TAC OP7

advertisement
TAC Vista
TAC OP7
Operator Panel
The TAC OP7 is a small but powerful operator panel designed to be used with all models of the TAC Xenta 700 series of controllers.
It has an LCD display, 240x160 pixels, with up to eight lines; four function buttons, four navigation buttons and one general purpose
wheel. The LCD display is backlit.
The OP7 is connected to Xenta 700 via an adapter that provides the power and the communication interface.
The operator panel allows access to control parameters and makes it possible to view and acknowledge alarms. Additionally, it is used
to monitor signal values, display trend graphs, adjust setpoints and time channels. All values are displayed with their name and unit,
and the trend curve display has zoom and pan facilities.
The TAC OP7 can be mounted in a cabinet door using the remote mounting kit, or hung on any flat, vertical surface using the wall
mounting kit. In both cases OP7 can be easily detached and used as a hand-held terminal.
Technical Data
Supply voltage (from the OP7 Adapter Xenta 700)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 V DC ±20%
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . max. 1 W
Transformer sizing (OP7 Adapter Xenta 700) . . . . . . . . . . . 3 VA
Part Numbers
TAC OP7 (mounting 1, 2, and 3; see next page) . . . 007309270
which includes, in addition to the operator panel:
RJ45 female/female adapter . . . . . . . . . . . . . . . . 3261217000
Remote cables 2 RJ45 conn. 3 m . . . . . . . . . . . . 3261218000
OP7 Adapter Xenta 700 (includes CPU cable) . . . . . 007309280
Ambient Temperature
Operation . . . . . . . . . . . . –10 °C to +60 °C (+14 °F to +140 °F) Remote mounting kit IP 54 (mounting 1) . . . . . . . . 3261214000
Storage . . . . . . . . . . . . . . . –25 °C to +70 °C (–13 °F to +158 °F) Door IP 65 (mounting 1) . . . . . . . . . . . . . . . . . . . . 3261215000
Humidity . . . . . . IEC 68-2-3, 5: up to 95% RH non-condensing OP7 Wall mounting kit (mounting 2) . . . . . . . . . . . . 007309290
Remote cables 2 RJ45 conn. 1 m . . . . . . . . . . . . . . 3261216000
Mechanical
Remote cables 2 RJ45 conn. 5 m . . . . . . . . . . . . . . 3261219000
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABS/PC
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . see Fig. 1
Cabinet door cutout . . . . . . . . . 105 x 116 mm (4.13 x 4.57 in.)
Enclosure rating:
92
25
Hand-held panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 20
(3.62)
(0.98)
Cabinet mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 54
Cabinet mounted with covering door . . . . . . . . . . . . . . . IP 65
mm
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.15 kg (0.33 lb.)
(in.):
Agency Compliances
Environment protection . . . . . . . . . . . . . . . . . . . . . . . . UL508C
Electrostatics discharge . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-2
Radiated EM field . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-3
Transient burst . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-4
Surge immunity . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-5
Immunity conducted radio frequency . . . . . . . . . . IEC 1000-4-6
Emission . . . . . CISPR 11, Class A /EN55011, Class A, EN55022
C-tick . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-tick N1831
RoHS directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2002/95/EG
Supported characters
Pan-European character set . . . . . . . . . . . . . . . . . . . . . . . WGL4
03-00072-02-en
108
(4.25)
Unit connection
Xenta 700 . . . . . . . . . . . . . via modular jack on the OP7 adapter
31
(1.22)
Figure 1
42
(1.65)
OP7, Xenta 700 and XBuilder
The operator panel is connected to
Xenta 700 via an adapter (see figure 2).
Adapter
24 VAC
RS 232
OP7
Transformer
To OP7 or
Remote/Wall
mounting
Additional FUNCTIONS
Multiple OP7 users can be defined. In
this way different user categories can be
given access to different parts and functions of the system.
Every user has an optional, personal
password.
The wheel is used for easy navigation and
to alter values.
Access rights for individual users can be
set for each folder of the web.
If no changes are made within 5 minutes,
the operator is logged off and the default
page displayed.
A set of shortcuts to the OP7 content
entries can also be specified for each user.
This greatly facilitates navigation to the
most common tasks.
There are functional tests for the keyboard, display, and the controller communication.
Mounting
The operator panel can be mounted in
one of two types of holder (figure 5:1
and 5:2). In both cases the OP7 (1) can
easily be removed and used as a handheld terminal (figure 5:3).
2. Wall mounting
Put the Wall mounting kit (2) on any flat,
vertical surface and use it as a convenient
holder for the OP7. The Remote cable (4)
and the RJ45 female/female adapter (5)
are supplied with the OP7. An additional
remote cable (6) is required.
CPU cable
The OP7 mirrors the web contents of
Xenta 711/731, and the simulated web
contents of Xenta 701/721, as an enduser web is not provided in these models.
XBuilder is used to program the Xenta
700. XBuilder will also mirror the contents
of the Xenta 700 web for the TAC OP7.
Signal viewer 2
Signal 1
value 1
°C
Signal 2
value 2
...
Signal 3
value 3
unit 3
Signal 4
value 4
unit 4
Signal 5
value 5
°C
value 6
unit 6
Signal 6
Force
View
1. Remote (cabinet door) mounting
Fix the Remote mounting kit (2) in a
cabinet door cut-out. The optional hinged
cover (3) will give added protection from
IP 54 to IP 65. The Remote cable (4),
supplied with the OP7, is used to connect the holder to the Xenta 700 adapter
(fig. 2).
128.1 (5.0)
Ø 3.6
(0.14)
Ø 2.9
(0.11)
2
4
5
To Xenta 700
adapter
1a. TAC OP7 with a Remote
(cabinet door) mounting kit
Edit
Figure 3
2. TAC OP7 with a Wall mounting kit and an additional cable
88.0 (3.5)
Figure 2
2
3
1
6
The OP7 mirror of the web includes:
1
-- Value pages (figure 3)
3. Handheld terminal
To use the OP7 as a handheld terminal
you must have a cable (4 or 6) and an
RJ45 female/female adapter (5), to connect it to:
-- Alarm viewers
-- Time Schedule viewers
-- Trendlog viewers (figure 4)
Additionally, the OP7 contains:
4
-- Additional Value pages, listing all System Variables
-- the wall mounted holder.
To Xenta 700 adapter
1b. Remote (cabinet door) mounting
*) cut-out, and
**) required area; mm (in.)
YB = 6.9
1
2008-04-16 14:55:51
<<
>>
More
Figure 5:1
Figure 4
Copyright © 2008-2010, Schneider Electric
All brand names, trademarks and registered trademarks are
the property of their respective owners. Information contained
within this document is subject to change
without notice. All rights reserved.
03-00072-02-en
35
(1.4)
Mar 2010
For more information visit
www.schneider-electric.com/buildings
4 or 6
28
(1.1)
16
(0.7)
YA = 14.3
116 (4.6)
105 (4.1)
A+B
3. TAC OP7 as a
handheld terminal
5
16
(0.7)
Trend log
-- a Xenta 700 adapter (fig. 2)
-- the remote (cabinet door) holder or
-- Additional Value pages, listing all
Variables
-- Additional Value pages, listing all Xenta
400 I/O signals (for the root user only)
Figure 5:2
*
**
To Xenta 700 adapter or
Remote/Wall mounting holder
Figure 5:3
Download