CHAPTER 2 COMPREHNSIVE REVIEW OF DIFFERENT BUSBAR PROTECTION SCHEMES 2.1 INTRODUCTION Modern electrical power system is spreaded over large geographical area with great complexity. Power quality requirements resulting from such great complex electrical network have motivated the improvement of fault location methods and development of protection scheme for busbar. Busbar is a vital, often overlooked, part of the power system. Even though faults on busbar are very rare, they can lead to disturbances & major shutdown of power system network. Thus, protection of busbar requires highly reliable, fast and high speed relaying scheme. With the fast changing technologies in the field of busbar protection, new protection concepts addressing new technologies are coming to the market. Therefore, there is an urgent need to keep track of different past and present relaying techniques, international standards, design and service experiences of digital/numerical relays and recent algorithmic developments taking place in the field of busbar protection. This chapter gives a bibliographical survey, comprehensive review of different busbar relaying schemes and conceptual aspect of research and developments in the field of busbar protection during the past 50 years, based on numerous published articles. Different busbar protection techniques have been studied and a comparative evaluation of them is undertaken with their relative advantages and disadvantages for identification of optimum technique as applied to specific bus configuration. 2.2 BUSBAR FAULTS AND PROTECTION REQUIREMENT Protection engineer try to implement a dedicated bus zone protection scheme from the various schemes developed by researchers. If it is not implemented perfectly, the clearing of bus fault will be performed by the backup protection provided to the lines terminating at the bus. The high fault levels associated with a busbar require fast protection. Typical fault clearing time should be less than 100 ms; with fast breakers, this means that the measuring time should be about 20 to 30ms. The prime requirement of the busbar protection scheme is the identification of fault in a particular region and disconnection of circuit breakers associated with that particular region so that healthy section of power system network remains unaffected. This 17 discriminating feature of the busbar protection scheme minimizes interruption of the plant. Hence, it is justified that discrimination on the basis of time graded relays is not a good choice, and hence, there is a need to develop genuine protection scheme for the busbar. Busbar protection scheme should not operate for any external (through) fault, as otherwise it unnecessarily trips other healthy lines connected to the bus. This is a very important feature of the busbar protection scheme with respect to the stability of the power system. It is to be noted that all these requirements cannot be achieved completely by any of the schemes without affecting the other requirements. Therefore, there is always a compromise between many factors such as speed versus selectivity and stability versus dependability. Whenever bus fault occurs, it results in severe disturbances as clearance of this fault requires tripping of all the breakers of the lines connected to the faulted bus. Moreover, the danger caused because of unprotected bus during bus fault is found to be very severe [110], [206]. Thus, in order to prevent hazard to the system, busbar protection scheme is designed and implemented in such a way that unwanted tripping should not occur. By involving bus sectionalizer and different bus arrangement, the number of circuits that must be opened for a bus fault is minimized and hence, eliminating total interruption of power [91]. Bus faults have been observed to be relatively rare around 8% of all faults compared with line faults which are over 60% [195], [10], [183]. It has been observed from the widely published literature that most of the bus faults are ground faults having 67% are single line to ground faults, 15% are double line to ground faults and 19% are triple line to ground faults [62]. Busbar faults can be broadly classified as: (i) Fault due to insulation failure caused from damaged CBs or insulators (ii) Arcing and insulator flashover caused by over voltages (iii) Faulty handling of switching equipments especially earthing switch (iv) Dropping off of metal parts across busbars Thus, the protection provided must possess the following characteristics (i) It is fast enough to minimize damage and maintain system stability (ii) It provides correct operation during an internal fault (iii) It maintains stability by avoiding maloperation in case of an external fault (iv) It supervises all CTs, which provides actuating quantity to the relay in case of fault 18 2.3 CLASSIFICATION OF BUSBAR PROTECTION SCHEMES The consolidated review of different techniques used by utilities along with their relative merits and shortcomings are presented here. These techniques are classified in three broad categories namely (i) Non-unit protection (ii) Unit protection and (iii) Commercial techniques Different techniques have been used by the utilities in order to detect faults on busbar in power system. The schemes categorized under unit protection are: (i) Directional comparison technique (ii) Differential protection technique and (iii) Techniques based on Artificial Intelligence (AI) Further, techniques used in commercial relay are sub-classified into five groups: (i) Microprocessor based scheme (ii) Digital differential scheme (iii) Nneural network based scheme (iv) Traveling-wave based scheme (v) Wavelet transform based scheme 2.3.1 Non-Unit Protection Scheme The non-unit protection scheme is governed by back-up over current, earth fault and distance relays. The high fault levels associated with busbars require that protection must be very fast. Typical fault clearing time should be less than 100 ms and with fast breakers it should be about 15 to 30 ms [38]. In order to minimize the interruption of the plant the protection system must correctly identify the area of the fault and open only the necessary and minimum number of breakers. However, because of speed requirements, these relays are usually found to be non-discriminative and slow in operation. Further, the vagrancy of the scheme applied to busbar protection can cause unnecessary tripping when relay spuriously trips thereby causing discontinuity of supply. In addition, it can cause havoc to equipment if back-up relays do not operate quickly. Hence, the philosophy of back-up 19 protection to clear busbar faults can be confined to radial system only. It is therefore preferable to have a clearly defined busbar protection scheme such as unit protection scheme which will be discussed in the next sub-section. 2.3.2 Unit Protection Scheme Unit protection scheme is a scheme that operates for a fault within its zone. Here, zone of protection is decided on the basis of current transformers (CTs), and it includes each and every fault point inside the CTs where measurement of currents is carried out. This type of protection scheme is widely used in busbar, generators, transformers, and large induction motors. Differential and directional comparison protection scheme is the best example of this type of protection scheme. 2.3.2.1 Directional Comparison When it is not economical to change out or add new current transformers then bus fault protection is achieved by directional comparison scheme using the existing line CTs. The main theme of this scheme is that if the power flow in one or more circuits is away from the bus, an external fault exists whereas for the power flow in all of the circuits into the bus, an internal bus fault exists [172]. This scheme is categorized in three parts namely Series Trip Directional Scheme, Directional Blocking Scheme and Directional Comparison Scheme. 1) Series Trip Directional Scheme: In this scheme all the directional relay trip contacts are connected in series. Figure 2.1(a) shows two directional relays R1 and R2 of line-1 and line-2 for bus protection. Figure 2.1(b) shows its control circuit in which the contacts of all line relays are connected in series. BUS + R1 - R2 Aux BUS P. T. CB-1 CT-1 R1 Line-2 AX2 A2 CT-2 R1 A1 TC CB-1 CB-2 Line-1 AX1 TC CB-2 (b) (a) A1 & A2 are mechanical switch, AX1 & AX2 are contacts of Aux relay TC CB is trip coil of circuit breaker Figure 2.1 Directional series trip scheme for busbar protection 20 In case of an internal fault, contacts R1 and R2 closes simultaneously and energizes the auxiliary relay (Aux) to trip both line circuit breakers. But the several disadvantages of this scheme are reduction in the reliability of the scheme due to too many series contacts, complex circuitry and requirement of careful and periodic review. 2) Directional Blocking Scheme: Figure 2.2 shows the control circuit of the directional blocking scheme for bus bar protection. The power circuit is same as shown in Figure 2.1(a). In this scheme, all the tripping contacts (R1 and R2) are connected in parallel and then to the tripping relay (Aux) whereas all the blocking contacts are connected in parallel and then to the blocking relay (B). During an external fault, the blocking relay (B) operates and blocks the operation of bus protection as per requirement by opening one of its contacts B-1, which is in series with auxiliary tripping relay. However, the main disadvantage of this scheme is its inapplicability in large cable network where the capacitance charging current is appreciable in comparison with minimum ground fault current. + - R1 B B-1 Aux R2 A1 AX1 TC CB-1 A2 AX2 TC CB-2 Figure 2.2 Directional blocking schemes for busbar protection 3) Directional Comparison Scheme: The problem of directional blocking scheme can be solved by this scheme which uses voltage restraint relay. But the main problem with all types of directional comparison scheme is that the relay settings must be reviewed and changed whenever system changes are made near the protected bus. 2.3.2.2 Differential Protection Comparison Protection of busbars is almost universally accomplished by differential protection scheme. In practice, this type of protection is mainly accomplished by different schemes such as Circulating Current Differential Protection Scheme, Biased Percentage 21 Differential Protection Scheme, High Impedance Voltage Scheme, Moderately High Impedance Scheme and Protection using Liner Couplers. Each of this method is discussed in details below. 1) Circulating Current Differential Protection: Figure 2.3 shows the concept of circulating current differential protection. This scheme operates on Kirchhoff’s current law i.e. current entering the substation bus equals to the vector sum of currents leaving the substation bus. But the main requirement of this scheme is that the CTs should be of the same ratio or matching CTs are required. However, the main drawback of this scheme is its maloperation because of production of error current due to CT saturation and also due to transient DC component. BUSBAR CB-2 CT-3 CB-3 CT-2 CT-1 CB-1 R Three Pole Relay Figure 2.3 Circulating current differential protection 2) Biased Percentage Differential Protection: In order to avoid the problem of maloperaration of relays due to CT saturation and transient DC current, biased differential protection scheme is used. Figure 2.4 shows connection logic and tripping characteristic of percentage biased differential protection scheme. BUS CT-1 CB-2 CT-2 Restraining Coil Operating Current (rms) CB-1 Tripping Zone Blocking Zone Restraint Current (rms) Operating Coil Figure 2.4 Percentage differential protection with percentage-bias characteristic 22 Application guideline for choosing a secure slope when applying percentage differential relay for bus protection is given in [132]. Maximum security for external faults is obtained when all CTs have the same ratio. The main advantages of this scheme are high tolerance against substantial CT saturation, reduced requirement of dedicated CTs and its use where comparatively high speed tripping is required. But the most important limitation of the said scheme is that the relay may maloperate in case of a close-in external fault due to complete saturation of CT. 3) High Impedance Voltage Scheme: To overcome the problem of spill current due to CT saturation in case of external fault, the high impedance voltage relaying scheme, as shown in Figure 2.5, is widely used. The effect of saturation is controlled by keeping CT secondary & lead resistance low & by adding resistance into relay circuit. Here, full wave bridge rectifier adds substantial resistance to that leg of circuit. The series L-C circuit is turned to 50 Hz fundamental frequency in order to respond only fundamental component of current and make over voltage relay immune to DC offset and harmonics. A dedicated IEEE standard was assigned as a guide for protective relay applications to power system buses [81], [43]. This scheme discriminates between internal and external faults by the relative magnitudes of the voltage across the differential junction points. The main merits of the said scheme are stability against transient DC component due to tuned circuit, improved CT saturation characteristics because of stabilizing resistors and faster operating time. This scheme, however, is not free from disadvantages. The most important ones are requirement of dedicated CTs (cost increases), maloperation of relay in case when the secondary leakage reactance is present and inapplicability of the scheme to re-configurable busbars. BUS CB-3 CT-3 CB-2 CT-2 CT-1 CB-1 C L Variable Resistor R Figure 2.5 High impedance bus differential protection 23 O/C Relay 4) Moderately High Impedance Scheme: This scheme is a combination of high impedance voltage relay and the percentage differential relay [178]. But the prime limitation of this scheme is that it requires special type of auxiliary transformer. 5) Protection Using Linear Couplers: Problem of CT saturation in case of iron core CT is rectified using linear couplers (air core mutual reactors) as they use air core. The secondary of all linear couplers are connected in series as shown in Figure 2.6. The output voltage of linear coupler is proportional to the derivative of the input current. If the voltage sum across relay is zero then input current is equal to output current at bus. During an internal fault, all line current flows toward bus and thus the induced voltage appears across the relay. Linear coupler is a special device which requires low energy relay. This may create problems with change in bus configuration. However, the need of extra equipments in order to achieve benefits of microprocessor based relays and high cost are the main drawbacks of this scheme [148]. BUS CB-3 LC3 CB-2 LC2 LC1 CB-1 R Voltage Differential Relay LC – Linear Coupler Figure 2.6 Bus protection relay with linear coupler 2.3.3 Techniques used in Commercial Relay and their Problems Digital/Numerical relays provide significant benefits for industrial as well as commercial systems where an economical but effective busbar protection scheme is required. These techniques are increasingly being applied to major power system networks and continuously improving power system operation [156], [129], [120], [37]. Further, they provide many advantages such as reduction in lifetime management costs, maintenance cost and also have the ability to extend the protection to cater for primary system changes with minimal hardware alterations and transmission system changes [95], [1]. The first numerical busbar protection system was commissioned in 1989. Thereafter, 24 up to the end of 2012, about 500 systems are in operation world-wide with different busbar configurations [179], [75], [158]. The common practice in busbar protection is to use numerical busbar protection scheme which provides complete protection for all types of extra/ultra high voltage bus configurations. The commercially available relays use innovative techniques such as CT saturation detection in less than 2 ms and dynamic topology processing algorithms which provides a unique combination of security, speed (operating time is 15 ms) and sensitivity [150], [36]. At the same time with regard to the protection of busbars, the reliability and the dependability are the most important parameters [81], [5]. Moreover, increased in-plant generations heighten the requirement for fast fault clearing which is required to maintain generator stability [33]. On the other hand, busbar protection shows a bad track, when comparing the number of times that it has shown an incorrect tripping (security) in comparison with the number of times that it has operated correctly (dependability) [6], [93]. Considerations in applying bus protection schemes to industrial and independent power producer are explained in [157]. Later, Brewis et al, [98] described busbar protection scheme based on instantaneous elements contained in numeric overcurrent relays and discussed design issues for busbar protection. But the failure of instantaneous blocking element in case of external fault is the prime limitation of the proposed scheme. 2.4 METHODOLOGIES AND COMPARATIVE ANALYSIS During the last two decade, remarkable success has been achieved in the field of microprocessor as well as digital/numerical based relaying schemes. Many digital busbar relaying schemes have been developed by researchers using microprocessors, microcontrollers, digital signal processors and employing various artificial intelligence techniques [34], [41]. These are explained in the following sub-sections. 2.4.1 Microprocessor based Busbar Protection Scheme The block diagram of a typical microprocessor-based relay is shown in Figure 2.7. The relay has five major components namely analog input system, digital input system, digital output system, microprocessor unit and storage unit. 25 Power System Network CT and PT Analog Input System Digital Input System Digital Output System Microprocessor Based Central Processing Unit Relay Logic Storage Unit Power Supply Figure 2.7 Block diagram of microprocessor based relay Analog input system contains signal conditioning devices, analog to digital converter and filtering circuit. It acquires analog signal (voltages and currents) from the power system network and convert into digital form. Digital input system acquires data such as breaker status, isolator status, etc. and provide to the microprocessor unit in digital form. Digital output system contains digital to analog converter. Storage unit contains Random Access Memory (RAM), Read Only Memory (ROM) and hard disc storage for permanent and temporary storage of data. Microprocessor unit samples the data according to the relay logic and takes decision accordingly. With the advent of digital technology, researchers and designers have made remarkable progress in the development of different microprocessor- based algorithms. Kennedy and his colleague [104] proposed a differential relay for busbar protection based on harmonic current restraint principle. However, the prime limitation of this scheme is inhibition of relay operation if the content of harmonics in the differential relay exceeds the threshold value. Later on Andow and his colleagues [54] presented a low impedance busbar protection scheme which stabilizes relay performance during CT saturation. However, the significant disadvantage of this scheme is the inhibition of the relay operation during CT saturation for a predetermined period. Royle et al. [85] and Wheatley [93] described a solid-state busbar protection scheme which uses electronic circuits to identify saturated CTs. But the main drawback of the said schemes is that the differential relay may not pick-up when electronic circuits bypass the operating coil of the relay for same portion of the cycle in which the output of a CT is distorted due to saturation. Peck et al. [49] proposed a new numerical busbar protection scheme using bay units which are 26 located close to the switchgear. The foremost feature of this scheme is that it adjusts characteristic and restraint factor in order to achieve stability during CT saturation on the occurrence of heavy through faults. Conversely, delayed operation in case of CT saturation during an internal fault is the fundamental constraint of the above scheme. Liu Pei et al. [108] suggested an adaptive busbar protection scheme which incorporates differential current protection and breaker protection. This scheme accommodates bus structure change and correctly determines new summations of currents. But when the currents on the two feeders are same then the separate auxiliary contacts of isolators are required. Kumar et al. [5] described a differential scheme based on multiprocessing. This scheme operates with a countermeasure for CT saturation and gives stability against external fault. But the main drawback of this scheme is that it provides delayed operation in case of in-zone faults. Furthermore, to achieve fast response in case of internal faults, a modified scheme has been described which issues a trip signal immediately if the initial trip decision occurs within a few milliseconds of fault occurrence [205]. However, the main disadvantage of this scheme is the assumption that for a worst-case internal fault, none of the CTs will saturate during the first few milliseconds. Thereafter, Kasztenny et al. [27] proposed a combine busbar protection scheme based on differential and directional operating principles. This scheme uses duel slop operating characteristic having low and high slop regions. Usage of differential and directional elements increases security of the relay. However, the higher operating time of relay during CT saturation on an internal fault is the prime limitation of this scheme. 2.4.2 Digital Differential Protection Scheme Digital differential relaying schemes are based on two distinctive architectures: (i) Distributed busbar protection scheme, as shown in Figure 2.8(a), which uses Data Acquisition Units (DAUs) installed in each bay to sample and pre-processes the signals and provides trip rated output contacts. It uses a separate Central Unit (CU) for gathering and processing all the information and fiber-optic communications between the CU and DAUs to deliver the data. The main advantages of this scheme is reduced wiring, however the architecture of this scheme is less reliable due to complexity in data transfer. (ii) Centralized busbar protection scheme, as shown in Figure 2.8(b), requires to wire all the signals to a central location, where a single “relay” performs all the functions. The wiring cannot be reduced and the calculations cannot be 27 distributed between a numbers of existing DAUs imposing more computational demand for the central unit. On the other hand, this architecture is perceived more reliable and suits better retrofit applications. BUS CB CT CB CT DAU CT DAU CT DAU CB CB CB CT CT CB CU (a) Copper Fiber CU (b) Figure 2.8 Block diagram of digital differential relay Fast tripping which is an essential requirement in case of busbar faults can be achieved primarily by low/high impedance differential protection schemes [14], [78]. Till now, high impedance differential protection scheme is widely used due to its low cost and simple arrangement. However, the above scheme has several disadvantages such as requirement of dedicated CTs, high cost due to additional switchgears and unavailability of numerical protection technology [121]. On the other hand, low impedance differential protection scheme inherits all the features of digital/numerical protection technology and can also be applied to different complex busbar arrangements. Kasztenny and his colleagues [29], [28] proposed low impedance differential protection scheme that combines percentage differential and current directional protection principles within a frame of an adaptive algorithm controlled by a dedicated CT saturation detection module. However, need of large number of inputs and outputs and processing power requirements are the major shortcomings of the said scheme. These problems can be solved by using distributed or centralized architectures [66]. But the requirement of large quantities of specialized hardware is the main weakness of this scheme. Thereafter, a concept of phase-segregated low impedance digital protection schemes for medium and large voltage busbars have been proposed in 2001-2002 [26], [76]. This concept has many benefits such as low cost, initial maturity and simplicity. Jiali and his colleagues [77] presented a protection scheme based on distributed principle. This scheme has distinguishing advantages over the traditional centralized principle such as enhancement in adaptability using the information of the whole power 28 system and reduction in the possibility of a serious blackout of the whole bus due to maloperation of the busbar protection scheme. However, the main weakness of the above scheme is the possibility of maloperation in case of severe CT saturation. Wong et al. [165] described a multi agent system which integrates case based and object oriented based approaches in the development of a distributed intelligent system. Thereafter, B-AlFakhari and his colleague [19] proposed a differential protection scheme for busbar and transformer using incremental currents. But the prime limitation of this scheme is that if CT saturation occurs in the first one or two cycles with an external fault then incremental currents are not sufficient. Hence, operating quantity exceeds restraining quantity and relay maloperates. 2.4.3 Performance of Busbar Protection Scheme during CT Saturation and Ratio Mismatch The iron core CTs are widely used in the electric power system for the protection of busbar. These types of CTs are not linear transducers due to the characteristics of the iron core. Different levels of saturation occur in almost all CTs depending on the magnitude of the fault current being measured. Figure 2.9 shows a block diagram of CT saturation. The secondary current I2, transformed from the primary current I1 by a CT, is sampled into a discrete-time sequence of values, i2(t), by a data-acquisition module. If a sample of i2(t) is determined within a saturation portion of the fault current waveform by the CT saturation detection scheme, a compensated sample will be generated by a compensation algorithm. Finally, the compensated currents are supplied to protective relays. The distorted secondary current can be compensated based on the detection of the CT saturation period [71]. CT i2(t) Current Sample CT Saturation Normal Detection CT Saturation Compensation Protective Relay Compensated Current Secondary Current (I2) Data Acquisition (A/D) Saturated Primary Current Figure 2.9 Real-time detection and compensation of CT saturation 29 The main requirement of busbar protection scheme is to remain stable during CT saturation [41], [212], [50]. Different researchers have proposed different busbar protection techniques to improve their performance during CT saturation and different CT ratio. Sachdev and his associates [127], [72] presented a busbar protection scheme which estimates the impedances of the positive and the negative sequence circuits in order to distinguish faults outside the bus protection zone from faults inside the protection zone. This technique is stable during CT saturation and not affected by CT ratio-mismatch. But the main disadvantage of this technique is that it requires voltage information which is not always available in bus protection applications. Thereafter, Eissa [118] proposed phase comparison based busbar protection scheme. The above two schemes are based on phase angle comparison and provide improved results in case of CT saturation and CT ratio mismatch than the algorithms based on magnitude comparison. However, the prime limitation of the above two techniques is the delayed operation in case of severe CT saturation. Kang and his colleagues [203], [202] presented a CT saturation detection algorithm based on the detection of start and end of each saturation period using a third difference function applied to the secondary current signal. The above two schemes ensure stability in case of external fault with CT saturation. However, the main drawback of the said two schemes is the difficulty in case of a progressive fault as the second fault may be detected as the saturation start or end. Guzman and his co-workers [16] proposed a reliable busbar protection scheme with advanced zone selection that is secure for external faults with heavy CT saturation. But the fundamental demerit of the above scheme is that the relay requires primary CTs that reproduce the primary current without saturation for at least 2 ms after the inception of external fault. In order to further improve the performance of the busbar protection scheme, Kang and his colleagues [204], [205], [201] suggested a compensating algorithm for the distorted current signal of a saturated CT. This scheme is unaffected by CT saturation and successfully operates even for a progressive fault from a feeder fault to a busbar fault. However, the stability of the proposed scheme cannot be guaranteed during severe CT saturation and it is also affected by CT error and CT ratio mismatch. 2.4.4 Neural Network Based Busbar Protection Scheme Artificial Neural Networks (ANN) are biologically inspired and consist of elements that are organized in way that may be related to the anatomy of the human brain. These 30 elements called neurons are capable of realizing basic logic functions. The unique feature of ANN structure can be used to estimate any continuous function. Figure 2.10 shows the block diagram of Artificial Neural Network (ANN) based differential relaying scheme for busbar protection. Current samples in secondary form, acquired from the power system network are given as an input to Analog to Digital Converter (ADC) through Signal Conditioning (SC) and Anti Aliasing Filter (AAF) block. AAF is a low pass filter and used to remove high frequency signals. The differential current signals are given as an input to ANN block. Depending upon nonlinearity in the input signal, the structure of ANN can be decided. Generally, the structure of ANN contains input layer, output layer and two or three hidden layers. The output of ANN is given to decision logic block, which gives tripping or blocking signal. Power System Network CT Units Id AAF SC ADC ANN Decision Logic Trip Figure 2.10 Block diagram of ANN based busbar protection scheme In the last two decades, the use of ANN for solving problems in power system is rapidly increasing [189]. Feser and his colleague described [100] ANN based busbar protection scheme in which a neural network is used for preprocessing the data and restoring the distorted signals. This work is further extended on a larger data base with an increased network size [187]. But the CT error and CT ratio-mismatch can still cause the maloperation of the proposed scheme. Thereafter, Zadeh and his co-worker [122], [69] proposed Fuzzy Neuro based pattern classifier scheme which distinguishes faults in a busbar protection zone from those outside the zone. The main advantage of the above scheme is the stability during CT saturation. But, large training sets, tedious training process, and a large number of neurons are the several disadvantages of the neural network based schemes. Moreover, another significant weakness of neural-network-based algorithms is that the training may not converge in some cases, as the starting point is chosen randomly and can end up in a local minimum. This is quite common, particularly in the case of retraining the neural network with new data associated with, for example, contingencies that may not converge to the desired value. When the learning gets stuck on local minima, the requisite performance can never be reached. Thus, the neural networks still remain black boxes and lack transparency [181]. 31 2.4.5 Travelling-Wave Based Busbar Protection The travelling wave based protection scheme measures the relative time of arrival of the travelling wavefront produced by the fault. The traveling wave detection system consists of Capacitive Coupling Voltage Transformer (CCVT), Fault Transient Interface Unit (FTIU), Global Positioning System (GPS) receiver with event storage and master station with software. Based on this logic, researchers have given different schemes which are summarized below. Wang and his co-workers [61] presented a busbar protection scheme based on polarities of transient current waves for identification of the in-zone or out of zone faults. Jiang and his colleagues [56] proposed Transient Based Protection (TBP) technique which depends on energy spectrum of fault transient. Subsequently, Chen and his co-workers [210] described busbar protection scheme based on wavelet analysis which works on fault generated transient current signals. Afterwards, Eissa [117] proposed a directional technique based on a combined signal derived from pre-fault voltage and post fault current signals. Subsequently, Xiang-ning et al. [199] presented directional relaying scheme for the protection of transmission line and busbar based on the polarity comparison of the current traveling waves. However, when a fault occurs at a voltage inception angle close to zero degrees, it does not generate significant traveling wave components. In addition, the bandwidth limitation of the transducers, particularly the CVT, limits the applicability of such techniques, particularly for close-up faults, which generates very-high-frequency traveling waves that are outside the bandwidth of receptibility of conventional CVTs [21]. 2.4.6 Wavelet Transform Based Busbar Protection Scheme Figure 2.11 shows the block diagram of Wavelet Packet Transform (WPT) based differential relaying scheme for busbar protection. Current samples, in secondary form, are received from the power system network. Thereafter, they are given as an input to Analog to Digital Converter (ADC) through Anti Aliasing Filter (AAF) and Signal Conditioning (SC) device. Afterwards wavelet packet transform block decomposes the differential current signal of the respective phase into detail and approximation coefficients. These coefficients are used in relay logic block for final decision about internal and external fault. 32 CT Id AAF SC ADC Decomposition of different current Using WPT Relay Logic Fault Classification Trip Figure 2.11 Block diagram of wavelet based busbar protection scheme Digital protective relaying of transmission lines has been greatly benefited from the development of artificial intelligence and signal processing techniques [154]. Fernandez et al. [160] presented an overview of the wavelet transform applications in a power system, which indicates that the use of wavelet transform in power system protection is increasing day-by-day. Eissa [118] presented busbar protection scheme which uses Continuous Wavelet Transform (CWT) in order to derive operating and restraining quantities. Soon after, Mohammed [112] described differential busbar protection technique using Wavelet Packet Transform. However, the above two schemes may maloperate in case of varying load conditions. Thereafter, Valsan et al. [169] presented a new busbar protection technique based on directional signal which is derived as the product of high frequency details of branch currents and bus voltage using a Wavelet transform approach. But the main disadvantage of this technique is that it requires voltage information which is not always available in bus protection applications. 2.5 CONCLUSION In this chapter an attempt is made to review most of the existing schemes of busbar in power system networks. The chapter also covers the concepts of the different protection schemes of busbars, with a bibliographical survey of relevant background, practical requirements, the historical events, the present state and techniques. Comparative evaluation of different techniques is also undertaken for identification of optimum technique as required by specific application. The citations listed in this bibliography provide a representative sample of current engineering thinking pertaining to next generation busbar protection problem. This chapter is based on many research articles published in the last 50 years and periodic bibliographic updates on this topic will be useful as the restructuring of power system network continues to evolve. Although, 33 numbers of busbar protection schemes have been proposed so far there exists a lot of scope for further improvement especially on the effective discrimination between in-zone and out of zone fault. A clear consensus is presently heading towards SVM and other AI based digital busbar protection scheme and can handle the present day complex busbar protection problem. 34