Wiring Instructions

advertisement

WIRING DIAGRAM

HDI DISCONNECT SWITCHES

FOR: ME 20MS1A-M2

ME 30MS1A-M2

ME 32MS1A-M2

ME 40MS1A-M2

ME 20MS4A-M2

ME 30MS4A-M2

ME 20MS5A-M2

ME 30MS5A-M2

ME 40MS5A-M2

ME 60MS5A-M2

Auxiliary Contact

L 1

OFF

T 1

L 2

T 2

ON

Auxiliary Contact

L 3

T 3

RELEASE MECHANISM*

CONTACT ARRANGEMENT

1 3

L 1 L 2 L 3

2 1

1 4

T 1 T 2 T

2 2

AUXILIARY CONTACTS

Rating: 10A 600Vac

Wiring: 13-14 N/O

21-22 N/C

EQUIPMENT GROUND TERMINAL BLOCK (GREEN/YELLOW)

*If needed - pull down with screwdriver in slot. Tilt upward on load side of switch.

EQUIPMENT GROUND

TERMINAL BLOCK (GREEN/YELLOW)

FOR: ME 80MS2A-M2

ME 100MS2A-M2

L 1 L 2 L 3

ON

43

31

32

44

OFF

CONTACT ARRANGEMENT

L 1 L 2 L

T 1

T 1 T 2 T

AUXILIARY CONTACT BLOCK

RELEASE MECHANISM*

AUXILIARY CONTACTS

Rating: 10A 600Vac

Wiring: 43-44 N/O

31-32 N/C

*If needed - pull down with screwdriver in slot. Tilt upward on load side of switch.

.

Connection and Grounding

See separate conduit connection and grounding instructions.

Use above wiring diagram.

Terminal Specifications

Switch

Ground

Auxiliary

25Amp(& 30Amp 10hp) Torque

#10AWG

#12 to #10AWG

#14AWG

13-16 lbs./in.

20 lbs./in.

4 lbs./in.

30, 40 & 60 Amp

#10 to #6AWG

#10 to #8AWG

#12AWG

Torque

20-24 lbs./in.

20 lbs./in.

7 lbs./in.

80 & 100 Amp

#6 to #2AWG

#8 to #6AWG

#12AWG

Torque

22-27 lbs./in.

20 lbs./in.

7 lbs./in.

MOUNTING INSTRUCTIONS

HDI DISCONNECT SWITCHES

NOTICE:

1. Turn off power feed to switch before installing or servicing.

2. This unit provides no overcurrent protection.

3. Select conductors in accordance with the 75 C column of

Ampacity Table 310-16 of the National Electrical Code.

To Remove and Replace Front Cover

Fully loosen screws (Do Not Remove) located in four corners of cover. Pull cover away from bottom of enclosure. To replace cover, reverse above procedure, slight wiggle of cover and switch handle may be needed to position cover. Do not force.

Do not over-torque.

Tighten cover screws to 15 in.lb. for MS1A Enclosure & to 25 in.lb for MS2A Enclosure.

Mounting Tubes

Use #10 Screw Direct Mount Using Mounting Tubes

For: MS1A/MS4A Enclosures

MS2A/MS5A Enclosures

TOP

1. Position Box Upright using ON/OFF as Reference.

2. Drop #10 Screw into each Mounting Tube.

See Fig. 1a Below.

3. Mount Unit on Secure Flat Vertical Surface.

MOUNTING DIMENSIONS

Enclosure A B

MS1A/MS4A 5.26” 4.039”

(Hardware not provided)

4. Reinstall Cover.

MS2A/MS5A 8.86” 6.00”

Dimensions +/- 1/32”

A

DO NOT MOUNT

THROUGH REAR WALL

OF BOX

B

Fig. 2a

Mount with External Mounting Feet

For: MS2A/MS5A Enclosures

Order KIT ME MS2A-MF

1. Turn Bottom Box Over to Expose Threaded

Rivets.

2. Screw Mounting Feet into Corner Rivets.

Position Mounting Feet as Required.

See Fig. 2a.

3. Position Box Upright Using ON/OFF as Reference.

4. Mount Unit to Flat Vertical Surface.

(Hardware not provided)

5. Reinstall Cover.

8.535”

11.654”

7.016”

TOP

DO NOT MOUNT

THROUGH REAR WALL

OF BOX

10.736”

4.815”

7.593”

Mount with External Mounting Feet

For: MS1A/MS4A Enclosures

Order KIT ME 236MIMF

1. Place Screw (provided in kit) through Mounting Tubes.

See Fig. 3a.

2. Place Mounting Foot Below Hole of Mounting Tube.

Position Horizontally.

3. Tighten Screws 13-17 in. Lb.

4. Position Box Upright using On/Off as Reference.

5. Mount Unit to Flat Vertical Surface.

(Hardware not provided)

6. Reinstall Cover.

277 Fairfield Road

Fairfield, New Jersey 07004

Tel. 973 - 882 - 8333 www.MENNEKES.COM

Fig. 3a

Copyright 2005 Mennekes Electronics, Inc.