VA, VF, and VS Series Direct Mounted Globe Valve

advertisement
TAC
1354 Clifford Avenue
P.O. Box 2940
Loves Park, Illinois 61132-2940
www.invensysibs.com
Two-Way and Three-Way Globe Valve
Assemblies with
220 lbf Linear (979 N)
Spring Return DuraDrive Actuators
Submittal Sheet
VA, VF, and VS Series Direct Mounted Globe
Valve Assemblies
The Invensys VA, VF, and VS-XXXX-5XX series direct
mounted, two-way and three-way globe valve assemblies are
complete actuator/valve assemblies that accept two position,
floating, or proportional control, respectively, from a DDC
system or from a thermostat, for control of hot water, chilled
water, and steam applications. These valve assemblies
consist of spring return linear actuators direct mounted to 1-1/
4" through 4" (32 mm through 100 mm) two-way and three-way
globe valve bodies. An integrated rack and pinion translates
the rotary motion of the actuator into the linear motion of the
valve stem.
Application
Typical applications include hot and chilled water coils in air
handling units, and unit ventilators.
VX-7XXX-5XX
Features
•
•
•
•
ISO 9001 Certification
Thermal isolation
3 ft. (91 cm) appliance cables, 1/2” conduit connectors
NEMA 1 actuator enclosure. NEMA 2, UL Type 2 (IEC IP54)
with customer supplied water tight conduit connectors
• Overload protection throughout rotation
• Visual position indicator
• 250 psig valve body static pressure rating per ANSI
Standards (B16.15—1985) for bronze bodies
• 125 psig valve body static pressure rating per ANSI
Standards (B16.15—1985) for cast iron flanged bodies
• Tight close-off to ANSI III (0.1% of rated Cv) or ANSI IV
(0.01% of rated Cv)
• Valve sizes 1-1/4” to 4”
• Spring-loaded TFE packing
• Manual override mechanism
VX-9XXX-5XX
Printed in U.S.A.
3-03
F-27167
Specifications
Valve
Valve Application
Valve Assembly Series
Type of End Fitting
Sizes Available
2-Way Valves
3-Way Valves
Chilled water, hot water, steam
Chilled water, hot water
❒ VX-7213-59X-4-P
❒ VX-7223-59X-4-P
❒ VX-7253-59X-4-P
❒ VX-7263-59X-4-P
❒ VX-7273-59X-4-P
❒ VX-7283-59X-4-P
❒ VX-9213-59X-4-P
❒ VX-9223-59X-4-P
❒ VX-9213-59X-5-P
❒ VX-9223-59X-5-P
❒ VX-7313-59X-4-P
❒ VX-7323-59X-4-P
❒ VX-9313-59X-4-P
❒ VX-9313-59X-5-P
NPT
NPT
Flanged
NPT
NPT
Flanged
1-1/4" to 2"
2-1/2" to 3"
2-1/2" to 4"
1-1/4" to 2"
2-1/2" to 3"
2-1/2" to 4"
Action
Stem up open, stem up closed
Mixing, Diverting
Material
Body
Bronze
Cast iron
Bronze
Cast Iron
Stem
316 stainless steel
303 stainless steel
316 stainless steel
303 stainless steel
Packing
Seat
VX-7213, 7223, 9213,
9223, 93X3
VX-7253, 7263, 7273, 7283
Plug
Disc
Spring-loaded TFE
Spring-loaded TFE
Bronze
Bronze
Stainless steel
VX-7213, 7223, 9213,
9223, 93X3
N/A
Brass
N/A
N/A
Bronze
VX-7253, 7263, 7273, 7283
Stainless steel
N/A
N/A
N/A
VX-7213, 7223, 9213, 9223
Composition
N/A
N/A
N/A
N/A
N/A
VX-7253, 7263
Teflon
N/A
N/A
VX-7273, 7283, 93X3
None
N/A
N/A
ANSI Pressure Class
125 psig (862 kPa)
up to 200 psig
(1379 kPa) below
150 q F (66 q C)
250 psig (1727 kPa) up to 400 psig
(2757 kPa) below 150 q F (66 q C)
N/A
None
250 psig (1727 kPa) up to 400 psig
(2757 kPa) below 150 q F (66 q C)
125 psig (862 kPa) up
to 200 psig
(1379 kPa) below
150 q F (66 q C)
Seat Leakage Class
VX-7213, 7223, 7253, 7263, 9213,
9223
ANSI IV (0.01% of Rated Cv)
VA-7273, 7283, 93X3
ANSI III (0.1% of Rated Cv)
N/A
N/A
N/A
ANSI III (0.1% of Rated Cv)
Allowable Fluid Temperaturea
40 to 281 q F
(4 to 138 q C)
20 to 300 q F
(-7 to 149 q C)
40 to 300 q F
(4 to 149 q C)
VX-7213, 7223, 9213, 9223, 93X3
20 to 281q F (-7 to 138 q C)
VX-7253-7263
20 to 340 q F (-7to 171 q C)
N/A
N/A
N/A
N/A
VX-7273, 7283
20 to 366 q F (-7 to 186 q C)
N/A
N/A
N/A
N/A
Maximum Steam Inlet Pressure
VX-7213, 7223, 9213, 9223, 93X3
N/A
N/A
N/A
VX-7253, 7263
100 psig (690 kPa)
35 psig (241 kPa)
N/A
N/A
N/A
N/A
N/A
VX-7273, 7283
150 psig (1034 kPa)
N/A
N/A
N/A
N/A
N/A
Allowable Differential Pressureb
Water
35 psi (241 kPa) for normal life
VX-7213, 7223, 9213,
9223, 93X3
Steam
35 psi (241 kPa) for normal life
20 psi (138 kPa)
N/A
N/A
N/A
VX-7253, 7263
35 psi (241 kPa)
N/A
N/A
N/A
N/A
N/A
VX-7273, 7283
50 psi (345 kPa)
N/A
N/A
N/A
N/A
N/A
a
Do not apply above valve pressure rating to the piping system.
b
Maximum recommended differential pressure. Do not exceed the recommended differential pressure (pressure drop) or the integrity of valve parts may be affected. Exceeding the
maximum recommended differential pressure voids the product warranty.
2
Specifications
Actuator
Inputs
Control Signal
Power Requirements
❒
MAX1-720X—On-off, SPST control contacts or Triacs (500 mA rated).
❒
MFX1-7203—Floating point control, 24 Vac.
❒
MSX1-7203—Proportional, 2 to 10 Vdc or 4 to 20 mAdc with 500: resistor.
All 24 Vac circuits are Class 2. Circuits 30 Vac and above are Class 1.
Running
Part Number
Connections
Motor Type
Mechanical
Voltage
50/60 Hz
50 Hz
Holding
60 Hz
VA
W
VA
W
DC
Amps
9.8
7.5
9.7
7.5
50 Hz 60 Hz
W
W
0.29
2.8
2.8
❒
MAX1-7203
24 Vac ± 20%
22-30 Vdc
❒
MSX1-7203
24 Vac ± 20%
22-30 Vdc
9.8
7.4
9.7
7.4
0.28
2.9
2.9
❒
MFX1-7203
24 Vac ± 20%
22-30 Vdc
9.8
7.7
9.7
7.7
0.30
3.3
3.3
❒
MAX1-7200
120 Vac ± 10%
11.7
8.8
10.0
8.4
❒
MAX1-7201
230 Vac ± 10%
15.5
9.5
10.6
8.5
—
3.6
5.0
4.6
3.3
3 ft. (91 cm) long, appliance cable.
Brushless DC
Linear Stroke: MX51-720X—5/8" (16mm). MX61-720X—1-1/16" (27 mm).
Approx. Stroke Timing: 100 seconds for 5/8" stroke. 190 seconds for 1-1/16" stroke.
Manual Override: Allows positioning of valve and preload using manual crank.
Right/Left Switch: Permits reverse acting/direct acting linear motion (MSX1 only).
Environment
Ambient Temperature Limits
Shipping & Storage: -40 to 160 q F (-40 to 71 q C).
Operating: 0 to 140 q F (-18 to 60 q C)
Temperature Restrictions:
Actuator
MX51-720X
MX61-720X
Max. Allowable Ambient
@ Max. Fluid Temperatures
Valve body
140 q F (60 q C)@ 281q F (138 q C)
VB-721X, 722X
120 q F (49 q C) @ 300 q F (149 q C)
VB-73XX
100 q F (38 q C)@ 340 q F (171 q C)
VB-725X, 726X
90 q F (32 q C)@ 366q F (186 q C)
VB-727X, 728X
140 q F (60 q C)@ 300q F (149 q C)
VB-9XXX 2-1/2"-4"
current production
Humidity
15 to 95% RH, non-condensing
Location
NEMA 1, NEMA 2, UL Type 2 (IEC IP54) with customer supplied water tight conduit and
connectors.
Agency Listings
UL 873: Underwriters Laboratories (File #E9429 Category Temperature-Indicating and
Regulating Equipment).
CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards C22.2
No. 24-93.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC)
Australia: This product meets requirements to bear the C-Tick Mark according to the terms
specified by the Communications Authority under the Radiocommunications Act 1992.
3
(
)
(
)(
) (
)
(
)
Direct Mounted Globe Valve Assembly Part Numbering System
VX-XXXX-XXX-X-XX
Control
Signal Type
A = Two Position
F = Floating
S = Proportional
Connection
Pattern Code
1 = Union Straightway
4 = Straightway
3 = Thread NPT or Flanged
5 = Globe Flanged
Port Code
Configuration
1
721, 921 = 2-Way, Stem Up Open
722, 922 = 2- Way, Stem Up Closed
2-Way
725 = 2-Way, NO (Stem Up Open) Stainless Steel Trim w/disc
Size
Cv
726 = 2-Way, NC (Stem Up Closed) Stainless Steel Trim w/disc
3-Way
P Code
Cv (Kvs)
P Code
727 = 2-Way, NO (Stem Up Open) Stainless Steel Trim
1-1/4"
(Kvs)
20 (17)
728 = 2-Way, NC (Stem Up Closed) Stainless Steel Trim
1-1/2"
28 (24)
731, 931 = 3-Way, Mixing
2"
40 (35)
11
41 (36)
732 = 3-Way, Diverting
2-1/2"
56 (48)
12
67 (58)
-
65 (56)
12
74 b (64)
-
12
85 (73)
13
91 (78)
-
13
85 (73)
13
101 b (87)
-
13
145 (125)
14
170 (147)
-
14
3"
Actuator
Two Position
MA51-7203=593
MA51-7200=592
MA51-7201=591
MA61-7203=596
MA61-7200=595
MA61-7201=594
Proportional
MS51-7203=593
MS61-7203=596
4"
Floating
Mixing
Diverting
9
20 (17)
20
9
10
28 (24)
28
10
40
11
a
Threaded valve body
b
Flanged valve body
a
a
12
MF51-7203=593
MF61-7203=596
1 The configuration of the valve assembly determines the valve stem position
and flow, as shipped from the factory. See the table below.
Table-1 Valve Configuration Chart.
Normal Position
Valve Body
Valve Body Action
Action
Valve Stem
Flow
VB-721X
VB-7253
VB-7263
Two-Way Stem Up Open
Up
Open
Port A to AB flow decreases as actuator extends
VB-722X
VB-7273
VB-7283
Two-Way Stem Up Closed
Up
Closed
Port A to AB flow increases as actuator extends
VB-731X
VB-931X
Three-Way Mixing
Up
B to AB
Port A to AB flow increases as actuator extends
Port B to AB flow deceases as actuator extends
VB-732X
Three-Way Diverting
Up
B to AB
Port B to A flow increases as actuator extends
Port B to AB flow decreases as actuator extends
4
Spring Return Models
Note: Choose a valve assembly having a close-off pressure capability sufficient for the application.
Table-2 Two-Way Direct Mounted Globe Valve Assemblies with Spring-Return Actuators — Selection Chart.
Spring-Return Two-Way Direct Mounted Globe Valve Assemblies
Actuator Torque Rating (minimum)
220 lbf
(979 N)
Two-Position
MAX1-720X (591) (592) (593) (594) (595) (596)
Floating
MFX1-7203 (593) (596)
Proportional
MSX1-7203 (593) (596)
Valve Assembly
Part Number a
VX-72X1-XXX-4-P
VX-72X3-XXX-4-P
VX-72X3-XXX-4-P
VX-9213-XXX-4-P
VX-9223-XXX-4-P
VX-9213-XXX-5-P
VX-9223-XXX-5-P
P
Code
Valve Size
in.
Cv b
kvsb
Close-off Pressure psigcd
9
1-1/4
20
17
150
10
12
13
12
13
14
1-1/2
2-1/2
3
2-1/2
3
4
28
56
85
65
85
145
24
48
73
56
73
125
100
33
22
33
22
12
a
To determine a specific part number, see the Direct Mounted Globe Valve Assembly Part Numbering System,
kvs = m3/h ('P = 100 kPa)
kvs = Cv / 1.156
Cv = kvs x 1.156
c
Close-off ANSI IV (.01%) for soft seats.
d
Close-off pressure ratings describe only the differential pressure which the actuator can close-off with adequate seating force. Consult valve body specifications
for other limitations. The rating value is the pressure difference between the inlet and outlet ports.
b
Table-3 Three-Way Globe Valve Assemblies with Spring-Return Actuators — Selection Chart.
Spring-Return Three-Way Linked Globe Valve Assemblies
Actuator Torque Rating (minimum)
220 lbf
(979 N)
Two-Position
MAX1-720X (591) (592) (593) (594) (595) (596)
Floating
MFX1-7203 (593) (596)
Proportional
MSX1-7203 (593) (596)
Valve Assembly
Part Number a
P
Code
VX-73X3-2XX-4-P
11
2
9
1-1/4
10
1-1/2
11
2
12
2-1/2
13
3
12
2-1/2
13
3
14
4
VX-73X3-XXX-4-P
VX-9313-XXX-4-P
VX-9313-XXX-5-P
Valve Size
in.
Cvb
kvsb
Close-off Pressure psic
9
1-1/4
1-1/2
20
28
41
20
28
40
67
91
74
101
145
17
24
36
17.3
24.2
34.6
58
79
64
87
125
150
10
a
100
65
250
250
250
33
22
33
22
12
To determine a specific part number, see the Direct Mounted Globe Valve Assembly Part Numbering System.
kvs = m3/h ('P = 100 kPa)
kvs = Cv / 1.156
Cv = kvs x 1.156
c
Close-off ANSI III (0.1%) for metal-to-metal seats with pressure at inlet (port A). For seat leakage ratings see “Applicable Literature” section for the list of
literature on specific valve bodies.
b
5
Dimensions
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
2-Way
A
VX-721X-59X-4-9
VX-722X-59X-4-9
VX-721X-59X-4-10
VX-722X-59X-4-10
VX-721X-59X-4-11
VX-722X-59X-4-11
4-5/8 (117)
5-3/8 (137)
6-1/8 (156)
C
E
1-3/8 (35)
8-11/16 (221)
H
1-3/4 (44)
8-3/8 (213)
1-1/2 (38)
8-7/8 (225)
1-13/16 (46)
8-1/5 (216)
1-9/16 (40)
9-1/16 (230)
2-1/4 (57)
8-9/16 (217)
11-11/16 (297)
12-1/16 (306)
12-7/16 (316)
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
3-Way
A
C
E
H
VX-731X-59X-4-9
4-5/8 (117)
1-7/8 (48)
8-3/8 (213)
11-11/16 (297)
VX-731X-59X-4-10
5-3/8 (137)
1-5/8 (41)
8-1/2 (216)
12-1/16 (306)
VX-731X-59X-4-11
6-1/8 (156)
1-15/16 (49)
8-9/16 (217)
12-7/16 (316)
10 9/16 (268)
2 9/16
(65)
4 1/16
(103)
6 15/16
(176)
E
C
A
H
Minimum clearance: 5 inches for removal of the actuator.
Figure-1 MX51-720X Spring Return Valve Actuator Dimensions.
6
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
2-Way
A
C
E
H
VX-92XX-59X-4-12
8-1/2 (216)
3-13/16 (97)
13-15/16 (354)
13-9/16 (344)
VX-92XX-59X-4-13
9-1/2 (241)
4-1/4 (108)
14-1/4 (362)
13-5/8 (346)
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
3-Way
A
C
E
H
VX-93XX-59X-4-12
8-1/2 (216)
4-5/8 (117)
13-15/16 (354)
13-9/16 (344)
VX-93XX-59X-4-13
9-1/2 (241)
5 (127)
14-1/4 (362)
13-5/8 (346)
2 9/16
(65)
10 9/16 (268)
4 1/16
(103)
9 9/16
(243)
E
C
A
H
Minimum clearance: 5 inches for removal of the actuator.
Figure-2 MX61-720X Spring Return Valve Actuator Dimensions.
7
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
VX-9213-59X-5-12
2-Way Stem-Up Open Flanged Valve
A
C
E
F
G
H
8-1/2 (216)
3-1/2 (89)
13 (330)
7 (178)
5-1/2 (140)
13-5/8 (346)
VX-9213-59X-5-13
9-1/2 (241)
3-3/4 (95)
14-1/2 (368)
7-1/2 (191)
6 (152)
14-1/8 (359)
VX-9213-59X-5-14
11-1/2 (292)
4-1/2 (114)
15-3/8 (391)
9 (229)
7-1/2 (191)
15-1/8 (384)
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
VX-9223-59X-5-12
2-Way Stem-Up Closed Flanged Valve
A
C
E
F
G
H
8-1/2 (216)
4 (107)
12-3/8 (314)
7 (178)
5-1/2 (140)
13-5/8 (346)
VX-9223-59X-5-13
9-1/2 (241)
5 (127)
12-5/8 (320)
7-1/2 (191)
6 (152)
14-1/8 (359)
VX-9223-59X-5-14
11-1/2 (292)
7-1/8 (181)
13-3/8 (340)
9 (229)
7-1/2 (191)
15-1/8 (384)
Valve Dimensions in inches (millimetres)
Valve Assembly
Part Number
VX-9313-59X-5-12
3-Way Stem-Up Open Flanged Valve
A
C
E
F
G
H
8-1/2 (216)
5-3/8 (137)
13-3/4 (349)
7 (178)
5-1/2 (140)
13-5/8 (346)
VX-9313-59X-5-13
9-1/2 (241)
6-3/8 (162)
14 (356)
7-1/2 (191)
6 (152)
14-1/8 (359)
VX-9313-59X-5-14
11-1/2 (292)
8-1/2 (216)
14-3/4 (375)
9 (229)
7-1/2 (191)
15-1/8 (384)
2 9/16
(65)
10 9/16 (268)
4 1/16
(103)
9 9/16
(243)
E
C
G
A
F
H
Minimum clearance: 5 inches for removal of the actuator.
Figure-3 MX61-720X Spring Return Flanged Valve Actuator Dimensions.
All specifications are nominal and may change as design improvements are introduced.
Invensys Building Systems shall not be liable for damages resulting from misapplication
or misuse of its products.
The following trademarks are the property of Invensys:
Invensys
DuraDrive
F-27167
Printed in U.S.A.