VBS TBS KTS TBS. Surge protection systems Order information and technical data Basic line protection Selection guide for network system TN-C-S Selection guide for network system TN-S Selection guide for network system TT Lightning arresters Coordinated LighningControllers VG and SA series system solutions Decoupling inductance Lightning/surge arresters Surge arresters Signalling device for lightning and surge arresters Surge arrester for photovoltaic installations ISOLAB monitoring system Peak Current Sensor PCS checking system BSS LFS UFS TN-C-S system Domestic connection box F1 L1 Line length Main distribution board L1-4 Circuit distribution unit e. g. sub-distribution board Line length Precision mains protection F2 (RCD) L2 L3 PEN F3 F4 B1) C1) D1) Main EBB 1) Local EBB Requirement class to DIN VDE 0675 Part 6 (A1/A2). 500 A 63 A 125 A EP 220-D Order No. 5099 90 0 3 x MC 50-B VDE Order No. 5096 84 7 4 x LC 63 Order No. 5096 97 0 See selection list, pages 14 and 15 V 20-C/3+NPE Order No. 5095 64 6 KNS-D Order No. 5092 50 7 160 A CNS 3-D Order No. 5092 70 1 VF 230-AC Order No. 5097 64 9 V 25-B+C/3 Order No. 5097 00 2 alternative protection-set pages 24 and 25 16 class C, medium protection) must be installed in the individual sub-distribution boards. Separate fuses before the arrester are only necessary if the ratings of the upstream fuses (e. g. incoming supply fuses) are higher than the values required for the surge protection. The relevant details can be taken from the technical data on the product pages. TBS_GB_V0_15072002 In the TN-C-S mains supply system triple-pole lightning arresters of requirement class B (broad-based protection) are used. The arresters are connected in parallel with the incoming supply lines (L1, L2, L3), which are connected via the arresters to the PEN. If multi-level surge protection is required, an arrester of type V 20-C/3+NPE (arrester of requirement Please always state the order number when ordering. TN-S system Domestic connection box L1 Line length Main distribution board F1 L1-4 Circuit distribution unit e. g. sub-distribution board Line length F2 (RCD) Precision mains protection L2 L3 N PE F3 F4 B1) C1) D1) Main EBB 1) Local EBB Requirement class to DIN VDE 0675 Part 6 (A1/A2). 63 A 500 A 125 A EP 220-D Order No. 5099 90 0 3 x MC 50-B VDE Order No. 5096 84 7 1 x MC 125-B/NPE VDE Order No. 5096 86 3 4 x LC 63 Order No. 5096 97 0 V 20-C/3+NPE Order No. 5095 64 6 KNS-D Order No. 5092 50 7 See selection list, pages 14 and 15 160 A CNS 3-D Order No. 5092 70 1 VF 230-AC Order No. 5097 64 9 V 25-B+C/3+NPE Order No. 5097 40 1 TBS_GB_V0_15072002 alternative protection-set pages 24 and 25 In the TN-S mains supply system, lightning arresters of requirement class B (broad-based protection) are used in the 3+1 circuit. In the 3+1 circuit, the incoming supply lines are connected via arresters to the neutral line. The neutral line is connected to the protective earth (PE) line via a sum spark gap. This prevents voltages reaching the protective conductor due to the insulation problems that may occur with leakage currents. Please always state the order number when ordering. If multi-level surge protection is required, an arrester of type V 20-C/3+NPE (arrester of requirement class C, medium protection) must be installed in the individual sub-distribution boards. Separate fuses before the arrester are only necessary if the ratings of the upstream fuses (e. g. incoming supply fuses) are higher than the values required for the surge protection. The relevant details can be taken from the technical data on the product pages. 17 TT system Domestic connection box L1 Line length Main distribution board F1 L1-4 Circuit distribution unit e. g. sub-distribution board Line length F2 (RCD) Precision mains protection L2 L3 N F3 F4 B1) C1) D1) Main EBB 1) Local EBB Requirement class to DIN VDE 0675 Part 6 (A1/A2). 63 A 500 A 125 A EP 220-D Order No. 5099 90 0 3 x MC 50-B VDE Order No. 5096 84 7 1 x MC 125-B/NPE VDE Order No. 5096 86 3 See selection list, pages 14 and 15 4 x LC 63 Order No. 5096 97 0 V 20-C/3+NPE Order No. 5095 64 6 KNS-D Order No. 5092 50 7 160 A CNS 3-D Order No. 5092 70 1 VF 230-AC Order No. 5097 64 9 V 25-B+C/3+NPE Order No. 5097 40 1 alternative protection-set pages 24 and 25 18 of type V 20-C/3+NPE (arrester of requirement class C, medium protection) must be installed in the individual sub-distribution boards. Separate fuses before the arrester are only necessary if the ratings of the upstream fuses (e. g. incoming supply fuses) are higher than the values required for the surge protection. The relevant details can be taken from the technical data on the product pages. TBS_GB_V0_15072002 In TN systems, lightning arresters of requirement class B (broad-based protection) are used in the 3+1 circuit. In the 3+1 circuit, the incoming supply lines are connected via arresters to the neutral line. The neutral line is connected to the protective earth (PE) line via a sum spark gap. This prevents voltages reaching the protective conductor due to the insulation problems that may occur with leakage currents. If multi-level surge protection is required, an arrester Please always state the order number when ordering. Basic line protection LPZ 0 → 1 Lightning arrester LightningController MC 50-B VDE LightningController MC 50-B VDE is a plug-in multiple spark gap. The device consists of nine partial spark gaps, formed by ten heavy-duty carbon discs. The precisely defined spacing of the spark gaps is safely ensured by highly heat-resistant Teflon discs. Blade contacts of pressure die-cast zinc, which are screwed to each other, clamp the spark gap together with accurate positioning. Eight of the nine spark gaps are capacitively controlled and thus ensure a precisely defined operating surge voltage of ≤ 2 kV. The lightning arrester conforms to requirement class B to DIN VDE 0675 Part 6 (Draft 11.89) A1, A2 and class I to IEC 61643-1 (02.98). The device is designed to be used between interface 0 to 1 in accordance with the lightning protection zone concept of IEC 61312-1. In a lightning protection installation in a building, LightningController MC 50-B VDE provides lightning protection potential equalisation with the power supply lines. The device has been successfully tested with respect to the lightning current parameters according to ENV 61024-1 and IEC 61024-1. Test marks 20 Since the protective action of LightningController MC 50-B VDE is ensured even with a direct lightning strike on an overhead line, the device can also be used in buildings supplied with power via an overhead line. F Block diagram of LightningController Mounting LightningController MC 50-B VDE is easy to install, since the dimensions of the housing of the device conform to the space-saving 17.5 mm grid module. The lightning arrester is installed simply by snapfitting it to the top-hat rail. The LightningController has two terminals each for the N and PE-conductors. Note: since the spark gap of the device is enclosed, no plasma arcs are produced outside the casing. Other marks TBS_GB_V0_15072002 Operation and fields of application Please always state the order number when ordering. Technical data LightningController lightning arrester Type MC 50-B VDE Nominal voltage UN 230 V / 50-60 Hz Maximum continuous operating voltage Uc 255 V Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2 to IEC 61643-1 B class I LPZ 0→1 Insulation resistance Rins >100 MΩ Voltage protection level Up <2 kV Response time tA <100 ns Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95) Peak current Iimp Charge Q Spec. energy W/R 50 kA 25 As 0.63 MJ/Ω Mains follow-up current quenching capacity of the arrester at Uc Maximum asymmetric short-circuit current 12.5 kArms 25 kA Ip Max. series fuse (only required if there is no such fuse already in the network) 500 A gL/gG Short-circuit strength (series fuse 500 A gL) Maximum asymmetric short-circuit current Ip 17.6 kArms 25 kA Temperature range ϑ -40 °C to +85 °C Air humidity ≤95% IP Code IP 20 10-50 / 0-25 / 10-35 mm2 AWG 8-2 Connection cross-section rigid/flexible/stranded Tightening torque (MA) at least 4 Nm Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Subject to technical alterations Ordering data TBS_GB_V0_15072002 MC 50-B VDE Complete1) MC 50-B VDE/O Upper part MC 50-B VDE/U Base 1) Complete = upper part and base Order no. 35 49.5 5096 84 7 5096 82 0 5096 83 9 100 Description 44.9 Type Features at a glance MC 50-B VDE Advantages in use Enclosed system, no plasma arcs outside the casing Can be installed in any standard commercial distribution board enclosure Safety-tested, VDE, ÖVE, KEMA KEUR, MEEI, EZU test marks Reliable arrester in all applications, tested by several independent institutes Low protection level Decoupling inductances only needed where the distance (line length) between class B and C arresters is less than 5 metres Plug-in upper part Simple checking of the technical connection condition (TAB) of the VDEW (see page 24) Two connection possibilities on each side Easy to install High follow-up current quenching capacity Can be used close to transformers Connection duct at side No busbars required Please always state the order number when ordering. 21 Basic line protection LPZ 0 → 1 Lightning arrester LightningController MC 125-B/NPE Operation and fields of application L1 L2 L3 PE N LightningController MC 125-B/NPE was designed to be used in TN-S, TT and IT systems as a sum current spark gap between the neutral conductor (N) and the protective earth conductor (PE). At the heart of the device there are two partial spark gaps made up of three carbon discs which can handle heavy loads. The precisely defined spacing of the spark gaps is ensured by highly heat-resistant Teflon discs. The lightning arrester satisfies the preconditions of requirement class B to DIN VDE 0675 Part 6 (Draft 11.89) A1, A2 and of Class I to IEC 61643-1 (02.98). The device is designed to be used between interface 0 to 1 in accordance with the lightning protection zone concept of IEC 61312-1. In the lightning protection installation of a building or where power is supplied via an overhead line, the MC 125-B/NPE, combined with LightningController MC 50-B VDE, provides lightning protection potential equalisation. Circuit for TN-S, TT and IT systems Mounting LightningController MC 125-B/NPE is easy to install, since the dimensions of the housing of the device conform to the space-saving 17.5 mm grid module. The lightning arrester is installed simply by snapfitting it to the top-hat rail. The LightningController has two terminals each for the N and PE conductors. F Block diagram of LightningController 22 Other marks TBS_GB_V0_15072002 Test marks Please always state the order number when ordering. Technical data LightningController lightning arrester Type MC 125-B/NPE Nominal voltage UN 230 V / 50-60 Hz Maximum continuous operating voltage Uc 255 V Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2 to IEC 61643-1 B class I LPZ 0→1 Insulation resistance Rins >100 MΩ Voltage protection level Up <2.5 kV Response time tA <100 ns Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95) Peak current Iimp Charge Q Spec. energy W/R 125 kA 62.5 As 3.9 MJ/Ω Follow-up current quenching capacity at Uc Ip 100 Arms Temperature range ϑ -40 °C to +85 °C Air humidity ≤95% IP Code IP 20 10-50 / 10-25 / 10-35 mm2 AWG 8-2 Connection cross-section rigid/flexible/stranded Tightening torque (MA) at least 4 Nm Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Subject to technical alterations Ordering data Complete Order no. 35 49.5 5096 86 3 TBS_GB_V0_15072002 44.8 MC 125-B/NPE Description 100 Type Features at a glance MC 125-B/NPE Advantages in use Enclosed system, no plasma arcs outside the casing Can be installed in any standard commercial distribution board enclosure Safety-tested, VDE, ÖVE, KEMA KEUR, MEEI, EZU test marks Reliable arrester in all applications, tested by several independent institutes High lightning current capacity, 125 kA (10/350) Safety in service Two connection possibilities on each side Easy to install Connection duct at side No busbars required Please always state the order number when ordering. 23 Basic line protection LPZ 0 → 1 Lightning arrester Coordinated LightningControllers MCD 50-B and MCD 125-B/NPE Operation and fields of application the surge arrester (requirement class C) with compact TT and TN-S systems can be omitted. Coordinated LightningControllers MCD 50-B and MCD 125-B/NPE are lightning arresters of requirement class B to DIN VDE 0675 Part 6 (Draft 11.89) A1, A2, and Class I to IEC 61643-1 (08.98). In combination with surge arresters connected directly after them, they ensure coordinated operation. No additional decoupling components are needed. The fundamental advantages of the innovative multi-carbon technology of OBO LightningControllers are fully preserved. Mounting The low protection level (Up ≤ 1.3 kV) makes it unnecessary to install decoupling inductances or to provide additional lengths of conductor between lightning arresters (requirement class B) and surge arresters (requirement class C). The result is up to 45 percent space saving on installation. And this proves to be a particular advantage, especially with compact EMC concepts. In addition, the separate NPE spark gap at Coordinated LightningControllers are suitable for snap-fitting to standard commercial 35 mm top-hat rails to DIN EN 50022 and conform to the space-saving 17.5 mm grid module. At each connection point there are two possibilities for Lx and N/PE. Note: Since the arrester elements of the devices are enclosed, no plasma arcs are produced outside the casing. TN-C-S networks L1 L2 L3 PEN F Preferred fields of application for the new Coordinated LightningControllers are compact surge protection concepts in separate housings and the installation of arresters of requirement classes B and C in a distribution board. A typical application: compact mobile radio transmitters. TN-S networks Decoupling distance no longer necessary MCD 50-B F V 20-C TT network systems Decoupling distance no longer necessary F L1 L2 L3 N L1 L2 L3 N PEN MCD 50-B V 20-C V 20-C MCD 50-B MCD 125-B/NPE MCD 125-B/NPE EBB Decoupling distance no longer necessary EBB EBB 24 TBS_GB_V0_15072002 Other marks Please always state the order number when ordering. Technical data Coordinated LightningController Type Nominal voltage Maximum continuous operating voltage Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2 to IEC 61643-1 MCD 50-B MCD 125-B/NPE 230 V / 50-60 Hz 255 V coordinated B NPE spark gap coordinated class I UN Uc LPZ Insulation resistance Rins Voltage protection level Up Response time tA Surge voltage test (10/350) with the lightning parameters set out in IEC 61312-1 (02.95) Peak current Iimp Charge Q Spec. energy W/R Mains follow-up current quenching capacity of the arrester at Uc Maximum asymmetric short-circuit current Ip 50 kA 25 As 0.63 MJ / Ω 12.5 kArms 25 kA 125 kA 62.5 As 3.9 MJ / Ω 100 Arms Max. series fuse (only required if there is no such fuse already in the network) Short-circuit strength (series fuse 500 A gL) Maximum asymmetric short-circuit current Ip 500 A gL/gG 17.6 kArms 25 kA - Temperature range Connection cross-section rigid/flexible/stranded Tightening torque (MA) at least 4 Nm 0→1 100 MΩ ≤1.3 kV <100 ns - -40 °C to +85 °C 10-50 / 10-25 / 10-35 mm2 AWG 8-2 ϑ Subject to technical alterations Ordering data Complete Upper part Base Complete Ord. no. 35 49.5 5096 84 9 5096 82 2 5096 83 9 5096 86 5 100 MCD 50-B MCD 50-B/0 MC 50-B/U MCD 125-B/NPE Description 44.9 Type PS... series: Protection Set: Pre-assembled, ready-to-connect combination of lightning arrester (requirement class B) type MCD and surge arresters (requirement class C) type V 20-C Description PS4-B+C/TT+TNS 4-pole for TT + TN-S1) PS4-B+C/TT+TNS-FS 4-pole for TT + TN-S1) w. FS PS3-B+C/TNC 3-pole for TN-C1) 1) network systems FS = remote signalling Ord. no. 5089 60 7 5089 61 1 5089 60 3 157,5 100 Type Dimension drawing PS3-B+C/TNC TBS_GB_V0_15072002 Features at a glance Coordinated LightningControllers Advantages in use Low protection level (Up <1.3 kV) Additional decoupling inductances or decoupling distance between arresters of requirement class B and C no longer needed Compact EMC concepts Up to 45% space saving, installation saving High arrester availability No sensitive trigger electronics inside the arrester In compact TT or TN-S network systems, an additional NPE sum spark gap at surge arresters of requirement class C is no longer necessary Cost and space savings Proven carbon technology as in the LightningController All LightningController advantages (page 21/22 and page 23/24) are retained without restriction Please always state the order number when ordering. 25 Surge protection devices of requirement class B in main power supply systems (upstream of the meter) If a lightning arrester of requirement class B is to be installed, it must be installed in accordance with the lightning protection zone concept to DIN VDE 0185 Part 103 in the region of lightning protection zone 0 to 1. In most cases the arrester is installed where the power lines enter the building. If the meter is not located directly at lightning protection zone 0 to 1, it may be necessary to install lightning arresters of requirement class B in the unmetered region. 4. 5. 6. Preconditions Several points must be considered when choosing and installing arresters in the unmetered region. The VDEW has published guidelines for the use of surge protection devices of requirement class B in main power supply systems (01/98). 1. Surge protection devices of requirement class B to DIN VDE 0675 Part 6 (A1, A2) are used. They are chosen, and their parameters are set up, in accordance with DIN VDE 0100-534 (A1). 2. It is essential to ensure that the surge protection device is permanently isolated from the mains in the event of an internal short-circuit. 3. The ability of the surge protection device to carry lightning current must conform to the regulations 26 7. 8. in force where it is installed, in accordance with DIN VDE 0185 Part 100. If the ability to carry lightning current is not known, it must be chosen to suit lightning protection class I to DIN VDE 0100-534. Only surge protection devices that are designed as a spark gap are used. It is not permissible to connect varistors in parallel. The manufacturer guarantees the short-circuit strength of the surge protection devices in accordance with TAB Section 7.2. Voltage surge protection devices of requirement class B must always be installed in combination with the correctly chosen current surge protection devices, approved by the manufacturer for this purpose – especially housings with protection IP 54 with protective insulation. It must be possible to lead-seal the protectively-insulated housings of surge protection devices in accordance with the “lead-sealing requirements” issued by the VDEW. The surge protection devices must be checked at least every four years to ensure that they are in perfect condition. Electricity supply companies may demand relevant proof. ÜSS_D_V0_30102000 Application Please always state the order number when ordering. Solution Condition Re 1: OBO LightningControllers MC 50-B/VDE and MC 125-B/NPE/VDE are lightning arresters of requirement class B to DIN VDE 0675 Part 6 (A1, A2) as well as class I to IEC 61643-1 (02/98), and fulfil the conditions for use in the unmetered region. Fulfils n Re 2: Section 2 of the requirements is met by the fuses before the lightning arrester (max. 500 A without separate upstream fuse). Fulfils n Re 3: Section 3 of the requirements is met by the 50 kA lightning current capacity of OBO LightningController MC 50-B/VDE. Note that the maximum lightning current directed into the building is 100 kA and that it is shared between the conductors that leave the building. Fulfils n Re 4: The operation of OBO LightningControllers is based on the principle of multiple spark gaps which conform to the requirements of Section 4. Fulfils n Re 5: It has been shown in several tests that a surge current withstand strength of 25 kA is achieved by OBO LightningController MC 50-B/VDE, using the principle of multiple spark gaps. Fulfils n Re 6 and 7: Since the spark gap of the OBO LightningController is enclosed, no plasma arcs are produced outside the casing. The arrester can therefore be used in any commercially available housing that meets the requirements of Sections 6 and 7. Fulfils n Re 8: The requirements of Section 8 for the testability of class B surge protection devices in the VDEW guideline are comprehensively met by the use of a plug-in upper part. Fulfils n Result MC 50-B/VDE Call our hotline for further information on the subject of “the use of class B surge protection devices in main power supply systems (upstream of the meter)”. Ordering data VG... series: LightningController mounted in an IP 65 (sealable) housing of insulating material. Type Description VG3-B/TNC Triple-pole (MC 50-B/VDE) for TN-C1) VG4-B/TNS+TT Four-pole (3+1-Var.) for TN-S, TT, IT1) Order no. 5089 21 2 5089 20 0 ÜSS_D_V0_30102000 SA... series: LightningController mounted on adapter rail (adapter width 108 mm) for simple and professional installation on 40 mm busbar systems (12 x 5 and 12 x 10). Type Description Order no. SA3-B/TNC SA4-B/TNS+TT Triple-pole (MC 50-B/VDE) for TN-C1) Four-pole (3+1-Var.) for TN-S, TT, IT1) 5089 50 6 5089 51 4 Please always state the order number when ordering. 1) Supply system 27 Basic line protection Decoupling inductance LightningCoordinator LC 63 Operation and fields of application If there are several surge protection devices in a network, they may influence each other, and this may mean that the parallel arresters must be coordinated in terms of energy. The effect of this coordination is that, in the event of a voltage surge due to lightning, the lightning arrester (class B) responds reliably, diverting the high-energy currents, so protecting the other surge arrester(s) (class C or D) from overload. This energy coordination is provided by LightningCoordinator type LC 63. This device establishes coordination between spark-gap lightning arresters (requirement class B) and varistor-based surge arresters (requirement class C). The LightningCoordinator also ensures the coordination of NPE arresters of different requirement classes. It is only necessary to install the LightningCoordinator if the distance between lightning arrester and surge arrester at the zone interfaces (total line length) is not more than five meters. Where this is the case, the natural inductances of the conduction path are not sufficient, and a decoupling inductance must therefore be connected between the protection devices which operate in different ways. Typical fields of application are compact surge protection installations in a separate housing, and installations with arresters of requirement classes B and C inside a distribution board. The good commutation properties of the LightningCoordinator are due to its optimally arranged inductance. The large cross-section of the strip-shaped coil conductor gives a low DC resistance, resulting in only a slight temperature rise in normal operation. Input Output Block diagram of LC 63 Mounting LightningCoordinator type LC 63 is designed for snap-fitting to standard commercial 35 mm top-hat rails. It is connected to integral terminals in the coil housing. 28 TBS_GB_V0_15072002 Other marks Please always state the order number when ordering. Technical data OBO LightningCoordinator Type LC 63 Nominal voltage UN < 500 V / 50-60 Hz Rated load current IL 63 A Inductance (50-60 Hz) Ln 5 µH ± 10% DC resistance Rcu 1 mΩ Temperature rise ∆T 45 K (63 A) ϑ -40 °C to +85 °C Max. required series fuse 63 A gL/gG Temperature range IP Code to IEC 60 529 / EN 60 529 IP 20 10-50 / 10-25 / 10-35 mm2 AWG 8-2 Connection cross-section rigid/flexible/stranded Tightening torque (MA) at least 4 Nm Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Dimensions to DIN 43880 Height Width Depth 100 mm 35 mm 75 mm Subject to technical alterations Ordering data Complete Order no. 35 49.5 5096 97 0 TBS_GB_V0_15072002 44.8 LC 63 Description 100 Type Features at a glance LC 63 Advantages in use Compact design in a 35 mm housing Space-saving surge protection concept Two connection options, for one or two outputs Simple installation via several terminals Rated current up to 63 A Elements up to max. 63 A in the conductor branch can be decoupled Outstanding inductive characteristics with transient and energy-rich lightning currents Reliable operation of the lightning arrester guaranteed in the event of a fault Separate channel in the lower side area Further possibility for direct connection Please always state the order number when ordering. 29 Basic line protection LPZ 0 → 2 Lightning/surge arresters CombiController V 25-B+C, V 25-B+C/...+NPE Lightning and surge arrester V 25-B+C ensures lightning protection potential equalisation in accordance with VDE 0185, Part 1 and Part 100. The device is an arrester of requirement Class B+C to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2. It ensures potential equalisation for the energy supply line in lightning protection installations for buildings. The arrester can also be used in buildings that are supplied with power via an overhead line, since direct or partial lightning currents may be expected there as well. Version V 25-B+C/3+NPE (requirement Class B+C) is a special surge arrester for TN-C-S, TN-S, TT and IT systems. This device was developed for the new requirements of DIN VDE 0100, Part 534/A1, to allow simple, safe installation of the devices. High-performance arrester OBO V 25-B+C has a special varistor circuit made up of powerful zinc oxide varistors with a highly non-linear characteristic (a>30). This design ensures maximum protection Test marks 30 even with powerful surges. Even at a maximum load Imax of 50 kA the protection level is below 1.5 kV. This enables this type of device to withstand even partial lightning currents from direct lightning strikes. In the event of an overload, the built-in isolating device isolates the faulty arrester module from the network and indicates this with a red field. Because of the low residual voltage, OBO lightning arrester V 25-B+C can also be used as a combined arrester B and C. Service location in accordance with VDS 2031. Mounting The OBO V 25-B+C can easily be installed in any distribution box or switchgear cabinet by snap-fitting to any commercial 35 mm top-hat rail. The NPE arrester element type C 25-B+C/NPE and the matching base are designed so that they cannot be plugged in the wrong way round (coding). This ensures correct installation of the upper parts of the arresters. Other marks TBS_GB_V0_15072002 Operation and fields of application Please always state the order number when ordering. Ordering data Type V 25-B+C/1 V 25-B+C/2 V 25-B+C/3 V 25-B+C/4 V 25-B+C/3+NPE Description Order no. 1-pole, complete1); 280 V 2-pole, complete1); 280 V 3-pole, complete1); 280 V TN-C 4-pole, complete1); 280 V TN-S 3+1-pole, complete1) 280 V TT + IT 5097 04 5 5097 01 0 5097 00 2 5097 03 7 5097 40 1 V 25-B+C/2-385 5097 09 6 2-pole, complete1); 385 V V 25-B+C/4-385 5097 10 0 4-pole, complete1); 385 V V 25-B+C/3+NPE-385 3+1-pole, complete1) 385 V TT + IT 5097 10 3 V 25-B+C/0-150 V 25-B+C/0-280 V 25-B+C/0-385 Upper part; 150 V version Upper part; 280 V version Upper part; 385 V version 5097 08 8 5097 05 3 5097 06 1 C 25-B+C/NPE Upper part NPE spark gap 5095 60 3 V 25-B+C/4-G 4-pole V 25-B+C in insulating material housing (IP 65); 280 V 5097 25 8 1) Complete = upper part and base The V 25-B+C/... is also available on request in a 150 V and a 385 V version. TBS_GB_V0_15072002 Suitable bases for V 25-B+C, see page 35 Features at a glance V 25-B+C Advantages in use Simple installation via the marked terminals Arresters still work after frequent operation Combined arresters B and C for compact applications One arrester in main distribution board is sufficient Plug-in upper part A faulty arrester module can be changed with the mains voltage on Pre-wired arrester blocks, 1-4-pole blocks Easy to install Thermal isolating device with optical indication Permanent check of arrester serviceability Arrester with NPE spark gap in one module Certainty in TN-S, TT and IT systems that no voltage can reach the protective earth (PE) conductor C 25-B+C/NPE with protection against reversed insertion (coding) Simple, professional installation of the arrester modules Please always state the order number when ordering. 31 Technical data CombiController lightning arrester V 25-B+C Description Maximum continuous operating voltage (max. permitted operating voltage) Uc AC Uc DC 150 280 385 150 V~ 200 V - 280 V~ 350 V - 385 V~ 505 V - LPZ 0→2 Requirement class to DIN VDE 0675, Part 6 (Draft 11.89) A1, A2 to IEC 61643-1 B+C class I-class II Tested to Test currents to DIN VDE 0675, Part 6, A1 + A2 Nominal discharge current Max. discharge current per block CombiController V 25-B+C/1... CombiController V 25-B+C/2... CombiController V 25-B+C/3... CombiController V 25-B+C/4... IEC 61643-1, prEN 61643-1, E DIN VDE 0675-6:1989-11 and Part 6/A1 In (8/20). 30 kA Imax (8/20) 50 kA 100 kA 150 kA 200 kA Maximum discharge current (8/80) in accordance with VdS 2031 for CombiController V 25-B+C/4... Imax 100 kA Surge voltage test (10/350) with the lightning current parameters set out in IEC 61312-1 (02.95) Impulse current Iimp Charge Q Specific energy W/R 8 kA 4 As 16 kJ/Ω 7 kA 3.5 As 12 kJ/Ω 7 kA 3.5 As 12 kJ/Ω Voltage protection level at 1 kA (8/20) at 5 kA (8/20) at In Up Up Up ≤450 V ≤500 V ≤600 V ≤650 V ≤700 V ≤900 V ≤1.0 kV ≤1.2 kV ≤1.5 kV Response time tA < 25 ns Short-circuit withstand strength 25 kA with max. upstream fuse 160 A gl/gG 2.5-25 mm2 (fine-stranded with core end sleeves) 2.5-35 mm2 (single and multi-stranded) Connection cross-section Mounting on 35 mm top-hat rail to EN 50022 IP Code Temperature range IP 20 -40 °C to +80 °C ϑ Spark gap CombiController NPE C 25-B+C/NPE Maximum continuous operating voltage Uc 255 V / 50-60 Hz Insulation resistance at 100 V Rins >10 GΩ Surge voltage test (10/350) with the lightning current parameters set out in IEC 61312-1 (02.95) Impulse current Iimp Charge Q Specific energy W/R 25 kA 12.5 As 160 kJ/Ω Nominal discharge current In (8/20) Voltage protection level Up ≤1.2 kV 50 kA Response time tA ≤100 ns Follow current at Uc If 100 Arms Temperature range ϑ -40 °C to +80 °C 32 TBS_GB_V0_15072002 Subject to technical alterations Please always state the order number when ordering. L1 L2 61.5 L3 1 54 L L 90 L 2 PE Block diagram of V 25-B+C/3 L1 Dimension drawing L2 L3 61.5 N 1 72 L L L 90 L 2 PE Block diagram of V 25-B+C/4 L1 L2 Dimension drawing L3 PE 72 61.5 1 L 3 L L 90 2 N Block diagram of V 25-B+C/3+NPE L2 L3 180 L1 Dimension drawing N 1 2 110 PE 182 Block diagram of V25-B+C/4-G Dimension drawing TBS_GB_V0_15072002 Key 1) Thermal isolating device 2) Metal-oxide varistor 3) NPE sum current spark gap Please always state the order number when ordering. 33 Basic line protection LPZ 1 → 2 Surge arresters SurgeController V 20-C, V 20-C/...+NPE SurgeControllers V 20-C are surge arresters of requirement class C to DIN VDE 0675, Part 6 (Draft 02.89) A1, A2. These devices protect low-voltage consumer installations from voltage surges of all kinds. They are available in single-pole to four-pole versions. Type V 20-C/3+NPE (requirement class C) is a special surge arrester for TN-C-S, TN-S, TT and IT systems. This device was developed for the new requirements of DIN VDE 0100, Part 534/A1, to allow simple, safe installation of the devices. The voltage-dependent active part of the V 20-C is a high-performance zinc oxide varistor with a highly non-linear characteristic. Among the advantages of this component are an extremely short response time, a low protection level and a high current diversion capacity, combined with long life. A further feature of Test marks 34 these devices is that no follow-up current can be registered after the surge has decayed. If the surge arrester is damaged by overloading, the integral isolating device breaks the connection to the mains. This is signalled by a red fault indicator. Mounting The V 20-C can easily be installed in any distribution box or switchgear cabinet by snap-fitting to any commercial 35 mm top-hat rail. The poles of multi-pole arresters are connected together by an earthing bridge at the factory, so that there is only one earth (PE) connection to make on site. The NPE arrester element type C 25-B+C/NPE and the matching base are designed so that they cannot be plugged in the wrong way round (coding). This ensures correct installation of the upper parts of the arresters. Other marks TBS_GB_V0_15072002 Operation and fields of application Please always state the order number when ordering. Ordering data Type Description Order no. Type V 20-C/1 V 20-C/2 V 20-C/3 V 20-C/4 V 20-C/1+NPE V 20-C/3+NPE 1-pole complete1); 280 V 2-pole complete1); 280 V 3-pole complete1); 280 V, TN-C 4-pole complete1); 280 V, TN-S 1+1-pole complete1); 280, V 3+1-pole complete1); 280 V, TT+IT 5099 42 0 5099 43 9 5099 44 7 5099 45 5 5095 61 1 5095 64 6 V 20-C/1-385 V 20-C/2-385 V 20-C/3-385 V 20-C/4-385 V 20-C/1+NPE-385 V 20-C/3+NPE-385 V 20-C/0- 75 V 20-C/0-150 V 20-C/0-280 V 20-C/0-335 V 20-C/0-385 V 20-C/0-440 V 20-C/0-550 Upper part; 75 V version Upper part; 150 V version Upper part; 280 V version Upper part; 335 V version Upper part; 385 V version Upper part; 440 V version Upper part; 550 V version 5099 57 9 5096 70 7 5099 60 9 5099 85 0 5099 59 5 5099 70 6 5099 61 7 C 25-B+C/NPE Upper part NPE spark gap 5095 60 3 V 20-C/U-1 1-pole base2) V 20-C/U-2 2-pole base2) V 20-C/U-3 3-pole base2) V 20-C/U-4 4-pole base2) V 20-C/U1+NPE 1+1 pole base2) V 20-C/U3+NPE 3+1 pole base2) 1) Complete = upper part and base 2) Suitable for V 25-B+C and V 20-C V 20-C/3-G 3-pole V 20-C arrester in insulating ma- 5099 49 8 terial housing (IP 65); 280 V version 4-pole V 20-C arrester in insulating ma- 5099 52 8 terial housing (IP 65); 280 V version V 20-C/4-G Description 1-pole complete1); 385 V 2-pole complete1); 385 V 3-pole complete1); 385 V 4-pole complete1); 385 V 1+1-pole complete1); 385 V 3+1-pole complete1); 385 V Order no. 5099 16 1 5099 13 7 5099 19 6 5099 14 5 5095 68 9 5095 70 0 5099 63 3 5099 64 1 5099 66 8 5099 67 6 5095 86 7 5095 87 5 The V 20-C/... is also available on request in a 75 V, 150 V, 335 V and a 550 V version. Advantages in use Metal-oxide varistor Arresters still work after frequent operation Plug-in upper part An arrester module can be changed with the mains voltage on Pre-wired arrester blocks, 1-4-pole blocks Simple installation via the marked terminals Thermal isolating device with optical indication Permanent check of arrester serviceability Arrester with NPE spark gap in one module Certainty in TN-S, TT and IT systems that no voltage can reach the protective earth (PE) conductor C 25-B+C/NPE with protection against reversed insertion (coding) Simple, professional installation of the arrester modules TBS_GB_V0_15072002 Features at a glance V 20-C Please always state the order number when ordering. 35 Technical data SurgeController surge arrester V 20-C Description Maximum continuous operating voltage (max. permitted operating voltage) Uc AC Uc DC 75 150 280 335 385 440 550 75 V~ 100 V- 150 V~ 200 V- 280 V~ 350 V- 335 V~ 420 V- 385 V~ 505 V- 440 V~ 585 V- 550 V~ 745 V- LPZ 1→2 Requirement class to VDE 0675, Part 6 (Draft 11.89) A1, A2 to IEC 61643-1 C class II Tested to IEC 61643-1, prEN 61643-1, E DIN VDE 0675-6:1989-11 and Part 6/A1 Nominal discharge current of the upper part Max. discharge current per block In (8/20) 15 kA 20 kA Imax (8/20) SurgeController V 20-C/1... SurgeController V 20-C/2... SurgeController V 20-C/3... SurgeController V 20-C/4... Maximum discharge current of the upper part Voltage protection level Response time tA Short-circuit withstand strength 25 kA with max. upstream fuse 40 kA ≤300 V ≤350 V ≤400 V ≤500 V ≤650 V ≤700 V ≤900 V ≤1.1 kV ≤1.4 kV ≤1.0 kV ≤1.3 kV ≤1.6 kV ≤1.2 kV ≤1.5 kV ≤1.8 kV Mounting ≤1.7 kV ≤2.1 kV ≤2.5 kV <25 ns 125 A gL/gG Snap-fitting on 35 mm top-hat rail to DIN EN 50 022 IP Code IP 20 ϑ Spark gap CombiController NPE -40 °C to +80 °C C 25-B+C/NPE Maximum continuous operating voltage Uc 255 V /50-60 Hz Insulation resistance at 100 V Rins >10 GΩ Impulse current Charge Specific energy Iimp Q W/R 25 kA 12.5 As 160 kJ/Ω Nominal discharge current In (8/20) Voltage protection level Response time ≤1.5 kV ≤1.8 kV ≤2.2 kV 2.5-35 mm2 (single and multi-stranded); 2.5-25 mm2 (fine-stranded with core end sleeves) Connection cross-section Temperature range 40 kA 75 kA 110 kA 150 kA Imax (8/20) at 1 kA (8/20) Up at 5 kA (8/20) Up at In Up 15 kA 50 kA ≤1.2 kV tA ≤100 ns Follow current at Uc If 100 Arms Temperature range ϑ -40 °C to +80 °C 36 TBS_GB_V0_15072002 Subject to technical alterations Please always state the order number when ordering. L1 L2 L3 61.5 54 1 90 2 3 PE Dimension drawing Block diagram of V 20-C/3 L1 L2 L3 N 61.5 72 1 90 2 3 PE Dimension drawing Block diagram of V 20-C/4 L1 L2 L3 PE 61.5 72 1 4 90 2 3 N Block diagram of V 20-C/3+NPE L2 L3 N 180 L1 Dimension drawing 1 2 110 3 PE 182 Block diagram of V 20-C/4-G Dimension drawing TBS_GB_V0_15072002 Key 1) Dynamic isolating device 2) Thermal isolating device 3) Metal-oxide varistor 4) NPE sum current spark gap Please always state the order number when ordering. 37 Basic line protection Signalling device for CombiController V 25-B+C/FS and SurgeController V 20-C/FS Operation and fields of application Remote signalling allows central monitoring of the serviceability of lightning arresters and surge arresters, even when the devices cannot be observed directly or are installed where access is difficult. 1 2 3 A monitoring module is installed at each arrester block to provide a constant check that all the connected arresters are ready to operate. If an arrester fails, a mechanism passes a command to the microswitch in the monitoring module. This fault signal is then passed to the remote indicating unit, where the fault is indicated optically or acoustically. L1 L2 L3 PE Block diagram of OBO V 20-C/3-FS Mounting The device is installed by snap-fitting to any standard commercial 35 mm top-hat rail. The monitoring unit is easily and quickly installed by means of screwless terminals. 38 Other marks TBS_GB_V0_15072002 Test marks Please always state the order number when ordering. Technical data Signalling device OBO V 25-B+C/FS or V 20-C/FS monitoring module Max. switching voltage U~max. ≤250 V Max. switching current I~max. 6A Connection cross-section single-stranded, multi-stranded, fine-stranded fine-stranded with: core end sleeve, pin cable lug, crimp sleeve 0.14- 2.5 mm2 Stripping length for connecting cables 6-7 mm Signal contact NO (make) NC (break) 1-2 1-3 Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Subject to technical alterations Ordering data Type Description Order no. 61.5 90 4-pole upper part and base with FS3) in insulating material housing (IP 65) 5097 31 2 Description Order no. V 20-C/1-FS V 20-C/2-FS V 20-C/3-FS V 20-C/4-FS V 20-C/1+NPE-FS V 20-C/3+NPE-FS 1-pole complete1) with FS3); 280 V 2-pole complete1) with FS3); 280 V 3-pole complete1) with FS3); 280 V 4-pole complete1) with FS3); 280 V 1+1-pole complete1) with FS3); 280 V 3+1-pole complete1) with FS3); 280 V 5096 00 6 5096 01 4 5096 02 2 5096 03 0 5095 65 4 5095 67 0 V 20-C/3-FS-385 V 20-C/4-FS-385 V 20-C/3+NPE-385 3-pole complete1); with FS3); 385 V 4-pole complete1); with FS3); 385 V 3+1-pole complete1); 385 V 5095 98 0 5095 99 9 5095 73 5 V 20-C/U-1-FS V 20-C/U-2-FS V 20-C/U-3-FS V 20-C/U-4-FS V 20-C/U-1+NPE-FS V 20-C/U-3+NPE-FS 1-pole base2) with FS3) 2-pole base2) with FS3) 3-pole base2) with FS3) 4-pole base2) with FS3) 1+1-pole base2) with FS3) 3+1-pole base2) with FS3) 5096 30 8 5096 31 6 5096 32 4 5096 33 2 5095 84 0 5095 85 9 V 20-C/U-PH-FS 3-pole base2); photovoltaic installations, remote signalling 5096 63 4 V 25-B+C/4-FS-G Type 1) 2) 3) 90 3-pole complete1) with FS3); 280 V V 25-B+C/3-FS 5097 13 4 V 25-B+C/4-FS 4-pole complete1) with FS3); 280 V 5097 14 2 V 25-B+C/3+NPE-FS 3+1-pole complete1) with FS3); 280 V 5097 42 8 Complete = upper part and base Suitable for V 25-B+C and V 20-C FS = remote signalling Versions of V 25-B+C/...-FS and V 20-C/...-FS for other voltages are available on request. TBS_GB_V0_15072002 Features at a glance V 25-B+C/FS, V 20-C/FS Advantages in use Floating contact Voltage level at the signalling device can be freely defined Changeover contact Can be used as NO or NC (make or break) contact Modular construction (only one switch) No additional wiring needed, saving time Spatial separation between signalling device and arrester Prevents mutual influence Please always state the order number when ordering. 39 Basic line protection Acoustic signalling device for CombiController V 25-B+C/AS and SurgeController V 20-C/AS Operation and fields of application 230 V L1 Acoustic signalling is a safety component which permanently checks the serviceability of arresters and indicates a fault by means of a warning tone. Constant self-checking of the arrester fitted with this monitoring module provides unbeatable safety – even without visual inspection. The device is ideal wherever optical signalling does not appear rational or feasible. Examples are dwelling houses, agricultural buildings, banks, office and administration buildings, and so on. The warning tone can be silenced for the next 24 hours by operating a black switch. When the faulty device has been replaced, a green LED indicates that the arrester block is working properly. Test marks 40 L3 PE Block diagram of OBO V 20-C/3-AS Mounting The monitoring module has user-friendly screwless terminals. Installation cost is very low. The arresters are mounted on a top-hat rail in the distribution board. Other marks TBS_GB_V0_15072002 The control module starts an acoustic alarm immediately after the operation of an isolating device. The alarm takes the form of a high-frequency warning tone which can be heard at a considerable distance. In addition, a red LED flashes on the monitoring module. L2 Please always state the order number when ordering. Technical data Signalling device OBO V 25-B+C/AS or V 20-C/AS monitoring module Nominal voltage UN Maximum continuous operating voltage Uc 230 V / 50-60 Hz 250 V Rated load current IL 40 mA Connection cross-section single-stranded, multi-stranded, fine-stranded fine-stranded with: core end sleeve, pin cable lug, crimp sleeve 0.14-2.5 mm2 Stripping length for connecting cables 6-7 mm Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Subject to technical alterations Ordering data Type Description Order no. 90 61.5 3-pole complete1) with AS3); 280 V 4-pole complete1) with AS3); 280 V 5097 18 5 5097 19 3 Description Order no. 2-pole complete1) with AS3); 280 V 3-pole complete1) with AS3); 280 V 4-pole complete1) with AS3); 280 V 5096 37 5 5096 38 3 5096 39 1 Type V 20-C/2-AS V 20-C/3-AS V 20-C/4-AS V 20-C/U-2-AS 2-pole base2) with AS3) V 20-C/U-3-AS 3-pole base2) with AS3) V 20-C/U-4-AS 4-pole base2) with AS3) 1) Complete = upper part and base 2) Suitable for V 25-B+C and V 20-C 3) AS = acoustic signalling L L L L 90 V 25-B+C/3-AS V 25-B+C/4-AS 5096 41 3 5096 42 1 5096 44 8 TBS_GB_V0_15072002 Versions of V 25-B+C/...-AS and V 20-C/...-AS for other voltages are available on request. Features at a glance V 25-B/AS, V 20-C/AS Advantages in use High-frequency warning tone Perceived immediately as a warning signal Muting switch with repeat action Can be used in office buildings with poor access Modular construction No additional wiring - saves time Spatial separation between signalling device and arrester Prevents mutual influence Please always state the order number when ordering. 41 Basic line protection Signalling device for CombiController V 25-B+C/FS-SÜ and SurgeController V 25-B+C/FS-SÜ, V 20-C/FS-SÜ Operation and fields of application 1 2 3 L1 L2 L3 CombiControllers and SurgeControllers used in electrical installations with main fuses rated above 160 A and 125 A respectively are provided with their own fuses. To ensure permanent monitoring of the surge protection, signalling devices V 25-B+C/FS-SÜ and V 20-C/FS-SÜ are installed. The control module monitors all three phases of the arrester and the serviceability of the series-connected fuses. Any drop in the supply voltage and any fault in a fuse, as well as tripping of an isolating device in the arrester module, is registered immediately and indicated by remote signalling. The duct on top of the arrester block covers the connections of the monitoring module to the three-phase network. In this way the applied voltage is monitored. Not only the failure of an arrester is registered, but also the failure of a series-connected fuse. Mounting The standard 17.5 mm case of the V 25-B+C/FS-SÜ and V 20-C/FS-SÜ snap-fits to a 35 mm top-hat rail. Screwless terminals keep installation time short. PE Block diagram of OBO V 20-C/3-FS-SÜ >125 A gl or >160 A gl L1 L2 L3 PEN 160 A gl with V 25-B+C or 125 A gl with V 20-C V 25-B+C/FS-SÜ or V 20-C/FS-SÜ Installation example 42 Other marks TBS_GB_V0_15072002 Test marks Please always state the order number when ordering. Technical data Signalling device OBO V 25-B+C/FS-SÜ or V 20-C/FS-SÜ monitoring module Nominal voltage UN Rated load current IL 3/400 V (50-60 Hz) 12 mA Switching voltage U 0 ... 250 V Max. switching voltage U~max. Max. switching current I~max. 250 V 3A 0.14-2.5 mm2 Connection cross-section single-stranded, multi-stranded, fine-stranded fine-stranded with: core end sleeve, pin cable lug, crimp sleeve Stripping length for connecting cables 6-7 mm Signal contact NO (make) NC (break) 1-2 1-3 Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50022 Subject to technical alterations Ordering data V 25-B+C/3-FS-SÜ V 25-B+C/4-FS-SÜ Description 3-pole complete1) with FS-SÜ3); 280 V 4-pole complete1) with FS-SÜ3); 280 V Type Description Order no. 90 L 5097 11 8 5097 35 5 L L L FS Order no. V 20-C/3-FS-SÜ V 20-C/4-FS-SÜ 3-pole complete1) with FS-SÜ3); 280 V 4-pole complete1) with FS-SÜ3); 280 V 5096 25 1 5096 27 8 V 20-C/U-3-FS-SÜ V 20-C/U-4-FS-SÜ 3-pole base2) with FS-SÜ3); 4-pole base2) with FS-SÜ3); 5096 35 9 5096 36 7 1) Complete = upper part and base 2) Suitable for V 25-B+C and V 20-C 3) FS-SÜ = remote signalling and voltage 61.5 90 Type monitoring TBS_GB_V0_15072002 Versions of V 25-B+C/...-FS-SÜ and V 20-C/...-FS-SÜ for other voltages are available on request. Features at a glance V 25-B+C/FS-SÜ, V 20-C/FS-SÜ Advantages in use Immediately indicates the failure of only one phase Simultaneous monitoring of the voltages on the load Remote signalling and voltage monitoring in one housing Saves space Floating contact Freely definable voltage level at the signalling device Changeover contact Can be used as NC or NO (break or make) contact Please always state the order number when ordering. 43 Basic line protection Surge arrester SurgeController V 20-C/U-PH Mounting Surge arrester V 20-C/U-PH is designed for snapfitting to 35 mm top-hat rails. In versions with monitoring module, installation is made easier by screwless terminals. Note: The upper parts of the V 25-B+C must be used when connecting the external lightning protection installation to the solar modules. Solar modules Operation and fields of application V 20-C/U-PH is the basic building block for the surge protection of photovoltaic installations. The simple connection of the plus, minus and earth wires allows optimum protection in the branch distribution box directly behind the photovoltaic module, before the inverter. The basic building block is available in versions for remote or acoustic signalling. The upper parts required are ordered separately. For an application example, see page 112. House with photovoltaic installation. 1 2 Branch distribution box V 20-C/U-PH Test joint Distribution board with inverter, overvoltage and undervoltage monitoring and FI safety switch Circuit distribution board with circuit-breakers and surge arresters 3 V 20-C/... Solar current meter 3 to electricity supply company Block diagram of V 20-C/U-PH 1) Dynamic isolating device 2) Thermal isolating device 3) Metal-oxide varistor 44 TBS_GB_V0_15072002 Other marks Please always state the order number when ordering. Technical data Surge arrester V 20-C/U-PH Description Base 2.5-35 mm2 (single and multi-stranded); 2.5-25 mm2 (fine-stranded with core end sleeves) Connection cross-section Mounting Snap-fitting on 35 mm top-hat rail to DIN EN 50 022 Temperature range -40 °C to +80 °C ϑ Monitoring module Nominal voltage UN Max. continuous operating voltage Uc Max. switching current Imax. Rated load current IL Remote signalling (FS) Acoustic signalling (AS) 0 ... 250 V 230 V~ 250 V~ 250 V~ 6 A~ - - 40 mA 0.14-2.5 mm2 Connection cross-section Signal contact NO (make) NC (break) 1-2 1-3 Subject to technical alterations Ordering data Type Description Order no. 50 V 20-C/U-PH V 20-C/U-PH-FS 5096 62 6 5096 63 4 Upper parts must be chosen to suit the voltage of the photovoltaic installation: Arrester type for single module V 20-C/0-75 V 20-C/0-150 V 20-C/0-280 V 20-C/0-335 V 20-C/0-385 V 20-C/0-440 V 20-C/0-550 Max. no-load voltage of solar module Number required Order no. 100 V 200 V 350 V 420 V 505 V 585 V 745 V 3 3 3 3 3 3 3 5099 57 9 5096 70 7 5099 60 9 5099 85 0 5099 59 5 5099 70 6 5099 61 7 90 Suitable for V 25-B+C and V 20-C 89.8 1) 3-pole base1) 3-pole base1) with remote signalling 53.4 When connecting the external lightning protection installation to the solar modules, use arrester V 25-B+C: Arrester type for single module V 25-B+C/0-150 V 25-B+C/0-280 V 25-B+C/0-385 Max. no-load voltage of solar modules Number required Order no. 170 V 350 V 500 V 3 3 3 5097 08 8 5097 05 3 5097 06 1 TBS_GB_V0_15072002 Features at a glance V 20-C/U-PH Advantages in use Base suitable for V 20-C and for V 25-B+C Can be used as a lightning arrester or as a surge arrester Pre-wired arrester blocks Professional installation Marked terminals Easy to install Suitable for special voltages Universal for the most common photovoltaic systems Please always state the order number when ordering. 45 Basic line protection ISOLAB checking system ISOLAB, which has been tested by the VDE, is an insulation and arrester tester. This combination device can be used for insulation testing of electrical installations to DIN VDE 0100/Part 610 as well as to determine the characteristics of the upper parts of type V 25-B+C and V 20-C. The ISOLAB tester is also suitable for checking the insulation performance of LightningControllers MC 50-B/VDE and MC 125-B/NPE. 1. Insulation measurement Before insulation testing starts, the mains voltage must be switched off. In other words, there must be no voltage on any part of the installation. When the test leads have been connected, insulation testing is Test marks 46 started by pressing the start button. The resistance reading appears on the display. (Note: before insulation testing, the upper parts of arresters must be removed and other surge protection devices must be disconnected.) 2. Arrester test The selector switch is used to select the type of module to be tested (V 25-B or V 20-C). Plugging in the upper part starts the test procedure automatically. The 1 mA or 3 mA point can be read off on the display. By comparing the results with the printed tolerance field table, it is possible to tell whether the arrester has suffered ageing and needs to be replaced. Note: test leads are supplied with the tester. Other marks TBS_GB_V0_15072002 Operation and fields of application Please always state the order number when ordering. Technical data ISOLAB insulation tester Measuring range Error class Test voltage Test current Max. test current 0.5 MΩ-19.99 MΩ ±5% ±0.01 MΩ 500 V 1 mA <10 mA ISOLAB arrester tester Test current V 20-C V 25-B+C 1 mA 3 mA Measuring range Error class Max. test voltage Power supply (device) Nominal discharge current Working temperature Storage temperature Temperature for stated accuracy Battery type Weight Tolerance fields V 20-C/0-75 V V 20-C/0-150 V V 20-C/0-280 V V 20-C/0-330 V V 20-C/0-385 V V 20-C/0-440 V V 20-C/0-550 V 0 V-999 V ±1% ±1 volt 999 V 6V 5 mA 0 °C to +40 °C -10 °C to +50 °C +23 °C ±5 °C R6 AA UM3 (Mignon) 680 g Subject to technical alterations V 25-B+C/0-230 V MC 50-B/VDE MC 125-B/NPE MCD 50-B MCD 125-B/NPE 108 V-132 V 184 V-225 V 387 V-473 V 459 V-561 V 558 V-682 V 643 V-786 V 819 V-1001 V 387 V-473 V to DIN VDE 0100, Part 610 >0.5 MΩ to DIN VDE 0100, Part 610 >0.5 MΩ to DIN VDE 0100, Part 610 >0.5 MΩ to DIN VDE 0100, Part 610 >0.5 MΩ Ordering data National version, Germany National version, United Kingdom Order no. 120 50 5096 79 0 5096 81 2 250 ISOLAB ISOLAB Description TBS_GB_V0_15072002 Features at a glance ISOLAB Advantages in use Testers for testing arresters MC 50-B VDE, MC 125-B/NPE/VDE, V 25-B+C and V 20-C One device for all types of arrester Insulation testing to DIN 0100/Part 610 Service-friendly Arresters can be tested with special voltages Universal device Please always state the order number when ordering. 272 Type 47 Basic line protection Peak Current Sensor PCS monitoring system Operation and fields of application Mounting The Peak Current Sensor records and permanently stores impulse currents on a magnetic card. The magnetic strip of the PCS is encoded in a special way. Since every current-carrying conductor produces a magnetic field proportional to the current, such a magnetic field influences the encoding of the magnetic strip. This change is evaluated and displayed on a special magnetic card reader PCS-CS. This makes it possible to measure impulse current in lightning protection installations and – using the test kits in the equipotential bonding lines – in lightning and surge arresters. In this way, the effectiveness of these protection devices can be checked at any time. The Peak Current Sensor is held in a card holder which is attached to 8 or 10 mm round wire (usual in outdoor lightning protection installations). The card holder secures, protects and positions the magnetic card. Special mounting kits from the OBO range are used for simple, quick installation of the magnetic card on equipotential bonding bars (a) and on lightning arresters in buildings (b). Note: each magnetic card can be evaluated once at the factory free of charge. 48 TBS_GB_V0_15072002 Other marks Please always state the order number when ordering. Technical data Magnetic card reader Nominal voltage Charging time Storage and operating temperature Fuse Measuring range Measurement tolerance Operating time of battery Dimensions UN 230 V / 50-60 Hz 8h -10 °C to +50 °C mt 1.25 A 3-120 kA ≤2 kA about 4 h (continuous operation) 250 x 200 x 380 mm 300 x 200 x 440 mm ϑ F with handle Magnetic card holder Clamping range Material Mounting Dimensions 8-10 mm (round wire) Polypropylene, elastomer seal Clamp mounting 115 x 72 x 7 (17) mm Magnetic card Material Dimensions Polycarbonate 85.7 x 54 mm Ordering data 10 magnetic cards, incl. holder Type PCS-CS-D PCS-CS-GB PCS-CS-F Description Card reader (German version) Card reader (UK version) Card reader (French version) Type PCS Description 10 magnetic cards/pack Description 5091 32 2 Order no. 5091 68 3 5091 69 1 5091 71 3 Order no. PC 5091 43 8 85.5 Order no. PP 60 Type Order no. 10 magnetic card holders/pack 5091 52 7 11 PCS-H 72 MK-B Description 54.5 Type 104 TBS_GB_V0_15072002 Features at a glance PCS Advantages in use Card holder with seal The service-friendly sensor does not require maintenance Magnetic-strip decoding No power supply required Card holder can be lead-sealed Tamper-proof Clamping range of the card holder suitable for 8-10 mm round conductors with snap-fixing Easy to install Please always state the order number when ordering. 49