SOLAR PCU – SUN MAGIC (3KVA to 6KVA)
FEATURES
 True bidirectional inverter/solar PCU
 Hybrid inverter (Solar /Grid/ BATT)
 Single phase i/p, single phase o/p
 Range 1KVA to 15KVA
 MPPT Based Solar Charger
 Generator compatible
 Modes available are SGB/GSB/SBG/GFM /INV(selectable)
 SBG Modes with Buffer level selection facility 25/50/75
 Grid FEED Function/Mode (GFM) Available
 GFM Feeds power to grid when grid available, feeds power to load
When grid fails.
 GFM levels are selectable 0/25/50/75/100
 Changeover time less than =20ms
 Input power Factor for grid charging – near to unity
 Zero loss on bypass mode/ grid mode
 Auto bypass and manual bypass
 Optional RS232
 Solar KW and KWH Meter
 Fault logs
 Optional I/P Terminal Wind
 Auto fault reset for non critical faults
 Multi mode MPPT charger
SUN MAGIC (3KVA TO 6KVA)
INVERTER
Continuous Rated Output Power
DC Voltage
Output Voltage (Inverter Mode)
Output Frequency (Free Running)
Output Waveform
Peak Inverter Efficiency (Full Load)
Overload
Changeover Time (At Full Load)
Bypass Facility
DC To AC Isolation
3KVA
5KVA
6KVA
2400 W
96 V
4000 W
96 V
230V AC ±2%, 1 Phase
50Hz ± 0.5%
Pure Sine Wave
>90%
125% FOR 60 SEC, 150% FOR 5 SEC
<=20ms
Manual for Service
Transformer
4800W
96 V
BATTERY
Nominal Battery Voltage
Grid Charging Current
96V DC
Selectable
Input Power Factor (Grid Charging)
Near to Unity
Battery Charging Voltage
Selectable
INPUT
Input Voltage Range
170V to 260V (±5V), 1 Phase
DG Compatibility
Input Frequency Range
Yes
50Hz ± 6%
SOLAR
Charger Type
MPPT
Max PV Voltage (VOC)
180V
Min PV Voltage (VMPP)
MPPT Modes Available
115V
2 ( Selectable)
Solar Charger Current Rating
KVA=KW as per rating
Panel Reverse Protection
YES
Solar Charger Efficiency
>92%
CONFIGURATION
Modes Available
SBG/SGB/GSB/Grid Feed mode/Inv
Battery Buffer Setting
SELECTABLE
GRID Feed Mode
RESET
SELECTABLE
Manual Fault Reset/Buzzer Reset
YES
Auto Reset
BATTERY Low and Overload
DISPLAY
Input
Output
Battery
Voltage, Current and Frequency
Voltage, Current and Frequency
Voltage and %of Discharge
Solar
Other
Voltage, Current, KW, KWh
Current Status, Configuration, Fault Log
INDICATIONS
LCD
Grid On, PV On, Grid Charger On, Inverter On, Load On Mains,
Load On Grid, Fault
KVA Rating, Current Status,
Input -Voltage/Current/Frequency,
Inverter –Voltage/Current,
Output- Voltage/Current/Frequency,
Solar-Panel Voltage /Current &KWH Rating,
Battery-Voltage &Status ,Configuration
ALARM
Audible For Fault And Warnings
LED
ENCLOSURE
Degree of Protection
Indoor
Cooling
Force Air Cool
Siemens Grey
Color
ENVIRONMENTAL
Temperature Range (Operating)
Temperature Range (Storage)
Altitude (max)
0°C to 40°C
-10°C to 60°C
1000m
Battery Reverse Indication
Panel Reverse Indication
OPTIONAL @ Extra
PV Side Surge Protection
RS 232 Communication Port
GSM Remote Monitoring Facility
Wind Charger Connection Terminal
Wind charge current
Solar radiation (with external Pyranometer)
Wind speed (with external anemometer)
Disclaimer :
1. Specification Subjected to Change without Prior Notice
2. Stabilizer not recommended for GRID FEED Mode
3. Additional External Protection Recommended for Battery and Output Side
4. Display Parameters are for Indicative Purpose Only. Subjected to Accuracy
5. Load shall be cross verified before connecting
6. System Not Designed for any Life support system
ENERTECH UPS PVT LTD
S. No. 399/1-2, Bhare, P.O. Ghotawade, Near MSEB Substation, Pirangut, Taluka -Mulshi,
Pune – 412115
T: 020-22923172, F: 020-20291176
Email – sales@enertechups.com
Website: www.enertechups.com
West: Mumbai | Nagpur | Aurangabad | Kolhapur | Ahmedabad | Surat | Jaipur | Indore| Bhopal
South: Bangalore| Hyderabad | Vizag | Chennai | Madurai | Coimbatore |
North: Delhi | Jammu | Gurgaon | Noida
Download