slab shall be utilized. Depressed slab and all membranes/materials beneath the terrazzo shall be fully detailed. Confirm use of sand cushion system with Owner’s Project Manager. C. Indicate that flooring materials shall be installed using adhesives/products which are recommended for use by the manufacturer. Require that shop drawing submittals for flooring material include information on the proposed installation product(s) and substantiate that they are as recommended for use by the manufacturer. Indicate that in cases where products differ from those recommended by the manufacturer, the installer/contractor shall bear sole responsibility for any resulting deficiencies. D. Require that flooring materials be installed as late in the construction schedule as practical, and be protected from damage from construction operations and placement of equipment and fixtures during the remainder of the construction period. Require use of protection methods recommended in writing by manufacturer and installer that ensure the flooring material is without damage or deterioration at time of Substantial Completion. The University of Texas MD Anderson Cancer Center ODG041712 FLOOR FINISHES C3020 2 OF 4 Element C Interiors Interior Finishes C3020 Floor Finishes E. Indicate that immediately prior to Substantial Completion inspections, resilient flooring (sheet vinyl and vinyl composition tile) is to have a floor finish applied and be buffed/burnished as recommended by the manufacturer to a level acceptable to Owner. F. Schedule walk off carpet in lieu of using recessed mats at building entrances. G. Select floor joint assemblies that are appropriate for expected traffic. PART 4 - PRODUCTS 4.01 GENERAL A. Obtain approval from Owner’s Project Manager/Planner Designer for all finish schedules prior to issuance of Construction Documents. B. For renovation projects, refer to Owner’s Master Construction Specifications and Interior Finishes Standards. These are available on the Owner’s Design Guidelines website: Construction Specifications - http://www2.mdanderson.org/depts/cpm/standards/specs.html Interior Finish Standards - http://www2.mdanderson.org/depts/cpm/standards/interiors.html PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Reviser 01-01-07 Initial Adoption of Element Rev. 1 08-14-08 Various revisions throughout document incorporating interior standards and eliminating project specific requirements. LN, JC, DB Rev. 2 07-08-10 Revised finish at Laboratories, and added more types of spaces to the category; Added Research Laboratory Special Function Rooms; Deleted Special Function Room. KB Rev. 3 09-16-10 Added 3.01 B. JRC Rev. 4 08-02-11 Deleted "Non-static" from the floor finish type for Storage, Building Services, Security and Telecommunications Rooms. Paragraph 2.01 A. JRC Rev. 5 11-22-11 Added 3.01 C, D, and E related to installation product approval, protection during construction, and final finish application prior to inspection. Changed finishes for telecom and break rooms. JRC Rev. 6 04-17-12 Added Operating Rooms in table; Added 2.01 F and 2.01 G. JRC The University of Texas MD Anderson Cancer Center ODG041712 FLOOR FINISHES C3020 3 OF 4 Element C Interiors Interior Finishes C3020 Floor Finishes END OF ELEMENT C3020 The University of Texas MD Anderson Cancer Center ODG041712 FLOOR FINISHES C3020 4 OF 4