Engineering Data Minimum Wire Bending Space Minimum wire bending space at terminals and minimum width of wiring gutters NEC Table 312.6(A) AWG OR CIRCULAR-MIL SIZE OF WIRE 14–10 8–6 4–3 2 1 1/0–2/0 3/0–4/0 250 kcmil 300–350 kcmil 400–500 kcmil 600–700 kcmil 750–900 kcmil 1000–1250 kcmil 1500–2000 kcmil 1 MM WIRES PER TERMINAL 3 MM IN. – – – – – – – – – – – – – – 203 8 203 8 254 10 254 10 305 12 356 14 – – 2 IN. Not specified 38.1 1 1⁄ 2 50.8 2 63.5 2 1⁄ 2 76.2 3 88.9 3 1⁄ 2 102 4 114 4 1⁄ 2 127 5 152 6 203 8 203 8 254 10 305 12 MM IN. – – – – – – 127 152 152 203 203 254 305 – – – – – – – 5 6 6 8 8 10 12 – 4 5 MM IN. MM IN. – – – – – – – – 254 305 305 356 406 – – – – – – – – – 10 12 12 14 16 – – – – – – – – – – – 456 406 457 – – – – – – – – – – – 14 16 18 – Bending space at terminals shall be measured in a straight line from the end of the lug or wire connector (in the direction that the wire leaves the terminal) to the wall, barrier or obstruction. Minimum wire bending space at terminals NEC Table 312.6(B) Engineering Data WIRE SIZE (AWG OR KCMIL) COMPACT STRANDED ALL OTHER AA-8000 ALUMINUM CONDUCTORS ALLOY CONDUCTORS (SEE NOTE 3.) 12 14–10 8 6 4 3 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000 12-8 6 4 2 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700-750 800-900 1000 – – – – – – – – WIRES PER TERMINAL 2 1 MM IN. Not Specified 38.1 11⁄ 2 50.8 2 76.2 3 76.2 3 88.9 31⁄ 2 114 41⁄ 2 140 51⁄ 2 152 6 165a 61⁄ 2a 178b 7b 216d 81⁄ 2d 254e 10e 305e 12e 330e 13e 356e 14e 381e 15e 406e 16e 432e 17e 457 18 483 19 508 20 559 22 610 24 610 24 610 24 3 4 OR MORE MM IN. MM IN. MM IN. – – – – – – – 140 152 165a 190c 229b 254d 305e 330e 356e 406e 457e 483e 508 559 – – – – – – – – – – – – 51⁄ 2 6 61⁄ 2a 71⁄ 2c 81⁄ 2b 10d 12e 13e 14e 16e 18e 19e 20 22 – – – – – – – – – – – – 178 190 203 216a 254b 279b 330e 356e 381e 457e 508e 559e 559 610 – – – – – – – – – – – – 7 71⁄ 2 8 81⁄ 2a 9b 11b 13 e 14e 15e 18e 20e 22e 22 24 – – – – – – – – – – – – – – – – 254 305 356d 381e 406e 483e 559e 610e 610 610 – – – – – – – – – – – – – – – – 10 12 14d 15e 16e 19e 22e 24e 24 24 – – – – – 1. Bending space at terminals shall be measured in a straight line from the end of the lug or wire connector in a direction perpendicular to the enclosure wall. 2. For removable and lay-in wire terminals intended for only one wire, bending space shall be permitted to be reduced by the following number of millimeters (inches) : a 12.7mm (1/2 in.) b 25.4mm (1 in.) c 38.1mm (11/2 in.) d 50.8mm (2 in.) e 76.2mm (3 in.) 3. This column shall be permitted to determine the required wire-bending space for compact stranded aluminum conductors in sizes up to 1000 kcmil and manufactured using AA-8000 series electrical grade aluminum alloy conductor material in accordance with 310.14. 182 Data subject to change without notice.