Chapter 12: Three-Phase Circuits

advertisement
Chapter 12: Three-Phase Circuits
Exercises
Ex. 12.3-1
VC = 120∠ − 240° so VA = 120∠0° and VB = 120∠ − 120°
Vbc = 3 (120 ) ∠ − 90°
Ex. 12.4-1
Four-wire Y-to-Y Circuit
Mathcad analysis (12v4_1.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 120
⋅0
j⋅
Vb := Va⋅ e
Describe the three-phase load:
Calculate the line currents:
IaA = 1.079 − 0.674i
IaA = 1.272
180
π
⋅ arg( IaA ) = −32.005
IaA :=
π
180
⋅ − 120
Vc := Va⋅ e
ZA := 80 + j⋅ 50
Va
IbB :=
ZA
j⋅
Vb
ZB
IbB = 1.061
π
180
⋅ 120
ZB := 80 + j⋅ 80
IbB = −1.025 − 0.275i
180
π
⋅ arg( IbB) = −165
IcC :=
ZC := 100 − j⋅ 25
Vc
ZC
IcC = −0.809 + 0.837i
IcC = 1.164
180
π
⋅ arg( IcC) = 134.036
12-1
Calculate the current in the neutral wire:
INn := IaA + IbB + IcC
INn = −0.755 − 0.112i
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
SA = 129.438 + 80.899i

SC := IcC⋅ IcC⋅ ZC
SB = 90 + 90i
SC = 135.529 − 33.882i
Total power delivered to the load: SA + SB + SC = 354.968 + 137.017i
Calculate the power supplied by the source:

Sa := IaA ⋅ Va

Sb := IbB⋅ Vb

Sc := IcC⋅ Vc
Sa = 129.438 + 80.899i
Sb = 90 + 90i
Sc = 135.529 − 33.882i
Total power delivered by the source:
Sa + Sb + Sc = 354.968 + 137.017i
Ex. 12.4-2
Four-wire Y-to-Y Circuit
Mathcad analysis (12x4_2.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 120
⋅0
j⋅
Vb := Va⋅ e
Describe the three-phase load:
Calculate the line currents:
IaA = 1.92 − 1.44i
IaA = 2.4
180
π
⋅ arg( IaA ) = −36.87
IaA :=
π
180
⋅ − 120
Vc := Va⋅ e
ZA := 40 + j⋅ 30
Va
IbB :=
ZA
j⋅
Vb
ZB
IbB = 2.4
π
⋅ 120
ZB := ZA
IbB = −2.207 − 0.943i
180
π
180
⋅ arg( IbB) = −156.87
IcC :=
ZC := ZA
Vc
ZC
IcC = 0.287 + 2.383i
IcC = 2.4
180
π
⋅ arg( IcC) = 83.13
12-2
Calculate the current in the neutral wire:
INn := IaA + IbB + IcC
INn = 0
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
SA = 230.4 + 172.8i

SC := IcC⋅ IcC⋅ ZC
SB = 230.4 + 172.8i
SC = 230.4 + 172.8i
Total power delivered to the load: SA + SB + SC = 691.2 + 518.4i
Calculate the power supplied by the source:

Sa := IaA ⋅ Va

Sb := IbB⋅ Vb

Sc := IcC⋅ Vc
Sa = 230.4 + 172.8i
Sb = 230.4 + 172.8i
Sc = 230.4 + 172.8i
Total power delivered by the source:
Sa + Sb + Sc = 691.2 + 518.4i
Ex. 12.4-3
Three-wire unbalanced Y-to-Y Circuit with line impedances
Mathcad analysis (12x4_3.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 120
⋅0
j⋅
Vb := Va⋅ e
Describe the three-phase load:
π
180
⋅ − 120
ZA := 80 + j⋅ 50
j⋅
Vc := Va⋅ e
π
180
⋅ 120
ZB := 80 + j⋅ 80
ZC := 100 − j⋅ 25
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
ZA ⋅ ZC⋅ e
4
j⋅ ⋅ π
3
+ ZA ⋅ ZB⋅ e
2
j⋅ ⋅ π
3
+ ZB⋅ ZC
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
VnN = −25.137 − 14.236i
VnN = 28.888
⋅ Vp
180
π
⋅ arg( VnN) = −150.475
12-3
Calculate the line currents:
IaA :=
Va − VnN
ZA
IaA = 1.385 − 0.687i
π
Check:
Vb − VnN
IcC :=
ZB
IbB = −0.778 − 0.343i
IaA = 1.546
180
IbB :=
180
π
ZC
IcC = −0.606 + 1.03i
IbB = 0.851
⋅ arg( IaA ) = −26.403
Vc − VnN
IcC = 1.195
180
⋅ arg( IbB) = −156.242
π
⋅ arg( IcC) = 120.475
IaA + IbB + IcC = 0
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
SA = 191.168 + 119.48i

SC := IcC⋅ IcC⋅ ZC
SB = 57.87 + 57.87i
Total power delivered to the load:
SC = 142.843 − 35.711i
SA + SB + SC = 391.88 + 141.639i
Ex. 12.4-4
Three-wire balanced Y-to-Y Circuit with line impedances
Mathcad analysis (12x4_4.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 120
⋅0
Describe the three-phase load:
j⋅
Vb := Va⋅ e
π
180
⋅ − 120
ZA := 40 + j⋅ 30
j⋅
Vc := Va⋅ e
ZB := ZA
π
180
⋅ 120
ZC := ZA
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
ZA ⋅ ZC⋅ e
4
j⋅ ⋅ π
3
+ ZA ⋅ ZB⋅ e
2
j⋅ ⋅ π
3
+ ZB⋅ ZC
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
⋅ Vp
12-4
− 14
VnN = −1.31 × 10
− 14
Calculate the line currents:
IaA :=
VnN = 2.301 × 10
Va − VnN
ZA
IaA = 1.92 − 1.44i
π
⋅ arg( VnN) = 124.695
Vb − VnN
IcC :=
ZB
180
π
− 15
IaA + IbB + IcC = 1.055 × 10
180
⋅ arg( IbB) = −156.87
π
− 15
⋅ arg( IcC) = 83.13
− 2.22i × 10
SB = 230.4 + 172.8i
Total power delivered to the load:
ZC
IcC = 2.4
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
SA = 230.4 + 172.8i
Vc − VnN
IcC = 0.287 + 2.383i
IbB = 2.4
⋅ arg( IaA ) = −36.87
Check:
IbB :=
π
IbB = −2.207 − 0.943i
IaA = 2.4
180
180
− 14
+ 1.892i× 10

SC := IcC⋅ IcC⋅ ZC
SC = 230.4 + 172.8i
SA + SB + SC = 691.2 + 518.4i
Ex. 12.6-1
Balanced delta
load:
phase currents:
(See Table 12.5-1)
Z ∆ = 180∠ − 45°
I AB =
VAB
360∠0°
=
= 2∠45° A
Z ∆ 180∠− 45D
I BC =
VBC 360∠−120°
=
= 2∠− 75° A
°
Z ∆ 18∠− 45
I CA
line currents:
VCA 360∠120°
=
=
= 2∠165° A
°
Z ∆ 180∠− 45
I A = I AB − I CA = 2∠45° − 2∠165° = 2 3∠15° A
I B = 2 3∠−105° A
I C = 2 3∠135° A
12-5
Ex. 12.7-1
Three-wire Y-to-Delta Circuit with line impedances
Mathcad analysis (12x4_4.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 110
⋅0
j⋅
Vb := Va⋅ e
Describe the delta connected load:
π
180
⋅ − 120
Z1 := 150 + j⋅ 270
j⋅
Vc := Va⋅ e
π
180
Z2 := Z1
⋅ 120
Z3 := Z1
Convert the delta connected load to the equivalent Y connected load:
ZA :=
Z1⋅ Z3
Z1 + Z2 + Z3
ZA = 50 + 90i
Describe the three-phase line:
ZB :=
Z2⋅ Z3
Z1 + Z2 + Z3
ZB = 50 + 90i
ZaA := 10 + j⋅ 25
ZC :=
Z1⋅ Z2
Z1 + Z2 + Z3
ZC = 50 + 90i
ZbB := ZaA
ZcC := ZaA
12-6
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
( ZaA + ZA ) ⋅ ( ZcC + ZC) ⋅ e
− 14
− 14
IaA :=
IaA = 0.392 − 0.752i
IaA = 0.848
Check:
− 14
+ 1.784i× 10
Calculate the line currents:
π
+ ( ZaA + ZA ) ⋅ ( ZbB + ZB) ⋅ e
2
j⋅ ⋅ π
3
+ ( ZbB + ZB) ⋅ ( ZcC + ZC)
( ZaA + ZA ) ⋅ ( ZcC + ZC) + ( ZaA + ZA ) ⋅ ( ZbB + ZB) + ( ZbB + ZB) ⋅ ( ZcC + ZC)
VnN = −1.172 × 10
180
4
j⋅ ⋅ π
3
⋅ arg( IaA ) = −62.447
VnN = 2.135 × 10
Va − VnN
IbB :=
ZA + ZaA
⋅ arg( VnN) = 123.304
IcC :=
ZB + ZbB
IbB = 0.848
π
π
Vb − VnN
IbB = −0.847 + 0.036i
180
180
⋅ arg( IbB) = 177.553
⋅ Vp
Vc − VnN
ZC + ZcC
IcC = 0.455 + 0.716i
IcC = 0.848
180
π
⋅ arg( IcC) = 57.553
IaA + IbB + IcC = 0
Calculate the phase voltages of the Y-connected load:
VAN := IaA ⋅ ZA
VAN = 87.311
180
π
⋅ arg( VAN) = −1.502
VBN := IbB⋅ ZB
VBN = 87.311
180
π
⋅ arg( VBN) = −121.502
VCN := IcC⋅ ZC
VCN = 87.311
180
π
⋅ arg( VCN) = 118.498
Calculate the line-to-line voltages at the load:
VAB := VAN − VBN
VAB = 151.227
180
π
⋅ arg( VAB) = 28.498
VBC:= VBN − VCN
VBC = 151.227
180
π
⋅ arg( VBC) = −91.502
VCA := VCN − VAN
VCA = 151.227
180
π
⋅ arg( VCA) = 148.498
Calculate the phase currents of the ∆ -connected load:
IAB :=
VAB
Z3
IAB = 0.49
180
π
⋅ arg( IAB) = −32.447
IBC :=
VBC
Z1
IBC = 0.49
180
π
⋅ arg( IBC) = −152.447
ICA :=
VCA
Z2
ICA = 0.49
180
π
⋅ arg( ICA) = 87.553
12-7
Ex. 12.8-1
Continuing Ex. 12.8-1:
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
SA = 35.958 + 64.725i

SC := IcC⋅ IcC⋅ ZC
SB = 35.958 + 64.725i
Total power delivered to the load:
SC = 35.958 + 64.725i
SA + SB + SC = 107.875 + 194.175i
Ex. 12.9-1
P1 = VAB I A cos(θ +30° ) + VCB I C cos(θ − 30° )= P + P2
1
pf = .4 lagging ⇒ θ = 61.97
°
So P T = 450(24)  cos 91.97° + cos 31.97°  = 8791 W
∴ P 1 = − 371 W P2 = 9162 W
Ex. 12.9-2
Consider Fig. 12.9-1 with P1 = 60 kW P2 = 40 kW .
(a.) P = P1 + P2 = 100 kW
(b.) use equation 12.9-7 to get
tan θ = 3
P2 − P1
40− 60
= 3
= − .346 ⇒ θ = − 19.11°
PL + P2
100
then
pf = cos ( − 19.110°) = 0.945 leading
12-8
Problems
Section 12-3: Three Phase Voltages
P12.3-1
Given VC = 277 ∠45° and an abc phase sequence:
VA = 277 ∠ ( 45−120 ) ° = 277 ∠ − 75°
VB = 277 ∠( 45° +120 )° = 277 ∠165°
VAB = VA − VB =( 277 ∠− 75° )−( 277 ∠165° )
=( 71.69 − j 267.56 ) −( −267.56+ j 71.69 )
=339.25− j 339.25 = 479.77 ∠− 45° 480 ∠− 45°
Similarly:
VBC = 480 ∠ − 165° and VCA = 480 ∠75°
P12.3-2
VAB
3∠30°
= 12470 ∠145° V
VAB = VA × 3∠30° ⇒ VA =
VAB = −VBA = − (12470 ∠−35° )
In our case:
VA =
So
12470 ∠145°
= 7200∠115°
3∠30°
Then, for an abc phase sequence:
VC = 7200 ∠ (115 + 120 ) ° = 7200 ∠235° = 7200 ∠ − 125°
VB = 7200 ∠ (115 − 120 ) ° = 7200 ∠ − 5° V
P12.3-3
Vab = Va × 3∠30° ⇒ Va =
Vab
3∠30°
In our case, the line-to-line voltage is
So the phase voltage is
Vab = 1500 ∠30° V
1500 ∠30°
Va =
= 866∠0° V
3∠30°
12-9
Section 12-4: The Y-to-Y Circuit
P12.4-1
Balanced, three-wire, Y-Y circuit:
where Z A = Z B = Z C = 12∠30 = 10.4 + j 6
MathCAD analysis (12p4_1.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp :=
208
3
⋅0
j⋅
Vb := Va⋅ e
Describe the balanced three-phase load:
π
180
⋅ − 120
j⋅
Vc := Va⋅ e
ZA := 10.4 + j⋅ 6
π
180
⋅ 120
ZB := ZA
ZC := ZB
Check: The voltage at the neutral of the load with respect to the neutral of the source should be zero:
VnN :=
ZA ⋅ ZC⋅ e
4
j⋅ ⋅ π
3
+ ZA ⋅ ZB⋅ e
IaA :=
Va − VnN
ZA
IaA = 8.663 − 4.998i
Check:
− 14
⋅ Vp
IbB :=
VnN = 2.762 × 10
Vb − VnN
IbB = −8.66 − 5.004i
IaA = 10.002
π
+ ZB⋅ ZC
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
Calculate the line currents:
180
2
j⋅ ⋅ π
3
IbB = 10.002
180
⋅ arg( IaA ) = −29.982
π
− 15
IaA + IbB + IcC = 4.696 × 10
IcC :=
ZB
Vc − VnN
ZC
−3
IcC = −3.205 × 10
+ 10.002i
IcC = 10.002
⋅ arg( IbB) = −149.982
180
π
⋅ arg( IcC) = 90.018
− 14
− 1.066i× 10
12-10
Calculate the power delivered to the load:


SA := IaA ⋅ IaA ⋅ ZA
SB := IbB⋅ IbB⋅ ZB
3
SA = 1.04 × 10 + 600.222i
Total power delivered to the load:

SC := IcC⋅ IcC⋅ ZC
3
SB = 1.04 × 10 + 600.222i
3
3
SC = 1.04 × 10 + 600.222i
3
SA + SB + SC = 3.121 × 10 + 1.801i× 10
Consequently:
(a) The phase voltages are
Va =
208
∠0° = 120∠0° V rms, Vb = 120∠ − 120° V rms and Vc = 120∠120° V rms
3
(b) The currents are equal the line currents
(c)
I a = I aA = 10∠ − 30° A rms, I b = I bB = 10∠ − 150° A rms
and
I c = I cC = 10∠90° A rms
(d) The power delivered to the load is S = 3.121 + j1.801 kVA .
P12.4-2
Balanced, three-wire, Y-Y circuit:
where
Va = 120∠0° Vrms, Vb = 120∠ − 120° Vrms and Vc = 120∠120° Vrms
Z A = Z B = Z C = 10 + j ( 2 × π × 60 ) (100 × 10−3 ) = 10 + j 37.7 Ω
and
Z aA = Z bB = Z cC = 2 Ω
Mathcad Analysis (12p4_2.mcd):
12-11
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 120
⋅0
j⋅
Vb := Va⋅ e
π
180
⋅ − 120
π
j⋅
180
Vc := Va⋅ e
⋅ 120
Describe the three-phase load:
ZA := 10 + j⋅ 37.7
ZB := ZA
ZC := ZB
Describe the three-phase line:
ZaA := 2
ZbB := ZaA
ZcC := ZaA
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
( ZaA + ZA ) ⋅ ( ZcC + ZC) ⋅ e
VnN :=
4
j⋅ ⋅ π
3
+ ( ZaA + ZA ) ⋅ ( ZbB + ZB) ⋅ e
2
j⋅ ⋅ π
3
+ ( ZbB + ZB) ⋅ ( ZcC + ZC)
( ZaA + ZA ) ⋅ ( ZcC + ZC) + ( ZaA + ZA ) ⋅ ( ZbB + ZB) + ( ZbB + ZB) ⋅ ( ZcC + ZC)
− 15
VnN = −8.693 × 10
− 14
Calculate the line currents:
IaA = 0.92 − 2.89i
IaA :=
VnN = 2.396 × 10
Va − VnN
ZA + ZaA
π
180
π
− 15
Calculate the phase voltages at the load:
VA = 118.301
180
π
π
Vc − VnN
ZC + ZcC
IcC = 2.043 + 2.242i
180
π
⋅ arg( IcC) = 47.656
− 15
− 3.109i× 10
VA := ZA ⋅ IaA
180
IcC :=
IcC = 3.033
VB = 118.301
⋅ arg( VA) = 2.801
⋅ arg( VnN) = 111.277
ZB + ZbB
⋅ arg( IbB) = 167.656
IaA + IbB + IcC = −1.332 × 10
π
Vb − VnN
IbB = 3.033
⋅ arg( IaA ) = −72.344
Check:
IbB :=
IbB = −2.963 + 0.648i
IaA = 3.033
180
180
− 14
+ 2.232i× 10
⋅ Vp
⋅ arg( VB) = −117.199
VB := ZB⋅ IbB
VC := ZC⋅ IcC
VC = 118.301
180
π
⋅ arg( VC) = 122.801
Consequently, the line-to-line voltages at the source are:
Vab = Va × 3∠30° = 120∠0°× 3∠30° = 208∠30° Vrms,
Vbc = 208∠ − 120° Vrms and Vca = 208∠120° Vrms
The line-to-line voltages at the load are:
VAB = VA × 3∠30° = 118.3∠3°× 3∠30° = 205∠33° Vrms,
Vbc = 205∠ − 117° Vrms and Vca = 205∠123° Vrms
and the phase currents are
I a = I aA = 10∠ − 72° A rms, I b = I bB = 3∠168° A rms and I c = I cC = 3∠48° A rms
12-12
P12.4-3
Balanced, three-wire, Y-Y circuit:
where
Va = 10∠0° V = 7.07∠0° V rms, Vb = 7.07∠ − 120° V rms and Vc = 7.07∠120° V rms
and
Z A = Z B = Z C = 12 + j (16 )(1) = 12 + j16 Ω
MathCAD analysis (12p4_3.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp :=
10
2
⋅0
j⋅
Vb := Va⋅ e
Describe the balanced three-phase load:
π
180
⋅ − 120
j⋅
Vc := Va⋅ e
ZA := 12 + j⋅ 16
π
180
⋅ 120
ZB := ZA
ZC := ZB
Check: The voltage at the neutral of the load with respect to the neutral of the source should be zero:
VnN :=
ZA ⋅ ZC⋅ e
4
j⋅ ⋅ π
3
+ ZA ⋅ ZB⋅ e
IaA :=
IaA = 0.212 − 0.283i
IaA = 0.354
π
+ ZB⋅ ZC
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
Calculate the line currents:
180
2
j⋅ ⋅ π
3
⋅ arg( IaA ) = −53.13
Va − VnN
ZA
− 15
⋅ Vp
IbB :=
VnN = 1.675 × 10
Vb − VnN
IbB = −0.351 − 0.042i
IbB = 0.354
180
π
⋅ arg( IbB) = −173.13
Calculate the power delivered to the load:


SB := IbB⋅ IbB⋅ ZB
SA := IaA ⋅ IaA ⋅ ZA
SA = 1.5 + 2i
Total power delivered to the load:
SB = 1.5 + 2i
IcC :=
ZB
Vc − VnN
ZC
IcC = 0.139 + 0.325i
IcC = 0.354
180
π
⋅ arg( IcC) = 66.87

SC := IcC⋅ IcC⋅ ZC
SC = 1.5 + 2i
SA + SB + SC = 4.5 + 6i
12-13
Consequently
(a) The rms value of ia(t) is 0.354 A rms.
(b) The average power delivered to the load is P = Re {S} = Re {4.5 + j 6} = 4.5 W
P12.4-4
Unbalanced, three-wire, Y-Y circuit:
where
Va = 100∠0° V = 70.7∠0° V rms, Vb = 70.7∠ − 120° V rms and Vc = 7.07∠120° V rms
Z A = 20 + j ( 377 ) ( 60 ×10−3 ) = 20 + j 22.6 Ω, Z B = 40 + j ( 377 ) ( 40 × 10−3 ) = 40 + j 15.1 Ω
Z C = 60 + j ( 377 ) ( 20 ×10−3 ) = 60 + j 7.54 Ω
and
Z aA = Z bB = Z cC = 10 + j ( 377 ) ( 5 × 10−3 ) = 10 + j 1.89 Ω
Mathcad Analysis (12p4_4.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 100
⋅0
j⋅
Vb := Va⋅ e
π
180
⋅ 120
j⋅
Vc := Va⋅ e
π
180
⋅ − 120
Enter the frequency of the 3-phase source: ω := 377
Describe the three-phase load:
ZA := 20 + j⋅ ω⋅ 0.06
Describe the three-phase line:
ZaA := 10 + j⋅ ω⋅ 0.005 ZbB := ZaA
ZB := 40 + j⋅ ω⋅ 0.04
ZC := 60 + j⋅ ω⋅ 0.02
ZcC := ZaA
12-14
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
( ZaA + ZA ) ⋅ ( ZcC + ZC) ⋅ e
4
j⋅ ⋅ π
3
+ ( ZaA + ZA ) ⋅ ( ZbB + ZB) ⋅ e
2
j⋅ ⋅ π
3
+ ( ZbB + ZB) ⋅ ( ZcC + ZC)
( ZaA + ZA ) ⋅ ( ZcC + ZC) + ( ZaA + ZA ) ⋅ ( ZbB + ZB) + ( ZbB + ZB) ⋅ ( ZcC + ZC)
VnN = 12.209 − 24.552i
Calculate the line currents:
IaA :=
Va − VnN
ZA + ZaA
IaA = 2.156 − 0.943i
IaA = 2.353
180
π
180
VnN = 27.42
IbB :=
π
IcC :=
ZB + ZbB
180
π
⋅ arg( IbB) = 100.492
(
SA = 55.382 + 62.637i
Total power delivered to the load:
ZC + ZcC
IcC = 1.244
Calculate the power delivered to the load:


IbB⋅ IbB
IaA ⋅ IaA
⋅ ZA
SB :=
⋅ ZB
SA :=
2
2
)
Vc − VnN
IcC = −0.99 − 0.753i
IbB = 2.412
⋅ arg( IaA ) = −23.619
(
⋅ arg( VnN) = −63.561
Vb − VnN
IbB = −0.439 + 2.372i
⋅ Vp
)
SB = 116.402 + 43.884i
180
π
⋅ arg( IcC) = −142.741
SC :=

(IcC
⋅ IcC)
2
⋅ ZC
SC = 46.425 + 5.834i
SA + SB + SC = 218.209 + 112.355i
The average power delivered to the load is P = Re {S} = Re {218.2 + j112.4} = 218.2 W
P12.4-5
Balanced, three-wire, Y-Y circuit:
where
Va = 100∠0° V = 70.7∠0° V rms, Vb = 70.7∠ − 120° V rms and Vc = 7.07∠120° V rms
Z A = Z B = Z C = 20 + j ( 377 ) ( 60 ×10−3 ) = 20 + j 22.6 Ω
and
Z aA = Z bB = Z cC = 10 + j ( 377 ) ( 5 × 10−3 ) = 10 + j 1.89 Ω
12-15
Mathcad Analysis (12p4_5.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 100
⋅0
j⋅
Vb := Va⋅ e
π
180
⋅ 120
π
j⋅
180
Vc := Va⋅ e
⋅ − 120
Enter the frequency of the 3-phase source: ω := 377
Describe the three-phase load:
ZA := 20 + j⋅ ω⋅ 0.06
ZB := ZA
ZC := ZA
Describe the three-phase line:
ZaA := 10 + j⋅ ω⋅ 0.005
ZbB := ZaA
ZcC := ZaA
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
( ZaA + ZA ) ⋅ ( ZcC + ZC) ⋅ e
4
j⋅ ⋅ π
3
+ ( ZaA + ZA ) ⋅ ( ZbB + ZB) ⋅ e
2
j⋅ ⋅ π
3
+ ( ZbB + ZB) ⋅ ( ZcC + ZC)
( ZaA + ZA ) ⋅ ( ZcC + ZC) + ( ZaA + ZA ) ⋅ ( ZbB + ZB) + ( ZbB + ZB) ⋅ ( ZcC + ZC)
− 15
VnN = −8.982 × 10
− 14
Calculate the line currents:
IaA :=
IaA = 1.999 − 1.633i
IaA = 2.582
180
π
− 14
+ 1.879i× 10
⋅ arg( IaA ) = −39.243
VnN = 2.083 × 10
Va − VnN
ZA + ZaA
IbB :=
180
π
⋅ arg( VnN) = 115.55
Vb − VnN
IcC :=
ZB + ZbB
IbB = 0.415 + 2.548i
π
⋅ arg( IbB) = 80.757
Vc − VnN
ZC + ZcC
IcC = −2.414 − 0.915i
IbB = 2.582
180
⋅ Vp
IcC = 2.582
180
π
⋅ arg( IcC) = −159.243
Calculate the power delivered to the load:
SA :=

(IaA
⋅ IaA )
⋅ ZA
2
SA = 66.645 + 75.375i
Total power delivered to the load:
SB :=

(IbB
⋅ IbB)
⋅ ZB
2
SB = 66.645 + 75.375i
SC :=

(IcC
⋅ IcC)
⋅ ZC
2
SC = 66.645 + 75.375i
SA + SB + SC = 199.934 + 226.125i
The average power delivered to the load is P = Re {S} = Re {200 + j 226} = 200 W
12-16
P12.4-6
Unbalanced, three-wire, Y-Y circuit:
where
Va = 10∠ − 90° V = 7.07∠ − 90° V rms, Vb = 7.07∠150° V rms and Vc = 7.07∠30° V rms
and
Z A = 4 + j ( 4 )(1) = 4 + j 4 Ω, Z B = 2 + j ( 4 )( 2 ) = 2 + j 8 Ω and Z C = 4 + j ( 4 )( 2 ) = 4 + j 8 Ω
Mathcad Analysis (12p4_6.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 10
⋅ − 90
j⋅
Vb := Vp⋅ e
π
180
⋅ 150
j⋅
Vc := Vp⋅ e
π
180
⋅ 30
Enter the frequency of the 3-phase source: ω := 4
Describe the three-phase load:
ZA := 4 + j⋅ ω⋅ 1
ZB := 2 + j⋅ ω⋅ 2
ZC := 4 + j⋅ ω⋅ 2
Calculate the voltage at the neutral of the load with respect to the neutral of the source:
VnN :=
ZA ⋅ ZC⋅ Vb + ZA ⋅ ZB⋅ Vc + ZB⋅ ZC⋅ Va
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
VnN = 1.528 − 0.863i
Calculate the line currents:
IaA :=
IaA = −1.333 − 0.951i
IaA = 1.638
180
π
180
VnN = 1.755
⋅ arg( IaA ) = −144.495
Va − VnN
ZA
IbB :=
π
Vb − VnN
IbB = 0.39 + 1.371i
IbB = 1.426
180
π
⋅ arg( VnN) = −29.466
⋅ arg( IbB) = 74.116
IcC :=
ZB
Vc − VnN
ZC
IcC = 0.943 − 0.42i
IcC = 1.032
180
π
⋅ arg( IcC) = −24.011
12-17
Calculate the power delivered to the load:


IaA ⋅ IaA
IbB⋅ IbB
SA :=
⋅ ZA
SB :=
⋅ ZB
2
2
(
)
(
SA = 5.363 + 5.363i
)
SC :=
SB = 2.032 + 8.128i
Total power delivered to the load:

(IcC
⋅ IcC)
2
⋅ ZC
SC = 2.131 + 4.262i
SA + SB + SC = 9.527 + 17.754i
The average power delivered to the load is P = Re {S} = Re {9.527 + j17.754} = 9.527 W
P12.4-7
Unbalanced, three-wire, Y-Y circuit:
where
Va = 10∠ − 90° V = 7.07∠ − 90° V rms, Vb = 7.07∠150° V rms and Vc = 7.07∠30° V rms
and
Z A = Z B = Z C = 4 + j ( 4 )( 2 ) = 4 + j 8 Ω
Mathcad Analysis (12p4_7.mcd):
Describe the three-phase source:
j⋅
Va := Vp⋅ e
π
180
Vp := 10
⋅ − 90
j⋅
Vb := Vp⋅ e
π
180
⋅ 150
j⋅
Vc := Vp⋅ e
π
180
⋅ 30
Enter the frequency of the 3-phase source: ω := 4
Describe the three-phase load:
ZA := 4 + j⋅ ω⋅ 2
ZB := ZA
ZC := ZA
The voltage at the neutral of the load with respect to the neutral of the source should be zero:
VnN :=
ZA ⋅ ZC⋅ Vb + ZA ⋅ ZB⋅ Vc + ZB⋅ ZC⋅ Va
ZA ⋅ ZC + ZA ⋅ ZB + ZB⋅ ZC
− 15
VnN = 1.517 × 10
12-18
Calculate the line currents:
IaA :=
IaA = −1 − 0.5i
π
IbB :=
ZA
Vb − VnN
180
π
⋅ arg( IbB) = 86.565
SA = 2.5 + 5i
Total power delivered to the load:
(
ZC
IcC = 1.118
Calculate the power delivered to the load:


IaA ⋅ IaA
IbB⋅ IbB
SA :=
⋅ ZA
SB :=
⋅ ZB
2
2
)
Vc − VnN
IcC = 0.933 − 0.616i
IbB = 1.118
⋅ arg( IaA ) = −153.435
(
IcC :=
ZB
IbB = 0.067 + 1.116i
IaA = 1.118
180
Va − VnN
)
SB = 2.5 + 5i
180
π
⋅ arg( IcC) = −33.435
SC :=

(IcC
⋅ IcC)
2
⋅ ZC
SC = 2.5 + 5i
SA + SB + SC = 7.5 + 15i
The average power delivered to the load is P = Re {S} = Re {7.5 + j15} = 7.5 W
Section 12-6: The ∆- Connected Source and Load
P12.5-1
Given I B = 50∠ − 40° A rms and assuming the abc phase sequence
we have
I A = 50∠80° A rms and I C = 50∠200° A rms
From Eqn 12.6-4
I A = I AB × 3∠ − 30° ⇒ I AB =
so
IA
3∠ − 30°
50∠80°
= 28.9∠110° A rms
3∠−30°
= 28.9∠ − 10° A rms and ICA = 28.9∠ − 130° A rms
I AB =
I BC
12-19
P12.5-2
The two delta loads connected in parallel are equivalent to a single delta
load with
Z ∆ = 5 || 20 = 4 Ω
The magnitude of phase current is
480
Ip =
= 120 A rms
4
The magnitude of line current is
I L = 3 I p = 208 A rms
Section 12-6: The Y- to ∆- Circuit
P12.6-1
We have a delta load with Z = 12∠30° . One phase current is
I AB
 208
  208

∠−30°  −
∠−150° 

V
V −V
3
  3
 = 208∠0° = 17.31∠ − 30° A rms
= AB = A A = 
Z
Z
12∠30°
12∠30°
The other phase currents are
I BC = 17.31∠ − 150° A rms and I CA = 17.31∠90° A rms
One line currents is
I A = I AB × 3∠ − 30° = (17.31∠ − 30° ) ×
(
)
3∠ − 30° = 30∠0° A rms
The other line currents are
I B = 30∠ − 120° A rms and I C = 30∠120° A rms
The power delivered to the load is
P = 3(
208
) (30) cos ( 0 − 30° ) = 9360 W
3
12-20
P12.6-2
The balanced delta load with Z ∆ = 39∠− 40° Ω is
equivalent to a balanced Y load with
ZY =
Z∆
= 13∠ − 40° = 9.96 − j 8.36 Ω
3
Z T = Z Y + 4 = 13.96 − j 8.36 = 16.3∠ − 30.9 Ω
480
∠−30°
3
then I A =
= 17∠0.9° A rms
°
16.3 ∠−30.9
P12.6-3
Vab = Va × 3∠30° ⇒ Va =
Vab
3∠30°
In our case, the given line-to-line voltage is
Vab = 380 ∠30° V rms
380 ∠30°
So one phase voltage is Va =
= 200∠0° V rms
3∠30°
So
VAB = 380∠30° V rms
VA = 220∠0° V rms
VBC = 380∠-90° V rms
VB = 220∠−120° V rms
VCA = 380∠150° V rms
VC = 220∠120° V rms
One phase current is
IA =
VA 220∠0°
= 44∠ − 53.1° A rms
Z
3+ j4
The other phase currents are
I B = 44∠−173.1° A rms amd I C = 44∠66.9° A rms
12-21
P12.6-4
Vab = Va × 3∠30° ⇒ Va =
Vab
3∠30°
In our case, the given line-to-line voltage is
Vab = 380 ∠0° V rms
Va =
So one phase voltage is
So
380 ∠0°
= 200∠ − 30° V rms
3∠30°
Vab = 380∠0° V rms
Va = 220∠ − 30° V rms
Vbc = 380∠-120° V rms
Vb = 220∠−150° V rms
Vca = 380∠120° V rms
Vc = 220∠90° V rms
One phase current is
IA =
Va 220∠−30°
=
= 14.67∠ − 83.1° A rms
Z
9 + j12
The other phase currents are
I B = 14.67∠ − 203.1° A rms and I C = 14.67∠36.9° A rms
12-22
12-23
Section 12-7: Balanced Three-Phase Circuits
P12.7-1
Va =
IA
25
×103 ∠0° Vrms
3
25
×103 ∠0°
Va
=
= 3
= 96∠ − 25° A rms
Z
150 ∠25°
 25

×103  96 cos(0 − 25°) = 3.77 mW
P = 3 Va I A cos (θ v -θ I ) = 3 
 3

P12.7-2
Convert the delta load to an equivalent Y connected load:
ˆ = 50 Ω
Z∆ ⇒ Z
Y
3
To get the per-phase equivalent circuit shown to the right:
The phase voltage of the source is
Z ∆ = 50 Ω
Va =
45×103
∠0° = 26∠0° kV rms
3
The equivalent impedance of the load together with the line is
50
3 + 2 = 12 + j 5 = 13∠22.6° Ω
Z eq =
50
10 + j 20 +
3
(10 + j 20 )
The line current is
Ι aA =
Va 26 × 103 ∠0°
=
= 2000∠ − 22.6° A rms
Z eq
13∠22.6°
The power delivered to the parallel loads (per phase) is
50 

 (10 + j 20 ) 3 
2
6
PLoads = I aA × Re 
 = 4 ×10 × 10 = 40 MW
50
10 + j 20 + 
3 

The power lost in the line (per phase) is
12-24
PLine = I aA × Re {Z Line } = 4 × 106 × 2 = 8 MW
2
The percentage of the total power lost in the line is
PLine
8
× 100% =
× 100% = 16.7%
PLoad + PLine
40 +8
P12.7-3
Ia =
Va 5∠30°
=
= 0.5∠ − 23° A ∴ I a = 0.5 A
Z T 6 + j8
2
PLoad
I
= 3 a Re {Z Load } = 3 × 0.125 × 4 = 1.5 W
2
also (but not required) :
PSource = 3
(5) (0.5)
cos(−30 − 23) = 2.25 W
2
2
Pline
I
= 3 a Re{Z Line } = 3×0.125× 2 = 0.75 W
2
12-25
Section 12-8: Power in a Balanced Load
P12.8-1
Assuming the abc phase sequence:
VCB = 208∠15° V rms ⇒ VBC = 208∠195° V rms ⇒ VAB = 208∠315° V rms
Then
VA =
VAB
208∠315° 208
=
=
∠285° V rms
3∠30°
3∠30°
3
also
I B = 3∠110° A rms ⇒ I A = 3∠230° A rms
Finally
P = 3 VAB I A cos (θ V − θ I ) = 3(
208
) (3) cos(285° − 230°) = 620 W
3
P12.8-2
Assuming a lagging power factor:
cos θ = pf = 0.8 ⇒
θ = 36.9°
The power supplied by the three-phase source is given by
Pin =
Pout
η
=
Pin = 3 I A VA pf
20 ( 745.7 )
= 17.55 kW where 1 hp = 745.7 W
0.85
⇒
Pin
17.55 ×103
IA =
=
= 26.4 A rms
3 VA pf
 480 
3
 ( 0.8 )
 3
480 °
I A = 26.4∠ − 36.9° A rms when VA =
∠0 V rms
3
12-26
P12.8-3
(a) For a ∆-connected load, Eqn 12.8-5 gives
PT
1500
=
= 4.92 A rms
3 VP I L pf 3( 220 )(.8)
3
The phase current in the ∆-connected load is given by
PT = 3 VP I L pf ⇒ I L =
I
IL
4.92
⇒ IP = L =
= 2.84 A rms
3
3
3
The phase impedance is determined as:
IP =
Z=
V
220
VL VL
=
∠ (θ V − θ I ) = L ∠ cos −1 pf =
∠ cos −1 0.8 = 77.44∠36.9° Ω
IP
IP
IP
2.84
(b) For a ∆-connected load, Eqn 12.8-4 gives
PT = 3 VP I L pf ⇒ I L =
PT
1500
=
= 4.92 A rms
3 VP I L pf 3( 220 )(.8)
3
The phase impedance is determined as:
220
V
V
V
Z = P = P ∠ (θ V − θ I ) = P ∠ cos −1 pf = 3 ∠ cos −1 0.8 = 25.8∠36.9° Ω
IP
IP
IP
4.92
P12.8-4
Parallel ∆ loads
Z1Z 2
(40∠30° ) (50∠−60° )
Z∆ =
=
= 31.2 ∠−8.7° Ω
°
°
Ζ1 + Ζ 2
40∠30 + 50∠− 60
VL = VP , Ι P =
VP
600
=
= 19.2 A rms,
Z∆
31.2
IL =
3 Ι P = 33.3 A rms
So P = 3 VL I L pf = 3 (600) (33.3) cos ( − 8.7° ) = 34.2 kW
12-27
P12.8-5
We will use
In our case:
S = S ∠θ = S cosθ + S sin θ = S pf + S sin ( cos −1 pf )
S 1 = 39 (0.7) + j 39 sin ( cos −1 ( 0.7 ) ) = 27.3 + j 27.85 kVA
15
sin ( cos −1 ( 0.21) ) = 15 − j 69.84 kVA
S 2 = 15 +
0.21
S
S 3φ = S 1 + S 2 = 42.3 − j 42.0 kVA ⇒ S φ = 3φ = 14.1− j 14.0 kVA
3
The line current is
*
 S  (14100+ j 14000)
S = Vp I L ⇒ I L =   =
= 117.5 + j 116.7 A rms = 167 ∠45° A rms
V 
208
 p
3
208
∠0° = 120∠0° V rms. The source must
The phase voltage at the load is required to be
3
provide this voltage plus the voltage dropped across the line, therefore
*
= 120∠0° + (0.038 + j 0.072)(117.5 + j 116.7) = 115.9 + j 12.9 = 116.6 ∠6.4° V rms
V
Sφ
Finally
V
= 116.6 V rms
Sφ
P12.8-6
The required phase voltage at the load is VP =
4.16
∠0° = 2.402∠0° kVrms .
3
Let I1 be the line current required by the ∆-connected load. The apparent power per phase
500 kVA
required by the ∆-connected load is S1 =
= 167 kVA . Then
3
S1 = S1 ∠θ = S1 ∠ cos −1 ( pf ) = 167 ∠ cos−1 ( 0.85) = 167∠31.8° kVA
and
*
3
 S1   (167 ×10 ) ∠31.8° 
 = 69.6∠ − 31.8° = 59 − j36.56 A rms
⇒ I1 =   = 
3
 VP   ( 2.402 ×10 ) ∠0° 
*
S1 = VP I1
*
12-28
Let I2 be the line current required by the first Y-connected load. The apparent power per phase
75 kVA
required by this load is S 2 =
= 25 kVA . Then, noticing the leading power factor,
3
S 2 = S 2 ∠θ = S 2 ∠ cos −1 ( pf ) = 25 ∠ cos −1 ( 0 ) = 25∠ − 90° kVA
and
*
3
 S 2   ( 25 ×10 ) ∠ − 90° 

 = 10.4∠90° = j10.4 A rms
⇒ I2 =   =
3


V
×
∠
°
2.402
10
0
) 
 P (
*
S 2 = VP I 2
*
Let I3 be the line current required by the other Y-connected load. Use Ohm’s law to determine I3
to be
2402∠0° 2402∠0°
I3 =
+
= 16 − j 10.7 A rms
150
j 225
The line current is
I L = I1 + I 2 + I 3 = 75− j 36.8 A rms
4.16
∠0° = 2.402∠0° kVrms .The source
3
must provide this voltage plus the voltage dropped across the line, therefore
The phase voltage at the load is required to be VP =
VSφ = 2402∠0° + (8.45 + j 3.9) (75 − j 36.8) = 3179 ∠−0.3° Vrms
Finally
VSL = 3 (3179) = 5506 Vrms
P12.8-7
The required phase voltage at the load is VP =
4.16
∠0° = 2.402∠0° kVrms .
3
Let I1 be the line current required by the ∆-connected load. The apparent power per phase
1.5 MVA
required by the ∆-connected load is S1 =
= 0.5 MVA . Then
3
S1 = S1 ∠θ = S1 ∠ cos −1 ( pf ) = 0.5 ∠ cos −1 ( 0.75) = 0.5∠41.4° MVA
and
*
6
 S1   ( 0.5 ×10 ) ∠41.4° 

 = 2081.6∠ − 41.4° = 1561.4 − j1376.6 A rms
⇒ I1 =   =
3

V
×
∠
°
2.402
10
0
) 
 P (
*
S1 = VP I1
*
12-29
Let I2 be the line current required by the first Y-connected load. The complex power, per phase,
is
0.67
S 2 = 0.67 +
sin ( cos −1 ( 0.8 ) ) = 0.67 + j 0.5 MVA
0.8
*
6
 S 2   ( 0.67 + j 0.5 ) ×106   ( 0.833 ×10 ) ∠ − 36.9° 
 =

I2 =   = 
3
3
 VP   ( 2.402 ×10 ) ∠0°   ( 2.402 ×10 ) ∠0° 
= 346.9∠ − 36.9° = 277.4 − j 208.3 A rms
The line current is
I L = I1 + I 2 = 433.7 − j 345.9 = 554.7∠ − 38.6 A rms
*
*
4.16
∠0° = 2.402∠0° kVrms .The source
3
must provide this voltage plus the voltage dropped across the line, therefore
The phase voltage at the load is required to be VP =
VSφ = 2402∠0° + (0.4 + j 0.8) (433.7 − j 345.9) = 2859.6 ∠ − 38.6° Vrms
Finally
VSL = 3 (2859.6) = 4953 Vrms
The power supplied by the source is
PS =
3 (4953) (554.7) cos (4.2° + 38.6° ) = 3.49 MW
The power lost in the line is
PLine = 3 × ( 554.7 2 ) × Re {0.4+ j 0.8} = 0.369 MW
The percentage of the power consumed by the loads is
3.49 − 0.369
×100% = 89.4%
3.49
12-30
P12.8–8
The required phase voltage at the load is VP =
600
∠0° = 346.4∠0° Vrms .
3
θ = cos −1 (0.8)
= 37 °
Let I be the line current required by the load. The complex power, per phase, is
S = 160 +
160
sin ( cos −1 ( 0.8 ) ) = 160 + j 120 kVA
0.8
The line current is
 S   (160 + j 120 ) × 103 
I=  =
 = 461.9 − j 346.4 A rms
346.4∠0°
 VP  

*
*
600
∠0° = 346.4∠0° Vrms .The source
3
must provide this voltage plus the voltage dropped across the line, therefore
The phase voltage at the load is required to be VP =
VSφ = 346.4∠0° + (0.005 + j 0.025) (461.9 − j 346.4) = 357.5 ∠1.6° Vrms
Finally
VSL = 3 (357.5) = 619.2 Vrms
The power factor of the source is
pf = cos (θ V − θ I ) = cos (1.6 − ( − 37)) = 0.78
12-31
Section 12-9: Two-Wattmeter Power Measurement
P12.9-1
W
= 14920 W
hp
P
14920
Pin = out =
= 20 kW
0.746
η
Pout = 20 hp × 746
Pin = 3 VL I L cos θ
Pin
20 × 103
=
= 0.50
3 VL I L
3 (440) (52.5)
⇒ cos θ =
⇒ θ cos -1 ( 0.5 ) = 60°
The powers read by the two wattmeters are
P1 = VL I L cos (θ + 30° ) = (440) (52.5)cos ( 60° + 30° ) = 0
and
P2 = VL I L cos (θ − 30° ) = (440) (52.5)cos ( 60° − 30° ) = 20 kW
P12.9-2
VP = VL = 4000 V rms
IP =
VP
4000
=
= 80 A rms
Z∆
50
Z
∆
= 40 + j 30 = 50 ∠36.9°
Ι L = 3 I P = 138.6 A rms
pf = cos θ = cos (36.9° ) = 0.80
P1 = VL I L cos (θ + 30° ) = 4000 (138.6) cos 66.9° = 217.5 kW
P2 = VL I L cos (θ −30° ) = 4000 (138.6) cos 6.9° = 550.4 kW
PT = P1 + P2 = 767.9 kW
Check : PT = 3 Ι L VL cos θ =
3 (4000) (138.6) cos 36.9°
= 768 kW which checks
12-32
P12.9–3
Vp = Vp =
200
= 115.47 Vrms
3
VA =115.47∠0° V rms, VB = 115.47∠−120° V rms
and VC = 115.47∠120° V rms
IA =
VA
115.47∠0°
=
= 1.633∠ − 45° A rms
Z
70.7∠45°
I B = 1.633 ∠ − 165° A rms and I C = 1.633 ∠75° A rms
PT =
3 VL I L cos θ = 3 (200) (1.633) cos 45° = 400 W
PB = VAC I A cos θ1 = 200 (1.633) cos (45° − 30° ) = 315.47 W
PC = VBC I B cos θ 2 = 200 (1.633) cos (45° + 30° ) = 84.53 W
P12.9-4
ZY = 10∠ − 30° Ω and Z ∆ = 15∠30° Ω
Convert Z ∆ to Z Yˆ → Z Yˆ =
then Zeq =
Z∆
= 5∠30° Ω
3
(10∠−30° ) ( 5∠30° ) =
10∠−30°+5∠30°
208
Vp = Vp =
= 120 V rms
3
VA = 120∠0° V rms ⇒ I A =
50∠0°
= 3.78∠10.9° Ω
13.228 ∠−10.9°
120∠0°
= 31.75 ∠−10.9°
3.78 ∠10.9°
I B = 31.75∠−130.9°
I C = 31.75∠109.1°
PT = 3VL I L cos θ = 3 ( 208 ) ( 31.75 ) cos (10.9 ) =11.23 kW
W1 = VL I L cos (θ −30°) = 6.24 kW
W2 = VL I L cos (θ + 30°) = 4.99 kW
12-33
P12.9-5
PT = PA + PC = 920 + 460 = 1380 W
tan θ = 3
( −460 ) = −0.577 ⇒ θ = −30°
PA − PC
= 3
1380
PA + PC
PT = 3 VL I L cos θ so I L =
IP =
P12.9-6
IL
= 4.43 A rms
3
∴ Z∆ =
Z = 0.868 + j 4.924 = 5∠80°
VL = 380 V rms, VP =
I L = I P and I P =
1380
PT
=
=7.67 A rms
3 VL cos θ
2 ×120×cos( −30 )
⇒
120
= 27.1 Ω ο r Z ∆ = 27.1 ∠−30°
4.43
θ = 80°
380
= 219.4 V rms
3
VP
= 43.9 A rms
Z
P1 = ( 380 ) ( 43.9 ) cos (θ −30° ) = 10,723 W
P2 = ( 380 ) ( 43.9 ) cos (θ + 30° ) = −5706 W
PT = P1 + P2 = 5017 W
12-34
PSpice Problems
SP 12-1
FREQ
6.000E+01
IM(V_PRINT3)IP(V_PRINT3)IR(V_PRINT3)II(V_PRINT3)
3.142E+00 -1.644E+02 -3.027E+00 -8.436E-01
FREQ
6.000E+01
IM(V_PRINT1)IP(V_PRINT1)IR(V_PRINT1)II(V_PRINT1)
3.142E+00 -4.443E+01
2.244E+00 -2.200E+00
FREQ
6.000E+01
VM(N01496)
2.045E-14
FREQ
6.000E+01
IM(V_PRINT2)IP(V_PRINT2)IR(V_PRINT2)II(V_PRINT2)
3.142E+00
7.557E+01
7.829E-01
3.043E+00
VP(N01496)
2.211E+01
VR(N01496)
1.895E-14
VI(N01496)
7.698E-15
3.1422
20 = 98.7 W
2
3.1422
I B = 3.142∠75.57° A and RB = 20 Ω ⇒ PB =
20 = 98.7 W
2
3.1422
I C = 3.142∠ − 164.4° A and RC = 20 Ω ⇒ PC =
20 = 98.7 W
2
I A = 3.142∠ − 43.43° A and RA = 20 Ω ⇒ PA =
P = 3 ( 98.7 ) = 696.1 W
12-35
SP 12-2
FREQ
6.000E+01
IM(V_PRINT3)IP(V_PRINT3)IR(V_PRINT3)II(V_PRINT3)
1.612E+00 -1.336E+02 -1.111E+00 -1.168E+00
FREQ
6.000E+01
IM(V_PRINT1)IP(V_PRINT1)IR(V_PRINT1)II(V_PRINT1)
2.537E+00 -3.748E+01
2.013E+00 -1.544E+00
FREQ
6.000E+01
VM(N01496) VP(N01496)
1.215E+01 -1.439E+01
FREQ
6.000E+01
IM(V_PRINT2)IP(V_PRINT2)IR(V_PRINT2)II(V_PRINT2)
2.858E+00
1.084E+02 -9.023E-01
2.712E+00
VR(N01496) VI(N01496)
1.177E+01 -3.018E+00
2.537 2
20 = 64.4 W
2
2.8582
I B = 2.858∠108.4° A and RB = 30 Ω ⇒ PB =
30 = 122.5 W
2
1.6122
I C = 1.612∠ − 133.6° A and RC = 600 Ω ⇒ PC =
60 = 78 W
2
I A = 2.537∠ − 37.48° A and
RA = 20 Ω ⇒ PA =
P = 64.4 + 122.5 + 78 = 264.7 V
12-36
Verification Problems
VP 12-1
416
= 240 V = VA
3
Z = 10 + j4 = 10.77 ∠21.8° Ω
VA =
VA
240
=
= 22.28 A rms ≠ 38.63 A rms
Z
10.77
38.63
= 22.3 . It appears that the line-to-line voltage was
The report is not correct. (Notice that
3
mistakenly used in place of the phase voltage.)
IA =
VP 12-2
VL = VP = 240∠0° Vrms
Z = 40 + j 30 = 50 ∠36.9° Ω
IP =
VP
240∠0°
=
= 4.8 ∠−36.9° A rms
Z
50∠36.9°
The result is correct.
Design Problems
DP 12-1
P = 400 W per phase,
0.94 = pf = cos θ
⇒
θ = cos-1 ( 0.94 ) =20°
208
I L 0.94 ⇒ I L = 3.5 A rms
3
I
I ∆ = L = 2.04 A rms
3
V
208
= 101.8 Ω
Z = L =
2.04
I∆
400 =
Z = 101.8 ∠20° Ω
12-37
DP 12-2
VL = 240 V rms
PA = VL I L cos (30° + θ ) = 1440 W
PC = VL I L cos (30° − θ ) = 0 W ⇒
30−θ = 90° or θ = −60°
then 1440 = 240 I L cos (−30° )
I L = 6.93 A rms
IL
= IP =
VP
Z
⇒
⇒
240
V
Z = P = 3 = 20 Ω
IP
6.93
Finally, Z = 20 ∠ − 60° Ω
DP 12-3
Pin =
Pout
η
100 hp × (746
=
W
)
hp
0.8
= 93.2 kW, P =
φ
Pin
= 31.07 kW
3
VL = 480 V rms, pfc = 0.9 and pf = 0.75. We need the impedance of the load so that we can use
Eqn 11.6-7 to calculate the value of capacitance needed to correct the power factor.
0.75 = pf = cos θ
⇒
θ = cos-1 ( 0.75) = 41.4°
480
I P 0.75 ⇒ I P = 149.5 A rms
3
480
VP
3 = 1.85 Ω
Z =
=
IP
149.5
31070 =
Z = 1.85 ∠41.4° Ω = 1.388 + j1.223 Ω
The capacitance required to correct the power factor is given by
 tan (cos −1 0.75) − tan (cos −1 0.9) 
1.365
C=
= 434 µ F
×
1.3652 +1.2042
377
(Checked using LNAPAC 6/12/03)
12-38
DP 12-4
VL = 4∠0° kV rms
n2
25
VL = 4000∠0° = 100∠0° kVrms
n1
1
Try n2 = 25 then V2 =
VL 4×103∠0°
= 3∠0° kA rms
=
IL =
4
ZL
3
3000∠0°
The line current in 2.5 Ω is I =
= 120∠0° A rms
25
Thus V1 = ( R + j X ) I + V2
= (2.5 + j 40) (120∠0°) + 100×103 = 100.4 ∠2.7° kV
Step need : n1 =
Ploss = I
2
100.4 kV
= 5.02 ≅ 5
20 kV
R = 120
2
(2.5) = 36 kW, P = (4×103 ) (3× 103 ) = 12 MW
12 − .036
× 100% = 99.7 % of the power supplied by the source
12
is delivered to the load.
∴η =
12-39
Download