SECTION 10 BUILDING SPECIFICATIONS 10.1 10.1.1 CONCRETE Tolerance Floor and roof slabs shall be level to a point within ± 5 mm of the level shown on the drawings. Columns and beams shall have no irregularities exceeding 3 mm in a 3m length. The position of the face of columns, beams and walls at any point shall be within 5 mm of its position derived from the drawings. 10.1.2 Concrete Finish All exposed concrete beams, columns and slab surface described as fair-faced shall be Type f.f. as follows:Type f.f. shall be an as struck finish entirely free from honeycombing, stains, pins, clippings, lining joint marks, nail and screw marks, raised grain marks, air holes and surface defects and shall be uniform in colour tone and surface texture with clean true faces and arises. 10.1.3 Construction Bays The Contractor shall submit to the Engineer for his approval prior to concreting his proposals for the sequence of placing concrete and the position of horizontal and vertical construction joints. 10.1.4 Small Precast Items Small precast items such as lintels, sills and padstones shall be built in as the work proceeds and have a fair-faced Type f.f. finish where exposed to view and hacked surfaces where plastered. Lintels shall have a minimum bearing of 100 mm or larger if indicated on the drawings and shall have inserts for fixing windows and/or doors cast-in. Sills shall be weathered and have a throat as described, if projecting, and shall have inserts for fixing windows and/or doors cast-in. 10.1.5 Cast-in Fixings Cast-in fixings shall be securely fixed to formwork ready for casting and shall be true to line in the positions shown on the drawings. 10/1 SECTION 10 BUILDING SPECIFICATIONS 10.1.6 Timber Cast-in Fixings Timber cast-in fixings shall be made from 38 mm x 38 mm dovetailed shaped softwood battens pressure impregnated with preservative. 10.2 BRICKWORK AND BLOCKWORK 10.2.1 Damp-Proof Course Horizontal and vertical damp-proof courses shall be hessian based lead cored bituminous damp-proof course weighing not less than 4.4 kg/m2 to accepted standards and approved by the Engineer. Horizontal damp-proof courses shall be laid on an even level bed of fresh mortar and shall be lapped for the full width of the sheet at corners and junctions. Stepped damp-proof courses shall be wide enough to be built in to both skins of the wall and to cross the cavity in one piece. Vertical damp-proof courses shall be continuous and shall be the width of the block closing the reveal. Damp-proof courses shall not be bridged with mortar. 10.2.2 Wall Ties Wall ties shall be 18/8 stainless steel vertical twist type 200 mm long. Wall ties shall be built in the mortar beds as the work proceeds and shall be spaced at a maximum of 900 mm horizontally and 450 mm vertically and shall be staggered. Each door and window opening shall have wall ties at each joint at 225 mm centres vertically. 10.2.3 Door and Window Frame Ties As described for Joinery Fixing Accessories. Door and window frame ties shall be fixed as described under Joinery Work. 10.2.4 Mastic Mastic for pointing door and window frames shall be one part gun-grade polysulphide mastic to accepted standards and approved by the Engineer. 10/2 SECTION 10 BUILDING SPECIFICATIONS Mastic seals to windows or door frames shall be neatly gun applied to clean, solid and dry backgrounds in one operation. The mastic shall be a triangular seal across the whole joint and any surplus shall be cleaned off when set. 10.2.5 Brickwork and Blockwork Brickwork and blockwork shall be as specified in Section 5. 10.2.6 Cement Mortar Cement Mortar shall be as specified in Section 5. 10.2.7 Pointing All pointing shall be done as the work proceeds and shall be flush with face of blockwork. 10.2.8 Hollow Walls Hollow walls shall be constructed with an outer skin of blockwork and an inner skin of blockwork leaving a cavity of the widths shown. The two walls shall be tied together with wall ties as described and the cavity shall be kept and left clear of all droppings. Openings shall be left at intervals in the blockwork at the bottom of the cavities and all debris shall be cleared out and the openings bricked up on completion. Cavities shall be closed at opening reveals with either brick or block to match the surrounding material and a continuous vertical damp-proof course shall be built in. 10.3 ROOFING 10.3.1 Roof Screed Roof screed shall be laid to fall over the concrete roof slab and have a minimum thickness of 35 mm and maximum thickness of 75 mm. The screed shall be thoroughly mixed 1:4 cement/sharp sand mix with very little water added. The screed shall be laid and compacted and shall be levelled off and finished with a steel trowel. Precautions must be taken to prevent rapid or excessive drying out. 10.3.2 Roof Primer Primer for concrete shall be suitable for use with the waterproofing membrane and shall be applied in accordance with the manufacturer's instructions. 10/3 SECTION 10 BUILDING SPECIFICATIONS 10.3.3 Waterproofing Membrane Flexible waterproofing membrane for roofing shall be bitumen based to accepted standards and approved by the Engineer. Surfaces to receive the membrane shall be smooth, dry and free from dust. The membrane shall be laid on a primed surface and in accordance with the manufacturer's recommendations. 10.3.4 Roof Insulation Roof insulation shall be 75 mm thick closed cell non-absorbent rigid polystyrene insulation board. The insulation boards shall be placed immediately after the membrane has been laid. 10.3.5 Roof Surface Roof surface shall be 50 mm thick 450 mm x 450 mm precast concrete paving slabs laid dry. 10.3.6 Roof Decking The roof decking shall be aluminium profiled sandwich sheeting fixed to Metsec ‘Z’ section purlins all in accordance with the manufacturer’s instructions. The Contractor shall provide working drawings and manufacturer’s literature for approval before ordering the same. 10.3.7 Fascia Cladding The fascia cladding shall be of single skin construction formed from profiled aluminium sheeting with matching aluminium profiled flashings. The Contractor shall provide working drawings and manufacturer’s literature for approval before ordering the same. 10.4 JOINERY 10.4.1 Timber-General Timber for joinery shall be air dried and the moisture content be allowed to reduce until it reaches a level in equilibrium with local conditions. It will be deemed to have reached equilibrium when the moisture content is 12% + 2%. 10/4 SECTION 10 BUILDING SPECIFICATIONS 10.4.2 Timber Sizes Timber shall be 3 mm less per wrought or finished face than the sawn size. 10.4.3 Hardwood Hardwood for joinery shall be sound, well conditioned and seasoned Mahogany 3 or Meranti with an average density of 529 Kg/m and a moisture content of 12% + 2%. Exposed surfaces of joinery shall comply with the following requirements. Knots Checks & Shakes : : Pitch Pockets Plugs and Inserts : : Pin knots up to 6 mm diameter will be permitted. Checks up to 3 mm width and 300 mm long will be permitted. Not permitted unless cut out and filled. Not permitted. Joints and Lamination Glue Lines Rate of Growth : : Slope of Grain : Species & Character : Pinholes : Not permitted. Not fewer that 8 growth rings per 25 mm at any point on any cross section. Not greater than 1 in 8. Same on all surfaces and matched as far as possible. Permitted if filled. A sample of each representative section for use in the work shall be previously submitted for approval by the Engineer's Representative. 10.4.4 Timber Fixing Accessories Nails for fixing joinery shall be aluminium or sheradised mild steel. Screws for fixing joinery shall be sheradised mild steel. Bolts shall be stainless steel. Adhesives for exterior use shall be synthetic resin types, weather and boil-proof, complying with the approved standard. Adhesives for interior use shall be synthetic resin types, moisture resistant and moderately weather resistant, complying with the approved standard. 10/5 SECTION 10 BUILDING SPECIFICATIONS Door frame and lining fixing cramps shall be of 25 mm wide x 14 swg thick x 250 mm girth stainless steel, one end turned up 50 mm and twice drilled and the end fishtailed for building-in. Dowels for fixing door frames shall be 10 mm dia. x 100 mm long stainless steel. 10.4.5 Timber Preservative Timber preservative shall be water repellent and protect the timber from all wood destroying fungi and insects particularly termites. The preservative shall be applied in accordance with the manufacturer's instructions including treatment to all ends, notches and joints in treated timber out on site. 10.4.6 Ironmongery Ironmongery shall be as shown on the drawings. 10.4.7 Workmanship All exposed faces of joiners work shall have wrought faces. All arises shall be rounded to a 1.5 mm minimum radius unless specified or drawn to a greater radius. Where the term 'framing or framed' is used it shall mean all halvings, dovetails, tenons and hardwood pins and the best known means of putting this work together. 10.4.8 Storage All joinery shall be protected from the weather during transit and shall be stored under cover, clear of the ground in clean, dry ventilated conditions so as to maintain the specified moisture content. All framework shall be put together loosely and stored as described and shall not be wedged and glued together until required for fixing. 10.4.9 Door Frames External door frames shall be built-in as work proceeds with fixing cramps as described. The fixing cramps shall be screwed to the back of the frames at 450 mm maximum centres with two sheradised screws 25 mm long. The fishtail ends 10/6 SECTION 10 BUILDING SPECIFICATIONS shall be built-in to the brickwork or blockwork mortar joints as the work proceeds. 10.4.10 Doors External doors shall be hung on one and a half pairs of hinges unless otherwise detailed, to give a maximum tolerance all round of 2 mm. 10.5 METALWORK 10.5.1 Aluminium Aluminium alloy sections for aluminium shall be type H59 TF box sections. 10.5.2 Aluminium Louvers Aluminium louvers shall be made from NS 4 H3 aluminium and have a natural or bronze anodised finish. Sizes to be as shown on the drawings. 10.5.3 Aluminium Windows Aluminium windows shall be manufactured by an approved specialist window manufacturer from extruded aluminium sections mechanically cleated and sealed. Glazing to be fixed into opening with clip on aluminium beads and gasket sealed. Finish to windows to be natural anodised 25 microns in thickness. Windows are to be fixed into openings with stainless steel screws and sealed all round in mastic bedding. 10.5.4 Ironmongery Rates for supplying and fixing ironmongery shall include for all boring, cutting, mortising, sinking, making good, replacing damaged screws, oiling, adjusting, leaving in good working order and mastering all locks. Screws shall be of suitable gauge and material for the purpose and shall match the item to be fixed. 10.6 PLUMBING 10.6.1 Copper Tubes 10/7 SECTION 10 BUILDING SPECIFICATIONS Copper tubes shall be half hard copper tube of accepted standard approved by the Engineer. 10.6.2 Copper Fittings, Waste Pipes, Ball Valves etc. All fittings shall be of an accepted standard approved by the Engineer and as described on the drawings. 10.6.3 uPVC Pressure Pipes and Fittings uPVC pressure pipes and fittings for water supply shall be of an accepted standard approved by the Engineer. 10.6.4 Workmanship The plumbing installation shall be carried out to the satisfaction and in accordance with the Acts and By-laws of the Dubai Electricity and Water Authority. 10.6.5 Pipework All pipework shall be neatly executed in long lengths to avoid unnecessary jointing. Horizontal pipes shall be fixed with a slight fall to prevent airlocks and to enable the system to be easily drained down. 10.6.6 Copper Tube Fixing Copper tube shall be fixed clear of walls and ceilings with two piece copper spacing clips or with proprietary plastic pipe clips. Clips shall be at 1.20m horizontally and 1.50m vertically for 15mm diameter pipes and at 1.80m and 2.40m respectively for 22mm and 28mm diameter pipes. Capillary joints shall be neatly made with all surplus solder removed. Screw threads on compression joints shall be wrapped with PTFE tape prior to tightening. 10.6.7 Waste Pipes uPVC waste pipes for sinks and urinals shall be fixed and jointed in accordance with the manufacturer's instructions. Fixing clips shall be at 0.50m horizontally and 1.20 m vertically and joints shall be by 'O' rings, seals or solvent cement. Care shall be taken to allow for expansion in accordance with manufacturer's instructions. 10/8 SECTION 10 BUILDING SPECIFICATIONS 10.6.8 Sleeves uPVC sleeves shall be provided through walls and ceilings for pipes and shall be internally 3 mm minimum larger than the pipes. 10.6.9 Testing Soil and waste pipes shall be air tested for leaks to a pressure of 38 mm water gauge, constant for three minutes. Rainwater pipes shall be tested for leaks as above and gutters shall be tested by filling with water to overflow level. Testing shall be undertaken to hidden sections of pipework before they are built-in. All leaks found shall be rectified and retested. 10.6.10 Storage Tanks GRP cold water storage tanks shall be placed on 2 nos. galvanised mild steel brackets bolted to the wall. 10.7 PLASTERWORK & OTHER WALL, FLOOR & CEILING FINISHES 10.7.1 Cement 10.7.2 Cement shall be Portland Cement as described in Section 3. Lime Lime shall be the hydrated type to the approved standard. 10.7.3 Sand Sand for plasterwork with gypsum plasters shall be suitable for use with the brand of gypsum plaster used. Sand for rendering, internally and externally, and floor screeds shall comply with Clause 5.1.3. 10.7.4 Gypsum Plasters Gypsum plaster shall be of an accepted standard approved by the Engineer. 10/9 SECTION 10 BUILDING SPECIFICATIONS 10.7.5 Plaster Trims Metal angle beads and plaster stops for plasterwork and plasterboard shall be manufactured from galvanised mild steel. 10.7.6 Metal Lathing Metal lathing shall be manufactured from galvanised mild steel having a minimum shortway aperture of 6 mm. 10.7.7 Plasticizers Plasticizers shall be an approved vinyl resin type and used in the manner and proportions recommended by the manufacturer. 10.7.8 Bonding Agents Bonding agents generally shall be an approved polyvinyl acetate (PVA) type and used in the manner and proportions recommended by the manufacturer. 10.7.9 Storage Plaster shall be stored in a building in dry condition on timber platforms and shall be used within two months of manufacture. Plasterboards shall be stored in a building in dry condition and shall be laid flat and stacked on a sheet of polythene. 10.7.10 Floor Tiles Vitrified and fully vitrified floor tiles shall be as detailed on the drawings. Floor tiling shall be laid with a proprietary tile adhesive (approved by the Engineer) either directly onto a clean, dry and level concrete sub-floor, or on a cement/sand screed laid over the sub-floor. The sub-floor surface shall be scabbled to remove all surface laitance prior to tiling or screeding. The screed shall be mixed semi-dry by hand or in a pan mixer and shall be a 1:4 cement/sharp sand mix with just enough water to enable it to hold together when squeezed in the hand. The sub-floor shall be kept damp for 24 hours and the screed shall be laid and well compacted to a thickness of 56mm and brought to the required levels using a draw float. The finished floor screed shall be kept damp for a period of 7 days prior to commencement of tiling. The tile adhesive shall be spread evenly by steel trowel to a thickness of 3mm onto which the clean, 10/10 SECTION 10 BUILDING SPECIFICATIONS dry tiles shall be laid to give a 3mm minimum joint width. The tiles shall be grouted with a proprietary and approved tile grout within a minimum period of 24 hours after laying. 10.7.11 Wall Tiles (Internal) Coloured wall tiles shall be 152 x 152 x 5.5mm thick glazed tiles approved by the Engineer. 10.7.12 Wall Tiles (External) External wall tiles shall be as detailed on the drawings. The concrete surface to receive tiling shall be prepared as follows :1) Concrete surface to be 100% keyed by either bush hammering, hacking or water scabbling of smooth surface. 2) Concrete surface shall be thoroughly moistened and a concrete slurry mix of one part cement to two parts of medium sharp sand applied as splatterdash thrown onto concrete surface. 3) While the surface is wet apply 1:3.5 mix sand/cement render to a thickness of 12mm in two coats to a plumb and level finish and with wood float finish. The completed rendering is to be protected and allowed to dry slowly with damping as necessary. After curing, the surface is to be allowed to dry completely before the fixing of tiles. Tiles shall be fixed with proprietary tile adhesive (approved by the Engineer). The tiles are to be bedded strictly in accordance with the manufacturer's instructions with 10mm joints between tiles. At least 24 hours after fixing tiles are to be jointed using approved mortar. Movement joints are to be formed between tiles in positions shown on the drawings to the full depth of the tiles, bedding and render. Joints are to be 10mm wide and are to be filled to within 8mm of surface with inert filler and finished with 2 part polysulphide pointing in colour to match tile jointing. 10.7.13 Tile Adhesive 10/11 SECTION 10 BUILDING SPECIFICATIONS Tile adhesive for floor and wall tiling shall be as recommended by the Tile Manufacturer and used in accordance with the adhesive manufacturer's instructions. 10.7.14 Tile Grout Tile grout for floor or wall tiles shall be as recommended by the manufacturers of the ceramic tiles and used in accordance with the manufacturer's instructions. 10.7.15 Expansion Joints Expansion joints in floor and wall tiling shall be 6.5 mm wide Polyethylene backing strip with 6.5 mm wide approved silicone sealant, gun applied on the face in accordance with the manufacturer's instructions. Expansion joints in floor tiling shall be at 6 m maximum centres in both directions and around the perimeter of rooms, over structural joints and around machine bases and holes in the floor. The joints shall be the full depth of the floor tiles, bedding and screed x 6.5 mm minimum width. The joints shall be primed with two coats of approved primer and when dry, filled up to within 6 mm of the tile finish with polyethylene compressible foam strip. An approved joint sealant shall then be gun applied and tooled to a slightly concave smooth even finish. 10.7.16 Backgrounds All backgrounds shall be clean, dry, free from efflorescence, paint, oil and dust and adequately prepared to provide a good key. All loose, flaking and unsound material shall be completely removed and all mortar joints shall be raked out, if required, to a minimum depth of 10 mm. Concrete surfaces shall be well wetted five minutes prior to plastering or rendering. 10.7.17 Dissimilar Materials Joints between dissimilar materials such as blockwork and concrete shall be covered with a 300 mm wide continuous strip of expanded metal lathing fixed to both sides with masonry nails or plugs and screws at 200 mm centres. 10.7.18 Hacking Concrete surfaces shall be well hacked to expose the aggregate thus providing a firm coarse textured background. 10/12 SECTION 10 BUILDING SPECIFICATIONS 10.7.19 Dubbing Out Dubbing out of all areas to receive plaster or render shall be in the same mix as the subsequent coat, not exceeding 10 mm thickness in one application, and shall be allowed to harden. 10.7.20 Splatterdash or Stipple Coat Splatterdash or stipple coats shall consist of 1:1.5 cement/sharp sand mixed with 50% water/50% PVA bonding agent to form a thick slurry. The mixture shall be vigorously brushed onto the background and stippled to give a close textured key. The resulting finish shall be kept damp to prevent rapid drying out and allowed to harden for seven days minimum before subsequent coats are applied. 10.7.21 Internal Finishes-General All internal finishes shall not commence until the building is watertight, including glazing, and reasonably dried out. 10.7.22 Internal Render Internal render shall be applied to concrete blocks as follows :The render shall be two coat work comprising a stipple coat as described previously and a finishing coat giving a maximum thickness of 12 mm. The mix shall be in the proportion 1:1:6 cement/lime/sand. The render shall be kept damp for a minimum of three days. All window and door openings must be closed to prevent through draughts causing rapid drying out. 10.7.23 Stucco A PVA copolymer based putty for concrete and plaster shall be applied, in accordance with the manufacturer's instructions, to the surface of the internal render after curing has taken place. The stucco shall only be applied in sufficient thickness to seal the surface of the render and remove minor surface irregularities to give a smooth surface ready to receive the decorative finish. 10.7.24 External Render External render shall be applied to concrete, concrete blocks and clay bricks as follows :- 10/13 SECTION 10 BUILDING SPECIFICATIONS The render shall be three coat work comprising a stipple coat as described previously, an undercoat and a finish coat giving a maximum thickness of 16 mm. The mixes shall be in the proportions shown on the schedule of mixes. The undercoat shall be level, true and of sufficient thickness to prevent the background joints showing through and shall be kept damp for three days before applying the final coat. Where shown on the drawings the final coat shall be approximately 5 mm thick coloured Tyrolean open honeycombed texture machine applied render. A key for the final coat shall be provided by combing the undercoat prior to setting with wavy lines 20 mm apart and 5 mm deep. The final coat shall be 6 mm minimum thickness and worked to a level and smooth finish with a wooden float with clean, true and level arises. The whole shall be protected from rapid drying out in hot, dry and windy weather. Table 10-1. Schedule of Mixes for External Render Concrete,Concrete Blocks Aerated Concrete Blocks Mix Type or Engineering Bricks of Soft Clay Bricks Undercoat Finish Undercoat Finish Cement:Lime:Sand Cement:Ready-Mixed Lime / Sand Cement:Sand with Plasticizers 10.8 GLAZING 10.8.1 Glass 1:1.5:4 to 4.5 1:4 to 4.5 1:3 to 4 1:1:5 to 6 1:5 to 6 1:5 to 6 1:2:8 to 9 1:8 to 9 1:7 to 8 1:2:8 to 9 1:8 to 9 1:7 to 8 Glass for glazing shall be the best of its respective kind and free from blemishes and imperfections. Glass shall be as shown on the drawings. 10.8.2 Bedding Compound The bedding compound for external glazing shall be an approved non-setting butyl rubber based proprietary compound and sufficiently elastic to allow for thermal or other movement of the glass and timber, compatible with the approved decorative wood stain. The bedding compound shall show no sign of separation after bedding. 10/14 SECTION 10 BUILDING SPECIFICATIONS 10.9 PAINTING AND DECORATING 10.9.1 Painting-General All primers, oil bound undercoats and finishes, emulsions and polyurethane interior varnishes shall be used in strict accordance with the manufacturer's recommendations and shall be obtained from an approved manufacturer. Only fresh paint delivered to site in original sealed containers shall be used. Each container shall be labelled with the manufacturer's name, contents, colour, quantity, batch number and date and instruction on method of application. 10.9.2 Exterior Stain Pigmented stain shall be PX 65 as manufactured by Sadolin's Ltd., and used in accordance with their recommendations, or other equal and approved, two coats before fixing and one coat after fixing. 10.9.3 Workmanship All painting shall be carefully executed with clean brushes and in the best manner and applied strictly in accordance with the manufacturer's instructions. All paints, stains and varnishes shall be well stirred before use and thinned only in accordance with the manufacturer's recommendations. Painting of exterior work shall not be carried out in wet, dusty or foggy weather and interior work shall not proceed in dusty conditions. All woodwork shall be prepared to a fine clean finish by scraping or sanding all made dust free immediately before painting and coating. 10.9.4 Stopping to Plaster Plaster shall be clean and dry and free from loose material. Holes and cracks shall be cut back and solidly filled, allowed to dry and rubbed down smooth. 10.9.5 Steel Priming 10/15 SECTION 10 BUILDING SPECIFICATIONS Mild steel shall be blast cleaned and primed with two coats of primer within four hours of cleaning. Galvanised mild steel shall be degreased with white spirit and primed with two coats of primer. 10.9.6 Oil-Based Paint Interior primed softwood and all primed mild steel shall be painted with two undercoats and one gloss or semi-matt finish coat of oil-based paint to give a smooth, even and solid finish, all as instructed. Each coat shall dry overnight before applying further coats. 10.9.7 Internal Finish to Walls The paint finish to internal walls shall be PVA copolymer matt emulsion paint or as detailed on the drawings. 10.9.8 Ironmongery All fixed ironmongery except hinges shall be removed before painting and refixed on completion. 10/16