Three Phase Systems 9.11 295 MEASUREMENT OF POWER Star-Connected Balanced Load with Neutral Point Power can be measured in this case by connecting a single wattmeter with its current coil in one line and the pressure coil between the line and the neutral point as shown in Fig. 9.16. The reading of the wattmeter thus connected, gives the power per phase. Total power = 3 ´ power per phase = 3 ´ wattmeter reading R L W R 3-phase balanced load N 3-phase ac supply R L R L Y B Fig. 9.16 Measurement of power by single wattmeter Measurement of Power by Two Wattmeter Method Power in a 3-phase three wire system, with balanced or unbalanced load can be measured by using two wattmeters. The load may be star or delta connected. The current coils of the two wattmeters are connected in any of the two lines and the pressure coils are connected between these lines and the third line, as shown in Fig. 9.17. Let eRN,, eYN and eBN be the voltages across the three phases of the load and iR, iY and iB the currents flowing in the three lines. Total instantaneous power in the load = eRN iR + eYN iY + eBN iB Instantaneous current through the current coil of wattmeter W1 = iR Instantaneous voltage across the pressure coil of wattmeter W1 eRB = eRN – eBN Instantaneous power measured by wattmeter W1 = iR ´ (eRN – eBN) = iR ´ eRB Instantaneous current through current coil of wattmeter W2 = iY Basic Electrical Engineering 296 R iR W1 eRN Z1 3-phase load 3-phase ac supply N Z2 eYN W2 Y B Fig. 9.17 Z3 eBN iY iB Measurement of power in 3-phase, three wire system Instantaneous voltage across the pressure coil of wattmeter W2 eYB = eYN – eBN Instantaneous power measured by W2 = iY ´ (eYN – eBN) = iY ´ eYB Total instantaneous power = eRN iR + eYN iY + eBN iB Moreover, for 3-phase, 3-wire system, iR + iY + iB = 0 (9.18) \ iB = – (iR + iY) Substituting the value of iB in Eq. (9.18) Total instantaneous power = eRN iR + eYN iY + eBN (– iR – iY) = iR (eRN – eBN) + iY (eYN – eBN) = Power measured by W1 + Power measured by W2 Hence at any instant, the total power is equal to the sum of the two wattmeter readings. However, the inertia of the moving system of the wattmeters causes it to indicate the mean value of power taken over a cycle. Thus the sum of the readings of the two wattmeters gives the average value of the total power fed to the three phase load. No particular conditions have been assumed, while deriving the above relationship, hence, the result holds good for balanced as well as unbalanced load. Though a star-connected load has been assumed in the above derivation, but the same result will be obtained by taking a delta-connected load. Three Phase Systems 297 Measurement of Power by Three Wattmeter Method In case the supply is 3-phase, 4-wire system, then for unbalanced loads the two wattmeter method cannot be used as there is a current flowing in the neutral. For such a system, three wattmeters are to be used to measure the total 3-phase power. Each wattmeter is connected with its current coil in series with the line and the pressure coil connected between the phase and neutral as shown in Fig. 9.18. Total Power = PR + PY + PB = WR + WY + WB Thus, the addition of the readings of three wattmeters will give the total power consumed by the load. R IR WR 3-phase ac supply VRN 3-f unbalanced load N N WY IY Y VBN VYN WB B Fig. 9.18 IB Measurement of power by three wattmeter method 9.12 MEASUREMENT OF POWER AND POWER FACTOR IN THREE-PHASE SYSTEM WITH BALANCED LOAD USING TWO WATTMETER METHOD Figure 9.17 shows 3-phase star-connected balanced load, supplied from a 3-phase supply system with two wattmeters properly connected in the circuit to measure the input power to the load. Let IR, IY and IB be the rms values of the currents in the lines and VRN, VYN and VBN the rms values of voltages across the phases. The phasor diagram of such a circuit with an assumption of lagging current has been shown in Fig. 9.19. The load being balanced, currents IR, IY and IB are taken equal in magnitude and lagging by an angle f with respect to its own phase voltage. Similarly, phase voltage VRN, VYN and VBN are equal in magnitude but displaced by 120°, the phase sequence being RYB. Current through the current coil of wattmeter W1 = IR Basic Electrical Engineering 298 –V B N VRB VRN IR f VYB IB VBN Fig. 9.19 f f 30° IY N –V B VYN Phasor diagram for measurement of power Voltage across the pressure coil of wattmeter W1 = VRN – VBN = VRB Referring to the phasor diagram, Fig. 9.19, phase difference between IR and VRB = (30 – f) (9.19) Thus, the reading of wattmeter W1 = IR VRB cos (30 – f) Current through the current coil of wattmeter W2 = IY Voltage across the pressure coil of wattmeter W2 = VYN – VBN = VYB Referring to the phasor diagram (Fig. 9.19), the phase difference between the current IY and voltage VYB = (30 + f). Thus, reading of wattmeter W2 = IY VYB cos (30 + f) As the load is balanced, IR = IY = IB = IL VRY = VYB = VBR = VL Substituting these in Eqs 9.19 and 9.20, W1 = VL IL cos (30 – f) W2 = VL IL cos (30 + f) Adding Eqs. (9.21 and 9.22) W1 + W2 = VL IL cos (30 – f) + VL IL cos (30 + f) = VL IL [cos 30° cos f + sin 30° sin f + cos 30° cos f – sin 30° sin f] (9.20) (9.21) (9.22) = 3 VL IL cos f = Total power input to a balanced load. Hence, the sum of the readings indicated by the two wattmeters connected as per Fig. 9.17 is equal to the total power drawn by a 3-phase balanced load. Now, W1 + W2 = 3 VL IL cos f (9.23) Three Phase Systems Subtracting Eq. (9.22) from Eq. (9.21), W1 – W2 = VL IL cos (30 – f) – [VL IL cos (30 + f)] = VL IL [cos 30° cos f + sin 30° sin f – cos 30° cos f + sin 30° sin f] W1 – W2 = VL IL sin f Dividing Eq. (9.24) by Eq. (9.23), W1 - W2 = W1 + W2 tan f = Power factor, cos f = = (9.24) V L I L sin f 3 V L I L cos f 3 FG W - W IJ HW +W K 1 2 1 2 (9.25) 1 1 = sec f cos f = 299 sec 2 f 1 1 + tan 2 f 1 L W - W OP 1 + 3M NW + W Q 1 2 1 2 2 (9.26) Hence, power factor can be calculated using Eq. (9.26) from the readings of two wattmeters. Equation (9.26) may also be put in the following form, 1 cos f = 2 W 1- 2 W1 1+ 3 W2 1+ W1 F GG GH cos f = I JJ JK 1 L1 - r OP 1+ 3 M N1 + r Q 2 (9.27) W2 W1 A graph of power factor vs the ratio of wattmeter reading using Eq. (9.27), has been drawn in Fig. 9.20 for r varying from +1 to –1. This graph can also be used for finding out the value of power factor, corresponding to a particular ratio of wattmeter readings. The following important conclusions can be drawn from the graph of power factor plotted in Fig. 9.20. where r = ratio of wattmeter readings = (i) Reading of wattmeter W2 is zero, when the load power factor is 0.5 lagging, i.e. f = 60°. Basic Electrical Engineering 300 1.0 0.8 Ratio of wattmeter reading 0.6 0.4 0.2 0 –0.2 –0.4 –0.6 –0.8 –1.0 Fig. 9.20 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 Power factor Relation between pf and ratio of wattmeter readings (ii) Reading of wattmeter W2 is negative, for the load power factor less than 0.5 lagging, i.e. for f > 60°. In such a case it is necessary to reverse the connections to either the current or pressure coil, in order to measure the power registered by wattmeter W2. However, the reading thus obtained must be taken as negative, while calculating the total power and the power factor. (iii) The reading of wattmeter W2 will be positive, when the load power factor is greater than 0.5 lagging, i.e. f < 60°. (iv) Both the wattmeters will indicate the same readings, when the power factor of the load is unity, i.e. f = 0. Examples on Power Measurement Example 9.8 Two wattmeters connected to measure the power input to a 3-phase circuit indicate 15 kW and 1.5 kW respectively, the latter reading being obtained after reversing the current coil connections. Calculate the power and power factor of the load. Solution: Reading of first wattmeter, W1 = 15 kW Reading of second wattmeter has been obtained after reversing the current coil connections. As such this reading is really negative, because of reversing the current coil connections. Thus reading of second wattmeter, W2 = – 1.5 kW Total power fed to the load = W1 + W2 = 15 + (– 1.5) = 13.5 kW Three Phase Systems Power factor of the load can be calculated from the above reading by first finding out tan f, that is tangent of the power factor angle. tan f = 3 W1 - W2 W1 + W2 = 3 15 - ( - 15 .) 15 + ( - 15 .) = 3´ 16.5 = 2.117 . 135 Hence power factor angle, f = 64.7° Power factor of the load, cos f = 0.427 Example 9.9 Two wattmeters have been used to measure the power input to a 150 kW, 440 V, 3-phase slip ring induction motor running at full load. The wattmeter readings are 115 kW and 50 kW. Calculate (i) the input to the motor, (ii) power factor of the motor, (iii) line current drawn by the motor and (iv) efficiency of the motor. Solution: (i) Power input to the motor = W1 + W2 = 115 + 50 = 165 kW (ii) tan f = 3 W1 - W2 = W1 + W2 3 115 - 50 = 0.682 115 + 50 Power factor angle, f = 34.3° Power factor, cos f = 0.826 (iii) Power input to the motor = = Thus line current, IL = 3 ´ VL ´ IL ´ cos f 3 ´ 440 ´ IL ´ 0.826 165 ´ 10 3 = 262.1 A 3 ´ 440 ´ 0.826 (iv) Output of the motor = 150 kW Input to the motor = 165 kW output 150 = 165 input = 0.909 = 90.9% Thus, the efficiency of the induction motor = Example 9.10 A balanced star-connected load is supplied from a symmetrical, 3-phase, 440 V, 50 Hz supply system. The current in each phase is 20 A and lags behind its phase voltage by an angle 40°. Calculate (i) phase voltage, (ii) load parameters, (iii) total power and (iv) readings of two wattmeters, connected in the load circuit to measure the total power. Solution: Figure 9.17 shows a balanced star-connected load connected across a 3-phase supply. (i) Line voltage, VL = 440 V V 440 Phase voltage in star-connected circuit, Vph = L = = 254 V 3 3 301 Basic Electrical Engineering 302 (ii) Current in each phase = 20 A Impedance of the load per phase, Zph = Zph = Vph 254 = = 12.7 W Iph 20 R2 + X 2 = 12.7 (i) Moreover, the current in each phase lags behind its voltage by 40°, hence X tan 40° = R or Inductive reactance of the load, X = 0.839 R Substituting the value of X in Eq. (i) R2 + (0.839)2 R2 = (12.7)2 12.7 Resistance of the load, R = 1 + (0.839 )2 = 9.73 W Inductive reactance of the load, X = 0.839 ´ 9.73 = 8.16 W (iii) Power consumed by each phase = VPh Iph cos f = 254 ´ 20 ´ cos 40° = 3891.5 W Total power = 3 ´ 3891.5 = 11674.5 W = 11.6745 kW (iv) Total power = W1 + W2 (reading of two wattmeters) Thus W1 + W2 = 11.6745 W - W2 Also tan 40° = 3 1 W1 + W2 or W 1 – W2 = (ii) 11.6745 ´ 0.839 3 W1 – W2 = 5.656 Solving Eqs (ii and iii), W1 = 8.665 kW W2 = 3.009 kW (iii) Example 9.11 Power input to a 3-phase 440 V, 37.3 kW induction motor, whose efficiency and power factor are respectively 88 percent and 0.82, is to be measured by two wattmeter method. Find the reading of both the wattmeters and the full load line current drawn by the motor. Solution: Power output of 3-phase induction motor = 37.3 kW Efficiency of the motor = 88 % output 37.3 Power input to the motor = = = 42.386 kW 0.88 efficiency Power input when measured by two wattmeter method = W1 + W2 where, W1 and W2 are the readings of the two wattmeters. Hence W1 + W2 = 42.386 Power factor of the motor, cos f = 0.82 Power factor angle, f = cos–1 0.82 = 34.91° (i) Three Phase Systems 303 In power measurement by two wattmeter method, W - W2 tan f = 3 1 W1 + W2 W1 - W2 42.386 42.386 ´ 0.698 W1 – W2 = = 17.081 kW 3 tan 34.91° = Thus, 3 (ii) Solving Eqs (i and ii) 2 W1 = 42.386 + 17.081 59.467 W1 = = 29.734 kW 2 W2 = 42.386 – 29.734 = 12.652 kW Hence the readings of two wattmeters are 29.734 and 12.652 kW. power inpu t Full load line current drawn by the motor = 3 ´ VL ´ cos f 42.386 ´ 10 3 3 ´ 440 ´ 0.82 = 67.8 A = Example 9.12 Three inductive coils, each having a resistance of 20 W and reactance of 15 W are connected (i) in star (ii) in delta, across a 3-phase, 400 V, 50 Hz supply. Calculate in each case, the readings on two wattmeters connected in the circuit to measure the power input. Also determine the phase and line currents in each case. Solution: (i) Three coils with resistance 20 W and reactance 15 W each, are connected in star configuration. V 400 = 231 V Phase voltage, Vph = L = 3 3 Impedance of each coil, i.e. of each phase, Zph = (20 )2 + (15)2 = 25 W Phase current = Vph 231 = = 9.24 A Zph 25 Line current = phase current (for star–connected circuits) = 9.24 A Power factor of the circuit, cos f = Power input to the circuit, P = Rph 20 = = 0.8 Zph 25 3 ´ VL ´ IL cos f = 3 ´ 400 ´ 9.24 ´ 0.8 = 5121 W When two wattmeters are connected in the circuit to measure the power input to the circuit, then, Basic Electrical Engineering 304 Power input = W1 + W2 (W1 and W2 are the readings of two wattmeters) Hence W1 + W2 = 5121 (i) Power factor of the circuit as calculated from the parameters of the circuit, cos f = 0.8 f = 36.87° or However, when power is measured by two wattmeters W1 - W2 tan f = 3 W1 + W2 tan 36.87° = or W1 – W2 = 3 W1 - W2 5121 0.75 ´ 5121 = 2217.5 3 (ii) Solving Eqs (i and ii) 5121 + 2217.5 W1 = = 3669.25 W 2 W2 = 1451.75 W Hence the readings of two wattmeters in case of star connection are 3669.25 and 1451.75 W. (ii) Now the same coils are connected in mesh across a 3-phase, 400 V, 50 Hz supply. Thus, phase voltage = 400 V (equals line voltage) Impedance per phase, Zph = 25 W 400 Current per phase = = 16 A 25 Line current = 3 ´ phase current (in delta-connected circuits) = 3 ´ 16 = 27.72 A Power factor of the delta connected circuit = 0.8 (remains same) Power input to the circuit = = Thus, 3 VL IL cos f 3 ´ 400 ´ 27.72 ´ 0.8 = 15362 W W¢1 + W¢2 = 15362 W ¢- W2¢ tan f = 3 1 W1¢+ W2¢ 0.75 = W1¢ – W¢2 = 3 (iii) W1¢- W2¢ 15362 0.75 ´ 15362 3 W1¢ – W¢2 = 6652.5 Solving Eqs (iii and iv), W¢1 = 11007.75 W W¢2 = 4315.25 W Readings on two wattmeters are, 11007.75 and 4315.25 W. (iv)