TAC Vista TAC OP7 Operator Panel The TAC OP7 is a small but powerful operator panel designed to be used with all models of the TAC Xenta 700 series of controllers. It has an LCD display, 240x160 pixels, with up to eight lines; four function buttons, four navigation buttons and one general purpose wheel. The LCD display is backlit. The OP7 is connected to Xenta 700 via an adapter that provides the power and the communication interface. The operator panel allows access to control parameters and makes it possible to view and acknowledge alarms. Additionally, it is used to monitor signal values, display trend graphs, adjust setpoints and time channels. All values are displayed with their name and unit, and the trend curve display has zoom and pan facilities. The TAC OP7 can be mounted in a cabinet door using the remote mounting kit, or hung on any flat, vertical surface using the wall mounting kit. In both cases OP7 can be easily detached and used as a hand-held terminal. Technical Data Supply voltage (from the OP7 Adapter Xenta 700) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 V DC ±20% Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . max. 1 W Transformer sizing (OP7 Adapter Xenta 700) . . . . . . . . . . . 3 VA Part Numbers TAC OP7 (mounting 1, 2, and 3; see next page) . . . 007309270 which includes, in addition to the operator panel: RJ45 female/female adapter . . . . . . . . . . . . . . . . 3261217000 Remote cables 2 RJ45 conn. 3 m . . . . . . . . . . . . 3261218000 OP7 Adapter Xenta 700 (includes CPU cable) . . . . . 007309280 Ambient Temperature Operation . . . . . . . . . . . . –10 °C to +60 °C (+14 °F to +140 °F) Remote mounting kit IP 54 (mounting 1) . . . . . . . . 3261214000 Storage . . . . . . . . . . . . . . . –25 °C to +70 °C (–13 °F to +158 °F) Door IP 65 (mounting 1) . . . . . . . . . . . . . . . . . . . . 3261215000 Humidity . . . . . . IEC 68-2-3, 5: up to 95% RH non-condensing OP7 Wall mounting kit (mounting 2) . . . . . . . . . . . . 007309290 Remote cables 2 RJ45 conn. 1 m . . . . . . . . . . . . . . 3261216000 Mechanical Remote cables 2 RJ45 conn. 5 m . . . . . . . . . . . . . . 3261219000 Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABS/PC Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . see Fig. 1 Cabinet door cutout . . . . . . . . . 105 x 116 mm (4.13 x 4.57 in.) Enclosure rating: 92 25 Hand-held panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 20 (3.62) (0.98) Cabinet mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP 54 Cabinet mounted with covering door . . . . . . . . . . . . . . . IP 65 mm Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.15 kg (0.33 lb.) (in.): Agency Compliances Environment protection . . . . . . . . . . . . . . . . . . . . . . . . UL508C Electrostatics discharge . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-2 Radiated EM field . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-3 Transient burst . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-4 Surge immunity . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 1000-4-5 Immunity conducted radio frequency . . . . . . . . . . IEC 1000-4-6 Emission . . . . . CISPR 11, Class A /EN55011, Class A, EN55022 C-tick . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-tick N1831 RoHS directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2002/95/EG Supported characters Pan-European character set . . . . . . . . . . . . . . . . . . . . . . . WGL4 03-00072-02-en 108 (4.25) Unit connection Xenta 700 . . . . . . . . . . . . . via modular jack on the OP7 adapter 31 (1.22) Figure 1 42 (1.65) OP7, Xenta 700 and XBuilder The operator panel is connected to Xenta 700 via an adapter (see figure 2). Adapter 24 VAC RS 232 OP7 Transformer To OP7 or Remote/Wall mounting Additional FUNCTIONS Multiple OP7 users can be defined. In this way different user categories can be given access to different parts and functions of the system. Every user has an optional, personal password. The wheel is used for easy navigation and to alter values. Access rights for individual users can be set for each folder of the web. If no changes are made within 5 minutes, the operator is logged off and the default page displayed. A set of shortcuts to the OP7 content entries can also be specified for each user. This greatly facilitates navigation to the most common tasks. There are functional tests for the keyboard, display, and the controller communication. Mounting The operator panel can be mounted in one of two types of holder (figure 5:1 and 5:2). In both cases the OP7 (1) can easily be removed and used as a handheld terminal (figure 5:3). 2. Wall mounting Put the Wall mounting kit (2) on any flat, vertical surface and use it as a convenient holder for the OP7. The Remote cable (4) and the RJ45 female/female adapter (5) are supplied with the OP7. An additional remote cable (6) is required. CPU cable The OP7 mirrors the web contents of Xenta 711/731, and the simulated web contents of Xenta 701/721, as an enduser web is not provided in these models. XBuilder is used to program the Xenta 700. XBuilder will also mirror the contents of the Xenta 700 web for the TAC OP7. Signal viewer 2 Signal 1 value 1 °C Signal 2 value 2 ... Signal 3 value 3 unit 3 Signal 4 value 4 unit 4 Signal 5 value 5 °C value 6 unit 6 Signal 6 Force View 1. Remote (cabinet door) mounting Fix the Remote mounting kit (2) in a cabinet door cut-out. The optional hinged cover (3) will give added protection from IP 54 to IP 65. The Remote cable (4), supplied with the OP7, is used to connect the holder to the Xenta 700 adapter (fig. 2). 128.1 (5.0) Ø 3.6 (0.14) Ø 2.9 (0.11) 2 4 5 To Xenta 700 adapter 1a. TAC OP7 with a Remote (cabinet door) mounting kit Edit Figure 3 2. TAC OP7 with a Wall mounting kit and an additional cable 88.0 (3.5) Figure 2 2 3 1 6 The OP7 mirror of the web includes: 1 -- Value pages (figure 3) 3. Handheld terminal To use the OP7 as a handheld terminal you must have a cable (4 or 6) and an RJ45 female/female adapter (5), to connect it to: -- Alarm viewers -- Time Schedule viewers -- Trendlog viewers (figure 4) Additionally, the OP7 contains: 4 -- Additional Value pages, listing all System Variables -- the wall mounted holder. To Xenta 700 adapter 1b. Remote (cabinet door) mounting *) cut-out, and **) required area; mm (in.) YB = 6.9 1 2008-04-16 14:55:51 << >> More Figure 5:1 Figure 4 Copyright © 2008-2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. All rights reserved. 03-00072-02-en 35 (1.4) Mar 2010 For more information visit www.schneider-electric.com/buildings 4 or 6 28 (1.1) 16 (0.7) YA = 14.3 116 (4.6) 105 (4.1) A+B 3. TAC OP7 as a handheld terminal 5 16 (0.7) Trend log -- a Xenta 700 adapter (fig. 2) -- the remote (cabinet door) holder or -- Additional Value pages, listing all Variables -- Additional Value pages, listing all Xenta 400 I/O signals (for the root user only) Figure 5:2 * ** To Xenta 700 adapter or Remote/Wall mounting holder Figure 5:3