QS System STEP-PS24DC/3.8-CPN5550 QS Link Power Supply 369336 Rev. C 1 11.06.13 QS Link Power Supply The STEP-PS QS link power supply provides up to 22 Power Draw Units (PDUs) on a QS link. The STEP-PS powers additional compatible accessories and devices, allowing them to be added to a QS system. Specifications Input Power •Nominal input voltage: 100–240 V •Frequency: 50/60 Hz •Current consumption, fully loaded: approx. 0.8 A (230 V ) approx. 1.3 A (120 V ) Power Supply Output •Nominal output voltage and tolerance: 24 V / ±1%, 22 Power Draw Units* •Setting range of output voltage: 22.5–25.0 V ; at time of shipment, the output voltage is 24 V * Power supply is rated to provide a maximum of 22 Power Draw Units to devices on the QS Link. Use above this maximum will reduce the lifetime of the supply and void all Lutron® warranties. Note: This power supply is NOT rated for use with motorized shades/window treatments. Environment •Ambient temperature operation: -25 to +70 °C (-13 to +158 °F) (> 55 °C / 131 °F Derating 2.5% / K or 3.5% / F) •Ambient temperature storage: -40 to +85 °C (-40 to +185 °F) •Humidity at +25 °C (77 °F), no condensation: ≤ 95% ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: STEP-PS24DC/3.8-CPN5550 (STEP-PS/1AC/24DC/3.8/C2LPS-CPN5550) Standards •Electrical Safety: IEC60950 / VDE 0805, UL/cUL Recognized UL 60950 •Safety Transformer: EN61558-2-17 •Electronic equipment for electrical power installations: EN 50178 / VDE 0106-101 •Safe isolation: DIN VDE 0100-410 / DIN VDE 0106-101 •Industrial regulating devices: UL/cUL Listed UL 508 •Shipbuilding: GL •Limitation of main harmonic currents: EN 61000-3-2 •Electromagnetic compatibility CE in conformance with EMC Guidelines: 2004/108/EG ; 2006/95/EG. - Immunity to interference: EN 61000-6-2 - Noise emission: EN 61000-6-3 •Protection Class II •UL Approvals: - UL/cUL Listed UL 508 - NEC® Class 2 as per UL 1310 - UL/cUL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D Page 1 en_02 QS System STEP-PS24DC/3.8-CPN5550 QS Link Power Supply 369336 Rev. C 2 11.06.13 Dimensions Dimensions shown as: mm (in) 90 (3.5) 30 (1.18) 55 (2.17) 44 (1.73) 150 (5.9) 100-240V 100-240V 24V 3.8 A 24V 3.8 A 90 (3.5) 22.5-25.0 V 22.5-25.0 V 50 (1.97) 30 (1.18) Required clearance above and below the power supply. 61 (2.4) Mounting •Surface mount using screws, or mount on DIN rail •Use an IP20 (minimum) rated consumer panel or breaker panel with integrated DIN ® Job Name: DIN Rail Mounting: Surface Mounting: Snap onto DIN rail. To remove, pull out tabs with screwdrivers and lift off. Pull out tabs with screwdrivers. Screw through tabs to secure. S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page 2 Job Number: PHOENIX CONTACT PHOENIX CONTACT 8 8 QS System STEP-PS24DC/3.8-CPN5550 QS Link Power Supply 369336 Rev. C 3 11.06.13 Wiring •Wire product in accordance with national and local electrical codes •Each terminal takes one 0.2 to 2.5 mm2 (24 to 12 AWG) wire, with 6.5 mm (1/4 in) stripped bare •Maximum torque: 0.6 to 0.8 N∙m (5.0 to 7.0 in∙lb) Hot/live (L) and neutral (N) in from distribution panel L + + N - + 24 V out to terminal 2 of QS devices on the link. Do not connect to terminal 2 of other power sources on the link (see Link Power Distribution diagram) - Common out to terminal 1 of all QS devices on the link, including other power sources 24V 3.8 A 100-240V 22.5-25.0 V ® Job Name: Job Number: S P E C I F I C AT I O N S U B M I T TA L Model Numbers: Page 3 QS System STEP-PS24DC/3.8-CPN5550 QS Link Power Supply 369336 Rev. C 4 11.06.13 QS Link Power Distribution On the QS link, there are devices that supply power and devices that consume power. Each device has a specific number of Power Draw Units (PDUs) it either supplies or consumes. A Power Group consists of one device that supplies power and one or more devices that consume power; each Power Group may have only one power‑supplying device. Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on the QS link that supply power, connect only terminals 1, 3, and 4 (NOT terminal 2), shown by the letter B on the diagram. See Wiring section on the previous page for details on wiring the STEP-PS power supply to the QS link. erminals 1, 2, 3, and 4 connect devices A T within a power group. Example: Power Group Wiring A Terminals 1, 3, and 4 connect between B Power Groups. Terminal 2 is NOT connected between Power Groups. LUTRON GRAFIK Eye® QS QSE-CI-NWK-E B Power Group 1 seeTouch® QS keypad Power Group 2 A Energi Savr NodeTM QS seeTouch® QS keypad B seeTouch® QS keypad seeTouch® QS keypad Power Group 3 A STEP-PS power supply QSE-IO seeTouch® QS seeTouch® QS keypad keypad 1 3 4 − STEPPS + ® Job Name: Job Number: 1 2 3 4 Power consuming device 1 2 3 4 S P E C I F I C AT I O N S U B M I T TA L Model Numbers: QS sensor module and occupancy sensor STEP-PS Power Supply Power Group Wiring Detail Between power supplying devices: Connect only terminal 1 (common; “−” terminal on the STEP-PS). See previous page. Between Power Group 3 devices and STEP-PS: Connect terminals 1 (common) and 2 (power). Between the QS link and devices powered by the STEP-PS: Connect terminals 3 and 4 (communication/data). Page 4