2 TAC Xenta 500/700/911/913

advertisement
TAC Vista
TAC Pangaea
WorkStation
TAC Xenta 500/700/911/913
Product Manual
TAC Vista
TAC Xenta 500/700/911/913
Product Manual
Copyright © 2011 Schneider Electric Buildings AB. All rights reserved.
This document, as well as the product it refers to, is only intended for licensed users. Schneider Electric Buildings AB owns the copyright of
this document and reserves the right to make changes, additions or deletions. Schneider Electric Buildings AB assumes no responsibility for
possible mistakes or errors that might appear in this document.
Do not use the product for other purposes than those indicated in this document.
Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or
mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express
written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
TAC Xenta 500/700/911/913, Product Manual
Contents
Contents
INTRODUCTION
1
About this Manual
11
1.1
1.2
1.3
1.4
12
12
13
14
Structure .....................................................................................................................
Typographic Conventions ..........................................................................................
Terminology ...............................................................................................................
Related Documents ....................................................................................................
REFERENCE
2
3
4
TAC Xenta 500/700/911/913
17
2.1
2.1.1
2.1.2
2.1.3
2.1.4
2.2
2.2.1
2.2.2
2.2.3
2.3
2.3.1
2.3.2
2.4
2.5
17
18
21
23
23
25
25
26
28
31
32
34
35
36
Hardware ....................................................................................................................
Communication Interface...........................................................................................
Port Pins .....................................................................................................................
Fail-Safe State ............................................................................................................
LEDs ..........................................................................................................................
Configuring the TAC Xenta 500/700/911/913 ..........................................................
Configuration Data.....................................................................................................
Configuring Windows HyperTerminal ......................................................................
Configuring the TAC Xenta.......................................................................................
Verifying the TAC Xenta Communication ................................................................
Accessing the TAC Xenta ..........................................................................................
Changing the Root Password .....................................................................................
Temporary Login ID ..................................................................................................
Upgrading the System Program .................................................................................
Connecting the TAC Xenta to Your Network
41
3.1
3.1.1
42
42
Alternative Port Settings ............................................................................................
HTTP and HTTPS......................................................................................................
TAC Xenta 511
4.1
4.1.1
4.2
4.2.1
4.3
4.3.1
4.3.2
4.3.3
4.3.4
43
Configuration Phase ................................................................................................... 43
Connections, configuration ........................................................................................ 44
Engineering Phase ...................................................................................................... 45
Connections, engineering ........................................................................................... 46
Operating Phase ......................................................................................................... 47
Directly Connected..................................................................................................... 47
Connections, operation directly ................................................................................. 48
Dialed-Up, operation.................................................................................................. 49
Connections................................................................................................................ , operation dial-up ............................................................................................................ 50
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
5 (134)
Contents
4.4
5
6
7
8
TAC Xenta 500/700/911/913, Product Manual
Port Usage ..................................................................................................................
51
TAC Xenta 527
53
5.1
5.1.1
5.2
5.2.1
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.4
5.5
5.6
53
54
55
56
58
58
58
60
60
63
64
65
Configuration Phase ...................................................................................................
Connections ................................................................................................................
Engineering Phase ......................................................................................................
Connections ................................................................................................................
Operating Phase..........................................................................................................
Directly Connected.....................................................................................................
Connections ................................................................................................................
Dialed-Up ...................................................................................................................
Connections ................................................................................................................
Port Usage ..................................................................................................................
Connecting the TAC Xenta 527 to an I/NET Controller LAN ..................................
Using a Direct Connection to I/NET ..........................................................................
TAC Xenta 555
67
6.1
6.1.1
6.2
6.2.1
6.2.2
6.3
6.3.1
6.4
6.5
6.5.1
6.5.2
6.5.3
67
68
69
70
72
73
73
75
76
77
78
78
Configuration Phase ...................................................................................................
Connections ................................................................................................................
Engineering Phase ......................................................................................................
Connections ................................................................................................................
RS485 LAN Wiring....................................................................................................
Operating Phase..........................................................................................................
Connections ................................................................................................................
Port Usage ..................................................................................................................
Connecting the TAC Xenta 555 to a MicroNet Controller LAN ...............................
Connecting to a MicroNet NCP network (MN MI not used).....................................
Connecting to a MicroNet ARCNET network (MN MI used)...................................
Connecting to a Satchnet network (MIU not used) ....................................................
TAC Xenta 701/711/721
79
7.1
7.1.1
7.2
7.2.1
7.3
7.3.1
7.3.2
7.3.3
7.3.4
7.4
79
80
81
82
83
83
84
85
86
87
Configuration Phase ...................................................................................................
Connections ................................................................................................................
Engineering Phase ......................................................................................................
Connections ................................................................................................................
Operating Phase..........................................................................................................
Directly Connected.....................................................................................................
Connections ................................................................................................................
Dialed-Up ...................................................................................................................
Connections ................................................................................................................
Port Usage ..................................................................................................................
TAC Xenta 731
89
8.1
8.1.1
8.2
8.2.1
8.3
8.3.1
8.3.2
8.3.3
8.3.4
89
90
91
92
94
94
95
97
98
6 (134)
Configuration Phase ...................................................................................................
Connections ................................................................................................................
Engineering Phase ......................................................................................................
Connections ................................................................................................................
Operating Phase..........................................................................................................
Directly Connected.....................................................................................................
Connections ................................................................................................................
Dialed-Up ...................................................................................................................
Connections ................................................................................................................
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8.4
9
Contents
Port Usage .................................................................................................................. 100
Connecting the OP7 to Xenta 700
9.1
9.2
9.3
9.4
103
Connecting the OP7 ...................................................................................................
Remote (cabinet door) mounting ...............................................................................
Wall mounting............................................................................................................
Handheld terminal ......................................................................................................
10 TAC Xenta 911
10.1
10.1.1
10.2
10.2.1
10.3
10.3.1
10.3.2
10.3.3
10.3.4
10.3.5
10.4
105
Configuration Phase ...................................................................................................
Connections................................................................................................................
Engineering Phase ......................................................................................................
Connections................................................................................................................
Operating Phase .........................................................................................................
LonTalk Adapter ........................................................................................................
Connections................................................................................................................
IP Modem...................................................................................................................
Connections................................................................................................................
Serial Gateway ...........................................................................................................
Port Usage ..................................................................................................................
11 TAC Xenta 913
11.1
11.1.1
11.2
11.2.1
11.3
105
105
106
106
107
107
107
108
108
110
111
113
Configuration Phase ...................................................................................................
Connections................................................................................................................
Programming and Operating Phase............................................................................
Connections................................................................................................................
Port Usage ..................................................................................................................
12 Engineering TAC Xenta 911
12.1
103
103
104
104
113
114
115
115
117
119
Programming the TAC Xenta 911 ............................................................................. 119
APPENDIX
A
Hardware
A.1
A.1.1
A.1.2
A.1.3
A.1.4
A.2
A.2.1
A.2.2
A.2.3
125
Adapters .....................................................................................................................
DB9/Female-to-RJ45/Female Adapter.......................................................................
DB25/Female-RJ45/Female Adapter .........................................................................
RJ45/Female-to-DB25/Male Adapter ........................................................................
DB9/Female-to-DB25/Male Adapter.........................................................................
Cables .........................................................................................................................
RJ45-to-RJ45 Rollover Cable ....................................................................................
RJ45-to-RJ10 Cable ...................................................................................................
RJ-45-to-RJ-45 TAC Xenta-to-Xenta Cable..............................................................
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
125
125
126
127
128
129
129
129
130
7 (134)
Contents
8 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
INTRODUCTION
1
About this Manual
TAC Xenta 500/700/911/913, Product Manual
1
1 About this Manual
About this Manual
This handbook describes
•
The hardware interface of the Xenta 500/700/911/913 devices
•
Cables required for various communication configurations for the
Xenta 500/700/911/913 devices
•
The upgrading of the system program for the
Xenta 500/700/911/913 devices
•
The engineering procedure of the Xenta 911
For more information on engineering Xenta 500/700/913, see
•
TAC Xenta Server – TAC Networks, Technical Manual
•
TAC Xenta Server – Web Server, Technical Manual
•
TAC Xenta Server – Controller, Technical Manual
•
TAC Xenta Server – Gateway, Technical Manual
For more information on the use of the OP7 operator panel, together
with the TAC Xenta 700 series, see
•
TAC OP7 Operator Panel, Mini Manual
Notes
•
We are continuously improving and correcting our documentation. This manual may have been updated.
•
Please check ExchangeOnline at http://extranet.tac.com for the
latest version.
The Xenta devices as well as other products mentioned in this manual,
must not be used for any other purposes than those for which they were
designed.
Installation, connection and repair should only be carried out by authorized personnel.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
11 (134)
1 About this Manual
1.1
TAC Xenta 500/700/911/913, Product Manual
Structure
The manual is divided into the following parts:
1.2
•
Introduction
The Introduction section contains information on how this manual
is structured and where to find additional information.
•
Reference
The Reference section contains comprehensive information about
the products. It also provides you with information on mounting
and electrical installation.
Typographic Conventions
Throughout the manual the following specially marked texts may occur.
!
Warning
•
Alerts you that failure to take, or avoid, a specific action might
result in physical harm to you or to the hardware.
Caution
•
Alerts you to possible data loss, breaches of security, or other
more serious problems.
Important
•
Alerts you to supplementary information that is essential to the
completion of a task.
Note
•
Alerts you to supplementary information.
Tip
•
12 (134)
Alerts you to supplementary information that is not essential to
the completion of the task at hand.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
1.3
1 About this Manual
Terminology
•
DHCP – Dynamic Host Configuration Protocol. A protocol for
assigning dynamic IP addresses to devices on a network. With
dynamic addressing, a device can have a different IP address every
time it connects to the network. In some systems, the device's IP
address can even change while it is connected. DHCP also supports a mix of static and dynamic IP addresses.
•
DNS – Domain Name System (or Service), an Internet service that
translates domain names into IP addresses. Because domain names
are alphabetic, they are easier to remember. The Internet however,
is based on IP addresses. Consequently, every time you use a
domain name a DNS service must translate the name into the corresponding IP address.
•
FTP – File Transfer Protocol. An application used to transfer files
from one host to another and to store the files on the requesting
host.
•
IP Network – A network (for example Internet or Intranet) using
the Internet Protocol (IP) and IP addressing.
•
LTA – LonTalk Adaptor. A computer interface with the LonWorks
network.
•
NTP – Network Time Protocol. An Internet standard protocol
(used on top of TCP/IP) that assures accurate synchronization to
the millisecond of computer clock times in a network of computers.
•
SNMP – Simple Network Management Protocol. A set of protocols for managing complex networks. SNMP works by sending
messages, called protocol data units (PDUs), to different parts of a
network.
•
SNTP – Simple Network Time Protocol. A simplified version of
NTP.
•
SSL – Secure Sockets Layer. A protocol developed by Netscape
for transmitting private documents via the Internet. By convention,
URLs that require an SSL connection start with https: instead of
http:.
•
TCP/IP – Transmission Control Protocol/Internet Protocol. The
suite of protocols that when combined create the “language of the
Internet”.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
13 (134)
1 About this Manual
1.4
TAC Xenta 500/700/911/913, Product Manual
Related Documents
•
TAC Xenta Server – TAC Networks, Technical Manual
Part No.: 04-00121
•
TAC Xenta Server – Web Server, Technical Manual
Part No.: 04-00122
•
TAC Xenta Server – Controller, Technical Manual
Part No.: 04-00123
•
TAC Xenta Server – Gateway, Technical Manual
Part No.: 04-00124
•
TAC OP7 Operator Panel, Mini Manual
Part No.: 04-00072
14 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
REFERENCE
2
TAC Xenta 500/700/911/913
3
Connecting the TAC Xenta to Your
Network
4
TAC Xenta 511
5
TAC Xenta 527
6
TAC Xenta 555
7
TAC Xenta 701/711/721
8
TAC Xenta 731
10
TAC Xenta 911
11
TAC Xenta 913
12
Engineering TAC Xenta 911
TAC Xenta 500/700/911/913, Product Manual
2
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913
The Xenta 500/700/911/913 all share the same hardware design and
hardware layout. For a more detailed description on each Xenta device,
see the Docnet site at www.schneider-electric.com/buildings.
2.1
Hardware
The Xenta device is designed around a microprocessor. The module
consists of two parts, an electronics unit containing the circuit boards
and contacts, and a terminal part including the terminal blocks.
Fig. 2.1: The Xenta device – Electronics and terminal.
•
Power Outage Protection – Settings like configurations and web
pages are stored in the non-volatile (flash) memory and will not be
lost in the event of a power outage. A built-in capacitor maintains
operation of the RAM memory for at least 72 hours in the event of
a power outage.
•
Real Time Clock – The real time clock provides the internal event
log with a time stamp. The capacitor maintains operation of the
clock for at least 72 hours in the event of a power outage.
•
Mounting – The Xenta device is cabinet mounted on a TS 35 mm
norm rail EN 50022.
To simplify commissioning, the terminal part can be pre-mounted
in the cabinet.
If the Xenta device is to be wall-mounted, a wide range of standardized boxes are available.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
17 (134)
2 TAC Xenta 500/700/911/913
2.1.1
TAC Xenta 500/700/911/913, Product Manual
Communication Interface
24
1 2 3 4 5 6 7 8 9 10
21
22
23
11 12 13 14 15 16 17 18 19 20
Fig. 2.2: Connections on the Xenta device.
Table 2.1: Connections on the Xenta device.
Position
1–2
3–4
18 (134)
Description
Power supply. Minimum cross-sectional area 0.75 mm2
(AWG-19).
•
1 (G) – 24 V AC (or DC+)
•
2 (G0) – Ground
LonWorks TP/FT-10 connection.
•
3 (C1)
•
4 (C2)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2 TAC Xenta 500/700/911/913
Table 2.1: Connections on the Xenta device. (Contd.)
Position
5–8
Internal
port A
Description
RS-485 A connection.
•
5 (RX/TX+)
•
6 (RX/TX-)
•
7 (RX+)
•
8 (RX-)
Note that the interface RS-232 A (position 21) and
interface RS-485 A (position 5–8) are internally connected to port A on the processor. Only one should be
connected.
9
Ground.
•
9 (G0)
10
Fail-safe.
11–15
Unused.
16–17
Ground.
•
16 (G0)
•
17 (G0)
18
Unused.
19–20
Internal
port C
RS-485 C (SDLC) connection.
•
19 (RX/TX+)
•
20 (RX/TX-)
21
Internal
port A
RS-232 A connection.
22
Internal
port B
RS-232 B console connection.
23
Ethernet 10Base-T connection.
24
Service pin.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Note that the interface RS-232 A (position 21) and
interface RS-485 A (position 5–8) are internally connected to port A on the processor. Only one should be
connected.
19 (134)
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913, Product Manual
Caution
20 (134)
•
G0 equals GROUND.
•
Only G0 may be connected to protective ground.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2.1.2
2 TAC Xenta 500/700/911/913
Port Pins
Serial Port – RS-232 A
The RS-232 A port (position 21) is used for serial communication
between the Xenta device and the connected unit. The connector is an
8-pin modular jack (RJ-45).
Note
•
The interface RS-232 A (position 21) and interface RS-485 A
(position 5–8) are internally connected to port A on the processor. Only one should be connected.
The port uses the following signals:
Table 2.2: Port pins – RS-232 A.
87654321
1
CTS/RI (input)
2
RTS (output)
3
TxD (output)
4
RxD (input)
5
Ground
6
DSR (input)
7
DCD (input)
8
DTR (output)
Fig. 2.3: Connection using hardware signals for modem communication.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
21 (134)
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913, Product Manual
Serial Port – RS-232 B
The RS-232 B port is used for communication between the Xenta
device and a computer. It is used for configuration of the Xenta device
using Windows HyperTerminal. The connector is a 4-pin modular jack
(RJ-10).
The port uses the following signals:
Table 2.3: Port pins – RS-232 B
4321
1
TxD (output)
2
RxD (input)
3
Not used
4
Ground
Fig. 2.4: Connection using basic RS-232 signals, primarily intended for a
computer running, for example Windows HyperTerminal during the
configuration phase.
Ethernet Port – 10Base-T
The Ethernet 10Base-T port is used for communication between the
Xenta device and the TCP/IP network.
The port uses the following signals:
Table 2.4: Port pins – 10Base-T
87654321
1
TX+
2
TX-
3
RX+
4–5
Connected to ground via 75 ohms
6
RX-
7–8
Connected to ground via 75 ohms
Fig. 2.5: Connection for a LAN (Ethernet) cable.
22 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2.1.3
2 TAC Xenta 500/700/911/913
Fail-Safe State
The Xenta can enter a fail-safe state if a severe problem arises in the system program.
The unit can be forced into fail-safe mode by shorting terminals 9 and
10 in Fig. 2.2 during power-up. This can be useful if the system program
experiences problems.
The overall Run indicator (position 3 in Fig. 2.6) will show a steady red
light in the fail-safe state.
2.1.4
LEDs
A number of light-emitting diodes (LEDs) on the Xenta device indicate
that the application program is running and when communication is in
progress.
1
2
3
4
6
5
Fig. 2.6: LEDs on the Xenta device.
Table 2.5: LEDs on the Xenta device.
Position
1
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Description
Neuron status indicator
•
Off – Normal mode
•
Red, blinking – Unconfigured mode
•
Red, steady – Hardware fault
23 (134)
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913, Product Manual
Table 2.5: LEDs on the Xenta device. (Contd.)
Position
2
Description
Serial RS-232 B port activity indicators:
3
•
RX – Indicates that data is received
•
TX – Indicates that data is transmitted
Overall Run indicator
4
•
Green, steady – Normal mode
•
Green, blinking – Start mode
•
Red, steady – Fail-safe mode
(see description below)
•
Red, blinking – Unit fault
Serial RS-232 A port activity indicators:
•
RX – Indicates that data is received
•
TX – Indicates that data is transmitted
5
Serial RS-485 C port activity indicator.
6
Ethernet 10Base-T activity indicator
Note
•
The LEDs for the RS-232 A interface (position 4) do not indicate
communication when using the RS-485 A interface although
internal port A is used for both.
Serial Ports
RS-232 Port 21
A
RS-485 Port pins 5, 6 (7, 8)
Processor
B
RS-232 Port 22
C
RS-485 Port pins 19, 20
Fig. 2.7: Internal serial ports and RS-232/485 interfaces.
24 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2.2
2 TAC Xenta 500/700/911/913
Configuring the TAC Xenta 500/700/911/913
The technician uses Microsoft Windows and HyperTerminal to initialize and configure the Xenta.
2.2.1
•
For more information on how to connect the Xenta 511, see
Section 4.1, “Configuration Phase”, on page 43.
•
For more information on how to connect the Xenta 527, see
Section 5.1, “Configuration Phase”, on page 53.
•
For more information on how to connect the Xenta 555, see
Section 6.1, “Configuration Phase”, on page 67.
•
For more information on how to connect the Xenta 701/711/721,
see Section 7.1, “Configuration Phase”, on page 79.
•
For more information on how to connect the Xenta 731, see
Section 8.1, “Configuration Phase”, on page 89.
•
For more information on how to connect the Xenta 911, see
Section 10.1, “Configuration Phase”, on page 105.
•
For more information on how to connect the Xenta 913, see
Section 11.1, “Configuration Phase”, on page 113.
Configuration Data
To configure the Xenta, the following information should be obtained
from the network administrator:
•
DHCP is used or not used
•
IP address (only if DHCP is not used)
•
Subnet mask (only if DHCP is not used)
•
Default gateway
•
DNS server
•
Web site name (can be set later, using XBuilder)
•
Domain name (only used as information)
•
Host name (only used as information)
This information is used once you have connected to the Xenta using
HyperTerminal and a serial cable (null modem cable).
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
25 (134)
2 TAC Xenta 500/700/911/913
2.2.2
TAC Xenta 500/700/911/913, Product Manual
Configuring Windows HyperTerminal
When you use Windows HyperTerminal you need to set up a connection. Once created it can be used when required. In the example below
a Xenta 511 is configured.
To configure Windows HyperTerminal
26 (134)
1
Connect the Xenta to the engineering PC.
2
On the Start menu, point to All Programs, point to Accessories,
point to Communications, and then click HyperTerminal.
3
In the Connection Description dialog box, in the Name box, type
a name that describes the connection. In the example “Connection
to Xenta 511”.
4
In the Icon box, click the required icon.
5
Click OK.
6
In Connect To dialog box, in the Connect using list, click the
COM port used in step 1 above.
7
Click OK.
8
In the COM1 Properties dialog box, in the Bits per second list,
click 9600.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
9
2 TAC Xenta 500/700/911/913
In the Flow control list, click None.
10 Click OK.
11 On the File menu, click Save to save the HyperTerminal connection. The HyperTerminal for the Xenta is now ready to use.
12 Press ENTER to activate the command prompt.
Tips
•
To reopen the HyperTerminal connection to the Xenta, click
Start, point to All Programs, point to Accessories, point to
Communications, point to HyperTerminal and then click Connection to Xenta 511.ht.
•
You can also click Open on the File menu in HyperTerminal.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
27 (134)
2 TAC Xenta 500/700/911/913
2.2.3
TAC Xenta 500/700/911/913, Product Manual
Configuring the TAC Xenta
The configuration parameters for the Xenta are entered using HyperTerminal. The parameters enable the Xenta to communicate using its
TCP/IP port.
Important
•
Because the Xenta’s TCP/IP default parameters are set at the factory, you can immediately access it using a web browser and
change the parameters without having to use HyperTerminal.
The default parameters are:
•
IP address: 192.168.255.2
•
Subnet mask: 255.255.255.0
To configure the TAC Xenta
28 (134)
1
Start Windows HyperTerminal using the connection created in
Section 2.2.2, “Configuring Windows HyperTerminal”, on
page 26.
2
Press ENTER to activate the command prompt.
3
Type the user name “root” and press ENTER.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2 TAC Xenta 500/700/911/913
4
Type the password “root” and press ENTER.
5
Type the command “setip” and press ENTER.
6
Type the configuration parameters, collected in Section 2.2.1,
“Configuration Data”, on page 25. Press ENTER after each entry.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
29 (134)
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913, Product Manual
In the example, the configuration parameters appear as follows.
The root password is not changed.
7
Type the command “restart” and press ENTER, to activate the new
configuration parameters.
8
Quit HyperTerminal.
The Xenta is now configured to communicate over TCP/IP, this means
that you can access the Xenta through a web browser and that you can
send web pages to the Xenta using XBuilder.
Important
30 (134)
•
The password can be changed from a configuration page on the
web site in the Xenta.
•
The user name and the password are used by the operator when
logging on to the web site and by XBuilder when sending the
project to the Xenta.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2.3
2 TAC Xenta 500/700/911/913
Verifying the TAC Xenta Communication
Once the Xenta has been configured with respect to its address on the
TCP/IP network, it can be accessed through a web browser.
•
For more information on how to connect the Xenta 511, see
Section 4.2, “Engineering Phase”, on page 45.
•
For more information on how to connect the Xenta 527, see
Section 5.2, “Engineering Phase”, on page 55.
•
For more information on how to connect the Xenta 555, see
Section 6.2, “Engineering Phase”, on page 69.
•
For more information on how to connect the Xenta 701/711/721,
see Section 7.2, “Engineering Phase”, on page 81.
•
For more information on how to connect the Xenta 731, see
Section 8.2, “Engineering Phase”, on page 91.
•
For more information on how to connect the Xenta 911, see
Section 10.2, “Engineering Phase”, on page 106.
•
For more information on how to connect the Xenta 913, see
Section 11.2, “Programming and Operating Phase”, on page 115.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
31 (134)
2 TAC Xenta 500/700/911/913
2.3.1
TAC Xenta 500/700/911/913, Product Manual
Accessing the TAC Xenta
The Xenta is accessed using an standard web browser.
To access the TAC Xenta
1
Start Internet Explorer.
2
In the Address box, type the IP address of the Xenta. In the example “10.158.12.210”.
3
Press ENTER.
A security alert appears, similar to the following figure, with information about the site’s security certificate.
32 (134)
4
Click Yes.
5
In the Username box, type “root”.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2 TAC Xenta 500/700/911/913
6
In the Password box, type the password. In the example, “root”.
7
Click Login.
The default web page in the Xenta appears.
Note
•
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
A java applet security dialog warning may be displayed. Click
Yes in the dialog.
33 (134)
2 TAC Xenta 500/700/911/913
2.3.2
TAC Xenta 500/700/911/913, Product Manual
Changing the Root Password
The default password for the system administrator is widely known. To
avoid unauthorized access to the system the password has to be
changed. You can change the password using the Change Password
page on the Xenta web site.
To change the password
1
In the navigator, expand Configuration-User Administrator, and
click Change Password.
2
In the Old password box, type the old password. In the example,
“root”.
3
In the New password box, type the new password. In the example,
“seagull3”.
4
In the Confirm new password box, confirm the new password.
5
Click Save.
Use the new password the next time you log on as system administrator.
34 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2.4
2 TAC Xenta 500/700/911/913
Temporary Login ID
If you do not have access to the root password when you try to connect
to a Xenta 500/700/913, a temporary user name and password can be
used. The temporary password is generated by based on the Session ID
displayed on the Login page.
Send the Session ID to helpdesk@tac.com, which generates and returns
a temporary password. Then type the Session ID in the Username box
and the temporary password in the Password box.
Tip
•
You can select the text on the login page, copy it and then paste it
into the e-mail message and the Username box.
The Session ID changes each day, so the temporary password is only
valid on the day it is generated.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
35 (134)
2 TAC Xenta 500/700/911/913
2.5
TAC Xenta 500/700/911/913, Product Manual
Upgrading the System Program
The Xenta system program can be upgraded via the IP network from a
computer running the installation program. The installation program is
distributed by Schneider Electric. In the example the Xenta 511 will be
upgraded.
Note
•
To upgrade the system program of the Xenta device you must
first configure the Xenta using Windows HyperTerminal. For
more information on how to configure the Xenta, see
Section 2.2, “Configuring the TAC Xenta 500/700/911/913”, on
page 25.
To upgrade the system program
1
Connect the Xenta and a computer to a TCP/IP network according
to the figure.
TCP/IP
36 (134)
TCP/IP
2
Obtain the installation program from Schneider Electric’s web site
or from the TAC Software CD-ROM.
3
Double-click the installation program to start the installation.
The following screen shots show the installation procedure for a
Xenta 511 but they are similar for other Xenta devices.
4
Read the instructions.
5
If the requirements are met, click Next.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2 TAC Xenta 500/700/911/913
6
Select temporary folder for the installation program.
7
Click Next.
8
Select skin.
9
Click Next.
10 Select which kind of installation you want to carry out. In our
example, select Install full system.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
37 (134)
2 TAC Xenta 500/700/911/913
TAC Xenta 500/700/911/913, Product Manual
11 Click Next.
12 In the TAC Xenta 511 target unit parameters dialog box, in the
Username box, type root.
13 In the Password box, type the password for root.
14 In the IP address box, type the IP address (or the URL address) of
the Xenta device.
15 Click Next.
16 Read the list of actions that will be carried out during the installation.
38 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
2 TAC Xenta 500/700/911/913
17 Click Yes.
18 Click Finish to complete the installation.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
39 (134)
2 TAC Xenta 500/700/911/913
40 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
3
3 Connecting the TAC Xenta to Your Network
Connecting the TAC Xenta to Your
Network
The Xenta integrates with your building control system by communicating across the Ethernet using TCP/IP transport protocols.
In order for the Xenta to successfully establish communications with
your building control system, certain network criteria must be met.
More specifically, the ports required for proper communication with
these systems must be open and available to the Xenta . The Xenta uses
the following communication ports:
•
Port 80 (HTTP access, configurable)
•
Port 443 (HTTPS access, configurable)
•
Port 20/21 (FTP access)
•
Port 25 (SMTP access)
•
Port 80 (Status Viewer, Alarm Viewer and Graphics Viewer)
•
Port 1068 (LTA for Vista)
•
Port 161 (SNMP access)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
41 (134)
3 Connecting the TAC Xenta to Your Network
3.1
Alternative Port Settings
3.1.1
HTTP and HTTPS
TAC Xenta 500/700/911/913, Product Manual
Perhaps you are unable to make the necessary configuration changes to
your proxies/firewalls because of restrictions imposed by your company’s network security policies. In this case, you have the option of
choosing different numbers for the HTTP and HTTPS communication
ports shown above.
The following steps describe how to select other communication ports:
42 (134)
1
From the web browser, expand the navigation tree as shown in the
following figure and select HTTP Server.
2
Set the HTTP and HTTPS communication port assignments to the
appropriate values.
3
Accept your settings by selecting Save & Restart.
4
Configure your network to allow communication on the ports you
assigned to the Xenta.
5
Verify that the Xenta can now successfully communicate across
the Internet and with your building control systems.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
4
4 TAC Xenta 511
TAC Xenta 511
A Xenta 511 can be configured as a web-based presentation system for
LonWorks networks. Using a standard web browser, the operator can
easily view and control the devices in the LonWorks network.
4.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal via an
RS-232 connection to initialize and configure the Xenta 511. For more
information on how to initialize and configure the Xenta 511,
see Section 2.2, “Configuring the TAC Xenta 500/700/911/913”, on
page 25.
RS-232
Windows HyperTerminal
Fig. 4.1: Windows HyperTerminal communicating with a TAC Xenta 511
using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
43 (134)
4 TAC Xenta 511
4.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections, configuration
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 4.2: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
44 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
4.2
4 TAC Xenta 511
Engineering Phase
The technician uses XBuilder to program the Xenta 511 via the TCP/IP
network. To access the Xenta 511 web site a standard web browser is
used.
TCP/IP
TAC XBuilder
Web browser
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 4.3: TAC XBuilder or a web browser communicating with a TAC
Xenta 511 using IP during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
45 (134)
4 TAC Xenta 511
4.2.1
TAC Xenta 500/700/911/913, Product Manual
Connections, engineering
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
Fig. 4.4: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta RS485Aport pins 5–6 (5–8) to the
Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 511does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
46 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
4.3
4 TAC Xenta 511
Operating Phase
The operator uses a standard web browser to view and control the
devices in the LonWorks network, either via a directly connected or
using a dialed-up connection.
4.3.1
Directly Connected
The operator uses a standard web browser to view and control the
devices in the LonWorks network.
TCP/IP
Web browser
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 4.5: A web browser communicating with a TAC Xenta 511 using
TCP/IP during the operating phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
47 (134)
4 TAC Xenta 511
4.3.2
TAC Xenta 500/700/911/913, Product Manual
Connections, operation directly
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
Fig. 4.6: Connections during the operating phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta RS485Aport pins 5–6 (5–8) to the
Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 511does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
48 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
4.3.3
4 TAC Xenta 511
Dialed-Up, operation
The operator uses a standard web browser to view and control the
devices in the LonWorks network, using a dialed-up connection via
RS-232 with the possibility to use a TCP/IP network.
RS232
Web browser
RS232
Fig. 4.7: Dialed-up connection.
ISP Modem
TCP/IP
Web browser
RS232
Fig. 4.8: Dialed-up connection via TCP/IP.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
49 (134)
4 TAC Xenta 511
4.3.4
TAC Xenta 500/700/911/913, Product Manual
Connections, operation dial-up
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309160.
3
1
4
2
5
Modem
Fig. 4.9: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
1
DB25/Male-to-RJ45/Female adapter connecting the modem serial
port to the cable directly below.
1
3-621-3052-01
22
RJ-45-to-RJ-45 rollover cable connecting the adapter to the Xenta
serial port RS-232 A.
1
3-781-0118-01
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com
1
N/A
42
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP to the
Xenta 10Base-T port.
1
N/A
5
1. Part of cable kit no. 007309160.
2. Only one should be connected.
50 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
4.4
4 TAC Xenta 511
Port Usage
If a Xenta 511 and the IP network are located on opposite sides of one
or several firewalls, these firewalls must be configured to allow traffic
through.
The Xenta 511 uses the following ports:
Table 4.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 511 operating as an LTA
port.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
No
51 (134)
4 TAC Xenta 511
52 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
5
5 TAC Xenta 527
TAC Xenta 527
A Xenta 527 can be configured as a web-based presentation system for
I/NET networks. Using a standard web browser, the operator can easily
view and control the devices in the LonWorks network via the Internet
or a local intranet.
5.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal via a
RS-232 connection to initialize and configure the Xenta 527. For more
information, see Section 2.2, “Configuring the
TAC Xenta 500/700/911/913”, on page 25.
RS-232
Windows HyperTerminal
Fig. 5.1: Windows HyperTerminal communicating with a TAC Xenta 527
using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
53 (134)
5 TAC Xenta 527
5.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 5.2: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
54 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
5.2
5 TAC Xenta 527
Engineering Phase
The technician uses XBuilder to program the Xenta 527 via the TCP/IP
network. To access the Xenta 527 web site a standard web browser is
used.
TCP/IP
TAC XBuilder
Web browser
I/NET
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 5.3: TAC XBuilder or a web browser communicating with a TAC
Xenta 527 using IP during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
55 (134)
5 TAC Xenta 527
5.2.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
5
2
LAN
TCP/IP
WAN
6
TxD 3
RxD 4
Cr 5
4
Fig. 5.4: Connections during the engineering phase.
56 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Pos.
Description
5 TAC Xenta 527
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
I/NET Controller LAN cable connected to serial port RS-485 C.
1
42
Use either of the following wire types:
•
22 AWG (0.324 mm2) shielded, twisted pair, 5000' (1500 m)
maximum per segment, 150 Ω impedance, 9 pF/ft. conductor-to-conductor, 14 pF/ft. conductor-to-shield.
Belden 9184
24 AWG (0.206 mm2) shielded, twisted pair, 4000' (1200 m)
maximum per segment, 120 Ω impedance, 13 pF/ft. conductor-to-conductor, 23 pF/ft. conductor-to-shield.
Belden 9841
or
•
53
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
63
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 527 does not support Ethernet MDI, a crossover cable may be required.
2. Maintain proper polarity when connecting this cable to each device on the controller LAN.
3. Only one may be connected.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
57 (134)
5 TAC Xenta 527
5.3
TAC Xenta 500/700/911/913, Product Manual
Operating Phase
The operator uses a standard web browser to view and control the
devices in the LonWorks network, either via a directly connected or
using a dialed-up connection.
5.3.1
Directly Connected
The operator uses a standard web browser to view and control the LonWorks devices directly connected via TCP/IP.
I/NET
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
TCP/IP
Web browser
Fig. 5.5: A web browser communicating with a TAC Xenta 527 using
TCP/IP during the operating phase.
5.3.2
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
5
2
TCP/IP
6
TxD 3
RxD 4
Cr 5
4
Fig. 5.6: Connections during the operating phase.
58 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Pos.
Description
5 TAC Xenta 527
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
I/NET Controller LAN cable connected to serial port RS-485 C.
1
42
Use either of the following wire types:
•
22 AWG (0.324 mm2) shielded, twisted pair, 5000' (1500 m)
maximum per segment, 150 Ω impedance, 9 pF/ft. conductor-to-conductor, 14 pF/ft. conductor-to-shield.
Belden 9184
24 AWG (0.206 mm2) shielded, twisted pair, 4000' (1200 m)
maximum per segment, 120 Ω impedance, 13 pF/ft. conductor-to-conductor, 23 pF/ft. conductor-to-shield.
Belden 9841
or
•
53
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
63
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 527 does not support Ethernet MDI, a crossover cable may be required.
2. Maintain proper polarity when connecting this cable to each device on the controller LAN.
3. Only one may be connected.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
59 (134)
5 TAC Xenta 527
5.3.3
TAC Xenta 500/700/911/913, Product Manual
Dialed-Up
The operator uses a standard web browser to view and control the LonWorks devices using a dialed-up connection via RS-232 with the possibility to use a TCP/IP network.
RS232
Web browser
RS232
Fig. 5.7: Dialed-up connection.
ISP Modem
TCP/IP
Web browser
RS232
Fig. 5.8: Dialed-up connection via TCP/IP.
5.3.4
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
60 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
5 TAC Xenta 527
Required Cable Kit
Part. No. 007309160.
3
1
2
4
Fig. 5.9: Connections during the operating phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
61 (134)
5 TAC Xenta 527
Pos.
TAC Xenta 500/700/911/913, Product Manual
Description
Qty
Part No.
1
DB25/Male-to-RJ45/Female adapter connecting the modem serial
port to the cable directly below.
1
3-621-3052-01
22
RJ-45-to-RJ-45 rollover cable connecting the adapter directly above
to the Xenta serial port RS-232 A.
1
3-781-0118-01
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com
1
N/A
I/NET Controller LAN cable connected to serial port RS-485 C.
1
43
Use either of the following wire types:
•
22 AWG (0.324 mm2) shielded, twisted pair, 5000' (1500 m)
maximum per segment, 150 Ω impedance, 9 pF/ft. conductor-to-conductor, 14 pF/ft. conductor-to-shield.
Belden 9184
24 AWG (0.206 mm2) shielded, twisted pair, 4000' (1200 m)
maximum per segment, 120 Ω impedance, 13 pF/ft. conductor-to-conductor, 23 pF/ft. conductor-to-shield.
Belden 9841
or
•
1. Part of Modem Connect Cable Kit no. 007309160.
2. Only one should be connected.
3. Maintain proper polarity when connecting this cable to each device on the controller LAN.
62 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
5.4
5 TAC Xenta 527
Port Usage
If a Xenta 527 and the IP network are located on opposite sides of one
or several firewalls, these firewalls must be configured to allow traffic
through. The Xenta 527 uses the following ports:
Table 5.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 527 operating as an LTA
port.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
I/NET
50069
Local
No
I/NET UDP/IP.
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
No
63 (134)
5 TAC Xenta 527
5.5
TAC Xenta 500/700/911/913, Product Manual
Connecting the TAC Xenta 527 to an I/NET
Controller LAN
The Xenta 527 connects to the I/NET controller LAN through terminal
19 and 20 of its lower terminal block connector.
10Base-T
A RS 232 B
TAC Xenta
RS485 C
RX/ RX/
IP address.................-................-...............-................ TX+
TX–
11 12 13 14
15
16 17 18 19 20
Controller LAN
Connections
Fig. 5.10: Controller LAN Connections
To connect the Xenta 527 to an I/NET controller LAN
1
Connect the positive (+) line to position 19.
2
Connect the negative (–) line to position 20.
3
Splice shield wires together at each device on the controller LAN,
and connect to a good earth ground at one location only. Ensure
that shield wire continuity is maintained across the controller
LAN.
Note
•
64 (134)
The polarity of the RS485 connection is important. It is recommended that you observe the network’s polarity convention (the
positive line connected to position 1, and the negative line to
position 2, on all devices). This convention will help ensure consistent voltage measurements should diagnostic troubleshooting
become necessary.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
5.6
5 TAC Xenta 527
Using a Direct Connection to I/NET
The Xenta 527 is intended for use on an Ethernet LAN. However, you
can also directly connect an I/NET host workstation to the RS-232 A
port on the front of the Xenta 527. This allows the directly connected
I/NET host to communicate with devices on the Xenta 527’s controller
LAN. This type of connection can also be used when you are configuring the Xenta 527’s communication parameters.
In order to directly connect an I/NET host workstation to the Xenta 527,
you must connect a cable from the workstation’s serial COM port to the
Xenta 527’s RS-232 B port. TAC Xenta Programming Serial Kit
007309200 provides that adapters and cables required for this type of
connection, as well as for a console connection. to the Xenta 527’s
RS-232 B port.
Once you have connected an I/NET host workstation to Xenta 527, set
I/NET’s link type to “NetPlus Router” in the I/NET Configuration editor. Refer to TCON298, I/NET Seven Getting Started, for complete
instructions.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
65 (134)
5 TAC Xenta 527
66 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6
6 TAC Xenta 555
TAC Xenta 555
A Xenta 555 can be configured as a web-based presentation system for
MicroNet networks. Using a standard web browser, the operator can
easily view and control the devices in the MicroNet network via the
Internet or a local intranet.
6.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal via an
RS-232 connection to initialize and configure the Xenta 555. For more
information, see Section 2.2, “Configuring the
TAC Xenta 500/700/911/913”, on page 25 of this handbook.
RS-232
Xenta 555
Windows HyperTerminal
Fig. 6.1: Windows HyperTerminal communicating with a Xenta 555
using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
67 (134)
6 TAC Xenta 555
6.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
Fig. 6.2: Connections during the configuration phase.
Table 6.1: Connector descriptions (configuration phase)
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
RJ-45-to-RJ-10 Serial cable (null modem cable) connecting adapter
directly above to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
68 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6.2
6 TAC Xenta 555
Engineering Phase
The technician uses XBuilder to program the Xenta 555 via the TCP/IP
network. To access the Xenta 555 web site a standard web browser is
used.
TCP/IP
MicroNet or Satchnet
LonTalk
Modbus TCP Client
TAC XBuilder
Web browser
Fig. 6.3: TAC XBuilder or a web browser communicating with a
Xenta 555 using IP during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
69 (134)
6 TAC Xenta 555
6.2.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you will find information on which cables to use and how
to connect the cables.
Required Cable Kit
Part. No. 007309200.
TCP/IP
MNMI
PL4
Fig. 6.4: Connections during the engineering phase.
70 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6 TAC Xenta 555
Table 6.2: Connector descriptions (engineering phase)
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
32
MicroNet or Satchnet Controller LAN cable connecting the Xenta
serial port RS-485 A pins 5-6 to a MicroNet device3.
1
Use one of the following cable types (as appropriate)4:
•
24 AWG (0.206 mm2), 7 x 32 stranded, shielded5, twisted pair,
3281' (1000 m) maximum per segment, 75 Ω impedance,
30 pF/ft. conductor-to-conductor, 50 pF/ft. conductor-to-shield.
Belden 95026
20 AWG (0.519 mm2), 7 x 28 stranded, shielded5, twisted pair,
3281' (1000 m) maximum per segment, 56 Ω impedance,
27 pF/ft. conductor-to-conductor, 49 pF/ft. conductor-to-shield.
Belden 8762
or
•
4
DB9/Female-to-RJ45/Female adapter connecting the MicroNet
Manager Interface PL4 to the cable directly below.
1
3-621-3056-07
5
RJ-45-to-RJ-45 rollover cable connecting the cable directly above
to the Xenta RS 232 Port A.
1
3-781-0118-07
1. TAC Xenta 555 does not support Ethernet MDI, a crossover cable may be required.
2. Maintain proper polarity when connecting this cable to a device on the MicroNet controller LAN.
3. Alternative communication is also possible by connecting the MicroNet Manager Interface directly to the
MicroNet network, using the same cable.
4. For MN50 Series networks, use Belden 9502. For older MicroNet or Satchnet networks, use Belden 8762.
5. Connect the shield at one end of the network only, either at the MicroNet end (see MicroNet data sheets)
or to a verified good earth at the Xenta end.
6. Connect the second twisted pair (i.e the LAN REF) to Pin 2 (G0) at the Xenta 555. Maintain the LAN REF
at all devices.
7. Part of cable kit no. 007309200. The cable kit also contains a serial cable no. 3-781-0128-0 (null modem
cable) which is not needed during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
71 (134)
6 TAC Xenta 555
6.2.2
TAC Xenta 500/700/911/913, Product Manual
RS485 LAN Wiring
The following illustrations show example RS485 LAN connections
from the Xenta 555 to MicroNet networks. For full MicroNet network
wiring details refer to the MicroNet System Engineering Guide and to
the relevant MicroNet controller data sheets.
1st twisted pair (signal)
Xenta 555
+
5
6
–
MN550
+
21
20
2
43
G0
LAN
REF
MN450
–
+
14
13
–
15
1
LAN
REF GND
2nd twisted pair (LAN REF)
Fig. 6.5: RS485 LAN from Xenta 555 to a MicroNet MN50 Series
network (Belden 9502 dual twisted pair used).
Xenta 555
+
5
6
–
MN500
+
6
5
MN440
–
+
13
12
MN620
–
+
6
5
–
1
GND
Fig. 6.6: RS485 LAN from Xenta 555 to an older MicroNet network
(Belden 8762 single twisted pair used).
Note
•
72 (134)
NCP networks are shown.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6.3
6 TAC Xenta 555
Operating Phase
The operator uses a standard web browser to view and control the
devices in the MicroNet network via TCP/IP.
TCP/IP
Web browser
MicroNet
or Satchnet
Fig. 6.7: A web browser communicating with a Xenta 555 using TCP/IP
during the operating phase
6.3.1
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which cables to use and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
TCP/IP
MNMI
PL4
Fig. 6.8: Connections during the operating phase.
Note
•
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Items 4 and 5 are required whenever an ARCNET network is
used.
73 (134)
6 TAC Xenta 555
TAC Xenta 500/700/911/913, Product Manual
Table 6.3: Connector descriptions (operating phase)
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
32
MicroNet or Satchnet Controller LAN cable connecting the Xenta
serial port RS-485 A pins 5-6 to a MicroNet device3.
1
Use one of the following cable types (as appropriate)4:
•
24 AWG (0.206 mm2), 7 x 32 stranded, shielded5, twisted pair,
5000' (1500 m) maximum per segment, 75 W impedance,
30 pF/ft. conductor-to-conductor, 50 pF/ft. conductor-to-shield.
Belden 95026
22 AWG (0.324 mm2), 7 x 28 stranded, shielded5, twisted pair,
4000' (1200 m) maximum per segment, 120 W impedance,
17 pF/ft. conductor-to-conductor, 24.3 pF/ft. conductor-to-shield.
Belden 8762
or
•
4
DB9/Female-to-RJ45/Female adapter connecting the MicroNet
Manager Interface PL4 to the cable directly below.
1
3-621-3056-07
5
RJ-45-to-RJ-45 rollover cable connecting the cable directly above
to the Xenta RS 232 Port A.
1
3-781-0118-07
1. TAC Xenta 555 does not support Ethernet MDI, a crossover cable may be required.
2. Maintain proper polarity when connecting this cable to a device on the MicroNet controller LAN.
3. Alternative communication is also possible by connecting the MicroNet Manager Interface directly to the
MicroNet network, using the same cable.
4. For MN 50 Series networks, use Belden 9502. For older MicroNet or Satchnet networks, use Belden 8762.
5. Connect the shield at one end of the network only, either at the MicroNet end (see MicroNet data sheets)
or to a verified good earth at the Xenta end.
6. Connect the second twisted pair (i.e the LAN REF) to Pin 2 (G0) at the Xenta 555. Maintain the LAN REF
at all devices.
7. Part of cable kit no. 007309200. The cable kit also contains a serial cable no. 3-781-0128-0 (null modem
cable) which is not needed during the operating phase.
74 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6.4
6 TAC Xenta 555
Port Usage
If a Xenta 555 and the IP network are located on opposite sides of one
or several firewalls, these firewalls must be configured to allow traffic
through. The Xenta 555 uses the following ports:
Table 6.4: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 555 operating as an LTA
port.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
MicroNet
7001
Local
Yes
VisiSat Port (TCP)
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
No
75 (134)
6 TAC Xenta 555
6.5
TAC Xenta 500/700/911/913, Product Manual
Connecting the TAC Xenta 555 to a MicroNet
Controller LAN
The method of connecting the Xenta 555 to a MicroNet controller LAN
depends on the MicroNet LAN type. These networks are:
!
•
MicroNet NCP network, that is, MicroNet controllers using the
Native Communications Protocol. A MicroNet Manager Interface
(MN MI) must not be used.
•
MicroNet ARCNET network, that is, MicroNet controllers using
the Attached Resource Computer Network protocol. An MN MI
must be used.
•
Satchnet network, that is, older products using the Satchwell Networking Protocol (SNP). A Modem Interface Unit (MIU) must not
be used.
Note
•
Auto dial remote sites are not supported by the Xenta 555.
Tip
•
76 (134)
The MN MI and the MIU are not required for NCP and SNP networks and can be removed when installing the Xenta 555.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
6.5.1
6 TAC Xenta 555
Connecting to a MicroNet NCP network (MN MI not used)
The Xenta 555 connects to the MicroNet controller network through terminals 5 and 6 of its upper terminal block connector.
MicroNet Controller
LAN Connection
(RS485)
5 VA
1
2
G
G0 C1 C2
LON
3
24 VAC
Rx Tx
Run
Rx Tx
4
5 6 7 8 9 10
RX/ RX/
RX+ RX- G0
TX+ TXFail-safe
LON RS485 A
Rx / Tx
Fig. 6.9: RS485 LAN connections (MicroNet NCP network)
To connect the TAC Xenta 555 to a MicroNet controller
LAN
1
Connect the positive (+) line to position 5.
2
Connect the negative (–) line to position 6.
Join the shield wires together at each device on the controller LAN, and
connect to a good earth ground at one location only. Ensure that shield
wire continuity is maintained across the controller LAN.
If Belden 9502 dual-twisted pair is being used (recommended), join
together both wires of the second twisted pair and connect them to the
LAN REF terminal at each MicroNet device (refer to the relevant
MicroNet data sheets for details). For the Xenta 555, connect the second
twisted pair to Pin 2 (G0).
Caution
•
Belden 9502 dual-twisted pair cable contains one black wire in
each twisted pair. It is essential to good communications that
these black wires are not crossed over between pairs.
Note
•
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
It is important to ensure that the polarity of the network connections is consistent throughout the system, that is, (–) is connected
to (–) and (+) is connected to (+).
77 (134)
6 TAC Xenta 555
6.5.2
TAC Xenta 500/700/911/913, Product Manual
Connecting to a MicroNet ARCNET network (MN MI used)
To connect to a MicroNet ARCNET network (MN MI used)
6.5.3
1
Connect adapter 3-621-3056-0 to the MN MI’s serial COM port
2
Connect cable 3-781-0118-0 to the above adaptor and then to the
Xenta 555’s RS232 A port
3
If connecting an ARCNET network, connect the LAN twisted pair
cable to the MN MI (MN50-MI-ARC) terminals as detailed in
MicroNet data sheet DS 10.217A.
4
If connecting an NCP network, connect the LAN twisted pair
cable to the MN MI (MN50-MI-NCP) terminals as detailed in
MicroNet data sheet DS 10.217A.
Connecting to a Satchnet network (MIU not used)
This method applies to Satchnet networks. The Xenta 555 connects to
the MicroNet controller network through terminals 5 and 6 of its upper
terminal block connector.
Satchnet Controller
LAN Connection
(RS485)
5 VA
1
2
G
G0 C1 C2
LON
3
24 VAC
Rx Tx
Run
Rx Tx
4
5 6 7 8 9 10
RX/ RX/
RX+ RX- G0
TX+ TXFail-safe
LON RS485 A
Rx / Tx
Fig. 6.10: RS485 LAN connections (Satchnet network)
To connect the TAC Xenta 555 to a MicroNet controller
LAN
1
Connect the positive (+) line to position 5.
2
Connect the negative (–) line to position 6.
Join the shield wires together at each device on the controller LAN, and
connect to a good earth ground at one location only. Ensure that shield
wire continuity is maintained across the controller LAN.
Note
•
78 (134)
It is important to ensure that the polarity of the network connections is consistent throughout the system, that is, (–) is connected
to (–) and (+) is connected to (+).
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
7
7 TAC Xenta 701/711/721
TAC Xenta 701/711/721
A Xenta 701/711/721 can be configured as a control system for LonWorks networks that communicate over a TCP/IP network. By using a
standard web browser, the operator can easily view and control the
devices in the LonWorks network via a TCP/IP network.
Note
•
7.1
Only the Xenta 711 is designed to be used by an operator for
day-to-day operation. The Xenta 701/721 can be accessed for
engineering purposes using a web browser.
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal via an
RS-232 connection to initialize and configure the Xenta 701/711/721.
For more information on how to initialize and configure the
Xenta 701/711/721, see Section 2.2, “Configuring the
TAC Xenta 500/700/911/913”, on page 25.
RS-232
Windows HyperTerminal
Fig. 7.1: Windows HyperTerminal communicating with a TAC Xenta
701/711/721 using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
79 (134)
7 TAC Xenta 701/711/721
7.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 7.2: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
80 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
7.2
7 TAC Xenta 701/711/721
Engineering Phase
The technician uses XBuilder to program the Xenta 701/711/721 via the
TCP/IP network. To access the Xenta 701/711/721 web site a standard
web browser is used.
TCP/IP
TAC XBuilder
Web browser
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 7.3: TAC XBuilder or a web browser communicating with a TAC
Xenta 701/711/721 using IP during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
81 (134)
7 TAC Xenta 701/711/721
7.2.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
Fig. 7.4: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 701/711/721 does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
82 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
7.3
7 TAC Xenta 701/711/721
Operating Phase
The operator uses a standard web browser to view and control the
devices in the LonWorks network, either via a directly connected or
using a dialed-up connection.
7.3.1
Directly Connected
The operator uses a standard web browser to view and control the
devices in the LonWorks network, directly connected via the TCP/IP
network.
TCP/IP
Web browser
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 7.5: A web browser communicating with a TAC Xenta using TCP/IP
during the operating phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
83 (134)
7 TAC Xenta 701/711/721
7.3.2
TAC Xenta 500/700/911/913, Product Manual
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
Fig. 7.6: Connections during the operating phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
1. TAC Xenta 701/711/721 does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
84 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
7.3.3
7 TAC Xenta 701/711/721
Dialed-Up
The operator uses a standard web browser to view and control the
devices in the LonWorks network, using a dialed-up connection via
RS-232 with the possibility to use a TCP/IP network.
RS232
Web browser
RS232
Fig. 7.7: Dialed-up connection.
ISP Modem
TCP/IP
Web browser
RS232
Fig. 7.8: Dialed-up connection via TCP/IP.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
85 (134)
7 TAC Xenta 701/711/721
7.3.4
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309160.
3
1
2
Modem
Fig. 7.9: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
1
DB25/Male-to-RJ45/Female adapter connecting the modem serial
port to the cable directly below.
1
3-621-3052-01
2
RJ-45-to-RJ-45 rollover cable connecting the adapter to the Xenta
serial port RS-232 A.
1
3-781-0118-01
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com
1
N/A
1. Part of cable kit no. 007309160.
86 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
7.4
7 TAC Xenta 701/711/721
Port Usage
If a Xenta 701/711/721 and the IP network are located on opposite sides
of one or several firewalls, these firewalls must be configured to allow
traffic through. The Xenta 701/711/721 uses the following ports:
Table 7.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 701/711/721 operating as
an LTA port.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
UDP
5069
Remote
Yes
Notification on Change (UDP).
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
No
87 (134)
7 TAC Xenta 701/711/721
88 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8
8 TAC Xenta 731
TAC Xenta 731
A Xenta 731 can be configured as a web-based presentation system for
LonWorks networks. Using a standard web browser, the operator can
easily view and control the devices in the LonWorks network via a
TCP/IP network.
8.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal via an
RS-232 connection to initialize and configure the Xenta 731. For more
information on how to initialize and configure the Xenta 731,
see Section 2.2, “Configuring the TAC Xenta 500/700/911/913”, on
page 25.
RS-232
Windows HyperTerminal
Fig. 8.1: Windows HyperTerminal communicating with a TAC Xenta 731
using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
89 (134)
8 TAC Xenta 731
8.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 8.2: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
90 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8.2
8 TAC Xenta 731
Engineering Phase
The technician uses XBuilder to program the Xenta 731 via the TCP/IP
network. To access the Xenta 731 web site a standard web browser is
used.
TCP/IP
TAC XBuilder
Web browser
I/NET
MicroNet
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 8.3: TAC XBuilder or a web browser communicating with a TAC
Xenta 731 using IP during the engineering phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
91 (134)
8 TAC Xenta 731
8.2.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
6
Fig. 8.4: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta RS485 A port pins 5–6 (5–8) to the
Modbus device. For more information on cable requirements, see
the Modbus equipment documentation.
1
N/A
or
cable connecting the Xenta serial port RS-485 A pins 5-6 to a
MicroNet device. For more information on MicroNet communication, see Chapter 6, “TAC Xenta 555”, on page 67.
92 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Pos.
Description
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
6
I/NET Controller LAN cable connected to serial port RS-485 C. For
more information on I/NET communication, see Chapter 5, “TAC
Xenta 527”, on page 53.
8 TAC Xenta 731
Qty
1
Part No.
N/A
1. TAC Xenta 731 does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
93 (134)
8 TAC Xenta 731
8.3
TAC Xenta 500/700/911/913, Product Manual
Operating Phase
The operator uses a standard web browser to view and control the
devices in the LonWorks network, either via a directly connected or
using a dialed-up connection.
8.3.1
Directly Connected
The operator uses a standard web browser to view and control the
devices in the LonWorks network, directly connected via the TCP/IP
network.
TCP/IP
Web browser
I/NET
MicroNet
LonTalk
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
Fig. 8.5: A web browser communicating with a TAC Xenta 731 using
TCP/IP during the operating phase.
94 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8.3.2
8 TAC Xenta 731
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
6
Fig. 8.6: Connections during the operating phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta RS485 A port pins 5–6 (5–8) to the
Modbus device. For more information on cable requirements, see
the Modbus equipment documentation.
1
N/A
1
N/A
or
cable connecting the Xenta serial port RS-485 A pins 5-6 to a
MicroNet device. For more information on MicroNet communication, see Chapter 6, “TAC Xenta 555”, on page 67.
52
Cable connecting the Xenta port RS-232 A to the Modbus device.
For more information on cable requirements, see the Modbus equipment documentation.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
95 (134)
8 TAC Xenta 731
Pos.
6
TAC Xenta 500/700/911/913, Product Manual
Description
Qty
Part No.
I/NET Controller LAN cable connected to serial port RS-485 C. For
more information on I/NET communication, see Chapter 5, “TAC
Xenta 527”, on page 53.
1. TAC Xenta 731 does not support Ethernet MDI, a crossover cable may be required.
2. Only one may be connected.
96 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8.3.3
8 TAC Xenta 731
Dialed-Up
The operator uses a standard web browser to view and control the
devices in the LonWorks network, using a dialed-up connection via
RS-232 with the possibility to use a TCP/IP network.
RS232
Web browser
RS232
Fig. 8.7: Dialed-up connection.
ISP Modem
TCP/IP
Web browser
RS232
Fig. 8.8: Dialed-up connection via TCP/IP.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
97 (134)
8 TAC Xenta 731
8.3.4
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309160.
3
1
4
2
5
Modem
6
Fig. 8.9: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
1
DB25/Male-to-RJ45/Female adapter connecting the modem serial
port to the cable directly below.
1
3-621-3052-01
22
RJ-45-to-RJ-45 rollover cable connecting the adapter to the Xenta
serial port RS-232 A.
1
3-781-0118-01
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com
1
N/A
42
Cable connecting the Xenta port pins 5–6 (5–8) to the Modbus
device. For more information on cable requirements, see the Modbus equipment documentation.
1
N/A
or
cable connecting the Xenta serial port RS-485 A pins 5-6 to a
MicroNet device. For more information on MicroNet communication, see Chapter 6, “TAC Xenta 555”, on page 67.
98 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Pos.
Description
5
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Modbus device.
6
I/NET Controller LAN cable connected to serial port RS-485 C. For
more information on I/NET communication, see Chapter 5, “TAC
Xenta 527”, on page 53.
8 TAC Xenta 731
Qty
1
Part No.
N/A
1. Part of cable kit no. 0-073-0916-0.
2. Only one should be connected.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
99 (134)
8 TAC Xenta 731
8.4
TAC Xenta 500/700/911/913, Product Manual
Port Usage
If a Xenta 731 and the IP network are located on opposite sides of one
or several firewalls, these firewalls must be configured to allow traffic
through.
The Xenta 731 uses the following ports:
Table 8.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 731 operating as an LTA
port.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
100 (134)
No
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
8 TAC Xenta 731
Table 8.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
UDP
5069
Remote
Yes
Notification on Change (UDP).
I/NET
50069
Local
No
I/NET UDP/IP.
MicroNet
7001
Local
Yes
VisiSat Port (TCP)
Protocol
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Comments
101 (134)
8 TAC Xenta 731
102 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
9
9 Connecting the OP7 to Xenta 700
Connecting the OP7 to Xenta 700
The TAC OP7 is a small but powerful operator panel designed to be
used with all models of the TAC Xenta 700 series of controllers.
There are two mounting possibilities: put in a cabinet door using the
Remote mounting kit, or hung on any flat, vertical surface using the
Wall mounting kit. In both cases the OP7 is easily removed and can be
used as a hand-held terminal.
9.1
Connecting the OP7
The OP7 is connected to the Xenta 700 via an adapter, providing power
supply and communication interface.
Adapter
24 VAC
731
Transformer
Xenta 700
To OP7 or
Remote/Wall
mounting
CPU cable
Fig. 9.1: Transformer, OP7 Power adapter, and Xenta 700
9.2
Remote (cabinet door) mounting
Fix the Remote mounting kit (2) in a cabinet door cut-out. The optional
hinged cover (3) will give added protection from IP 54 to IP 65. The
Remote cable (4), supplied with the OP7, is used to connect the holder
to the Xenta 700 adapter.
.
3
2
1
116 (4.57)
105 (4.13)
4
To Xenta 700 adapter
Fig. 9.2: Remote mounting receptacle and cutout dimensions: mm (in.)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
103 (134)
9 Connecting the OP7 to Xenta 700
9.3
TAC Xenta 500/700/911/913, Product Manual
Wall mounting
Put the Wall mounting kit (2) on any flat, vertical surface and use it as
a convenient holder for the OP7. The Remote cable (4) and the RJ45
female/female adapter (5) are supplied with the OP7. An additional
remote cable (6) is required.
2
4
5
To Xenta 700
adapter
1
6
Fig. 9.3: Wall mounting holder
9.4
Handheld terminal
To use the OP7 as a handheld terminal you must have a cable (4 or 6)
and an RJ45 female/female adapter (5), to connect it to:
•
a Xenta 700 adapter (Fig. 9.1)
•
the remote (cabinet door) holder or
•
the wall mounted holder
5
1
4 or 6
To Xenta 700 adapter or
Remote/Wall mounting holder
Fig. 9.4: Connecting OP7 as a handheld terminal
104 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
10
10 TAC Xenta 911
TAC Xenta 911
Xenta 911 can be used as a LonTalk adapter between Vista and the LonWorks network, as an IP modem or as a serial gateway.
10.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal to initialize and configure the Xenta 911. For more information, see Section 2.2,
“Configuring the TAC Xenta 500/700/911/913”, on page 25.
10.1.1
Connections
Cables that can be ordered from Schneider ElectricSchneider ElectricSchneider Electric are ordered as cable kits. Below you find information
on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 10.1: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains a RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
105 (134)
10 TAC Xenta 911
10.2
TAC Xenta 500/700/911/913, Product Manual
Engineering Phase
If the Xenta 911 is used as IP modem it needs to be programmed. Use
an ordinary TCP/IP network connection to access and program the
Xenta 911. For more information on how to program the Xenta 911,
see Section 12.1, “Programming the TAC Xenta 911”, on page 119. If
the Xenta 911 is used as an LonTalk adapter it does not need to be programmed.
TCP/IP
Web browser
Fig. 10.2: A web browser communicating with a TAC Xenta 911 using IP
during the engineering phase.
10.2.1
Connections
Below you find information on which cables to use and how to connect
the cables.
1
2
TCP/IP
Fig. 10.3: Connections during the engineering phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
1. If directly connected: use a TP UTP/UTS CAT.6 RJ-45 crossed cable.
106 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
10.3
10 TAC Xenta 911
Operating Phase
In the operating phase the Xenta 911 acts as a LonTalk adapter or as an
IP modem.
10.3.1
LonTalk Adapter
Xenta 911 can be used as a LonTalk adapter between Vista and the LonWorks network.
LonTalk
Modbus
TCP/IP
Fig. 10.4: Vista communicating with a TAC Xenta 911 using TCP/IP
during the operating phase.
10.3.2
Connections
Below you find information on which cables to use and how to connect
the cables.
3
1
2
TCP/IP
Fig. 10.5: Connections during the operating phase.
Pos.
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
3
Cable connecting the Xenta port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
107 (134)
10 TAC Xenta 911
TAC Xenta 500/700/911/913, Product Manual
1. If directly connected: use a TP UTP/UTS CAT.6 RJ-45 crossed cable.
10.3.3
IP Modem
Xenta 911 can be used as an IP modem, working as a direct replacement
for a telephone modem with dial-up functionality over the computer
network. Dial-up may be initiated by Vista (slow-poll) or by the
Xenta 300/401.
TCP/IP
RS232
RS232
?
Fig. 10.6: Vista communicating with an unknown device using two TAC
Xenta 911s as IP modems using RS-232 and IP during the operating
phase.
10.3.4
Connections
1
3
2
3
4
5
TCP/IP
6
5
7
8
9
Cr 5
RxD 4
TxD 3
Fig. 10.7: Connections during the operating phase.
108 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Pos.
Description
10 TAC Xenta 911
Qty
Part No.
1
DB9/Female-to-DB25/Male adapter connecting the computer serial
port to the adapter directly below.
1
3-621-0424-01
2
DB25/Female-to-RJ45/Female adapter connecting the adapter
directly above to the cable directly below.
1
3-621-3054-01
3
RJ-45-to-RJ-45 rollover cable connecting the adapter directly above
to the Xenta serial port RS-232 A.
1
3-781-0118-01
4
TP UTP/STP CAT.6 RJ-45 cable connecting the Xenta 10Base-T
port to the TCP/IP network.
1
N/A
5
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
62
RJ-45-to-RJ-45 TAC Xenta-to-Xenta cable connecting the Xenta
serial port RS-232 A to the Xenta serial port RS-232 A on the Xenta
901/401/301/302/281/282/283.
1
3-621-0129-03
72
RJ-45-to-RJ-45 rollover cable connecting the Xenta serial port
RS-232 A to the adapter directly below.
1
3-781-0118-04
82
RJ45/Female-to-DB25/Female adapter connecting the cable directly
above and ADU-L/KE-2/6505/5702/5708/PLB/Danfoss
GW-M/Danfoss Danduc.5
1
3-621-3054-04
92
RJ-45-to-RJ-45 rollover cable connecting the Xenta serial port
RS-232 A to the target device.6
1
N/A
1. Part of cable kit no. 007309170.
2. Configurations 6, 7+8, 9 cannot be used at the same time.
3. Part of cable kit no. 007309180.
4. Part of cable kit no. 007309190.
5. The modem connection cable for the selected unit is also required.
6. If a Xenta 2000 is used the target device is the serial signal amplifier, for example, RAD type PSA.
The IP modem interprets the AT (modem) commands from the RS-232
connections and transmits data between the IP modems across the IP
network. Normally, the IP address is used during dial-up, but a phone
number may also be used. This phone number will be translated into an
IP address in the Xenta 911.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
109 (134)
10 TAC Xenta 911
10.3.5
TAC Xenta 500/700/911/913, Product Manual
Serial Gateway
The Xenta 911 can operate as a serial gateway, allowing computer software to use the Xenta 911 serial port RS-232 A as a communication port
(COM port).
1
2
3
Cr 5
RxD 4
TxD 3
TCP/IP
Fig. 10.8: Connections during the operating phase.
Pos.
Description
Qty
Part No.
1
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
2
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
RJ-45-to-RJ-45 rollover cable connecting the Xenta serial port
RS-232 A to the target device.
1
N/A
31
1. If directly connected: use a TP UTP/UTS CAT.6 RJ-45 crossed cable.
110 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
10.4
10 TAC Xenta 911
Port Usage
If a Xenta 911 and the IP network are located on opposite sides of one
or several firewalls, these firewalls must be configured to allow traffic
through.
The Xenta 911 uses the following ports:
Table 10.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
LTA IP
1068
Local/
Remote
Yes
Protocol used between Vista Server
and Xenta 911 operating as an LTA
port.
IP Modem
1066,
1067
Local/
Remote
Yes
Protocol used between two
Xenta 911s operating as IP modems.
Protocol
Comments
With the exception of FTP access, these port numbers are adjustable in
the web configuration for the Xenta 911. If adjustment to the port number is made, it is necessary to reconfigure all communicating units.
HTTP and FTP access is only used for configuring and servicing the
units.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
111 (134)
10 TAC Xenta 911
112 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
11
11 TAC Xenta 913
TAC Xenta 913
A Xenta 913 can be configured as a web-based presentation system for
LonWorks networks. Using a standard web browser, the operator can
easily view and control the devices in the LonWorks network via a
TCP/IP network.
For more information about the available protocols for the Xenta 913,
see the TAC Xenta Server – Gateway, Technical Manual.
11.1
Configuration Phase
The technician uses Microsoft Windows and HyperTerminal to initialize and configure the Xenta 913. For more information, see Section 2.2,
“Configuring the TAC Xenta 500/700/911/913”, on page 25.
RS-232
Windows HyperTerminal
Fig. 11.1: Windows HyperTerminal communicating with a TAC Xenta
913 using RS-232 during the configuration phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
113 (134)
11 TAC Xenta 913
11.1.1
TAC Xenta 500/700/911/913, Product Manual
Connections
Cables that can be ordered from Schneider Electric are ordered as cable
kits. Below you find information on which kit to order and how to connect the cables.
Required Cable Kit
Part. No. 007309200.
1
2
Fig. 11.2: Connections during the configuration phase.
Pos.
Description
Qty
Part No.
1
DB9/Female-to-RJ45/Female adapter connecting the computer
serial port to the cable directly below.
1
3-621-3056-01
2
Serial cable (null modem cable) connecting adapter directly above
to the Xenta serial port RS-232 B.
1
3-781-0128-01
1. Part of cable kit no. 007309200. The cable kit also contains an RJ-45-to-RJ-45 rollover cable
(3-781-0118-0). This cable is not needed during the configuration phase.
114 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
11.2
11 TAC Xenta 913
Programming and Operating Phase
The technician uses XBuilder to program the Xenta 913. The programmer uses an ordinary TCP/IP network connection to access the
Xenta 511 unit.
Modbus Master, serial
Modbus Slave, serial
Modbus TCP Client
BACnet IP Client
BACnet MS/TP Master
BACnet PTP Master
M-Bus Metering
C-Bus Lighting Control
LonTalk
I/NET
TCP/IP
TAC XBuilder
Web browser
Fig. 11.3: TAC XBuilder or a web browser communicating with a TAC
Xenta 913 using IP during the programming and operating phase.
11.2.1
Connections
Below you find information on which cables to use and how to connect
the cables
3
1
4
2
TCP/IP
5
TxD 3
RxD 4
Cr 5
6
Fig. 11.4: Connections during the programming and operating phase.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
115 (134)
11 TAC Xenta 913
Pos.
TAC Xenta 500/700/911/913, Product Manual
Description
Qty
Part No.
11
TP UTP/STP CAT.6 RJ-45 cable connecting the computer network
port to the TCP/IP network.
1
N/A
21
TP UTP/STP CAT.6 RJ-45 cable connecting the TCP/IP network to
the Xenta 10Base-T port.
1
N/A
Cable connecting the Xenta RS232 A port pins 3–4 to the LonWorks device.
For more information on cables approved by Echelon,
see www.echelon.com.
1
N/A
42
Cable connecting the Xenta RS485 A port pins 5–6 (5–8) to the
device (Modbus, BACnet).
For more information on cable requirements, see the device documentation.
1
N/A
52
Cable connecting the Xenta port RS232 A to the device.
For more information on cable requirements, see the device documentation.
1
N/A
63
I/NET Controller LAN cable connected to serial port RS485 C.
1
3
Use either of the following wire types:
•
22 AWG (0.324 mm2) shielded, twisted pair, 5000' (1500 m)
maximum per segment, 150 Ω impedance, 9 pF/ft. conductor-to-conductor, 14 pF/ft. conductor-to-shield.
Belden 9184
24 AWG (0.206 mm2) shielded, twisted pair, 4000' (1200 m)
maximum per segment, 120 Ω impedance, 13 pF/ft. conductor-to-conductor, 23 pF/ft. conductor-to-shield.
Belden 9841
or
•
1. TAC Xenta 913 does not support Ethernet MDI, a crossover cable may be required.
2. Both 4 and 5 cannot be used for communication at the same time.
3. Maintain proper polarity when connecting this cable to each device on the controller LAN.
116 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
11.3
11 TAC Xenta 913
Port Usage
If a Xenta 913 and the IP network are located on opposite sides of one
or several firewalls, the firewalls must be configured to allow traffic
through.
The Xenta 913 uses the following ports:
Table 11.1: Port Usage
IP Ports
Local/
Remote
Xenta
Port
Configurable
FTP
20, 21
Local
No
File transfer protocol.
HTTP
80
Local
Yes
HTTP traffic.
HTTPS
443
Local
Yes
HTTP traffic over SSL, secure socket
layer.
DHCP Server
67
Remote
No
DHCP Client
68
Local
No
DNS
53
Remote
No
VarTransfer-http
80
Local/
Remote
Yes
VarTransfer-TCP
1233
Protocol
Comments
Dynamic data protocol, used by
applets to communicate on-line data.
The port number is the same as the
http port.
Dynamic data protocol, used between
Xenta 500/700/913s that exchange
variable data.
VarTransfer-UDP
9088/9089
Local/
Remote
SNMP
161
Local
No
Network management protocol
(UDP).
SNMP Trap
162
Remote
No
Network management protocol
(UDP).
SMTP
25
Remote
No
Mail protocol.
NTP, SNTP
123
Local/
Remote
No
Time synchronization (UDP).
I/NET
50069
Local
No
I/NET UDP/IP.
Modbus TCP
Client
502
Remote
Yes
Modbus TCP client to a server or
router on a network.
BACnet IP Client
47808
Remote
Yes
BACnet IP client to a server on a
BACnet network.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
No
117 (134)
11 TAC Xenta 913
118 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
12
12 Engineering TAC Xenta 911
Engineering TAC Xenta 911
Xenta 911 can be used as a LonTalk adapter between Vista and the LonWorks network, as an IP modem or as a serial gateway.
12.1
Programming the TAC Xenta 911
If the Xenta 911 is used as an IP modem it needs to be programmed. Use
a web browser and an ordinary TCP/IP network connection to access
and program the Xenta 911. For more information on how to connect
the Xenta 911, see Section 10.2, “Engineering Phase”, on page 106.
To program the TAC Xenta 911
1
Log in as root to Xenta 911 (use a valid password).
The default web page in the Xenta 911 appears in the web browser.
2
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Click the large arrow button on the screen.
119 (134)
12 Engineering TAC Xenta 911
120 (134)
TAC Xenta 500/700/911/913, Product Manual
3
Click the button to the left of step 1.
4
Enter date and time.
5
Click Save Settings.
6
Click Regional Settings.
7
Select time zone, time and date format and summer/winter time
settings.
8
Click Save Settings.
9
Click the button to the right of “Go to Step 2: Select Device Type”
at the bottom of the browser.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
12 Engineering TAC Xenta 911
10 In the Device selection list, select the device the Xenta 911 will be
connected to.
Example: In a system with two IP modems communicating
between a TAC Vista Server and a Xenta 901, the IP modem on the
Vista side is set to device type TAC Vista and the IP modem on the
Xenta 901 side is set to device type TAC Xenta 901.
11 Click Confirm Selection.
12 Click the button to the right of “Go to Step 3 (Optional): Tuning
The Communication Parameters” at the bottom of the browser.
13 Make the appropriate settings. Normally, the default values should
be used. Adjust only after consulting the TAC Solution Team
when it is vital to optimize the communication
14 If changes has been made on the Tune the Communication
Parameters page, click Save Start-Up Settings.
15 Click the button to the right of “Go to Step 4 (Optional): Configuring Telephone Numbers” at the bottom of the browser.
If the target device or the presentation system used together with a
Xenta 911 cannot handle IP addresses but demands telephone numbers, you can configure your IP addresses to phone numbers. Vista
and the Xenta devices handles IP addresses and when they are used
you can skip this step.
16 If changes has been made on the Configure Telephone Numbers
page, click Save Settings.
17 Click the button to the right of “Home” at the bottom of the
browser.
Repeat the programming procedure for the other Xenta 911 IP modems.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
121 (134)
12 Engineering TAC Xenta 911
122 (134)
TAC Xenta 500/700/911/913, Product Manual
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
APPENDIX
A
Hardware
TAC Xenta 500/700/911/913, Product Manual
A Hardware
A
Hardware
A.1
Adapters
A.1.1
DB9/Female-to-RJ45/Female Adapter
DB9/Female
Modular jack RJ45/Female
View from inside
GND 5
9
DTR 4
8
TxD 3
7
RxD 2
DSR 6
DCD 1
1 DSR
2 DCD
3 DTR
4 GND
5 RxD
6 TxD
7 CTS
8 RTS
Fig. A.1: DB9/Female-to-RJ45/Female adapter.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
125 (134)
A Hardware
A.1.2
TAC Xenta 500/700/911/913, Product Manual
DB25/Female-RJ45/Female Adapter
DB25/Female
Modular jack RJ45/Female
View from inside
13
25
12
24
11
23
10
22
8 RI
9
21
DCD 8
DTR 20
GND 7
19
DSR 6
18
CTS 5
17
RTS 4
16
RxD 3
15
TxD 2
14
1
7 RTS
6 RxD
5 TxD
4 GND
3 DSR
2 DCD
1 DTR
Fig. A.2: DB25/Female-RJ45/Female adapter.
126 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
A.1.3
A Hardware
RJ45/Female-to-DB25/Male Adapter
DB25/Male
Modular jack RJ45/Female
View from inside
1
14
TxD 2
15
RxD 3
16
RTS 4
17
CTS 5
1 DSR
18
DSR 6
19
GND 7
DTR 20
DCD 8
21
9
22
10
23
11
24
12
25
13
2 DCD
3 DTR
4 GND
5 RxD
6 TxD
7 CTS
8 RTS
Fig. A.3: RJ45/Female-to-DB25/Male adapter.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
127 (134)
A Hardware
A.1.4
TAC Xenta 500/700/911/913, Product Manual
DB9/Female-to-DB25/Male Adapter
DB25/Male
DB9/Female
View from inside
1
14
TxD 2
15
RxD 3
1 DCD
16
6 DSR
17
7 RTS
18
8 CTS
RTS 4
2 RxD
CTS 5
3 TxD
DSR 6
19
GND 7
DTR 20
DCD 8
21
9
22
10
23
11
24
12
25
13
4 DTR
9 RI
5 GND
Fig. A.4: DB25/Male-to-DB9/Female adapter.
128 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
A Hardware
A.2
Cables
A.2.1
RJ45-to-RJ45 Rollover Cable
Wire 1
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Fig. A.5: RJ45-to-RJ45 rollover cable.
Emission Damper
10 cm
Fig. A.6: RJ45-to-RJ45 rollover cable with emission damper.
A.2.2
RJ45-to-RJ10 Cable
Wire 1
1
2
3
GND 4
TxD 5
RxD 6
7
8
1 TxD
2 RxD
3
4 GND
5
6
7
8
Fig. A.7: RJ45-to-RJ10 cable.
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
129 (134)
A Hardware
A.2.3
TAC Xenta 500/700/911/913, Product Manual
RJ-45-to-RJ-45 TAC Xenta-to-Xenta Cable
Wire 1
CTS/RI
RTS
RxD
TxD
GND
DSR
DCD
DTR
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
CTS/RI
RTS
RxD
TxD
GND
DSR
DCD
DTR
Fig. A.8: RJ-45-to-RJ-45 Rollover Cable.
130 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
TAC Xenta 500/700/911/913, Product Manual
Index
Numerics
10Base-T, Ethernet port 22
A
Index
P
password
temporary 35
port pins 21
port settings
HTTP 42
HTTPS 42
adapter 125
DB25/Female-RJ45/Female adapter 126
DB9/Female-to-DB25/Male adapter 128
DB9/Female-to-RJ45/Female adapter 125
OP7 to Xenta 700 103
RJ45 female/female adapter 104
RJ45/Female-to-DB25/Male adapter 127
RJ45-to-RJ10 cable 129
RJ45-to-RJ45 rollover cable 129
RJ-45-to-RJ-45 TAC Xenta-to-Xenta cable 130
real time clock, in TAC Xenta 17
RJ45/Female-to-DB25/Male adapter 127
RJ45-to-RJ10 cable 129
RJ45-to-RJ45 rollover cable 129
RJ-45-to-RJ-45 TAC Xenta-to-Xenta cable 130
root password, change 34
RS-232 A, serial port 21
RS-232 B, serial port 22
D
S
DB25/Female-RJ45/Female adapter 126
DB9/Female-to-DB25/Male adapter 128
DB9/Female-to-RJ45/Female adapter 125
Satchnet network 76
serial port RS-232 A 21
serial port RS-232 B 22
system program, upgrade 36
E
emission damper 129
Ethernet port 10Base-T 22
F
fail-safe state 23
H
handheld terminal (OP7) 104
L
LEDs on the TAC Xenta 23
M
MicroNet ARCNET network 76
MicroNet NCP network 76
mounting the TAC Xenta 17
O
OP7 connection 103
OP7 operator panel 103
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
R
T
TAC OP7 operator panel 103
TAC Xenta
access 32
communication interface 18
hardware 17
LEDs 23
mounting 17
port pins 21
power outage protection 17
real time clock 17
TAC Xenta 511
configuration phase 43
operating phase 47
port usage 51
TAC Xenta 527
configuration phase 53
connect to an I/NET controller LAN 64
direct connection to I/NET 65
engineering phase 55
operating phase 58
port usage 63
131 (134)
Index
TAC Xenta 500/700/911/913, Product Manual
TAC Xenta 555
configuration phase 67
connect to a MicroNet controller LAN 76
engineering phase 69
operating phase 73
port usage 75
TAC Xenta 700 series
connecting the OP7 103
TAC Xenta 701
configuration phase 79
engineering phase 81
operating phase 83
port usage 87
TAC Xenta 711
configuration phase 79
engineering phase 81
operating phase 83
port usage 87
TAC Xenta 721
configuration phase 79
engineering phase 81
operating phase 83
port usage 87
TAC Xenta 731
configuration phase 89
engineering phase 91
operating phase 94
port usage 100
TAC Xenta 911
configuration phase 105
engineering phase 106
operating phase 107
port usage 111
programming 119
TAC Xenta 913
configuration phase 113
operating phase 115
port usage 117
programming phase 115
temporary login ID 35
U
upgrade system program 36
W
Windows HyperTerminal, configure 26
132 (134)
Schneider Electric Buildings AB, Feb 2011
04-00071-04-en
Copyright © 2011, Schneider Electric Buildings AB
All brand names, trademarks and registered trademarks are
the property of their respective owners. Information contained within this document is subject to changewithout notice. All rights reserved.
04-00071-04-en
For more information visit
www.schneider-electric.com/buildings
Last Manual Page
Related documents
Download
Study collections