DRAFT and INCOMPLETE Table of Contents from A. P. Sakis Meliopoulos Power System Modeling, Analysis and Control Chapter 4 _____________________________________________________________ 2 Modeling - Power Transformers and the Per Unit System ______________________ 2 4.1 Introduction____________________________________________________________ 2 4.2 Single Phase Transformers________________________________________________ 2 4.2.1 The Ideal Single Phase Transformer _____________________________________________ 3 4.2.2 Impedance Transformation ____________________________________________________ 5 4.2.3 Theory of Mutually Coupled Inductances _________________________________________ 7 4.3 The Per Unit System ____________________________________________________ 14 4.3.1 Axiomatic Definition of the Per-Unit Scaling System _______________________________ 16 4.3.2 Per-Unit Scaling Procedure ___________________________________________________ 16 4.3.3 Mutually Coupled Circuits ____________________________________________________ 21 4.3.4 The Per Unit System and Numerical Accuracy ____________________________________ 26 4.3.5 Discussion_________________________________________________________________ 28 4.4 Three Phase Transformers_______________________________________________ 29 4.4.1 The Ideal Three Phase Transformer _____________________________________________ 31 4.4.2 Non-Ideal Three Phase Transformer Model _______________________________________ 33 4.4.3 Sequence Circuits of Three Phase Transformers ___________________________________ 34 4.5 Autotransformers_______________________________________________________ 39 4.5.1 Single-Phase Autotransformers _____________________________________________ 39 4.5.2 Three Phase Autotransformers _____________________________________________ 41 4.6 The Regulating Transformer _____________________________________________ 41 4.7 Transformer Power Flow Equations _______________________________________ 47 4.8 Transformer Parameter Identification From Tests ___________________________ 51 4.8.1 The Open Circuit Test________________________________________________________ 51 4.8.2 The Short Circuit Test________________________________________________________ 52 4.9 Normalized Power System Model _________________________________________ 53 4.10 Summary and Discussion _______________________________________________ 55 4.11 Problems ____________________________________________________________ 56 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Chapter 4 Modeling - Power Transformers and the Per Unit System 4.1 Introduction In this chapter we examine the power transformer. Single phase, three phase as well as regulating transformers are considered. We start from the physical construction of a transformer, we examine the operation of the transformer and develop a mathematical model which naturally leads to an equivalent circuit. This approach is followed for all types of transformers, single phase, three phase or regulating transformers. Transformer models can be further simplified with the use of specific scaling of electrical quantities, otherwise known as the per unit system. The per unit system has been extensively used in modeling and analysis of power systems with multiple transformation levels of voltage (transformers). It is natural to introduce the per unit system in this chapter. 4.2 Single Phase Transformers A single phase power transformer consists of a magnetic core and two windings as it is illustrated in Figure 4.1a. This is a rather simple construction of a magnetic circuit. The excitation of the magnetic circuit is a result of electric current flow in the two windings. Specifically when electric current flows in one or both windings, a magnetic flux will be generated inside the iron core of the transformer. The alternating magnetic flux induces voltages on the two windings and it is responsible for the power transfer from one winding to another. The two windings many times are referred to as primary and secondary, which typically indicate the source side and the load side, respectively. Another description of the two windings is high voltage side or low voltage side depending on the voltage level at the two windings. When the electric current flows in one winding of the transformer of Figure 4.1, a magnetic field will be generated in the core of the transformer. If the electric current is alternating, the magnetic field will be also alternating. Consider the other coil. The alternating magnetic flux links this coil. As a result, a voltage will be induced in this coil. The polarity of the induced voltage with respect to the current i1(t) will depend on how the coil is wound. We can define the polarity of the transformer, and we symbolize the polarity with two dots as it is illustrated in Figure 4.1a, as follows. If the direction of the electric current flow in a coil is “into” the dot, then the induced voltage on the other coil will have positive polarity on the dot side of this coil. Considering the construction Page 2 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos of the transformer of Figure 4.1a, an electric current i1 flowing “into” the dot, will generate a magnetic flux in the indicated direction (use the right hand rule). This magnetic flux will induce a voltage on coil 2 which will have a positive polarity on the top terminal. This discussion should explain how the dots have been placed. Now, using the dots we can forget the construction of the transformer and instead use the symbolic representation of Figure 4.1b. Φm i1 i'2 Φl2 Φ l1 (a) i1 i'2 (b) Figure 4.1 Single Phase Transformer (a) Construction (b) Symbolic Representation 4.2.1 The Ideal Single Phase Transformer Power transformers are typically constructed with high conductivity wires (copper), and therefore low resistance. The magnetic core is typically made from carbon steel which has a very high permeability and it is laminated to minimize losses. It is expedient to take advantage of these observations, for the purpose of examining the basic properties of transformers. Specifically, we can idealize the parameters of the transformer, yielding the concept of the “ideal transformer”. The specific assumptions of the “ideal transformer” are • • No losses ( in the windings or in the core) Core material has infinite permeability, i.e. µ = ∞ which implies that there is no leakage fluxes The “ magnetic resistance” of the magnetic circuit of Figure 4.1a is: Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 3 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 1 l , µ A where l is the length of the magnetic circuit, A is the cross section of the core, and µ is the permeability of the core material. For the “ideal transformer”, ℜ = 0 , and the total magnetomotive force for the transformer of Figure 4.1 is ℜ= P = N1i1 (t ) + N 2i2 (t ) = ℜϕ (t ) = 0 Therefore: i1 (t ) N =− 2 i 2 (t ) N1 Note that the magnetiuc flux f(t) is linked by both windings. The magnetic flux linkage of the two windings are λ1 (t ) = N1ϕ (t ) and λ2 (t ) = N 2ϕ (t ) respectively. Therefore the following induced voltages will appear on the two windings: e1 (t ) = dλ1 (t ) dϕ (t ) = N1 , dt dt e2 (t ) = dλ2 (t ) dϕ (t ) = N2 dt dt Therefore (upon elimination of the flux variable): e1 (t ) N 1 = e 2 (t ) N 2 Above relationship indicates that the voltages at the terminals of an ideal transformer are inversely proportional to the number of turns of the two windings. The total power absorbed by the ideal transformer is p (t ) = e1 (t )i1 (t ) + e 2 (t )i 2 (t ) = ⎛ N ⎞ N1 e 2 (t )⎜⎜ − 2 ⎟⎟i 2 (t ) + e 2 (t )i 2 (t ) = 0 N2 ⎝ N1 ⎠ Above relationships are valid for the instantaneous values of voltage, current and power. Under sinusoidal steady state conditions, these relationships are also valid for the phasors of the voltage and current and the complex power, i.e. ~ E1 N 1 ~ = E2 N 2 ~ I1 N2 ~ =− N1 I2 Page 4 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos ~~ ~~ S1 = E1 I1* = − E 2 I 2* The above relationships characterize an ideal transformer. Practical transformers are designed so that their operation under normal operating conditions is close to the ideal case. 4.2.2 Impedance Transformation A transformer inserted between a source and an impedance (load) can transform the apparent impedance seen by the source as it is illustrated in Figure 4.2. If the transformer is near ideal, this transformation of the impedance can be achieved without any substantial power losses in the transformer. Considering Figure 4.2, the impedance at the left-hand side of the transformer is given with: ~ I2 ~ I1 ~ I1 ~ V2 Source z2 ⇔ 2 Source ⎛N ⎞ z1 = ⎜⎜ 1 ⎟⎟ z2 ⎝ N2 ⎠ N1:N2 Figure 4.2 Impedance Transformation by a Transformer N1 ~ V2 2 ~ 2 ~ ⎛ N 1 ⎞ V2 ⎛ N 1 ⎞ V1 N 2 ⎟ ⎟ Z Z1 = ~ = =⎜ =⎜ N 2 ~ ⎜⎝ N 2 ⎟⎠ I~2 ⎜⎝ N 2 ⎟⎠ 2 I1 I2 N1 Note that the insertion of a transformer with transformation ratio N1/N2 between a source and a load of impedance Z2, resulted in an apparent impedance (N1/N2)2Z2. This property is many times used for ‘’matching’’ a load to a specific source. Consider the problem of connecting a source to a load and that the source has an internal impedance of ZS while the load has an impedance ZL. For what value of the load impedance ZL, the source will transfer maximum power to the load? The power absorbed by ZL will be ( ) ~~ P = Re V L I L* = Re(Z L ) Copyright © A. P. Sakis Meliopoulos – 1990-2006 ~ E Zs + ZL 2 = RL ~2 E ( RS + RL ) 2 + ( X S + X L ) 2 Page 5 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos where ~ VL is the voltage at the terminal of the load, ~ E is the internal voltage source. Z s = Rs + jX s Z L = R L + jX L Now we would like to find the maximum of P by allowing the load impedance ZL to change. The maximum can be computed by solving the equations. ∂P =0 ∂ RL ∂P =0 ∂ XL The solution of above equations yields: R L = RS X L = −X S or Z L = Z S* Many times it is possible to achieve the above conditions (or come very close to it) by inserting a transformer between the source and the load. An example will illustrate this application. Example E4.1: Consider a source with a 50 ohm internal impedance. The source is to be connected to an 8 ohm load as it is illustrated in Figure E4.1. How can we transfer the maximum possible power to the load. 50Ω 8Ω 100Vrms Amplifier Speaker Figure E4.1 A Source and a Load Solution: If the load is directly connected to the source, the power transferred to the load will be computed as follows. First the electric current is Page 6 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos I = 100/58 = 1.724 A (rms) The power absorbed by the load is P = Re(VLI*) = Re[(8)(1.724)2] = 23.78 Watts For maximum power transfer, the load must be connected to the source via a transformer in such a way that the impedance of the transformer/speaker system, as indicated in Figure E4.1a, be: Z ′L = Z*S This means that (N1/N2)2⋅8Ω = 50 Ω and therefore N1/N2= 2.5. In this case I' =100V/100Ω = 1 A, and I = 2.5 I ′ = 2.5A. The maximum power absorbed at the load is P = (8Ω)(2.5A )2 = 50Waltts . 50Ω I' Z'L I 8Ω 100Vrms N1:N2 Figure E4.1a 4.2.3 Theory of Mutually Coupled Inductances In this section we consider a single phase transformer without the “ideal” assumption, i.e. the windings of the transformer have finite resistance and the magnetic core has finite permeability. In this case, the magnetic flux generated by the flow of currents in the windings is not confined in the magnetic core but some magnetic flux “leaks” in the air as it is illustrated in Figure 4.3. Specifically Figure 4.3a illustrates the magnetic flux due to electric current in winding 1 of the transformer and Figure 4.3b illustrates the magnetic flux due to electric current in winding 2 of the transformer. The notation in Figure 4.3a is as follows: ϕ 11 is the total magnetic flux due to current i1. ϕ112 is the magnetic flux due to current i1 and which links the winding 2. ϕ l1 is the magnetic flux due to electric current i1 and which “leaks” into air and therefore it does not link winding 2. The corresponding magnetic fluxes in Figure 4.3b due to current i2 are ϕ 22 , ϕ 221 and ϕ l2 . Now if the two windings carry currents i1 and i2 simultaneously, the magnetic flux linkage for windings 1 and 2 can be found by applying superposition (assuming that the transformer operates in the linear region): λ1 (t ) = N1ϕ11 (t ) + N1ϕ 221 (t ) = N1ϕ l1 (t ) + N1ϕ112 (t ) + N1ϕ 221 (t ) λ2 (t ) = N 2ϕ 22 (t ) + N 2ϕ112 (t ) = N 2ϕ l 2 (t ) + N 2ϕ112 (t ) + N 2ϕ 221 (t ) Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 7 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos The voltage of the two coils will be: dϕ (t ) d (ϕ112 (t ) + ϕ 221 (t )) dλ1 (t ) = r1i1 (t ) + N 1 l1 + N 1 dt dt dt dϕ l 2 (t ) dλ d (ϕ112 (t ) + ϕ 221 (t )) v 2 (t ) = r2 i2 (t ) + 2 = r2 i2 (t ) + N 2 + N2 dt dt dt v1 (t ) = r1i1 (t ) + Note that the flux leakage ϕ l1 is generated by the electric current i1 and therefore it will be proportional to this curtrent. Similarly, the flux leakage ϕ l2 is proportional to the electric current i2, i.e. ϕ l1 (t ) = a1i1 (t ) ϕ l 2 (t ) = a 2 i2 ( t ) ϕ 11 ϕ 112 i1(t) i2(t)=0 ϕ l1 v1(t) v2(t) (a) ϕ 221 ϕ 22 i1(t)=0 v1(t) i2(t) ϕ l2 v2(t) (b) Figure 4.3 Magnetic Flux in a Single Phase Transformer (a) Primary Coil Energization (b) Secondary Coil Energization Page 8 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos By defining obtain: φ(t) = ϕ112(t)+ ϕ221(t), and substituting into the above equations, we di1 (t ) dφ (t ) + N1 dt dt di 2 (t ) dφ (t ) v 2 (t ) = r2 i 2 (t ) + Ll 2 + N2 dt dt v1 (t ) = r1i1 (t ) + Ll1 Where Ll1 = N1 a1 and L l2 = N 2 a2 Now let ℜ be the reluctance of the magnetic core. Then ϕ112 (t ) = N 1i1 (t ) / ℜ ϕ 221 (t ) = N 2 i 2 (t ) / ℜ and ϕ (t ) = ( N 1 i1 (t ) + N 2 i 2 (t )) / ℜ For magnetic core transformers, the magnetic relunctance ℜ is very small and therefore N 1i1 (t ) + N 2 i 2 (t ) is also very small. Define an equivalent magnetomotive force in term of the “magnetizing” current im1: N1i1 (t ) + N 2 i2 (t ) = N1im1 (t ) Above equation can be rewritten: N1 (i1 (t ) − im1 (t )) + N 2 i2 (t ) = 0 di (t ) dφ (t ) N 12 di m1 (t ) e1 (t ) = N 1 = = Lm1 m1 Define ℜ dt dt dt dφ (t ) e2 (t ) = N 2 dt 2 N where: Lm1 = 1 ℜ Upon substitution, the equations of the transformer can be rewritten in the following form: di1 (t ) + e1 (t ) dt di (t ) v 2 (t ) = r2 i 2 (t ) + Ll 2 2 + e2 (t ) dt v1 (t ) = r1i1 (t ) + Ll1 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 9 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos di m1 (t ) dt i1 (t ) − im1 (t ) N =− 2 i2 (t ) N1 e1 (t ) N 1 = e2 (t ) N 2 e1 (t ) = Lm1 Above equations are represented with the equivalent circuit of Figure 4.4. Note that the last two equations represent an ideal transformer which is illustrated in Figure 4.4. i1(t) r1 Ll 1 i1-im1 Ll 2 r2 i2(t) im1 v1(t) Lm1 e1 e2 v2(t) Ideal Transformer Figure 4.4 Equivalent Circuit of a Single Phase Transformer The inductance Lm1 is referred to as the magnetizing inductance and the current im1 as the magnetizing current. For power transformers under normal operating conditions, the magnetizing current is very small and many times it is neglected, i.e. the inductance Lm1 is removed from the equivalent circuit. Through a simple transformation, the impedances can be moved to the other side of the ideal transformer. Under steady state conditions, the voltages and currents can be expressed in terms of their phasors (see Chpater 2). In this case, the transformer equations are transformed into: ~ ~ ~ ~ V1 = r1I1 + jωLl1I1 + E1 ~ ~ ~ ~ V2 = r2 I 2 + jωLl 2 I 2 + E2 ~ ~ E1 = jωLm1I m1 ~ ~ 1 I1 − I m1 N =− 2 =− ~ N1 t I2 ~ E1 N1 =t ~ = E2 N 2 It is important to note that the resistance and the leakage inductances of a typical transformer are very small while the magnetizing inductance is very large. Under these conditions, the leakage impedance of one side can be transferred to the other side. Recall that by transferring an impedance from one side of the transformer to the other, the Page 10 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos impedance is multiplied by the square of the transformation ratio. Because the magnetizing impedance is very large, the two leakage impedances can be moved to the same location providing an equivalent leakage impedance. The resulting equivalent circuit is shown in Figure 4.5. Note that this is an approximation. The error committed by this approximation is relatively small. Note that the simplified transformer model equivalent is described with the equivalent series impedance Zeq1, the magnetizing impedance Zm1 and the transformation ratio t. ~ I1 zeq1 jωLl 1 r1 r2t 2 jωLl 2t ~ V1 2 Ideal Transformer ~ I2 ~ V2 jωLm1 t:1 Figure 4.5 Simplified Equivalent Circuit of a Single Phase Transformer It is important to note that for the single phase transformer, it is always possible to develop an equivalent circuit without the presence of the ideal transformer. The procedure will be illustrated on the simplified equivalent circuit of Figure 4.5. Note that t=N1/N2. For this purpose, the terminal electric currents are expressed as a function of the terminal voltages yielding (details are omitted): ~ ⎡ I 1 ⎤ ⎡ Yeq1 ⎢ ~ ⎥ = ⎢− tY eq1 ⎣I 2 ⎦ ⎣ ~ ⎤ ⎡V1 ⎤ + t 2 Ym1 ⎥⎦ ⎢⎣V~2 ⎥⎦ − tYeq1 t 2 Yeq1 where: Yeq1 = 1 , and Z eq1 Ym1 = 1 Z m1 The equivalent circuit of Figure 4.6 represents exactly the above equations. The reader is encouraged to verify that the circuit of Figure 4.6 exhibits the same current/voltage relationships as the above equations. This can be done by simply expressing the terminal currents of the circuit of Figure 4.6 as functions of the terminal voltages and comparing the resulting equations to the above equations. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 11 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos ~ I1 ~ I2 t:1 Zeq=Yeq-1 ~ V1 ~ V2 Ideal Transformer (a) ~ I1 ~ V1 ~ I2 tYeq (t2-t)Yeq (1-t)Yeq ~ V2 (b) Figure 4.6 Simplified Single Phase Transformer Models The performance of transformers is characterized with a number of indices. The following most common indices are introduced: Transformer efficiency is defined as the ratio of the nominal real power output over the required real power input, i.e. η = Pout/Pin. Voltage Regulation is defined as the range of the ratio of the normalized output voltage magnitude over the normalized input voltage magnitude for loading conditions ranging from no load to full load. For typical transformers, the ratio of the normalized voltages at the two ends under no load conditions is approximately 1.0. Therefore the voltage regulation will be: R = 1.0 − V2u V V ( full load ) , where: V2u = 2 , and V1u = 1 . V2 n V1n V1u The subscript n means nominal voltage. Example E4.2: The equivalent circuit of a 14.4 kV/220 V, 60 Hz, 15 kVA transformer is illustrated in Figure E4.2. The transformer supplies at the secondary rated power under rated voltage with power factor 1.0. Compute: a) Page 12 Compute the voltage at the high side Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos b) c) ~ I1 ~ V1 20 Compute the transformer efficiency, and What is the transformer voltage regulation ~ I2 ~ I j300 3MΩ j1.4MΩ ~ E1 ~ V1 = 220 e j 0 Rated Load Power Factor = 10 ~ Ib ~ Ig High Voltage Side Low Voltage Side Figure E4.2. Parameters of the Transformer of Example E4.2 Solution: The data are marked on Figure E4.2. Note that o o 14400 ~ E1 = 220e j0 = 14400e j0 volts 220 ~ 15000 = 68.1818 A I2 = 220 o ~ 220 ~ I= I2 = 1.0416e j0 A 14400 a) The voltage at the transformer high side is computed as follows: o ~ 14, 400 j0o Ig = e =.0048e j0 A 3M Ω o 14 ,400 j0 o ~ Ib = e =.01028e − j90 A j1.4MΩ o o o o ~ ~ ~ ~ I1 = I + Ig + Ib = 1.0416e j0 +.0048e j0 +.01028e − j90 = 1.0465e − j.56 o o ~ V1 = 14, 400 + (20 + j300)(1.0465)e − j.56 = 14, 400 + 314.65e j.85.62 = 14, 427.4e j1.25 o b) The transformer losses are: Ploss = (20)(1.0465)2 + (3×106)(.0048)2 = 21.9 + 69.12 = 91.02 Watts Pout = 15,000 Watts Pin = 15,091.02 Watts η = 0.9939 c) The transformer voltage regulation is Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 13 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos R = 1.0 − 220 / 220 = 0.00187 14,427 / 14,400 4.3 The Per Unit System The per unit system is a scaling procedure by which physical quantities are expressed in a user selected set of units, called the bases. This transformation of physical quantities results in a transformation of the mathematical models for power apparatus. The basic idea of the procedure will be described first followed with examples. Then, the per unit system will be introduced axiomatically. The basic idea of the per unit system is to express physical quantities in a new system of units. Consider for example the physical quantity of complex power, S. S is a complex quantity and the unit of this quantity is VA (volt.ampere). Now assume that we want to establish a new unit for S which is SB VA, for example SB= 100 VA. Note SB is a scalar. Now the physical quantity S expressed in the new unit is Su, where Su = S/SB. Note that Su is now dimensionless. SB is referred to as the base for S and Su is the per unit value of S. Conceptually, this simple scaling procedure can be applied to all physical quantities. The bases for all physical quantities can be arbitrarily selected. In practice, however, we place constraints in the selection of the bases. For example, we require that physical laws such as Ohm’s law and the power equation are satisfied by the bases, i.e. VB = Z B I B S B = VB I B Where VB, ZB, IB, SB are the bases for voltage, impedance, current and power respectively. Above requirement limits the number of bases which can be selected arbitrarily. For the mentioned four quantities (V, Z, I and S), since they must satisfy two equations (above), then only two quantities can be arbitrarily selected. Usually, we arbitrarily select SB, VB. Then, the bases IB and ZB are determined from the power equation and Ohm’s law: IB = SB VB ZB = VB VB2 = I B SB The above described basic procedure will be illustrated with an example. Page 14 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Example E4.3: Consider the simplified circuit of Figure E4.3a. Select as bases for power and voltage SB = 1000 W and VB = 120 V, respectively. Then express the circuit equations in the new bases. r=2Ω 120Vrms ~ I jx = j2 Ω Figure E4.3a. A Simple Electric Circuit Solution: Since Then SB = 1000 W, VB = 120 V 120 2 = 14.4 Ω, and 1000 IB = 8.333 Amps ZB = The equation for the circuit of Figure E4.3a is ~ ~ ~ V = rI + jxI Dividing above equation by the voltage base, VB , and recognizing that VB = ZBIB, ~ ~ ~ jx I V r I = + VB Z B I B Z B I B or ~ ~ ~ Vu = ru I u + jxu I u where Vu= 1.0, ru= 0.1389, and xu= 0.1389. Thus ~ ~ 1.0 = 0.1389I u + j 0.1389I u The last equation is represented with the circuit of Figure E4.3b. Note that the circuit of Figure E4.3b is dimensionless. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 15 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 0.1389 1.0 ~ I j0.1389 Figure E4.3b. Scaled Version of the Simple Circuit of Figure E4.3a 4.3.1 Axiomatic Definition of the Per-Unit Scaling System The per unit system was introduced to simplify the modeling procedure of power systems. In this respect, there are some desirable characteristics that the per-unit scaling procedure should possess. These are: (a) The per unit system should be compatible with other standard systems, such as the metric system. Compatibility means that the physical laws should be described with the same familiar mathematical expressions, and (b) Bases should be selected so that scaled values are normally near unity. These requirement are met with a per unit system which satisfies the following axioms [???]: Axiom 1: Unscaled equations which describe physical laws shall be identical in form to their scaled versions. For example, a scaling procedure which converts Ohm's law to the form "V = kZI," where k ≠ 1 is unacceptable. Axiom 2: At a given location in a power system, the base value for each quantity to be scaled (voltage, current, impedance, power, etc.) must be unique. Axiom 3: Transformer models must be simplified by the scaling procedure. In the next section, we describe the procedure for selecting a per-unit system that meets above axioms. 4.3.2 Per-Unit Scaling Procedure The fundamental scaling equation is: per − unit value = actual value base value (4.1) where actual value base value per-unit value = the unscaled quantity in appropriate SI unit; a phasor or complex number or a function of time. = a real number selected to conform to the scaling axioms. = the scaled dimensionless quantity; a phasor or complex number, or a function of time. The term "quantity" here refers to any physical or mathematical entity relating to power system analysis, including, but not limited to, voltage, current, power, impedance, Page 16 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos resistance, inductance, capacitance, charge, flux linkage, time, torque, position (linear and angular), velocity, and acceleration. The procedure for selecting the bases for the per-unit system is similar to the process of selecting the SI system of units. Recall that the SI system of units [???] is based on a number of arbitrarily selected base units. All other units are expressed as functions of the base units and are called derived units. Consequently, it is necessary to follow the same procedure: arbitrarily select a minimum number of bases. These bases shall be called assigned bases. The remaining bases can be derived and shall be called derived bases. The derived bases must be selected such as axiom 1 is satisfied. For power engineering applications, is not necessary to select as assigned bases the full compliment of base SI units. For all practical power engineering applications, it suffices to select only the following three assigned bases: (a) power, (b) voltage, and (c) frequency. The derived bases of interest will be (a) time, (b) current, (c) impedance, (d) inductance, (e) capacitance, (f) electric charge, and (g) magnetic flux. The procedure is outlined below. Step 1: Select an arbitrary location in a power system as the reference bus. At this location, define: Assigned Bases fb = frequency base Vb = voltage base Sb = power base = normal operating system frequency, in Hz = nominal rms line-to-neutral voltage, in volts = nominal per phase power in VA Bases for all other physical quantities at this location can be derived from relations identical to those physical laws which interrelate the unscaled variables. Derived Bases tb = time base = Ib = current base = Zb = impedance base = Lb = inductance base = Cb = capacitance base = Qb = electric charge base = Copyright © A. P. Sakis Meliopoulos – 1990-2006 1 fb Sb Vb Vb Vb2 = I b Sb Zb Vb2 = 2πf b S b 2πf b Sb 1 = 2πf b Z b 2πf bVb2 Sb C bVb = 2πf bVb (4.2) Page 17 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos λb = magnetic flux base = Lb I b = Vb 2πf b Step 2: Select the assigned base values at the next location (bus) of the system. Two cases are recognized: Case 1: There is no transformer between the present location and another location (for example bus k) where the bases have already been assigned. In this case the assigned bases should be the same as the assigned bases at bus k. Note that the derived bases will be also the same. Case 2: There is a transformer between the present location and another location (for example bus k) where the bases have already been assigned. In this case we apply axiom 2 which requires that the transformer model be simplified by the scaling procedure. Let us examine the transformation of transformer models by the scaling procedure and then decide how to choose the bases. Consider a single phase transformer of transformation ratio t = N1/N2. Assume that the assigned bases have been determined at one side of the transformer, fb1, Sb1, and Vb1. It is self-understood that the derived bases have been also determined via equations (4.2). We consider the problem of selecting the assigned bases at the other side (side 2) of the transformer, i.e., fb2, Sb2, and Vb2. The equations describing the transformer are (for simplicity the magnetizing current is neglected): di1 (t ) dφ (t ) + N1 dt dt di 2 (t ) dφ (t ) v 2 (t ) = r2 i 2 (t ) + Ll 2 + N2 dt dt i1 (t ) N2 =− i2 (t ) N1 v1 (t ) = r1i1 (t ) + Ll1 The per-unitized equations are obtained by dividing the first equation by Vb1, and the second equation by Vb2. In the process, we can substitute Vb1 with its equal Ib1Zb2 , etc., as appropriate yielding: ⎛ i (t ) ⎞ d ⎜⎜ 1 ⎟⎟ v1 (t ) r i (t ) L ⎝ I b1 ⎠ N 1 dφ = 1 1 + l1 + Vb1 Z b1 I b1 Lb1 ⎛ t ⎞ Vb1 dt d ⎜⎜ ⎟⎟ ⎝ t b1 ⎠ Page 18 (4.3) Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos v 2 (t ) r i (t ) L = 2 2 + l2 Vb 2 Z b2 I b2 Lb 2 ⎛ i (t ) ⎞ d ⎜⎜ 2 ⎟⎟ ⎝ I b 2 ⎠ N 2 dφ + ⎛ t ⎞ Vb 2 dt d ⎜⎜ ⎟⎟ ⎝ tb2 ⎠ (4.4) i1 (t ) I b1 N I = − 2 b2 i 2 (t ) N 1 I b1 I b2 or di1u (t ) N 1 dφ (t ) + dt u Vb1 dt di (t ) N dφ (t ) v 2u (t ) = r2u i 2u (t ) + Ll 2u 2u + 2 dt Vb 2 dt i1u (t ) N I = − 2 b2 i 2u (t ) N 1 I b1 v1u (t ) = r1u i1u (t ) + Ll1u Imposing that the power flow equations will remain invariant (axiom 1) results in the additional requirements: Sb2 = Sb1 , tb2 = tb1 In this case, Ib1 = Sb1/Vb1, Ib2 = Sb2/Vb2 and therefore Ib2/Ib1 = Vb1/Vb2. Note now that the i (t) N / Vb 2 =− 2 last equation becomes iu . Above equations represent a transformer with i 2u ( t ) N 1 / Vb1 transformation ratio N1/Vb1 = N2/Vb2 which is illustrated with the circuit of Figure 4.7a. The circuit of Figure 4.7a is simplified if the bases are selected so that the transformation ratio of the ideal transformer is 1:1: N1 N 2 = Vb1 Vb 2 or N2 ⎛1⎞ Vb1 = ⎜ ⎟Vb1 N1 ⎝t ⎠ In this case, per unitized equations of the transformer become: Vb 2 = v1u (t ) = r1u i1u (t ) + Ll1u Copyright © A. P. Sakis Meliopoulos – 1990-2006 (4.5) di1u (t ) + eu (t ) dt u Page 19 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos v 2u (t ) = r2u i 2u (t ) + Ll 2u di2u (t ) + eu (t ) dt i1u (t ) = −1 i 2u (t ) where: eu (t ) = N 1 dφ (t ) N 2 dφ (t ) = Vb1 dt Vb 2 dt Above equations are represented with the circuit of Figure 4.7b. Note that in this case axiom 3 is satisfied, that is the equivalent circuit of the transformer has been simplified, the ideal transformer has been removed. However, many times it is not possible to select the bases according to Equation (4.5). An example will be given later. In this case, the per unitized transformer model includes an ideal transformer as illustrated in Figure 4.6a. i1u(t) r1u l1u Ideal Transformer l2u r2u i2u(t) v2u(t) v1u(t) N1 N2 = Vb1 Vb2 (a) i1u(t) r1u l1u l2u r2u i2u(t) v2u(t) (b) Figure 4.7. Perunitization of a Transformer (a) Circuit Realization of Equations (4.3) and (4.4) (b) Equivalent Circuit in Case N1/Vb1 = N2/Vb2 Above completes the procedures for the selection of the bases. Page 20 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos In summary, a practical way to apply above procedure to a power system is as follows: Classify all power system components as shunt or series components. Shunt components are those which are connected to one bus only, i.e. generators, loads, capacitor banks, etc. Series components are those which interconnect two buses. Examples include power transmission lines, transformers, solid state converters, etc. Select a bus of the power system, any bus. At this bus (let it be bus i), select the "assigned bases" as follows: (1) (2) (3) (4) The voltage base is selected to be the "nominal" line to ground rms voltage of the bus. The power base at bus i is arbitrarily selected to be Sb The frequency base at bus i is selected to be fb=normal operating system frequency at bus i. All other bases (derived) at bus i are computed from Equations (4.2). Select the assigned bases for all other buses proceeding one bus at a time. Specifically: (1) Consider a series component between buses j and k, for which the assigned bases have been determined at bus j but not at bus k. (2) If the series component is: (a) other than transformer: assign bases at bus k same as at bus j, (b) a transformer with nominal transformation ratio t: assign bases at this bus as follows: Sbk = Sbj Vbk = Vbjt fbk = fbj where t is the transformation ratio of the transformer. (3) Compute the derived bases at bus k with Equations (4.2). The per-unitization process is completed when assigned and derived bases have been defined for all buses in the system. 4.3.3 Mutually Coupled Circuits Consider two mutually coupled circuits (1 and 2). Assume that the two circuits are mutually coupled and that the assigned bases have been determined for the two circuits, i.e. fb1, Sb1, Vb1 and fb2 = fb1, Sb2 = Sb1, and Vb2. This system is illustrated in Figure 4.7. The equations describing this system are: ~ ~ ~ ~ V1 j − V1k = Z 1 I 1 + Z m I 2 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 21 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos ~ ~ ~ ~ V2 j − V2 k = Z 2 I 2 + Z m I 1 Above equation can be scaled by dividing the first equation by Vb1 and the second equation by Vb2, yielding ~ Zm I2 ~ ~ ~ V1 ju − V1ku = Z 1u I 1u + ~ Z b1 I b1 ~ Z m I1 ~ ~ ~ V 2 ju − V 2 ku = Z 2u I 2u + ~ Z b2 I b2 ~ I1 ~ V1 j ~ V2 j Z1 ~ V1k Zm ~ I2 ~ V2 k Z2 Figure 4.8 Two Mutually Coupled Circuits In above equations we used the fact that Vb1 = Zb1Ib1 and Vb2 = Zb2Ib2. Now observe that Z b1 I b1 = I b 2 Z b1 Z b 2 Z b 2 I b 2 = I b1 Z b1 Z b 2 The proof of above relationship can be affected by direct substitution of the equations of derived base quantities in terms of the assigned base quantities. Upon substitution in the equation for the coupled circuits: ~ ~ ~ V1 ju − V1ku = Z 1u I 1u + ~ ~ ~ V2 ju − V2 ku = Z 2u I 2u + Zm Z b1 Z b 2 Zm Z b1 Z b 2 ~ I 2u ~ I 1u Above equations suggest that the base for the mutual impedance should be Z bm = Z b1 Z b 2 Page 22 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Z mu = Zm Z bm Now the equations of the mutually coupled circuits are ~ ~ ~ ~ V1 ju − V1ku = Z1u I1u + Z mu I 2u ~ ~ ~ ~ V2 ju − V2 ku = Z 2u I 2u + Z mu I 1u The per-unitization process of a system with multiple mutually coupled circuits, such as a transformer with multiple windings or a synchronous generator, is rather complex. The per-unitization of a synchronous generator model will be addressed in Chapter 5. The interested reader should also consult Reference [???] for a comprehensive per-unitization procedure of the synchronous generator model. The per unitization procedure will be illustrated with two examples. Example E4.4: Consider the equivalent circuit of a single phase transformer and a load as it is illustrated in Figure E4.4. Select a per unit system, and per-unitize the equivalent circuit of Figure E4.4. The transformer is a 2400V/240V, 5 kVA transformer. 10Ω j100 Ω j1Ω 0.1Ω + 2450 V 11Ω -6 2x10 Ω -5 -j10 Ω j3Ω - 10:1 Figure E4.4 Equivalent Circuit of a Transformer and Electric Load Solution: The assigned and derived bases are: Primary Side: Vb1 = 2400 V Sb1 = 5000 VA 5000 = 2.0833 A Ib1 = 2400 (2400)2 Zb1 = = 1152 Ω 5000 1 Yb1 = = .000868055 S ZB Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 23 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Secondary Side: Vb2 = 240 V Sb2 = 5000 VA Ib2 = 20.833 A Zb2 = 11.52 Ω Yb2 = .0868055 S Upon computation of transformer parameters on the new base, the equivalent circuit of Figure E4.4b is obtained. j.0868 .00868 .00868 j.0868 + 1.0208 0.95486 .002304 -j.01152 j0.2604 - Figure E4.4a Per-Unitized Circuit of the System of Figure E4.4 Example E4.5: Consider an example power system. The positive sequence model of this system is illustrated in Figure E4.5. Assume that the assigned bases at bus 1 are fb1 = 60 Hz, Sb1 = 33.333 MVA, and Vb1 = 7.2 kV. a) Select the assigned bases at all buses of the system. b) Compute the per unit positive sequence network of the system. j0.2 ohms 1 j0.12 ohms 4+j50 ohms 2 3 j13 ohms 4 j0.25 ohms 7.2 kV 10.4 kV 7.2:66.4 66.4:10.4 1.5+j15 ohms 2.5+j28 ohms 5 j12.5 ohms 6 110:115 Figure E4.5 Positive Sequence Network of an Example Power System Solution: a) The assigned bases for all buses are selected and listed in Table E4.5a. Page 24 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Table E4.5a Assigned Bases for the Example System of Figure E4.5 Bus Vb(kV) Sb(MVA) fb(Hz) 1 2 3 4 5 6 7.2 66.4 66.4 10.4 66.4 66.4 33.333 33.333 33.333 33.333 33.333 33.333 60 60 60 60 60 60 Note that the derived bases are calculated directly from Equations (4.2). For example, at bus 6: Ib = Sb/Vb = 0.50196 kA Zb = Vb/Ib = 132.282 Ohms Lb = Zb/2πfb = 0.35089 H tb = 1/fb = 16.6667 ms, etc. b) The base impedances are computed using equations (4.2) and listed in Table E4.5b. Using the bases of Tables E4.5a and E4.5b, the per unit positive sequence network is computed and shown in Figure E4.5a. Table E4.5b Derived Impedance Bases for the Example System of Figure E4.4 Bus 1 2 3 4 5 6 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Zb (ohms) 1.555 132.282 132.282 3.245 132.282 132.282 Page 25 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos j0.1286 1 j0.077 0.302+j0.378 2 3 j0.098 1.0 4 j0.077 1.0 0.011+j0.1134 0.019+j0.2117 5 j0.0945 6 0.9565:1.0 Figure E4.5a Per Unit Positive Sequence Network of the Example System of Figure E4.5 4.3.4 The Per Unit System and Numerical Accuracy The advantages of the per unit system are two: (a) the numerical values of the per unit voltages indicate how close the voltages are near nominal values, i.e. a per unit value of 0.98 indicates that the voltage is 98% of the nominal value, and (b) the per unit values are dimensionless. Her we will discuss another less obvious advantage. Specifically, the per unit system conditions the power system equations in such a way that the numerical precision of computations on a finite precision computer will be increased. Recall a recent result [???] which states that the numerical error of a system of equations is proportional to the matrix condition number k which is defined as the ratio of the largest to the smallest singular value of the matrix, i.e. k = σmax/σmin. The per unit system results in system equations with smaller condition number and thus increased numerical accuracy. This property will be illustrated with an example. Example E4.6: Consider a 15 kVA, 14.4 kV/220 V, 60 Hz single phase distribution transformer. The parameters of the transformer are illustrated in Figure E4.6. For simplicity, the coil resistance will be neglected. The model describing the transformer of Figure E4.6 (see section ???) is: di (t ) di1 (t ) + Lm1 m1 dt dt di 2 (t ) Lm1 di m1 (t ) v 2 (t ) = Ll 2 + dt t dt v1 (t ) = Ll1 Page 26 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 1 i m1 (t ) = i1 (t ) + i 2 (t ) t Upon elimination of the magnetizing current, im1(t): di1 (t ) di (t ) L di (t ) + Lm1 1 + m1 2 dt dt t dt di (t ) L di (t ) L di (t ) v 2 (t ) = Ll 2 2 + m1 1 + m2 1 2 dt t dt dt t v1 (t ) = Ll1 i1(t) Ll 1 v1(t) Ll 2 i2(t) v2u(t) Lm1 14400:220 Figure E4.6 Single Phase Distribution Transformer Assume this model is to be used for transient analysis. Integrating above equations using the trapezoidal rule, with an integration step of h, we obtain: ⎡ 2( Ll1 + Lm1 ) ⎢ h ⎡ v1 (t ) ⎤ ⎢ = ⎢v (t )⎥ ⎢ ⎣ 2 ⎦ ⎢ 2 Lm1 ⎢ th ⎣ 2 Lm1 ⎤ ⎥ th ⎥ ⎧⎡ i (t ) ⎤ ⎡ i (t − h) ⎤ ⎫ ⎡ v1 (t − h) ⎤ Lm1 ⎞ ⎥ ⎨⎢ 1 ⎥ − ⎢ 1 ⎛ − 2⎜ Ll 2 + 2 ⎟ ⎣i 2 (t )⎦ ⎣i 2 (t − h)⎥⎦ ⎬ ⎢⎣v 2 (t − h)⎥⎦ ⎩ ⎭ t ⎠⎥ ⎝ ⎥ h ⎦ What we would like to do is to study the numerical properties of the matrix before and after per-unitization. For this purpose, select: Assigned Bases: High voltage side: Power : 15 kVA Voltage: 14.4 kV Frequency: 60 Hz Low voltage side: Power : Voltage: Copyright © A. P. Sakis Meliopoulos – 1990-2006 15 kVA 220 V Page 27 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Frequency: 60 Hz Derived Bases: High voltage side: Low voltage side: Mutual inductance base: Lb1 = 36.6693 H Lb2 = 0.00856 H Lbm= 0.56026 H Using these bases and an integration time step of h = 100 microseconds, the matrices are: Actual Units: ⎡74.2802645 1.1347166 ⎤ 10 6 × ⎢ ⎥ ⎣ 1.1247166 0.0173378⎦ Per-Unitized Matrix: ⎡ 33.7613 33.7577 ⎤ 10 3 × ⎢ ⎥ ⎣33.7577 33.7613 ⎦ Upon computation of the singular values of above matrix (using a mathematical package), we obtain: Actual Units Matrix: Largest singular value: Smallest singular value: Matrix condition number: 74.2975 0.3694 x 10-5 2.113 x 107 Per-Unitized Matrix: Largest singular value: Smallest singular value: Matrix condition number: 67.519 0.3597 x 10-2 1.8770 x 104 Note that the per-unitization reduced the condition number of the matrix by a factor of 1071.5! (a reduction of three orders of magnitude). This means the numerical truncation error will be reduced by a factor of 1071.5 using the per-unitized equations [???]. 4.3.5 Discussion The per unit system has three advantages: (1) power system component models are simplified, for example recall the case of a transformer, (2) the per unit values of voltage or power may be meaningful, for example a value of 1.0 pu for voltage may mean that Page 28 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos the voltage is equal to the nominal voltage, and (3) the model equations are better conditioned from the numerical point of view. Advantage (2) is very important from the practical point of view and applies to other quantities as well. Consider for example the leakage impedance of a transformer. When it is expressed in p.u. (using transformer ratings as the bases), the pu leakage impedance is typically constant for specific designs. Specifically, large power transformers have a leakage impedance of 0.07 to 0.1 pu. Small distribution class transformers have a leakage impedance of about 0.02 to 0.03 pu., etc. In other words while the parameters of a transformer may span a large range, when they are perunitized using the rated values as bases, the parameter values are located in a relatively narrow range. 4.4 Three Phase Transformers Three phase transformers can be constructed in a number of ways. Three of the most usual constructions are illustrated in Figure 4.9. Figure 4.9a illustrates a three phase core type transformer. The core has three legs, on each leg there are two windings for a total of six windings. Similarly, Figure 4.9b illustrates a shell type transformer which also has six windings. Figure 4.9c illustrates a “bank” of three single phase transformers. This arrangement also has six windings. The six windings of any configuration (a), (b), or (c) are grouped in two groups of three, the primary and the secondary. For example, in Figure 4.9a the primary may be the three windings located on the upper part of each leg and the secondary may be the other three winding. Both the primary and secondary windings may be connected in a delta or wye configurations leading to four possible arrangements of a three phase transformer: (a) delta-delta, (b) wye-delta, (c) delta-wye and (d) wye-wye. These arrangements are schematically represented in Figure 4.10. Note that from the circuit point of view, all three phase transformer constructions are similar, i.e. all have six winding grouped into three phases. However the magnetic circuit of each one of these constructions is different. For example, the three phase transformer bank consists of three independent magnetic circuits. The shell and core type three phase transformers are characterized with coupled magnetic circuits of the three phases. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 29 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos (a) (b) (c) Figure 4.9 Three Phase Transformers (a) Core Type (b) Shell Type (c) Three Single Phase Transformer Bank The model of a three phase transformer bank is the simplest since it consists of the interconnection of three single phase transformers. Replacing each one of the single phase transformers with its equivalent circuit, the equivalent circuit of the three phase transformer is obtained. This has been done in Figure 4.11 where the simplified equivalent circuit of a single phase transformer has been used. The Figure illustrates a delta-wye connection. In subsequent paragraphs we will consider first the ideal three phase transformer model for the purpose of examining its basic characteristics. Then the non-ideal transformer model will be studied. The use of the symmetrical transformation to the three phase transformer model will result in the sequence models. Page 30 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Y Y Y Y Figure 4.10 Schematic Representation of Three Phase Transformers ~ VA ~ VB ~ VC ~ IA ~ I 'a ~ Ia ~ I'b ~ Ib ~ I 'c ~ Ic ~ Va ~ IB ~ Vb ~ IC ~ Vc α:1 Figure 4.11 Delta-Wye Connected Three Phase Transformer Model 4.4.1 The Ideal Three Phase Transformer Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 31 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos An ideal three phase transformer consists of three ideal single phase transformers. The transformer of Figure 4.10 will be ideal if Y = ∞ (short circuit). The voltage relationships of an ideal three phase transformer are: ~ ~ V AB = aVan ~ ~ V BC = aVbn ~ ~ VCA = aVcn Under balanced operating conditions, the voltages will be: o ~ ~ VBn = V An e − j120 o ~ ~ VCn = V An e − j 240 o ~ ~ Vbn = Van e − j120 o ~ ~ Vcn = Van e − j 240 Note that: o o ~ ~ ~ ~ ~ ~ V AB = V An − VBn = V An − V An e − j120 = 3V An e j 30 o o o ~ ~ ~ ~ ~ ~ V BC = V Bn − VCn = V An e − j120 − V An e + j120 = 3V An e − j 90 o o o ~ ~ ~ ~ ~ ~ VCA = VCn − V An = V An e + j120 − V An e − j120 = 3V An e − j 210 Now the relationship between the primary and secondary voltages can be found. a ~ − j 30o ~ V An = Van e 3 Æ a ~ − j 30o ~ V Bn = Vbn e 3 Æ a ~ − j 30o ~ VCn = Vcn e 3 Æ ~ V An a − j 30 0 e ~ = V an 3 ~ V Bn a − j 30 0 e ~ = Vbn 3 ~ VCn a − j 30 0 e ~ = V cn 3 Above equations indicate that the per phase (positive sequence) equivalent model of a delta-wye connected ideal three phase transformer is a single phase ideal transformer with transformation ratio: ~ 0 V An a − j 30 0 n= ~ = e = te − j 30 V an 3 Note that in this case the transformation ratio is a complex number. Page 32 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 4.4.2 Non-Ideal Three Phase Transformer Model The non-ideal three phase transformer model can be derived from the proper interconnection of the non-ideal single phase transformers. For simplicity we assume that each single phase transformer is represented with its simplified non-ideal model. For the case of a delta-wye connected transformer, the result is illustrated in Figure 4.11. For the circuit of Figure 4.11, the following relationships are valid: ~ ~ ~ ~ I a' = (V A − V B − aVan )Y ~ ~ ~ ~ I b' = (V B − VC − aVbn )Y ~ ~ ~ ~ I c' = (VC − V A − aVcn )Y ~ ~ I a = −aI a' ~ ~ I b = −aI b' ~ ~ I c = −aI c' ~ ~ ~ I A = I a' − I c' ~ ~ ~ I B = I b' − I a' ~ ~ ~ I C = I c' − I b' ~ ~ ~ ~ ~ ~ Upon elimination of the variables E a , E b , E c and Ia' , Ib' , Ic' and expressing the remaining currents as a function of the voltages we obtain a set of six equations which, written in matrix notation, are: ~ ~ ⎡Ia ⎤ ⎡a2 0 0 −a a 0 ⎤ ⎡V a ⎤ ⎢~ ⎥ ⎥⎢ ~ ⎥ ⎢ 2 0 0 − a a ⎥ ⎢Vb ⎥ ⎢Ib ⎥ ⎢ 0 a ~ ⎢ I~c ⎥ ⎢ 0 0 a2 0 − a ⎥ ⎢V c ⎥ a = Y ⎢~ ⎥ ⎥⎢ ~ ⎥ ⎢ 2 − 1 − 1 ⎥ ⎢V A ⎥ a ⎢I A ⎥ ⎢− a 0 ⎢ I~ ⎥ ⎢ a − a 0 − 1 2 − 1 ⎥ ⎢V~ ⎥ B ⎢~ ⎥ ⎥ ⎢ ~B ⎥ ⎢ a − a − 1 − 1 2 ⎦⎥ ⎢⎣VC ⎥⎦ ⎢⎣ I C ⎥⎦ ⎣⎢ 0 Note that above equation expresses the input/output relationship of the three phase transformer. In compact matrix form, above equation can be written as ~ ⎡ I abc ⎤ ⎡ a2I = Y ⎢~ ⎥ ⎢ T ⎣ − aE ⎣ I ABC ⎦ ~ − aE ⎤ ⎡ V abc ⎤ ⎥⎢ ~ ⎥ F ⎦ ⎣V ABC ⎦ where I is 3x3 identify matrix, and the matrices E and F are: ⎡ 1 −1 0 ⎤ E = ⎢⎢ 0 1 − 1⎥⎥ ⎢⎣− 1 0 1 ⎥⎦ Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 33 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos ⎡ 2 − 1 − 1⎤ F = ⎢⎢− 1 2 − 1⎥⎥ ⎢⎣− 1 − 1 2 ⎥⎦ Above equations represent the simplified model of a delta-wye connected three phase transformer. The same procedure can provide the models for other connections, i.e. deltadelta, wye-wye and wye-delta connections. 4.4.3 Sequence Circuits of Three Phase Transformers Three phase transformers are inherently symmetric three phase elements. This means that by applying the symmetrical transformation, their model can be transformed to three equivalent circuits, namely the positive, negative and zero sequence equivalent circuits. The procedure will be illustrated on a delta-wye connected transformer model developed in the previous paragraph. It should be understood that the procedure equally applies to any other configuration. The phase voltages and currents are substituted with their corresponding symmetrical components as follows ~ ~ I abc = T −1 I R120 ~ ~ I ABC = T −1 I L120 ~ ~ Vabc = T −1V R120 ~ ~ V ABC = T −1V L120 where R and L indicate right and left side respectively. Replacing the phase quantities with the symmetrical components, the equation for the three phase transformer becomes: ~ ⎡ I R120 ⎤ ⎡ a 2 TIT −1 ⎢~ ⎥ = Y ⎢ T −1 ⎣ − aTE T ⎣ I L120 ⎦ ~ − aTET −1 ⎤ ⎡V R120 ⎤ ⎥⎢ ~ ⎥ TFT −1 ⎦ ⎣V L120 ⎦ Note that by direct evaluation, the following apply: TIT −1 = I Page 34 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos TET −1 ⎡ 3e j 30 ⎢ =⎢ 0 ⎢ 0 ⎣ TE T T −1 TFT −1 o ⎡ 3e − j 30 ⎢ =⎢ 0 ⎢ 0 ⎣ 0 o 3e − j 30 0 o 0 o 3e j 30 0 0⎤ ⎥ 0⎥ 0⎥ ⎦ 0⎤ ⎥ 0⎥ 0⎥ ⎦ ⎡3 0 0⎤ = ⎢⎢0 3 0⎥⎥ ⎢⎣0 0 0⎥⎦ Upon substitution and grouping the six equations into three groups of two we obtain: o ~ a2 a j 300 ~ ~ ~ ~ 3YV R1 − I R1 = a 2 YV R1 − 3aYe j 30 V L1 = e 3YV L1 3 3 o ~ a − j 300 ~ ~ ~ ~ I L1 = − 3aYe − j 30 V R1 + 3YV L1 = − e 3YV R1 + 3YV L1 3 o ~ a2 a − j 300 ~ ~ ~ ~ 3YV R 2 − 3YV L 2 I R 2 = a 2 YV R 2 − 3aYe − j 30 V L 2 = e 3 3 o ~ a j 300 ~ ~ ~ ~ I L 2 = − 3aYe j 30 V R 2 + 3YV L 2 = − e 3YV R 2 + 3YV L 2 3 a2 ~ ~ ~ I R 0 = a 2 YV R 0 = 3YV R 0 3 ~ I L0 = 0 Note that above relations represent three independent set of equations corresponding to three equivalent circuits which are illustrated in Figure 4.12. The variables appearing in Figure 4.12 are: te − j 30 = 0 a 3 e − j 30 , Therefore: t = 0 a 3 The reader is encouraged to verify that the circuits of Figure 4.12 correspond to the above developed equations. For this purpose, the terminal currents in Figure 4.12 should be expressed as functions of the terminal voltages and the resulting equations should be compared to the above equations. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 35 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos An example will illustrate the procedure. ~ I L1 ~ I R1 3Y Ideal Transformer ~ V L1 ~ V R1 te − j 30 : 1 0 ~ I L2 ~ I R2 3Y Ideal Transformer ~ VL 2 ~ VR 2 0 te j 30 : 1 ~ I L0 ~ VL 0 ~ I R0 3Y Ideal Transformer ~ VR 0 t :1 Figure 4.12 Sequence Equivalent of a Delta - Wye Connected Three Phase Transformer Example E4.7: A three phase transformer bank is made from three phase transformers. Each single phase transformer has the equivalent circuit of Figure E4.7a. The three phase connections are illustrated in Figure E4.7b. a) Draw the positive sequence equivalent circuit of the three phase transformer bank with all impedances shown on the left hand side. The transformer ratio and the impedance values should be clearly marked in actual quantities, i.e. volts and ohms. b) Draw the positive sequence equivalent circuit of the three phase transformer bank with all impedances shown on the right hand side. The transformer ratio and the impedance values should be clearly marked in actual quantities, i.e. volts and ohms. c) Draw the per phase equivalent circuit in per unit of the three phase transformer bank using the following bases. Left Hand Side: Page 36 Sb = 100 MVA (one phase) Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Vb1 = 66.395 kV (line to neutral) Sb = 100 MVA (one phase) Vb2 = 6.9282 kV (line to neutral) Right Hand Side: j6.6125Ω j0.024Ω 115kV: 12 kV 3 S=100MVA (a) A a B b C c (b) Figure E4.7 Construction of a Three Phase Transformer Bank (a) Circuit Model of Single Phase Transformer (b) Three Phase Connections. Each Block Represents the Single Phase Transformer of (a) Solution: The equivalent circuit of Figure E4.7a can be modified by referring the j0.024 ohm leakage impedance on the left hand side. By doing so, the three phase transformer model becomes identical to the circuit of Figure 4.12 with Y= 1 S = − j 0.07561 S j13.225 and a= 115.0 3 = 16.5988 12.0 a) By utilizing the results of the previous section, the positive sequence equivalent circuit of the transformer is shown in Figure E4.7a. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 37 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos -j0.2268 S Ideal Transformer 16 . 5988 e − j 30 : 1 0 Figure E4.7a b) By referring the admittance on the left hand side, the positive sequence equivalent circuit of Figure E4.7b is obtained. -j62.4962 S Ideal Transformer 16 . 5988 e − j 30 : 1 0 Figure E4.7b b) The base admittance at the left hand side is: S Yb1 = b21 = 0.02268 S . Vb1 The per unit value of the admittance is: Y1u = − j 0.2268 = − j10.0 . 0.02268 The per unit transformation ratio is: 16.5988 3 e − j 30 0 0 12 : 1 = e − j 30 : 1 . 115 Therefore the per unit equivalent circuit is shown in Figure E4.7c. Similarly the circuit of Figure E4.7d is developed. Page 38 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos -j10.0 Ideal Transformer e − j 30 : 1 0 Figure E4.7c -j10.0 Ideal Transformer e − j 30 : 1 0 Figure E4.7d 4.5 Autotransformers Autotransformers are extensively used in power systems for interconnecting two parts of a system operating at different voltages. Autotransformers are also used in many other applications. For example, a variac is an autotransformer. Autotranformers can be single phase devices or three phase devices. Both of these devices will be examined next. 4.5.1 Single-Phase Autotransformers The construction of a single phase autotransformer is simpler than the usual transformer, because it requires only one winding. The construction of a single phase autotransformer is illustrated in Figure 4.13a. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 39 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos φ i1 (t) + i2 (t) A V1 (t) N1 _ + N2 V2 (t) _ (a) + V1 + V2 _ _ (b) Figure 4.13 Single Phase Autotransformer (a) Construction (b) Symbolic Representation The basic relations of an autotransformer can be derived by assuming that the autotransformer is ideal. Let ϕ be the magnetic flux inside the core of the autotransformer of Figure 4.13a. Note that dϕ (t ) dt dϕ (t ) v 2 (t ) = N 2 dt v1 (t ) = N 1 Ρ = ( N 1 − N 2 )i1 (t ) + N 2 (i1 (t ) + i 2 (t )) = ℜϕ (t ) = 0 Forming the ratio of the voltages and currents: v1 (t ) N 1 = v 2 (t ) N 2 i1 (t ) N =− 2 i 2 (t ) N1 The power relationships are p (t ) = v1 (t )i1 (t ) = − v 2 (t )i 2 (t ) Page 40 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Above relationships of the ideal autotransformer are also valid for the phasors of the voltages and currents, i.e. ~ V1 N1 ~ = V2 N 2 ~ I1 N2 ~ =− N1 I2 ~~ ~~ S = V1 I 1* = −V2 I 2* Note that above equations are identical to the equations of the ideal two winding transformer. 4.5.2 Three Phase Autotransformers Three phase autotransformers have magnetic circuits similar to those of the usual transformers, except that there is only one winding on each magnetic leg of the transformer with a secondary tap. This winding forms one phase of the three phase autotransformer. Because of this arrangement and because of the need to ground the autotransformer, three phase autotransformers are always wye-wye connected. The analysis of these transformers follows the same procedure as the usual three phase transformers. 4.6 The Regulating Transformer The regulating transformer is a transformer arrangement which allows a variable transformation ratio. This ratio may be a real or a complex number. Typical constructions of regulating transformers are shown in Figure 4.14. Close examination of the topology of these transformers will reveal that that transformers 4.14a and 4.14b simply regulate voltage magnitude while transformer 4.14c regulate both voltage magnitude and phase. Transformers that regulate both magnitude and phase of the voltage are referred to as phase shifters. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 41 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos A a N b C c B (a) a A b B c C (b) a A b B c C (c) Figure 4.14 Example Construction of Regulating Transformers (a) Variable Tap UnderLoad Transformer (b) Voltage Magnitude Regulating Transformer (c) Phase Shifter Transformer Page 42 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Consider a regulating transformer which regulates both voltage and real power (phase shift). This transformer is structurally a symmetric three phase element. By modeling each component of this transformer and subsequent application of the symmetrical transformation, the positive, negative and zero sequence equivalent circuits can be developed. The details are omitted. The result is illustrated in Figure 4.15. The regulating properties of the transformer are expressed with the complex transformation ratio n = te jα . In Figure 4.15, y is the series admittance of the transformer while ys is the shunt admittance (magnetizing admittance). It should be clear that the per unit system can be applied to the models of Figure 4.15 yielding the perunitized positive, negative, and zero sequence models of the transformer. The models will be identical to those of Figure 4.15 with the exception that the parameters y, ys, and t will assume their per unit values. Thus Figure 4.15 illustrates either the actual sequence model or the perunit sequence model. ~ I L1 ~ I R1 y ~ V L1 yS Ideal Transformer ~ V R1 te − j 30 : 1 0 ~ I L2 ~ I R2 y ~ VL 2 yS Ideal Transformer ~ VR 2 0 te j 30 : 1 ~ I L0 ~ I R0 y ~ VL 0 yS Ideal Transformer ~ VR 0 t :1 Figure 4.15 Sequence Models of the Phase Shifter (a) Positive Sequence Model (b) Negative Sequence Model (c) Zero sequence Model Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 43 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos The voltage/current relationship for the regulating transformer can be developed directly from the equivalent circuits. As an example consider the positive sequence model (Figure 4.15a). Note that the voltage and current (in per unit) at the right hand side of the ideal ~ ~ transformer are V R 2 , and I R 2 . The voltages and currents at the other side of the ideal transformer will be: ~ te − jα V R 2 and 1 ~ I R 2 respectively. te jα These expressions are derived on the basis of zero power consumption inside the ideal ~ ~ transformer. Next, and with the help of Figure 4.15a, the currents I L1 and I R1 are ~ ~ expressed in terms of VL1 , V R1 : ~ ~ ⎡ I L1 ⎤ ⎡ y − te − jα y ⎤ ⎡VL1 ⎤ ⎢~ ⎥ = ⎢ ⎥⎢ ~ ⎥ jα 2 ⎣ I R1 ⎦ ⎣− te y t ( y + y s )⎦ ⎣VR1 ⎦ (4.6) For an equivalent circuit to exist, the admittance matrix must be symmetric. Thus only when α is real, an equivalent circuit exists and it is illustrated in Figure 4.16. The admittance between node 1 and 2 equals the negative of the entry (1,2) of the admittance matrix, i.e., the shunt admittance at node 1 will be equal to the sum of entries (1,1) and (1,2) of the admittance matrix i.e., the shunt admittance at node 2 will be equal to the sum of the entries (2,1) and (2,2) of the admittance matrix. The modeling of regulating transformers is illustrated with an example. ~ I L1 ~ V L1 ty (1-t)y ~ I R1 (t2-t)y+t2ys V~R1 Figure 4.16 pi-Equivalent Circuit of the Regulating Transformer of Figure 4.14a, for α=0 Example E4.8: Consider the four bus system of Figure E4.8. The electric load at bus 4 is 2.2 pu. The generating unit 2 generates 1.8 pu real power. The transformer is an off nominal tap transformer, its reactance is j0.08 pu and the transformer tap is set to 1.05 pu (bus 4 is the high side). The line data are given in Table E4.8. Derive the positive sequence equivalent circuit of the system in per unit. Page 44 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Table E4.8 System Data Circuit L1 L2 L3 From Bus 1 2 1 To Bus 2 3 4 Series Admittance -j10.0 -j9.0 -j12.5 Shunt Admittance J0.03 J0.02 J0.05 Solution: The positive sequence pi-equivalent parameters of the off-nominal tap transformer are : ys34 = (1.052 - 1.05) (-j12.5) = -j0.65625 ys43 = (1 - 1.05) (-j12.5) = +j0.625 y34 = (1.05) (-j12.5) = -j13.125 The overall positive sequence equivalent circuit is illustrated in Figure E4.8a. Slack bus 1 G2 2 L1 C1 L2 3 L3 T1 4 SD4 Figure E4.8 A Four Bus Example Power System Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 45 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos G2 G1 2 -j10 1 j.02 j.03 j.03 -j9 j.02 j.05 j.02 3 -j12.5 -j0.65625 j.05 -j13.125 j0.625 4 SD4 Figure E4.8a Positive Sequence Equivalent Circuit (in per unit) of the System of Figure E4.8 Example E4.9: Consider the simplified power system of Figure E4.9. Select bus 1 to be the reference bus and assume: S b = 100 MVA / 3, Vb = 15 kV / 3, f b = 60 Hz All the transmission lines have the same series impedance of 2.0+j23.5 ohms and negligible shunt impedance. It is desirable to develop the per-unit model of this system. For this purpose (a) select the assigned bases for the remaining buses 2, 3, 4, 5, and 6, (b) compute the positive sequence per-unit model of this system. Page 46 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 250MVA 15kV 60 Hz 1 450MVA 25kV 60 Hz Y 2 Y 3 4 Z=2.0+j23.5 Ohms 15/230kV 250 MVA 7.5% 230/25kV 450 MVA 8% Y 6 Y 235/230 150MVA 12% 5 Figure E4.9 A Simplified Power System Solution: (a) The selected bases appear in Table E4.9. The derived bases can be computed with the equations that have been presented in section (???). Table E4.9 Assigned Bases for Simplified Power System of Figure E4.9 Bus Vb(kV) Sb(MVA) fb(Hz) 1 2 3 4 5 6 8.66 132.8 132.8 14.434 132.8 132.8 33.333 33.333 33.333 33.333 33.333 33.333 60 60 60 60 60 60 (b) to be added. (intentionally omitted) 4.7 Transformer Power Flow Equations In this section we derive the power flow equations for various transformer models discussed in this chapter. We focus on power flow under steady state balance conditions and therefore we need to be concerned only with the positive sequence model. In practice, transformer models of varying accuracy are used based on the desired precision. Models of varying precision are shown in Figure 4.17. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 47 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos y ysh (a) y te jα : 1 ysh (b) 2y 2y te jα : 1 ysh (c) 2y 1+ t −1 2y te jα : 1 ysh (d) Figure 4.17 Positive Sequence Transformer Model (a) Non-regulating, (nominal transformation ratio) (b) Simplified Model of Regulating Transformer Page 48 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos (c) Intermediate Model of Regulating Transformer (d) Realistic Model of Regulating Transformer The nominal parameters of the transformer (in per unit) are: y s = g + jb , and y sh = jbs . Note that model (a) is the per unit model of a transformer with fixed tap (nominal tap). Model (b) is a simplified model of an off-nominal tap transformer. The simplification consists of assuming that the leakage impedance of the transformer is independent of the tap setting and that it is all on the left side of the transformer. Model (c) is a simplified model of an off-nominal tap transformer. The simplification consists of assuming that the leakage impedance of the transformer is independent of the tap setting. Model (d) is the most accurate transformer model. The leakage impedance on the non-tapped side is constant while the leakage impedance on the tapped side is proportional to the quantity (1+abs(t-1)) where t is the tap setting. This model results from considering the construction characteristics of the variable tap transformers. For accurate power flow computations, model (d) should be used. The power flow equations for the four models are: Power flow equations for model 1. THESE EQUATIONS ARE WRONG- Update P1 = gV12 − V1V2 [ g cos(δ 1 − δ 2 ) + b sin(δ 1 − δ 2 )] Q1 = −(b + bs )V12 + V1V2 [b cos(δ 1 − δ 2 ) − g sin(δ 1 − δ 2 )] P2 = gV22 − V1V2 [ g cos(δ 2 − δ 1 ) + b sin(δ 2 − δ 1 )] Q2 = −bVk22 + V1V2 [b cos(δ 2 − δ 1 ) − g sin(δ 2 − δ 1 )] Power flow equations for Model 2. P1 = t 2 gV12 − V1V2 t[ g cos(δ 1 − δ 2 + α ) + b sin(δ 1 − δ 2 + α )] Q1 = −(t 2b + bS )V12 + V1V2t[b cos(δ 1 − δ 2 + α ) − g sin(δ 1 − δ 2 + α )] P2 = gV22 − V1V2 t[ g cos(δ 2 − δ 1 − α ) + b sin(δ 2 − δ 1 − α )] Q2 = −bV22 + V1V2 t[b cos(δ 2 − δ 1 − α ) − g sin(δ 2 − δ 1 − α )] Power flow equations for Model 3. P1 = (2 gtA + (2bt + bs ) B)V12 − 2tV1V2α12 A + 2tV1V2 β12 B Q1 = (2 gtB − (2bt + bs ) A)V12 − 2tV1V2α12 B − 2tV1V2 β12 A P2 = (2 gA + (2b + bs ) B)V22 − 2tV1V2α 21 A + 2tV1V2 β 21B Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 49 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Q2 = (2 gB − (2b + bs ) A)V22 − 2tV1V2α 21B − 2tV1V2 β 21 A where: α12 = g cos(δ 1 − δ 2 + α ) + b sin(δ 1 − δ 2 + α ) β12 = g sin(δ 1 − δ 2 + α ) − b cos(δ 1 − δ 2 + α ) α 21 = g cos(δ 2 − δ 1 − α ) + b sin(δ 2 − δ 1 − α ) β 21 = g sin(δ 2 − δ 1 − α ) − b cos(δ 2 − δ 1 − α ) A= 4( g 2 + b 2 )(1 + t 2 ) + 2bbs 4( g 2 + b 2 )(1 + t 2 ) 2 + bs2 + 4bbs (1 + t 2 ) B= 2 gbs 4( g + b )(1 + t ) + bs2 + 4bbs (1 + t 2 ) 2 2 2 2 Power flow equations for Model 4. P1 = (2 gtA + (2bt + sbs ) B)V12 − 2tV1V2α12 A + 2tV1V2 β12 B Q1 = (2 gtB − (2bt + sbs ) A)V12 − 2tV1V2α12 B − 2tV1V2 β12 A P2 = (2 gA + (2b + bs ) B)V22 − 2tV1V2α 21 A + 2tV1V2 β 21B Q2 = (2 gB − (2b + bs ) A)V22 − 2tV1V2α 21B − 2tV1V2 β 21 A where: α12 = g cos(δ 1 − δ 2 + α ) + b sin(δ 1 − δ 2 + α ) β12 = g sin(δ 1 − δ 2 + α ) − b cos(δ 1 − δ 2 + α ) α 21 = g cos(δ 2 − δ 1 − α ) + b sin(δ 2 − δ 1 − α ) β 21 = g sin(δ 2 − δ 1 − α ) − b cos(δ 2 − δ 1 − α ) A= Page 50 4( g 2 + b 2 )( s + t 2 ) + 2 sbbs 4( g 2 + b 2 )( s + t 2 ) 2 + s 2bs2 + 4 sbbs ( s + t 2 ) Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos B= 2sgbs 4( g + b )( s + t ) + s 2bs2 + 4sbbs ( s + t 2 ) 2 2 2 2 ⎧ t , if t ≥ 1.0 s=⎨ ⎩2 − t , if t ≤ 1.0 4.8 Transformer Parameter Identification From Tests Actual modeling of transformers requires that their parameters be accurately determined. For this purpose, tests can be performed to measure the parameters of the transformer. Two simple tests are quite usual for this purpose: (a) the open circuit test and (b) the short circuit test. 4.8.1 The Open Circuit Test The open circuit test is shown in Figure 4.18. Specifically Figure 4.18a shows connections and measurements for an open circuit test of a single phase transformer. Note that the secondary of the transformer is open, while the primary is connected to a source. The voltage at the terminals of the transformer is typically near the nominal value. The voltage at the primary side is measured (V), the electric current of the primary is also measured (A) as well as the real power flow into the transformer (W). Transformer Under Test W A Open V (a) Transformer Under Test r1 W jxl1 A V g r2 jxl2 -jb Open (b) Figure 4.18 Open Circuit Test (a) Setup for the Open Circuit test (b) Equivalent Circuit of the Open Circuit Test Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 51 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Consider the measurements of voltage, current and power, Voc, Ioc and Poc respectively. By replacing the transformer under test with its equivalent circuit, as it is shown in Figure 4.18b, the following relationship can be derived: P g ≅ oc2 V oc ⎛I b = ⎜⎜ oc ⎝ Voc I g − jb ≅ oc Voc 2 ⎞ Poc2 ⎟⎟ − 4 ⎠ Voc Therefore this test provides the magnetizing reactance and the core loss of the transformer. 4.8.2 The Short Circuit Test The short circuit test is shown in Figure 4.19. Specifically, Figure 4.19a shows connections and measurements for a short circuit test of a single phase transformer. Note that the secondary of the transformer is shorted, while the primary is connected to a source. The applied voltage at the terminals of the transformer is adjusted so that the current flowing into the transformer is typically near the nominal value. The voltage at the primary side is measured (V), the electric current of the primary is also measured (A) as well as the real power flow into the transformer (W). Transformer Under Test Rated amps W A V (a) Transformer Under Test jxl1 r1 W A V g r2 jxl2 -jb (b) Figure 4.19 Short Circuit Test (a) Setup for the Short Circuit test (b) Equivalent Circuit of the Short Circuit test Page 52 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Consider the measurements of voltage, current and power, Vsc, Isc and Psc respectively. By replacing the transformer under test with its equivalent circuit as it is shown in Figure 4.19b, the following relationships can be derived: r1 + a 2 r2 ≅ Psc I sc2 ( ) r1 + a 2 r2 + x l1 + a 2 x l 2 ≅ xl1 + a x l 2 2 ⎛V = ⎜⎜ sc ⎝ I sc Vsc I sc 2 ⎞ P2 ⎟ − sc4 ⎟ I sc ⎠ Therefore this test provides the leakage impedance and equivalent resistance of the transformer. Note that this test does not provide the impedances of the individual coils (high and low side) but rather the overall equivalent. 4.9 Normalized Power System Model Delta-wye connected three phase transformers are extensively used in three phase power systems for a variety reasons. These transformers generate a 30o phase shift of the voltage phase angles. Systems are designed in such a way that these phase shifts are consistent in the sense that for any loop in the network the net phase shift will be zero. In this case, we call the system normal. In terms of modeling the system, the 30o phase shift of the delta-wye connected transformers can be ignored if the system is normal. However, if it is necessary to compute the actual system voltages, these phase shifts must be modeled. Consider for example the system of Figure 4.20. The Figure illustrates a typical system. Note that for this system, there is no network loop in which the net phase shift by deltawye (or wye-delta) connected transformers is different than zero. There are two deltawye connected transformers that are connected radially. Thus the system is normal. In modeling this system, the 30o phase shift of the delta-wye connected transformers are omitted for simplicity. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 53 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 18kV:230kV 230kV 230kV:115kV ∆Y YY ∆Y Auto 25kV:230kV 115kV:13.8kV ∆Y 230kV:115kV ∆Y 115kV:13.8kV Figure 4.20 Example Normal Power System Page 54 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 4.10 Summary and Discussion In this chapter, the modeling of power transformers has been addressed. The power transformer under normal operating conditions behaves as an approximately linear device. Three phase transformers are symmetric and therefore can be represented with their positive, negative and zero sequence networks. We developed these models for three phase transformers. These models are useful for power flow analysis, short circuit analysis and similar analysis problems. Regulating transformers were also addressed and their models were discussed. In this chapter we also introduced the per unit system. The per unit system is useful for simplifying transformer models, expressing power system quantities in a meaningful way and conditioning the power system model for better numerical stability. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 55 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 4.11 Problems Problem P4.1: A single phase transformer has the following ratings: 10-kVA, 60 Hz, 2300V/230V. The impedances of the transformer are: r1 = 4.2 ohms , r2 = 0.042 ohms xl1 = 5.5 ohms, x l 2 = 0.055 ohms, Lm1 = 17.0 Henries (on 2300V side) Subscript 1 denotes the 2300 V winding, subscript 2 the 230 V winding. The transformer delivers 90% of its rated volt-amperes (apparent power) at a 0.85 power factor (current lagging) to a load on the low voltage side with 230 V across the load. The core losses are 70 Watts. • • • • Compute the total leakage impedance referred to (1) the high voltage side, and (2) the low voltage side. Compute the high side terminal voltage, Compute the power factor at the high side terminals, Compute the transformer efficiency. Solution: 1st step: Compute ZL (230 V) IL = (.90)(10,000) VA ~ VL = 230e j.0 ⇒ IL = 39.13 A cos(ϕV - ϕI) = .85 ϕ V − ϕ I =.5548 ⇒ ~ IL = 39.13e − j.5548 ~ VL Z L = ~ = 5.8778 Ω e j.5548 = R L + jXL = 4.996 Ω + j3.0963 Ω IL ~ V1 = [ ( 499 + (2)( 4.2)) + j((2)(5.5) + 309.63)] 3.913e − j.5548 = (507.4 + j 320.63)(3.913) e − j.5548 = 2348.6423 V e − j.00875 ⇒ b) V1 = 2,348.6423 V Power factor pf = cos(φ V1 , I ' L ) = cos(.00875 + .5548) ⇒ Page 56 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos pf = .84536 c) Efficiency = 1 - Losses Pout Pout = (230)(39.13)(.85) = 7649.9 Watts Losses = 70 W + (2)(4.2)(3.913)2 = 198.62 Watts Efficiency = .974 Problem P4.2: Consider the three winding transformer of Figure P4.2. An electric current i1(t)= 210A cos ωt , ω = 377 sec-1 is injected into winding 1. Winding 2 is loaded with a series L, C circuit while winding 3 is open, i.e., i3(t) = 0. The values of L and C are: L=0.5H, C=10µF. The number of turns are: N1=20, N2=40, N3=100. Assume ideal magnetic material ( µ = ∞ ) and ideal windings (zero resistance). Compute the voltage v1(t) and v3(t) across the windings 1 and 3. i2 i1 L N + 2 V1 N 1 C + N3 i 3 V3 Figure P4.2 Solution: N 1i1 ( t ) + N 2 i 2 ( t ) + N 3 ⋅ 0 = 0 N1 i1 (t ) = − 2 5 A cos ωt N2 1 ~ ~ ~ V 2 = − jωLI 2 − I 2 = − j 383.76 V jωC ⇒ i 2 (t ) = − Recall Copyright © A. P. Sakis Meliopoulos – 1990-2006 ~ ~ V2 = jωN 2 Φ ~ Φ = −0.02545T Φ(t ) = 2 0.02545T cos(ωt − 180o ) Page 57 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos V1 (t ) = N 1 dΦ = 2191.89V cos(ωt − 90 o ) dt V3 (t ) = N 3 dΦ = 2 959.46V cos(ωt − 90 o ) dt Problem P4.3: A single phase distribution transformer has the following parameters: rated voltages 14.4 kV/220 V, rated power 37.5 kVA, rated frequency 60 Hz, leakage impedance 3.7%, total winding resistance 0.5% . (a) (b) (c) Compute and draw the equivalent circuit of the transformer including an ideal transformer. Refer all impedances to the high voltage side. Compute and draw the pi equivalent circuit of the transformer in actual units. Compute and draw the per unit equivalent circuit of the transformer assuming the following bases on the high voltage side of the transformer: Vb = 14.4 kV, Sb = 37.5 kVA. Select the low side bases as you like. Problem P4.4: Given a 125 MVA, 230kV/115kV three phase, wye/wye connected transformer with 10% leakage impedance and negligible resistance. The transformer has several taps on the 115 kV side. Assume that the tap of the transformer is set for 110 kV. Compute the per unit positive sequence equivalent circuit of the transformer. Use as bases the following (nominal voltages): High voltage side: Vb = 230 / 3 kV, Sb = 125/3 MVA, low voltage side: Vb = 115 / 3 kV, Sb = 125/3 MVA. Solution: The per phase equivalent circuit in pernuit is shown in Figure 1. Elimination of the ideal transformer yields the circuit of Figure 2. Problem P4.5: A 230 kV transmission line and a 115 kV line parallel each other for a distance of 12 miles. The zero sequence equivalent model of the system is illustrated in Figure P4.5. The assigned bases for the 230 kV line are: f b, 230 = 60 Hz, S b, 230 = 100 MVA / 3, Vb, 230 = 230 kV / 3 Page 58 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos The assigned bases for the 115 kV line are: f b,115 = 60 Hz, S b,115 = 100 MVA / 3, Vb,115 = 115 kV / 3 Compute the per unit zero sequence equivalent model of this system. What is the base impedance for the mutual impedance? 1 ohms j210 ohms 230 kV Line j10 ohms 115 kV Line j28 ohms 1.5 ohms Figure P4.5 Problem P4.6: Consider the electric power system of Figure P4.6. The transformer reactances are given in per unit on each transformer ratings. The generator controls the voltage at bus 1 to nominal value. Assume that the indicated electric load is a constant impedance load and it absorbs the indicated amount of power when the voltage is nominal. Compute and draw the positive sequence equivalent circuit of the system in per unit using a 100/3 MVA power basis (one phase) and nominal voltages. G1 1 3 2 Y Z=6+j62Ω 45MVA 15kV/115kV X=8% 4 Y 30MVA 115kV/25kV X=7.5% Sd 4 =20MW+ j10MVAR Figure P4.6 Solution: The base impedance at the three different kV levels of this system are: 2 ( 15) = = 2.25 ohms 100 (115)2 = 132.25 ohms Z b,115kV = 100 (25)2 = 6.25 ohms Z b, 25kV = 100 The transformer impedances referred to 100 MVA basis are: Z b,15kV z T 1 = j 0.08 100 = j 0.1778 45 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 59 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos z T 1 = j0.075 100 = j 0.25 30 The positive sequence equivalent circuit is: j0.178 0.0454 j0.469 j0.25 4 1.0pu j2 1:e j300 1:e -j300 Problem P4.7. Consider the phase-shifter transformer of Figure P4.7. Note that the phase shifter transformer is made of six identical single-phase transformers. Assume that each transformer is ideal and the primary to secondary transformation ratio is 0.5. What is the positive sequence equivalent of this phase-shifter transformer? What is the negative sequence equivalent of this phase-shifter transformer? What is the zero sequence equivalent of this phase-shifter transformer? Hint: Apply the appropriate voltage (positive, negative, or zero sequence) at one side of the phase-shifter transformer and compute the voltages at the other side. S A a P P P S S P B C S P S S b c P Phase Shifter Figure P4.7 Problem P4.8: An electric power system consists of a transmission line and a transformer as it is illustrated in Figure P4.8. Compute the admittance matrix of the system comprising the line and the transformer, i.e. neglect the presence of the generator and electric load. All relevant values are given in the Figure. Page 60 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos G1 3 2 1 Z=j0.1 pu 1:t Z=j0.12 pu t =1.05 Figure P4.8 Problem P4.9. Figure P4.9 illustrates a simplified power system consisting of two synchronous machines, a phase shifting transformer and a line. Assume that the synchronous machines are ideal voltage sources and that the phase shifter consists of a number of ideal transformers. Specifically, all illustrated transformers are ideal with a transformation ratio of secondary to primary voltage equal to 0.5 (Secondary Voltage/Primary voltage = 0.5) and they are connected as illustrated in the figure. Note that the primary is designated as P and the secondary as S. (a) Compute the phase to ground voltage (both magnitude and phase) at the two sides of the phase shifter. (b) Compute the total electric power absorbed or generated by the synchronuous machine 2. The following additional information is given. 0 0 0 ~ ~ ~ ~ ~ E1a = 8.66e j 0 kV , E1b = E1a e − j120 , E1c = E1a e − j 240 0 0 0 ~ ~ ~ ~ ~ E 2 a = 9.0e j 0 kV , E 2b = E 2 a e − j120 , E 2 c = E 2 a e − j 240 S ~ E 1a ~ E 1c y = 0.2 - j1.0 mhos ~ E 2a P ~ E 1b P P S S P y = 0.2 - j1.0 mhos ~ E 2b ~ E 2c S P Synchronuous Machine 1 S S y = 0.2 - j1.0 mhos P Phase Shifter Transmission Line Synchronuous Machine 2 Figure P4.9 Solution: The voltage at phase A at left hand side of the line is: Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 61 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos ( ) 0 ~ ~ ~ ~ E = E1a − 0.25 E1b − E1c = 9.437e j 23.41 kV The transformation ratio is: ~ 0 E n = ~ = 1.0897 e j 23.41 E1a The electric current of the line (going into the synchronous machine 2) is: ( ) 0 ~ ~ ~ I = (0.2 − j1.0) E − E 2 a = 3.839e j16.49 kA The power is: ~ ~ S 2 = (3)E 2 a I * = 99.41 MW − j 29.42 MVAr Synchronous machine absorbs real power therefore operates as motor. Problem P4.10. Consider the normalized model of the off nominal tap transformer of Figure P4.10. This tap setting of the ransformer corresponds to a normalized transformation ratio of t=1.09 pu as it is indicated in the figure. All indicated admittance values are in pu. Under the present operating conditions, the voltages at the terminals of the transformer are (magnitude in pu, phase in radians): ~ ~ V1 = 1.0e − j 0.15 , V2 = 0.98e − j 0.25 Compute the complex power flow at the left side of the transformer. -j10.9 -j10 + + ~ ~ V2 V1 1.09 : 1 Figure P4.10 Problem P4.10: The per phase positive sequence equivalent circuit of a three phase transformer is illustrated in Figure P4.10. At a certain instant of time the voltages at the Page 62 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos terminals of the transformer are as illustrated in the figure. Compute the total (threepahse) power P1 + j Q1 at the left hand side of the transformer. Ω -j9.18 Ω -j0.1 P1+jQ1 o o 63e j0 kV 7.2 e j18 kV o 11512 : e j30 kV Figure P4.10 Solution: ~ Assume voltage at high side of ideal transformer to be E . Then ( ) 0 12 j 300 ~ ⎞ ~ ⎛ I 2 = − j 9.18⎜ 7.2 j18 − e E⎟ 115 ⎝ ⎠ ~ ~ I 1 = − j0.1 63 − E , 115 j 300 ~ ~ I2 = − e I1 12 ~ Upon substitution of the currents we obtain one equation in E . Solution of this equation yields: 0 ~ E = 65.2458 − j 7.1714 = 65.6387e − j 6.27 kV Then: ( ) 0 ~ ~ I 1 = − j 0.1 63 − E = 0.71714 + j 0.22458 kA = 0.7515e j17.39 kA , and 0 115 j 300 ~ ~ I2 = − e I 1 = 7.2019e − j132.61 kA 12 The power at the two ends is: ( S 1 = P1 + jQ1 = 3(63.0) 0.7515e j17.39 ( )( 0 ) * = 142.0335e − j17.39 MVA = 135.415MW − j 42.4503MVAr 0 S 2 = P2 + jQ 2 = 3 7.2e j18 7.2019e − j132.61 0 0 ) * = 155.5611e j150.61 MVA = −135.415MW + j 76.3419MVAr 0 Note: the difference in real powers uis due to numerical precision errors. Problem P4.11: Consider the two models of an off-nominal tap transformer of Figure P4.11, the model of Figure P4.11a is the approximate model while the model of Figure P4.11b is an intermediate accuracy model. Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 63 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos (a) Assume that the applied voltages at the two terminals of the transformer are: 0 0 ~ ~ V1 = 1.025e j 0 , V 2 = 1.005e − j 5 . Compute the complex power flow from side 1 to side 2 for the two transformer models. Assume that the model shown in Figure P4.11b is the accurate model and compute the percent error of the real and reactive power flow for the model of Figure P4.11a. (b) Compute the pi-equivalent circuits of the two transformer models in Figures P4.11a and P4.11b. j0.10 + ~ V1 + ~ V2 1:1.05 (a) j0.05 + ~ V1 j0.05 + ~ V2 1:1.05 (b) Figure P4.11 Solution: (a) The complex power for model a is: ( ( ~ ~ ~ S 12 a = 1.05V1 − j10.0 1.05V1 − V 2 )) * = 1.12246e j 40.38 = 0.85505 + j 0.72719 0 The complex power for model b is: ~~ S 12b = V1 I 1* Where the current will come from ( ) ~ ~ ~ I 1 = − j 20.0 V1 − E , and ~ I1 ~ ~ = − j 20.0 1.05E − V 2 1.05 ( ) Upon solution for the current on side 1: ( ~ ~ ~ I 1 = − j9.988109 1.05V1 − V2 Page 64 ) Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Therefore: ( ( ~~ ~ ~ ~ S 12b = V1 I 1* = V1 − j 9.988109 1.05V1 − V 2 )) * = 1.1484745e j 40.38 = 0.87486 + j 0.74404 0 The error is: error = S 12 a − S 12 b = −2.3% S 12b (b) The pi-equivalent of model a is: -j10.5 -j0.525 j0.5 The pi-equivalent of model b is: -j9.9881 -j0.499405 j0.475624 Problem P4.12: Consider the three phase electric power system of Figure P4.12 consisting of two ideal synchronous machines G1 and G2, an ideal delta-wye connected transformer and a transmission line. The indicated generated voltages are: o ~ E1 = 7.2 kV e -j15 , o ~ E 2 = 14.9 kV e j0 Compute the total real and reactive power delivered or absorbed by the synchronous machine G1. Repeat for the synchronous machine G2. Which machine operates as a generator and which as a motor? Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 65 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Unit G1 ~ E1 S1 = P1 + jQ 1 2+j10Ω + _ 2+j10Ω Unit G2 + _ ~ E 2 2+j10Ω 1:1 Figure P4.12 Solution: o ~ V1 = 7.2 3 kV e j15 o o ~ I 1 = 7.2 3 e j15 − 14.9 3 e j0 (2 + j10) ~ I 1 = (− 2.8542 + j3.2277) (2 + j10) = 0.32277 + j0.28542 ( ) = 0.4309 kA e − j41.5 o Transformer is ideal. Thus ~ S1 = 3V1 I1* = (3)(7.2)( 3 )(0.4309) e − j26.5 MVA o = 16.121 e − j26.5 MVA = 14.427 MW -j7.193 MVAR o Unit 1 is operating as a generator. Problem P4.13: The following data apply to a single phase 1000 kVA 66kV/6.6kV, 60 Hz transformer: Frequency Voltage Current Power with low-voltage terminals short-circuited 60 Hz 3240 V (high voltage side) 15.2 A (high voltage side) 7,490 W With high-voltage terminals open 60 Hz 6600 V (low voltage side) 9.1 A (low voltage side) 9,300 W Assume that the primary and secondary resistances are equal when referred to the same side and that the primary and secondary leakage reactances are similarly equal. Page 66 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos a) b) Determine the equivalent circuit of the above transformer with all parameter values referred to the high side, Determine the equivalent circuit of the above transformer with all parameter values expressed in a per unit system. Use the ratings of the transformer as bases. Solution: 1) Short Circuit Test (r1 + r2 ) + ( jX1 + X2 ) = 3240 = 213.15 Ω 15.2 (r1 + r2)(15.2)2 = 7490 ⇒ r1 + r2 = 32.418 Ω X1 + X2 = 213.15 2 − 32.418 2 = 210.67 Ω referred to H.S. r1 = r2 = 16.21 Ω X1 = X2 = 105.34 Ω Open Circuit Test rf = 6600 2 = 4683.87 Ω 9300 1 6600 = g − jb 9.1 ⇒ ⇒ g = .0002134 S 2 ⎛ 9.1 ⎞ 2 b= ⎜ ⎟ − g =.001362 S ⎝ 6600 ⎠ Therefore 2) ZB = VB VB2 (66000) 2 = = = 4356 Ω IB S B 1000000 r2' pu = r1pu = X'2 pu = X1pu YB = 16.21 =.00372 4356 105.34 = =.02418 4356 1 ZB Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 67 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos g pu = .000002134 =.00929 YB b pu =.05932 Problem P4.14. Consider the simplified three-phase power system illustrated in Figure P4.14. The parameters of each component are given below. At a certain instant of time, the overall system operates under balanced conditions and the induction motor operates with a slip of 0.04. Compute: a) the electric current on Phase A of the induction motor terminal. b) the total real power absorbed by the induction motor. Wye-Wye Connected Transformer 1 SOURCE G 2 HIGHSIDE LOWSIDE Three-Phase Cable Three-Phase Source IM SPEED Induction Motor Figure P4.14 SOURCE: Voltage: 4.16 kV, Line to Line Assume ideal voltage source CABLE: Per phase (positive sequence) impedance: 0.69+j0.69 ohms TRANSFORMER Rated Transformation Ratio: 4.16kV/480 Volts Power Rating: 500 kVA Equivalent Impedance: j1.38 ohms referred to the high side Core Loss, Magnetizing current, winding losses: neglect INDUCTION MOTOR Power Rating: 500 kVA Voltage rating: 480 Volts, Line to Line Per Phase Stator resistance: 0.0046 ohms Per Phase Rotor resistance: 0.0092 ohms referred to stator Per Phase Stator leakage reactance: 0.0138 ohms Per Phase Rotor leakage reactance: 0.0184 ohms referred to stator Page 68 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Core loss, magnetizing reactance: neglect Problem P4.15. Consider the model of the “phase-shifter” transformer of Figure P4.15. All indicated transformers are identical. Note that the taps can move to different positions – all transformers at the same tap position by virtue of the mechanical link that is indicated by the dashed line. Note also that the centers of the secondary windings are bonded (solid line). Assume that at the indicated position (of the tap) the transformation ratio of the transformers is 0.06, i.e. V s , AB V s , AC = = ... = 0.06 V AB V AC Assume that all transformers are ideal and compute: a) the positive sequence transformation ratio b) the negative sequence transformation ratio, and c) the zero sequence transformation ratio. ~ ~ VS,AB VS,AC A a 1~ V 2 AB 1 ~ V 2 AC B b 1~ V 2 BC 1~ V 2 BA c C 1~ V 2 CA 1~ 2 VCB Figure P4.15 Solution: Given the current setting of the tap: ~ ~ ~ ~ ~ ~ ~ V a = V s , AC − V s , AB + V A = V A + 0.03V B − 0.03VC Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 69 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos Positive sequence: sequence. Then: Assume voltages on left hand side are balanced and positive ~ Va − j 2.9745 0 ~ = 1.00134 e VA ~ VA O ~ 0.03VB ~ -0.03VC ~ Va Negative sequence: sequence. Then: Assume voltages on left hand side are balanced and negative ~ Va j 2.9745 0 ~ = 1.00134 e VA Zero sequence: Assume voltages on left hand side are balanced and zero sequence. Then: ~ Va ~ = 1. 0 VA Problem P4.16: Consider the model of the off nominal tap transformer of Figure P4.16. The indicated transformation ratio t is in p.u. and y is the transformer leakage admittance in p.u. Note that the leakage admittance of the tapped coil is inveresely proportional to the tap setting t. Compute the equivalent circuit of this transformer. The equivalent circuit should contain only admittance elements, i.e. the ideal transformer should be eliminated. y/t y t:1 Figure P4.16 Solution: Page 70 Copyright © A. P. Sakis Meliopoulos – 1990-2006 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos The equations relating the terminal voltages and currents are (see designations on Figure): Figure ~ y ~ y ~ I 1 = V1 − Et t t Problem P4.17. Consider the normalized model of the off nominal tap transformer of Figure P2. This tap setting of the ransformer corresponds to a normalized transformation ratio of t=1.09 pu as it is indicated in the figure. All indicated admittance values are in pu. Under the present operating conditions, the voltages at the terminals of the transformer are (magnitude in pu, phase in radians): ~ ~ V1 = 1.0e − j 0.67 , V2 = 0.98e − j 0.25 , phase angles are in radians Compute the complex power flow at the left side of the transformer. -j10.9 ~ V1 j0.05 -j10 Ideal Transformer te − j 300 ~ V2 :1 Figure P2 Solution: Let E be the voltage on the right of the ideal transformer. Then: ( 0 ~ ~ ~ I 1 = − j10.9 V1 − 1.09e − j 30 E ( ~ ~ ~ I 2 = − j10.0 V2 − E ) ) ( ) ~ ~ j10.0 V 2 − E ~ − j 30 0 ~ − j 30 0 ~ j10.9 V1 − 1.09e E + j (0.05)(1.09 )e E+ =0 0 1.09e j 30 ( ) Solution of last equation for E: Copyright © A. P. Sakis Meliopoulos – 1990-2006 Page 71 Power System Modeling, Analysis and Control: Chapter 4, Meliopoulos 0 ~ 0 ~ ~ E = 0.5444606e j 30 V1 + 0.458261e j 30 V 2 Substitution in the equations for the terminal currents yields: ( ) ( ) ~ ~ ~ I 1 = − j 4.431263V1 − 5.4445989V2 ~ ~ ~ I 2 = − j − 5.444606V1 + 5.41739V 2 The power at the left side of the transformer is: ~~ S 12 = V1 I 1* = −2.17569 − j0.440712 pu Page 72 Copyright © A. P. Sakis Meliopoulos – 1990-2006