electric boq - Canara Bank

advertisement
B.O.Q. OF PROPOSED ELECTRICAL WORK FOR CURRANCY CHEST
AT BALDEV PLAZA , AJMER ROAD JAIPUR.
ANNEXURE 3(C) : electrical work
S.NO
ITEM
A
A1
Light, Power and UPS point.
Wiring for the following light points with 1.5sq.mm PVC insulated
stranded copper conductor wires in concealed PVC conduits in
false ceiling / walls as directed including providing 6amps modular
switches, 5sided G.I. boxes for housing switches and earthing
complete as required.wiring with 2x 2.5 sq. m + 1 x 1.5 sq.m.m.
with
QTY.
UNIT
25
no.
1
no.
4
no.
11
no.
8
no.
4
no.
11
no.
4
no.
Telephone/Computer conducting and wiring
20mm dia 2mm wall thickness PVC conduit
20
mt.
1
Providing and fixing in existing Metal box Krone Tag Block of
different size as mentioned below consisting of necessary Back
Mount Frame disconnection module and grommets complete as
required.
a. 10 Pair Krone Tag Block
1
no.
2
Supplying and drawing the following type of cables for telephone
system in existing conduit
a.For telephone system with
35
mt.
A2
A3
A4
A5
A6
A7
a. One point controlled by one 6 amp switch
Wiring for the call bell including token buser points with 1.5sq.mm
PVC insulated stranded copper conductor wires in concealed PVC
conduit in false ceiling / walls as directed including providing
6amps bell push switches, 5sided G.I. boxes for housing switches
and earthing complete as required.
Wiring for the following two way control light points with 1.5sq.mm
PVC insulated stranded copper conductor wires in concealed PVC
conduit in false ceiling / walls as directed including providing 2 way
6 amp modular switches, 5sided G.I. boxes for housing switches
and earthing complete as required
a.One point controlled by 2 Nos 2 way 6 amps switch
Wiring for wall fan & exaust fan points with 1.5sq.mm PVC
insulated stranded copper conductor wires in concealed PVC
conduits in false ceiling / walls as directed including providing 6A
5Pin socket near the wall fan 5 sided G.I. boxes for housing 6A
switch and earthing complete as required.
Wiring for 6 amps light plug outlets with 1.5sq.mm PVC insulated
copper conductor wires in PVC conduits in false ceiling / wall / floor
as directed including providing 6 amp modular 5 pin socket and 6
amps switch with cover plate, 5 sided G.I. boxes for housing
switches, sockets and earthing complete as required.
Wiring for 1.5 sq.mm PVC insulated copper conductor wires in
PVC conduits in false ceiling / wall / floor as directed including
providing and fixing in position 6 amp 5 pin socket outlet (3Nos)
and 1 No.5 amp switch in box covered with white polycarbonate
modular cover plate and earthing complete as required.
Wiring for 16 amps power outlets points with 4 sq.mm PVC
insulated stranded copper conductor wires in concealed / recessed
PVC as directed including providing 16 amp modular switch and 6
pin socket with cover plate, 5 sided G.I. outlet boxes for switches
and socket and earthing the third pin with 1.5 sq.mm PVC stranded
copper wire complete as required (only one outlet shall be
connected on each circuit).
A8
Wiring for AC outlets with 4.0 sq.mm PVC insulated copper
conductor wires in PVC conduit including providing 32A SPN metal
clad industrial plug socket outlet with 32A SP MCB and earthing
with 1.0 sq.mm PVC insulated copper wires complete as required.
A9
a
i. 2 Pair 0.6mm dia copper conductor (ATC) unarmoured cable.
RATE
AMOUNT
3
a
B
B1
a
C
1
D
Providing and installing in position the following outlets in recessed
G.I boxes
Telephone outlet box along with RJ 11 socket.
5
no.
Circuit and sub main wiring
Supply and laying of the following size of PVC insulated copper
conductor wires of 650/1100 V grade in PVC conduits, complete as
required.
4R X 10 sqmm. Copper wire for main panel to u.p..s panel.
13
mt.
1
no.
1
no.
Distribution Board
Designed, manufactured, supplied, fixed in position, tested
and commissioned of the following sheet metal enclosed wall
mounted / fully recessed in wall indoor cubical type, with dust
proof, hinged and lockable doors, complete with
interconnections with copper wires tapes, cables glands,
bonding to earth and painting.
a.(POWER D.B. )Sheet metal enclosed 12 way TPN with 8
Nos of 10/20 amps SP MCB’s i.e. 10 Nos of 10/20 SP
MCB’s arranged in 3 rows and controlled by 1 no 63 amp
TPN MCB
UPS D.B.:- supply , ercetion & commissioning of 4 way
TDN HCB DB comprising of recessed sheet steel one loose
with double door with loose wires box with 100 a hnned of
bus bars with nuteral , earth strips , interconnection with
following neuntings as required .
Grand Total
SAY AMOUNT