SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 1 OF 15 SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.01 SECTION INCLUDES A. 1.02 1. Control devices. 2. Air handling units. 3. Fan coil units. 4. Makeup air unit control. 5. Heating coils. 6. Boiler plant. 7. Cabinet heaters. 8. Unit heaters. 9. Radiant panels. 10. Radiation 11. Hot water heater control domestic. 12. Exhaust fans. 13. Emergency generators. 14. Duct mounted smoke dampers. 15. Excess pressure controls. 16. General alarm status monitoring. RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work of this section. B. The Following Division 15 Specifications Sections apply to the work of this section C. 102313 Sequence of operation for mechanical systems and components: 1. Section 23 09 23 - Direct Digital Control Equipment. 2. Section 23 09 00 - Instruments and Control Elements The requirements of Division 26 - Electrical apply to work of this section. PROJECT NO. BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 2 OF 15 1.03 SYSTEM DESCRIPTION This Section defines the manner and method by which controls function. Requirements for each type of control system operation are specified. Equipment, devices, and system components required for control systems are specified in other Sections. 1.04 SUBMITTALS A. Refer to Section 23 09 23 - Direct Digital Control Equipment B. Submit in accordance with Division 1 and Section 23 04 00. Submit diagrams indicating mechanical system controlled and control system components. Label equipment and control devices using the nomenclature on the drawings. Control devices shall be labeled with settings, adjustable range of control and limits. Include written description of control sequence. D. Include flow diagrams for each control system, graphically depicting control logic. Include draft copies of graphic displays indicating mechanical system components, control system components, and controlled function status and value. Include wiring schematics of each control panel clearly showing extent of internal and external wiring. Provide detail of panel face including controls, instruments, gauges and labels. Indicate factory and field wiring. Indicate each control panel required, with internal and external piping and wiring clearly indicated. Provide detail of panel face, including controls, instruments, and labeling. Include verbal description of sequence of operation. Maintenance Data: Include copy of shop drawings in each maintenance manual; in accordance with requirements of Division 1. Project Record Documents: Accurately record actual locations, setpoints and settings of controls, including changes to sequences made after submission of shop drawings. PART 2 - PRODUCTS Not Used PART 3 - EXECUTION 3.01 GENERAL Provide all controls, low voltage control wiring and accessories necessary to accomplish the sequence of operation as indicated below. Power wiring and interlockwiring shall be provided in accordance with Division 16 wiring requirements. All sequences shall be performed by the Building Management System (BMS) unless noted as a being controlled locally or specifically noted as controlled by other systems. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 3 OF 15 3.02 CONTROL DEVICES A. 3.03 All devices and sensors shall be adjustable. BMS shall display setpoints and actual conditions of all control devices and position of all actuators at the central personal computer (PC). AIR HANDLING UNITS & HEATING/VENTILATING UNITS (AHU-A1, RTU-#, ERV-#, HX-#) A. Unoccupied Mode: 1. Outside air, exhaust air and relief air dampers shall be closed. 2. Return air dampers shall be open. 3. Fans and energy recovery motors shall be deactivated. 4. BMS shall raise the zone temperature cooling setpoint to 85°F and drop the zone temperature heating setpoint of 65°F. If two or more zones are calling for heating or cooling the fans shall cycle on. When the call for heating or cooling is satisfied the fans shall be deactivated. 5. Compressors disabled and hot water valves shall be closed. If outside temperature is below 40°F, unoccupied mode heating valve shall be fully open. 6. Freezestat and temperature sensor within the unit's casing shall be monitored during unoccupied mode. If temperature drops below setpoint of either device, the main heating valve shall be fully open, fans shall be de-activated and an alarm shall be activated at the central PC. 7. B. C. 102313 If an occupied button is depressed on a zone temperature sensor then the unit shall leave the unoccupied mode for 2 hours. Occupied Mode: 1. The zone will calculate how long it will take to return from its unoccupied state to its occupied setpoint based on the heating or cooling capacity and the outside air temperature. The zone will then adjust its effective setpoint at the time necessary in order to ensure the desired zone conditions at occupancy. 2. The system will not start more than 4 hours before a scheduled occupancy. 3. BMS shall track the supply fan's accumulated runtime. When runtime exceeds 10,000 hours, the controller will generate a runtime expiration message. 4. Fans shall operate continuously. Energy recovery motors shall be energized 5. Outside air and relief air dampers shall be at minimum open positions. Coordinate setpoints of motorized dampers serving outside air and relief air dampers with air balancer. Fan Control: 1. When called to run, the fan will run for a minimum of 5 minutes. 2. When the fan cycles off, it will remain off for a minimum of 5 minutes. PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 4 OF 15 Alarm Conditions: Current sensing relays/VFD feedback: If fan has been signaled to start and feedback from respective relay or VFD does not indicate the fan has started after 30 seconds, unit shall be shut down and an alarm shall be activated at the central PC. Conversely, if fan on status is detected while the fan is turned off, a separate "Hand" alarm shall be activated at the central PC Damper end switches: If end switch does not indicate respective damper is open after 30 seconds, unit shall be shut down and an alarm shall be activated at the central PC. Conversely, if a damper is indicated open, a separate "Hand" alarm shall be activated at the central PC. Duct mounted smoke detectors: When a detector is in alarm mode the fire alarm system shall be notified, respective fans shall be de-energized and an alarm shall be activated at the central PC. If a freezestat trips, the hot water valve at the respective unit shall be fully open, fans shall stop, outside air damper shall be fully closed and an alarm shall be activated at the central PC. The controller will generate an alarm if the zone temperature remains 4°F higher than its cooling setpoint for 5 minutes. This alarm will not be enabled until the zone has been running for 30 minutes. The controller will generate an alarm if the zone temperature remains 4°F lower than its heating setpoint for 5 minutes. This alarm will not be enabled until the zone has been running for 30 minutes. The controller will generate an alarm if the discharge air temperature remains higher than 120°F with a hysteresis of 5°F for 5 minutes. This alarm will not be enabled until the zone has been running for 30 minutes. The controller will generate an alarm if the discharge air temperature remains lower than 45°F with a hysteresis of 5°F for 5 minutes. This alarm will not be enabled until the zone has been running for 30 minutes. Supply Air Temperature Setpoint Control BMS will run a cooling setpoint optimization algorithm and a heating setpoint optimization algorithm simultaneously. The initial cooling setpoint will be 55°F, with a minimum of 53°F and a maximum of 72°F. If any zones are still calling for cooling at the end of a 5 minute period, the setpoint algorithm will respond by lowering the setpoint by I°F for every zone requesting cooling. If no zones are still calling for cooling at the end of a period, the setpoint algorithm will respond by raising the setpoint by I°F. The cooling setpoint algorithm will not adjust the cooling setpoint by more than 2°F in any period. The initial heating setpoint will be 82°F with a minimum of 72°F and a maximum of 85°F. 102313 PROJECT NO. BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 5 OF 15 If any zones are still calling for heating at the end of a 5 minute period, the setpoint algorithm will respond by raising the setpoint by 2°F for every zone requesting heating. If no zones are still calling for heating at the end of a period, the setpoint algorithm will respond by lowering the setpoint by 1 °F. The heating setpoint algorithm will not adjust the heating setpoint by more than 4°F in any period. BMS shall determine the AHU supply air temperature setpoint based on the number of heating requests and cooling requests the AHU is receiving. If there are more cooling requests than heating requests coming into the AHU, or if there are the same number of heating requests as cooling requests, the AHU controller will use the cooling setpoint. If there are more heating requests than cooling requests coming into the AHU, the AHU controller will use the heating setpoint. When the BMS switches from the heating setpoint to the cooling setpoint, the setpoint control algorithm will ramp from the heating setpoint to the cooling setpoint at a rate of 1°F/minute. When the BMS switches from the cooling setpoint to the heating setpoint, the setpoint control algorithm will ramp from the cooling setpoint to the heating setpoint at a rate of 1°F/1.5 minute. 3. F. The user will be able to override the supply air temperature setpoint. Heating Control If the outside air temperature is less than 65°F with a 2°F hysteresis and the outside air temperature is valid, BMS will allow heating based on outside air conditions. 2. If the outside air temperature reading is not valid, BMS will still allow heating. Upon a call for heating, dampers at energy recovery units shall be modulated to increase flow rate through the energy recovery section and reduce flow rate at the energy recovery's bypass. Energy recovery modules shall be the first stage of heating. Upon a call for heating with the outside air is between 65°F and 40°F, BMS shall modulate the hot water valve, with the face and bypass damper full open to the coil, to maintain temperature setpoints if cooling has been off for at least 5 minutes. Upon a call for heating with the outside air below 40°F outside air, the hot water valve shall be fully open and the face and bypass damper shall be modulated to maintain temperature setpoint if cooling has been off for at least 5 minutes. The user will be able to lock the signal to the hot water valve. The user will be able to lock the signal to the face and bypass damper. Energy Recovery Modules (AHU-A1 exempt) - Frost Control: When outside air temperature is below unit's individual specific setpoint, bypass damper at the outside air side of the energy recovery module shall modulate open. If unit does not have a damper at the outside air, relief air/exhaust air bypass damper at the energy recovery module shall modulate open. Dampers shall modulate to 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 6 OF 15 maintain discharge air temperature setpoint. Setpoint for each unit shall be determined per Specification Sections 23 81 06. Cooling Control If the outside air temperature is greater than 60°F with a 2°F hysteresis and the outside air temperature is valid, the AHU controller will enable cooling based on outside air conditions. If the outside air temperature reading is not valid, the AHU controller will still enable cooling. Upon a call for cooling, BMS shall stage the compressors, to maintain temperature setpoints if heating been off for at least 5 minutes. Economizer Control BMS will allow economizer cycles to be activated based on outside air conditions if the return air temperature and enthalpy is greater than the outside air temperature and enthalpy with a hysteresis of 5°F, the outside air enthalpy is less than 22 Btu/Ib with a hysteresis of 2 Btu/Ib, the outside air temperature is less than 65°F with a hysteresis of 2°F, and the outside air readings are valid. In addition to all AHU's, economizer cycles shall be programmed for all Heating and Ventilating Units (ERV&HX units). Exhaust fans serving H&V units shall act as relief air fans and shall be activated when there is a call for cooling and permissive inputs allow economizer cycles to be activated. Economizer cycles for H&V Units shall be base on return air and outside air temperature, not enthalpy readings. If the outside air readings are not valid, BMS will disable the economizer. The user will be able to enable the economizer if the outside air readings are not valid. When economizer cycles are activated, energy recovery motors shall stop and energy recovery bypass dampers shall open. An economizer PID will modulate the economizer/ventilation dampers and relief air/exhaust fans between minimum setpoint and 100% to maintain the zone temperature at 2°F below the zone temperature cooling setpoint if heating has been off for at least 5 minutes. The relief air fans and exhaust fans shall and activated. The user will be able to adjust all PID parameters (P, I, and D gains, loop bias, and loop interval). The user will be able to lock the economizer damper position. The controller will limit the signal change sent to the economizer to 1% every 2 sec. when increasing. If the mixed air temperature drops below 45°F, the AHU controller will begin to close the economizer to protect the coil. The controller will continue to close the damper linearly until the temperature drops to 40°F, when the economizer/ventilation damper will be 100% closed. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 7 OF 15 If the AHU loses flow or the freezestat trips, the AHU controller will close the economizer dampers. The AHU controller will generate an alarm if the mixed air temperature remains lower than 45°F for 5 minutes with a 5°F hysteresis, This alarm will not be enabled until the supply fan has been running for 30 minutes, The AHU controller will generate an alarm if the mixed air temperature remains higher than 90°F for 5 minutes with a 5°F hysteresis, This alarm will not be enabled until the supply fan has been running for 30 minutes, I, Air Flow Monitoring Stations Outside Air: BMS shall monitor the outside air flow station(s) and modulate the outside air and relief air dampers to maintain minimum outside air flow setpoint. Supply air and return air flow rates at fans shall monitored as shown on the drawings, Outside Air - Demand Control Ventilation BMS shall monitor carbon dioxide (DO2) sensors for each zone (return air for DV units and VAV zones for VAV units), If DO2 levels rise above setpoint (800ppm DO2), the controller shall modulate the outside air and relief air dampers open an alarm shall be activated at the central PC. System shall have the capability of reducing the amount of outside air based upon CO2 levels, Space pressure control (Wood Shop - ERV-S5) During economizer operating mode of the ERV, space pressure monitoring devices shall continuously pole the space pressure and adjust the return air and exhaust damper positions of the Dust Collection Unit (D-l) to maintain the interior space pressure at -0.1" w.c. Whenever the economizer cycle of ERV-S5 is not operating, the space pressure monitoring devices shall be ignored and the D-1 dampers shall be in the 100% recirculation (return to space) position. 3.04 VAV AIR HANDLING UNIT CONTROL SEQUENCES A. Refer to General AHU Control Sequences above for additional Sequences or Operation. B. Supply Air Static Pressure Control When the fans have flow, the AHU controller will modulate the supply fan VFD with a reverse acting static pressure PID to maintain the duct static pressure at the static pressure setpoint (1,5" w,c,), When cooling is activated, the fan VFD shall not be allowed to drop below a speed setting that will produce a flow rate equal to the total of the minimum flow settings of all the VAV boxes served by the respective unit, 2. 102313 The user will be able to lock the output signal to the supply fan VFD. PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 8 OF 15 If the supply static pressure remains 25% higher than setpoint for 1 minute, an alarm shall be activated a the central PC. BMS shall generate an alarm if the supply static pressure remains 25% lower than setpoint for 5 minutes. This alarm will not be enabled until the supply fan has been running for 2 minutes. C. Return Fan Tracking Control The AHU controller will send the supply fan run signal to the return fan if the AHU is called to run. The return fan control logic is identical to that of the supply fan, and will produce similar alarms. If the return fan loses its run signal, the controller will set the return fan VFD output to zero. 4. 3.05 The user will be able to lock the output signal to the return fan VFD. UNIT HEATERS Unit heaters shall be controlled locally. When temperature falls below thermostat setpoint, unit heater's fan shall be energized. 3.06 CABINET HEATERS Single temperature thermostat maintains constant space temperature by cycling unit fan motor when the aquastat is satisfied. 3.07 DUCT MOUNTED SMOKE DAMPERS-RTU-C5&S5 Dampers shall be controlled by the fire alarm system. Dampers shall close when the respective air handling unit is shutdown or when smoke is detected at damper's respective duct mounted smoke sensor. Fire alarm system shall be capable of remotely controlling position of damper and have remote indication of position of damper. 3.08 BOILER PLANT Heating system startup shall be initiated by the Building Management System. (BMS) Boilers shall be allowed to operate when outdoor temperature is below setpoint of 60 degrees F (adj.) and shall be disabled once outdoor temperature rises above 65 degrees F (adj.). Once enabled, boilers shall operate by integral controls which shall inherently include boiler sequencing with all boilers wired in a cascade configuration from a single controller. The plant shall also utilize and outdoor air temperature sensor to change the system supply water temperature (SWT) setpoint as outdoor air temperature (OAT) varies based on the following schedule: 102313 1. Whenever OAT > 50°F, SWT shall be 120°F. 2. Whenever OAT < 20°F, SWT shall be 180°F. PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 9 OF 15 SWT shall vary inversely proportional from 120°F to 180°F for OAT's between 50°F and 20°F. The boiler(s) controller shall automatically equalize boiler runtime and adjust the firing sequence intervals. All boiler operating parameters including but not limited to cascade methods and system temperature operating setpoints shall be adjustable at the boiler control module. System operating parameters shall be communicated via applicable protocols for viewing at the BMS front end. The secondary system pumps (boiler injection pumps) shall be enabled by the boiler controller to run when the respective boiler is firing. The primary system pumps shall vary operating speed by variable frequency drives fitted on every pump. Both sets of primary pumps shall operate in a lead/lag configuration where the lead pump is enabled to run at minimum speed whenever the boiler plant is enabled. The lead pumps shall vary speed to maintain a constant differential pressure at all times. If a fault condition occurs with a lead pump at any time an alarm shall be generated by the BMS and the system shall automatically switch to the lag pump. A pump sequencer shall be provided for both sets of primary pumps and the lead pump designation shall be switched daily. NOTE: All wiring between control components of boilers including but not limited to gas train, boiler controller furnished by manufacturer and burner emergency switches shall be wired and tested by the temperature control contractor. 3.09 COMBUSTION FAN SYSTEM When water heater operation is requested, the BMS shall command the combustion fan system to start. The fan shall modulate to maintain a constant positive static pressure in the boiler room via linked space pressure sensor to the motor drive speed controller. B. 3.10 An alarm shall be provided by the BMS if the combustion fan fails to operate. GENERAL ALARM STATUS MONITORING The equipment and panels listed below shall be monitored for general alarm. Upon contact closure indicating an alarm condition, an alarm shall be activated at the control panel. 3.11 1. Water treatment system. 2. Water/leak detection in the boiler room. EXHAUST FANS All Fans: BMS shall monitor the operation or failure (fan status) through a current sensing relay switch. For fans with variable frequency drives (VFD), BMS shall monitor fan status through an alarm output contact at the VFD. If fan has been signaled to start and feedback from the relay or VFD does not indicate the fan has started after 30 seconds, fan shall be shut down and an alarm shall be activated at the central PC. If damper end switches do not indicate respective dampers are open, fan shall be shut down and an alarm shall be activated at the central PC. Conversely, if status is detected while the fan is turned off or a damper is indicated open, a separate "Hand" alarm shall be generated. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 10 OF 15 Temperature Controls: Upon a rise in space temperature above sensor setpoint, associated motorized dampers shall open and respective fans shall staG. Time of Day: Associated motorized dampers shall open and respective fans shall star only during scheduled occupied modes. Fans Controlled by Toggle Switches and Twist Type Timer Switches. Associated motorized dampers shall open and respective fan(s) shall star only when switch is in the "on" position. Operation shall also be subject to a Time of Day schedule. Fans Served by a Differential Pressure Switch: If differential pressure is below setpoint, an alarm shall be activated at the central PC. LEF-1,2,3,4,5,6 and 7: Fans shall be interlocked with RTU-C1, C2, & C3. LEF-2 and 5 shall operate continuously. LEF-1,3,4,6,&7 shall be activated via a toggle switch on the fume hood. The outside air dampers on RTU - C2 & C3 shall modulate to maintain a building differential pressure. The TSI ain%w monitor shall provide a local alarm to the user indicating the fan is inoperable. KEF-I&2: Fans shall be interlocked with MAU-I&2. The recirculation damper on MAUl&2 shall close and the units operate on 100% outside air while KEF-1 &2 of enabled. Fans shall be enabled via toggle switches mounted on the wall adjacent to the hoods. H. Dust Collector: StaG-stop of the dust collector fan shall be controlled by a wall mounted switch through the BMS. Operation shall be subject to a Time of Day schedule. If fan has been signaled to stag and a damper end switch does not indicate a damper is open after 30 seconds, unit shall be shut down and an alarm shall be activated at the central PC. Conversely, if fan is signaled to be off and a damper is indicated open, a separate "Hand" alarm shall be activated at the central PC. BMS shall monitor a separate switch which shall control position of the dampers at the discharge of the dust collector to exhaust the air or return the air back to the space. Dust collector shall be interlocked with ERV-S5. When dust collector is on and dampers are switched to exhaust mode, ERV-S5 shall be on and shall provide 100% outside air. 3.12 3.13 ELEVATOR MACHINE ROOMS A. Connect and monitor existing equipment. B. On room temperature above 80 degrees F and stag exhaust fans. C. On room temperatures above 90 degrees F signal alarm. EXCESS PRESSURE CONTROLS Maintain constant pressure differential between supply and return lines by varying pump speed through variable speed drive control. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 11 OF 15 3.14 RADIANT CEILING PANELS Space temperature sensor shall maintain constant space temperature by modulating two-way control valve in conjunction with the VAV box serving the zone. 3.15 RADIATION Space temperature sensor shall maintain constant space temperature by modulating two-way control valve. 3.16 TERMINAL AIR UNIT A. 3.17 Refer to section 23 36 00. MAKEUP AIR UNIT CONTROL Unit shall be activated through a wall switch which also serves the respective exhaust fan. When the unit is activated the supply fan shall operate continuously and the outside air damper in unit shall be fully open. Return air damper: Damper shall be open during the occupied cycle, except when the respective KEF is operating. Unit shutdown: Supply fan shall be de-energized and the outside air damper shall be fully closed. Freezestat: If the temperature at the outlet of the heating coil is below 40 degrees F, the supply fan shall stop, the outside air damper shall close, the heating valve shall modulate fully open and an alarm shall be activated. Differential pressure switch: When the differential pressure across the filters exceeds 0.4 in wg, an alarm shall be activated. When the supply fan is energized, "proof of fan running" shall be accomplished via air flow switch or current transformer relays. If fan does not start or stops operating, an alarm shall be activated. Temperature Control: The BMS shall modulate the burners to maintain the space temperature setpoint. 3.18 FAN COIL UNIT CONTROL A. Heating/Cooling Mode Change Over Supply fan coil unit with heating/cooling thermostat which will automatically change the unit from heating to cooling mode based on space temperature and thermostat set point. Thermostat shall have separate heating and cooling set points with an adjustable dead band. B. Heating/Cooling Mode Change Over Supply fan coil unit with heating/cooling thermostat which will automatically change the unit from heating to cooling mode based on space temperature and thermostat set point. Thermostat shall have separate heating and cooling set points with an adjustable dead bands. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 12 OF 15 Heating Mode Upon a drop in space temperature below the field adjustable set point of 70 degrees F the unit shall be placed in heating mode. The control valve on the heating coil shall be cycled opened and closed to maintain space temperature. Cooling Mode Upon a rise in space temperature above the field adjustable set point of 75 degrees F the unit shall be placed in cooling mode. The air cooled condenser shall be staged to provide cooling. Fan Control 1. Unoccupied mode: During unoccupied periods the fan shall be deactivated. Unoccupied mode: Upon a call for either heating or cooling the fan shall cycle on. when the call for heating or cooling is satisfied the fan shall be deactivated. 3. Occupied mode: Option 1 : The fan coil unit's fan shall be interlocked with EF-1 such that when EF-1 is activated the fan shall be activated and shall run continuously at a constant speed. Option 2: The fan coil unit's fan shall be interlocked with the lights such that when the lights are on the fan shall be activated and shall run continuously at a constant speed. Option 3: The fan coil unit shall be supplied with an occupancy sensor. The fan coil unit's fan shall be controlled by the occupancy sensor such that when the room is occupied the fan shall run continuously at a constant speed. 3.19 DUCT MOUNTED SMOKE DAMPERS A. 3.20 Dampers shall be controlled by the fire alarm system. The BMS shall monitor the fire alarm system for unit shutdown. Dampers shall close when the respective air handling unit is shutdown or when smoke is detected at damper's respective duct mounted smoke sensor. Fire alarm system shall be capable of remotely controlling position of damper and have remote indication of position of damper. DUCT MOUNTED HEATING COILS A. All Coils: Upon a drop in space temperature below sensor setpoint, heating mode shall be activated. Respective control valve shall modulate to maintain supply air temperature setpoint, reset by BMS. Freezestat: If supply air temperature is below freezestat setpoint, respective hot water coil shall be fully open, respective supply fan shall stop and an alarm shall be activated at the central PC. Freezestat shall be active when respective unit is in occupied and unoccupied modes. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 13 OF 15 3.21 FUEL OIL SYSTEM (at HVAC shop) Leak Detection: Monitor the local leak detection system for leaks in both the above ground oil storage tank interstitial space and the underground piping. Any leak shall create an alarm condition and shall shut the fuel oil pump set off. Pump Set and Day Tank: Provide oil sensors in the pans for both the fuel oil pump set and the day tank. Monitor both oil sensors. Upon sensing of oil in either pan, oil pump set shall shut off and an alarm condition shall be created. 3.22 SUMP PUMPS SP-1 &SP-3 Monitor the local pump controller for lag pump operation. When the lag pump operates an alarm condition shall be created. 3.23 GENERAL DEVICES Variable Frequency Drives: BMS shall control start/stop of each VFD and shall monitor a general alarm contact at the VFD. If the VFD is in alarm mode, an alarm shall be activated at the central PC. BMS shall control speed of each VFD. Alarm Contacts: BMS shall monitor alarm contacts as shown on the drawings. If a device is in alarm mode, an alarm shall be activated at the central PC. Water Heater Combustion Air: When the burner contact is engaged, the respective combustion air intake dampers shall open. If dampers have been signaled to open and a damper end switch does not indicate a damper is open after 30 seconds, the water heater shall be de-activated and an alarm shall be activated at the central PC. Conversely, if water heater is indicated as off and a damper is indicated open, a separate "Hand" alarm shall be activated at the central PC. Domestic Hot Water Recirculating Pumps: Pumps shall be controlled per a time of day schedule and shall be activated during occupied modes. Carbon Monoxide Sensors: BMS shall monitor panel and display alarms. If CO levels rise above setpoint, respective exhaust fan(s) shall start and heating and ventilating units shall start and provide 100% outside air. At the boiler room, boilers and water heater shall be shut down. 3.24 OUTDOOR AIR CONDITIONS MONITORING A. Functional Control The controller will read the outside air temperature and enthalpy and calculate the outside air enthalpy, and will make these values available to the system. If the outside air temperature sensor indicates a reading lower than -25°F with a hysteresis of 10 or higher than 225°F with a hysteresis of 10 the controller will make the alternate outside air temperature sensor available to the system. Ifthe sensor still indicates these readings after 5 minutes, the controller will generate a sensor failure alarm. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 14 OF 15 B. Temperature History Once the controller has established communication with the system after any interruption in communication, it will record a temperature history for the system. At 12:05 am every night, the controller will reset the high and low daily temperature peak recorders for the next day. The reset signal will last no longer than 5 seconds. When the high and low daily temperature peak recorders are reset for the first day of each month, the high and low month-to-date peak recorders will also be reset. When the high and low month-to-date peak recorders are reset for January, the high and low year-to-date peak recorders will also be reset. 3.25 ALARM NOTIFICATION Events and alarms shall be indicated on the appropriate equipment graphics page viewable and with automatic display updates available at the central server level. The graphic display will indicate an alarm condition by showing the appropriate object in red on the graphic display. Alarms and events shall be displayed on the Event Log Page viewable and with automatic display updates available at the central server level. Date and time of occurrence shall be recorded. Alarms and events shall be transferred out of the automation system to other network services for remote notification to: printers on the customer's network, e-mail system, local sounds, or other reporting actions, depending on user configuration. 3.26 TRENDING All I/O points will be linked to a trend log and additional trends will be provided as shown in the tables below. The controller will be able to record a trend sample every 10 minutes on each of the trend objects. The controller will save the most recent 144 samples of each trended point in the control module for viewing or printing. The user will be able to enable or disable trending of any of the points listed. Points marked with an asterisk will automatically be trended in the default configuration. For the first year of operation, the system will trend and record all data at 10 minute increments which can then be backed up on CD's. 3.27 COMMISSIONING Engage a factory-authorized service representative, to perform sta•tup service as per functional test sheets and requirements of Section 23 08 00 Commissioning. Verify that equipment is installed and commissioned as per requirements of Section 23 08 00 and manufacturer's written instructions. 102313 PROJECT NO, BI-RT-844-CMR SECTION 23 09 93 SEQUENCE OF OPERATION FOR HVAC CONTROLS PAGE 15 OF 15 Complete installation and startup checks and functional tests according to Section 23 08 00 and manufacturer's written instructions. Operational Test: After electrical and control systems have been energized, start units to confirm proper unit operation. Rectify malfunctions, replace defective parts with new one and repeat the start up procedure. Test and adjust controls and safety devices. Replace damaged and malfunctioning controls and equipment. END OF SECTION 102313 PROJECT NO. BI-RT-844-CMR