Diseño de Sistemas Eléctricos I: Residencial y Comercial Dr. Lionel R. Orama Exclusa, PE enero de 2006 Introducción al Diseño I. ¿Qué es diseño? A. B. Trabajo en equipo (arq., inci, inme, inel) Interesante, pero con complicaciones 1. 2. 3. C. D. E. F. 18-Jan-2006 el papel aguanta todo el campo no la sociedad tampoco Limitaciones (“constraints”) que cumplir Certificado por Ingeniero Licenciado Existen Códigos y Reglamentos Ética INEL 4407 © L.R.Orama/ A. Irizarry 2006 2 Puerto Rico’s Laws • Electrical Design must be certified by a licensed engineer • Graduate from a Credited University • Board Exams (“reválida”) must be approved •Fundamental, Professional • Active Member of CIAPR •Two years of supervised engineering experience • The design must comply with: • National Electrical Code (NEC) • “Reglamento Complementario al Código Eléctrico Nacional (AEE)” INEL 4407 © L.R.Orama/ A. Irizarry 2006 3 Proceso de Diseño II. Proceso A. Propuestas de diseño, arq. Solicita costos de electricidad para el proyecto En general, INEL último en comenzar y terminar una vez se aprueba la propuesta La AEE tiene que Endosar el proyecto B. C. 1. 2. Si la carga computada >50kVA (200A) Pasos para solicitar endoso a. b. c. Estudio de campo; líneas y voltaje disponibles Proyectos grandes, estudio de corto circuito Punto de conexión, donde se conectaran las líneas del edificio con las de la AEE INEL 4407 © L.R.Orama/ A. Irizarry 2006 4 Electrical Design for Buildings • Electrical systems do not exist on a vacuum – They are part of a product, a sub-system of an equipment or an structure • In this course we will confine ourselves to design of electrical systems for buildings – Residential - small and large dwellings units, multiple dwellings (apartments) – Commercial – general purpose units, offices, dining – Industrial – basic, light industrial facilities INEL 4407 © L.R.Orama/ A. Irizarry 2006 5 El diseño en sí A. Computo de cargas 1. 2. Tablas para estimados (RS Means-Electrical Cost Data, otros), para propuesta Por diseño, utilizando como guía el NEC B. Circuitos ramales de iluminación C. Circuitos ramales de receptáculos D. Circuitos ramales para cargas de potencia 1. 2. 3. E. F. Acondicionadores de aire Elevadores y escaleras automáticas Otros, equipos de cocina, etc. Alimentadores y paneles de distribución Subestación y bases de contadores INEL 4407 © L.R.Orama/ A. Irizarry 2006 6 National Electrical Code (NEC) • National Fire Protection Association (NFPA) & the American National Standards Institute (ANSI) regards the Code as purely advisory • States make it mandatory i.e. it becomes Law with the exceptions, provisions, clarifications that the State decides to adopt, hence the “Reglamento Complementario al Código Eléctrico Nacional” in Puerto Rico • Can be difficult to read and understand – Reading the NEC from beginning to end is worst than reading a dictionary from beginning to end 20-Jan-2006 INEL 4407 © L.R.Orama/ A. Irizarry 2006 7 NEC Article 90 - Introduction 90-1 Purpose a) Practical Safeguarding. The purpose of the code is the practical safeguarding of persons and property from hazards arising from the use of electricity b) Adequacy – compliance (with the Code) and proper maintenance will result in an installation free from hazard but not necessarily efficient, convenient or adequate for good service or future expansion of electrical use. INEL 4407 © L.R.Orama/ A. Irizarry 2006 8 National Electrical Code Article 90 - Introduction 90-1 Purpose c) Intention. This Code is not intended as a design specification nor an instruction manual for untrained persons. 90-2 Scope a) Covered 1. Installation of electric conductors and equipment within or on public and private buildings or other structures (mobile homes, recreational vehicles, floating bldg, yards, carnivals, parking, other lots, and industrial substations. INEL 4407 © L.R.Orama/ A. Irizarry 2006 9 National Electrical Code Article 90 - Introduction 90-2 Scope b) Not Covered 1. Installations in ships, watercrafts other than floating bldg, railway rolling stock, aircraft, or automobile vehicles other than mobile homes and recreational vehicles. 2. Installations underground in mines 3. Installations of railways for generation, transformation, transmission, or distribution to operate rolling stock, signaling and communications INEL 4407 © L.R.Orama/ A. Irizarry 2006 10 National Electrical Code Article 90 - Introduction 90-2 Scope b) Not Covered 4. Installations of communication equipment under the exclusive control of communication utilities located outdoors or in building spaces exclusively for such installations. 5. Installations under the exclusive control of electric utilities for the purpose of communications, metering, generation, control, transformation, transmission or distribution of electric energy. INEL 4407 © L.R.Orama/ A. Irizarry 2006 11 National Electrical Code Article 90 - Introduction 90-3 Code Arrangement Introduction and nine chapters Ch. 1-4 apply generally Ch. 5-7 special occupancies, special equipment or other special conditions. Ch. 1-4 apply except as amended by Ch. 5-7 for the particular conditions. Ch. 8 covers communications systems and it is independent of the other chapters except where they are specifically referenced therein. Ch. 9 are Tables INEL 4407 © L.R.Orama/ A. Irizarry 2006 12 National Electrical Code Article 90 - Introduction 90-8 Wiring Planning a) Future Expansion and Convenience. • Future expansion via ample space in raceways • Convenience via readily accessible distribution centers b) Number of Circuits in Enclosures. • The number of wires and circuits confined in a single enclosure will be varyingly restricted. • Limiting the number of circuits in a single enclosure will minimize the effects from a short circuit or ground fault in one circuit. INEL 4407 © L.R.Orama/ A. Irizarry 2006 13 Reglamento Complementario al Código Eléctrico Nacional (AEE) • • Published by the Puerto Rico Electric Power Authority (PREPA) – the authority having jurisdiction Defines electrical constructions in three types 1. Tipo 1 – instalaciones eléctricas interiores y exteriores 2. Tipo 2 – distribución eléctrica – urbanizaciones o lotes 3. Tipo 3 – extensiones de líneas eléctricas – instalaciones de líneas para llevar facilidades eléctricas desde líneas de la AEE hasta urbanizaciones, lotes y edificios *For every installation over 50kVA it includes substations 23-Jan-2006 INEL 4407 © L.R.Orama/ A. Irizarry 2006 14 Reglamento Complementario al Código Eléctrico Nacional Seccion II Disposiciones Generales Artículo A. Propósito Establece, junto al NEC, las normas y requisitos mínimos necesarios para garantizar la seguridad de personas y estructuras en la instalación de conductores y equipo eléctrico en Puerto Rico. INEL 4407 © L.R.Orama/ A. Irizarry 2006 15 ANSI Std Y32.9 – 1972 (1989) The standard provides a basis for 1) Showing the general physical location and arrangement of the sections of the required wiring system 2) Identifying the physical requirements for various types of materials needed to provide the electrical installation in buildings INEL 4407 © L.R.Orama/ A. Irizarry 2006 16 Drafting Graphic Symbols • Electrical layouts shall be drawn: – to an appropriate scale or figure dimensions noted – on drawing sheets separate from the architectural or structural drawings or the drawing sheets for mechanical or other facilities. – Clearly. DO NOT lay out on the same drawing sheet all different electrical systems to be installed in the same building area. Use separate drawing sheets for different systems such as signal system outlets and circuits vs. lighting and power branch circuit wiring. INEL 4407 © L.R.Orama/ A. Irizarry 2006 17 Drafting Graphic Symbols • Outlet and equipment locations with respect to the building should be shown as accurately as possible on the electrical drawing sheets to reduce reference to architectural drawings. • All branch circuits, control circuits, and signal system circuits shall be laid out in complete detail on the electrical drawings, including identification of the number, size, and type of all conductors. INEL 4407 © L.R.Orama/ A. Irizarry 2006 18 Drafting Graphic Symbols Complete drawings of the design shall have: • Floor plan layout, to scale, of all outlet and equipment locations and wiring runs • A complete schedule of all of the symbols used with appropriate description of the requirements • Riser diagram showing the physical relationship of the service, feeder and major power runs, unit substations, isolated power transformers, switchboards, panel boards, pull boxes, terminal cabinets, and other systems and equipment. INEL 4407 © L.R.Orama/ A. Irizarry 2006 19 Drafting Graphic Symbols 4) Where necessary for clearness. a single line diagram showing the electrical relationship of the component items and sections of the wiring system. 5) Where necessary to provide adequate information, elevations, sections and details of equipment and special installations, and details of special lighting fixtures and devices 6) Sections of the building or elevation of the structure showing floorto-floor, outlet, and equipment heights, relation to the established grade, general type of building construction, etc. Where practicable, suspended ceiling heights indicated by figure dimensions on either the electrical floor plan layout drawings or on the electrical building section or elevation drawings INEL 4407 © L.R.Orama/ A. Irizarry 2006 20 Drafting Graphic Symbols 7) Where necessary to provide adequate information, plot plan to scale, showing the relation of the building or structure to other buildings or structures, service poles, service manholes, exterior area lighting, exterior wiring runs, etc 8) In the case of exterior wiring systems for street and highway lighting, area drawings showing the complete system 9) Any changes to the electrical layout should be clearly indicated on the drawings, when such changes are made after the original drawings have been completed, and should be identified on the drawing by a revision symbol INEL 4407 © L.R.Orama/ A. Irizarry 2006 21 Examples of Electrical Symbols on an Architectural Plan Outlet (“salida”)– a point on a wiring system where current is taken to supply utilization equipment • receptacle outlet – an outlet where one or more receptacles are installed receptacle outlets symbols single duplex IG WP Insulated Ground Water Proof Ground Fault Circuit Interrupter triplex GFCI F Fan C Clock Floor Outlet Floor Single Floor Duplex Single Floor Special Purpose INEL 4407 © L.R.Orama/ A. Irizarry 2006 R D Range Clothes Dryer 22 Examples of Electrical Symbols on an Architecturallighting Planoutlets symbols lighting outlet – an outlet intended for the direct connection of a lampholder, lightning fixture, or a pendant cord terminating in a lampholder. incandescent incandescent wall surface fluorescent X RX J surface or pendant exit X recessed exit RX junction box J INEL 4407 © L.R.Orama/ A. Irizarry 2006 surface fluorescent wall surface or pendant exit (wall) recessed exit (wall) junction box wall 23 Examples of Electrical Symbols on an Architectural Plan Switch symbols S single-pole S2 double-pole S3 three-way S4 four-way SD door SDS dimmer SK key SWP water proof Circuiting symbols cable or raceway contains two wires three wires on cable or raceway wiring concealed in ceiling or wall wiring concealed in floor wiring exposed CO INEL 4407 © L.R.Orama/ A. Irizarry 2006 conduit only 24 Examples of Electrical Symbols on an Architectural Plan push button lighting panel buzzer power panel bell heating panel telephone (private system) T transformer TV television outlet telephone (outside line) T thermostat M motor circuit breaker overcurrent protection device INEL 4407 © L.R.Orama/ A. Irizarry 2006 25 System voltages There may be several system voltages available to supply a given load but not all service voltages are available for any load. • 3Ø service may not be available for residential loads • For 3Ø service a minimum load may be required • Minimum service voltage may be specified for large loads INEL 4407 © L.R.Orama/ A. Irizarry 2006 26 RC Secc IV. Artículo N: Clases de servicio 1. Monofásico, 120/240 V, 3 hilos. Es el servicio más común para cargas monofásicas. 120 V 240 V 120 V Voltaje primario de distribución - Al presente la AEE tiene 4 voltajes de distribución: 4.16, 7.2, 8.32 y 13.2 kV. Las subestaciones de distribución se conectan al sistema de transmisión a través de 38 ó 115 kV y sus capacidades varían desde 3.0 MVA hasta 50.0 MVA. Toda subestación nueva se construye a 13.2 kV y su capacidad será de 22.4 MVA si se conecta a voltaje 38 kV (estrella-estrella). Si la subestación se conecta a 115 kV su capacidad podría ser de 33.6 ó 44.8 MVA (delta-estrella), según las proyecciones de carga. INEL 4407 © L.R.Orama/ A. Irizarry 2006 27 120 V 240 V 120 V INEL 4407 © L.R.Orama/ A. Irizarry 2006 28 a c b INEL 4407 © L.R.Orama/ A. Irizarry d 2006 1Ø transf. connections (a) and (b) show two secondary coils rated at 120 V connected in parallel to supply a two-wire 120 V circuit. No longer used. (c) and (d) show two secondary coils rated at 120 V connected in series to supply a threewire 120/240 V circuit. 29 RC Secc IV. Artículo N: Clases de servicio 2. Trifásico, 208Y/120 V, 4 hilos. Común para cargas trifásicas pequeñas. 120 V 208 V 208 V 120 V 208 V primario en ∆ 120 V Sirve cargas trifásicas a 208 y cargas monofásicas a 208 y 120 V INEL 4407 © L.R.Orama/ A. Irizarry 2006 30 3Ø transformer connections – ∆Y four wire grounded secondary INEL 4407 © L.R.Orama/ A. Irizarry 2006 31 RC Secc IV. Artículo N: Clases de servicio 3. Trifásico, 480Y/277 V, 4 hilos. Común para cargas trifásicas mayores. 277 V 480 V 480 V 277 V 480 V primario en ∆ 277 V Sirve cargas trifásicas a 480 y cargas monofásicas a 277 y 480 V INEL 4407 © L.R.Orama/ A. Irizarry 2006 32 Otros (NO en RC) Trifásico, 240 V (ó 480) V, 3 hilos. A 240 V (ó 480 V) B C 240 V (ó 480 V) primario en ∆ Sirve cargas trifásicas a 240 V (ó 480 V) entre las fases A, B y C Sirve cargas monofásicas a 240 V (ó 480 V) entre dos fases INEL 4407 © L.R.Orama/ A. Irizarry 2006 33 RC Secc IV. Artículo B: Asuntos Generales • Se requiere subestación (1Ø ó 3Ø) para cualquier tipo de edificio con carga calculada mayor de 50 kVA. • Cualquier edificion con carga estimada que no exceda 75 kVA 1Ø ó 150 kVA 3Ø puede servirse de un transformador o banco de transformadores instalado en poste de hormigón de 40 pies mínimo (o entre dos postes de hormigón de 40 pies mínimo o estructura de metal certificada para servir graveros, hormigoneras y edificios en construcción). • En areas con problemas de espacio se permitirá, con permiso de la AEE, subestaciones 1Ø de 75 kVA en postes de la AEE si la subestación sirve más de un cliente. INEL 4407 © L.R.Orama/ A. Irizarry 2006 34 References 1. NFPA 70, National Electrical Code, NFPA, 2005. 2. Reglamento Complementario al Código Eléctrico Nacional, AEE, 2000. 3. ANSI Std Y32.9 – 1972 (1989) American National Standard Graphic Symbols for Electrical Wiring and Layout Diagrams Used in Architecture and Building Construction. American National Standard Institute. INEL 4407 © L.R.Orama/ A. Irizarry 2006 35