TBS. Surge protection systems/Basic line protection

advertisement
VBS
TBS
KTS
TBS. Surge protection systems
Order information and technical data
Basic line protection
Selection guide for network system TN-C-S
Selection guide for network system TN-S
Selection guide for network system TT
Lightning arresters
Coordinated LighningControllers
VG and SA series system solutions
Decoupling inductance
Lightning/surge arresters
Surge arresters
Signalling device for lightning and surge arresters
Surge arrester for photovoltaic installations
ISOLAB monitoring system
Peak Current Sensor PCS checking system
BSS
LFS
UFS
TN-C-S system
Domestic connection box
F1
L1
Line length
Main distribution
board
L1-4
Circuit distribution unit
e. g. sub-distribution board
Line length
Precision mains
protection
F2 (RCD)
L2
L3
PEN
F3
F4
B1)
C1)
D1)
Main EBB
1)
Local EBB
Requirement class to DIN VDE 0675 Part 6 (A1/A2).
500 A
63 A
125 A
EP 220-D
Order No. 5099 90 0
3 x MC 50-B VDE
Order No. 5096 84 7
4 x LC 63
Order No. 5096 97 0
See selection list, pages 14 and 15
V 20-C/3+NPE
Order No. 5095 64 6
KNS-D
Order No. 5092 50 7
160 A
CNS 3-D
Order No. 5092 70 1
VF 230-AC
Order No. 5097 64 9
V 25-B+C/3
Order No. 5097 00 2
alternative protection-set pages 24 and 25
16
class C, medium protection) must be installed in the
individual sub-distribution boards. Separate fuses before the arrester are only necessary if the ratings of
the upstream fuses (e. g. incoming supply fuses) are
higher than the values required for the surge protection. The relevant details can be taken from the technical data on the product pages.
TBS_GB_V0_15072002
In the TN-C-S mains supply system triple-pole lightning arresters of requirement class B (broad-based
protection) are used. The arresters are connected in
parallel with the incoming supply lines (L1, L2, L3),
which are connected via the arresters to the PEN.
If multi-level surge protection is required, an arrester
of type V 20-C/3+NPE (arrester of requirement
Please always state the order number when ordering.
TN-S system
Domestic connection box
L1
Line length
Main distribution
board
F1
L1-4
Circuit distribution unit
e. g. sub-distribution board
Line length
F2 (RCD)
Precision mains
protection
L2
L3
N
PE
F3
F4
B1)
C1)
D1)
Main EBB
1)
Local EBB
Requirement class to DIN VDE 0675 Part 6 (A1/A2).
63 A
500 A
125 A
EP 220-D
Order No. 5099 90 0
3 x MC 50-B VDE
Order No. 5096 84 7
1 x MC 125-B/NPE
VDE Order No. 5096 86 3
4 x LC 63
Order No. 5096 97 0
V 20-C/3+NPE
Order No. 5095 64 6
KNS-D
Order No. 5092 50 7
See selection list, pages 14 and 15
160 A
CNS 3-D
Order No. 5092 70 1
VF 230-AC
Order No. 5097 64 9
V 25-B+C/3+NPE
Order No. 5097 40 1
TBS_GB_V0_15072002
alternative protection-set pages 24 and 25
In the TN-S mains supply system, lightning arresters
of requirement class B (broad-based protection) are
used in the 3+1 circuit. In the 3+1 circuit, the incoming supply lines are connected via arresters to the
neutral line. The neutral line is connected to the protective earth (PE) line via a sum spark gap. This prevents voltages reaching the protective conductor
due to the insulation problems that may occur with
leakage currents.
Please always state the order number when ordering.
If multi-level surge protection is required, an arrester
of type V 20-C/3+NPE (arrester of requirement class
C, medium protection) must be installed in the individual sub-distribution boards. Separate fuses before the
arrester are only necessary if the ratings of the upstream fuses (e. g. incoming supply fuses) are higher
than the values required for the surge protection.
The relevant details can be taken from the technical
data on the product pages.
17
TT system
Domestic connection box
L1
Line length
Main distribution
board
F1
L1-4
Circuit distribution unit
e. g. sub-distribution board
Line length
F2 (RCD)
Precision mains
protection
L2
L3
N
F3
F4
B1)
C1)
D1)
Main EBB
1)
Local EBB
Requirement class to DIN VDE 0675 Part 6 (A1/A2).
63 A
500 A
125 A
EP 220-D
Order No. 5099 90 0
3 x MC 50-B VDE
Order No. 5096 84 7
1 x MC 125-B/NPE
VDE Order No. 5096 86 3
See selection list, pages 14 and 15
4 x LC 63
Order No. 5096 97 0
V 20-C/3+NPE
Order No. 5095 64 6
KNS-D
Order No. 5092 50 7
160 A
CNS 3-D
Order No. 5092 70 1
VF 230-AC
Order No. 5097 64 9
V 25-B+C/3+NPE
Order No. 5097 40 1
alternative protection-set pages 24 and 25
18
of type V 20-C/3+NPE (arrester of requirement class
C, medium protection) must be installed in the individual sub-distribution boards. Separate fuses before the
arrester are only necessary if the ratings of the upstream fuses (e. g. incoming supply fuses) are higher
than the values required for the surge protection.
The relevant details can be taken from the technical
data on the product pages.
TBS_GB_V0_15072002
In TN systems, lightning arresters of requirement
class B (broad-based protection) are used in the 3+1
circuit. In the 3+1 circuit, the incoming supply lines
are connected via arresters to the neutral line. The
neutral line is connected to the protective earth (PE)
line via a sum spark gap. This prevents voltages
reaching the protective conductor due to the insulation problems that may occur with leakage currents.
If multi-level surge protection is required, an arrester
Please always state the order number when ordering.
Basic line
protection
LPZ 0 → 1
Lightning arrester LightningController MC 50-B VDE
LightningController MC 50-B VDE is a plug-in multiple
spark gap. The device consists of nine partial spark
gaps, formed by ten heavy-duty carbon discs. The
precisely defined spacing of the spark gaps is safely
ensured by highly heat-resistant Teflon discs. Blade
contacts of pressure die-cast zinc, which are screwed
to each other, clamp the spark gap together with
accurate positioning. Eight of the nine spark gaps are
capacitively controlled and thus ensure a precisely
defined operating surge voltage of ≤ 2 kV.
The lightning arrester conforms to requirement class B
to DIN VDE 0675 Part 6 (Draft 11.89) A1, A2 and
class I to IEC 61643-1 (02.98). The device is
designed to be used between interface 0 to 1 in
accordance with the lightning protection zone concept of IEC 61312-1.
In a lightning protection installation in a building,
LightningController MC 50-B VDE provides lightning
protection potential equalisation with the power supply lines. The device has been successfully tested
with respect to the lightning current parameters
according to ENV 61024-1 and IEC 61024-1.
Test marks
20
Since the protective action of LightningController
MC 50-B VDE is ensured even with a direct lightning
strike on an overhead line, the device can also be
used in buildings supplied with power via an overhead line.
F
Block diagram of LightningController
Mounting
LightningController MC 50-B VDE is easy to install,
since the dimensions of the housing of the device
conform to the space-saving 17.5 mm grid module.
The lightning arrester is installed simply by snapfitting it to the top-hat rail. The LightningController has
two terminals each for the N and PE-conductors.
Note: since the spark gap of the device is enclosed,
no plasma arcs are produced outside the casing.
Other marks
TBS_GB_V0_15072002
Operation and fields of application
Please always state the order number when ordering.
Technical data
LightningController lightning arrester
Type
MC 50-B VDE
Nominal voltage
UN
230 V / 50-60 Hz
Maximum continuous operating voltage
Uc
255 V
Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2
to IEC 61643-1
B
class I
LPZ
0→1
Insulation resistance
Rins
>100 MΩ
Voltage protection level
Up
<2 kV
Response time
tA
<100 ns
Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95)
Peak current
Iimp
Charge
Q
Spec. energy
W/R
50 kA
25 As
0.63 MJ/Ω
Mains follow-up current quenching capacity of the arrester at Uc
Maximum asymmetric short-circuit current
12.5 kArms
25 kA
Ip
Max. series fuse (only required if there is no such fuse already in the network)
500 A gL/gG
Short-circuit strength (series fuse 500 A gL)
Maximum asymmetric short-circuit current
Ip
17.6 kArms
25 kA
Temperature range
ϑ
-40 °C to +85 °C
Air humidity
≤95%
IP Code
IP 20
10-50 / 0-25 / 10-35 mm2
AWG 8-2
Connection cross-section rigid/flexible/stranded
Tightening torque (MA) at least 4 Nm
Mounting
Snap-fitting on 35 mm
top-hat rail to DIN EN 50022
Subject to technical alterations
Ordering data
TBS_GB_V0_15072002
MC 50-B VDE
Complete1)
MC 50-B VDE/O
Upper part
MC 50-B VDE/U
Base
1) Complete = upper part and base
Order no.
35
49.5
5096 84 7
5096 82 0
5096 83 9
100
Description
44.9
Type
Features at a glance
MC 50-B VDE
Advantages in use
Enclosed system, no plasma arcs outside
the casing
Can be installed in any standard commercial
distribution board enclosure
Safety-tested, VDE, ÖVE, KEMA KEUR, MEEI,
EZU test marks
Reliable arrester in all applications, tested by
several independent institutes
Low protection level
Decoupling inductances only needed where
the distance (line length) between class B and C
arresters is less than 5 metres
Plug-in upper part
Simple checking of the technical connection
condition (TAB) of the VDEW (see page 24)
Two connection possibilities on each side
Easy to install
High follow-up current quenching capacity
Can be used close to transformers
Connection duct at side
No busbars required
Please always state the order number when ordering.
21
Basic line
protection
LPZ 0 → 1
Lightning arrester LightningController MC 125-B/NPE
Operation and fields of application
L1
L2
L3
PE
N
LightningController MC 125-B/NPE was designed to
be used in TN-S, TT and IT systems as a sum current
spark gap between the neutral conductor (N) and the
protective earth conductor (PE). At the heart of the
device there are two partial spark gaps made up of
three carbon discs which can handle heavy loads.
The precisely defined spacing of the spark gaps is
ensured by highly heat-resistant Teflon discs.
The lightning arrester satisfies the preconditions of
requirement class B to DIN VDE 0675 Part 6 (Draft
11.89) A1, A2 and of Class I to IEC 61643-1 (02.98).
The device is designed to be used between interface
0 to 1 in accordance with the lightning protection zone
concept of IEC 61312-1.
In the lightning protection installation of a building or
where power is supplied via an overhead line, the
MC 125-B/NPE, combined with LightningController
MC 50-B VDE, provides lightning protection potential
equalisation.
Circuit for TN-S, TT and IT systems
Mounting
LightningController MC 125-B/NPE is easy to install,
since the dimensions of the housing of the device
conform to the space-saving 17.5 mm grid module.
The lightning arrester is installed simply by snapfitting it to the top-hat rail. The LightningController
has two terminals each for the N and PE conductors.
F
Block diagram of LightningController
22
Other marks
TBS_GB_V0_15072002
Test marks
Please always state the order number when ordering.
Technical data
LightningController lightning arrester
Type
MC 125-B/NPE
Nominal voltage
UN
230 V / 50-60 Hz
Maximum continuous operating voltage
Uc
255 V
Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2
to IEC 61643-1
B
class I
LPZ
0→1
Insulation resistance
Rins
>100 MΩ
Voltage protection level
Up
<2.5 kV
Response time
tA
<100 ns
Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95)
Peak current
Iimp
Charge
Q
Spec. energy
W/R
125 kA
62.5 As
3.9 MJ/Ω
Follow-up current quenching capacity at Uc
Ip
100 Arms
Temperature range
ϑ
-40 °C to +85 °C
Air humidity
≤95%
IP Code
IP 20
10-50 / 10-25 / 10-35 mm2
AWG 8-2
Connection cross-section rigid/flexible/stranded
Tightening torque (MA) at least 4 Nm
Mounting
Snap-fitting on 35 mm
top-hat rail to DIN EN 50022
Subject to technical alterations
Ordering data
Complete
Order no.
35
49.5
5096 86 3
TBS_GB_V0_15072002
44.8
MC 125-B/NPE
Description
100
Type
Features at a glance
MC 125-B/NPE
Advantages in use
Enclosed system, no plasma arcs outside
the casing
Can be installed in any standard commercial
distribution board enclosure
Safety-tested, VDE, ÖVE, KEMA KEUR, MEEI,
EZU test marks
Reliable arrester in all applications, tested by
several independent institutes
High lightning current capacity, 125 kA (10/350)
Safety in service
Two connection possibilities on each side
Easy to install
Connection duct at side
No busbars required
Please always state the order number when ordering.
23
Basic line
protection
LPZ 0 → 1
Lightning arrester Coordinated LightningControllers
MCD 50-B and MCD 125-B/NPE
Operation and fields of application
the surge arrester (requirement class C) with compact
TT and TN-S systems can be omitted.
Coordinated LightningControllers MCD 50-B and MCD
125-B/NPE are lightning arresters of requirement class
B to DIN VDE 0675 Part 6 (Draft 11.89) A1, A2, and
Class I to IEC 61643-1 (08.98). In combination with
surge arresters connected directly after them, they
ensure coordinated operation. No additional decoupling components are needed. The fundamental advantages of the innovative multi-carbon technology of
OBO LightningControllers are fully preserved.
Mounting
The low protection level (Up ≤ 1.3 kV) makes it unnecessary to install decoupling inductances or to provide
additional lengths of conductor between lightning
arresters (requirement class B) and surge arresters
(requirement class C). The result is up to 45 percent
space saving on installation. And this proves to be a
particular advantage, especially with compact EMC
concepts. In addition, the separate NPE spark gap at
Coordinated LightningControllers are suitable for
snap-fitting to standard commercial 35 mm top-hat
rails to DIN EN 50022 and conform to the
space-saving 17.5 mm grid module. At each connection point there are two possibilities for Lx and N/PE.
Note: Since the arrester elements of the devices are
enclosed, no plasma arcs are produced outside the
casing.
TN-C-S networks
L1
L2
L3
PEN
F
Preferred fields of application for the new Coordinated
LightningControllers are compact surge protection
concepts in separate housings and the installation of
arresters of requirement classes B and C in a distribution board. A typical application: compact mobile
radio transmitters.
TN-S networks
Decoupling distance no
longer necessary
MCD 50-B
F
V 20-C
TT network systems
Decoupling distance no
longer necessary
F
L1
L2
L3
N
L1
L2
L3
N
PEN
MCD 50-B
V 20-C
V 20-C
MCD 50-B
MCD 125-B/NPE
MCD 125-B/NPE
EBB
Decoupling distance no
longer necessary
EBB
EBB
24
TBS_GB_V0_15072002
Other marks
Please always state the order number when ordering.
Technical data
Coordinated LightningController
Type
Nominal voltage
Maximum continuous operating voltage
Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2
to IEC 61643-1
MCD 50-B
MCD 125-B/NPE
230 V / 50-60 Hz
255 V
coordinated B
NPE spark gap
coordinated class I
UN
Uc
LPZ
Insulation resistance
Rins
Voltage protection level
Up
Response time
tA
Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95)
Peak current
Iimp
Charge
Q
Spec. energy
W/R
Mains follow-up current quenching capacity of the arrester at Uc
Maximum asymmetric short-circuit current
Ip
50 kA
25 As
0.63 MJ / Ω
12.5 kArms
25 kA
125 kA
62.5 As
3.9 MJ / Ω
100 Arms
Max. series fuse (only required if there is no such fuse already in the network)
Short-circuit strength (series fuse 500 A gL)
Maximum asymmetric short-circuit current
Ip
500 A gL/gG
17.6 kArms
25 kA
-
Temperature range
Connection cross-section rigid/flexible/stranded
Tightening torque (MA) at least 4 Nm
0→1
100 MΩ
≤1.3 kV
<100 ns
-
-40 °C to +85 °C
10-50 / 10-25 / 10-35 mm2
AWG 8-2
ϑ
Subject to technical alterations
Ordering data
Complete
Upper part
Base
Complete
Ord. no.
35
49.5
5096 84 9
5096 82 2
5096 83 9
5096 86 5
100
MCD 50-B
MCD 50-B/0
MC 50-B/U
MCD 125-B/NPE
Description
44.9
Type
PS... series: Protection Set: Pre-assembled, ready-to-connect combination of lightning arrester (requirement
class B) type MCD and surge arresters (requirement class C) type V 20-C
Description
PS4-B+C/TT+TNS
4-pole for TT + TN-S1)
PS4-B+C/TT+TNS-FS 4-pole for TT + TN-S1) w. FS
PS3-B+C/TNC
3-pole for TN-C1)
1) network systems
FS = remote signalling
Ord. no.
5089 60 7
5089 61 1
5089 60 3
157,5
100
Type
Dimension drawing PS3-B+C/TNC
TBS_GB_V0_15072002
Features at a glance
Coordinated LightningControllers
Advantages in use
Low protection level (Up <1.3 kV)
Additional decoupling inductances or decoupling
distance between arresters of requirement class B
and C no longer needed
Compact EMC concepts
Up to 45% space saving, installation saving
High arrester availability
No sensitive trigger electronics inside the arrester
In compact TT or TN-S network systems, an additional NPE sum spark gap at surge arresters of requirement class C is no longer necessary
Cost and space savings
Proven carbon technology as in the
LightningController
All LightningController advantages (page 21/22 and
page 23/24) are retained without restriction
Please always state the order number when ordering.
25
Surge protection devices of requirement class B in
main power supply systems (upstream of the meter)
If a lightning arrester of requirement class B is to be
installed, it must be installed in accordance with the
lightning protection zone concept to DIN VDE 0185
Part 103 in the region of lightning protection zone 0 to
1. In most cases the arrester is installed where the
power lines enter the building.
If the meter is not located directly at lightning protection zone 0 to 1, it may be necessary to install lightning arresters of requirement class B in the unmetered
region.
4.
5.
6.
Preconditions
Several points must be considered when choosing
and installing arresters in the unmetered region.
The VDEW has published guidelines for the use of
surge protection devices of requirement class B in
main power supply systems (01/98).
1. Surge protection devices of requirement class B
to DIN VDE 0675 Part 6 (A1, A2) are used. They
are chosen, and their parameters are set up, in
accordance with DIN VDE 0100-534 (A1).
2. It is essential to ensure that the surge protection
device is permanently isolated from the mains in
the event of an internal short-circuit.
3. The ability of the surge protection device to carry
lightning current must conform to the regulations
26
7.
8.
in force where it is installed, in accordance with
DIN VDE 0185 Part 100. If the ability to carry lightning current is not known, it must be chosen to
suit lightning protection class I to DIN VDE
0100-534.
Only surge protection devices that are designed
as a spark gap are used. It is not permissible to
connect varistors in parallel.
The manufacturer guarantees the short-circuit
strength of the surge protection devices in accordance with TAB Section 7.2.
Voltage surge protection devices of requirement
class B must always be installed in combination
with the correctly chosen current surge protection
devices, approved by the manufacturer for this
purpose – especially housings with protection IP
54 with protective insulation.
It must be possible to lead-seal the
protectively-insulated housings of surge protection
devices in accordance with the “lead-sealing requirements” issued by the VDEW.
The surge protection devices must be checked at
least every four years to ensure that they are in
perfect condition. Electricity supply companies
may demand relevant proof.
ÜSS_D_V0_30102000
Application
Please always state the order number when ordering.
Solution
Condition
Re 1: OBO LightningControllers MC 50-B/VDE and MC 125-B/NPE/VDE are lightning
arresters of requirement class B to DIN VDE 0675 Part 6 (A1, A2) as well as class I to
IEC 61643-1 (02/98), and fulfil the conditions for use in the unmetered region.
Fulfils n
Re 2: Section 2 of the requirements is met by the fuses before the lightning arrester
(max. 500 A without separate upstream fuse).
Fulfils n
Re 3: Section 3 of the requirements is met by the 50 kA lightning current capacity of
OBO LightningController MC 50-B/VDE. Note that the maximum lightning current directed
into the building is 100 kA and that it is shared between the conductors that leave the
building.
Fulfils n
Re 4: The operation of OBO LightningControllers is based on the principle of multiple
spark gaps which conform to the requirements of Section 4.
Fulfils n
Re 5: It has been shown in several tests that a surge current withstand strength of 25 kA
is achieved by OBO LightningController MC 50-B/VDE, using the principle of multiple
spark gaps.
Fulfils n
Re 6 and 7: Since the spark gap of the OBO LightningController is enclosed,
no plasma arcs are produced outside the casing. The arrester can therefore be used in
any commercially available housing that meets the requirements of Sections 6 and 7.
Fulfils n
Re 8: The requirements of Section 8 for the testability of class B surge protection devices in
the VDEW guideline are comprehensively met by the use of a plug-in upper part.
Fulfils n
Result
MC 50-B/VDE
Call our hotline for further information on the subject of “the use of class B surge protection devices in main
power supply systems (upstream of the meter)”.
Ordering data
VG... series: LightningController mounted in an IP 65 (sealable) housing of insulating material.
Type
Description
VG3-B/TNC
Triple-pole (MC 50-B/VDE) for TN-C1)
VG4-B/TNS+TT Four-pole (3+1-Var.) for TN-S, TT, IT1)
Order no.
5089 21 2
5089 20 0
ÜSS_D_V0_30102000
SA... series: LightningController mounted on adapter rail (adapter width 108 mm) for simple and professional
installation on 40 mm busbar systems (12 x 5 and 12 x 10).
Type
Description
Order no.
SA3-B/TNC
SA4-B/TNS+TT
Triple-pole (MC 50-B/VDE) for TN-C1)
Four-pole (3+1-Var.) for TN-S, TT, IT1)
5089 50 6
5089 51 4
Please always state the order number when ordering.
1)
Supply system
27
Basic line
protection
Decoupling inductance LightningCoordinator LC 63
Operation and fields of application
If there are several surge protection devices in a network, they may influence each other, and this may
mean that the parallel arresters must be coordinated
in terms of energy. The effect of this coordination is
that, in the event of a voltage surge due to lightning,
the lightning arrester (class B) responds reliably,
diverting the high-energy currents, so protecting the
other surge arrester(s) (class C or D) from overload.
This energy coordination is provided by LightningCoordinator type LC 63. This device establishes coordination between spark-gap lightning arresters (requirement class B) and varistor-based surge arresters
(requirement class C). The LightningCoordinator also
ensures the coordination of NPE arresters of different
requirement classes.
It is only necessary to install the LightningCoordinator
if the distance between lightning arrester and surge
arrester at the zone interfaces (total line length) is not
more than five meters. Where this is the case, the
natural inductances of the conduction path are not
sufficient, and a decoupling inductance must therefore be connected between the protection devices
which operate in different ways.
Typical fields of application are compact surge
protection installations in a separate housing, and installations with arresters of requirement classes B and
C inside a distribution board.
The good commutation properties of the LightningCoordinator are due to its optimally arranged inductance. The large cross-section of the strip-shaped coil
conductor gives a low DC resistance, resulting in only
a slight temperature rise in normal operation.
Input
Output
Block diagram of LC 63
Mounting
LightningCoordinator type LC 63 is designed for
snap-fitting to standard commercial 35 mm top-hat
rails. It is connected to integral terminals in the coil
housing.
28
TBS_GB_V0_15072002
Other marks
Please always state the order number when ordering.
Technical data
OBO LightningCoordinator
Type
LC 63
Nominal voltage
UN
< 500 V / 50-60 Hz
Rated load current
IL
63 A
Inductance (50-60 Hz)
Ln
5 µH ± 10%
DC resistance
Rcu
1 mΩ
Temperature rise
∆T
45 K (63 A)
ϑ
-40 °C to +85 °C
Max. required series fuse
63 A gL/gG
Temperature range
IP Code to IEC 60 529 / EN 60 529
IP 20
10-50 / 10-25 / 10-35 mm2
AWG 8-2
Connection cross-section rigid/flexible/stranded
Tightening torque (MA) at least 4 Nm
Mounting
Snap-fitting on 35 mm top-hat rail to
DIN EN 50022
Dimensions to DIN 43880
Height
Width
Depth
100 mm
35 mm
75 mm
Subject to technical alterations
Ordering data
Complete
Order no.
35
49.5
5096 97 0
TBS_GB_V0_15072002
44.8
LC 63
Description
100
Type
Features at a glance
LC 63
Advantages in use
Compact design in a 35 mm housing
Space-saving surge protection concept
Two connection options, for one or two outputs
Simple installation via several terminals
Rated current up to 63 A
Elements up to max. 63 A in the conductor branch
can be decoupled
Outstanding inductive characteristics with transient
and energy-rich lightning currents
Reliable operation of the lightning arrester guaranteed in the event of a fault
Separate channel in the lower side area
Further possibility for direct connection
Please always state the order number when ordering.
29
Basic line
protection
LPZ 0 → 2
Lightning/surge arresters CombiController
V 25-B+C, V 25-B+C/...+NPE
Lightning and surge arrester V 25-B+C ensures lightning protection potential equalisation in accordance
with VDE 0185, Part 1 and Part 100. The device is an
arrester of requirement Class B+C to DIN VDE 0675,
Part 6 (Draft 11.89) A1, A2. It ensures potential equalisation for the energy supply line in lightning protection installations for buildings. The arrester can also
be used in buildings that are supplied with power via
an overhead line, since direct or partial lightning currents may be expected there as well.
Version V 25-B+C/3+NPE (requirement Class B+C) is
a special surge arrester for TN-C-S, TN-S, TT and IT
systems. This device was developed for the new requirements of DIN VDE 0100, Part 534/A1, to allow
simple, safe installation of the devices.
High-performance arrester OBO V 25-B+C has a
special varistor circuit made up of powerful zinc
oxide varistors with a highly non-linear characteristic
(a>30). This design ensures maximum protection
Test marks
30
even with powerful surges. Even at a maximum load
Imax of 50 kA the protection level is below 1.5 kV. This
enables this type of device to withstand even partial
lightning currents from direct lightning strikes. In the
event of an overload, the built-in isolating device isolates the faulty arrester module from the network and
indicates this with a red field.
Because of the low residual voltage, OBO lightning
arrester V 25-B+C can also be used as a combined
arrester B and C.
Service location in accordance with VDS 2031.
Mounting
The OBO V 25-B+C can easily be installed in any distribution box or switchgear cabinet by snap-fitting to
any commercial 35 mm top-hat rail. The NPE arrester
element type C 25-B+C/NPE and the matching base
are designed so that they cannot be plugged in the
wrong way round (coding). This ensures correct installation of the upper parts of the arresters.
Other marks
TBS_GB_V0_15072002
Operation and fields of application
Please always state the order number when ordering.
Ordering data
Type
V 25-B+C/1
V 25-B+C/2
V 25-B+C/3
V 25-B+C/4
V 25-B+C/3+NPE
Description
Order no.
1-pole, complete1); 280 V
2-pole, complete1); 280 V
3-pole, complete1); 280 V TN-C
4-pole, complete1); 280 V TN-S
3+1-pole, complete1) 280 V TT + IT
5097 04 5
5097 01 0
5097 00 2
5097 03 7
5097 40 1
V 25-B+C/2-385
5097 09 6
2-pole, complete1); 385 V
V 25-B+C/4-385
5097 10 0
4-pole, complete1); 385 V
V 25-B+C/3+NPE-385 3+1-pole, complete1) 385 V TT + IT 5097 10 3
V 25-B+C/0-150
V 25-B+C/0-280
V 25-B+C/0-385
Upper part; 150 V version
Upper part; 280 V version
Upper part; 385 V version
5097 08 8
5097 05 3
5097 06 1
C 25-B+C/NPE
Upper part NPE spark gap
5095 60 3
V 25-B+C/4-G
4-pole V 25-B+C in insulating material housing (IP 65); 280 V
5097 25 8
1)
Complete = upper part and base
The V 25-B+C/... is also available on request in a 150 V and a 385 V version.
TBS_GB_V0_15072002
Suitable bases for V 25-B+C, see page 35
Features at a glance
V 25-B+C
Advantages in use
Simple installation via the marked terminals
Arresters still work after frequent operation
Combined arresters B and C for compact
applications
One arrester in main distribution board is sufficient
Plug-in upper part
A faulty arrester module can be changed with the
mains voltage on
Pre-wired arrester blocks, 1-4-pole blocks
Easy to install
Thermal isolating device with optical indication
Permanent check of arrester serviceability
Arrester with NPE spark gap in one module
Certainty in TN-S, TT and IT systems that no voltage can reach the protective earth (PE) conductor
C 25-B+C/NPE with protection against reversed
insertion (coding)
Simple, professional installation of the arrester
modules
Please always state the order number when ordering.
31
Technical data
CombiController lightning arrester
V 25-B+C
Description
Maximum continuous operating voltage
(max. permitted operating voltage)
Uc AC
Uc DC
150
280
385
150 V~
200 V -
280 V~
350 V -
385 V~
505 V -
LPZ
0→2
Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2
to IEC 61643-1
B+C
class I-class II
Tested to
Test currents to DIN VDE 0675, Part 6, A1 + A2
Nominal discharge current
Max. discharge current per block
CombiController V 25-B+C/1...
CombiController V 25-B+C/2...
CombiController V 25-B+C/3...
CombiController V 25-B+C/4...
IEC 61643-1, prEN 61643-1,
E DIN VDE 0675-6:1989-11 and Part 6/A1
In (8/20).
30 kA
Imax (8/20)
50 kA
100 kA
150 kA
200 kA
Maximum discharge current (8/80) in accordance with VdS 2031 for
CombiController V 25-B+C/4...
Imax
100 kA
Surge voltage test (10/350) with the lightning current parameters set out in
IEC 61312-1 (02.95)
Impulse current
Iimp
Charge
Q
Specific energy
W/R
8 kA
4 As
16 kJ/Ω
7 kA
3.5 As
12 kJ/Ω
7 kA
3.5 As
12 kJ/Ω
Voltage protection level at 1 kA (8/20)
at 5 kA (8/20)
at In
Up
Up
Up
≤450 V
≤500 V
≤600 V
≤650 V
≤700 V
≤900 V
≤1.0 kV
≤1.2 kV
≤1.5 kV
Response time
tA
< 25 ns
Short-circuit withstand strength 25 kA with max. upstream fuse
160 A gl/gG
2.5-25 mm2 (fine-stranded with core end sleeves)
2.5-35 mm2 (single and multi-stranded)
Connection cross-section
Mounting on
35 mm top-hat rail to EN 50022
IP Code
Temperature range
IP 20
-40 °C to +80 °C
ϑ
Spark gap CombiController NPE
C 25-B+C/NPE
Maximum continuous operating voltage
Uc
255 V / 50-60 Hz
Insulation resistance at 100 V
Rins
>10 GΩ
Surge voltage test (10/350) with the lightning current parameters set out in IEC 61312-1
(02.95)
Impulse current
Iimp
Charge
Q
Specific energy
W/R
25 kA
12.5 As
160 kJ/Ω
Nominal discharge current
In (8/20)
Voltage protection level
Up
≤1.2 kV
50 kA
Response time
tA
≤100 ns
Follow current at Uc
If
100 Arms
Temperature range
ϑ
-40 °C to +80 °C
32
TBS_GB_V0_15072002
Subject to technical alterations
Please always state the order number when ordering.
L1
L2
61.5
L3
1
54
L
L
90
L
2
PE
Block diagram of V 25-B+C/3
L1
Dimension drawing
L2
L3
61.5
N
1
72
L
L
L
90
L
2
PE
Block diagram of V 25-B+C/4
L1
L2
Dimension drawing
L3
PE
72
61.5
1
L
3
L
L
90
2
N
Block diagram of V 25-B+C/3+NPE
L2
L3
180
L1
Dimension drawing
N
1
2
110
PE
182
Block diagram of V25-B+C/4-G
Dimension drawing
TBS_GB_V0_15072002
Key
1) Thermal isolating device
2) Metal-oxide varistor
3) NPE sum current spark gap
Please always state the order number when ordering.
33
Basic line
protection
LPZ 1 → 2
Surge arresters SurgeController V 20-C,
V 20-C/...+NPE
SurgeControllers V 20-C are surge arresters of requirement class C to DIN VDE 0675, Part 6
(Draft 02.89) A1, A2. These devices protect
low-voltage consumer installations from voltage surges of all kinds. They are available in single-pole to
four-pole versions.
Type V 20-C/3+NPE (requirement class C) is a special
surge arrester for TN-C-S, TN-S, TT and IT systems.
This device was developed for the new requirements
of DIN VDE 0100, Part 534/A1, to allow simple, safe
installation of the devices.
The voltage-dependent active part of the V 20-C is a
high-performance zinc oxide varistor with a highly
non-linear characteristic. Among the advantages of
this component are an extremely short response time,
a low protection level and a high current diversion
capacity, combined with long life. A further feature of
Test marks
34
these devices is that no follow-up current can be
registered after the surge has decayed.
If the surge arrester is damaged by overloading, the
integral isolating device breaks the connection to the
mains. This is signalled by a red fault indicator.
Mounting
The V 20-C can easily be installed in any distribution
box or switchgear cabinet by snap-fitting to any commercial 35 mm top-hat rail. The poles of multi-pole
arresters are connected together by an earthing
bridge at the factory, so that there is only one earth
(PE) connection to make on site. The NPE
arrester element type C 25-B+C/NPE and the matching base are designed so that they cannot be
plugged in the wrong way round (coding). This
ensures correct installation of the upper parts of the
arresters.
Other marks
TBS_GB_V0_15072002
Operation and fields of application
Please always state the order number when ordering.
Ordering data
Type
Description
Order no.
Type
V 20-C/1
V 20-C/2
V 20-C/3
V 20-C/4
V 20-C/1+NPE
V 20-C/3+NPE
1-pole complete1); 280 V
2-pole complete1); 280 V
3-pole complete1); 280 V, TN-C
4-pole complete1); 280 V, TN-S
1+1-pole complete1); 280, V
3+1-pole complete1); 280 V, TT+IT
5099 42 0
5099 43 9
5099 44 7
5099 45 5
5095 61 1
5095 64 6
V 20-C/1-385
V 20-C/2-385
V 20-C/3-385
V 20-C/4-385
V 20-C/1+NPE-385
V 20-C/3+NPE-385
V 20-C/0- 75
V 20-C/0-150
V 20-C/0-280
V 20-C/0-335
V 20-C/0-385
V 20-C/0-440
V 20-C/0-550
Upper part; 75 V version
Upper part; 150 V version
Upper part; 280 V version
Upper part; 335 V version
Upper part; 385 V version
Upper part; 440 V version
Upper part; 550 V version
5099 57 9
5096 70 7
5099 60 9
5099 85 0
5099 59 5
5099 70 6
5099 61 7
C 25-B+C/NPE
Upper part NPE spark gap
5095 60 3
V 20-C/U-1
1-pole base2)
V 20-C/U-2
2-pole base2)
V 20-C/U-3
3-pole base2)
V 20-C/U-4
4-pole base2)
V 20-C/U1+NPE
1+1 pole base2)
V 20-C/U3+NPE
3+1 pole base2)
1) Complete = upper part and base
2) Suitable for V 25-B+C and V 20-C
V 20-C/3-G
3-pole V 20-C arrester in insulating ma- 5099 49 8
terial housing (IP 65); 280 V version
4-pole V 20-C arrester in insulating ma- 5099 52 8
terial housing (IP 65); 280 V version
V 20-C/4-G
Description
1-pole complete1); 385 V
2-pole complete1); 385 V
3-pole complete1); 385 V
4-pole complete1); 385 V
1+1-pole complete1); 385 V
3+1-pole complete1); 385 V
Order no.
5099 16 1
5099 13 7
5099 19 6
5099 14 5
5095 68 9
5095 70 0
5099 63 3
5099 64 1
5099 66 8
5099 67 6
5095 86 7
5095 87 5
The V 20-C/... is also available on request in a 75 V, 150 V, 335 V and a 550 V version.
Advantages in use
Metal-oxide varistor
Arresters still work after frequent operation
Plug-in upper part
An arrester module can be changed with the mains
voltage on
Pre-wired arrester blocks, 1-4-pole blocks
Simple installation via the marked terminals
Thermal isolating device with optical indication
Permanent check of arrester serviceability
Arrester with NPE spark gap in one module
Certainty in TN-S, TT and IT systems that no voltage can reach the protective earth (PE) conductor
C 25-B+C/NPE with protection against reversed
insertion (coding)
Simple, professional installation of the arrester
modules
TBS_GB_V0_15072002
Features at a glance
V 20-C
Please always state the order number when ordering.
35
Technical data
SurgeController surge arrester
V 20-C
Description
Maximum continuous operating voltage
(max. permitted operating voltage)
Uc AC
Uc DC
75
150
280
335
385
440
550
75 V~
100 V-
150 V~
200 V-
280 V~
350 V-
335 V~
420 V-
385 V~
505 V-
440 V~
585 V-
550 V~
745 V-
LPZ
1→2
Requirement class to VDE 0675, Part 6 (Draft 11.89)
A1, A2 to IEC 61643-1
C
class II
Tested to
IEC 61643-1, prEN 61643-1,
E DIN VDE 0675-6:1989-11 and Part 6/A1
Nominal discharge current of
the upper part
Max. discharge current
per block
In (8/20)
15 kA
20 kA
Imax (8/20)
SurgeController V 20-C/1...
SurgeController V 20-C/2...
SurgeController V 20-C/3...
SurgeController V 20-C/4...
Maximum discharge current of
the upper part
Voltage protection level
Response time
tA
Short-circuit withstand strength 25 kA with max. upstream fuse
40 kA
≤300 V
≤350 V
≤400 V
≤500 V
≤650 V
≤700 V
≤900 V
≤1.1 kV
≤1.4 kV
≤1.0 kV
≤1.3 kV
≤1.6 kV
≤1.2 kV
≤1.5 kV
≤1.8 kV
Mounting
≤1.7 kV
≤2.1 kV
≤2.5 kV
<25 ns
125 A gL/gG
Snap-fitting on 35 mm top-hat rail to DIN EN 50 022
IP Code
IP 20
ϑ
Spark gap CombiController NPE
-40 °C to +80 °C
C 25-B+C/NPE
Maximum continuous operating voltage
Uc
255 V /50-60 Hz
Insulation resistance at 100 V
Rins
>10 GΩ
Impulse current
Charge
Specific energy
Iimp
Q
W/R
25 kA
12.5 As
160 kJ/Ω
Nominal discharge current
In (8/20)
Voltage protection level
Response time
≤1.5 kV
≤1.8 kV
≤2.2 kV
2.5-35 mm2 (single and multi-stranded);
2.5-25 mm2 (fine-stranded with core end sleeves)
Connection cross-section
Temperature range
40 kA
75 kA
110 kA
150 kA
Imax (8/20)
at 1 kA (8/20) Up
at 5 kA (8/20) Up
at In Up
15 kA
50 kA
≤1.2 kV
tA
≤100 ns
Follow current at Uc
If
100 Arms
Temperature range
ϑ
-40 °C to +80 °C
36
TBS_GB_V0_15072002
Subject to technical alterations
Please always state the order number when ordering.
L1
L2
L3
61.5
54
1
90
2
3
PE
Dimension drawing
Block diagram of V 20-C/3
L1
L2
L3
N
61.5
72
1
90
2
3
PE
Dimension drawing
Block diagram of V 20-C/4
L1
L2
L3
PE
61.5
72
1
4
90
2
3
N
Block diagram of V 20-C/3+NPE
L2
L3
N
180
L1
Dimension drawing
1
2
110
3
PE
182
Block diagram of V 20-C/4-G
Dimension drawing
TBS_GB_V0_15072002
Key
1) Dynamic isolating device
2) Thermal isolating device
3) Metal-oxide varistor
4) NPE sum current spark gap
Please always state the order number when ordering.
37
Basic line
protection
Signalling device for CombiController V 25-B+C/FS
and SurgeController V 20-C/FS
Operation and fields of application
Remote signalling allows central monitoring of the
serviceability of lightning arresters and surge
arresters, even when the devices cannot be observed
directly or are installed where access is difficult.
1 2 3
A monitoring module is installed at each arrester
block to provide a constant check that all the connected arresters are ready to operate. If an arrester
fails, a mechanism passes a command to the microswitch in the monitoring module. This fault signal is
then passed to the remote indicating unit, where the
fault is indicated optically or acoustically.
L1
L2
L3
PE
Block diagram of OBO V 20-C/3-FS
Mounting
The device is installed by snap-fitting to any standard
commercial 35 mm top-hat rail. The monitoring unit is
easily and quickly installed by means of screwless
terminals.
38
Other marks
TBS_GB_V0_15072002
Test marks
Please always state the order number when ordering.
Technical data
Signalling device OBO V 25-B+C/FS or V 20-C/FS monitoring module
Max. switching voltage
U~max.
≤250 V
Max. switching current
I~max.
6A
Connection cross-section
single-stranded, multi-stranded, fine-stranded
fine-stranded with: core end sleeve, pin cable lug, crimp sleeve
0.14- 2.5 mm2
Stripping length for connecting cables
6-7 mm
Signal contact
NO (make)
NC (break)
1-2
1-3
Mounting
Snap-fitting on 35 mm top-hat rail to
DIN EN 50022
Subject to technical alterations
Ordering data
Type
Description
Order no.
61.5
90
4-pole upper part and base with FS3)
in insulating material housing (IP 65)
5097 31 2
Description
Order no.
V 20-C/1-FS
V 20-C/2-FS
V 20-C/3-FS
V 20-C/4-FS
V 20-C/1+NPE-FS
V 20-C/3+NPE-FS
1-pole complete1) with FS3); 280 V
2-pole complete1) with FS3); 280 V
3-pole complete1) with FS3); 280 V
4-pole complete1) with FS3); 280 V
1+1-pole complete1) with FS3); 280 V
3+1-pole complete1) with FS3); 280 V
5096 00 6
5096 01 4
5096 02 2
5096 03 0
5095 65 4
5095 67 0
V 20-C/3-FS-385
V 20-C/4-FS-385
V 20-C/3+NPE-385
3-pole complete1); with FS3); 385 V
4-pole complete1); with FS3); 385 V
3+1-pole complete1); 385 V
5095 98 0
5095 99 9
5095 73 5
V 20-C/U-1-FS
V 20-C/U-2-FS
V 20-C/U-3-FS
V 20-C/U-4-FS
V 20-C/U-1+NPE-FS
V 20-C/U-3+NPE-FS
1-pole base2) with FS3)
2-pole base2) with FS3)
3-pole base2) with FS3)
4-pole base2) with FS3)
1+1-pole base2) with FS3)
3+1-pole base2) with FS3)
5096 30 8
5096 31 6
5096 32 4
5096 33 2
5095 84 0
5095 85 9
V 20-C/U-PH-FS
3-pole base2); photovoltaic installations, remote signalling
5096 63 4
V 25-B+C/4-FS-G
Type
1)
2)
3)
90
3-pole complete1) with FS3); 280 V
V 25-B+C/3-FS
5097 13 4
V 25-B+C/4-FS
4-pole complete1) with FS3); 280 V
5097 14 2
V 25-B+C/3+NPE-FS 3+1-pole complete1) with FS3); 280 V 5097 42 8
Complete = upper part and base
Suitable for V 25-B+C and V 20-C
FS = remote signalling
Versions of V 25-B+C/...-FS and V 20-C/...-FS for other voltages are available on request.
TBS_GB_V0_15072002
Features at a glance
V 25-B+C/FS, V 20-C/FS
Advantages in use
Floating contact
Voltage level at the signalling device can be
freely defined
Changeover contact
Can be used as NO or NC (make or break) contact
Modular construction (only one switch)
No additional wiring needed, saving time
Spatial separation between signalling device
and arrester
Prevents mutual influence
Please always state the order number when ordering.
39
Basic line
protection
Acoustic signalling device for CombiController
V 25-B+C/AS and SurgeController V 20-C/AS
Operation and fields of application
230 V L1
Acoustic signalling is a safety component which permanently checks the serviceability of arresters and
indicates a fault by means of a warning tone. Constant self-checking of the arrester fitted with this monitoring module provides unbeatable safety – even without visual inspection. The device is ideal wherever
optical signalling does not appear rational or feasible.
Examples are dwelling houses, agricultural buildings,
banks, office and administration buildings, and so on.
The warning tone can be silenced for the next 24
hours by operating a black switch. When the faulty
device has been replaced, a green LED indicates that
the arrester block is working properly.
Test marks
40
L3
PE
Block diagram of OBO V 20-C/3-AS
Mounting
The monitoring module has user-friendly screwless
terminals. Installation cost is very low. The arresters
are mounted on a top-hat rail in the distribution
board.
Other marks
TBS_GB_V0_15072002
The control module starts an acoustic alarm immediately after the operation of an isolating device. The
alarm takes the form of a high-frequency warning tone
which can be heard at a considerable distance. In
addition, a red LED flashes on the monitoring module.
L2
Please always state the order number when ordering.
Technical data
Signalling device OBO V 25-B+C/AS or V 20-C/AS monitoring module
Nominal voltage
UN
Maximum continuous operating voltage
Uc
230 V / 50-60 Hz
250 V
Rated load current
IL
40 mA
Connection cross-section
single-stranded, multi-stranded, fine-stranded
fine-stranded with: core end sleeve, pin cable lug, crimp sleeve
0.14-2.5 mm2
Stripping length for connecting cables
6-7 mm
Mounting
Snap-fitting on 35 mm top-hat rail to
DIN EN 50022
Subject to technical alterations
Ordering data
Type
Description
Order no.
90
61.5
3-pole complete1) with AS3); 280 V
4-pole complete1) with AS3); 280 V
5097 18 5
5097 19 3
Description
Order no.
2-pole complete1) with AS3); 280 V
3-pole complete1) with AS3); 280 V
4-pole complete1) with AS3); 280 V
5096 37 5
5096 38 3
5096 39 1
Type
V 20-C/2-AS
V 20-C/3-AS
V 20-C/4-AS
V 20-C/U-2-AS
2-pole base2) with AS3)
V 20-C/U-3-AS
3-pole base2) with AS3)
V 20-C/U-4-AS
4-pole base2) with AS3)
1) Complete = upper part and base
2) Suitable for V 25-B+C and V 20-C
3) AS = acoustic signalling
L
L
L
L
90
V 25-B+C/3-AS
V 25-B+C/4-AS
5096 41 3
5096 42 1
5096 44 8
TBS_GB_V0_15072002
Versions of V 25-B+C/...-AS and V 20-C/...-AS for other voltages are available on request.
Features at a glance
V 25-B/AS, V 20-C/AS
Advantages in use
High-frequency warning tone
Perceived immediately as a warning signal
Muting switch with repeat action
Can be used in office buildings with poor access
Modular construction
No additional wiring - saves time
Spatial separation between signalling device
and arrester
Prevents mutual influence
Please always state the order number when ordering.
41
Basic line
protection
Signalling device for CombiController V 25-B+C/FS-SÜ
and SurgeController V 25-B+C/FS-SÜ, V 20-C/FS-SÜ
Operation and fields of application
1 2 3
L1
L2
L3
CombiControllers and SurgeControllers used in electrical installations with main fuses rated above 160 A
and 125 A respectively are provided with their own
fuses. To ensure permanent monitoring of the surge
protection, signalling devices V 25-B+C/FS-SÜ and
V 20-C/FS-SÜ are installed.
The control module monitors all three phases of the
arrester and the serviceability of the series-connected
fuses. Any drop in the supply voltage and any fault in
a fuse, as well as tripping of an isolating device in the
arrester module, is registered immediately and indicated by remote signalling.
The duct on top of the arrester block covers the connections of the monitoring module to the three-phase
network. In this way the applied voltage is monitored.
Not only the failure of an arrester is registered, but
also the failure of a series-connected fuse.
Mounting
The standard 17.5 mm case of the V 25-B+C/FS-SÜ
and V 20-C/FS-SÜ snap-fits to a 35 mm top-hat rail.
Screwless terminals keep installation time short.
PE
Block diagram of OBO V 20-C/3-FS-SÜ
>125 A gl
or
>160 A gl
L1
L2
L3
PEN
160 A gl with V 25-B+C
or
125 A gl with V 20-C
V 25-B+C/FS-SÜ
or
V 20-C/FS-SÜ
Installation example
42
Other marks
TBS_GB_V0_15072002
Test marks
Please always state the order number when ordering.
Technical data
Signalling device OBO V 25-B+C/FS-SÜ or V 20-C/FS-SÜ monitoring module
Nominal voltage
UN
Rated load current
IL
3/400 V (50-60 Hz)
12 mA
Switching voltage
U
0 ... 250 V
Max. switching voltage
U~max.
Max. switching current
I~max.
250 V
3A
0.14-2.5 mm2
Connection cross-section
single-stranded, multi-stranded, fine-stranded
fine-stranded with: core end sleeve, pin cable lug, crimp sleeve
Stripping length for connecting cables
6-7 mm
Signal contact
NO (make)
NC (break)
1-2
1-3
Mounting
Snap-fitting on 35 mm top-hat rail to
DIN EN 50022
Subject to technical alterations
Ordering data
V 25-B+C/3-FS-SÜ
V 25-B+C/4-FS-SÜ
Description
3-pole complete1) with FS-SÜ3); 280 V
4-pole complete1) with FS-SÜ3); 280 V
Type
Description
Order no.
90
L
5097 11 8
5097 35 5
L
L
L
FS
Order no.
V 20-C/3-FS-SÜ
V 20-C/4-FS-SÜ
3-pole complete1) with FS-SÜ3); 280 V
4-pole complete1) with FS-SÜ3); 280 V
5096 25 1
5096 27 8
V 20-C/U-3-FS-SÜ
V 20-C/U-4-FS-SÜ
3-pole base2) with FS-SÜ3);
4-pole base2) with FS-SÜ3);
5096 35 9
5096 36 7
1) Complete = upper part and base
2) Suitable for V 25-B+C and V 20-C
3) FS-SÜ = remote signalling and voltage
61.5
90
Type
monitoring
TBS_GB_V0_15072002
Versions of V 25-B+C/...-FS-SÜ and V 20-C/...-FS-SÜ for other voltages are available on request.
Features at a glance
V 25-B+C/FS-SÜ, V 20-C/FS-SÜ
Advantages in use
Immediately indicates the failure of only one phase
Simultaneous monitoring of the voltages on the load
Remote signalling and voltage monitoring in one
housing
Saves space
Floating contact
Freely definable voltage level at the signalling
device
Changeover contact
Can be used as NC or NO (break or make) contact
Please always state the order number when ordering.
43
Basic line
protection
Surge arrester SurgeController V 20-C/U-PH
Mounting
Surge arrester V 20-C/U-PH is designed for snapfitting to 35 mm top-hat rails. In versions with monitoring module, installation is made easier by screwless
terminals.
Note:
The upper parts of the V 25-B+C must be used when
connecting the external lightning protection installation to the solar modules.
Solar modules
Operation and fields of application
V 20-C/U-PH is the basic building block for the surge
protection of photovoltaic installations. The simple
connection of the plus, minus and earth wires allows
optimum protection in the branch distribution box directly behind the photovoltaic module, before the inverter.
The basic building block is available in versions for
remote or acoustic signalling. The upper parts required are ordered separately.
For an application example, see page 112. House
with photovoltaic installation.
1
2
Branch
distribution
box
V 20-C/U-PH
Test joint
Distribution board
with inverter, overvoltage and undervoltage
monitoring and FI
safety switch
Circuit distribution
board with
circuit-breakers
and surge arresters
3
V 20-C/...
Solar current
meter
3
to electricity supply company
Block diagram of V 20-C/U-PH
1) Dynamic isolating device
2) Thermal isolating device
3) Metal-oxide varistor
44
TBS_GB_V0_15072002
Other marks
Please always state the order number when ordering.
Technical data
Surge arrester V 20-C/U-PH
Description
Base
2.5-35 mm2 (single and multi-stranded);
2.5-25 mm2 (fine-stranded with core end sleeves)
Connection cross-section
Mounting
Snap-fitting on 35 mm top-hat rail to
DIN EN 50 022
Temperature range
-40 °C to +80 °C
ϑ
Monitoring module
Nominal voltage
UN
Max. continuous operating voltage Uc
Max. switching current
Imax.
Rated load current
IL
Remote signalling (FS)
Acoustic signalling (AS)
0 ... 250 V
230 V~
250 V~
250 V~
6 A~
-
-
40 mA
0.14-2.5 mm2
Connection cross-section
Signal contact
NO (make)
NC (break)
1-2
1-3
Subject to technical alterations
Ordering data
Type
Description
Order no.
50
V 20-C/U-PH
V 20-C/U-PH-FS
5096 62 6
5096 63 4
Upper parts must be chosen to suit the voltage of the photovoltaic
installation:
Arrester type for
single module
V 20-C/0-75
V 20-C/0-150
V 20-C/0-280
V 20-C/0-335
V 20-C/0-385
V 20-C/0-440
V 20-C/0-550
Max. no-load
voltage of solar
module
Number
required
Order no.
100 V
200 V
350 V
420 V
505 V
585 V
745 V
3
3
3
3
3
3
3
5099 57 9
5096 70 7
5099 60 9
5099 85 0
5099 59 5
5099 70 6
5099 61 7
90
Suitable for V 25-B+C and V 20-C
89.8
1)
3-pole base1)
3-pole base1) with remote signalling
53.4
When connecting the external lightning protection installation to the
solar modules, use arrester V 25-B+C:
Arrester type for
single module
V 25-B+C/0-150
V 25-B+C/0-280
V 25-B+C/0-385
Max. no-load
voltage of solar
modules
Number
required
Order no.
170 V
350 V
500 V
3
3
3
5097 08 8
5097 05 3
5097 06 1
TBS_GB_V0_15072002
Features at a glance
V 20-C/U-PH
Advantages in use
Base suitable for V 20-C and for V 25-B+C
Can be used as a lightning arrester or as
a surge arrester
Pre-wired arrester blocks
Professional installation
Marked terminals
Easy to install
Suitable for special voltages
Universal for the most common photovoltaic systems
Please always state the order number when ordering.
45
Basic line
protection
ISOLAB checking system
ISOLAB, which has been tested by the VDE, is an
insulation and arrester tester. This combination
device can be used for insulation testing of electrical
installations to DIN VDE 0100/Part 610 as well as to
determine the characteristics of the upper parts of
type V 25-B+C and V 20-C. The ISOLAB tester is also
suitable for checking the insulation performance
of LightningControllers MC 50-B/VDE and
MC 125-B/NPE.
1. Insulation measurement
Before insulation testing starts, the mains voltage
must be switched off. In other words, there must be
no voltage on any part of the installation. When the
test leads have been connected, insulation testing is
Test marks
46
started by pressing the start button. The resistance
reading appears on the display. (Note: before insulation testing, the upper parts of arresters must be removed and other surge protection devices must be
disconnected.)
2. Arrester test
The selector switch is used to select the type of module to be tested (V 25-B or V 20-C). Plugging in the
upper part starts the test procedure automatically.
The 1 mA or 3 mA point can be read off on the display. By comparing the results with the printed tolerance field table, it is possible to tell whether the arrester has suffered ageing and needs to be replaced.
Note: test leads are supplied with the tester.
Other marks
TBS_GB_V0_15072002
Operation and fields of application
Please always state the order number when ordering.
Technical data
ISOLAB insulation tester
Measuring range
Error class
Test voltage
Test current
Max. test current
0.5 MΩ-19.99 MΩ
±5% ±0.01 MΩ
500 V
1 mA
<10 mA
ISOLAB arrester tester
Test current
V 20-C
V 25-B+C
1 mA
3 mA
Measuring range
Error class
Max. test voltage
Power supply (device)
Nominal discharge current
Working temperature
Storage temperature
Temperature for stated accuracy
Battery type
Weight
Tolerance fields
V 20-C/0-75 V
V 20-C/0-150 V
V 20-C/0-280 V
V 20-C/0-330 V
V 20-C/0-385 V
V 20-C/0-440 V
V 20-C/0-550 V
0 V-999 V
±1% ±1 volt
999 V
6V
5 mA
0 °C to +40 °C
-10 °C to +50 °C
+23 °C ±5 °C
R6 AA UM3 (Mignon)
680 g
Subject to technical alterations
V 25-B+C/0-230 V
MC 50-B/VDE
MC 125-B/NPE
MCD 50-B
MCD 125-B/NPE
108 V-132 V
184 V-225 V
387 V-473 V
459 V-561 V
558 V-682 V
643 V-786 V
819 V-1001 V
387 V-473 V
to DIN VDE 0100, Part 610 >0.5 MΩ
to DIN VDE 0100, Part 610 >0.5 MΩ
to DIN VDE 0100, Part 610 >0.5 MΩ
to DIN VDE 0100, Part 610 >0.5 MΩ
Ordering data
National version, Germany
National version, United Kingdom
Order no.
120
50
5096 79 0
5096 81 2
250
ISOLAB
ISOLAB
Description
TBS_GB_V0_15072002
Features at a glance
ISOLAB
Advantages in use
Testers for testing arresters MC 50-B VDE,
MC 125-B/NPE/VDE, V 25-B+C and V 20-C
One device for all types of arrester
Insulation testing to DIN 0100/Part 610
Service-friendly
Arresters can be tested with special voltages
Universal device
Please always state the order number when ordering.
272
Type
47
Basic line
protection
Peak Current Sensor PCS monitoring system
Operation and fields of application
Mounting
The Peak Current Sensor records and permanently
stores impulse currents on a magnetic card. The magnetic strip of the PCS is encoded in a special way.
Since every current-carrying conductor produces a
magnetic field proportional to the current, such a
magnetic field influences the encoding of the magnetic strip. This change is evaluated and displayed on a
special magnetic card reader PCS-CS. This makes it
possible to measure impulse current in lightning
protection installations and – using the test kits in the
equipotential bonding lines – in lightning and surge
arresters. In this way, the effectiveness of these
protection devices can be checked at any time.
The Peak Current Sensor is held in a card holder
which is attached to 8 or 10 mm round wire (usual in
outdoor lightning protection installations). The card
holder secures, protects and positions the magnetic
card. Special mounting kits from the OBO range are
used for simple, quick installation of the magnetic
card on equipotential bonding bars (a) and on lightning arresters in buildings (b).
Note: each magnetic card can be evaluated once at
the factory free of charge.
48
TBS_GB_V0_15072002
Other marks
Please always state the order number when ordering.
Technical data
Magnetic card reader
Nominal voltage
Charging time
Storage and operating temperature
Fuse
Measuring range
Measurement tolerance
Operating time of battery
Dimensions
UN
230 V / 50-60 Hz
8h
-10 °C to +50 °C
mt 1.25 A
3-120 kA
≤2 kA
about 4 h (continuous operation)
250 x 200 x 380 mm
300 x 200 x 440 mm
ϑ
F
with handle
Magnetic card holder
Clamping range
Material
Mounting
Dimensions
8-10 mm (round wire)
Polypropylene, elastomer seal
Clamp mounting
115 x 72 x 7 (17) mm
Magnetic card
Material
Dimensions
Polycarbonate
85.7 x 54 mm
Ordering data
10 magnetic cards, incl. holder
Type
PCS-CS-D
PCS-CS-GB
PCS-CS-F
Description
Card reader (German version)
Card reader (UK version)
Card reader (French version)
Type
PCS
Description
10 magnetic cards/pack
Description
5091 32 2
Order no.
5091 68 3
5091 69 1
5091 71 3
Order no.
PC
5091 43 8
85.5
Order no.
PP
60
Type
Order no.
10 magnetic card holders/pack
5091 52 7
11
PCS-H
72
MK-B
Description
54.5
Type
104
TBS_GB_V0_15072002
Features at a glance
PCS
Advantages in use
Card holder with seal
The service-friendly sensor does not require
maintenance
Magnetic-strip decoding
No power supply required
Card holder can be lead-sealed
Tamper-proof
Clamping range of the card holder suitable for
8-10 mm round conductors with snap-fixing
Easy to install
Please always state the order number when ordering.
49
Download