I IEE REVIEW Automatic controls in building services M.V. Harrold D.M. Lush Indexing terms: Control systems, Power systems, Power utilisation Abstract: Until recently, the term ‘controls’ was confined, in building services, to the thermostatic devices associated with the heating, ventilating and air conditioning (HVAC) systems. Nowadays, the definition is generally considered as encompassing the motor starter and control panels, energy management and building automation systems, lighting controls and, at least, the interfacing with fire, security and lift systems. Based on this premise, the review covers the range and applications of the automatic control systems now available, with a review of the state of the art, and some predictions as to the likely direction in future. The aim of the review is to provide an insight into current and future control systems. The intention is to enable electrical engineers to better co-ordinate their activities with their mechanical and HVAC colleagues who commonly specify the control systems which have to be integrated into the total services design. The topics reviewed include the effect of correct selection on the operation of the HVAC system, the electrical requirements of controls, guidelines on the application of controls to particular systems, coordination of effort between all the parties involved, the variations and scope of EMS/BAS and direct digital control, lighting control, and testing and commissioning. 1 Introduction Control theory for process work and environmental purposes is, essentially, identical, but in practice, applications are markedly different. The use of controls in industrial processes is generally accomplished by the application of highly-priced equipment to satisfy a very precisely defined set of requirements, which if not satisfied may be very costly in terms of lost production. Because reaction times within the process may be very rapid, and instability is never far away, it is important to engineer and check on the stability criteria for each control loop. The controls used for environmental purposes are sold in a highly competitive market at an order of cost lower than their industrial counterparts, but are functionally comparable. The controls are applied to systems which, like process plants, have their performance requirements Paper 5982B. first received 20th February and in revised form 6th August 1987. Commissioned IEE Review The authors are with Arup Research & Development, 13 Fitzroy Street, London W1P 6BQ, United Kingdom 1EE PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y I988 closely specified. However, the systems are inherently stable, the reaction times are normally much slower than industrial processes, and less than specified performance creates discomfort instead of financial loss. Fairly obviously, extreme or prolonged discomfort may produce less efficient output from the people affected, with consequential financial implications. It is often believed that expertise in process control is readily transferred into the simpler automatic controls systems for building services, a view possibly reinforced by the preceding comments on stability and reaction times. There are however major unpredictable elements which negate this assertion - people, their use of the building and their very personal views of what is the most acceptable environment for themselves. Environmental control systems are not simply technical agglomerations of specific items to satisfy a given set of conditions, they have to be sufficiently flexible to adapt to a large number of options that can be set and reset over many years with changing patterns of use. To appreciate the importance of the environmental requirements, the topic is covered in some detail. Costs and engineering input have already been mentioned and, while the market is competitive, it should not be thought that engineering requirements are ignored. While it is not necessary to carry out stability analysis for control loops, the engineering required to design and specify the control system for all the combinations of usage patterns and environmental requirements is very demanding and relatively costly when compared to the design input for other elements of building services. The march of technology, particularly in the electronics field, has had a marked and continuing effect on the development of automatic controls over the last ten to fifteen years. What used to be impossible or horrendously expensive is now commonplace and, at face value, apparently inexpensive. This frequently creates situations where the seductive quality of high technology obscures the fact that a mundane solution would be simpler, cheaper, better understood, more easily commissioned and maintained and, most important of all, perfectly suited to the problem it solves. It is essential to understand what technology can offer to automatic controls systems, but it is crucial for the long term benefit of the final user to keep the system as simple as possible to satisfy the needs. This review covers automatic controls for building services from their earliest known history through their development for environmental purposes, their theory, systems and applications. It will concentrate on the use of electrical/electronic controls, remembering that equivalent pneumatic systems exist for most electrical arrangements. Until the early 1970’s the more complex projects, 105 mainly air conditioned, tended to use pneumatic controls. The advent of cheap electronics/chips has now made controls available for individual air conditioning terminal units which are competitive with their pneumatic equivalents. The pneumatic arrangement of a temperature sensor and small pneumatically actuated valve(s) for this purpose were the only cost effective solution prior to this development. It is not the object of this review to cover the contractual and interface problems which arise and have to be overcome on projects both large and small, simple and complex. It is however becoming increasingly true that automatic controls elements occur within all building services systems and that analogously they frequently form the mortar holding the bricks together to provide a homogeneous co-ordinated arrangement. In this context it is advantageous to design the automatic controls as part of a single package which also includes the motor starter and control panels, the interconnecting wiring and, whenever used, the building management system. The term automatic controls applied to building services used to be confined almost exclusively to the environmental controls used on heating, ventilating and air conditioning (HVAC) systems. It now encompasses controls for lighting, fire, security and building management and spreads into lift control and communication systems. This review is primarily concerned with HVAC, lighting and building management. 2 History Controls, for most of us, have been available at whatever level is appropriate to the HVAC systems that are in vogue at that Particular time. Sometimes there might have been an apparent lag between what be ‘Onsidered ideal and what is actually manufactured, but good engineering (design and control) has always been able to improvise suitable control schemes. At the present time, we all suffer from a surfeit of control devices, systems and literature (which is not always concise or technically relevant). In some ways it has not always been like this, and in other instances very little has changed. The history of thermostatic control in the modern sense dates back to around the middle of the 19th century, when mercury in glass thermometers, incorporating electrical contacts, initiated alarms. However, Galileo in the 16th century produced a simple device to investigate degrees of heat and cold. In the late 19th century, electric thermostats were available in Europe and the USA, and pneumatics as we know them were developed in the USA in the early 20th century, although they were not in common use in the HVAC industry until the 1930s in the USA, and later still in the UK. The first UK thermostat of note was not available until the late 1920s when the Rheostatic Company (now Satchwell Control Systems Ltd) produced such a device, and the industry has always owed a lot to manufacturers outside the UK. Until the last ten years, when a multiplicity of firms in the UK started to manufacture electronic devices, very few wholly UK companies have operated in the commercial controls business. Despite the advances in the design and range of suitable appliances for controls, thermostats, detectors, controllers, valves, etc., there are doubts about their use. To quote an address to a learned society: ‘It is difficult to understand the prejudice against automatic control. It is 106 not many years ago that the President of the Institution ‘deprecated in his own Practice the elaboration of automatic mechanisms, because in his view they were not needed, and, in the second place they were liable to get out of order . . . . In normal heating work, all that fancy work was not needed‘.’ You may recognise the sentiments, but they date back to 1941 in an address to the Newcomen Society by Dufton. Things have not changed, as another recognisable comment is : ‘These devices are very complicated, their cost is very high and their performance is very uncertain, so it seems that they ought to be abandoned completely’. Do not despair: despite these quotes, successful control systems can be designed which do not suffer the implied problems, but the factors mentioned later must be taken into account. Incidentally, the second quotation precedes the first, having been made by Picard in 1897, in a paper on heating & ventilating. The tenor of comments such as those quoted should always be in the forefront of any controls philosophy. Good control systems always depend on designing correctly, selecting the controls to do the job as efficiently as necessary, and ensuring that the systems will be kept in working order by the users. To do this, it is necessary to remember that the history and development of controls now encompass many other systems in addition to the simple choice of which elements will control a given loop, and whether the system should be electronic or pneumatic. 3 Environmental and usage requirements 3.1 Genera, The environment in which we live and work has two basic elements: the external, Over which we have, as yet, no control, and the internal, which can be maintained at a specified condition according to our needs. The three major sub,ects for which internal environmental control is considered are: (4 people (b) machines (c) processes. While the conditions for each may differ, frequently there are common requirements. In the case of people, the requirements are often referred to as ‘comfort’ or ‘environmental comfort’ conditions. Environmental control is sometimes considered only in terms of the ability of a thermostatic control system to maintain specific conditions, but this is a narrow concept. It is necessary to consider the internal environment in terms of the overall building design, as the selection and construction of the building fabric may have a marked effect on the environmental performance and energy consumption. Equally, the selection of suitable plant and equipment may also affect the same parameters. In the past, the achievement of a specified environment tended to ignore the efficient use of the energy utilised for the purpose. Since the fuel crisis of 1973/74, this attitude has radically altered, and energy conservation is considered as a major design parameter in all building services systems. In the UK approximately half of the overall energy is used in building services, overlapping with the domestic sector, which in its own right consumes about a quarter of the overall total. As both sectors are directly related to the internal environment, there is considerable potential for energy conservation by suitable integrated design and selection of equipment. IEE PROCEEDINGS, Vol. 135, P t . E , N o . 3, M A Y 1988 The use of electrical energy is important in all forms of environmental control, whether it is for the supply of thermal power, circulation of air and water, or control. Apart from thermal power, where the choice of fuel is often governed either by its availability or the apparent economics during the design period, electricity will virtually always be involved with the other elements. The use of particular energy sources such as oil, gas, coal, electricity, etc. may be governed by the specific application. The comparison of fuels in terms of economics and costs to the client, as distinct from the primary energy consumption for each fuel, is important and needs to be considered in selecting building services systems, but is an indirect element of environmental control. the occupants. Fig. 2 illustrates the elevation in temperature required to compensate for increasing air movement. V ’r 3.2 Internal environment The indoor environment should be safe, appropriate for its purpose, and pleasant to inhabit. The parameters to be considered include the thermal, acoustic and visual conditions. 3.3 Personal comfort In human terms, an individual senses skin temperature, not room temperature, although the latter affects the former. The body loses heat by evaporation of moisture from the skin, convection to the surrounding air, and radiation to, or conduction with, cold surfaces. These mechanisms, together with the degree of activity and the type of clothing worn, tend to maintain the skin temperature constant (except for exposed extremities) over a wide range of environmental conditions. The narrow zone of real comfort conditions is often classified as neutral or comfortable. This is shown in Fig. 1 in terms of temperature, and illustrates the degree of satisfaction for a group of people in a particular space, about the optimum neutral temperature for the group. The specified space temperature is therefore always a compromise and is only one of the criteria affecting comfort. 0.2 0 I 0.4 I I I 0.6 0.8 1.0 oir movement, mm Fig. 2 Corrections to dry resultant temperature for air movement 3.4 Temperature and humidity The term ‘space temperature’ has been used so far to avoid confusion. Most people assume that space temperature, specified in terms of the dry bulb air temperatures, defines levels of warmth. The previous comments indicate that this may not be valid, although temperature detectors in common use are mainly calibrated for, and measure, dry bulb air temperature. Alternative temperature indices may provide better definitions of comfort conditions, or are used for design calculations: these include equivalent, effective, globe, dry resultant and environmental temperatures. Resultant temperature t,,, is considered to be a measure of comfort dependent on internal dry bulb temperature tai, mean radiant temperature t, and speed of air movement u as defined as follows : (1) tres = Ctr + taiJ(lOu)I/C1 + J(1Ou)I Give that the recommended values of t,, are those in Table 1, it is possible to adjust room temperature detectors or thermostats to a level suitable for comfort, for any mean radiant temperature and air velocity. 3.5 Limits - 0 - 5 -4 -2 0 2 4 5 departure from neutral temperature,T Fig. 1 Comfort vote for personnel, at around the neutral temperature for varying criteria Comfort scale : hot warm slightly warm slightly cool cool cold Other important parameters that affect comfort are the radiant temperatures of the surfaces surrounding the space, and the relative humidity and air speed in the space, all of which can have a marked effect on the space temperature necessary to provide optimum satisfaction to IEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y I988 Limits need to be applied to any specified comfort conditions, particularly in the case of temperature and humidity. Generally, in terms of human comfort, limits of f 1°C about a specified temperature and a relative humidity (rh) of *lo%, about a mean of 50%, will be acceptable. Limits more critical than is necessary will create additional and unnecessary costs. There may also be statutory limits which have to be applied in terms of energy conservation. In the UK since 1974, outside the domestic sector, space temperatures now have an upper limit of 19°C. This is only a partial limit, because the reference covers only the heating. To complete the limit, the regulation would have to specify an upper limit of 19°C for heating cycles and a lower limit of, say, 25°C for cooling cycles. Between these two limits there would be neither heating nor cooling input. The level of humidity in a space can have a considerable impact on comfort, but in a heated building there is a limited range of control over its value. Artificially increasing the air change rate by opening doors and windows is unlikely to be acceptable in winter, and is a palliative in summer. Fortunately, the band of comfort conditions in humidity terms is fairly broad for most people, and often occurs, in practice, internally. Below 107 Table 1 : Recommended design values for dry resultant temperature Type of building Assembly halls, lecture halls Canteens and dining rooms Churches and chapels: up to 7000 m3 >7000 m3 Dining and banqueting halls Factories: sedentary work light work heavy work Flats, residences and hostels: living rooms bedrooms bathrooms Hospitals: corridors off ices operating theatre suite wards and patient areas Hotels: bedrooms (standard) bedrooms (luxury) Laboratories Offices Restaurants and tea-shops Schools and colleges Shops and showrooms Swimming baths: changing rooms bath hall Warehouses: working packing - and . - spaces . storage space trms ("C) 18 20 18 18 21 19 16 13 21 18 22 16 20 18-21 18 22 24 20 20 18 18 18 22 26 16 13 approximately 35% rh, static electricity effects occur, and noses and throats may be affected; above, say, 65%, the effect of stickiness may be felt. Air conditioned systems are normally designed to avoid these extremes. 3.6 Visual and acoustic parameters The acoustic and visual impact on comfort conditions is extremely important. The correct level of illuminance for a particular task is important in its own right, but the overall aesthetics are a combination of the lighting level, the lighting source, the architectural finishes and their reflecting properties, furniture and equipment. These aesthetics contribute to the comfort of the occupant. Sound, in terms of personal comfort, is also related to the particular task. People's reaction to sound varies according to age and situation. Acoustics is both complex and subjective, and only a broad outline is included for the purpose of defining general criteria for comfort. Because the response of the ear is non-linear and less sensitive at low frequencies, it perceives equal loudness for various combinations of frequency and sound pressure levels, units of loudness being defined in phons. Sound pressure is a fluctuating air pressure sensed by the ear. The fluctuations are minute in relation to atmospheric pressure; sound pressure levels are specified in decibels The levels are created by the sound power (the power transmitted by the sound waves) which is normally considered only in reference to a sound source. Sound power levels L are also referred to in dB: L = 10 log (W/W,) decibels (2) where W is source power (measured in W) and W, is reference level (normally 1 pW). Sound pressure is proportional to the square root of sound power. 108 Acoustic control does not form part of the automatic controls covered in this review. It is normally part of the design and equipment selection process of the heating ventilating and air conditioning (HVAC) system. The incorrect selection or use of automatically controlled dampers in the ductwork systems can contribute to noise problems, as can rotating machinery which may transmit noise through structure, pipework or ductwork. 3.7 Machines and processes Apart from comfort criteria for personnel, there are two other areas where environmental conditions may be important: machine rooms and process plants. The former covers spaces such as computer rooms and medical machine areas and the latter covers areas such as electronic manufacturing or food processing factories. In many ways the criteria are similar to those for personal comfort, but there may be requirements for closer limits and, in particular, air filtration becomes a significant factor, the number and size of particles being very closely defined according to the process. In certain critical processes, the air movement patterns are also specified, laminar flow probably being the most difficult to achieve. While temperatures are often specified with limits of not greater than k0.25 or fOS°C, with humidities of - 2% rh or better, two points should be made: (a) Limits specified may be unnecessarily stringent and need to be questioned. As an example, computer rooms in the past needed close limits if the machines were to operate correctly, but nowadays this not normally necessary. (b) The achievement of conditions throughout the treated space. Strictly, the specified conditions can normally be achieved only at the point of detection, the variation throughout the remainder of the space being largely dependent on good plant design and distribution of the heating and cooling media. + 3.8 Safety requirements In environmental control, the specified conditions and their limits have to be achieved, but generally only during normal periods of occupation. It is therefore necessary to consider the environmental conditions necessary under abnormal circumstances. Examples include emergency or maintained lighting levels when the normal system breaks down or during unoccupied hours, the low limit temperatures to be maintained to prevent freezing or damage to equipment and furniture and the maintenance of humidity below a specified dewpoint condition to prevent condensation on cold glazing. 3.9 Usage and plant The operating patterns of plant usage vary considerably in any particular building and from one to another. The plant sizing, hours of operation and functional performance are interrelated as well as being dependent on other external factors. To design a comprehensive control system, an understanding of these matters is essential, and a summary of the main features follows. 3.10 Plant operating periods Periods of plant operation should be optimised so that comfort conditions are achieved during the occupied periods within those areas of the building being used. With the exception of special buildings e.g. museums or art galleries, and special areas e.g. computer rooms, the specified conditions are not required outside occupation periods and during the unoccupied periods only protecIEE PROCEEDINGS, Vol. 135, P t . E , N o . 3, M A Y 1988 tive conditions such as frost protection and security lighting are normally required. For mechanical services plant, such optimisation is achieved by variable switch-on and (switch-off) times for the plant so that the required conditions are reached as the occupation period commences. Optimisers may also provide a variable stop time, set for operation some time before the building occupation ceases. Lighting systems will normally be switched independently of the mechanical plant, and switching may be automatic, manual or a combination of both. Arrangements should be made to limit the lighting levels according to the task, e.g. daytime office work and night-time office cleaning. The switching requirements may often be programmed through a building management system, that has been provided primarily to control other building services. 3.11 Intermittent heating and cooling The calculation of loads for steady state and cyclic situations leads naturally to consideration of the effects of running the plant intermittently to satisfy only the specified environmental conditions during periods of occupation. Inherent in this are the following: (a) the preheat period necessary to bring the building up to temperature under varying climatic conditions; in particular, on the coldest day for which the load is calculated (b) the thermal response of the building during preheat, which will depend on its construction, insulation and ventilation (c) the thermal response of the plant when first switched on ( d ) the ratios between preheat, normal heating and plant-off periods (e) the relative running and capital costs. 3.12 Matching plant output to load Boilers and chillers are selected to match the maximum heating and cooling design loads with, often, a known standby capacity. To obtain maximum efficiency, the control system should be designed to control the plant without the standby capacity being normally on line. In most buildings the plant operates for the greater proportion of its life at an output well below the maximum design figure. Plant should be selected with the capability of being turned down to match the minimum normal load requirement and the control system must be designed so that this turn down is accomplished in accordance with the varying load. The overall efficiency of plant operation is normally improved if the plant and controls are selected on the basis of modulating operation, rather than start/stop cycles. It is necessary that the degree of tolerance permitted from the desired temperature be clearly defined and not invalidated by incorrect selection of boilers or chillers. 3.13 Zoning The efficient operation of any control system in terms of energy consumption and environmental comfort is governed to a very large extent by zoning the building in accordance with differing usage patterns and the spatial planning for accommodation. Because a large open-plan officewith South and West facing aspects cannot be adequately controlled from a single space temperature detector, due to the solar gains on each face varying with time, zoning is required. There are several identifiable areas I E E PROCEEDINGS, Vol. 135, Pt. B, No. 3, MAY 1988 which affect zoning and the adequacy, or otherwise, of the final control system, and they can be interactive. 3.14 Internal conditions and gains The varying usage of portions of a building will indicate heating and cooling loads which differ from day to day, or season to season, because of differences in occupancy, process heat gains and specified environmental con&tions in the spaces. Each portion may constitute a zone with separate controls to satisfy the environmental requirements. 3.15 External load variations Heating and cooling loads in various parts of the building vary because of solar effects, changes in direction and intensity of wind, and changes in outdoor conditions. The effect of these variations may suggest splitting the building into zones of aspect. This has the effect of simplifying the control problems and reducing the overall energy consumption. A further split into upper and lower zones should be considered on tall buildings where the exposure at the higher levels may lead to increased heat losses and also where one zone per aspect may create excessively large plants. Zoning based on the proximity of other buildings, which shelter or shadow the building being zoned, should only be carried out after careful consideration, since the configuration of neighbouring buildings may change after the system is designed. Inner areas of buildings, more than 6 m from the perimeter, are not usually affected by external load variations. Corner areas that are fed from two aspect zones need special detailing to ensure that the two zone inputs do not cause local discomfort. 3.16 Construction Tall buildings may suffer from stack effects causing uncontrolled heating to the upper floors. These can be alleviated by sealing off stair wells, lift shafts, and other vertical openings. However, with or without horizontal zoning, the use of terminal controls will overcome this problem. Spaces having large areas of glazing may require special treatment as independent zones. 3.17 Economics Piping arrangements, plant space and ductwork distribution will, in many cases, be governing factors in selecting the number of zones. However, the segregation of those portions of the building which are not being used, or require different conditions from their neighbours, may well justify the expenditure on extra zoning, both economically and in the context of energy conservation. 4 Theory Mathematical control theory is extremely well documented in text books, and forms part of the curricula for all electrical engineering courses, and it is not the itention to cover it here. There are, however, some texts which deal with the subject as it relates to HVAC plant [l]. This Section identifies those areas particularly relevant to the subject generally [2]. 4.1 Control modes A controller can be made to operate a final control element (FCE), e.g. a valve, damper or luminaire, in a number of different ways in response to a signal. The way in which the FCE acts in response to the signal is known 109 as the control mode. There are several principal control modes, sometimes used singly or in combination, while a number of variations also occur. The control mode does not define the means by which control is effected, which may be through mechanical, electro-mechanical, electronic or pneumatic systems. Apart from the on/off mode, all other modes are continuously variable (modulating) and the means of obtaining the signal were all based on variations of the imbalance obtained when the resistances in the legs of a Wheatstone bridge were altered. Modern systems now use a bridge network with voltage division capability to provide the necessary facilities. some of the characteristics described under Section overshoot a 4.I. 1 On/off control: On/off control provides only two plant outputs, maximum (on) or zero (off). The control sensor usually takes the form of an on/off thermostat, pressure switch, humidistat, etc. and operates so that when the controlled variable is below the set point, the contacts close; this is known as direct acting. The reverse operation i.e. contacts made when the controlled variable is above the setting, is said to be reverse acting, and devices with changeover contacts are common. There will always be an interval in between the contacts making and breaking when no signal change can be given. This range, where no control signal change occurs, is generally referred to as the differential. Since on/off control can normally produce only two plant outputs, cycling is bound to occur, see Fig. 3, and such control is '18 I I I I I I I I I I time ! ZL Fig. 3 Action of onloff controller more suited to high capacity systems where the time taken to reach design temperature is long. It should be noted that the temperature swing is wider than the differential, owing to the thermal inertia of the system being controlled. Simple room thermostats used for heating applications often have a slow response characteristic, resulting in wide switching differentials. This problem is often solved by the addition of an accelerator in the form of a very high resistance heating element which is energised only when the thermostat is calling for heat. The effect of this is to heat the sensing element artificially, thus anticipating the effect of the space heating on the thermostat. This increases the speed of response, and reduces the switching differential, as shown in Fig. 4a. There is a complementary effect associated with this particular arrangement. The ratio of on to off periods of the thermostat with increasing space load varies the internal heat input to the thermostat, and alters the controlled condition as indicated in Fig. 4b. This variation is normally acceptable, but it does effectively produce a proportional band (see Section 4.3), and the thermostat 110 load, % b Action of thermostat fitted with accelerator Fig. 4 * Corresponds to a small differential in space temperature together with a variation in the thermostat enclosure temperature equivalent lo the differential of the nonaccelerated thermostat There are certain specialised forms of on/off controller which permit multiple stages of plant capacity. These include multistep thermostats and step controllers. The former are uncommon except for specific applications, but the latter are frequently used in conjunction with detectors and conventional controllers and solid state versions are now replacing the rotating cam types. 4.12 Proportional control: Proportional control action refers to a control element having an output signal proportional to the change in its input signal. The proportional band is the range of input necessary to produce the full range of control output. It can be expressed in terms of a physical quantity (e.g. "C, Pa, '?4 humidity, lux, etc.) or as a percentage of the controller scale range. If the scale range of a temperature controller is from 20 to lOO"C, and the proportional band setting is such that the controlled variable must change through 100°C to make the valve move from full open to shut, then the proportional band is 100/80 = 1.25 or 125%. If a change of only 20°C is required to bring about this same 100% control action then the proportional band is 20/80 = 0.25 or 25%. Alternatively, in the latter case, the proportional band may be said to be 20°C. Fig. 5 illustrates the relationship between the control action and the proportional band width, and shows that the controller will give the desired value corresponding to the set point at only one position of the FCE. This occurs at the 50% open position. The diagram is drawn for a heating system. Under all other load conditions, within the range of stable control, some degree of offset (a sustained deviation) will be present depending on the proportional band setting and the prevailing load. For a controller with proportional only action, the output signal is given by : where k p is the proportional control action constant (equal to the reciprocal of the proportional band), fii is the input signal, and Po is the output signal. 4.7.3 Integral control: A correcting element may be arranged to remain stationary when the controlled medium is at the desired value, and move in a corrective manner at an increasing speed that is proportional to the I E E PROCEEDINGS, Vol. 135. Pt. B, No. 3, M A Y 1988 deviation from the desired value. For a controller with integral action only, the output signal is given by : by : r (7) (4) where k, is the integral control action constant, and 8 is time. 6o t I 0 100 4.3 Availability of various modes The stand alone proportional controller used to be the most common in use despite its inherent offset problem, I I I I 1 J 75 50 25 0 valve p o s i t i o n (%) open closed time- 7------ u c - offset remaining if controller h a s proportional action only U - 0 C I c time t , ! .I! " oc .Q :or t i m e d ,-.7 5 r 1 c > a 25 Fig. 5 time Action of a proportional controller 4.I .4 Derivative control: A correcting element may be set so that its speed of operation is proportional to the rate of change of the controlled variable. This action is used to eliminate overshoot during a fast load change. Derivative control is mainly applied in special process systems. For a controller with derivative action only, the output signal is given by : Action of proportional plus integral ( P + I ) controller Fig. 6 +I I where kd is the derivative control action constant. 4.2 Combinationsof basic modes There are many combinations of the basic modes, but apart from the stand alone proportional controller, the most common combinations are: ( a ) Proportional plus integral (P I) control: This mode combines the stability of proportional control with the accuracy of the integral mode to eliminate offset. The behaviour of P + I control is shown in Fig. 6, and the output signal is given by: + Bo = -k,,pi - k, s /3i d e (6) (b) Proportional plus integral plus derivative (PID) control: This form of control combines the advantages of (P + I) control with derivative, to combat sudden load changes, while maintaining a zero offset under steady state conditions (see Fig. 7). The output signal is given IEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y 1988 Fig. 7 Action of proportional ( P + I ) plus derivative (PID)controller 111 because the cost of adding the additional mode (term) or modes (terms) was expensive and only justified where very close control tolerances were specified. The advent of the microchip has effectively made it cheaper generally for manufacturers to provide all three terms, rather than tailored units, and depending on the application the same unit can be used as P, P + I, I or PID. 4.4 Time lags The full effect of corrective action is not immediately apparent in the controlled medium, owing to various time lags, which are functions of the plant characteristics, involving units of quantity, potential and time. The most common types of lag are: 4.4.1 Dead time: The time interval between a change in a signal and the initiation of a perceptible response to that change, see Fig. 8. 4.4.2Distance-velocity lag: The time between a signal being sent to an element and the element starting to respond, arising from the finite speed of propagation of the signal, see Fig. 8. I y ' w I ,I I valve movement Fig. 8 I time Transfer functions of a typical plant A Calorifer coil temperature B Calorifier secondary temperature 4.4.3 Exponential lag: An exponential lag occurs when the change with time in the output from an element or system (resulting from the application of a step change in the input signal to that element or system), is of simple exponential form. In heating and air-conditioning applications, a step change in input signal to a plant rarely produces a pure exponential characteristic at the plant output, partly because of distance-velocity lag and partly because the signal is generally passed through a series of stages. For example, if the position of a three-port valve, feeding a calorifier is changed, in order to change the temperature of the water flowing on the secondary side, the following time lags are involved (relating to Fig. 8 which illustrates the general shape of the transfer functions of such a plant): (a) distance-velocity lag, being the time taken for the hotter water leaving the mixing valve to reach the coil (b) time lag which occurs in raising the temperature of the coil (c) time lag which occurs in raising the temperature of the water in the calorifier. The time lag described in (b) is associated with a temperature/time relationship which, to all intents and 112 purposes, is a pure exponential (curve A). The temperature/time relationship in (C) is not a pure exponential (curve B) because its shape is dependent upon the form of the preceding temperature/time relationship. Curve A has a time constant of T . In curve B, the time constant is not valid in the sense of the simple exponential mathematical expression, but a notional time constant of T, as illustrated, is sometimes employed if control equipment and plant are to be analysed. 4.4.4 Capacity lag: This lag may be defined as a capacity for storing energy which may be on the demand side of the process e.g. heated water in a tank, or on the supply side e.g. the hot water in the primary heating coils. Capacity lag will occur when satisfying this demand. In a single capacity process this lag would be exponential, but in practice most processes are multicapacity. Where heat is transferred from one capacity to another transfer lag also occurs. These lags tend to slow up response, and vary considerably according to the process in hand and the magnitude and frequency of the load changes. They may also affect the choice of control mode. An integral mode will provide a temperature with close limits when used to control the air temperature directly downstream of a heater, but if the same heater battery is to be controlled from the extract duct this mode is not suitable. The controller operates over a very narrow band of temperature and in the first case, there is only a minimal lag between the detector calling for a change in output and sensing the resulting change. In the second case, the lag time (comprising capacity, transfer and distance-velocity elements) is large, and the change of output will continue until the detector senses the change, which may occur only after the general space temperature has altered very considerably. 4.5 Open and closed loop control Control systems are applied to control loops, each loop normally comprising one section of an overall plant, e.g. reheater, calorifier, smoke alarms. Loops are normally defined as being open or closed, most in the HVAC field being closed. When the condition of the controlled variable changes in closed loop control the sensor detects the change and initiates correcting action to the final control element. The effect of this is reflected in the controlled variable and reassessed by the sensor which continuously provides feedback to the controller. Examples of this are space temperature control, control of secondary domestic hot water system (DHWS) temperature, and static pressure control of supply fan volume in variable volume systems. All modes of control may be used to provide closed loop control. Open loop control does not include feedback of the type described above. The simplest form of such a loop would be the detection of smoke, when a local and/or remote alarm is initiated by a smoke detector without any feedback to the detector. A more common version in the HVAC field is the use of an external sensor to control the output from an air curtain in a shop entrance. In this case the output from the heater battery serving the air curtain would be modulated in accordance with the outside temperature so that, for example, at 0°C externally there would be full output, and at 15"C, no output. The external sensor is not affected by any variation from the final control element (heater battery control valve), and therefore there is no feedback. Only on/off or proportional modes of control may be used for this type of loop. IEE PROCEEDINGS, Vol. 135, Pt. B,No. 3, M A Y 1988 I 4.6 Stability analysis In the past, little attention has been paid to the stability of heating and air conditioning systems at the design stage. Generally speaking, systems have depended for stability upon the large thermal capacity of traditional and heavyweight buildings with large capacity boilers, heat exchangers, etc. However, with the trend towards lightweight and better insulated buildings, and the use of air conditioning and low capacity boilers and heat exchangers, it is necessary to consider system stability in greater detail. Stability analysis makes this possible. Such analysis is normally complex and the analytical solutions require numerical data for a wide number of parameters to test the stability criteria. It should also be added that there may be difficulties in applying these techniques to conventional HVAC systems which frequently have nonlinearities due to actuator reactions, heat transfer characteristics, and limited plant outputs. At present, suitable techniques for the HVAC field are in their infancy. 4.7 Valve parameters In defining the control modes it must be remembered that the selected controller operates an actuator which normally forms part of a valve assembly (or damper assembly) which is controlling the output from a heat exchanger such as a heater or cooler battery. The aim of the vast majority of HVAC control loops is to achieve a linear relationship between thermal power output and valve spindle movement. The flow characteristics of the valve have a marked effect on heater and cooler battery outputs, and correct selection is an extremely important part of control system design. 4.8 Basic valve characteristics The relationship between valve spindle lift and area of the valve opening is known as the valve characteristic. In the case of shoe type (or rotary) valves a similar relationship exists between shoe rotation and area. The valves in general use for HVAC systems are shown in Fig. 9. There is a large range of possible valve characteristics but those most commonly encountered in control systems are : (a) linear, where the orifice area is directly proportional to the valve spindle movement, and the flow varies a b linearly with spindle lift (this should not be confused with power linear which is basically achieved with (6) and (c)) (6) characterised V-port, with a characteristic falling between linear and equal percentage (c) equal percentage, or similar modified parabolic, where equal increments of valve spindle lift provide an equal percentage change of the previous area. The characteristic is represented by: s = log (2) where s is change in valve stroke (%), V, is volume flow rate at zero stroke if valve was characterised to this point (m3/s), and VI,, is volume flow rate with valve fully open (m3/s) (d) quick opening, where the flow increases very rapidly from zero for small valve spindle movements, with a fairly linear relationship between flow and spindle movement. Beyond this initial movement the flow rate varies more slowly with increased spindle movement. Such valves are primarily used for on/off service. The terminology used to describe valve characteristics varies considerably, and it may be necessary to check with manufacturers if there is any doubt. Fig. 10 shows in stylised form the basic characteristic curves for valves described in (a) to (4. The basic characteristics are obtained by measuring flow against a constant pressure drop across the valve for all positions of the valve. In these circumstances, the valve is said to have an ‘authority’ of unity. In practice, these curves are modified as the valve authority decreases. Normally, the plug design determines the characteristics on the assumption that the plug lift will be directly proportional to the signal from the control loop. However, it is possible to achieve a particular characteristic by making the plug lift follow a particular curve not proportional to the signal and the use of software based controllers makes this easier. 4.9 Valve authority Normally, a control valve is employed to regulate the flow in a system where the total pressure drop in the circuit concerned is derived from the circulating head of a pump which should be reasonably constant. Figs. 11 and C n d e Fig. 9 Some common valve types a Three-port single seat valve d Three-port shoe type valve b Three-port double seat valve e Butterfly valve c Two-port single seat valve IEE PROCEEDINGS, Vol. 135, Pt. E , N o . 3, M A Y 1988 valve spindle lift, % Fig. 10 Stylised basic valve characteristics A Linear C Equal percentage B Characterised V-port D Quick opening 113 12 show examples of systems where the valve authority is defined by : represent the quantity of fluid which passes through a fully open control valve at unit pressure drop. In SI units, a flow coefficient A, based on the quantity of fluid in m2/s for a pressure drop of 1 Pa across the valve, has been defined in BS4740 (Part 1, 1971), to replace the existing coefficients. In practice, manufacturers' figures are published only as C, and k, values. The traditional imperial valve capacity coefficient C, is defined from: (9) where N is valve authority, P , is pressure drop across the valve (fully open, (Pa), P 2 is pressure drop across the remainder of the circuit (Pa). Suitable valve authorities in practical terms should be kept as high as possible. To achieve this, the pressure drop through the battery has to be known, or defined to suit the selected valve. The pressure drop across the valve itself is based on its flow coefficients. 4.10 Flow coefficients (capacity indices) The pressure drop across given control valves is a function of the flow coefficients, or capacity indices, which are published by individual manufacturers. These coefficients v where is volume flow rate (imperial units, gal/min), C, is the valve coefficient (imperial units), Pi is the pressure drop across valve (imperial units, psi), and sf is relative density (specific gravity) of fluid. The two indices are not compatible, but the conversion factor is given by : A, = 28.8 x a b Fig. 11 Valve authority a Three-port mixing application b Three-port diverting application C, (1 1) 4.1 1 Combination of valve parameters and battery characteristics The thermal output characteristics of heater and cooler coils do not vary in a linear manner with changing water flow rates. They tend to give a large percentage of their rated output for a small percentage of the design flow rate. The controls objective is to ensure that this nonlinear characteristic is modified so that thermal power output has a linear relationship with valve spindle movement. Fig. 13 illustrates the importance of suitable valve authority: the upper right hand quadrant of the diagram shows a stylised set of valve authority curves for both linear and equal percentage valves, while the lower right hand quadrant depicts a typical heater or cooler battery characteristic. The relationship between valve lift and power (heating or cooling output) is shown in the bottom left hand quadrant and this is a function generated from valve lift flow Fig. 12 Valve authority P ,. iP ,- P = (1 Basic two-port application (typica-I) b Two-port application,ladder arrangement Fig. 13 Stylised valve authority and power output characteristics equal percentage N = Valve authority ~ _ _ _linear ~ 114 I E E PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y 1988 a valve authority curve and the battery output characteristic. Using curve 2 (equal percentage characteristic N = 0.7) the points on the new curve are defined by drawing a series of lines a,b,, a , c , , a, b,, a, c , , etc. and then drawing lines vertically through b,, b,, etc. and horizontally through c,, c , , etc. The points of intersection d,, d,, etc. define the power output/valve lift curve. This particular curve shows an almost linear relationship between lift and output, but for comparison, the power/ lift curve is also shown based on curve E (linear characteristic N = 0.8). The latter illustrates why linear valves are not recommended for this type of application. It indicates that any valve selection which provides an output curve of this form could provide stability at or near maximum output and be unstable at low load conditions. Note that the latent cooling characteristic of the cooler battery does not follow the same curve as the total output as this may be relevant to applications where latent cooling is paramount. 4.12 Setting out control requirements To move from the theoretical to the practical control system requires receipt and understanding of data on environment and usage, plus the following conditions and tolerances. 4.13 Conditions and tolerances The design, selection and operation of overall systems are related to the specified conditions and tolerances for both the internal environment and the individual items of plant. These parameters are of particular significance to the control system, and care should be taken to ensure that the tolerances are appropriate to the application. The relationship between dry bulb temperature, wet bulb temperature and relative humidity of air are fixed for specified barometric pressures, and normally defined by a psychrometric chart (Fig. 14). Moisture content on r e l a t i v e humidity, 100 % 50 must be considered on its merits, particularly for projects outside the UK. In special areas, the tolerances may need to be maintained to f5% rh and f 1"C of the specified desired values, and in critical cases these figures could be as low as 1 2 % rh and f0.5"C. Both the general and special cases should be quoted in specific terms, e.g. 50% f 10% rh and 20°C f 2"C, or 24°C 4°C - 0°C. Fig. 14 indicates this problem where there is individual temperature control of a space, with central control of the humidity. If the specified space requirements are 22°C f 2"C, and 50% f 5 % rh, and the moisture content corresponds to the line A-B, then at 22"C, 50% rh will be achieved, but at 20°C and 24°C for the same moisture content, the relative humidity will fall outside the specified limits. Equally, at 22"C, moisture contents designated by lines C-D and E-F will not quite satisfy the humidity limits, but if the temperature varies from 22°C to the permitted limits, with either of these constant moisture contents, the humidity limits will be decisively broken. From this example, the relevance of conditions and tolerances to design is illustrated clearly. Either, there should be separate control of humidity in each space if the specified conditions are precisely what is wanted, or the tolerances should be amended so that they can be achieved with normal operation of the plant. In the example this would mean specifying 22" f 2°C for temperature control, and accepting a relative humidity of 50% + 12% - 10% for a central plant capable of holding the moisture content between C-D and E-F. In addition to limits for space conditions, those for heating and cooling source flow and return temperatures, and for particular locations within air handling plant must be specified with suitable tolerances. Select the tolerances for the correct space requirements and then provide the controls to satisfy these parameters. The use of conditions or limits of less than 1 2 % rh for humidity is not normally practical. The stability of flow temperatures for boilers and chillers may be important to the control of individual plants elsewhere in the system. Again, any limits specified must be within the capability of the selected plant and control system. Limits of f 2 " C and f0.5"C for heating and cooling, respectively, are the lowest figures likely to be achieved under all load conditions. + 5 Equipment and systems In this Section prominence is given to the electric/ electronic elements of control systems rather than the purely mechanical components e.g. valve bodies, or pneumatic controls. Electronics encompasses microprocessorbased systems and building management systems. Until we consider building management systems, most control systems loops comprise a sensor, a controller (except in the case of the on/off mode), and a final control element (or elements) that is normally a motorised valve or damper assembly. There are wide variations across each of these elements and the more common types are described with some indication of their specific features. d r y b u l b temperature, Fig. 14 "C Psychrometric diagram of conditions and tolerances the chart is indicated by horizontal lines in units of kg/kg. Humidity in the range of 40-70% rh and temperatures of 19 to 23°C will normally be acceptable, if the air velocity is low enough to prevent the sensation of draught. There may be situations even for general comfort where these tolerances are too wide. Each case 1EE PROCEEDINGS, Vol. 135. Pt. B, N o . 3, M A Y 1988 5.1 Sensors Irrespective of the form of sensing element or the parameter being controlled, the siting of the elements is vitally important. Pipework and ductwork applications require that the total active portion of the element is immersed in the fluid flow, and where large cross-sectional areas are encountered, averaging elements serpentined across the area should be considered. In space mounted applica115 tions, the moutning surfaces should not be affected by solar radiation either directly or indirectly, nor should they be part of hot or cold structural bridges. In large spaces it may be difficult to select a representative position for a single detector, and consideration must then be given to multiple averaging detectors, split plant or acceptance of a reduced level of overall control. Methods of sensing are described for the common parameters in HVAC systems, i.e. temperature, pressure, humidity, flow and enthalpy. Different sensor mechanisms are available for each parameter, and manufacturers usually select particular elements for use in their own ranges of equipment. The selected elements are suitable for general applications in building services. Sensitivity and drift in calibration are becoming more important with improving standards for environmental control. Both these parameters can have a marked effect on comfort and energy consumption. 16). Water should flow past the sensing element at not less than 0.3 m/s to minimise the time lag, whereas air should circulate around the sensing element at a minimum of 2 m/s. 5.1.1 Temperature: The most commonly used temperature detectors rely on either thermal expansion or electrical changes due to temperature variations. The familiar bimetallic strip, and rod and tube elements both rely on the differential thermal expansion of two dissimilar metals rigidly fastened together. Sealed bellows are used as temperature sensitive primary elements. The bellows are evacuated, and partially filled with a volatile liquid such as Freon, a proportion of which is boiled off as a vapour until an equilibrium pressure is reached. This pressure is a direct function of the temperature of the liquid, particularly at the liquid surface. The change in pressure creates movement of the control mechanism. Remote bulb sensing elements are an extension of the vapour-filled bellows principle, a remote bulb being connected to the bellows by a capillary tube. Resistance bulbs operate on the principle that the electrical resistance of certain kinds of wire (nickel, copper, platinum) change with temperature. Usually a resistance bulb is made up of a coil of wire wound round a core and installed in a rigid capsule. Thermocouples are formed when two dissimilar metals are welded or twisted together at one end and this junction is heated. A voltage, proportional to the temperature difference between the welded and free ends, is then developed. The pairs of metals are usually copper/ constantan, iron/constantan, chromel/alumal or platinum/platinum-rhodium. Thermistors are semi-conductor devices which have an inverse relationship between temperature and electrical resistance. This relationship is nonlinear, but the output can be made approximately linear over a range of 10°C by using linearising resistors. These are very sensitive detectors up to 100°C. In any practical system, the response to a change in input will not be instantaneous. This delay in response is called lag, and the lag coefficient is defined as the time needed to reach 63.2% of the total change. Fig. 15 gives the response curve for various sensors. For example, from curve C, the lag coefficient is 1 min. It will be seen that a protective tube or pocket causes the lag coefficient to increase considerably, and also that sensing elements respond much more quickly in moving liquid than in moving air, since air has a very low thermal capacity and conductivity. Another factor influencing response is the type and velocity of the fluid in which the detector is immersed. A low fluid speed, with respect to the sensing element, greatly increases the resistance to heat transfer (see Fig. A Thermistor in water B Thermistor in pocket in water time, rnin Fig. 15 1 I6 Typical temperature sensor response curves C Resistance bulb in water D Thermistor in still air I I I I I 0.2 0.4 0.6 0.8 1.0 water velocity, ms-1 Fig. 16 Effect of water velocity on heat transfer 5.1.2 Pressure: For pressure sensors, bellows, diaphragms, Bourdon tubes, or similar devices may be used. The medium under pressure may be transmitted directly to the device used to operate the mechanism of a pneumatic or electric controller. Rate of flow, quantity of flow, liquid level, and static pressure may all be controlled by pressure sensors. The most common types of pressure sensing devices utilise a bellows or diaphragm acting against a spring. Elements of this type are very sensitive, being able to detect pressure changes of about 10 Pa and can be used over a range of absolute pressures from 0.15 Pa to 150 Pa. The Bourdon tube is made from a flattened thin-walled tube formed into a C shape and sealed at one end. As the pressure is applied to the open end, the tube tends to straighten out, producing movement at the tip, proportional to the applied pressure. 5.1.3 Humidity: The primary element of a humidity sensor can be human hair, nylon, wood or other substance that responds to humidity change. As the moisture content of the surrounding air changes, moisture is absorbed or released and the element expands or contracts, operating the mechanism of the controller. A biwood element operates on a similar principle to the bimetalic element for temperature measurement, but in this case two woods with differing moisture absorbancies are used. Humidity sensing elements suitable for electronic application and control may also consist of metallic contacts fused to a piece of glass or plastic. Electrical contact is maintained between the two strips by a hygroscopic salt, e.g. lithium chloride, painted over the surface of the material. The resistance of the salt varies with the amount of moisture absorbed. IEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y 1988 5.1.4 Flow: Existing flow measurement instruments operate on a variety of principles, but the most widely used are based on the differential pressure across a restriction. This readily lends itself to either electric or pneumatic transmission and control. The restriction is installed in a duct or pipe to create a pressure differential that bears a square law relationship to the rate of flow. This restriction may be an orifice plate, a Venturi tube or a flow nozzle. The orifice plate is widely used because of its convenience and economy, and reliable data are available for its calibration. Extensive use is now also made of calibrated regulating and control valves for the same purpose. Positive displacement and turbine instruments are commonly used, and magnetic flux flow meters are now available. 5.1.5 Enthalpy (total heat): A measure of enthalpy is obtained using temperature and relative humidity sensors (often mounted in a common housing) which feed their signals into a controller, the output of which is characterised to give an approximately proportional signal. Because the major application is optimising the use of fresh and return air in air conditioning systems, some devices include a four input controller (i.e. inputs related to the temperature and humidity of both fresh and return air). The enthalpies of the two air streams are compared, and used to control mixing dampers or heat recovery equipment. 5.2 Actuators An actuator is a device that responds to the signals from a controller, and enables power to be transmitted to a final control element. A variety of types of actuator exist, the most common of which are detailed here. The two characteristics which most affect actuator selection are the available torque (and its efficient transmission to the final element) and stroke time, which may be significant in terms of overall system response. The most common application of actuators is to the operation of valves and dampers. 5.2.1 Electric motors: Electric motors in the 5 to 50 VA range, operating through a reduction gear train, produce relatively high torque at low speeds. The motors are usually single-phase, and may operate on either line voltage or extra-low-voltage supplies. Reversible motors are essential for modulating systems, but either reversible or unidirectional motors are suitable for two-position operation. In unidirectional motors the limits of operation are determined by internal limit switches. Where safety features are required, motors may be fitted with a spring return mechanism that returns the motor to a specified condition when the normal power fails. Alternatively, an internal power pack with rechargeable batteries may be incorporated. Some electric motor actuators are also designed to drive a screw which is part of the actuator spindle; others are arranged to provide a linear motion of the spindle directly proportional to the detector signal, and some can provide a linear motion which follows any required characteristic related to the detector signal. 5.2.2 Solenoids: Solenoid actuators are normally electromagnets with a movable armature linked directly to the device to be controlled. However, the use of such actuators with dampers is unusual. The most common solenoid actuators provide two-position operation, and generally return to the de-energised position on power IEE PROCEEDINGS, Vol. 135, P t . B, No. 3, M A Y 1988 failure, and are therefore suitable for failsafe operations. To achieve the maximum force from these valves, the armature travel is relatively short. Their application is normally limited to small size valves, and they have a very restricted maximum differential pressure rating. A particular type of solenoid valve may be used for modulating control whereby a variable voltage is applied to the solenoid, and the valve spindle takes up a position proportional to the applied voltage. This arrangement normally utilises very restricted valve spindle movements. 5.2.3 Pneumatic actuators: Pneumatic actuators comprise a piston, or diaphragm, to which air pressure is applied to provide a linear displacement. The construction of the actuator and its method of connection to the valve or damper determines whether, with increasing air pressure, the fluid flow is increased or decreased. Most pneumatic actuators are of the single action type in which the force on the diaphragm is opposed by a spring, and the net force applied to the valve or damper is the difference between them. When the air pressure is removed, the spring will return the valve to the selected extreme position, and this may be used for failsafe requirements by specifying the necessary conditions. In certain process applications, double acting actuators are employed in which air is applied to one or other side of the diaphragm or piston while exhausing the opposing side. In these cases, only the air is used to drive the actuator, and there is no automatic failsafe feature. Single action actuators operate from air at pressures from 100 to 250 kPa. However, air pressures up to 1 MPa are used for double acting actuators because of the high forces required, although this is rare in building services applications. When pneumatic actuators are required to deliver a large power output, or operate against variable forces, the position of the actuator spindle may not be proportional to the signal pressure from the controller. To overcome this, a pneumatic relay, known as a positioner, is fitted to the actuator which uses main air line pressure to ensure that the actuator is correctly positioned for a given controller signal. To do this, a positive feedback of actuator position is used. 5.2.4 Electrohydraulic actuators: Electrohydraulic actu- ators consist of an oscillating pump, pressure cylinder and piston for opening, and return spring and bypass valve for closing. A variation, sometimes used for control valves, employs wax filled actuators in which the change in volume associated with phase change in the wax is used to operate the valve. 5.2.5 Self operating actuators: Self-operating actuators are based on the pressure change applied to a sealed liquid or vapour-filled bellows system which then operates the spindle of the valve directly. When the temperature changes, the liquid or vapour in the sensing element expands or contracts, and the consequent pressure change is transmitted, normally via a capillary, to the bellows system which acts against a return spring and moves the valve spindle. Radiator valves frequently employ this form of actuator. Some wax operated actuators may be regarded as self-operating. 5.2.6 Manual actuators: Manually operated actuators are normally added to automatic control valves to permit the normal actuators to be overridden. Various versions are available which allow valves to be manually positioned in one or two specific positions or in any position. 117 I 5.3 Valves A valve which is aqtomatically controlled to regulate fluid flow from zero tb full quantity is generally a control valve. Manually ope ated valves which can be made to perform the same fu ction also have a control function, but they are more co monly referred to as regulating or isolating valves, or y their means of construction, e.g. gate or globe valves. he type of control valve for a specific duty depends oq the service required, conditions of temperature and pres ure of the fluid involved, and other circumstances, includ ng valve characteristics, described in Section 4.7 ‘Valve arameters’. Terminology in re pect of valves varies according to the field of applicatign. The terms used here are those generally associated yith the building services industry. The use of the alterqative terms ‘two-way’ and ‘threeway’ or ‘two-port’ and ‘three-port’, respectively, is normally acceptable. A qonventional control valve consists of four basic componeplts: (a) actuator (b) body (shown in Fig. 9) (c) bonnet, containing a packing box or gland (shown in Fig. 9) (d) valve plug (shown in Fig. 9b). The selection of the correct control valve for a system is an integral part of overall design, and an essential prerequisite for a stable system which can be properly commissioned. Whereas two position, or on/off, valves need be selected for specific throughputs under clearly defined conditions, the requirements of modulating valves need much closer attention. It has been noted in Section 4.11 that power output is not directly proportional to flow, and i 4 11 l-----l parallel Fig. 17 A Ideal 118 U varies with both valve and emitter characteristics. It is important to ensure that the valve may be shut off or opened against the prevailing pump and/or static pressures; this is particularly true of large valves, but some terminal unit control valves have a very limited tolerance in this respect. 5.4 Control dampers The following details and data on dampers and their basic application are intended to illustrate the effect of suitable selection on the stability of air flow for control purposes. Certain assumptions have been used to simplify the techniques. Where detailed selection becomes necessary, a more rigorous procedure should be adopted. The flow of air in an air handling system is regulated by control dampers in a similar fashion to the regulation of water by valves. Control may be either two-position, as in the case of an isolating damper, or modulating, where two air streams are to be mixed, as in face and bypass control. Regulating or balancing dampers are not dealt with here. 5.5 Characteristics There are two arrangements of rotating blade dampers : parallel and opposed. The relationships between damper blade rotation and flow through the damper, for a constant pressure drop across the damper, are shown in Fig. 17. These are called the inherent, or intrinsic, characteristics of the damper. Ideally, these would be straight lines, but in practice they take the form shown. In practice also, the pressure drop across the damper is not constant, but increases as the damper is closed. Consequently, the inherent characteristics are modified to the installed characteristics (see Fig. 18). 100 80 z 6 60 c e 3 z” 40 20 opposed Damper types and inherent characteristics B Parallel C Opposed n “0 20 ‘0 20 40 60 blade rotation, % 80 100 40 60 80 blade rotation, % b Fig. 18 Installed damper characteristics a Parallel blades b Opposed blades 100 I E E PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y I988 5.6 Time controls There are three basic methods of time control: on/off time switch, fixed time/boosted start, and optimum start control. The selection for a heated or air conditioned building requires a number of factors to be considered, including the following: (a) size of building and annual fuel consumption. (b) hours of occupation and length of unoccupied periods. (c) thermal inertia of the building structure (e.g. heavy or light building structure and degree of thermal insulation). (d) boiler or chiller margin. 5.6.7 Onloff time switch: Simple time switch control is usually limited to small installations such as small fan convector and unit heater installations. This method is simple, low in cost, and easy to install. The method has the disadvantage that the start time is selected to ensure that the space is at the desired temperature at the start of occupation under the design temperature conditions. This means that in less severe conditions energy is wasted. Some optimum start controllers include the facility for optimum stop. The early stop time is again determined by the comparison of inside and outside temperatures. The application of this feature is not common at present, owing to the uncertainties of prediction, and possible problems associated with stopping air circulation in ventilated and air conditioned buildings. Some of the energy saved by this arrangement is required for boost the following morning. The operation of optimum start control is shown in Fig. 19 which indicates the basic principle, coupled with frost control. Fig. 20 illustrates how this same optimiser copes with different situations including varying outside air temperatures (too). p temperature $ 3 i- $ F night minimum 2 g ._ cn C ._ typically 5.6.2 Fixed time boosted start: Fixed time boosted start is designed to reduce preheat time by allowing the central plant to provide maximum preheat capacity. Facilities for an earlier start time following a prolonged shutdown (e.g. a weekend break) should also be provided on the time switch to supply the additional heat required to bring the building up to the correct temperature for occupation. The system should incorporate a means of terminating the boost by either time or temperature. This method is now largely superseded by optimum start control which reduces the energy used for preheat in the intermediate seasons. 5.6.3 Optimum start and stop control: This is a time controller for intermittently occupied buildings which has shown substantial energy savings when compared to an on/off time switch or fixed time boosted start. It provides optimum plant start time by continuously monitoring both inside and outside temperatures to provide sufficient preheat to give the desired conditions at the beginning of the occupancy period. Early start can also be provided following prolonged shut-down, such as at weekends. Early-on and day omission devices are normally provided, and a day extension timing facility with manual setting can be added. The controller takes into account the thermal response of the system, structure, and duration of the off periods over a daily cycle. The largest energy savings are generally from buildings having light structures and with a heating system of low thermal capacity. For maximum economy, the plant should be started at the latest possible time, allowing for the minimum preheat period at full capacity. Termination of boost may be provided by an internal detector in advance of occupation time if the internal conditions are satisfactory. This detector may also be used for frost protection. The cost and performance of optimisers vary widely, and care should be taken to ensure that the model selected is suitable for the particular application. Modern versions use adaptive software which simplifies initial setting and permits the unit to monitor and correct its own performance. During unoccupied periods, control should be based on minimum inside air temperature, to prevent freezing or condensation and separate frost protection override can be provided where required. IEE PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y 1988 10°C I plant off Fig. 19 t i m e t frost and condensation protection optimised on occupation time Optimum start control characteristics with frost protection )design temperature t i m e d roccupation optimum time intermediate additional boost p e r i o d a f t e r prolonged shutdown Fig. 20 o p t i m u m start for design condition Optimum start control characteristics for varying conditions 5.7 Controllers There has been a marked change over the past decade in the ‘controllers’ used in conventional HVAC control systems. In the past, such controllers, other than pneumatic, were based on a bridge network (electromechanical, electronic or solid state) which provided, via a balance or motor relay, an extra-low voltage signal, energising either the open or close terminal of the actuator. In addition, there was, very frequently, a potentiometer on the actuator which provided feedback signals to the controller. A version of this arrangement, for an early proportional plus integral controller, is shown in Fig. 21. Modern controllers and their associated actuators can take many forms, and the overall electronics may be distributed between them. The most common ranges of controllers generally provide a ramped output of 0-10 V DC according to load demand. This signal is fed to an elec119 logue basis using setting potentiometers for each value. With the advent of softeware based control logic, the setting of each parameter has been by a structured setting-up procedure where each parameter has been selected and set via alpha numeric key pads. The digital nature of such software is thus replacing the traditional analogue controllers. tronic positioning device that may be part of, or independent from, the actuator. This device, or relay, controls the position of the actuator via a bridge and amplifier, a Schmitt trigger device, a triac switch and a feedback potentiometer on the actuator. The block diagram for such an arrangement is shown in Fig. 22 which is self explanatory. The settings at which the actuated device Fig. 21 Controller schematic 0Satchwell Control Systems Ltd. bridge circuit bridae summer amplifier 0 temp. detector p.b. actuator T1 - + - t oc EO Schmitt 7 2LV OC - - ! feedback signal (motorised valve or damper) may operate can be adjusted in terms of the voltage at which the actuator is allowed to start opening (or closing) and the voltage span (between 0 and 10) over which it will drive from one end to the other. The settings may be in voltage terms or in those of the parameters under control e.g. temperature set point (start) and proportional band (span). The arrangement may be set for direct acting or reverse acting operation. It is difficult to cover the setting variants possible in the enormous range of proportional (P), proportional plus integral (P + I) and proportional plus integral plus derivative (PID) controllers and their common cousins with different nomenclatures. Reference to manufacturers' literature is necessary, if sometimes confusing. Controllers for the HVAC industry will normally be single, two or three stage (as distinct from single, two or three term see under Section 4). This means that a controller may operate up to three stages of an HVAC plant in sequence when required i.e. a heating coil valve, dampers controlling fresh, exhaust and recirculated air, and a cooling coil valve. Other features such as dead zones (temperature bands between heating and damper operations, etc.) and compensation (the variation of set point with outside temperature) are often available. The simplest single stage proportional controller will require a set value (SV) adjustment and a proportional band (PB) adjustment. A similar two stage controller could have an additional PB setting or two: SV and two PB settings, and in the latter case the difference between the two SV's would constitute the dead zone (DZ) value. As terms are added e.g. P + I, extra settings are available for the integral action time (for each stage). Until fairly recently, the settings have been on an ana~ 120 I + Fig. 22 Block diagram of an AET series controller 0Satchwell Control Systems Ltd. In effect, the use of this form of control is direct digital control (DDC), that, in the controls field for HVAC systems, distinguishes it from conventional analogue control. It also leads directly to the growing use of software, resident in building management systems (BMS), to perform the same control functions as the independently mounted digital controllers. Whenever a BMS is incorporated into a building services system, a decision on whether to use DDC or conventional controllers is required. The use of DDC is not necessarily the best solution for all HVAC systems - initial cost, complexity of project and levels of maintenance capability are all important factors. The emphasis on defining the meaning of DDC in the HVAC controls field is deliberate. Jargon, particularly that associated with computing and its high technology, electronics/chips, etc., is a constant problem for all engineering disciplines. Nowhere is this more apparent than in the area under discussion. Automatic controls for building services sit firmly among an enormous number of interfaces, between such diverse elements as electrical engineering, mechanical and building services engineering, HVAC controls suppliers, companies with a process background who see a lucrative future in building services controls, and a multiplicity of software and computing organisations who sell building management systems. Words of one syllable become extremely important when specifying the requirements for a comprehensive controls and building management system. 5.8 Building management and automation systems A building management system (BMS) is one of a number of terms which is used to describe an integrated or overlaid system over and above the basic HVAC IEE PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y 1988 control system. Here again a more precise definition is required to avoid confusion. While standard definitions for the various terms are not known to be available, a good basis follows: 5.8.1 Building management system ( B M S ): A system which can provide management functions e.g. billing and programmed maintenance, in addition to building automation and energy management. 5.8.2 Building automation system (BAS): A system which automates the operation of building plant and services to considerably reduce the extent of manual operation which would otherwise be required. It can include energy management functions as part, albeit important, of the facilities it offers. 5.8.3 Energy management system (EMS): A stand alone arrangement specifically related to the energy management functions and efficient use of energy in a building (inherently it will include some automation functions). The terms are loosely used and this need not be a problem, but when a specification for a project is to be produced the terms need be very precise, otherwise facilities which are not required may be included, and vice versa. 5.8.4 General: Most thermostatic control manufacturers now market building automation systems to monitor and control other building services such as energy, security and fire protection systems. Other manufacturers also offer such systems, particularly in the fire and security sector, and there is a rapidly increasing number of large and small firms with basic processor and software capabilities who are entering the market. It is always advisable to question the level and validity of the software offered to perform the tasks required in the context of building services automation. Much of the software has still not been proven in practice, and it is unwise to accept these programs until they have been demonstrated on a real project. There is often a deep gulf between software capability and the necessary knowledge of building usage patterns and building services operation to produce adequate programs. One other item that requires emphasis is the possible susceptibility of all processor based systems to electrical interference, however caused. Interference phenomena and their suppression is not fully understood, and many building automation systems suffer intermittent faults as a result of this [3]. The rapid advance of microelectronics and the consequential reduction in equipment costs has made the consideration and use of these systems much more widespread. Because the technology and associated software are both still being developed, this section covers the essential principles and requirements to obtain satisfactory systems. It also covers the facilities available, and associated arrangements that are now being incorporated. The principles apply whether the system has one unit with 10-20 points, or multiple processors and outstations serving 10,000 points. The problems of communication and ambiguity lead to one other generalised statement. It is essential that the specification for any BMS/BAS/EMS is precisely detailed in terms of all performance requirements, functional sequences and clearly defined interface conditions for every facility required. Minor facets or requirements, genIEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y I988 erally accepted amongst engineers as basic to any operational sequence, will not be provided by the software unless they are identified in the specification. A detailed specification of this nature will be more conducive to a satisfactory conclusion than one which concentrates on detailing the precise technology which is to be used for each element of the system. 5.9 Basic considerations The basis of operation of these systems is to continuously scan the connected input data points and report unusual occurrences whilst carrying out control functions automatically. The centralisation of the logic equipment allows greater flexibility of operations than conventional hard wired systems and also frees maintenance staff from watchkeeping duties, enabling more effective use of manpower. If such a system is considered on any project there are essential prerequisites if it is to provide its optimum performance. (a) It must be considered very early on in the building/ plant design concept. If it is added at a later stage it will duplicate a number of other elements which are complete in themselves. (b) The client should be prepared to employ suitable staff to operate the centre and utilise all its facilities. (c) The cost effectiveness should be properly evaluated and include the following: (i) capital cost of system, including outstations, detectors, instrumentation, modified plant, standard software and wiring, less any savings for equipment which it replaces (ii) interest on capital cost (iii) value of energy savings which the system itself will provide (iv) cost of additional staff employed to operate the system, less the saving on those maintenance staff who will be replaced by the system (v) annual cost of maintaining the building automation system (vi) a substantial capital sum to cover the cost of collecting data from the building during the first one to three years of operation and producing software for optimising the energy use in the building, since much of the existing software does not cover the full range of optimisation possibilities for large buildings or complexes (vii) costs saved by using programmed maintenance co-ordinated by the system (which should include value of increased plant life), less the cost of preparing such a programme (viii) savings in using the software capability of the system to replace the interlocking relays, etc. normally used in motor control centres and control panels, set against the cost of the project oriented software. This basic list of factors leads on to direct cost details and interface problems that must be considered when such a system is contemplated. Some examples are: (a) The functions of a BMS/BAS could be achieved by hard wired control systems and the economic justification for a sophisticated system includes the fact that the engineering, site wiring and commissioning costs can be a fraction of the hard wired system. (b) If process control is to be achieved by direct digital control (DDC) then savings will occur in the elimination of local loop controllers and in the avoidance of duplicating sensors for control and monitoring purposes. (c) Energy management programs will optimise energy usage but this does not relieve the designer from 121 ular plant is off, for the period following start-up and when they sequentially follow on from an initial alarm. Many computer based systems allow various control and energy management programs, as detailed later, thus dispensing with the need for conventional items of equipment, instrumentation or controls. Ultimately, they will reduce control panels to little more than starter boards, where control relays are superseded by software. Such a system permits the logic to be changed without extensive wiring modifications, but this is not intended to encourage delayed design decisions. Planned and programmed maintenance schedules can also be produced and monitored by the computer based systems but this requires a large memory storage capability and considerable project orientated input data. his responsibilities for the correct selection of building services systems. (d) Failure of power or plant may result in a direct loss to the customer, e.g. computer rooms, specified pathogen-free animal buildings. If it can be shown that a building automation system minimises the number of failures and reduces the down time, this is a strong factor in the economic argument. BMS/BAS with full facilities will be more easily justified on larger projects, and offer the most savings where services are particularly complex. Options include fully owned systems and those where third parties own the central building automation equipment and sell a ‘remote’ supervision and control service. It should be remembered that if a BMS/BAS is not fully utilised or understood, the building services control and data collection will not be adequate, and it is possible to increase rather than decrease energy used, due to the system falling into disuse. 5.1 1 Software Software (programs) available can be defined in two categories : operational and management. The following describes the software currently available, but this is a rapidly developing technology and as knowledge of designers’ requirements increases, so will the availability of programs. In the meantime, special requirements are expensive and, as a general rule, best avoided. User friendly programs, i.e. those where the operator is provided with data or instructions in plain language, are now in common use, and should always be requested as part of the design requirement. 5.10 Computer based systems Transmission of information from the data collecting outstations to the central monitoring panel is via a single or two-wire trunk using pulse coded messages (see Fig. 23). In some systems the scan initiation is entirely from the central processor that addresses each individual point in turn, and then processes the data received. The processor may include software providing PID control of loops, or it may be part of the outstation facilities. The use of software for this purpose is currently described as direct digital control (DDC), and individual conventional controllers are made redundant. Alternatively, intelligent outstations are provided, whereby the outstations address the processor on alarm occurrence. A variation is the use of microprocessors at various locations which contain all the intelligence needed for local supervision and control, including DDC, hosted by a central computer having overall control. This is particularly suitable for larger projects possibly involving several buildings where more conventional transmission systems become overloaded. Data transmission rates are, typically, 300 to 9600 baud. Alarms for analogue devices may be set and programmed at the central processor and/or the outstations, for each of the separate sensors. These alarms can normally be inhibited by means of software when the partic- 5.11.1 Alarm priorities: Most systems allow several levels of alarms to ensure that first order alarms can be quickly identified. Low priority alarms, e.g. maintenance alarms, can be programmed to print out only on request. 5.1 1.2 Alarm inhibition: Certain digital and analogue points inevitably go into alarm when the associated plant is switched off. Similarly, some alarms will not be expected to disappear until the plant has been running for some time, e.g. room temperature out of limits. Such alarms may be inhibited by software. 5.1 1.3 Analogue alarms: Computer based systems allow limits to be set by software for each of the measuring elements. 5.1 1.4 Integration: Integration of measured values allows the calculation of other quantities, e.g. energy con- I II centra I processor data transmission cabling possible data I selective peripherals flow digital I 1 plant panel keyboard alarms displov [unit‘ I IMI t intercom computing L 1 central control Fig. 23 122 I outstat ions i n s t a l l a t i o n I Block diagram of typical building automation system 1EE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y 1988 sumption from flow rate and temperature difference. This minimises the need for complex metering systems, and allows alarms to be set as for other analogue devices. 5.11.5 Totalisation: The major function is the summation of motor run times from status signals which occur as part of a control function. Alarms set for various times may be used for maintenance reminders and duty sharing. 5.11.6 Timeswitching: Plants can be allocated to various daily programs and special programs account for holidays, shut down periods, etc. Lighting control is one specific area which utilises this feature, and programs and hardware have been developed to provide individual control of luminaires from the system and locally, with the use of power cables for signalling. 5.11.7 Event initiated sequences: An external event, normally an alarm (analogue or digital) may be arranged to initiate a sequence of control operations. 5.11.8 Load shedding: A maximum demand meter, or an integrated value of particular variables, may be used for load shedding pruposes. 5.11.9 Restart after power failure: If the system detects that power has been restored (after a failure) the program restarts plants in planned sequence. 5.1I .IOOptimised startlstop: Summer and winter optimisation can be achieved through software, using drybulb/wet-bulb or enthalpy inputs as appropriate, eliminating the need for local optimiser controls. 5.11 .I 1 Cycling: Where statutory regulations permit, plant cycling may be employed to reduce energy consumption. Suitable programs permit out of limit conditions to initiate restart of plant. 5.1I. 12 Process control: Control of analogue values has previously been achieved by local pneumatic or electronic controllers. Temperature and humidity control is now possible through computer programs using PID algorithms based on digital systems, instead of the traditional controllers. The software must permit overrides for manual and emergency use. Standby systems using secondary processors or conventional controllers for priority items may be necessary. This form of control is now commonly referred to in the thermostatic controls industry as direct digital control (DDC). The use of terms such as centralised control when applied to a BAS or BMS does not normally include DDC, unless it has been specifically requested. 5.11.13 Reheat reduction : A program allowing an increase in the offcoil conditions of the supply plant, determined by the zone with the greatest cooling load, minimises energy consumption in constant volume reheat systems. 5.1I. 14 Optimum damper control: Dampers may be controlled through software from enthalpy sensors to optimise the use of recirculated, and fresh, air. 5.1I .I5Security: Security patrols may be supervised by programs arranged for a sequential or timed patrol tour with alarm indication on default. These alarms may be used to indicate a sequence of events. I E E PROCEEDINGS, Vol. 135, P t . B, N o . 3, M A Y 1988 5.11.16 Fire: Air handling plant may be controlled automatically on detection of heat or smoke. There is a move towards the replacement of hard wired fire alarm systems by software data transmission and control systems, but in the UK specific agreement is required from local fire authorities before use. 5.11.1 7 Miscellaneous: Among programs which are commonly available is one for programmed maintenance, and there are many other options, such as translation to a second language. 5.12Specification and installation In order to obtain a BMS/BAS suitable for a particular project it is essential that the installer is provided with a clear specification. Schedules, used in conjunction with schematic diagrams of the systems are a convenient method of conveying details of requirements, connections and interfaces to the suppliers and installers. One example of this is shown in Fig. 24. The following are some areas to be considered: (a) Who is to supply and install data input devices (analogue and digital)? Are pockets provided with pipe line mounting equipment? What special contact features are required on the digital devices? (b) Where are outstations to be located in order to minimise wiring? (c) Who is to supply and/or install input, transmission and intercom cables? Who is to be responsible for checking and terminating these cables? In special screening or segregation required? (d) How is switching of 240 V start/stop circuits to be handled, i.e. will relays be located at the outstation or the start panel ? How will back-feeds between systems be avoided? (e) Who will provide the hand (test)/off/auto switches which are essential both to enable basic commissioning and for emergency operation of connected plant? (f) Can power and monitoring cable terminals at the starter panels be segregated to minimise damage to outstations due to cross connection? (9)If sequence/control logic is to be executed through the automation system, will safety interlocks be required and how will they be incorporated? (h) Can all the necessary control and energy management programs be supplied as standard software? Have the programs been validated in actual use? ( i ) What special requirements are there for duplication of peripherals? Are mimic diagrams and annunciator panels necessary? (j) Which language and units are to be used for display on VDUs and printers, and who will bear the cost of translation? (k) What are the power supply requirements? Are batteries necessary for software/memory protection of back-up facilities? ( I ) How much spare capacity is to be allowed for later additions? (m)Are spare parts provided? Is there a local service organisation? What is the maximum callout time for attendance to correct faults? (n) Who will carry out the testing and commissioning of the system hardware and software? What system of servicing and maintenance is to be employed during and after the defects liability period? (0) How are the interfaces between all the different systems and subcontracts to be defined in an unambiguous manner? Who will be responsible for specific interfaces ? 123 5.13 Control panels and motor control centres Describing such units to electrical engineers may be analogous to carrying coals to Newcastle. However, there are certainly differences of approach between the building services requirements for nonindustrial type buildings when compared with their industrial counterparts. Generally, the work is carried out under contractual conditions which may differ from those for industrial process work and the participants are often allied wholly with the HVAC industry. While many of the requirements may parallel those of the industrial sector and switchgear panels, the following resume highlights the more common areas which require particular attention for the automation and controls systems. Cupboard style panels with enclosed starter/isolators behind single or double doors are more normal than the cubicle style panel favoured by the process industry. Cupboard style panels do not suffer the problems of starters being located very close to the floor and the age-old dilemma of where to locate the duty selector switch for a run/standby pair of drives. Panels should be designed to be worked on when live, with all components being shrouded so that general day to day maintenance can be carried out. 5.13.1 Equipment and wiring ( a ) Electric or pneumatic controls: The choice may affect who does what in the panel prior to, and after, delivery. ( b ) Starters: It is essential to identify power ratings at which changeover from direct online to star-delta, etc. takes place. Ensure that any special features are also stipulated, e.g. back contacts on overloads for alarm purposes, closed transition on star-delta starters. Ensure suitability of overloads for run up times on large motors. ( c ) Fuses: Specify characteristics to suit applications, e.g. motors, immersion heaters, SCR controllers. ( d ) Isolators: Stipulate whether suitable for on load iso- lation. ( e ) Switches and lamps: Types and method of operation are important for control, e.g. three position switch for selection of run and standby plant should have a positive off position between the two operational positions. (f)Ammeters: These are necessary only for the largest drives. ( 9 )Relays and contactors: Suitable circuitry and performance criteria should be detailed, e.g. coil voltages, in-rush currents and acceptable number and types of contacts. ( h ) Controllers: The majority of environmental controllers are designed for fascia mounting and are usually mounted on the control panel doors. ( i ) Wiring standards: Is the wiring to be loomed or carried in trunking? Detail the methods of identifying each connection to match drawings. Specify the type of wiring to be used. 0’) Terminations: Detail the type of terminations to be used both for the incoming and outgoing cables and for interconnections in the panel. ( k ) Space and spares: Plan for additional space for future modifications and include necessary spares, e.g. fuses. Sample of points for a plant associated with a building Fig. 24 automation system 124 IEE PROCEEDINGS, Vol. 135, P t . B, No. 3, M A Y 1988 5.13.2Interlocking ( a ) Logic: Functional sequences should include all the requirements for control ,loops as described elsewhere, and all interfaces between items of equipment and plants should be interlocked, to ensure that incorrect sequences cannot occur. ( 6 ) Safety and alarms: Ensure that all safety and limit devices to protect plant and satisfy any statutory or other regulations are included in the logic sequences. Include visual and audible alarms to indicate the operation of these devices at the control panel, with repeater devices at remote locations where necessary. ( c ) Equipment for logic operations: Decide whether the interlocking sequences are to be carried out using conventional relays or programmable controllers (processor software). In the latter case the software facility of the (remote) controllers may be used to set up the logic sequences. 5.13.3Responsibilities ( a ) Panel supplier: Who will supply the control panels? Interface problems are minimised if panels are provided by the controls supplier. ( b ) Wiring and pneumatic pipework: The wiring in the panel is always carried out by the panel manufacturer. The external wiring to the panel may be by the electrical sub-contractor, the controls supplier, or a specialist sub-contractor. It is often advisable to make the HVAC sub-contractor responsible for the co-ordination, even if the work is carried out by others, thus, the wiring is included in the HVAC sub-contract, with the exception of main incomers to panels which are the responsibility of the electrical sub-contractor. Connection of the incoming cables is normally carried out by the installer unless there are exceptional reasons such as computer based automation systems, for which the specialist equipment supplier often makes the final connections after the cable has been laid by the installer. The pipework is normally carried out by the control’s supplier within, and external, to the panel. Clarification of any alternatives which may be permitted, e.g. pre-fabrication by the controls supplier is necessary before fitting to the panel at works or on site. ( c ) Drawings: The information for obtaining and co-ordinating the information required from the various suppliers should be vested in one of the sub-contractors alone. The HVAC sub-contractor is usually best suited to this function. Drawings finally incorporated into panel diagrams will include those from: (a) Controls supplier (b) Boiler supplier (c) Chiller supplier (d) Cooling tower supplier (e) Starter supplier ( f ) Electrical sub-contractor (9)HVAC sub-contractor. ( 6 ) On site: All connections into the panel should be checked before power is switched on, and the functional, operational and safety sequences should be rechecked before the plant is operated. Systems and applications 6 To provide a brief, but electrically orientated, description of the application of controls to systems, this section will be restricted to an examination of multiple boiler/chiller controls, and the control of a dewpoint system for an air conditioning plant. It will be seen that the selection of the suitable combination of sensor, controller and motorised valve(s) is relatively simple compared to the associated interlocking required to cover all the eventualities associated with usage patterns and limit and safety features. While the interlocking diagrams are shown in one of the traditional forms, software based versions are becoming much more common, and will probably become the norm within the next decade. 6.1 Multiple source control With multiple boiler or chiller combinations, the first choice to be made is whether to run them for series or parallel operation and control : chillers may occasionally be installed for series/parallel operation. The answers to a number of checklist questions are essential for the selection of a suitable system. The different basic arrangements are shown in Figs. 25 to 28. constant or variable volume primary p u r n p ( s ) Fig. 25 Parallel sources with primary pumping For variable volume systems use connection AB For constant volume systems use connection BC This Figure excludes all regulating, isolating and control valves and bypasses rm I constant or variable volume primary pump(s) secondarv source source source I I I Fig. 26 Parallel sources with primarylsecondary pumping This diagram excludes all regulating and isolating valves constant or variable volume primary pump(s) 5.13.4 Testing ( a ) At works: All functional, operational, and safety sequences should be simulated and checked, and compliance with any statutory or other requirements, such as the IEE wiring regulations, should be ensured. IEE PROCEEDINGS, Vol. 135, Pt. E, No. 3, M A Y I988 load Fig. 27 u Series sources with primary pumping This diagram excludes all regulating, isolating and control valves and bypasses 125 In the parallel mode points to be considered are: (a) The amount of over-temperature (boilers) and subcooling (chillers) which can be tolerated during sequence constant or variable volume primary pump(s) D loads Fig. 28 facturers’ guarantees should not be affected but modifications to the normal single unit operating functions may be required. (e) Are the unit sizes selected so that operation at low partial loads does not create additional problems? On multiple unit installations one unit normally operates at minimum load more frequently than the overall system operates at maximum load. Large machines are only permitted a limited number of starts in a given period. What is the maximum turndown ratio? At least one machine must be selected so that its minimum output is less than the lowest normal operating load. (f)Do the limit devices have the span to cope with the unit operation over the full range of loads? This is illustrated by the simple example in Fig. 29. Series sources with primarylsecondary pumping This diagram excludes all regulating and isolating valves load operation over the total load spin. (Over temperature situations are shown in Fig. 29). Will the return water temperature on boiler systems drop below an acceptable level? (b) The choice. of primary plus secondary pumps or primary only, in conjunction with the valving-off, of nonoperational units. This is related to both hydraulic stability and (a) above. (c) The permitted variation in flow through the units (flows through boilers and, particularly, chillers), should not be reduced much below design rating. (d) Flow balance between individual units. Short circuiting may occur for flows below maximum, unless the system is correctly designed. (e) The maximum number of units which can reasonably be controlled in sequence. This is related to overtemperature and sub-cooling and the availability of a suitable control system. In the series mode the points are: (a) the problems of over temperature (boilers) and sub-cooling (chillers) do not occur. What is the minimum temperature rise (boilers) or fall (chillers) acceptable across each unit? Is there a likelihood of flow between the cold feed and common boiler vent? (b) the choice of primary plus secondary pumping, or primary only. (c) Does the selected sequence of operation for the sources affect their output capability? For example, for three chillers in series on a system designed for 5°C flow and 11°C return, any one chiller must be capable of providing its maximum 2°C drop, for inlet conditions varying from 5°C to 9°C. (d) Will the advantages of a series system outweigh the additional pumping costs for units in series, particularly chillers ? For both series and parallel operation: (a) The choice between modulating or stepped mode of temperature control. Modulating control is prefereable for system stability. (b) Is temperature control from flow or return? Control from the return is not acceptable except with constant total flow through the units, and control from the flow is not advisable with the stepped mode. (c) Is there a suitable sequence control system available for the proposed arrangement? There may be difficulties for more than three units. (d) What is the effect of superimposing an overall control system over that of the individual units? Manu126 @d ”5 v, tr T: Boiler control detector. Isolating and regulating valves not shown. Case 1 (LPHW) Load t,, @ = 90°C;t , , Case 2 (HPHW) = 78°C t,, = 130°C;t,, = 85°C (”/.I Return Boiler flow temp. temp. rd”c t,rc 78 100 66.7 82 33.3 86 ,t, 1 2 3 90 94 98 90 94 86 90 82 86 Return Boiler flow temp. temp. r,rc t,rc 85 100 115 1 2 3 130 130 130 145 145 100 160 115 115 = design flow temperature t , = design return temperature Fig. 29 Constant volume system It should be emphasised that the analysis of the conditions at the heating or cooling source cannot be treated in isolation from the remainder of the hydraulic circuit. The converse is also true. The example shown in Fig. 29 illustrates some of the problems listed. They are relevant to a boiler sequence control system with continuous constant flow through all the boilers for both low pressure hot water (LPHW) and high pressure hot water (HPHW) systems. This clearly shows the magnitude of the over-temperature problem with sequence control under partial load conditions. While the over-temperature may be acceptable for the LPHW system, other than for roof top boiler houses, the HPHW system reaches over-temperature conditions which may be outside the limits of the designed system pressure. Both systems illustrate that any boiler-mounted thermostats must be set much higher than normal, impossibly so in some cases, if the sequence control is to operate correctly and efficiently. The tabulated temperatures are simply calculated from the load percentage with a fixed flow temperature. There is also the necessary consideration of the safety requirements and devices under the Heatlh and Safety at Work act. In the equivalent chiller system, similar calculations may be carried out for the subcooling case. There is however, little latitude for subcooling before the operating chiller is locked out by its low temperature cutout thermostat. This must always be a primary consideration for selecting a suitable multiple chiller configuration. Sources in parallel are more common than those in series and this is particularly so for boiler systems. One I E E PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y I988 example of such a system is shown in Fig. 30, with the interlocking shown in Fig. 31. The features, details and requirements for such a system are tabulated in Table 2. mixed flow llmlt detector YT2 I I 1 I 1 I ' constant volume primary pump(s) < 3 "' i solat Ing control tf 1 I 'd - tf F t a n t or vnrinhle - volume secondary pump(s) control detector Basic schematic diagram for Schemes I and 2 Fig. 30 Any two sources selected for operation with the other as automatic standby The scheme has the following parameters: (a) sources in parallel (b) constant volume through selected sources (c) reciprocating chillers or high/low boilers (d) control from the return (e) automatic changeover to standby source. Note that where there is variable flow through the sources, control from the return is not a viable option, and that if the sources can be fully modulated from low to high, control from the flow would be the best option, irrespective of source flow rate. 6.2 Dewpoint control The control of air systems may be considered in two parts, the first related to the main air plant and the second to the terminal units. The basic controls for the main plants are generally the same, regardless of system type. However, some systems may require additional controls. The dewpoint control system with its various options and special features, represents a large proportion of the problems encountered in the control of all air systems. The psychrometrics for air conditioning and air systems generally are covered in detail in Section B3 of the Chartered Institution of Building Services Engineers' (CIBSE) Guide and are an essential part of understanding the operation of the control system. Only the basic psychrometrics necessary for particular elements of the schemes described below are shown here. In energy conservation terms, overall dewpoint systems may not be the most efficient. Sequential heating and cooling with separate humidification and a cooling coil overrride feature for dehumidification, or dewpoint control only for the fresh air supply, should be considered as alternatives. 6.3 Dewpoint control and auxiliary features In the system shown in Fig. 32, the dewpoint is controlled by detector T, which sequentially modulates a pre-heater battery control valve V,, dampers D l a , D l b and D l c , which operate in parallel, and a sprayed cooler battery valve V, to maintain a constant saturated temperature condition. A low-limit detector 7 ' is sometimes employed in the discharge duct to override T, and maintain the discharge temperature above a predetermined limit. Floating, thermal feedback, or proportional plus integral controllers should be used, because, for stability, proportional control alone requires a wide band which IEE PROCEEDINGS, Vol. 135, Pt. E, N o . 3, M A Y 1988 results in unacceptable deviation from dewpoint. The reheater, which is part of many systems, is controlled by the extract temperature detector T, , modulating the control valve V, to maintain a constant space temperature. The psychrometrics of the system are shown in Fig. 33, in which the dewpoint plant is set to provide a moisture content of H so that air is supplied to the space after reheat in a condition S . This permits the design room condition R to be achieved when the latent gains ( R X ) are added and the sensible losses (S,X), or gains (SsX) are taken into account. In winter when the incoming air is at O w ,the dampers can be modulated to achieve a mixed air condition corresponding to condition M , with the cooler and preheater both off (any point on the line O,R, represents a mixed air condition with 0, defining full fresh air and R represents total air recirculation). Normally, there is a requirement that the fresh air quantity shall not fall below a minimum quantity, represented by MF, which means that the dampers cannot take up a position between M F and R . From M the air is then adiabatically saturated as it passes through the spray coil, moving the condition point along the wet bulb line to H . An ideal spray coil would saturate to point D, where the wet bulb and dry bulb settings are identical, but in practice, the spray is not perfect, and the dry bulb detector (TI) is set at F to ensure that H corresponds to the required moisture content. When selecting the dewpoint, allowances should be made for the inefficiency of the spray coil and the latent gains to the space ( R X ) . In a very cold situation, such as shown at Ow,, the room condition R at start up may be below the line DM, and the mixing point M , cannot then be achieved. Alternatively, the mixing condition may not be possible because the minimum fresh air position MF, is below the line D M . In either case, the dampers are modulated to M , , (points on line M,,R not being permitted), and the preheater control valve is then modulated from closed toward the open position to reach the wet-bulb line at M , , where adiabatic saturation again takes place to move the condition point to H . In any situation where point M (or M , , etc.) can be achieved by the use of mixed fresh and recirculating air, with or without the preheat, and with no output from the cooling coil, the term 'free cooling' is used, as the dewpoint can then be maintained without the assistance of mechanical cooling. Thus, in very cold weather the dampers are in the minimum fresh air position to minimise preheating and, as the external temperature rises, the preheater valve closes and the dampers modulate to the full fresh air condition. In summer conditions such as O s , the preheater is off, the dampers are in the full fresh air position, and the cooler valve V, is modulated to achieve point H . Although each of the previous steps have been described as discrete operations, the three stage controller permits continuous sequential operation of each stage according to load conditions. When point H is achieved it is necessary to reheat the air to the desired discharge condition, point S , or Ss for winter and summer conditions, respectively. A reduction in mechanical cooling load can be provided by overriding the damper control in certain conditions. Fig. 34 is similar to Fig. 33, but shows specific enthalpy (total heat) lines in addition to the wet bulb line. For all practical pruposes, either wet bulb or specific enthalpy can be used to measure the total heat content of the air, and for simplification one can assume that H coincides with D. Normally, the dampers are fully open 127 h' l i m i t detector in mixed flow 2, start signal fleeting contacts inst break on energisation and delay remake safety interlocks auxiliary switch makes when valve I S open _ _ _ _ _ _ detector i n +common return step switches Fig. 31 128 thermostatic controls Interlocking wiring for system of Fig. 30 IEE PROCEEDINGS, Vol. 135, Pt. B, N o . 3, M A Y I988 to fresh air before the coder battery is required, but one must consider the three summer conditions, Os,, Os, and O s , . For any condition Osl between lines OR and DZ, the minimum amount of cooling (smallest reduction in total heat) is required when the dampers are in the full fresh air position MI, i.e. DO, is a minimum. Any condition Os, which falls on the line 0 , R requires the same amount of cooling DO,, irrespective of the damper position. The cooling load for a condition Os,, above line 0 , R can be reduced to a minimum DO, by moving the dampers to the minimum permissible fresh air position M , . In the past, a fixed minimum fresh air quantity was often employed. However, energy conservation considerations now render this approach unsuitable in most circumstances, and the system shown in Fig. 32 incorporates damper modulation to achieve the desired conditions. In the example above, Os, represents the case where the enthalpy of the outside air exceeds that of the return air, and it is more economic to cool return air than outside air. A detection device is therefore required Table 2: System details and requirements, (Figs. 30 and 31) Element Reciprocating chillers Complete units High/low boilers Interlaced units System use Constant volume through sources for all load conditions. Secondary systems may be constant or variable volume. Two sources operating to satisfy the design load, with one as automatic standby - its isolating control valve closed. Use where sub-cooling with only Use where step functions in flow Use where sub-cooling from one At one complete unit operating is complete unit is not acceptable or temperature = l, and/or overacceptable. when each source is composed 6 of multiple compressors. temperature is acceptable. The system may be extended to a greater number of steps and/or units than the example if the sub-cooling or over-temperature is acceptable and suitable step controllers are available. Control wiring As Fig. 31 but: As Fig. 31 generally but connections need alteration between terminal groups 1 to 24 and 25 to 36,and: reverse the action of the thermostats, controller etc., to suit the cooling function. Diagram assumes that all steps are brought in by making a circuit, but there may be instances where the circuit needs breaking to bring in steps. Check. The single wafer sequence selector switch could be replaced by a multiple wafer switch and fewer External interlocks Other interlocks Proof of primary pumping and fuel feed interlocks. On power failure and for any other form of interruption of the start signal line, the sources restart unloaded (R16).The 'safety interlock' may be a 'fireman's switch' or 'boiler house door cut-off switch' etc. If a unit is locally isolated, restart is sequenced from sequence starting relays. If it is necessary to prevent low temperature return water at start up, add necessary equipment and modify the diagram. The closure of the source isolating control valves should take not less than 120 s, and the actuators should be selected and/or the wiring modified to achieve this. The valves should be of the butterfly type. The isolating control valve on the leading source must always be held oDen. relays. Proof of primary pumping and proof of condenser operation Requirements Contain high and low pressure cut-outs and low temperature limit device, all of source with hand reset and alarm features and integral sequence controls. packages Package to include switch to permit the use of the local unit package sequence controls, or the overall sequence system. Control settings For the two stages on each boiler Fig. 31 would be modified by deleting: Switch and step controller elements 3,4,7, 8. Relays R6, R7, R10, R1 1 , R14, R15. Sequential relays SR1,SR2, SR3. Contain limit, high/low and low/off thermostats, all suitable for overtemperature setting. Package to include switch to permit local control through the three thermostats, or the overall sequence control. Limit thermostat to be oDerative for both systems. System assumes all selected units are required for full load operation. Normally proportional band (PB) setting equals design temperature fall (rise) across sources (ArJ but this may not be the same as the design temperature drop across the load (At,),if the source volume (V,) exceeds the design load volume (V,) and/or the source capacity (C,)exceeds the design load capacity ( C , ) . The basic relationship is Ats = At, x 5 5. The Ats actually used when setting the PB, should be x U s . This permits a dead zone over which the step controller continues to operate Total no. of source switching v= steps after all the selected sources are allegedly operating at full capacity. At the end of the dead zone the standby sequence is initiated. The setting of the desired value (DV) of T,should be ,t - ;At, (boilers) and ,f + ;Ats (chillers). The differential settings on the step switches should be set so that the return temperature variation between the on and (-) 4 off action is f x (assuming equal sized steps). No. of steps The limit thermostat (T,)in the mixed flow should be set at ,t - 2°C for cooling, and at ,t + 5°C for heating Standby facilities Standby is automatically accomplished if the selected sources do not apparently provide sufficient capacity. This is detected by an out of limit return water temperature - too high for cooling and too low for heating, which initiates the changeover. The changeover moves the sequence to the next selection on the switch and closes and opens the necessary source isolating valves. If the sequence still contains a faulty source the sequence will move on again to the next sequence and repeat the valve changeover. Number of starts Specify timers in packages or motor control centres to limit the number of starts in accordance with the requirements of the electrical eaubment and the source unit sumliers. Alternatives Modular boilers may also be controlled using the same basic concept. Sufficient steps would be required for the number of boilers/stages and the sequence selection would require modification. The over-temperature conditions could be extreme. If control from the flow is considered, the same general interlocking may be used as shown in Fig. 31, but a proportional Controller is NOT suitable. Use a two-term proportional plus integral, thermal feedback, or floating controller with suitable sensitivity. There will also be problems of hunting between steps, which will require very careful setting of the differential stem on the steD controller and the addition of timino devices in the control svstem to limit the rate of resoonse. IEE PROCEEDINGS, Vol. 135, P t . B, N o . 3, M A Y 1988 129 to measure the total heat (enthalpy) or wet bulb temperature. The enthalpy of the outside air can be measured created by the plant fans can vary the surface level of the water system. U T4b Fig. 32 Dewpoint schematic Dewpoint detector Temperaturedetector Low limit detector Enthalpy detectors/comparators T5 Boost limit thermostat T, T, T, T, T, Secondary water control detector T, Modulating low limit T8 Frost protection thermostat T9 Free cooling limit thermostat TI, Free cooling enthalpy detector directly T4a as being above the design room value, or by dual detectors T4a and T4b which compare the room and outside air total heat conditions. In either case, when the room total heat is exceeded by the outside air, a signal from the device drives the dampers to the minimum fresh air position ( M 3 in Fig. 34). A wet bulb detector may be used as T4a, provided that the wetsock assembly remains wet. If not, the dampers will motor to the minimum fresh air position for all conditions to the right of D-N (see Fig. 34). The use of such detectors therefore requires permanent water supplies to the wetsock assemblies, and an appreciation that pressures HI Return air humidity detector PI Differential pressure switch VI Preheater valve V, Cooler valve V, Reheater valve V, Secondary chilled water valve Free cooling may also be utilised to satisfy the secondary cooling requirements of terminals such as fan coil units, that operate with water chilled to only about 12°C (at temperatures below this, water condenses on the fan coil units). In such circumstances, it is common to feed the terminal circuit from the return from the main cooling coil (points A and B in Fig. 32). It is then necessary, after the early morning boost heating (described later and terminated by thermostat T,) to maximise the use of fresh air to achieve cooling. In winter it is possible to use this cool air to provide water at a suitable temperature without the use of chillers, by running the I ' I -owl E E dry bulb temperature ,"C Fig. 33 Psychrometric process for a dewpoint plant 0, Winter outside condition 0, Summer outside condition S Supply condition R Room condition D Adiabatic saturation H Design moisture content M Mixed air condition 130 Fig. 34 Specific summertime psychrometric dewpoint processes IEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y I988 primary chilled water pumps and spray pumps without energising the chillers or the condenser pumps, and with the valve on the cooling1 coil driven to the fully open position. The amount of secondary cooling thus obtained may vary according to the control regime adopted. If the normal dewpoint temperature is maintained at T, the amount of cooling obtained will be less than if the control point of T, is lawered, or dewpoint is uncontrolled. In the latter cases the relative humidity in the controlled space will drop, but this is often acceptable. The case shown in Fig. 32 is for an uncontrolled dewpoint where the dampers are modulated by signals from detector T6 with valve V, fully open (in normal operation T6 would modulate V, to maintain the necessary 12°C).It is necessary under these conditions to protect the preheat and cooling coils from too low a temperature, and detector T, acts as a modulating low limit override device for this purpose set at, say, 4°C. The absolute protection offered by frost thermostat T8 remains in operation. While the external dry bulb temperature remains below a specified level the system remains in operation. Above this limit ( 5 to 8"C),thermostat T' switches the plant controls back to normal operation. If the plant is used to obtain secondary chilled water without mechanical cooling the cooling coil should be sized for this purpose so that the necessary secondary cooling capacity can be obtained for a particular setting of T9. Detector T, can also be used to determine when the plant should revert to normal operation. Alternatively, an additional detector adjacent to it may be utilised with suitable timing delays and interlocks. Where no secondary cooling capacity is T / S signal required, it is possible to almost satisfy the dewpoint condition without mechanical cooling whenever the enthalpy of the external air is below point D on Fig. 33. This is accomplished by detector TI, which holds off the chiller and cooling tower plants whenever the enthalpy is below the predetermined level. In rare cases, a humidity detector HI, mounted in the extract duct from the conditioned space, is provided to monitor any excessive or reduced latent gains in the space, and resets the dewpoint detector TI accordingly. When the plant is started up in the morning, or after a shutdown, and the space temperature is below the setting of the boost thermostat in the extract duct T5 a boost heating regime is initiated. The dampers remain in the no fresh air position (to which they run when the plant is shut down), the chiller and spray plants remain off, the boiler system is started, the fans are run when the water is up to temperature, and the preheater and reheater run fully open until T, is satisfied. When this occurs the plant reverts to the normal operating sequence, and T5 is latched out for the day. A differential pressure detector P , fitted across the plant filter is a standard control item for providing a warning of high pressure across the filter for both maintenance and energy conservation purposes. There are many variations to the interlocking which may be necessary, but two general features are desirable for all dewpoint plants. These are: (a) The minimum fresh air position of the dampers is important for ventilation and energy conservation. TO permit ease of setting up, commissioning and adjustment, N1 Fig. 35 EA OA RA T/S PH RH CIA sensor R A sensor IEE PROCEEDINGS, Vol. 135. P t . B, No. 3, M A Y 1988 Dewpoint controls Exhaust air Outside air Recirculated air Time switch Preheater Reheater Relay - 131 the controls should include an integral minimum fresh air position adjustment. This allows the minimum fresh air quantity to be altered without changing the mechanical linkages to the dampers, and also provides a simple method of overriding the partly open fresh air and exhaust air dampers for periods of plant shutdown and early morning boost heating. (b) Fire protection considerations often require that, in the event of smoke or fire, the plant shuts down automatically and that the firemen have the facility to start boost A i I firelsmoke C minimurn F A D time swltch E F 9 I - I I PH I 1I I I FA NIC I I_ I I I EA RA N/O NIC dampers n o r m a l sequence PH dampers, cooling 10 .I-+ I --- CLG I --u I N/C& I I ' I v I PH control Ler to suit !I minimum F A position ad) ust ment dewpoint controller to E P R , - ~ : ~ ~ ~ - - + (proportional p l u s reset) discharge stat I / dewpoint stat 'I Dewpoint controls: pneumatic continuation All necessary penuematic pipework within boundary by controls suppler EPR Electropneumatic relays by control supplier: 5 RA open, night 1 MinimumFA 6 RA closed, smoke 2 FA closed, night and smoke 7 Cooling valve open, free cooling 3 FA closed, night 4 FA closed. smoke 132 main p l a n t chiller E L& I Fg. 36 the extract fan independently of the supply fan, with the dampers operated out of sequence. A frequent requirement is for the exhaust damper to be open and the fresh air and recirculation dampers to be fully closed to facilitate smoke exhaust. As an indication of the interlocking complexity which may occur, Figs. 35 to 37 identify many of the items described in this section for both electronic and pneumatic control systems. The principles identified are frequently applied to other systems. 8 Dewpoint DV setdown, free cooling 9 PH open, night and boost 10 PH open, night and boost IEE PROCEEDINGS, Vol. 135, Pt. B, No. 3, M A Y 1988 It can be seen that a knowledge of the functional requirements of the plant for a host of extraneous circumstances is crucial if the electrical logic is to be cornprehensive. - minimum FA fire/ smoke boost C I 0 A I mainplant chiller D E I I I I F I I II I I time switch I I I I I matic Controls and their Implications for Systems Design’, and Butterworth & Co. (Publishers) Ltd. for permission to use extracts from ‘Electrical Engineers Reference Book’ (Chapter 28, Environmental Control). The I I I I I l - O ’ $ ~ ~ ~ l l e dRHvalvel ~ 1 dampers( I I 1 I normal I normal I flclos:.*i I ilve DV 1 - O -0 I I I I dewpoint controller ( t w o l t h r e e t e r m or floating thermal /feedback) I ,FA I I ‘.A RA, I I PH d a m p e r s , cooling I adjustment damDers I I also a l l r e l a y s f o r % v1 normal s e q u e n c e reheater controller t o choice I I D. I i I ,I R A detector @ R H valve 3 The use of the two examples for illustrating, in the one case, controls for water systems and, in the other, air systems is a suitable point to conclude this review of controls in building services. More detailed information is avilable from manufacturers (for equipment details) and from other sources [2] for design information. 7 I detector Acknowledgments The authors wish to thank the Chartered Institution of Building Services Enginedrs for permission to use extracts and Figures from the CIBSE Applications manual ‘AutoIEE PROCEEDINGS, Vol. 135, P t . B, N o . 3, M A Y 1988 I Fig. 37 I Wiring within boundary according to particular supplier’sdetails Dewpoint controls: electric continuation historical section reuses some quotations from ‘Building Services Engineering: A Review of its Development’ by N.S. Billington and B.M. Roberts. 8 References 1 LETHERMAN, K.M.: ‘Automatic controls for heating and air conditioning’ (Pergamon Press, Oxford, 198 1) 2 CIBSE applications manual: ‘Automatic controls and their h p l i c a tions for systems design’ (Chartered Institution of Building Services Engineers, London, 1985 3 FISK, D.J.J.: ‘Micro-electronics in building services’ (Building Research Establishment, Garston, 1979) 133