Minimum Energy Performance Standards

advertisement
Minimum Energy
Performance Standards
MEPS regulations worldwide
www.siemens.de/international-efficiency
Introduction MEPS................................................................................................. 2
Argentina ............................................................................................................. 6
Australia ............................................................................................................... 7
Brazil .................................................................................................................... 8
Canada................................................................................................................. 9
Chile .................................................................................................................. 10
China ................................................................................................................. 11
Colombia ............................................................................................................ 12
Europe ............................................................................................................... 13
India .................................................................................................................. 14
Israel .................................................................................................................. 15
Japan ................................................................................................................. 16
Mexico ............................................................................................................... 17
Peru ................................................................................................................... 18
Philippines .......................................................................................................... 19
Russia ................................................................................................................ 20
Saudi Arabia ....................................................................................................... 21
South Africa ........................................................................................................ 22
South Korea ........................................................................................................ 23
Switzerland ........................................................................................................ 24
Taiwan ............................................................................................................... 25
Thailand ............................................................................................................. 26
Turkey ................................................................................................................ 27
United Arab Emirates........................................................................................... 28
USA ................................................................................................................... 29
www.siemens.de/international-efficiency
1
Warranty, liability and support
We shall not be held liable for any information provided in this document.
We accept no liability for any damage or loss caused by the applications,
information, programs, planning data, or performance data described in this
example, irrespective of the legal basis for claims arising from such damage
or loss, unless liability is mandatory. For example, according to the product
liability law, in cases of malfeasance, gross negligence, due to endangerment
of life, body or health, due to assumption of a guarantee for a product's
characteristics of state, due to malicious concealment of a defect or due to
violation of basic contractual obligations. Any claims for damages caused by
violation of basic contractual obligations, however, shall be limited to the
foreseeable damage or loss which is typically envisaged in contracts unless
there has been malfeasance or gross negligence or unless liability is
mandatory due to endangerment of life, the body or health. This does not
entail a change in the burden of proof to your disadvantage.
Copyright© 2015 Siemens AG. Reproduction or transmissions of these
examples or extracts thereof are forbidden without the express written
authority of Siemens AG.
www.siemens.de/international-efficiency
2
MEPS
On one hand, considerable emphasis is placed on energy efficiency
to protect our environment. On the other hand, a higher energy
efficiency allows companies to improve their cost position,
therefore increasing their competitiveness.
Sustainably reducing energy usage
Regarding energy efficiency, the focus has been on industrial direct-on-line
(DOL) motors from a very early stage. This is because electric drives consume
70% of the electric energy in the industry. As a consequence, electric drives
represent a huge potential when it comes to boosting efficiency. Many
countries have already created a legal framework to reduce energy
consumption in their industrial landscape – and to achieve the environmental
goals that have been set.
Standards
Initially, global standards were defined to achieve this, for instance IEC
60034-30-1 and NEMA MG1. The standards were either taken over – or
transitioned into minimum legal efficiency requirements. The term used
around the globe for these minimum efficiencies is MEPS: Minimum Energy
Performance Standards.
www.siemens.de/international-efficiency
3
Profit from MEPS
Companies operating plants especially profit from MEPS regulations as these
help them to boost their productivity. For instance, for a 110kW motor, the
energy costs represent up to 99% of the overall lifecycle costs. As a
consequence, by increasing the efficiency of a motor, the energy
consumption can be significantly reduced – and along with it, the associated
costs. Companies operating plants can sustainably benefit when investing in
energy efficiency.
Tools
Tools are available that can be used to define when it makes sense to invest in
energy efficient motors:
SIMOTICS EE Comparator
The efficiency of IE4 motors is 14% higher than for IE1. Operating costs can
be reduced with a high efficiency. A payback calculation always makes sense
in order to select the most cost-effective motor for line operation. Every
country has its own specific MEPS requirements. An overview of these
requirements is listed below, but can also be simply viewed using the
SIMOTICS EE-COMPARATOR App.
www.siemens.de/international-efficiency
4
SinaSave
Answers to questions, such as "What is the payback time when investing in a
more efficient motor?", "Does it make sense to use a variable-speed drive or a
DOL motor for my applications?", "How does the energy efficiency class of a
motor impact the cost effectiveness of the drive system?", can be found in the
web-based SinaSave tool. Based on individual operating characteristics as
well
as
system-specific
parameters,
SinaSave
calculates
the
energy
requirements of various drive products and systems, which are then
compared with one another. Further, SinaSave tells you the payback time
when investing in an energy-efficient drive solution. Based on the investment
and operating costs as well as the energy-saving potential, this tool calculates
the expected payback time. Not only this, it also provides fast and
straightforward help for decision-making when it comes to financially
assessing the investment in energy-efficient products.
You can find SinaSave here: siemens.de/sinasave.
Low-voltage motors for every requirement
SIMOTICS low-voltage motors are available in a power range from 0.09 kW to
3500 kW – to address many efficiency standards worldwide. We can offer you
the optimum solution for every specific requirement: in addition to energy
efficient motors in compliance with specific standards, explosion-protected
motors for the highest safety standards, along with motors for specific sectors
and
customers.
Employing
state-of-the-art
product
and
production
technologies, these motors are especially compact – and in many cases have
the same dimensions irrespective of the particular efficiency class.
More information is available at siemens.de/niederspannungsmotoren
www.siemens.de/international-efficiency
5
Argentina
Voltage/Frequency
Voltage up to 660 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
6
Australia
Voltage/Frequency
Voltage up to 1100 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
AS/NZS 1359.5:2004 (MEPS)
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 – 185 kW
1 HP – 250 HP
2,4,6,8
IE2 mandatory since 31.03.2006
Exceptions
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently from
the product;
3. Motors specially designed for inverter duty;
4. Pole-changing motors;
5. Duty type S2;
6. Torque motors;
7. Re-export motors (from Australia/ New Zealand).
www.siemens.de/international-efficiency
7
Brazil
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
Portaria Interministerial No. 553
INMETRO NBR 17094-1
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 110 kW
1 HP - 150 HP
8
IE2 mandatory since
08.12.2009*
0,75 kW - 150 kW
1 HP - 200 HP
6
IE2 mandatory since
08.12.2009*
0,75 kW - 185 kW
1 HP - 250 HP
2, 4
IE2 mandatory since
08.12.2009*
Exceptions
* The minimum efficiency values are close to the IE2 values defined in IEC 60034-30
Exceptions according INMETRO NBR 17094-1 / Portaria Interministerial No. 553:
1. Motors specially designed for inverter duty;
2. Motors specifically designed to operate:
i) in potentially explosive atmospheres (Ex e, Ex d(e));
ii) in special applications (i.e. smoke extraction);
3. Duty type different to S1 or S3 (with a rated cyclic duration factor of 80 % or higher);
4. Water cooled motors;
5. Motors designed to operate wholly immersed in a liquid.
www.siemens.de/international-efficiency
8
Canada
Voltage/Frequency
Voltage up to 600 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
Energy Efficiency Act
CSA C390-10
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 150 kW
1 HP - 200 HP
2, 4, 6
NEMA Premium Efficient
mandatory since 12.04.2012
160 kW - 375 kW
215 HP - 500 HP
2, 4, 6
NEMA Energy Efficient
mandatory since 12.04.2012
0,75 kW - 375 kW
1 HP - 500 HP
8
NEMA Energy Efficient
mandatory since 12.04.2012
Exceptions
Can be operated as “NEMA Energy Efficient”:
1. Foot, foot & flange mounted motors or/and IEC design N or H;
2. Footless motors;
3. NEMA design C or IEC design H;
4. Close-coupled pump motor;
5. Fire extinguishing pumps.
Exceptions according Canada Energy Efficiency Act (EEA C390-10 since 12.04.2012)
1. Motors labeled for inverter operation;
2. Multi-speed motors;
3. Flange mounted motors except C & D design;
4. U Frame motors;
5. Two-digit NEMA frames (48-56).
www.siemens.de/international-efficiency
9
Chile
Voltage/Frequency
Voltage up to 690 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
NCh 3086 of. 2008
PE N° 7/01/2.
IEC 60034-30
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW – 7,5 kW
1 HP – 10 HP
2, 4, 6
IE1 mandatory since
04.01.2011.*
Exceptions
Exceptions according NCh 3086 of 2008
1. Brake motors;
2. Motors specially designed for inverter duty.
* The engines must be certified according to the requirements for the Energy label from
the protocol PE N ° 7/01/2. The Energy label only applies to engines which are kept on store
by distributors.
www.siemens.de/international-efficiency
10
China
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
GB18613-2012
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW – 375 kW
1 HP – 500 HP
2, 4, 6
IE2 mandatory since
01.09.2012
2016
0,75 kW – 5,5 kW
1 HP – 7,5 HP
2, 4, 6
IE2 mandatory since
01.09.2012
7,5 kW – 375 kW
10 HP – 500 HP
2, 4, 6
IE3 mandatory
from 01.09.2016
2017
0,75 kW – 375 kW
1 HP – 500 HP
2, 4, 6
IE3 mandatory
from 01.09.2017
Exceptions
Exceptions China Energy Label since 1.09.2012:
1. Motors completely integrated into a machine (for example pump, fan and compressor)
that cannot be tested separately from the machine;
2. Special design motors for special application environment such as application in high
sea altitude above 1.000 m;
3. Special design motors for special application such as smoke-extraction motors, textile
industry specified motors and etc. ;
4. Motors designed for variable conditions, such as inverter duty motor;
5. Motors with integrating brake inside;
6. Motor working duty with Non S1 or S3 with a rated cyclic duration factor of 80 % or
higher;
7. Dual-windings and/or multi-windings motors;
8. 60Hz motors (only 60Hz data on rating plate).
www.siemens.de/international-efficiency
11
Colombia
Voltage/Frequency
Voltage up to 460 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
12
Europe (2015 & 2017)
Voltage/
Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
EU regulation 640/2009
EU regulation 04/2014
IEC 60034-30-1
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 5,5 kW
1 HP - 7,5 HP
2, 4, 6
IE2 mandatory
since 16.06.2011
7,5 kW – 375 kW
10 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory since
01.01.2015
2017
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory from
01.01.2017 on
Exceptions
Exceptions according to regulation (EG) 640/2009 and (EG) 4/2014:
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently from the
product;
3. Motors specifically designed to operate:
i) at altitudes exceeding 4.000 meters above sea-level;
ii) where ambient air temperatures exceed 60 °C;
iii) in maximum operating temperature above 400 °C;
iv) where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C
for a motor with air cooling;
v) where the water coolant temperature at the inlet to a product is less than 0 °C or
exceeding 30 °C;
vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European
Parliament and of the Council ( 3 );
4. Brake motors;
5. Duty type different to S1 or S6;
6. Motors specially designed for inverter duty.
www.siemens.de/international-efficiency
13
India
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No regulation
Standard - IS: 12615- 2011
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements *
Exceptions
* The minimum efficiency requirements according to IS: 12615-2011 (IE3 is mentioned)
are not mandatory and only valid for energy efficient motors
in the power range of 0,75 -375 kW and 2-/4-/6-poles.
Exceptions according to IS:12615-2011:
1. Motors made exclusively for converter duty application;
2. Motors completely integrated into the machine (for example, pumps, compressors,
special machines etc.) that cannot be tested separately from the machine;
3. Motors rated for duty cycles S2, S4 and above, except if an equivalent S1 duty is
specified by the driven equipment manufacturer;
4. Slip-ring Induction Motors;
5. Single phase motors;
6. Pole-changing motors.
www.siemens.de/international-efficiency
14
Israel
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No special Regulations
referring to European Standards (e.g. IEC 60034-30-1) and requirements
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW – 5,5 kW
1 HP – 7,5 HP
2, 4, 6
IE2 mandatory since
16.06.2011
7,5 kW – 375 kW
10 HP – 500 HP
2, 4, 6
IE3 mandatory since
01.01.2015
Exceptions
Referring to European exceptions:
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently from the
product;
3. Motors specifically designed to operate:
a. at altitudes exceeding 4.000 meters above sea-level;
b. where ambient air temperatures exceed 60 °C;
c. in maximum operating temperature above 400 °C;
d. where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C
for a motor with air cooling;
e. where the water coolant temperature at the inlet to a product is less than 0 °C or
exceeding 30 °C;
f. in potentially explosive atmospheres as defined in Directive 94/9/EC of the European
Parliament and of the Council ( 3 );
4. Brake motors;
5. Duty type different to S1 or S6;
6. Motors specially designed for inverter duty.
www.siemens.de/international-efficiency
15
Japan
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50/60 Hz
Regulation/Directive/
Standard
JIC C4034-2-1: IEC 60034-2-1:2007 (MOD)
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6
IE3 mandatory since
01.04.2015
Exceptions
Exceptions:
1. Explosion proof motors;
2. Special insulation (Temp class H, N, R, 250);
3. Delta-star starting;
4. Marine motors;
5. Motors designed to operate wholly immersed in a liquid;
6. High-slip motors;
7. Gate motors;
8. Canned motors;
9. Used in very low temperature (designed for lower than -20 degree C);
10. Design only for Inverter and with Forced ventilation.
www.siemens.de/international-efficiency
16
Mexico
Voltage/Frequency
Voltage up to 600 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
NOM-016-ENER-2010
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6, 8
NEMA Premium Efficient
mandatory since 19.12.2010
Exceptions
Exceptions:
1. Motors assembled in a machine;
2. Duty type different to S1.
www.siemens.de/international-efficiency
17
Peru
Voltage/Frequency
Voltage up to 480 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
NTP 399.450.2008
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
18
Philippines
Voltage/Frequency
Voltage up to 460 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
19
Russia
Voltage/Frequency
Voltage up to 690 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
20
Saudi Arabia
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50/60 Hz
Regulation/Directive/
Standard
SASO IEC 60034-30:2013
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW – 375 kW
1 HP – 500 HP
2, 4, 6
IE2 mandatory since 01.07.2015
2017
0,75 kW – 375 kW
1 HP – 500 HP
2, 4, 6
IE3 mandatory from 01.01.2017
Exceptions
Exceptions according to SASO IEC 60034-30:2013:
1. Motors made solely for converter operation in accordance with IEC 60034-25;
2. Motors completely integrated into a machine (for example pump, fan and compressor)
that cannot be tested separately from the machine;
3. Brake motors, Gear motors and Wound rotor motors;
4. Motors specifically designed to operate:
a. In maximum operating temperatures above 400º C;
b. In potentially explosive atmospheres (e.g. explosion proof motors);
c. wholly immersed in a liquid;
d. with a starting torque over 100% of the rated torque (e .g. gate motor & crane
motor);
e. With cooling from external equipment (e .g. Air over motors, or liquid cooling
motors);
f. In an enclosed container and part of an integrated system (e .g. canned motor).
www.siemens.de/international-efficiency
21
South Africa
Voltage/Frequency
Voltage up to 525 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
22
South Korea
Voltage/Frequency
Voltage up to 600 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
MKE-2015-28
KS C IEC60034
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 30 kW
1 HP - 40 HP
2, 4, 6, 8
IE2 mandatory since 01.01.2013
37 kW - 200 kW
50 HP - 275 HP
2, 4, 6, 8
IE3 mandatory since 01.10.2015
0,75 kW - 30 kW
1 HP - 40 HP
2, 4, 6, 8
IE2 mandatory since 01.01.2013
37 kW - 200 kW
50 HP - 275 HP
2, 4, 6, 8
IE3 mandatory since 01.10.2015
200 kW - 375 kW
275 HP - 500 HP
2, 4
IE3 mandatory from 01.10.2016
0,75 kW - 200 kW
1 HP - 275 HP
2, 4, 6, 8
IE3 mandatory from 01.10.2018
200 kW - 375 kW
275 HP - 500 HP
2, 4
IE3 mandatory from 01.10.2016
2016
2018
Exceptions
Exceptions according to KS C IEC60034:
1. Motors specifically designed to operate:
i) at altitudes exceeding 1 000 meters above sea-level;
ii) where ambient air temperatures exceed 40 °C;
2. Duty type different to S1;
3. Motors specially designed for inverter duty;
4. Motors designed to operate wholly immersed in a liquid;
5. TENV and TEAO enclosure (totally enclosed non-ventilated, totally enclosed air over);
6. Pole changing motors;
7. Torque curve: Design C and D.
www.siemens.de/international-efficiency
23
Switzerland
Voltage/
Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
SR 730.01 Energieverordnung (EnV) from 07. 12.1998 (Update: 01.08.2014)
IEC 60034-30-11
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 5,5 kW
1 HP - 7,5 HP
2, 4, 6
IE2 mandatory
since 16.06.2011
7,5 kW – 375 kW
10 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory since
01.01.2015
2017
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory from
01.01.2017 on
Exceptions
Exceptions according to regulation Energieverordnung (EnV) from 07. 12.1998
(Update: 01.08.2014):
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently from the
product;
3. Motors specifically designed to operate:
i) at altitudes exceeding 4.000 meters above sea-level;
ii) where ambient air temperatures exceed 60 °C;
iii) in maximum operating temperature above 400 °C;
iv) where ambient air temperatures are less than – 30 °C for any motor or less than 0 °C
for a motor with air cooling;
v) where the water coolant temperature at the inlet to a product is less than 0 °C or
exceeding 30 °C;
vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European
Parliament and of the Council ( 3 );
4. Motors specially designed for inverter duty.
www.siemens.de/international-efficiency
24
Taiwan
Voltage/Frequency
Voltage up to 690 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
IEC60034-2-1
CNS 14400 (MEPS)
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW – 200 kW
1 HP – 275 HP
2,4,6,8
IE2 mandatory since 2015
Exceptions
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently
from the product;
3. Motors specially designed for inverter duty;
4. Pole-changing motors.
www.siemens.de/international-efficiency
25
Thailand
Voltage/Frequency
Voltage up to 400 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements *
Exceptions
* on a voluntary base tax benefits can be applied when installing motors with an energy
efficiency class IE3 for 2,4,6 and 8 poles motors with an output range from 0,73kW –
185kW.
No exceptions
www.siemens.de/international-efficiency
26
Turkey
Voltage/Frequency
Voltage up to 1000 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
Regulation SMG 2012/2
IEC 60034-30-1
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 5,5 kW
1 HP - 7,5 HP
2, 4, 6
IE2 mandatory since
01.01.2015
7,5 kW - 375 kW
10 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory since
01.01.2015
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6
IE3 or IE2 with variable speed
drive mandatory
from 01.01.2017
2017
Exceptions
Exceptions according to the Turkish regulation SMG-2012/2:
1. Motors designed to operate wholly immersed in a liquid;
2. Motors completely integrated into a product (for example gear, pump, fan or
compressor) of which the energy performance cannot be tested independently from the
product;
3. Motors specifically designed to operate:
i) at altitudes exceeding 1 000 meters above sea-level;
ii) where ambient air temperatures exceed 40 °C;
iii) in maximum operating temperature above 400 °C;
iv) where ambient air temperatures are less than – 15 °C for any motor or less
than 0 °C for a motor with air cooling;
v) where the water coolant temperature at the inlet to a product is less than 5 °C or
exceeding 25 °C;
vi) in potentially explosive atmospheres as defined in Directive 94/9/EC of the European
Parliament and of the Council ( 3 );
4. Brake motors;
5. Duty type different to S1 or S6;
6. Motors specially designed for inverter duty.
www.siemens.de/international-efficiency
27
United Arab Emirates
Voltage/Frequency
Voltage up to 690 V,
Frequency: 50 Hz
Regulation/Directive/
Standard
No standard or regulation
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
/
/
/
No minimum efficiency
requirements
Exceptions
No exceptions
www.siemens.de/international-efficiency
28
USA (2015)
Voltage/Frequency
Voltage up to 600 V,
Frequency: 60 Hz
Regulation/Directive/
Standard
EPAct;
EISA 2007;
NEMA MG-1 Table 12-12 and Table 12-11;
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2015
0,75 kW - 150 kW
1 HP – 200 HP
2, 4, 6
NEMA Premium Efficient
mandatory since 19.12.2010
160 kW - 375 kW
215 HP – 500 HP
2, 4, 6
NEMA Energy Efficient
NEMA Design B
mandatory since 19.12.2010
0,75 kW - 375 kW
1 HP – 500 HP
2, 4, 6
NEMA Energy Efficient
mandatory since 19.12.2010
Exceptions
Can be operated as “NEMA Energy Efficient” - EISA 2007
1. Motors that do not fall under EPAct 1992 (EPAct 1992, NEMA MG-1 Table 12-11);
2. U-frame motors;
3. Design C motors;
4. Close-coupled pump motors;
5. Footless motors;
6. Vertical solid shaft normal thrust motors (tested in a horizontal configuration);
7. Polyphase motors not exceeding 600 V (different from 230 or 460 V);
8. Fire extinguishing pumps.
Exceptions out of EISA-2007 (since 19.12.2010):
1. Motors designed to operate wholly immersed in a liquid;
2. Integral with gearing or brake where motor cannot be used separately;
3. Multi-speed motors;
4. Two-digit NEMA frames (48-56);
5. Intermittent duty (not S1);
6. Only- Inverter duty motors;
7. TENV and TEAO enclosure (totally enclosed non-ventilated, totally enclosed air over).
www.siemens.de/international-efficiency
29
USA (2016)
Voltage/Frequency
Voltage up to 600 V,
Frequency: 60 Hz
Regulation / Directive /
Standard
Energy Conservation Standards for Commercial and Industrial Motors, Final rule:
2014
EPAct;
EISA 2007;
NEMA MG-1 Table 12-12 und Table 12-11;
Legal requirements
Year
Power range [kW]
Power range [HP]
Poles
Minimum efficiency
2016
0,75 kW - 375 kW
1 HP – 500 HP
2,4,6,8
NEMA Premium Efficient
mandatory from
01.06.2016 on for NEMA
Design A & B
0,75 kW - 150 kW
1 HP – 200 HP
4,6,8
NEMA Premium Efficient
mandatory from
01.06.2016 on for NEMA
Design C
0,75 kW - 375 kW
1 HP – 500 HP
2,4,6,8
NEMA Energy Efficient
mandatory from
01.06.2016 on for fire
pumps
www.siemens.de/international-efficiency
30
Exceptions
Requirements until May 31st 2016
Can be operated as “NEMA Energy Efficient” - EISA 2007:
1. Motors that do not fall under EPAct 1992 (EPAct 1992, NEMA MG-1 Table 12-11);
2. U-frame motors;
3. Design C motors;
4. Close-coupled pump motors;
5. Footless motors;
6. Vertical solid shaft normal thrust motors (tested in a horizontal configuration);
7. Polyphase motors not exceeding 600 V (different from 230 or 460 V);
8. Fire extinguishing pumps.
Exceptions out of EISA-2007 (since 19.12.2010):
1. Motors designed to operate wholly immersed in a liquid;
2. Integral with gearing or brake where motor cannot be used separately;
3. Multi-speed motors;
4. Two-digit NEMA frames (48-56);
5. Intermittent duty (not S1);
6. Only- Inverter duty motors;
7. TENV and TEAO enclosure (totally enclosed non-ventilated, totally enclosed air over).
From June 1st 2016 on
"Electric Motors" covered under the Energy Conservation Standards for Commercial
and Industrial Motors, Final rule: 2014 are:
1. Single-speed, induction motor;
2. Rated for continuous duty (MG 1) operation or for duty type S1 (IEC);
3. Contains a squirrel-cage (MG 1) or cage (IEC) rotor;
4. Built in a three-digit or four-digit NEMA frame size (or IEC metric equivalent), including
those designs between two consecutive NEMA frame sizes (or IEC metric equivalent) or
an enclosed 56 NEMA frame size (or IEC metric equivalent);
5. Meets all of the performance requirements of a NEMA Design A, B, or C motor or of an
IEC Design N or H motor.
Exceptions according to "Electric Motors" covered under the Energy Conservation
Standards for Commercial and Industrial Motors, Final rule: 2014:
1. Air-over electric motors;
2. Component sets of an electric motor;
3. Liquid-cooled electric motors;
4. Submersible electric motors;
5. Inverter-only electric motors;
6. Multi-speed motors;
7. Smoke extraction motors with maximum operating temperature above 400 °C.
www.siemens.de/international-efficiency
31
Global Siemens Headquarters
Siemens AG
Wittelsbacherplatz 2
80333 Muenchen
Germany
Global Siemens Headquarters
Siemens AG
Lorem Sector
Henkestrasse 127
91052 Erlangen
Telephone: +49 9131 84-0
Germany
www.siemens.com/international-efficiency
Siemens AG
Industry Sector
Large Drives
Postfach 47 43
90025 Nuernberg
DEUTSCHLAND
© 11.2015, Siemens AG
The information provided in this brochure contains merely
general descriptions or characteristics of performance
which in case of actual use do not always apply as
described or which may change as a result of further
development of the products. An obligation to provide the
respective characteristics shall only exist if expressly
agreed in the terms of contract.
All product designations may be trademarks or product
names of Siemens AG or supplier companies whose use by
third parties for their own purposes could violate the
rights of the owners.
www.siemens.de/international-efficiency