VersaMax 48VDC Grouped Input Modules October 2008 GFK-2544 Product Description Module Characteristics Discrete input modules IC200MDL635 and BXIOID1648 provide two groups of 8 discrete inputs. Discrete input modules IC200MDL636 (shown below) and BXIOID3248 provide four groups of 8 discrete inputs. Inputs in each group can be either positive logic inputs that receive current from input devices and return the current on the common, or negative-logic inputs that receive current from the common and return current to the input device. Input devices are connected between the input terminals and common terminals. Points IC200MDL635, BXIOID1648: 16 (2 groups of 8) IC200MDL636, BXIOID3248: 32 (4 groups of 8) Module ID IC200MDL635, BXIOID1648: FFFF8008 IC200MDL636, BXIOID3248: 80088008 Isolation: User input to logic (optical) and frame ground: 250VAC continuous; 1500VAC for 1 minute Group to Group: 250VAC continuous; 1500VAC for 1 minute Point to point: None I 1 OK 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 IC200MDL636 INPUT POS/NEG GRP 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 1234567 LED indicators One LED per point shows individual point ON/OFF status OK LED indicates backplane power is present Backplane current consumption (5V output) IC200MDL635, BXIOID1648: 70mA maximum IC200MDL636, BXIOID3248: 140mA maximum External power supply None Thermal derating IC200MDL635, BXIOID1648: No derating IC200MDL636, BXIOID3248: See chart Configuration parameters Input response times 48VDC 32PT 831 Input Characteristics I OK Input voltage Power for module operation comes from the backplane. Intelligent processing for the module is performed by the CPU or NIU. LED Indicators Individual green LEDs indicate the on/off state of each input point. Backplane power must be present for LEDs to provide status of inputs. The green OK LED is on when backplane power is present to the module. 0 to 60VDC, 48VDC nominal User input current 1.7mA typ. @ 48VDC, 2.1mA typ. @ 60VDC Input impedance 28K Ohm typical On state voltage Off state voltage 34VDC to 60VDC 0 VDC to 10VDC On state current Off state current 1.0mA minimum 0 to 0.4mA maximum On response time Off response time 0.5ms maximum Configurable filter time 0 ms, 1.0ms (default), or 7.0ms Product Revision History Rev Preinstallation Check Date Description IC200MDL635E BXIOID1648E IC200MDL636E BXIOID3248E October 2008 IC200MDL635D BXIOID1648D IC200MDL636D BXIOID3248D April 2005 Improvement to latching mechanism Configuration Parameters IC200MDL635C IC200MDL636C April 2004 Changed to V0 plastic for module housing. The module’s basic input on/off response time is 0.5ms. IC200MDL635B IC200MDL636B January 2004 ATEX approval for Group 2 Category 3 applications. BXIOID1648C BXIOID3248C January 2004 Changed to V0 plastic for module housing. ATEX approval for Group 2 Category 3 applications. Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system. For some applications, it may be preferable to add additional filtering to compensate for conditions such as noise spikes or switch bounce. Input filter times of 0ms, 1.0ms, or 7.0ms are selectable via software configuration, for total response times of 0.5ms, 1.5ms, and 7.5ms respectively. The default is 1.0ms filter time (total response time is 1.5ms). IC200MDL635A BXIOID1648A IC200MDL636A BXIOID3248A 1 Updated Power Supply OK signal circuitry. September 2000 Initial product release VersaMax 48VDC Grouped Input Modules October 2008 GFK-2544 Field Wiring Terminals Installation in Hazardous Locations • EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D, DIV. 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY • WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2; • WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; AND • WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS. Terminal A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 Thermal Derating No derating is required for the 16-point modules, or for the 32-point modules at 48VDC in any orientation. A18 For 32-point modules at 60VDC, the number of points that can be on at the same time depends on the ambient temperature, the external voltage, and the orientation of the module and DIN rail. Terminal B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 B17 Connection Input 17 * Input 18 * Input 19 * Input 20 * Input 21 * Input 22 * Input 23 * Input 24 * Input 25 * Input 26 * Input 27 * Input 28 * Input 29 * Input 30 * Input 31 * Input 32 * Inputs 17-24 Common * Inputs 25-32 Common * B18 * Inputs available on 32-point modules only. The 32 inputs form groups of 8. Each group has a common connection. Each group may be wired for positive or negative logic inputs. There is no derating when 32-point modules are mounted vertically (A and B). Deratings at 60C when the modules are mounted horizontally (C and D) are shown below. A Connection Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Input 9 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Inputs 1-8 Common Inputs 9-16 Common For the 16-point modules, if additional bussed terminals are needed, the B terminals can be made available using a shorting bar. The shorting bar has a maximum current-carrying capacity of 2 Amps per point. See the VersaMax I/O Modules Manual, GFK-1504 for information about using a shorting bar. A C Wiring Connections for Carriers with Two Rows of Terminals Row B connections shown below are for 32-point modules only. I1 D A Number of Points On At the Same Time 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 55ºC 3 I18 I19 60ºC 24 D C 60VDC 60VDC I7 6 6 I20 + (-) I6 5 5 I21 (+) + (-) I5 4 4 32 28 I4 3 2 I17 50ºC I3 2 1 Ambient Temperature 10ºC I2 1 B 5ºC (+) + (-) D B I8 7 8 7 I22 8 I23 I9 9 10 9 I24 I10 10 I25 11 I12 11 12 11 I26 12 I27 I13 I14 13 14 13 I28 14 I29 15 15 I30 (+) (+) I16 16 16 I31 17 17 I32 18 18 (+) (+) (+) + (-) (+) I15 Wiring Connections for Carriers with Three Rows of Terminals Side B connections shown below are for 32-point modules only. 20 + (-) 16 12 I13 I14 (+) I16 I15 + (-) (+) + (-) I29 I30 (+) I32 I31 (+) + (-) 8 13 4 14 I7 7 Operating Note If hot insertion of a module is done improperly, the operation of other modules on the same backplane may be disrupted. See Installing a Module on a Carrier in the VersaMax Modules Manual, GFK-1504. 8 2 1 9 I2 2 16 I9 I8 I1 A 15 I10 10 I3 3 17 I11 11 I4 4 7 12 B 1 15 8 9 I18 2 16 I25 I24 I17 I6 6 14 I23 I12 I5 5 13 18 I26 10 I19 3 17 I27 11 I20 4 18 12 I21 5 I28 I22 6